United Electric Controls H119, 119 Series, F119, F119A, H119A Installation And Maintenance Instructions Manual

Installation & Maintenance Instructions
H119 S E R I E S
Pressure & Temperature Switch
Supplied by
.com
Call us on +44 (0)118 916 9420 | Email info@247able.com
Pressure
Pressure controls may be mounted via two mounting slots for #10 screws in the enclosure or directly to a rigid pipe using the pressure connection. Low pressure units, models 520-535, are also available with an optional sur­face mounting bracket. Always use a wrench to tighten pressure connection to the pipe. To prevent damaging pressure sensor, use a backup wrench to hold the hex nut in place when surface mounting.
Temperature
Temperature controls must be surface mounted via #10 screw slots. For remote bulb temperature controls, fully immerse bulb and 6” of capillary in the control zone for most efficient control. Best control is usually obtained by placing the bulb close to the heating or cooling source in order to sense temperature fluctuations quick­ly. Be sure to locate bulb so that it will not be exposed to temperature beyond the instrument range limits.
WIRING
WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING.
ELECTRICAL RATINGS STATED IN LITERATURE
AND ON NAMEPLATE SHOULD NEVER BE EXCEEDED. OVER-LOAD ON A SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE.
1/2” NPTM conduit connection is provided on top of the unit with 18” leadwires. Unit is available with SPDT or DPDT (119A) operation. External grounding screw and clamp (GND symbol is cast into enclosure) is provided.
UNITED ELECTRIC
CONTROLS
Installation and Maintenance Instructions
IM119
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended Practices, Liabilities and Warrantees.
119 Series Pressure and Temperature Switches
Types H119, H119A, F119, F119A
UL & CSA Listed Switch Capsule Div.1 & 2 Class I Groups A, B, C & D Class II Groups E, F, G; and Class III CENELEC EExd IIC T6 per EN 50 014/50 018
Part I - Installation
Leadwires to the terminal block are color coded:
SPDT DPDT
SWT1 SWT2
Common Brown Brown Yellow Normally Closed Red Red Black Normally Open Blue Blue Violet Ground Green Green
GENERAL
Pressure
Types H119 and H119A controls are activated when a diaphragm sensor responds to a pressure change. This response, at a predetermined set point, actuates a SPDT or a DPDT snap acting switch, converting a pressure sig­nal into an electrical signal. Control set point may be var­ied by turning the internal slotted adjustment screw bush­ing according to procedures outlined in this document. (See Adjustment Procedures-Pressure Models PART II)
Temperature
Types F119 and F119A (Bulb and Capillary) controls sense temperature variations with a liquid filled sensing bulb. Liquid expansion or contraction is hydraulically transmitted to a diaphragm which actuates a SPDT or a DPDT snap action switch at a predetermined set point, converting a temperature signal into an electrical signal. Set point is adjusted by turning the internal hex adjust­ment screw according to procedures outlined in this docu­ment. (See Adjustment Procedures-Temperature Models PART II)
Tools Needed
1 1/16” Open End Wrench
Flat Head Srewdriver
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION AND
TEMPERATURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT SO THAT MOISTURE IS PREVENTED FROM ENTERING THE ENCLOSURE. IF UNIT IS BEING INSTALLED WHERE HEAVY CONDENSATION IS EXPECTED, VERTICAL MOUNTING (PRESSURE CONNECTION DOWN) IS REQUIRED. DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUB­LISHED LIMITS. CONTROLS MAY BE MOUNTED AND OPERATED IN ANY POSITION.