United Electric Controls 800, 800S, T800, T800S, 802S Installation And Maintenance Instructions Manual

...
GENERAL
Temperature variations are sensed by the liquid filled bulb which hydraulically transmits motion through a mechanism which rotates the indicating pointer and actuates precision snap-acting switch(es). Controller settings are made by turning the adjustment knob(s). Thermometer types T800 (with enclosure) and T800S (skeleton) provide temperature indication only with no control switches.
Tools Needed
Screwdriver to secure
customer supplied screws
Screwdriver
5/64” Allen Wrench
INSTALL UNIT WHERE SHOCK, VIBRA-
TION AND TEMPERATURE FLUCTUA­TIONS ARE MINIMAL. ORIENT UNIT SO THAT MOISTURE IS PREVENTED FROM ENTERING THE ENCLOSURE. IT IS IMPERATIVE THAT PROPERLY RATED EXPLOSION-PROOF SEAL­ING FITTINGS BE USED FOR ELECTRICAL WIRE ENTRY OR 820E AND 822E TYPE UNITS. DO NOT MOUNT UNIT IN AMBIENT TEMPERA­TURES EXCEEDING PUBLISHED LIMITS.
PREVENTATIVE MAINTENANCE / PERIODIC
TESTING (6 MONTHS OR SOONER AS DIC­TATED BY THE ENVIRONMENT) IS NECESSARY TO ENSURE OPERATION OF THE PRODUCT TO SPECIFICATION. LUBRICATE ALL PIVOT POINTS AND MOVING PARTS, TO PREVENT CORROSION, WITH COMPATIBLE DRY LUBRICANTS OR LIGHT GREASE.
DO NOT KNOCKOUT ANY PLUGS ON EXPLOSION-PROOF TYPES 820E OR 822E
When mounting 800 or 802 type controls, it may be necessary to remove adjustment knob and front cover. The knob is secured with a 5/64” Allen Setscrew. The cover is secured by four screws at the corners.
MOUNTING
The controller may be mounted in any position to either a surface or panel (1/4” thick maximum). Locate it where vibration, shock and ambient temperature fluctuations are minimal. It is recom­mended that mounting the unit with the conduit connection on the top be avoided.
To Flush Mount
(Not applicable to explosion-proof types) Cut out the panel as shown in Figure 1A. Mount to the panel using the two holes located on the flange of the enclosure.
To Panel Mount
(Skeletons) Prepare the cut out, drilling the holes for the knob shaft and the mounting holes per Figure 1B.
UNITED ELECTRIC CONTROLS
Installation and Maintenance Instructions
IM800-03
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended Practices, Liabilities and Warranties.
800 Series Temperature Controllers and Thermometers
Types 800, 800S, T800, T800S, 802, 802S, 802P, 802PS, 820E*, 822E*
*Explosion-Proof Class I, Groups B, C, D; Class II, Groups E, F & G; Class III
Part I - Installation
Figure 1A - Flush Mounting
Figure 1B - Panel Mounting (Skeleton)
Clearance for #6 screw
(4) places (3/16 Max.
Panel Thickness)
Clearance for #8 screw - (2) places
Avoid bending or coiling the capillary tube tighter than 1/2” radius. Exercise caution when making bends near the capillary ends.
If a separable well or union connector is used follow separate instructions included with them.
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING.
ELECTRICAL RATINGS STATED IN LIT-
ERATURE AND ON NAMEPLATE SHOULD NEVER BE EXCEEDED. OVERLOAD ON A SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE.
WIRE UNITS ACCORDING TO LOCAL
AND NATIONAL ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE IS 14 AWG.
Types 800, 802, 802P
(Enclosed units) Connect the electrical conduit to the case securing it with the grounding locknut supplied.
Note: Unless control is connected to a metallic conduit, grounding bushing should be removed from grounding wire. A separate conductor should be provided from grounding system directly to the non-current carrying metal parts of control (splice the grounding wire).
Conduit opening is available on the left side as standard. It can be supplied on the right side on request. See PART III, option M007. Wire through the 7/8” conduit hole directly to the lead-wire(s) provided, color coded as follows, or to the optional terminal block.
Switch 1 Switch 2
Common Violet Yellow Normally Open Blue Orange Normally Closed Black Red
Avoid bending or coiling the capillary tube
See wiring Diagrams Figure 2A and 2B. Optional terminal block wiring is available for single or dual switch controls (option M100). See Figure 2C.
To Surface Mount
(Explosion Proof Types) 820E and 822E type units must be surface mounted. Drill mounting holes per Figure 1C.
(Option M449) Attach 2 mounting ears found in separate package to recessed areas on back side of enclosure by means of 2 self-tapping screws. Mount to surface per Figure 1D. On dual switch explosion-proof types requiring seal fitting, install the nipple and the seal fitting prior to sur­face mounting the controller.
Mounting Bulb and Capillary
Fully immerse the bulb and 6” of capillary in the control zone. For best control it is generally desirable to place the bulb close to the heating or cooling source in order to sense temperature fluctuations quickly. Be sure to locate the bulb so it will not be exposed to temperature beyond the instruments range limits.
Try to place the remaining capillary adjacent to the control head so it will sense the same ambient temperatures (control is ambient tem­perature compensated).
Unless otherwise specified, factory calibration, allows for 6” of capillary tube in the control zone. If longer lengths are required recalibra­tion may be necessary. Follow the procedure outlined in PART II.
‘C’ style bulbs can be coiled or shaped to fit the installation. Avoid sharp bends and coils tighter than a 2” radius. Do not bend ‘B’ style bulbs.
Figure 1C - Explosion-Proof Mounting
Figure 1D - Surface Mounting
WIRING
Clearance for 1/4
screw (4) places
Clearance for #10 screw - (2) places
Types 800S, 802S and 802PS
(Skeleton units) Wire directly to the leadwires, in the same manner as above.
Types 820E and 822E
(Explosion-proof) Connect the electrical conduit directly to the die­cast aluminum enclosure via 3/4 NPTF connec­tion. Wire directly to the terminal block. See Figure 2D. Wiring enclosure includes grounding terminal.
Figure 2D - Explosion Proof
Tools Needed
5/64th” Allen Wrench
5/16” Open End Wrench (2 required)
Screwdriver
1/4” Open End Wrench
9/16” Open End Wrench
Switch Settings
(Dual switch types only) The basic enclosed and skeleton dual switch controllers are furnished with a choice of individual or common adjustment of set points as described below.
Types 802 and 802S have a separate knob and pointer for each switch. Turn black knob for switch #2 and turn green inserted knob for switch #1. Set points are shown by individual pointers and may be separated up to 100% of dial range apart, so long as the red pointer is set higher than the green pointer.
Types 802P, 822E AND 802PS have a single knob and pointer for both switches. Both switches are standardly, factory set together within 5% of the dial range. Turning the knob positions both switch simultaneously, maintain­ing a constant separation between switches.
Replace cover and adjustment knob if removed during installation. Controller is ready for operation. Turn setting pointer to desired control temperature and start up the process. To suit particular process conditions or for greater controller accuracy it may be desirable to make slight alterations to the set point or indicator reading. Procedures for making these adjustments are described below.
Note:
Indicating Pointer Deflection:
The indicating pointers will read slightly low when the bulb temperature is 15° above the controller setting. This deflection is normal and repeatable (approximately 0.5% of scale range on single switch models) and is due to the transference of the switching mechanism load to the thermal system. It can be measured by moving the setting pointer from the high to the low end of the scale and observing the resultant indicating pointer deflection.
Note:
Prior to making any controller adjust­ments, the cover and adjustment knobs should be removed. When adjustments are completed, all applicable parts should be replaced.
Part II - Adjustments
Figure 2A - Dual Switch
Figure 2B - Single Switch
Figure 2C - Terminal Block Option
Loading...
+ 5 hidden pages