SAFETY NOTICE: IF THIS FURNACE IS NOT PROPERLY INSTALLED, A HOUSE
FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND
INSTALLATION REQUIREMENTS IN YOUR AREA. REFER TO MARKINGS ON
APPLIANCE FOR ADDITIONAL INFORMATION.
Installation/Operator's Manual #851547A
1
INTRODUCTION
CLEARANCES
Thank you for your purchase of a U.S. Stove Wood and Coal
burning furnace. Your decision to buy our Clayton Furnace was
undoubtedly reached after much careful thought and consideration. We are very proud you chose the U.S. Stove furnace and trust
you will receive the comfort and economy that others realize
when heating with a U.S. Stove product.
Your dealer is important in your experience with the Furnace not
only in your purchase, but in his recommendations for professional installation in your home. The qualified professional
installer (as recommended by your dealer) has been expertly
trained in solid-fuel furnace installation to assure the safety and
comfort for your family while saving you money. Trust your
experienced installer. He is a specialist in his field.
IMPORTANT
Before installing and using your Clayton Furnace, please read
the following pages thoroughly and carefully. If you follow the
instructions, your Clayton furnace will give you safe and more
dependable service in the years to come.
First step; check your local codes. This installation must
comply with their rulings.
Do not install this furnace in a mobile home or trailer.
Always have a smoke or ionization detector and a CO
detector installed in your home.
To prevent injury or damage, do not allow anyone who is
unfamiliar with the furnace to operate it.
Spend some time with your furnace to become well
acquainted with different settings and how each will
affect its burning patterns. It is impossible to state just
how each setting will affect your furnace because of
the variations in each installation.
DISCLAIMER NOTICE
The BTU ranges and heating capacity specifications are provided as a guide only and in no way guarantee the output or
capacity of the units. The actual BTU output depends on the type
of fuel being burned and its conditions, the thermostat setting, the
draft adjustment and the chimney to which the unit is attached.
The actual area that the unit will heat depends on factors such as
the conditions of the building, heat loss, type of construction,
amount of insulation, type of air movement, and the location of the
unit, and more importantly, your duct work and return air facility.
WARNING:
Do not alter this appliance in any way. Doing so may void
your warranty.
These instructions comply with CAN/CSA-B365
FLAMMABLE WALL
20"
22"
FLUE
12"
15"
(TOP VIEW)
MINIMUM
CLEARANCE TO
FLAMMABLE WALLS
CAUTION: Do not
store combustible or
flammable material
near furnace.
REDUCED CLEARANCES
NFPA guidelines and most codes permit reduced clearances to
combustible walls and ceilings if adequate protection is added.
A common mistake is to assume that sheet metal, masonry, or
millboard placed directly against a wall protects it. Materials
installed in this manner give very little protection. These materials
are good heat conductors, so they will be almost as hot on their
back side as they are on the exposed side. Therefore, the
combustible wall behind is still a fire hazard.
A wall can be kept cool using these items but only if they're
mounted and spaced out from the wall by an inch or two to allow
free circulation of room air behind the protective panel. The
protective panel should start within a few inches of floor level.
The three rules to follow when constructing wall protectors:
1. Non-combustibility of all materials including mounting
or supporting.
2.A well ventilated air space between protector or wall.
3.Sufficient strength and rigidity so that the protector and
air space will be durable.
2" FROM CEILING
CONSTRUCTING
NON-FLAMMABLE
WALLS
1" AIR SPACE
PROTECTIVE COVERING
AND ALL SUPPORTS MUST
BE NON-COMBUSTIBLE.
LOCATING YOUR FURNACE
The furnace is to be installed maintaining clearances as shown
in illustration.
Do not place the furnace directly on a combustible floor. If you're
placing it on a combustible floor, an approved fire retardant
material equivalent to 3/8" UL Listed millboard should be placed
under the furnace. The material must extend at least 16" in front
of and 8" on either side of the fuel-loading and ash-removal doors,
and underneath the chimney connector and extending at least 2"
on either side of the chimney connector.
2" FROM FLOOR
CHIMNEY REQUIREMENTS
A fireclay lined masonry or Class A 103HT All-Fuel Metal Insulated Chimney must be used in all airtight wood furnace installations. The minimum recommended flue size for the U.S. Stove
Clayton Furnace is 6" (inside diameter) for round flues, and 7" x
7" for square flues. When making new chimney installations,
always follow the chimney manufacturers instructions.
2
NOTE: Type of chimney: Class A All-Fuel UL 103HT
TOP OF CHIMNEY MUST
BE 2 FT. ABOVE HIGHEST
POINT OF ROOF WITHIN
10 FEET
CAP SHOULD HELP
PREVENT DOWNDRAFT
WHILE STILL PROVIDING
ADEQUATE EXHAUST.
on the flue lining. When ignited, this creosote makes an extremely
hot fire.
The chimney connector and chimney should be inspected at
least twice monthly during the heating season to determine if a
creosote build-up has occurred. If creosote has accumulated, it
should be removed to reduce the risk of a chimney fire.
2 FT.
MINIMUMS
MINIMAL 3 FT.
FROM TOP OF
CHIMNEY TO POINT
AT WHICH IT PASSES
THROUGH THE ROOF.
CHIMNEY FLUE
SHOULD BE
CONSTANT DIAMETER
THROUGHOUT ITS
ENTIRE HEIGHT.
APPROVED
CHIMNEY
CLEANOUT DOOR
SHOULD HAVE
AIRTIGHT FIT. DO
NOT LEAVE OPEN
WHEN FURNACE IS
IN OPERATION.
3 FT.
MINIMUM
CHIMNEY FLUE
MUST BE AS
LARGE OR 20%
LARGER THAN
FURNACE FLUE
PIPE
RECOMMENDED
MINIMAL
20 FT. HEIGHT
SMOKE PIPE INSTALLATION
Clearances to combustible materials (i.e. paneling, ceiling tile,
sheet rock, plaster, draperies, casements or wood trim, etc.)
will vary with the type of flue connection used. Be sure to
maintain the specified clearances for your type of installation.
TYPE OF FLUEREQUIRED
CONNECTIONCLEARANCE
24 Gauge or Heavier18"
Single Wall Stainless Steel
or Black Pipe
Double Wall Stainless Steel6"
Class A 103HT All-Fuel or Equivalent2"
COMBUSTIBLES
SMOKE PIPE
CHIMNEY THIMBLE SHOULD BE
CONSTRUCTED OF FIRE CLAY, AND
SHOULD FIT TIGHTLY TO FLUE PIPE.
1.The furnace should be the only heating appliance using
a chimney flue. One furnace per flue.
2.A masonry chimney should have a tile or stainless steel
liner.
3.The masonry chimney should not have any missing
mortar or loose bricks.
4.There should be no mortar or parts of the chimney
blocking the chimney flue.
5.There should be a two inch clearance between any
chimney (masonry or metal) and combustibles (such
as the house).
6.The chimney should extend at least 2' above the
highest point of the house, or 2' above the point at
which the chimney is 10' from the roof.
7.The chimney should be relatively straight and vertical.
8.The portion of an all-fuel metal chimney that extends
above the roof should be well secured.
9.A masonry chimney should be built on footings and not
attached to the house.
10. A rain cap, complete with an animal or bird screen,
should be installed on top of the chimney.
CREOSOTE — FORMATION AND NEED
FOR REMOVAL
When wood is burned slowly, it produces tar and other organic
vapors, which combine with expelled moisture to form creosote.
The creosote vapors condense in the relatively cool chimney flue
of a slow-burning fire. As a result, creosote residue accumulates
According to NFPA standards, single wall stove pipes can be
within 9" of combustibles provided an approved fire retardant
material covered with 28 gauge sheet metal, spaced out 1" on
non-combustible spacers, is utilized. See illustration.
CEILING OR WALL
18"
9"
18"
When using a Class A or double wall flue pipe connection,
follow the manufacturer's instructions.
When constructing a single wall smoke pipe, the following
guidelines must be observed.
1.The connector pipe should be 24 gauge or heavier
stainless steel or black pipe.
2.Secure all joints with three #8 screws.
3.If the connector pipe must pass through a wall, an approved insulated or ventilated thimble, at least three
times the diameter of the smoke pipe must be used. (i.e.
a 6" diameter smoke pipe needs an 18" thimble).
4.The connector pipe should never be used as a chimney.
IMPORTANT INFORMATION FOR
ALL CONNECTOR PIPES
The connector pipe must be constructed and installed so that it
3
maintains clearances, keeps condensation and creosote within
the pipe, and is capable of withstanding a two to three thousand
degree chimney fire.
1.The connector pipe should slant down toward the
furnace a minimum of 1/4" to the foot. At no time should
the pipe turn downward toward the chimney or run
horizontal.
2.There should be no more than two 90 degree elbows.
3.The connector pipe should never be longer than six
feet. If it is absolutely necessary to make a run of more
than six feet (not recommended) use extra support
brackets every 3 feet.
4.The connector pipe should never be reduced to a
smaller size than flue opening on the furnace.
5.The connector pipe should not block the flue of the
chimney or extend into it in any way.
6.A good airtight thimble should be used to hold the
connector pipe in the chimney. It should be constructed
so the connector pipe can be removed for cleaning.
7.The connector pipe should not leave the heated portion
of the building to reach the chimney.
8.The connector pipe should not pass from one story to
the next before entering the chimney, nor should it pass
through any closed or enclosed space.
9.The connector pipe and any elbows must be of 24 ga.
or greater.
10. The connector pipe should not be located near or in a
walk way or well traveled area.
11. All male ends of connector pipe should run or point
towards the furnace.
DAMPERS ON STOVE PIPES
When you have installed the connector pipe between your
furnace and the chimney, tap the pipe hard with your fingernail.
Remember the sound it makes - it will be a "ting" echoing inside
the stove pipe. If later you tap and hear a muffled thud, you are
building up soot in the pipe and should clean it. This pipe should
be cleaned at least once or twice during the heating season.
DO NOT CONNECT TWO HEATERS TO THE SAME CHIMNEY
FLUE. The National Fire Prevention Association recommends
that woodburning appliances vent into a separate flue from gas
or oil furnaces. If such an installation is contemplated, first check
with a local building inspector to find out if a separate flue for a
woodburner is required.
If codes allow, use extreme care in making such installations. Be
sure that one pipe is higher than the other so that the two openings
will not be opposite each other. Also, when connecting two
heaters into the same chimney flue, the flue size should be large
enough to handle both heaters. Very few codes and standards
allow same flue connection. Such installations can cause severe
problems. Gas hoods and barometric dampers allow excess air
into the chimney causing cooling of the flue gases and a greater
creosote build-up potential. If the same flue connections are
used, chimneys must be inspected more frequently and the
chimney should be cleaned any time the creosote deposits
exceed 1/4" thickness. A creosote fire in such a chimney can burn
out of control because of the air leak through the barometric
damper or gas hood. Keeping the chimney clean and burning
well-seasoned wood is absolutely necessary. This type of installation does require more frequent inspection and maintenance.
HEATED AIR DISCHARGE
The Clayton furnace is designed for use as a supplemental
heating source. When used as a supplementary furnace, the
1600M is connected in conjunction with an oil, gas, or electric
furnace to the existing duct work which distributes the heated air
into several rooms and/or areas.
Though United States Stove Company expressly Does Not
recommend the use of its furnaces to be installed and/or used as
a free-standing heater, it is possible to achieve a reasonably safe
and functional installation
followed. The following are guidlines only and are intended to
enable the furnace user to obtain resonable efficiency from his
furnace, and with due respect to safety when installing as a "freestanding heater". If installed correctly, and in accordance with
the instructions found in this manual, your warm air furnace may
be installed as a "space heater" within living quarters, cabins,
garage, or workshop. Please adhere to the following:
1) The use of a cold air return and/or filter box is mandatory. This
will not only inscrease your blower life and provide filtered air, it
will also help prevent the blower or blowers from "capturing"
heated air exiting from the top of the furnace heat outlets.
2) If installed as purchased , without directing the heat away from
the furnace itself, it will simply sit and cycle, turning the blowers
off and on. The thermostat may not function properly.
3) All larger furnaces (or those with multi-speed blowers)
absolutely require BACK PRESSURE to prevent premature
winding failure. If allowed to operate at high RPM (As in "FREE
AIR" mode - no ductwork or flow restrictions) the windings
overheat, insulation melts and the motor simply burns up - not
covered under warranty.
IF certain standard procedures are
CONNECTING HOT AIR DUCT TO
FURNACE
We strongly recommend that the warm air duct work be installed
by a home heating specialist. If doing the installation yourself,
before you decide which installation will best suit your needs,
consult a qualified heating technician and follow his recommendations as to the safest and most efficient method of installation.
The warm air duct must be constructed of metal with a minimum
temperature rating of 250°F
The following illustrations are the only acceptable configurations
when installed with existing oil or gas furnaces.
INSTALLATION EXAMPLES
INSTALLATION NO.1
With this installation, a back draft damper is inserted into the heat
run before the plenum of the existing furnace to prevent air from
the existing furnace to blow back into the furnace when it is not
in use. When a back draft damper is employed, it should be
located as close to the existing furnace plenum as practical.
BACK
DRAFT
DAMPER
HOTBLAST
FURNACE
EXISTING
FURNACE
4
INSTALLATION NO. 2
Extending the hot air duct from the furnace into the existing
plenum will help direct the flow of air from the 1600M as well as
the flow in the existing furnace. Ducting entering the existing
plenum at an angle (approximately 45 degrees) will facilitate air
flow from the furnace while diverting air from the existing furnace.
INSTALLATION NO. 3
The baffle on this system should be made the full width of the
furnace plenum in order to properly direct the air into the
distribution ducts.
BAFFLE
HOTBLAST
FURNACE
1" MIN.
9 FEET
EXISTING
FURNACE
(if used)
EXISTING
FURNACE
RETURN AIR IS VERY IMPORTANT
When installing a Clayton Furnace, return air must be incorporated into the system. Return air can be provided by installing a
separate duct system or by tying into the cold air return of an
existing gas or oil furnace. The cold air return duct can be
connected to the furnace with either a factory manufactured U.S.
Stove filter box or an equivalent fabricated from sheet metal (See
pages 22-23).
When installing a cold air return, the following minimum
size should be maintained to insure proper furnace
performance.
Model 1600M — 16" x 20" or equivalent (320 sq. in.)
Failure to provide return air ducts of the specified size
voids the furnace warranty.
A filter should be installed in the cold air return. Furnace filters
should be checked and cleaned or replaced regularly.
If return air is not provided, the warm air distributed into your home
will be restricted and the efficiency of the furnace decreased.
Without a return air system, warm air will be drawn into your
basement, unnecessarily heating unused areas of the home. In
extreme cases, if your basement or utility room is fairly air tight,
the large blower on the 1600M could depressurize the room and
pull toxic flue gases from the furnace, a gas water heater, or gas
furnace. The fumes could then be distributed throughout the
house.
2" MIN.
HOT AIR
PLENUM
HOTBLAST
FURNACE
9 FEET
HOTBLAST
FURNACE
EXISTING
FURNACE
HOT AIR DUCT
MINIMUM CLEARANCES
TO COMBUSTIBLES
CAUTION: The warm air supply outlet of the supplementary
furnace should not be connected to the cold-air return inlet of the
central furnace because a possibility exists of components of the
central furnace overheating causing it not to operate properly.
INCORRECT
INSTALLATION
NO RETURN
AIR PROVIDED
HOTBLAST
FURNACE
COMBUSTION AIR
All fires need air (specifically oxygen) to burn. Furnaces, fireplaces, and wood-burning furnaces need enough oxygen for
complete combustion of their fuels. The incomplete combustion
that takes place when a furnace is "air starved" causes carbon
monoxide (CO) to be formed in quantities that can be dangerous
inside a well-sealed house. Having a source of combustion air
from outside prevents this "air starvation" of the furnace. A simple
positive air supply can be constructed using dryer vent and a
modified termination.
5
1" MIN.
EXISTING
FURNACE
ASSEMBLY INSTRUCTIONS
Your furnace is shipped from the factory in four (2) packages. 1)
the furnace, 2) the blower. The draft kit and parts box containing
all parts necessary, and the fan thermodisc kit is boxed and
packed in the firebox or ash pan. Before assembling the furnace,
check to make sure there is no shipping damage, and that all
necessary parts are located in the firebox. See parts list below.
If you find shipping damage or any of the parts missing, contact
the dealer immediately. He will take the necessary steps to
correct the problem.
Parts List
All models include the following:
(2) Door Handles
(1) Fuel Door Latch
(1) Ash Door Latch
(2) 1/2" Washers
(9) 1/4" Kep Nuts
(2) Spin Draft
(4) Brass Coil Knobs
(1) Shaker Handle
(1) 1/4" x 1" Hex Bolt
(1) 3/8" Lock Nut
(1) 3/8" Jam Nut
(2) 3/8" x 2 1/2" Carriage Bolt
(6) 1/4" x 3/4" Hex Bolts
(1) Smoke Door
(1) Hinge Bracket
(2) 1/4" x 1-1/4" Carriage Bolts
(2) Smoke Door Clips
BRICK INSTALLATION
(PRE-INSTALLED AT FACTORY)
NOTE: Prior to operation, be sure to remove brick
retaining strips.
MODEL 1600M - (6) BRICKS ON EACH SIDE
FIREBOX LEFT SIDE
BRICK RETAINING STRIP
SLIDE 4th BRICK BACK
BEFORE INSTALLING 5th
AND 6th BRICK
FIREBOX:
The firebrick must be inserted on each side resting on the grate
frame. First, place cut brick in each back corner. Place remaining
brick in place.
DOOR HANDLE INSTALLATION
Insert door handle into door. From rear side of door place
1/2" washer over threaded part of door handle. Then attach
1/2" lock nut, being careful not to over tighten. Handle should turn
freely.
FUEL & ASH DOOR LATCH INSTALLATION
With two 1/4" x 3/4" hex bolts, attach the door latch to the door latch
mounting bracket on the left side of door frame as illustrated.
Adjust latch until door closes securely.
FUEL DOOR
ILLUSTRATION
ASH DOOR
ILLUSTRATION
LOCK
WASHER
HEX
NUTS
6