Unitronics Jazz Micro-OPLC JZ10-11-T17 Installation Manual

Unitronics 1
JZ10-11-T17
Jazz™ Micro-OPLC™ Installation Guide
6 Digital, 2 Analog/Digital, 2 Analog Inputs, 7 Transistor
Outputs
Before using this product, the user must read and understand this document. For additional information regarding this product, refer to the user guide and technical specifications.All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations. Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
Do not attempt to use this device with parameters that exceed permissible levels. To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Ventilation: 10mm space required between the controller’s
top/bottom edges & enclosure walls.
Do not place in water or let water leak onto the unit. Do not allow debris to fall inside the unit during installation.
Mounting
Dimensions
8
5
.
7
m
m
(
3
.
3
7
4
"
)
113.7 mm (4.476")
13.2 mm (0.52")
16.8 mm (0.661")
46.6 mm (1.835")
4 mm (0.157")
7.5 mm (0.295")
12 mm (0.472")
147.5 mm (5.807")
117 mm (4.606")
Add-on modules
Note: Installing an add-on module requires space.
During installation After installation
Panel mounting
- Cut-out: 117 x 89mm (WxH) 4.606”x 3.504”
- Hold bracket against unit while tightening screw
72 mm (2.835")
27.5 mm (1.083")
3
8
m
m
(
1
.
4
9
6
"
)
3
5
.
8
m
m
(
1
.
4
0
9
"
)
Gasket
Panel 5mm (max)
0.197" (max)
Bracket
JZ10-11-T17
2 Unitronics
DIN-rail mounting
Mounting
Snap PLC onto the DIN rail
Removal
Push mounting clip down
35 mm
(1.378")
53 mm
(2.087")
..
Note: Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58”).
Wiring
Note: All diagrams are based on the rear view of the OPLC.
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring. Use appropriate circuit protection devices. Unused pins should not be connected. Ignoring this directive may damage the device. Double-check all wiring before turning on the power supply.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break. Install at maximum distance from high-voltage cables and power equipment.
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 2–3.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share the same wire. Allow for voltage drop and noise interference with input lines used over an extended distance. Use
wire that is properly sized for the load.
The controller, I/O signals, and outputs’ power supply must be connected to the same 0V signal.
Inputs
This model comprises a total of 10 inputs in 3 groups.
1. I0 to I5 are digital inputs. They may be wired, in a group, as either npn or pnp.
2. I6 and I7 may be wired as either digital or analog inputs. These may be wired as either:
npn digital inputs
pnp digital inputs
analog (voltage) inputs
In addition, 1 input may be wired as a pnp input, while the other is wired as an analog input. Note that if 1 input is wired as an npn input, the other may not be wired as an analog input.
3. AN0 and AN1 are analog (current) inputs that may be wired using 2, 3, or 4 wires.
Loading...