United States Stove Company 1800 User Manual

UNITED STATES
Keeping America Warm Since 1869
MODEL: 1600 / 1800
THE WOOD AND COAL FURNACE
SAFETY NOTICE: IF THIS FURNACE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION REQUIREMENTS IN YOUR AREA.
Installation/Operator's Manual #851062E
TABLE OF CONTENTS
Introduction ..........................................................................1
Locating Your Furnace.........................................................1
Clearances ...........................................................................1
Chimney Requirements.....................................................1-2
Smoke Pipe Installation.....................................................2-3
Dampers on Stove Pipes......................................................3
Installation Examples ........................................................3-4
Assembly Instructions .......................................................5-8
Electrical installation.............................................................9
Draft Wiring Diagram..........................................................10
Testing and Operating Procedures.................................11-12
Trouble Shooting and Problem Solving.............................13
Parts Lists
Model 1600/1800 .....................................................14-16
Motorized Natural Draft................................................17
Forced Air Draft............................................................18
Optional Electronic Control System
Installation....................................................................19
Parts List Model 1600 ..................................................19
Wiring Diagrams.......................................................20-23
Installation of Optional Equipment
Domestic Hot Water Coil..............................................24
Back Draft Damper ......................................................25
Filter Boxes..............................................................26-27
TC
INTRODUCTION
chimney connector and extending at least 2" on either side of the chimney connector.
Thank you for your purchase of a U.S. Stove Woodburning furnace. Your decision to buy a Hotblast Furnace was undoubtedly reached after much careful thought and consid­eration. We are very proud you chose the U.S. Stove furnace and trust you will receive the comfort and economy that others realize when heating with a U.S. Stove product.
Your dealer is important in your experience with the Furnace not only in your purchase, but in his recommendations
for professional installation in your home. The qualified professional installer (as recommended by your dealer) has been expertly trained in solid-fuel furnace installation to assure the safety and comfort for your family while saving you money. Trust your experienced installer. He is a specialist in his field.
IMPORTANT
Before installing and using your Hotblast Furnace, please read the following pages thoroughly and carefully. If you follow the instructions, your Hotblast furnace will give you safe and more dependable service in the years to come.
First step; check your local codes. This installation must
comply with their rulings.
Do not install this furnace in a mobile home or trailer.
Always have a smoke or ionization detector installed in
your home.
4 To prevent injury or damage, do not allow anyone who is
unfamiliar with the furnace to operate it.
Spend some time with your furnace to become well
acquainted with different settings and how each will affect its burning patterns. It is impossible to state just how each setting will affect your furnace because of the variations in each installation.
DISCLAIMER NOTICE
The BTU ranges and heating capacity specifications are provided as a guide only and in no way guarantee the output or capacity of the units. The actual BTU output depends on the type of fuel being burned and its conditions, the thermostat setting, the draft adjustment and the chimney that the unit is hooked up to. The actual area that the unit will heat depends on factors such as the conditions of the building, heat loss, type of construction, amount of insulation, type of air move­ment, and the location of the unit.
CLEARANCES
FLAMMABLE WALL
MODEL 1600 - 20" MODEL 1800 - 25"
MODEL 1600 - 22" 1800 - 19"
MODEL 1600 - 12"
1800 - 8"
FLUE
REDUCED CLEARANCES
NFPA guidelines and most codes permit reduced clearances to combustible walls and ceilings if adequate protection is added. A common mistake is to assume that sheet metal, masonry, or asbestos board placed directly against a wall protects it. Materials installed in this manner give very little protection. These materials are good heat conductors, so they will be almost as hot on their back side as they are on the exposed side. Therefore, the combustible wall behind is still a fire hazard.
A wall can be kept cool using these items but only if they're mounted and spaced out from the wall by an inch or two to allow free circulation of room air behind the protective panel. The protective panel should start within a few inches of floor level.
The three rules to follow when constructing wall protectors:
1. Non-combustibility of all materials including mounting or supporting.
2.A well ventilated air space between protector or wall.
3.Sufficient strength and rigidity so that the protector and
2" FROM CEILING
air space will be durable.
CONSTRUCTING
NON-FLAMMABLE
WALLS
MODEL 1600 - 15" MODEL 1800 - 18"
(TOP VIEW)
MINIMUM
CLEARANCE TO
FLAMMABLE WALLS
CAUTION: Do not store combustible or flammable material near furnace.
PROTECTIVE COVERING
AND ALL SUPPORTS MUST
BE NON-COMBUSTIBLE.
LOCA TING YOUR FURNACE
The furnace is to be installed maintaining clearances as shown in illustration.
Do not place the furnace directly on a combustible floor. If you're placing it on a combustible floor, an approved fire retardant material equivalent to 3/8" asbestos millboard should be placed under the furnace. The material must extend at least 16" in front of and 8" on either side of the fuel-loading an d ash-removal doors, and underneath the
1" AIR SPACE
2" FROM FLOOR
CHIMNEY REQUIREMENTS
A masonry or Class A All-Fuel Metal Insulated Chimney must be used in all airtight wood furnace installations. The mini­mum recommended flue size for the U.S. Stove Hotblast Furnace is 6" (inside diameter) for round flues, and 7" x 7" for square flues. When making new chimney installations,
1
always follow the chimney manufacturers instructions.
NOTE: Type of chimney: Class A All-Fuel also referred to as Low-Heat appliance type chimney per Uniform Mechanical Code:
Chimney, low-heat appliance type is a factory built, masonry or metal chimney suitable for removing the products of combustion from fuel-burning low-heat
appliances producing combustion gases not in excess of 1000°F under normal operating conditions but capable of producing combustion gases of 1400°F during intermittent forced firing for periods up to one hour. All temperatures are measured at the appliance flue outlet.
TOP OF CHIMNEY MUST BE 2 FT. ABOVE HIGHEST POINT OF ROOF
2 FT. MINIMUMS
MINIMAL 3 FT. FROM TOP OF CHIMNEY TO POINT AT WHICH IT PASSES THROUGH THE ROOF.
CAP SHOULD HELP PREVENT DOWNDRAFT WHILE STILL PROVIDING ADEQUATE EXHAUST.
3 FT.
MINIMUM
RECOMMENDED
MINIMAL
20 FT. HEIGHT
highest point of the house, or 2' above the point at which the chimney is 10' from the roof.
7.The chimney should be relatively straight and vertical.
8.The portion of an all-fuel metal chimney that extends above the roof should be well secured.
9.A masonry chimney should be built on footings and not attached to the house.
10. A rain cap, complete with an animal or bird screen, should be installed on top of the chimney.
CREOSOTE — FORMATION AND NEED
FOR REMOVAL
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire.
The chimney connector and chimney should be inspected at least twice monthly during the heating season to determine if a creosote build-up has occurred. If creosote has accumu­lated, it should be removed to reduce the risk of a chimney fire.
SMOKE PIPE INSTALLATION
CHIMNEY FLUE SHOULD BE CONSTANT DIAMETER THROUGHOUT ITS ENTIRE HEIGHT.
APPROVED
CHIMNEY
CLEANOUT DOOR SHOULD HAVE AIRTIGHT FIT. DO NOT LEAVE OPEN WHEN FURNACE IS IN OPERATION.
CHIMNEY THIMBLE SHOULD BE CONSTRUCTED OF FIRE CLAY, AND SHOULD FIT TIGHTLY TO FLUE PIPE.
CHIMNEY FLUE MUST BE AS LARGE OR LARGER THAN FURNACE FLUE PIPE
1.The wood furnace should be the only heating appliance using a chimney flue. One furnace per flue.
2.A masonry chimney should have a tile or stainless steel liner.
3.The masonry chimney should not have any missing mortar or loose bricks.
4.There should be no mortar or parts of the chimney blocking the chimney flue.
5.There should be a two inch clearance between any chimney (masonry or metal) and combustibles (such as the house).
6.The chimney should extend at least 2' above the
Clearances to combustible materials (i.e. paneling, ceiling tile, sheet rock, plaster, draperies, casements or wood trim, etc.) will vary with the type of flue connection used. Be sure to maintain the specified clearances for your type of installation.
TYPE OF FLUE REQUIRED CONNECTION CLEARANCE
24 Gauge or Heavier 18" Single Wall Stainless Steel
COMBUSTIBLES
SMOKE PIPE
or Black Pipe Double Wall Stainless Steel 6" Model 1600
8" Model 1800
Class A All-Fuel or Equivalent 2" According to NFPA standards, single wall stove pipes can be within 9" of combustibles provided an approved fire retardant material covered with 28 gauge sheet metal, spaced out 1" on
CEILING OR WALL
18"
9"
18"
non-combustible spacers, is utilized. See illustration.
2
When using a Class A or double wall flue pipe connection, follow the manufacturer's instructions.
When constructing a single wall smoke pipe, the following guidelines must be observed.
1.The smoke pipe should be 24 gauge or heavier
stainl ess steel or black pipe.
2.Secure all joints with three #8 screws.
3.If the smoke pipe must pass through a wall, an ap-
proved insulated or ventilated thimble, at least three times the diameter of the smoke pipe must be used. (i.e. a 6" diameter smoke pipe needs an 18" thimble).
4.The smoke pipe should not be used as a chimney.
IMPORTANT INFORMATION FOR
ALL SMOKE PIPES
The smoke pipe must be constructed and installed so that it maintains clearances, keeps condensation and creosote within the pipe, and is capable of withstanding a two to three thousand degree chimney fire.
1.The smoke pipe should slant down toward the furnace a minimum of 1/4" to the foot. At no time should the pipe turn downward toward the chimney or run horizontal.
2.There should be no more than two 90 degree elbows.
3.The smoke pipe should never be longer than six feet. If it is absolutely necessary to make a run of more than six feet (not recommended) use extra support brackets every 3 feet.
4.The smoke pipe should never be reduced to a smaller size than flue opening on the furnace.
5.The smoke pipe should not block the flue of the
chimney or extend into it in any way.
6.A good airtight thimble should be used to hold the
smoke pipe in the chimney. It should be constructed so the smoke pipe can be removed for cleaning.
7.The smoke pipe should not leave the heated portion of the building to reach the chimney.
8.The smoke pipe should not pass from one story to the next before entering the chimney, nor should it pass through any closed or enclosed space.
9.Heat reclaimers should not be installed or used in the smoke pipe.
10. The smoke pipe should not be located near or in a walk way or well traveled area.
11. All male ends of smoke pipe should run or point
towards the furnace.
heating season. DO NOT CONNECT TWO HEATERS TO THE SAME CHIM-
NEY FLUE. The National Fire Prevention Association recom­mends that woodburning appliances vent into a separate chimney from gas or oil furnaces. If such an installation is contemplated, first check with a local building inspector to find out if a separate flue for a woodburner is required.
If codes allow, use extreme care in making such installations. Be sure that one pipe is higher than the other so that the two openings will not be opposite each other. Also, when connect­ing two heaters into the same chimney flue, the flue size should be large enough to handle both heaters. Very few codes and standards allow same flue connection. Such installations can cause severe problems. Gas hoods and barometric dampers allow excess air into the chimney causing cooling of the flue gases and a greater creosote build-up potential. If the same flue connections are used, chimneys must be inspected more frequently and the chimney should be cleaned any time the creosote deposits exceed 1/4" thickness. A creosote fire in such a chimney can burn out of control because of the air leak through the barometric damper or gas hood. Keeping the chimney clean and burning well­seasoned wood is absolutely necessary. This type of installa­tion does require more frequent inspection and maintenance.
HEATED AIR DISCHARGE
The Hotblast furnace is designed for use as a supplemental heating source. When used as a supplementary furnace, the 1600/1800 is connected in conjunction with an oil, gas, or electric furnace to the existing duct work which distributes the heated air into several rooms and/or areas.
When used as a space heater, heated air from the 1600/1800 furnace is expelled directly into the room in which the furnace is located. In installations of this type, the flow of heated air from the furnace must not be blocked. It is recommended that an elbow be attached to the heated air discharge to divert the heated air away from combustibles. All other criteria for installation remains unchanged.
CONNECTING HOT AIR DUCT TO FURNACE
We strongly recommend that the hot air duct work be installed by a home heating specialist. If doing the installation yourself, before you decide which installation will best suit your needs, consult a qualified heating technician and follow his recom­mendations as to the safest and most efficient method of installation.
The following illustrations are the only acceptable configura- tions when installed with existing oil or gas furnaces.
INSTALLATION EXAMPLES
DAMPERS ON STOVE PIPES
When burning coal, we recommend a Barometric Draft Damper be installed at a safe convenient place between chimney and your furnace.
When you have installed the smoke pipe connecting your furnace to the chimney, tap the pipe hard with your fingernail. Remember the sound it makes - it will be a "ting" echoing inside the stove pipe. If later you tap and hear a muffled thud, you are building up soot in the pipe and should clean it. This pipe should be cleaned at least once or twice during the
3
BACK DRAFT DAMPER
HOTBLAST FURNACE
EXISTING FURNACE
INSTALLATION NO.1
With this installation, a back draft damper is inserted into the heat run before the plenum of the existing furnace to prevent air from the existing furnace to blow back into the furnace when it is not in use. When a back draft damper is employed, it should be located as close to the existing furnace plenum as practical.
INSTALLATION NO. 2
Extending the hot air duct from the furnace into the existing plenum will help direct the flow of air from the 1600/1800 as well as the flow in the existing furnace. Ducting entering the
BAFFLE
EXISTING FURNACE
1" MIN.
HOTBLAST FURNACE
9 FEET
EXISTING FURNACE (if used)
existing plenum at an angle (approximately 45 degrees) will facilitate air flow from the furnace while diverting air from the existing furnace.
2" MIN.
HOT AIR PLENUM
HOTBLAST FURNACE
9 FEET
HOTBLAST FURNACE
EXISTING FURNACE
1" MIN.
HOT AIR DUCT
MINIMUM CLEARANCES
TO COMBUSTIBLES
incorporated into the system. Return air can be provided by installing a separate duct system or by tying into the cold air return of an existing gas or oil furnace. The cold air return duct can be connected to the furnace with either a factory manufac­tured U.S. Stove filter box or an equivalent fabricated from sheet metal (See pages 21-23).
INCORRECT
When installing a cold air return, the following minimum
INSTALLATION
size should be maintained to insure proper furnace performance.
NO RETURN
Model 1600 — 16" x 20" or equivalent
AIR PROVIDED
Model 1800 --- 16" x 20" or equivalent
INSTALLATION NO. 3
The baffle on this system should be made the full width of the furnace plenum in order to properly direct the air into the distribution ducts.
RETURN AIR IS VERY IMPORTANT
When installing a Hotblast Furnace, return air must be
4
Failure to provide return air ducts of the specified size voids the furnace warranty.
HOTBLAST FURNACE
EXISTING FURNACE
A filter should be installed in the cold air return. Furnace filters should be checked and cleaned or replaced regularly.
If return air is not provided, the warm air distributed into your home will be restricted and the efficiency of the furnace decreased. Without a return air system, warm air will be drawn into your basement, unnecessarily heating unused areas of the home. In extreme cases, if your basement or utility room is fairly air tight, the large blower on the 1600/1800 could depressurize the room and pull toxic flue gases from the
furnace, a gas water heater, or gas furnace. The fumes could then be distributed throughout the house.
COMBUSTION AIR
All fires need air (specifically oxygen) to burn. Furnaces, fireplaces, and wood-burning furnaces need enough oxygen for complete combustion of their fuels. The incomplete combustion that takes place when a furnace is "air starved" causes carbon monoxide (CO) to be formed in quantities that can be dangerous inside a well-sealed house. Having a source of combustion air from outside prevents this "air starvation" of the furnace.
ASSEMBLY INSTRUCTIONS
to make sure there is no shipping damage, and that all necessary parts are located in the firebox. See parts list below.
If you find shipping damage or any of the parts missing, contact the dealer immedi-
Three 1/2" Lock Nuts One 1/2" x 2 1/2" Carriage Bolt Six 1/4" x 3/4" Hex Bolts Smoke Door Two 1/4" x 1-1/4" Carriage Bolts
MODEL 1600 - (6) BRICKS ON EACH SIDE
FIREBOX LEFT SIDE
Your furnace is shipped from the factory in four (4) packages.
1) the furnace, 2) the blower, 3) draft kit, 4) fan limit kit or
electronic circuit board . Before assembling the furnace, check ately. He will take the necessary steps to correct the problem.
Parts List
All models include the following: Two Door Handles One Fuel Door Latch One Ash Door Latch One Shaker Grate Handle Two 1/2" Washers Four 1/4" Hex Nuts Four Lock Washers Spin Draft Five 1/4" Lock Nuts One Pivot Bracket Four Brass Coil Knobs One 1/4" x 1" Hex Bolt
FUEL DOOR ILLUSTRATION
ASH DOOR ILLUSTRATION
BRICK RETAINING STRIP
SLIDE 4th BRICK BACK BEFORE INSTALLING 5th AND 6th BRICK
MODEL 1800 - (8) BRICKS ON EACH SIDE
FIREBOX LEFT SIDE
BRICK RETAINING STRIP
LOCK
WASHER
HEX
NUTS
Two Smoke Door Clips Rod Extension Manual
5
DOOR HANDLE INSTALLATION
Insert door handle into door. From rear side of door place 1/2" washer over threaded part of door handle. Then attach 1/2" lock nut, being careful not to over tighten. Handle should turn freely.
FUEL & ASH DOOR LATCH INSTALLATION
With two 1/4" x 3/4" hex bolts, attach the door latch to the
MODEL 1600 (41/2) BRICKS
MODEL 1800 (6) FULL BRICKS
2
1
1/2 BRICK
3
5
4
6
BAFFLE ROD EXTENSION
BAFFLE
ROD
1-1/2" HEX COUPLING
THE MODELS 1600 AND 1800 HAVE BEEN
2
1
3
4
5
6
7
EQUIPPED WITH DIFFERENT PLENUM OPENINGS, THEY ARE AS FOLLOWS:
door latch mounting bracket on the left side of door frame as illustrated. Adjust latch until door closes securely.
TOP
REAR OF FIREBOX
MODEL 1800
18"x18" Square Plenum Opening
6
BRICK INSTALLATION
(PRE-INSTALLED AT FACTORY)
The firebrick must be inserted on each side resting on the
SMOKE DOOR CLIPS
1/4" LOCK NUTS
1/4" X 1-1/4" CARRIAGE BOLTS
FRONT OF FURNACE
NOTE: Prior to operation, be sure to remove brick retaining strips.
FIREBOX:
1
2
FUEL
SMOKE DOOR
LOADING DOOR FRAME
grate frame. First, place cut brick in each back corner. Place remaining brick in place.
SMOKE CHAMBER:
1.Place #1 firebrick in the back of smoke chamber.
2.Slide baffle plate into smoke chamber, flat side down.
3.Place remaining firebrick in smoke chamber as
SPIN DRAFT CAP 1/2" X 2-1/2" CARRIAGE BOLT
3
1/2" LOCK NUT
7
MOUNTING PROCEDURE FOR DRAFTS
DRAFT TUBE CLAMP
MOTORIZED NATURAL DRAFT
FORCED AIR DRAFT
(SHIPPED WITH UNIT)
1. Using (2) 1/4" x 1" bolt, lock washer and nut, attach draft adapter bracket to furnace draft tube.
OPTIONAL
MOTORIZED NATURAL DRAFT
Models 1600 / 1800
1.Using (2) 1/4" x 1" bolts, lock washers and nuts, attach draft to furnace with draft tube clamp.
2.Plug draft power cord into receptacle on front of furnace.
MODEL 1600/1800 ­ KIT #C60357M
MODEL 1600/1800
KIT #69189
8
Loading...
+ 22 hidden pages