United CoolAir MARVEL MINI Installation, Operation And Maintenance Manual

Page 1
MARVEL MINI HVAC
MICROPROCESSOR CONTROLLER
Installation, Operation and Maintenance Manual
Effective December 2018
Building Management System
***Interactive PDF***
Page 2
CONTENTS
Installation, Operation and Maintenance Manual
GENERAL PURPOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Marvel Mini™ - Controllable System Component
Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
AVAILABLE FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . 5
HARDWARE AND ARCHITECTURAL LAYOUT. . . . . . . 6
MARVEL MAIN BOARD. . . . . . . . . . . . . . . . . . . . . . . . 7
MARVEL TERMINAL (WALL CONTROL) . . . . . . . . . . 8
MARVEL WALL DISPLAY BUTTONS . . . . . . . . . . . . . 9
PROGRAMMING AND OPERATING SCREENS . . . 10
DISPLAY DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . .11
CONNECTING CABLE . . . . . . . . . . . . . . . . . . . . . . . 13
SENSOR INSTALLATION AND ELECTRICAL
TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Static Pressure Transducer
(Duct Mount) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
MARVEL MULTIAPP CONTROLLER – SEQUENCE OF
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
STANDARD SYSTEM SAFETIES . . . . . . . . . . . . . . . 29
OPTIONAL SYSTEM SAFETIES. . . . . . . . . . . . . . . . 31
Marvel Terminal Keypad and Display Operation . . . . 32
Controller Operation. . . . . . . . . . . . . . . . . . . . . . . . . . 32
Changing Set Points, Parameters, And Values . . . . . 33
SYSTEM ENABLES. . . . . . . . . . . . . . . . . . . . . . . . . . 39
SET POINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ALARM SET POINTS . . . . . . . . . . . . . . . . . . . . . . . . 44
Run Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Clock Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Set-Back. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
CHANGE PASSWORD . . . . . . . . . . . . . . . . . . . . . . . 51
Technician Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
FAN DELAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
SYSTEM UNITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
NETWORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
SENSOR SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
MANUAL CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . 56
DIGITAL INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ECONOMIZER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
BLOWER VFDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
CHANGE PASSWORDS . . . . . . . . . . . . . . . . . . . . . . 58
SYSTEM INFORMATION . . . . . . . . . . . . . . . . . . . . . 58
INPUT WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
OPTIONAL BOARDS. . . . . . . . . . . . . . . . . . . . . . . . . 60
SYSTEM NETWORKING. . . . . . . . . . . . . . . . . . . . . . 61
Subject to change without notice. 120.9-IM (1218)
2
Page 3
Installation, Operation and Maintenance Manual
GENERAL PURPOSE
The Marvel Mini™ is a microprocessor based electronic programmable controller with a multi-tasking operating system used to control United CoolAir manufactured HVAC systems using a newly developed Multi-Application software package. With this new system all of the previous applications provided by United CoolAir are all now bundled into one software package. So this one Multi-Application software package can now handle standard heating, cooling,
dehumidication, humidication, as well as the heat pump,
Variable Air Volume, and Outdoor Air applications. The only difference will be the size of the hardware controller installed in each unit. Since this is a mini controller package, options are limited so please inquire with sales and marketing when there are questions. The basis of design for the Marvel Mini Controller is for a maximum of one compressor and/or one heater with two modulating analog outputs to regulate optional devices based on demand. All available device options are listed starting on page 4.
Each Marvel Mini™ controller comprises of two ash drives
“volume 0”, having 32MB in which the main application program resides and cannot be accessed by the user and
an additional drive “volume 1”, having 96MB of NAND ash
memory available to the user and accessed through the USB port or FTP Protocol. Volume 1 is useful to the end user as there is free space to add unit-operating literature, web pages, and system logs. The microprocessor is based on 32 bit, 100 MHz so now variables can be communicated in 32bit data-type format.
Since the Marvel controller has a multi-tasking operating system, it now supports networking of additional programmable controllers, remote user terminals, communicating devices as well as interfacing with Building Management Systems much easier than its predecessors
that had BIOS rmware.
Figure 1 – System Layout is made up of the Marvel Mini™ main control board showing options for communicating devices, networking, building management and supervisory system setups. Customers have the option of either a built­in or wall mount display and keypad or even both of these if desired. The Marvel Mini™ system also contains common
required standard sensors as well as optional sensors that
must be eld installed and wired to the factory provided eld
interface terminal blocks in the air handlers electrical control box.
Each Marvel Mini™ has numerous standard setups built for interfacing with ECM Fans and VFDs for low ambient
and duct pressure control and/or Humidier controllers
through serial communication ports saving additional I/O for system sensors. The Universal Input channels have been developed so that a customer can replace or add a sensor
in the eld and set up the characteristics of the sensor
under a sensor setup menu however, it is recommended to contact the local distributor or factory before doing so for detailed information.
The Marvel Mini™ is equipped with a set of plug in terminal block connectors used to connect the Main Board to the controlled devices (i.e. solenoid valves, compressor contactor(s), blower contactors, heater contactors, VFDs, etc.). The application program is stored in Flash Memory of the controller and the unit’s hardware setup and control set points and parameters are stored in permanent memory (even in case of power failure). The software program is designed for “smart control”, to automatically predict and project required changes based upon present readings over time intervals in efforts to proactively adjust to changing conditions. The Marvel Mini™ can be linked with Building Management Systems RS485 serial or Ethernet connections with customer provided communication protocol details.
As a standard unless otherwise specied, the Marvel Mini™
microprocessor-based Remote User Terminal unit comes complete with LCD Display and Keypad for viewing and setting of the control parameters (set points, proportional bands, dead bands, and alarm set points, system run hours. etc.). The Terminal also allows viewing of the operating parameters, staging of system components, and system demands. Connection between the Marvel Mini™ main board and remote user terminal is only required for viewing or changing of the operating conditions and set points.
Subject to change without notice. 120.9-IM (1218)
3
Page 4
Installation, Operation and Maintenance Manual
Marvel Mini™ - Controllable System Component Information
With this new format, one of the key benets of the Marvel Mini™ application software is set up universally so that any of the
following functions could literally be added to any of the corresponding channels. This means for example, any of the listed functions under Analog/Universal Inputs could be placed onto any of the Universal Channels U1 though U10 whereas in
the past and with most control vendors, a software modication would be required. In addition now all of the Analog Inputs,
Digital Inputs, Analog Outputs, and Digital Outputs are all selectable for any of their corresponding channels. So for instance
the digital output for Compressor 1 could be congured on any of the Digital Outputs NO1 through NO18 (example of large
controller maximum number of Digital Outputs). These Universal Functions for each of the four I/O Groups are:
ANALOG/UNIVERSAL INPUTS
Return Temperature Compressor 1 Liquid Temperature Compressor Liquid Pressure
Space Temperature Compressor 1 Suction Temperature Space Humidity
Outdoor Air Temperature Water Temperature Outdoor Air Humidity
Supply Air Temperature 1 Return Humidity
ANALOG OUTPUTS
Modulating Hot Gas Bypass Modulating Waterside Economizer Discharge Pressure Valve 1
Airside Economizer Modulating Reheat
Modulating Heater Modulating Humidifier
DIGITAL INPUTS
Compressor 1 High Pressure Remote ON/OFF Heater High Limit
Compressor 1 Low Pressure Dirty Filter Water Flow
Loss of Airflow Compressor Freeze Stat Smoke Purge
Drain Pan Overflow Fire/Smoke Alarm Heat Pump Defrost Switch
DIGITAL OUTPUTS
Supply Blower Heater Global Alarm Output
Outdoor/Fresh Air Damper Reversing Valve
Compressor Reheat
Subject to change without notice. 120.9-IM (1218)
4
Page 5
Installation, Operation and Maintenance Manual
AVAILABLE FUNCTIONS
The following is a listing of available functions please inquire with the local United CoolAir Distribution for unit design
congurations with these functions:
● One Compressor Staged ON/OFF or Digital.
● One Heater Staged ON/OFF or Modulating or Hot Water Coil or Steam Coil for modulating control valves at 0-10vdc output.
● Modulating Humidier controlled via Modbus Communications.
● Modulating Hot Gas Bypass for system capacity control.
● Modulating Blower control for Variable Air Volume applications with VFDs communication via Modbus to display critical information from the VFD to the Display where as previously important information such as motor current, motor speed, voltage, kw hours was not supplied due to hard wire
congurations.
● Modulating Blower for Variable Air Volume applications via ECM motors.
● Hot Gas Reheat either by Stage or Modulating.
● Compressor safeties for high and low pressure are wired independently for true notication of which failure High or Low Pressure.
● An Air Switch has been incorporated to turn off cooling, heating, dehumidication, and humidication in
the event of a loss of air ow due to a broken v-belt or other means.
● On a heater high limit failure the heaters are locked out, but automatically reset when the safety resets. The display and alarm button will indicate an alarm occurred with the heating function.
● Airside or Waterside Economizer.
● Integrated Economizer function that allows Mechanical Cooling Compressors to assist is also available.
● Networking of multiple units with Unit Lead Lag and Backup unit assist is built into the main software
platform so if multiple units are shipped to the eld and the customer decides to network the units
together at a later date the software is already capable of networking up to 16 total units.
● Building Management Systems via the following BMS Protocols is available: BACnetTM Modbus®, Lonworks®, HTML Web Pages
Subject to change without notice. 120.9-IM (1218)
5
Page 6
HARDWARE AND ARCHITECTURAL LAYOUT
HARDWAREANDARCHITECTURALLAYOUT
Terminal /
Wall Mount
Control
            
Interface Wiring
Interface
RS485
Installation, Operation and Maintenance Manual
Building
Management
System
BMS - Interface
Networking Cable
RS485
Interface
Marvel Premium
Mini Main Board 1
FIGURE 1 – HARDWARE / ARCHITECTURE LAYOUT
Subject to change without notice. 120.9-IM (1218)
6
Marvel Premium
Mini Main Board 2
Page 7
Installation, Operation and Maintenance Manual
MARVEL MAIN BOARD
Figure 2 – Marvel Mini™ Main Board is the layout of the main control board. The reference designator Jxx specically lists
the functions of each location on the board. These references are as follows:
FIGURE 2 – MARVEL MAIN BOARD
J1 Control Voltage connection terminals. 24 VAC required.
J2 Universal Inputs used for sensor readings. Each channel can handle any of the Analog/Universal Input
functions.
J3 Used for connecting the Remote Display/Wall Terminal
J4 Fieldbus Device Connections.
J6 BMS Interface RS-485 or Ethernet based on model ordered.
J7 No Function for the Marvel Mini™ controller.
J8 Digital Inputs used for safety and alarm devices and Analog Outputs used for optional modulating devices.
J9 Power supply +5 vdc or +24 vdc to power sensor devices.
J10 Normally Open Digital Outputs 1 and 2.
J11 Normally Open Digital Outputs 3 through 5.
J12 Normally Open/Normally Closed Digital Output 6.
Subject to change without notice. 120.9-IM (1218)
7
Page 8
Installation, Operation and Maintenance Manual
MARVEL TERMINAL (WALL CONTROL)
The Marvel Terminal is complete with LCD Display and Keypad. The Terminal has LED indicators integral to the buttons. A description of each indicator light is discussed with the function of the each button starting on page 11.
The Marvel Terminal contains no sensors and does not need to be located in the building’s space that is being conditioned. The Terminal can be mounted up to 1000 feet from the equipment. See Figure 3 – Terminal below for reference. The Terminal is made up of the following components:
A. External buttons Prg, Esc, , , and or (adjustment buttons) with integral LED indicators.
B. Submenus include System ON/OFF, System Status, System Enables, Set Points, Alarm Set Points, Run
Hours, Day Min/Max, Clock Settings, Schedule, Setback, Unocc Control, Change Passwords, Technician Menu, Factory Menu
C. A 22 character by 8 row LCD Display with English text for ease of understandability for adjustment.
FIGURE – 3 TERMINAL (WALL MOUNT) CONTROL
Subject to change without notice. 120.9-IM (1218)
8
Page 9
MARVEL WALL DISPLAY BUTTONS
See Figure 4 – Control Buttons for reference.
Installation, Operation and Maintenance Manual
ALARM BUTTON
PROGRAM BUTTON ENTER BUTTON
ESCAPE BUTTON DOWN BUTTON
UP BUTTON
FIGURE 4 – CONTROL BUTTONS
ALARM BUTTON
The button is used for viewing the present alarms with the system. During an alarm condition, the button is illuminated a continuous Red. Depending on the type of alarm, the system may shut down or continue to operate. Some types of alarms are just simple faults known as indicators which are not harmful to the operation of the unit but may require attention in the near future. Pressing the button will reveal what alarm caused the system to shut down. To reset an alarm, press the button until the screen displays “NO MORE ALARMS; To reset the alarm, simply press the button again to reset the alarm.
PROGRAM BUTTON
The Prg button is used to enter into menus and sub menus. On controllers with built in displays, the is the program button.
ESCAPE BUTTON
The Esc button is used to return to the main system status from a menu or sub-menu or escape to the previous menu from a sub-menu. On controllers with built in displays, the is the escape button.
UP BUTTON
The up button is used to scroll upward through status screens, menus, sub-menus and change the value of parameters or settings.
ENTER BUTTON
Upon application of power to the system, the splash screens appear then the main status home screen will appear. Use the
enter button to move the cursor to the next eld (set points or parameters) where the change is desired. Also use the Enter
button to initialize/save changed parameters and set points into memory.
DOWN BUTTON
The down button is used to scroll downward through status screens, menus, sub-menus and change the value of parameters or settings.
Subject to change without notice. 120.9-IM (1218)
9
Page 10
Installation, Operation and Maintenance Manual
PROGRAMMING AND OPERATING SCREENS
As shown in Figure 4 previous, each of the buttons are used to access specic locations to Read or Change (such as set
point) values. Below is a list of the menus that are accessible from the wall mount controller. By pressing the Prg button multiple times, the following menus will appear:
4. SET POINTS menu – Used for changing temperature and humidity settings. It is also used to set temperature high and low alarm set points as well as humidity high and low alarm set points. If customers have the pressure control option, settings will also appear to adjust duct or room pressure.
5. TIME CLOCK SETTINGS menu – Used for changing the Time Clock Readings to the current Time and Date. This menu is also used for setup of Daylight Savings Time based on region and enabling of the Night Set Back Function. Once the Night Set Back Function is enabled, the type of control (Temp/Humidity Setback) is enabled and Set Points for Temperature and Humidity Setback Control shall appear as well as the day of the week to enable Night Set Back and time of day for occupied and unoccupied period.
6. SYSTEM ENABLES menu – This sub-menu allows for re-enabling of system functions (System ON/OFF,
Humidication/Dehumidication, Compressors, Heaters, ON/OFF and Modulating Reheat, etc.) after an alarm
condition has occurred.
7. EQUIPMENT RUN HOURS menu – Displays the operational run hours of system components such as Fan,
Humidier, Compressors, Heaters, etc.).
8. ANALOG/DIGITAL INPUTS/OUTPUTS menu – This sub-menu is used to calibrate sensors and alarm input setup settings.
9. PRG & ESC (Factory Setup menu) – Used for changing the Factory Default System settings. It is used to change control functions with their equipment.
LCD Display
The Terminal provides eight lines of twenty-two characters per line LCD Display. The character is 5 mm in height. See Figure 5 – LCD Display.
U01 Mon 07:21 03/19/17
Return Hum > 55.0% Return Temp> 74.7 °F Supply Temp> 57.2 °F
One Compressor ON
FIGURE 5 – LCD DISPLAY
Subject to change without notice. 120.9-IM (1218)
10
Page 11
Installation, Operation and Maintenance Manual
DISPLAY DIMENSIONS
Refer to Figure 6 – Terminal Dimensions for dimensional data. Dimensions shown are in inches.
FIGURE 6 – TERMINAL DIMENSIONS
Marvel Display (Terminal) – Wall Mounting
Refer to Figure 7 – Wall Mounting for instructions to mount the Terminal to a wall.
FIGURE 7 – WALL MOUNTING
Components of the Wall Controller:
A. Faceplate
B. Wall Controller
C. Mounting Plate
Subject to change without notice. 120.9-IM (1218)
11
Page 12
Installation, Operation and Maintenance Manual
For best results in mounting of the wall controller, obtain an single position Receptacle/Switch Electrical Box which typically measures approximately 3.75” high x 2.25” wide x 2.83” deep. Install the box sideways (90 degrees) internal to the wall
from the original upright position. The box may be installed on metal or wood studded framing. Route the eld provided
connecting cable to the box.
1. Remove the Faceplate “A” from the Wall Controller.
2. Using a small straight screw driver, remove the two screws which secure the Wall Controller “B” to the Mounting
Plate “C”.
3. Route the connector/cable through the back of the Mounting Plate “C” then screw the mounting plate to the electrical box.
4. Plug the eld provided Connecting Cable to the Wall Controller “B” then reinstall the Wall Controller “B” back onto
the Mounting Plate “C”.
5. Connect the eld supplied standard phone cable into the coupler at the Main Board end.
Subject to change without notice. 120.9-IM (1218)
12
Page 13
Installation, Operation and Maintenance Manual
CONNECTING CABLE
The Marvel Terminal (Wall Control) connects to the Marvel Main Board using a factory provided 100-foot phone cable. Install the factory supplied 6-conductor cable from the Marvel Main Board located inside the control box to the location the Marvel Terminal shall be installed.
CAUTION: The factory provided is a special cable. If longer or shorter cable is desired, please contact the local Distributor for a longer/shorter length making sure to provide the desired length. NEVER ATTEMPT TO LENGTHEN THE FACTORY SUPPLIED CABLE as this cable specic pin connections. The Marvel Terminal will not work if the pin terminations are not correct and may damage the Marvel Main Board or blow the fuse due to improper connections.
SENSOR INSTALLATION AND ELECTRICAL TERMINATIONS
ELECTRICAL CONNECTIONS
All electrical wiring must be in accordance with NEC (National Electrical Code)/NFPA (National Fire Protection Agency), as well as state and, local building codes. Refer to
the specications section or the unit’s data tag for the unit’s
power requirements.
SERVICE DISCONNECT
A eld installed fused single point power service disconnect
is required. Install the service disconnect in accordance with NEC, State, and Local building codes. NEC guidelines require the unit’s disconnect be installed within sight of the unit.
A factory provided power block is installed internal to the unit’s electrical control panel. Route the main power wires
in accordance with electrical codes to the eld provided unit
service disconnect and terminate them on the line side of the disconnect. Route the power wires from the Load side
of the eld provided service disconnect to unit power block
inside the electrical control panel.
A ground termination point is located within the unit’s electrical control panel. All units must have a hard wired ground from a source Earth Ground.
IMPORTANT: Metal Conduit is not an acceptable source
of ground as there may be air gaps between connection points.
SENSOR FIELD MOUNTING & WIRING
All sensors and optional components that must be eld
installed and wired to the electrical control panel must be wired as shown on the electrical diagram provided with the unit. The installation instructions correspond with the
electrical diagram for the eld installable components.
For special order options which are not listed within these sensor installation instructions, please refer to unit’s factory provided electrical diagram and the installation instructions provided with each component for proper installation requirements.
Static Pressure Transducer (Duct Mount)
Mounting
The static pressure transducer shown in Figure 8 – Pressure Transducer must be installed in the main supply air ducting at a location approximately two-thirds of the distance down the straightest duct run from the supply air outlet of the unit.
The location must be a non-turbulent area of supply air ow.
Mount the pressure transducer as follows:
1. Remove the pressure transducer’s cover plate screws using a Phillips head screw driver.
2. Select the mounting location. Install the sensor at the approximate mid-point/center of the vertical plane of the ducting.
3. The sensor must be mounted vertically with the electrical entrance/strain relief facing downward.
4. Drill a ½” hole through the face of the duct.
5. Before installing the duct pressure transducer, make
sure the gasket at the base where the duct probe meets the transducer housing is intact and sealed to the sensor (so that it will seal the perimeter of the hole drilled).
6. Insert the probe into the duct and mount the pressure
transducer using two (2) eld provided #8 sheet metal
screws.
Wiring
Using a minimum 18-20 AWG 300 volt rated two conductor shielded cable with drain wire make the following electrical connections.
Subject to change without notice. 120.9-IM (1218)
13
Page 14
Installation, Operation and Maintenance Manual
IMPORTANT: Please observe polarity of this sensor. The “+”
is +24 vdc and the “–“ is the output (4-20 mA) to the Analog Input of the controller.
7. Connect from the positive terminal “+” inside the
pressure transducer to the unit’s electrical terminal block TB-DMPT +.
FIGURE 8 – PRESSURE TRANSDUCER
8. Connect from the negative terminal “–” inside the pressure transducer to the unit’s electrical terminal block TB-DMPT –.
9. Connect the drain wire to ground at the unit end only.
The factory provided static pressure transducer is preset for application requirements. The unit’s controller will read
the preset conguration. If a higher or lower pressure conguration is required, use the manufacturer’s provided literature to re-congure the sensor to read the desired
lower or higher pressure setting.
NOTE: When changing the conguration of the pressure
transducer, the range for the sensor must also be changed within the unit’s controller/sensor setup area. Refer to the Marvel Controller’s Technician’s Menu – Sensor Setup area for setting up the range of the sensor.
Duct Mount Supply Air Temperature Sensor
The duct mount supply air temperature sensor(s) shown
in Figure 9 – Supply Air Sensor must be eld installed in
the supply air ducting. The location of the sensor must be relatively close to the duct pressure transducer and must
not impede with airow to the inlet of the transducer. A few
feet (2/3 feet) from the transducer is recommended.
Mounting
1. Cut out the mounting template provided with the sensor.
2. Select the location to mount the sensor and drill a hole through the supply air duct at least ¾” in diameter.
3. Using a 7/64” drill-bit, drill the three fastening screw holes located on the template for the fastening ring.
4. Remove the duct sensor’s mounting ring from the duct probe being careful not to lose the sealing gasket.
5. Position the mounting ring over the ¾” hole drilled in step 2.
6. Use three (3) eld provided #6 x ¾” Pan Head sheet
metal screws and fasten bracket to the duct.
7. Place the probe through the mounting bracket and into the supply air duct.
8. Using the screw provided with the sensor installation kit, place the screw into the clamping ring and tighten the ring to secure the sensor to the clamping ring.
Subject to change without notice. 120.9-IM (1218)
14
Page 15
Installation, Operation and Maintenance Manual
FIGURE 9 – SUPPLY AIR SENSOR
Wiring
Figure 10 – Supply Air Sensor Wiring shows how the sensor is wired. Using a minimum 18-20 AWG 300 volt rated two conductor shielded cable with drain wire make the following electrical connections. The supply air temperature sensor is non-polarity observant.
1. Connect from one NTC terminal inside the supply air temperature sensor to terminal block TB-SATS – NTC inside the unit’s electrical control box.
2. Connect the other NTC terminal inside the supply air temperature sensor to terminal block TB-SATS – NTC inside the unit’s electrical control box.
3. Connect the drain wire to ground inside the unit’s electrical control box.
FIGURE 10 – SUPPLY AIR SENSOR WIRING
Duct Mount Return Air Temperature Sensor (Optional Humidity)
The return air temperature sensor shown in Figure 11 –
Return Air Sensor must be eld installed in the return air
ducting close to the unit. The return air sensor must be located relatively close to the Filter Rack of the unit.
IMPORTANT: If the unit has optional humidity control, please observe when making electrical connections.
Mounting
1. Cut out the mounting template provided with the sensor.
2. Select the location to mount the sensor and drill a hole through the supply air duct at least ¾” in diameter.
3. Using a 7/64” drill bit; drill the three fastening screw holes located on the template for the fastening ring.
4. Remove the duct sensor’s mounting ring from the duct probe being careful not to lose the sealing gasket.
5. Position the mounting ring over the ¾” hole drilled in step 2.
6. Use three (3) eld provided #6 x ¾” Pan Head sheet
metal screws and fasten bracket to the duct.
7. Place the probe through the mounting bracket and into the supply air duct.
8. Using the screw provided with the sensor installation kit, tighten the clamping ring.
Subject to change without notice. 120.9-IM (1218)
15
Page 16
NOTES: 1. Return Temp & RH Sensor is Factory Provided &
Field Installed.
FIGURE 11 – RETURN AIR SENSOR
Wiring
Figure 12 – Return Air Temperature/Humidity Sensor Wiring shows how the sensor is wired. Using a minimum 18-20 AWG 300 volt rated two conductor shielded cable with drain wire make the following electrical connections.
NOTE: Use a minimum two conductor cable for temperature
only. Use a minimum ve conductor for temperature
and humidity control.
1. The return air temperature sensor is non-polarity
observant.
2. Connect from one NTC terminal inside the return air temperature sensor to TB – RATS - NTC.
3. Connect the other NTC terminal inside the temperature sensor to TB – RATS - NTC.
4. Connect the drain wire to ground at the unit’s electrical control panel end only.
Installation, Operation and Maintenance Manual
FIGURE 11.5 – CONNECTING THE TERMINAL
Optional Humidity Control
If the sensor for Return Air has the optional humidity sensor, continue with steps 7, 8, and 9.
7. Connect from the terminal marked G+ inside the sensor to terminal TB-RATHS – G+ inside the unit’s electrical box.
8. Connect from the terminal marked M inside the sensor to terminal TB-RATHS – M inside the unit’s electrical control box.
9. Connect from the terminal marked Hout inside the sensor to terminal TB-RATHS – Hout inside the unit’s electrical control box.
c.pCOmini
Use the accessory cable P/N S90CONN0S0, connected
as shown in the gure. The maximum distance allowed
between controller and terminal is 10 m.
Subject to change without notice. 120.9-IM (1218)
FIGURE 12 – REUTRN AIR TEMPERATURE/HUMIDITY
SENSOR WIRING
(Example shown with TB-RATHS humidity connections option)
16
Page 17
Installation, Operation and Maintenance Manual
Room/Space Wall Mount Temperature and Optional Humidity Sensor
The room temperature with humidity sensor option must be
eld installed in the room being conditioned. Never install the sensor at a location that can be inuence by solar gain
such as sunlight or by drafts such as doors opening/closing or direct movement of conditioned air such as from supply air outlet grills. The location of this sensor should be reading mixed air, which means the best location should be close to a return air grille. The installation height should be between
40” to 60” above the room’s oor.
BE AWARE: If the unit has optional humidity control, polarity
must be observed when making electrical connections.
NOTE: Use a minimum two-conductor cable for temperature
only. Use a minimum ve conductor for temperature
and humidity control. It may be required to preinstall this wire (addition of drywall, paneling, ceilings, etc.) if the interior room shall be completed before this sensor will be installed. If the interior is complete, install the cable as required being careful not to damage the cable during installation.
Mounting
1. Cut out the mounting template provided with the sensor.
2. Select the location to mount the sensor and drill the appropriate size holes (for the factory supplied wall anchors) into the surface the sensor is being installed on.
3. Install the wall anchors as required for installation of the sensor.
4. Drill a through hole approximately 3/8” to 1/2” in diameter for the cable as required.
5. Place the cable through the back of the sensor.
6. Using the screws provided, screw the sensor to the
wall.
Wiring
Figure 13 – Room Temperature Humidity Sensor Wiring shows the electrical connections for the sensor. Using a minimum 18-20 AWG 300 volt rated two conductor shielded cable with drain wire make, the following electrical connections.
NOTE: Use a minimum two-conductor cable for temperature
only. Use a minimum ve conductor for temperature
and humidity control.
1. The room air temperature sensor is non-polarity
observant.
Room/Space Wall Mount Temperature Sensor Only
2. Connect from one NTC terminal inside the room air temperature sensor to TB-RTS – NTC (room temperature only)
3. Connect the other NTC terminal inside the room air temperature sensor to TB-RTS – NTC (room temperature only).
Or
Room/Space Wall Mount Temperature / Humidity Sensor
4. Connect from one NTC terminal inside the room temperature/humidity sensor to TB-RTHS – NTC (room temperature and humidity sensor)
5. Connect the other NTC terminal inside the room temperature/humidity sensor to TB-RTHS – NTC (room temperature and humidity sensor).
6. Connect the drain wire to ground at the unit’s electrical control panel end only.
Optional Humidity Control
If the Room Temperature and Humidity Sensor for Room Air has the optional humidity sensor, continue with steps 7, 8, and 9.
7. Connect from the terminal marked G+ inside the sensor to terminal TB-RTHS – G+ inside the unit’s electrical box.
8. Connect from the terminal marked M inside the sensor to terminal TB-RTHS – M inside the unit’s electrical control box.
9. Connect from the terminal marked Hout inside the sensor to terminal TB-RTHS – Hout inside the unit’s electrical control box.
Subject to change without notice. 120.9-IM (1218)
17
Page 18
Installation, Operation and Maintenance Manual
FIGURE 13 – ROOM TEMPERATURE HUMIDITY SENSOR WIRING
(Example shown with TB-RTHS humidity connections option)
Duct Mount Outdoor Air Temperature Sensor
The duct mount outdoor air temperature sensor shown in Figure 14 – Outdoor Air Temperature / Humidity Sensor
must be eld installed in the outdoor air ducting close to an
outdoor air louver but back inside of the ducting far enough that it does not rain onto the sensor. It should also be located before the outdoor air inlet damper in order to always monitor the outdoor air temperature and humidity correctly unless the unit will always be providing a minimal amount of outdoor air when occupied (in this case the sensor could be located between the outdoor air louver and the unit).
IMPORTANT: If the unit has humidity control for airside economizer, polarity must be observed when making electrical connections.
1. Cut out the mounting template provided with the sensor.
2. Select the location to mount the sensor and drill a hole through the supply air duct at least ¾” in diameter.
3. Using a 7/64” drill bit; drill the three fastening screw holes located on the template for the fastening ring.
4. Remove the duct sensor’s mounting ring from the duct probe being careful not to lose the sealing gasket.
5. Position the mounting ring over the ¾” hole drilled in step 2.
6. Use three #6 x ¾” Pan Head sheet metal screws and
fasten bracket to the duct.
7. Place the probe through the mounting bracket and into the supply air duct.
8. Using the screw provided with the sensor installation kit, tighten the clamping ring.
Subject to change without notice. 120.9-IM (1218)
18
Page 19
Installation, Operation and Maintenance Manual
FIGURE 14 – OUTDOOR AIR TEMPERATURE / HUMIDITY SENSOR
Wiring
Using a minimum 18-20 AWG 300 volt rated two conductor shielded cable with drain wire make the following electrical
connections. Use a minimum ve conductor for temperature
and humidity control. Refer to Figure 15 – Outdoor Temperature/Humidity Sensor Wiring.
1. The return air temperature sensor is non-polarity observant.
2. Connect from one NTC terminal inside the outdoor temperature/humidity sensor to TB-OTHS – NTC.
3. Connect the other NTC terminal inside the outdoor temperature/humidity sensor to TB-OTHS – NTC.
4. Connect the drain wire to ground at the unit’s electrical control panel end only.
5. Connect from the terminal marked G+ inside the outdoor temperature/humidity sensor to terminal TB­OTHS – G+ inside the unit’s electrical box.
6. Connect from the terminal marked M inside the outdoor temperature/humidity sensor to terminal TB­OTHS – M inside the unit’s electrical control box.
7. Connect from the terminal marked Hout inside the outdoor temperature/humidity sensor to terminal TB­OTHS – Hout inside the unit’s electrical control box.
FIGURE 15 – OUTDOOR TEMPERATURE/HUMIDITY
SENSOR WIRING
Subject to change without notice. 120.9-IM (1218)
19
Page 20
Installation, Operation and Maintenance Manual
Remote Alarm Output Option
On systems without BMS Communications, an option can be provided for Remote/Global Alarm Output, which closes a set of voltage free dry contacts on global alarm to terminals TB-RA – 1 and TB-RA – 2. With this option, look for terminal block TB-RA. The device must not exceed 10 amps at 240 VAC or 10 Amps at 24 VDC. Install two conductors 14 – 18 AWG 600 volt rated from the Remote Alarm device to the unit’s terminal blocks TB-RA. Whether connecting a buzzer or an indicator light, the device must have a separate power source. Determine which side of the device to disconnect (hot or common/neutral) through the factory provided dry contact terminal blocks and wire as follows:
Wiring the Remote/Global Alarm Output
1. Remove one wire from the Coil of the Alarm Device and wire nut or splice cap this wire with one of the two wires going to the Remote Alarm interlock wiring.
2. Connect the other wire of the Remote Alarm interlock wiring to the location of the wire removed from Remote Alarm device.
3. At the unit, connect one wire to terminal TB-RA – 1.
4. Connect the other wire to TB-RA – 2.
3. At the unit, connect one of the wires to TB-WP – 1.
4. Connect the other wire to TB-WP – 2.
Optional Airside Economizer Damper Control
If the customer’s system has optional Airside Economizer Dampers that must be modulated for free cooling, the terminal blocks for interlocking this function are TB-ASE – 1, TB-ASE – 2, and TB-ASE – 3. Install three conductors 16 – 18 AWG minimum 300 volt rated from the Airside Economizer Damper Actuators’ location to the unit’s terminal blocks TB-OAD.
Connect the wires as follows:
Wiring of the Airside Economizer Damper Actuators
1. Connect the Common wire at the Damper Actuator to terminal TB-ASE – 1 inside the unit’s electrical box.
2. Connect the 24 vac wire at the Damper Actuator to terminal TB-ASE – 2 inside the unit’s electrical box.
3. Connect the 0-10 vdc wire at the Damper Actuator to terminal TB-ASE – 3 inside the unit’s electrical box.
Remote Water Pump ON/OFF Option
If the customer’s system has an ON/OFF Water Pump that must be commanded on when there is a call for cooling, and the unit has the optional Remote Water Pump ON/ OFF terminal blocks, the terminal blocks for interlocking this function are TB-RWP – 1 and TB-RWP – 2. Determine whether the Hot or Common/Neutral shall be wire through the contacts for Remote Water Pump interlock. Next, install two conductors 14 – 18 AWG 600 volt rated from the Remote Water Pump’s Contactor/Starter location to the unit’s terminal blocks TB-RWP. Connect the wires as follows:
Wiring at the Pumps Contactor/Starter
1. Remove one wire from the Coil of the Water Pump’s Contactor/Starter and wire nut or splice cap this wire with one of the two wires going to the Remote Water Pump interlock wiring.
2. Connect the other wire of the Remote Water Pump interlock wiring to the location of the wire removed from the Contactor/Starter Coil.
Optional Outdoor Air Damper Control
If the customer’s system has an Outdoor/Fresh Air Damper that must be opened or closed by the unit during system start and occupancy schedule, the terminal blocks for interlocking this function are TB-OAD – 1 and TB-OAD –
2. Determine whether the Hot or Common/Neutral shall be wired through the contacts for Outdoor Air Damper interlock. Next, install two conductors 16 – 18 AWG minimum 300 volt rated from the Outdoor Air Damper Actuator’s location to the unit’s terminal blocks TB-OAD. Connect the wires as follows:
Wiring at the Outdoor Air Damper
1. Connect the Common wire at the Damper Actuator to terminal TB-OAD – 1 inside the unit’s electrical box.
2. Connect the 24 vac wire at the Damper Actuator to terminal TB-OAD – 2 inside the unit’s electrical box.
Optional Smoke Detector
If the factory ordered smoke detector option is provided, four terminations shall be required. Follow the installation/
Subject to change without notice. 120.9-IM (1218)
20
Page 21
Installation, Operation and Maintenance Manual
mounting instructions provided with the device. Install a four conductor cable minimum 18 AWG 300 volt rated from the smoke detector to the terminal blocks labeled TB-SD provided inside the unit.
Wiring
1. Terminate from the device terminal number 9 to the factory provided terminal TB-SD – 9.
2. Terminate from the device terminal number 10 to the factory provided terminal TB-SD – 10.
3. Terminate from the device terminal number 6 to the factory provided terminal TB-SD – 6.
4. Terminate from the device terminal number 16 to the factory provided terminal TB-SD – 16.
On units with both a supply and return smoke detectors, these terminals shall have terminal designations of TB-SSD for Supply Smoke Detector and TB-RSD for Return Smoke Detector instead of TB-SD. The terminal number pattern is the same. Terminal 9 inside the Smoke Detectors terminate to terminal 9, 10 inside the smoke detector terminates to 10 inside the unit and so on. The only difference is the location of the smoke detectors (supply or return air streams). Please remember to account for this during installation.
Optional Fire Stat Terminations
For a Field Supplied Fire Stat, two terminations shall be required. Follow the installation/mounting instructions provided with the device. Install a two-conductor cable minimum 18 AWG 300 volt rated from the smoke detector/
re stat to the terminal blocks provided inside the unit.
Wiring
1. Locate the Normally Closed dry contact terminations, which open on alarm, inside of the Firestat.
2. Terminate from one of the terminals inside of the Fire Stat to the factory provided terminal TB-FS – 1.
3. Terminate from the other terminal inside of the Fire Stat to the factory provided terminal TB-FS – 2.
Optional Remote On/Off Control
With the optional Remote On/Off Control, the unit will start when a voltage free dry contact closure is provided to Terminals TB-RMTO – 1 and TB-RMTO – 2. This closure should be provided by a dry contact closure switch installed at a remote location. Install two conductors minimum 18 AWG 300 volt rated from the Remote ON/OFF Switch
location to the unit’s terminal blocks TB-RMTO. Connect the wires as follows:
Wiring
1. Connect one wire at the Remote ON/OFF switch to one termination pole of the switch.
2. Connect the other wire of the Remote ON/OFF switch to the other termination pole of the switch.
3. At the unit, connect one of the wires to TB-RMTO – 1.
4. Connect the other wire to TB-RMTO – 2.
MARVEL MULTIAPP CONTROLLER – SEQUENCE OF OPERATION
Outdoor Air Damper (option)
On units without the Airside Economizer option, the system has an option for a Fresh Air Damper Output. If the Fresh Air Damper Output is enabled and the system is in the Occupied Mode, the output will open the outdoor air damper once the System ON/OFF is set to the ON position. After the initial
startup delay of 5 seconds (default and eld adjustable),
the output for the fresh air damper will supply a dry contact closure to start the Fresh Air Damper. This option allows the damper to drive open based on two methods.
1. Outdoor Air Damper Time Delay – Allows the Outdoor Air Damper to drive open for the adjustable damper time delay before starting the Supply Air Blower.
2. Outdoor Air Damper End Switch – Allows the Outdoor Air Damper to drive open but will not start the unit’s Supply Air Blower(s) until the Outdoor Air Damper End Switch provides contact closure back to the Marvel Multi-Application controller verifying that the Outdoor Damper is open.
Outdoor Air Damper End Switch (option)
On units with the optional Outdoor Air Damper End Switch enabled, the Marvel Multi-Application Controller will not start the Supply Air Blower until there is contact closure on the Outdoor Air Damper End Switch proving that the Outdoor Air Damper is open. If the controller does not receive proof that the outdoor air damper is open within the
specied adjustable time delay, the Marvel Multi-Application
controller will provide and Alarm to alert personnel that the Outdoor Air Damper failed to open.
Subject to change without notice. 120.9-IM (1218)
21
Page 22
Installation, Operation and Maintenance Manual
Supply Air Blower
Once the Outdoor Air Damper is open either by time delay timeout or by proof of the damper end switch contact closure, the controllers blower output for the Supply Air Blower energize the blower contactor for the Supply Air Blower Motor. During the Occupied Mode, the blower will operate continuously unless the system is set to operate based on
system demands (Cooling, Heating, Dehumidication, or Humidication). The unit controller has a selection to set
the blower(s) to operate solely based on System Demands
(Cooling, Heating, Dehumidication, or Humidication) only
on units with Constant Air Volume and non-Outdoor Air systems.
Supply Air Blower – Variable Air Volume (option)
Once the Outdoor Air Damper is open either by time delay timeout or by proof of the damper end switch contact closure, the output for the Supply Air Blower is energized to the Variable Frequency Drive (VFD). The supply air blower will provide a percentage of air volume based on change in duct pressure. As the duct static pressure falls due to VAV boxes connected to tenant occupied spaces opening for their requirement to provide conditioned air, the controller will increase the output demand to the VFD causing the Supply Air Blower(s) to speed up thus providing
an increase in airow. As tenant occupied VAV boxes close
requiring less conditioned air, the duct static pressure starts to increase causing the controller to decrease the output demand to the VFD which slows down the speed supply air blower(s).
Upon startup of the Supply Air Blower the blower(s)
will ramp to the Minimum Speed (eld adjustable set to
18 Hertz default) set into the Marvel Multi-Application controller provided for the VFD. After a Sixty (60) second
eld adjustable time delay the VFD starts to follow the
static pressure demand to increase (increase on startup) or decrease based on the Static Pressure Set Point 1.00
inches of water column (iwc) (default but eld adjustable).
As the Duct Static Pressure increases or decreases above or below the Duct Pressure Set Point ± the Duct Pressure
Proportional Band Set Point 0.2 iwc (default but eld
adjustable) the controller starts to increase or decrease the output demand to the VFD causing the blower to speed up or slow down. If the Duct Pressure is within the Duct Pressure Dead Band Set Point range Duct Pressure Set Point and Duct Pressure Dead Band Set Point ±0.15 iwc
there is no output adjustment the VFD so the blower speed will remain constant.
On units with Electronically Commutated Blower Motors, the output adjustment is the same only without the VFD interface since Electronically Commutated Motors have motor speed control built directly into the housing of the motor. Duct pressure is maintained by regulating the speed of a supply air blower by increasing or decreasing the demand to the Electronically Commutated “EC” Motor to increase or decrease the blower speed.
Room Pressure Control (option)
Typical applications for this type of control are Clean Rooms and Isolation Rooms. Room Pressure Control is an option designed to maintain the air pressure within a room at a Room Pressure Set Point. This option requires
a factory provided wall mountable, eld installed, pressure
transducer to monitor air pressure within the room being controlled against any adjoining room(s). The room pressure is then maintained as close to the pressure set
point as possible using factory or eld provided damper and
damper actuators.
When the Room Pressure rises above the Room Pressure Set Point plus Room Pressure Band Set Point, the controller will
modulate eld provided-eld installed damper(s) actuator(s)
closed until the Room Pressure Set Point is achieved. If the Room Pressure falls below the Room Pressure Set Point, the controller will modulate the damper(s) actuator(s) open to increase the room pressure until the room pressure set point is achieved.
Airside Economizer Mode (option)
Airside Economizer is an optional feature for free cooling
that requires a factory-provided duct mount type, eld-
installed, Outdoor Air Temperature and Humidity sensor, a factory provided wall or duct mountable Return Air Temperature and Humidity sensor, and a factory supplied duct mount Supply Air or Mixed Air Temperature sensor. With the Airside Economizer Option, there is a minimum damper position set point to maintain a minimum amount of fresh outdoor air based on regional code requirements. Also with the Airside Economizer Option, there is a maximum damper position set point to maintain a maximum amount of
outdoor air based on maximum outdoor air and airow limits
required. The minimum and maximum outdoor air damper
set points are eld adjustable under the Technician Menu -
Economizer Setup.
Subject to change without notice. 120.9-IM (1218)
22
Page 23
Installation, Operation and Maintenance Manual
If the Cooling Demand rises above minimum damper position set point, and the Outdoor Air Enthalpy is less than the Return Air Enthalpy, and the Outdoor Air Temperature is below the Outdoor Air Temperature Set Point minus the Outdoor Air Temperature Band Set Point, the unit will perform Airside Economizer mode of operation. The amount of demand for Airside Economizer can be viewed by looking at the System Demands screen for Air Side Economizer x%. When operating in airside economizer mode, the outdoor air dampers are modulated to the position that the Economizer demand is calling for. If the outdoor air temperature is less than the Mixed/Supply Air Temperature Set point, the system will regulate the Outdoor and Return Air Dampers to maintain the Mixed Air/Supply Air Temperature Set point.
Waterside Economizer Mode (option)
Waterside Economizer Mode is an option available for a
more energy efcient method of cooling when customers
have cooling towers available that can periodically supply water at a temperature of 55.0°F or lower. The Waterside Economizer option requires a factory-provided, factory­installed, water temperature sensor to monitor the inlet water temperature to the unit. If the entering water temperature is below the Water Temperature Set Point minus the Water Temperature Band Set Point, the controller regulates the water valve position in an effort to maintain the cooling set point.
Waterside Economizer Mode will stop when the Cooling Demand is 0% or the entering water temperature rises above the Water Temperature Set Point plus the Water Temperature Band Set Point. When the Water Temperature rises above the Water Temperature Set Point plus the Water Temperature Band Set Point and there is still a demand for cooling, the unit will revert back to mechanical cooling with compressors to provide the required cooling to meet the cooling demand.
Waterside Economizer plus Mechanical Cooling Assist (option)
The Mechanical Cooling plus Waterside Economizer Assist option follows the same sequence of operation as the Waterside Economizer option. If the customer selects the Waterside Economizer plus Mechanical Cooling Assist Option, the water piping shall be piped internally so that mechanical cooling will be able to assist the waterside economizer operation. The controller shall be enabled for the mechanical cooling assist option. The Compressors
will be staged when the Waterside Economizer Demand is
equal to 100% for greater than the Economizer Assist (eld
adjustable) time delay. The amount of compressors shall be limited based on the water temperature.
Chilled Water Mode (option)
Should the system have the Chilled Water Mode option, the control valve for chilled water mode could be either ON/OFF or Modulating depending on customer preference at the time of order. If the Chilled Water Valve is ON/OFF (open/ close) type, the valve will energize/de-energize based on start and hysteresis points much like a compressor (refer to the next paragraph of Cooling Mode for example of “start and hysteresis points”). If the Cooling Demand is greater than the Chilled Water Valve Start Set Point plus the Chilled Water Valve Hysteresis Set Point, the valve will open completely. Should the Cooling Demand be less than the Chilled Water Start Set Point minus the Chilled Water Hysteresis Set Point, the valve will be closed. Should the Chilled Water Valve type be modulating, the valve is modulated open or closed based on the percentage of Cooling Demand so if the Cooling Demand is 60% of the 0 to 100% cooling demand cooling range, then the chilled water valve will be 60% open.
Cooling Mode by Return Air Temperature
Cooling by Return Air Temperature is based on the Cooling Demand. This Cooling Demand is calculated by the Return Air Temperature, Return Air Temperature Set point, and Return Air Temperature Band Set Point. If the Return Air Temperature is greater than or equal to the Return Air Temperature Set Point plus ½ of the Return Air Temperature Band Set Point, the Cooling Demand shall be 100%.
Compressors are then staged based on Compressor Start and End points. Each compressor starts when the Cooling Demand rises above its Start point. Each compressor stops when the Cooling Demand falls below the previous compressors start point. The Compressor Start and End points are based on the maximum number of compressors enabled.
Example: In a two-stage compressor system, the Start point for Compressor 1 is 33.3% and the End point is 0.0%. Compressor 1 energizes when the Cooling Demand rises above the Start point of 33.0% and stops at 0.0%. These Start and End points are determined by the program and
are not eld adjustable.
Subject to change without notice. 120.9-IM (1218)
23
Page 24
Installation, Operation and Maintenance Manual
Important: Cooling Start and End points also allow for a buffer around the Temperature Set Point to help prevent overshoot.
Cooling Mode by Supply Air Temperature
Cooling by Supply Air Temperature is based on the Cooling Demand. This Cooling Demand is calculated by the Supply Air Temperature, Supply Air Temperature Cool Set point, and Supply Air Temperature Band Set point. If the Supply Air Temperature is greater than or equal to the Supply Air Temperature Set point plus ½ of the Supply Air Temperature Band Set Point, the Cooling Demand shall be 100%. Compressors are then staged upon Compressor Start and End points. Each compressor starts when the Cooling Demand rises above its start point. Each compressor stops when the Cooling Demand falls below the previous compressors start point. The Start and End points are calculated based on the maximum number of compressors.
Example: Compressor Start and End points are calculated
by the controller as previously stated and are not eld
adjustable.
Important: Cooling Start and End points also allow for a buffer around the Temperature Set Point to help prevent overshoot.
Heating Mode by Return Air Temperature
Heating by Return Air Temperature is based on the Heating Demand. This Heating Demand is calculated by the Return Air Temperature; Return Air Temperature Set point and Return Air Temperature Band Set point. If the Return Air Temperature is less than or equal to the Return Air Temperature Set point minus ½ of the Return Air Temperature Band Set Point, the Heating Demand shall be 100%.
Heaters are then staged based on Heater Start and Hysteresis Set points. Each heater starts when the Heating Demand rises above its Start Set point plus the Hysteresis Set point. Each heater stops when the Heater Demand falls below its Start Set point minus the Hysteresis Set point. The Start and Hysteresis Set points are based on the maximum number of heaters enabled.
Example: In a two-stage heater system, the Start Set point for Heater 1 is 33.3% and the Hysteresis Set point is 33.0%. Heater 1 energizes when the Heating Demand rises above
66.3% and stops at 0.3%. These Start and Hysteresis Set points are adjustable but it is not recommended unless
consulting with United CoolAir’s support team rst.
Important: Heating Start and End points also allow for a buffer around the Temperature Set Point to help prevent overshoot.
Heating Mode by Supply Air Temperature
Heating by Supply Air Temperature is based on the Heating Demand. This Heating Demand is calculated by the Supply Air Temperature; Supply Air Temperature Heat Set point and Supply Air Temperature Band Set point. If the Supply Air Temperature is less than or equal to the Supply Air Temperature Set point minus ½ of the Supply Air Temperature Band Set Point, the Heating Demand shall be 100%. Heaters are then staged upon a start and hysteresis set point. Each heater starts when the Heating Demand rises above its start set point plus its hysteresis set point. Each heater stops when the Heating Demand falls below its start set point minus its hysteresis set point. The Start and Hysteresis set points are based on the maximum number of heaters.
Example: In a two heater system, the Start Set point for Heater 1 is 33.3% and the Hysteresis Set point is 33.0%. Heater 1 energizes when the Heating Demand rises above
66.3% and stops at 0.3%. These Start and Hysteresis Set
points are adjustable but it is not recommended unless
consulting with United CoolAir’s support team rst.
Important: Heating Start and End points also allow for a buffer around the Set Point to help prevent overshoot.
Modulating Heat by Return Air Temperature
Modulating Heat by Return Air Temperature is based on the Heating Demand. This Heating Demand is calculated by the Return Air Temperature; Return Air Temperature Set point and Return Air Temperature Band Set Point. If the Return Air Temperature is less than or equal to the Return Air Temperature Set Point minus ½ of the Return Air Temperature Band Set Point, the Heating Demand shall be 100%.
The amount of modulating heat applied parallels the Heating Demand. A total of 50% Heating Demand equals 5.0 vdc on the analog output controlling the Modulated Heating device.
Important: Heating Start and End points also allow for a buffer around the Set Point helping to prevent overshoot. These Start and Hysteresis Set points are adjustable but it is not recommended unless consulting with United CoolAir’s
support team rst.
Subject to change without notice. 120.9-IM (1218)
24
Page 25
Installation, Operation and Maintenance Manual
Modulating Heat by Supply Air Temperature
Modulating Heat by Supply Air Temperature is based on the Heating Demand. This Heating Demand is calculated by the Supply Air Temperature; Supply Air Temperature Heat Set point and Supply Air Temperature Band Set Point. If the Supply Air Temperature is less than or equal to the Supply Air Temperature Set Point minus ½ of the Supply Air Temperature Band Set Point, the Heating Demand shall be 100%.
The amount of modulating heat applied parallels the Heating Demand. A total of 50% Heating Demand equals 5.0 vdc on the analog output controlling the Modulated Heating device. Modulating Heater outputs are only 0 to 10 vdc type.
Important: Heating Start and End points also allow for a buffer around the Set Point helping to prevent overshoot. These Start and Hysteresis Set points are adjustable but it is not recommended unless consulting with United CoolAir’s
support team rst.
Heat Pump – Option
For systems with the Heat Pump option, Heat Pump mode is available for heating if the heat rejection type (air cooled or water cooled) temperature is above the Low Temperature Lockout Set Point (applies to both air and water cooled systems). United CoolAir strongly recommends Auxiliary Heaters for those systems located within geographical regions with inclement climates that heat pump mode will not always be available due to low ambient conditions. As a standard, the heat pump mode of operation shall operate down to low ambient lockout temperature. Once the Outdoor Temperature or Water Temperature is below the Low Temperature Lockout Set Point, the heat pump mode will be locked out from operation until the temperature rises back above the Low Temperature Lockout Temperature Set Point plus the Low Temperature Lockout Temperature Band Set Point.
Heat Pump Option with Supplemental Heating (option)
If the Heat Pump option was ordered with the Supplemental Heating Option, if the heat pump mode of operation is locked out due to the Temperature of the Outdoor Air or Water being colder than the Low Temperature Lockout Set Point, the Supplemental Heaters are Staged or Modulated to maintain the demand for Heating. As the Temperature of
the Outdoor Air or Water rises above the Low Temperature Lockout Set Point plus the Low Temperature Lockout Band Set Point, the Supplemental Heaters are staged off or modulated down to allow the Heat Pump Mode to restart.
Defrost Cycle
Heat Pump systems have a defrost cycle that performs defrost mode based on a temperature switches connected to the refrigerant lines of the outdoor coil of each compressor circuit. Should one of these switches close due to the temperature of the refrigerant line falling below the switches low temperature cutout set point, the compressors which are currently in operation will continue to remain on and the reversing valves will be energized to cycle cooling long enough to bring the temperature of the refrigerant line back above the Defrost Switches reset set point. Once the Defrost Switch(s) reset, the Reversing Valves are then de­energized placing the system back into heat pump mode of operation.
Should the system go into the defrost cycle and supplemental heating is available, the supplemental heaters are brought on to maintain the heating requirement.
Modulating Hot Gas Bypass for Lightly Loaded Compressor Management (option)
Modulating Hot Gas Bypass for Lightly Loaded Compressor Management is an option used to false load the evaporator coil and compressor system during reduced loading conditions to the evaporator coil. Since the cooling demand
has not been completely satised the compressor will
continue to operate and the evaporator coil may start to freeze. The unit’s controller regulates the amount of hot gas applied to the evaporator coil to prevent the evaporator coil from freezing based on the cooling demand.
As the Cooling Demand increases, compressors are staged ON based on the percentage of demand for each Compressor as well as the overall Cooling Demand. As the Cooling Demand decreases to a point where the demand for cooling required is less than the hot gas bypass start set point, Hot Gas shall be modulated through the electrically modulated Hot Gas Bypass Valve into the Evaporator Coil. If the cooling demand should then rise above the hot gas bypass start point, the Modulating Hot Gas Bypass will modulate closed and if the demand becomes high enough, Compressor(s) 2 and/or 3 will stage on.
Subject to change without notice. 120.9-IM (1218)
25
Page 26
Installation, Operation and Maintenance Manual
Modulating Hot Gas Bypass by Supply Temperature (option)
Modulating Hot Gas Bypass for Supply Air Temperature control is an option used to control the Supply Air Temperature as close to the Supply Air Temperature set point as possible. This option requires a factory provided Supply Air Temperature Sensor and a factory provided Modulating Hot Gas Bypass Valve. The Cooling Demand will increase or decrease based on the Discharge Air Temperature Set Point and Discharge Air Temperature Band Set Point. The compressors are then staged up/down based on Cooling and Compressor Demands. As the Supply Air Temperature falls below the Supply Air Temperature Set Point, the controller will modulate the hot gas bypass valve open to regulate the amount of hot gas to the evaporator coil in order to maintain the supply air temperature as close to the supply air temperature set point as possible.
If the Supply Air Temperature starts to increase, less hot gas will be required to maintain the Supply Air Temperature. At that point, the controller will modulate the hot gas valve closed as much as required to maintain the supply air temperature as close to the supply air temperature set point as possible. Likewise if the load in the space starts to decrease, the supply air temperature may start to decrease. At that point, the modulating hot gas valve will be modulated open again to maintain the supply air temperature at or as close to the supply air temperature set point as possible.
Dehumidication Mode (option)
If the Room/Return Air Humidity is above the Room/Return Humidity Set point plus ½ the Room/Return Air Humidity
Band Set point, the dehumidication demand will be 100%. The Demand for Dehumidication is placed into the Cooling
Demand in order to stage the compressors ON/OFF based on each Compressor’s Start and Hysteresis Set points.
Dehumidication plus Reheat Mode (option)
If the Room/Return Air Humidity is above the Room/ Return Humidity set point plus ½ the band set point,
the dehumidication demand will be 100% and the compressor(s) will energize for dehumidication.
If the Room/Return Air Temperature falls below the Room/ Return Air Temperature Set Point minus ½ the band set point
during dehumidication, the heating demand will become
100%. The compressor(s) will continue operating and reheat will stage on/off or modulate to satisfy the optional reheat function. The reheat type could be Hot Gas Reheat, Electric Reheat, or a Hot Water or Steam Coil.
Humidication (option)
Each system with the Humidication option will have a Modulating Humidier controlled through the controller via Modbus Communications. Humidication is based on the Humidication Demand. The Humidication Demand
is based on Room/Return Air Humidity, Room/Return Air Humidity Set Point, and Room/Return Air Humidity Band
Set point. The Humidication Demand shall be 100% when
the Room/Return Air Humidity is equal to or greater than the Room/Return Humidity Set point plus ½ of the Room/ Return Air Humidity Band Set Point.
Dedicated Outdoor Air System Control (option)
For the Dedicated Outdoor Air System Control to control the system correctly, the unit must be purchased as a DOAS system. This means the unit is designed with the coils and refrigeration system as well as a cabinet structure designed to handle 100% Outdoor Air. Even though the control software has the ability to operate the unit as a Dedicated Outdoor Air System if the unit is not designed for this, it will most likely not dehumidify and reheat to condition the outdoor air properly.
In order to understand the system’s dehumidication mode,
it is important to understand there are several factors
involved in the dehumidication process.
Dehumidication is based on the following set point values:
(a) Outdoor Dry Bulb Temperature
(b) Outdoor Wet Bulb Temperature
(c) Supply Air Dew Point Temperature
(d) Supply or Space Air Dry Bulb Temperature
Dehumidication mode is based on seasonal outdoor
air, dry bulb temperature and wet bulb temperature averages. The average seasonal temperatures vary
signicantly throughout different geographic regions. Since dehumidication is based upon these temperatures, it will
be important for United CoolAir to know the location where the unit will be installed because each controller is set up with the Outdoor Air Dry Bulb and Wet Bulb, Temperature Set Points for the particular region of installation.
Though these set points are preset, they are not xed set
points as they may be readjusted by service technicians under the technician’s menu. It is important to understand that changes to these set points may affect the performance of the system so minor adjustments at a time are strongly recommended. These set points are located under a
Subject to change without notice. 120.9-IM (1218)
26
Page 27
Installation, Operation and Maintenance Manual
password protected Technicians Menu to prevent easy access.
Once the outdoor air, dry bulb and wet bulb temperatures
are set, dehumidication will operate based on the supply
air dew point set point as selected by the customer. When the controller is set up for a Dedicated Outdoor Air System, the default Supply Air Dew Point Set Point is 55 degrees.
If the outdoor air dew point as calculated by the outdoor temperature and humidity sensor is greater than the supply air dew point set point, the Dedicated Outdoor Air System
controller setup shall enable dehumidication mode.
Compressors 1 and 2 are sequenced ON/OFF based on the settings previously described. Compressor 1 is always cycled ON if the Outdoor Air Dew Point is greater than the Supply Air Dew point Set point. Compressor 2 is cycled on based on a pre-calculated set point called an enthalpy set point. This set point is calculated by the outdoor air dry bulb and outdoor air wet bulb, temperature set points for the geographic location of installation. If the outdoor air enthalpy is lower than the enthalpy set point, the controller shall operate Compressor 1 only. If the outdoor air enthalpy is above the enthalpy set point, Compressor 2 is sequenced ON with a delay between the stages.
Modulating Hot Gas Reheat (Dedicated Outdoor Air System - option)
While the system is dehumidifying, since the leaving air temperature will be much colder leaving a Dedicated Outdoor Air System’s Evaporator Coil, Compressor 1 shall always have Hot Gas Reheat as a Standard. Compressor 1 and Modulating Hot Gas Reheat shall be used to temper the leaving air temperature back to either the Supply Air Temperature Set point or the Space Temperature Set point.
Cooling Assist (Dedicated Outdoor Air System - option)
The controller has the ability to provide primary cooling assistance utilizing Compressor 2. There are two key components required to provide primary cooling assistance with this dedicated outdoor air system.
(a) a) System has to be sized appropriately.
(b) b) Cooling Assist must be enabled.
When the system is set up for Cooing Assist, Compressor 1 will operate to provide cooling. If Compressor 1 cannot meet the demand for cooling and the Cooling Demand remains
equal to 100% for greater than 10 minutes, Compressor 2 shall be cycled on to provide Cooling Assistance. The Cooling Demand is calculated by the Space or Supply Temperature (based on system setup for control method by supply or return temperature); Space or Supply Temperature Set Point and Space or Supply Temperature Band Set Point. The Cooling Demand is equal to 100% when the Space or Supply Temperature is greater than or equal to the Space or Supply Temperature Set point plus ½ of the Space or Supply Temperature Band Set Point.
Unoccupied Mode
During Unoccupied Mode, all outputs are de-energized. The Supply Air Blower has an option to operate continuously during the unoccupied period. The system also has the capability for both a Night Set Up and a Night Set Back function to maintain minimum temperature and humidity settings during the unoccupied mode. These Temperature and Humidity Set Points are located under the Unoccupied Control menu. Temperature and/or Humidity Control are based on the options ordered with the equipment. For instance in order to maintain a Return Air Temperature Set Point of greater than 60 degrees Return Air Temperature, when the temperature falls below 60 degrees, the system will require some form of heating option.
Unoccupied Override
There are three methods of Unoccupied Override that may be utilized to override the Unoccupied Mode, temporarily starting the unit to continue the conditioning process. The methods for Unoccupied Override are initiated 1) by User Interface, 2) by Digital Input, or 3) by BMS point interlock. The system will accept all three methods for Unoccupied Override mode so if connected to either a digital input or a BMS system, Unoccupied Override can be initiated from any of the three methods.
Unoccupied Override by User Interface
The User Interface has an Unoccupied Override trigger built in on the last page of the main System Status screens. Simply press the Up Arrow button one time to get to this page quickly then enable the Override to the ON position. Set the Unoccupied Override timeout time for the system to go back into Unoccupied Mode. Press the Enter button to drop the cursor under the Override Time and change it to the desired Override Time by pressing the UP/DOWN buttons. Press the Enter button to initiate the time into memory. The
Subject to change without notice. 120.9-IM (1218)
27
Page 28
Installation, Operation and Maintenance Manual
cursor will now be at the Override ON/OFF point. Press the UP/DOWN buttons to set Override to ON and then press the Enter button. Unoccupied Override will start and follow the Override Timeout Time. To reset the Override Time, simply move the cursor back to the Override ON/OFF point
and set the eld to the Reset position and press enter which
will send the unit back into Unoccupied mode.
Unoccupied Override by Digital Input
(Requires available digital input and a voltage free dry
contact closure momentary push button)
A digital input can be set up to receive a momentary pushbutton contact closure to initiate the start period of the Unoccupied Override function. The Unoccupied Time period will follow the time that is set into the wall display just as it would by initiating it at the wall controller.
Unoccupied Override by BMS (Requires the BMS Communications option)
A BMS Point is available and requires the BMS Option to initiate the Unoccupied Override function. The time period for Unoccupied Override mode is also adjustable through BMS. Simply set the unoccupied override time period in minutes. Then Enable/Disable the Unoccupied Override point to start the Unoccupied Override process. If terminating Unoccupied Override before time expiration is desired then a reset point is also available.
Morning Warm-Up
Morning Warm-Up is a function typically found in Variable Air Volume applications. There are numerous methods of enabling the Morning Warm-Up function. The three basic methods available through the controller are:
1. By Time
2. By BMS Communications (Building Management
System)
Morning Warm-Up by Time
When selected to Morning Warm-Up by Time, the Warm-Up Schedule is located and setup under the Schedule menu. The Morning Warm-Up Set Points are adjusted through the Set Points menu. Warm-Up should be scheduled to operate during the Unoccupied Mode just before the start of the occupied day. Morning Warm-Up shall start the heating cycle and heat until either the Return Air Temperature rises
above the Morning Warm-Up Set point or the Morning Warm-Up Time period expires. Once this occurs, the start of the occupied day becomes active.
Morning Warm-up by BMS (Requires BMS Communications option)
Should the controller have the BMS option, Morning Warm­Up by BMS can be enabled. Morning Warm-Up by BMS simply enables the Morning Warm-Up Mode when the BMS point for Morning Warm-Up is enabled ON. Once active, the Morning Warm-Up Mode will start the heating process based on the Morning Warm-Up Set points located under the Set Points menu. These set points are also adjustable via BMS points.
NOTE:
Control of Heaters
If the system has staged heaters, there will be a Morning Warm-Up ON Temperature Set point and a Morning Warm-Up OFF Temperature Set point. If the system has modulating type heaters, the amount of modulation is based the Morning Warm-Up Return Air Temperature Set point and Morning Warm-Up Return Air Temperature Band Set point.
Morning Cool-Down
Morning Cool-Down is a function typically found in Variable Air Volume applications. There are numerous methods of enabling the Morning Cool-Down function. The three basic methods available through the controller are:
1. By Time
2. By BMS Communications (Building Management
System)
Morning Cool-Down by Time
When selected to Morning Cool-Down by Time, the Cool­Down Schedule is located and setup under the Schedule menu. The Morning Cool-Down Set Points are adjusted through the Set Points menu. Cool-Down should be scheduled to operate during the Unoccupied Mode just before the start of the occupied day. Morning Cool-Down shall start the cooling cycle and cool until either the Return Air Temperature falls below the Morning Cool-Down Set point or the Morning Cool-Downtime period expires. Once this occurs, the start of the occupied day becomes active.
Subject to change without notice. 120.9-IM (1218)
28
Page 29
Installation, Operation and Maintenance Manual
Morning Cool-Down by BMS
(Requires BMS Communications option)
Should the controller have the BMS option, Morning Cool­Down by BMS can be enabled. Morning Cool-Down by BMS simply enables the Morning Cool-Down Mode when the BMS point for Morning Cool-Down is enabled ON. Once active, the Morning Cool-Down Mode will start the cooling process based on the Morning Cool-Down Set points located under the Set Points menu. These set points are also adjustable via BMS points.
NOTE:
Control of Compressors
If the system has staged compressors, there will be a Morning Cool-Down ON Temperature Set point and a Morning Cool-Down OFF Temperature Set point. If the system has modulating type compressors (Digital Scrolls or Variable Compressors), the amount of modulation is based the Morning Cool-Down Return Air Temperature Set point and Morning Cool-Down Return Air Temperature Band Set point.
Preheat Heater – Option
Preheat heating option is used to preheat the outdoor air before it enters the unit. Heaters for the Preheat Heaters can
be either factory or eld provided. Control of this function
requires a factory provided preheat temperature sensor to monitor the air temperature entering the return air inlet of the unit. The Preheat Heater supplies heat based on the Preheat Temperature, Preheat Temperature Set Point and Preheat Temperature Band Set Point. These set points are
eld adjustable but do have low and high limits.
Should the preheat heater be a Hot Water or Steam Coil and the temperature leaving the coil is lower than the Freeze Limit Set Point, output to the control valve will be
100% demand so that ow will remain at 100% to prevent
the system from freezing.
Remote Start/Stop
Remote Start/Stop is a standard feature with all units. The Remote Start/Stop feature allows customers to tie in a
eld provided external Voltage Free Dry Contact Switch to
Remotely Start and Stop the unit based on their own time of day schedule.
Global Alarm
As a standard, Interlock Terminal Blocks are provided for
eld connection to the Global Alarm dry contact closure
output. Should the unit go into an alarm condition on any of the following items listed below, a relay will be energized
to provide a dry contact closure to control a eld provided
alarm buzzer or indicator light to alert the customer of the alarm condition with the unit. The power required to drive
the eld provided device shall be 24VAC powering a device
of less than 3 amps maximum through the factory provided relay.
● Loss of Airow
● Drain Pan Overow
● Dirty Air Filter
● Heater High Limit
● Damper Failed to Open
● Fan Motor Overload
● High Duct Pressure
● Water Flow
● Fire/Smoke Detected
● Freeze Stat Alarm (with Freeze Stat
option)
● Preheat Coil Freeze Protection (with
Preheat Coil option)
● Compressor High and Low Pressure
● Sensor Failure
● Temperature High or Low Alarms
● Humidity High or Low Alarms
STANDARD SYSTEM SAFETIES
Proof of Airow (Air Flow Switch)
Each system has a switch to monitor for loss of airow. The
output for the Supply Air Blower must be energized for a
minimum 60 seconds (eld adjustable) before any modes of operation are enabled. Should the airow switch remain open after the time delay expires or the airow switch opens
while any system modes are in operation, the system shuts down the modes of operation and the supply air blower and
provides a loss of airow alarm.
Subject to change without notice. 120.9-IM (1218)
29
Page 30
Installation, Operation and Maintenance Manual
Fire/Smoke Detection
The Fire/Smoke Detection shut down is a factory standard feature (electrical termination points only). This Fire/Smoke
Detector can either be factory provided as an option or eld
provided. The electrical termination points require a voltage free (dry) normally closed (opens on alarm) contact which must be connected to the factory provided terminal blocks. If the Fire/Smoke Detector is factory provided, the detector
will be shipped loose for eld installation.
If the Fire Stat/Smoke Detector goes into alarm, the normally closed contact opens, all functions of the system will be shut down, and the controller will provide a Fire/Smoke Alarm. The system will reset based on the setup for reset of the Fire/Smoke Alarm. There are two types of reset for a Fire/ Smoke Alarm “Automatic or Manual”.
Automatic reset will automatically reset and restart the system without resetting the audible or visual alarm so the customer knows when the unit tripped on a Fire Stat/ Smoke Detector Alarm. Manual reset requires the customer to manually reset the Fire Stat/Smoke Alarm condition before the unit will restart the functions of the system. The default setup for Fire/Smoke Alarm is to lock the system out from operation requiring a manual reset/restart at the unit’s
Interface Controller. The eld has the ability to set the unit to
auto-reset/auto-restart once the Fire/Smoke Alarm resets.
Compressor High Pressure Switch
Each Compressor is protected with a high pressure cutout switch. The switch may vary in pressure range based on the type of refrigerant within the refrigerant circuit. For ON/ OFF Type Compressors, the high-pressure switch is wired in series with the digital output that controls the ON/OFF function of the corresponding compressor.
For instance Compressor 1 High Pressure switch connected to Digital Output 2 will start and stop Compressor 1 by whether the switch is open or closed. The High-pressure switch will open if the refrigerant pressure is greater than the refrigerant pressure set point. The open Compressor 1 High Pressure Switch will de-energize the relay that energizes and de-energizes the Compressor 1 Contactor. One contact energizes and de-energizes the compressor contactor and the other relay contact sends the alarm signal back to the controller to let the control know that Compressor 1 High Pressure switch tripped. The high-pressure switch will take
the compressor ofine as it is wired to the relay that controls
the contactor for the compressor but it will also allow the relay to provide the alarm signal.
Once the High Pressure Trip occurs, the compressor must be re-enabled under the System Enables menu in the controller.
NOTE: R410A Refrigerant Systems also require a manual
reset of the switch due to higher operating pressures within the system.
Compressor Low Pressure Switch
Each Compressor is protected by a Low Pressure cutout switch. The switch may vary in pressure range based on the type of refrigerant within the refrigerant circuit. Unlike the high-pressure switch, the low-pressure switch is connected directly to a digital input on the controller. Should the Low Pressure Switch open during a compressor run cycle, the corresponding compressor will trip on low-pressure safety. If this occurs, the controller will de-energize the corresponding digital output to the compressor contactor.
Once the Low Pressure Trip occurs, the compressor must be manually re-enabled under the System Enables menu in the controller. The low-pressure switches automatically reset once the pressure at switch rises above the switches reset point.
Heater High Temperature Cutout
Factory provided heating banks are supplied with a heater high temperature cutout switch that trips as the surrounding air temperature at the switch causes the temperature on the switch to rise above the cutout point. The switch is bimetallic auto reset type. Should the switch trip; an alarm will be displayed on the controller alerting the customer to Heater High Temperature Cutout. If a heater high temperature cutout occurs, the heaters automatically restart once the surrounding air temperature cools the surface of the switch enough to allow the switch to reset.
Sensor Failure
There are two methods for sensor failure. One method is when the reading is above or below minimum and maximum range of the sensor. With this method, the sensor should be displaying a value on the display of the controller. The other method is a mis-wired or sensor that simply was not
installed during installation. This method will display a ###.#
output for the failed sensor on the wall controller along with the label of the sensor.
High and Low Limit Alarms
Each controller has adjustability for High and Low set point
Subject to change without notice. 120.9-IM (1218)
30
Page 31
Installation, Operation and Maintenance Manual
alarms for the following sensors. The High and Low Limit Set Points are available under the Alarm Set Points menu. The sensors must be enabled for the High and Low Alarm Set Point display screens to appear. The following sensors have high and low alarm set point capability:
● Return Air Temperature
● Return Air Humidity
● Supply Air Temperature
● Duct Pressure
● Room Pressure
● Refrigerant Pressure
● Room Temperature
● Room Humidity
● Space Temperature
● Space Humidity
High Duct Pressure (VAV only)
On system with the VAV option, a factory provided high duct pressure switch will open when the duct pressure
rises above the eld adjustable trip point. If this occurs, all
modes of operation are de-energized and the supply air blower is de-energized. A manual reset of the High Duct Pressure Switch as well as a manual reset of the Alarm on the controller is required.
OPTIONAL SYSTEM SAFETIES
Outdoor Air Damper End Switch
If the eld provided Outdoor Air Damper Actuator has
a Damper End Switch, the Damper End Switch could be
connected to the unit’s controller for Alarm notication and
shut down if the outdoor air damper does not open. The
damper and damper actuator must be eld installed and
wired back to the optional factory terminal blocks for the Outdoor Damper End Switch option.
If the actuator fails to drive the damper open, an alarm
notication will alert the customer of the damper actuator
failure and the system is locked out from operation. There is a delay for the contact closure that should allow ample time for the actuator to drive completely open. This time delay has a factory default of 3 minutes. Please refer to the Factory Settings section for details on adjusting this time delay. Once the problem is corrected, the system must be manually reset through the controller’s user interface.
Drain Pan Overow Switch
The drain pan overow switch is an optional factory supplied component. The drain pan overow switch is water level
detection switch that opens when the water level is too high in the unit’s drain pan indicating that the condensate drain may be blocked. If there is a blockage in the condensate line, the rising water level in the condensate drain pan will open the drain pan switch creating an alarm at the controller. The
drain pan overow switch shuts down cooling preventing the condensate from overowing the drain pan. The alarm will notify the customer of the drain pan overow condition.
Once the blockage is removed from the condensate drain line, the system must be manually reset at the controller’s user interface.
Dirty Filter Switch
The dirty lter switch is an optional factory supplied component. When the air lter becomes dirty and should be replaced, the contacts on the lter switch will open causing
an alarm at the controller. The alarm will be in the form of a
notication recommending that the air lter be changed for
preventive maintenance. The system will continue to run in
its current mode of operation. The alarm notication can be
reset through the units user interface.
Freeze Stat (Compressor)
If the Compressor Freeze Stat option is ordered, the freeze stat switch is factory provided, factory installed and wired to the unit’s controller. If the temperature of the evaporator coil falls below the temperature set point of the freeze stat, the switch contacts open to the controller providing an alarm and the controller shuts down the cooling mode of operation.
The Freeze Stat switch automatically resets once the temperature of the evaporator coil rises above the reset temperature set point of the switch.
The system will reset based on the controller’s setup for reset of the Freeze Stat Alarm. The controller’s set-up for reset to the Freeze Stat Alarm is selectable for either automatic reset or manual reset. As a standard, cooling mode restarts to provide cooling. The controller will retain the alarm to alert the customer of the coil freezing condition and that the system should be checked by a technician to ensure proper operation of the cooling cycle.
Automatic reset will automatically reset and restart cooling mode without resetting the audible or visual alarm so the customer knows when the unit tripped on Freeze Stat. Cooling will automatically restart once the Temperature
Subject to change without notice. 120.9-IM (1218)
31
Page 32
on the Freezestat rises above the Freeze stat’s reset temperature setting. Manual reset requires the customer to manually reset the Freeze Stat Alarm condition before the unit will restart the functions of the system.
Freeze Stat (Hot Water/Steam Preheating Coil)
If the Hot Water/Steam Coil Freeze Stat option is ordered, the freeze stat switch is factory provided, factory installed and wired to the unit’s controller. If the temperature freeze stat falls below the Freeze Stat Set point, the Freeze Stat sends the system into a Freeze Protection Mode.
The output to the Hot Water/Steam Coil will drive the valve
completely open to send full ow through the coil to assist
with freeze protection. All of the system outputs will be de­energized to prevent operation of the system while preheat is not available and all modes of operation are shut down. A Freeze Protection Active alarm will appear on the display of the controller to alert the customer of the freeze condition and that the system requires service.
Installation, Operation and Maintenance Manual
Marvel
Controller by :
United CoolAir Corp.
Information at:
www.unitedcoolair.com
Controller Operation
Up Button
The button is used to scroll upward through status screens, menus, sub-menus and change the value of parameters or settings.
Water Flow Switch (option)
This option prevents compressors from operating on Water
Cooled units when there is no water ow. Factory provided dry contacts are provided for a eld provided eld installed water ow switch. If there is no water ow after the alarm time delay time out an alarm notication shall be provided and the compressors will remain off until water ow is restored. This is only a notication type alarm and the compressors will automatically restart once water ow is restored to the unit. The alarm notication can be reset at the controller or
by optional BMS.
Marvel Terminal Keypad and Display Operation
This section is provided as a guide to explain the functions of each of the display screens associated with the operation of the unit. Upon application of power, there will be two screens called splash screens identifying United CoolAir with a Logo (not pictured) then transferring it to the name of the controller being developed by United CoolAir Corporation as well as information for further reference.
Alarm Button (Alarms and Resetting)
When an Alarm occurs, an audible alarm buzzer will sound off to alert the customer of the alarm condition. The LED indicator inside the button will illuminate ashing on and off Red. Present Alarms are displayed in English text in order of occurrence. Press the button one time to display the present and most recent alarm condition. Press the button to display all remaining alarms that may be present. When the button is pressed one time, the audible alarm will silence. In an alarm condition, the appropriate system’s stage or mode of operation is shut down preventing the particular stage or mode from operation to protect it. Once repairs are made to the particular mode or stage, pressing the button and then pressing the button until the screen Press ALARM for 3 seconds appears and then physically pressing and holding the button will clear the alarm. The Red LED inside the button will disappear.
For example, if the low pressure switch for Compressor 1 opens due to a low refrigerant pressure condition, Compressor 1 Low Pressure will be displayed when the
button is pressed. Compressor 1 will be shut down and locked out from operation until repairs are made to Compressor 1’s refrigerant system.
Subject to change without notice. 120.9-IM (1218)
32
Page 33
DANGER: BEFORE ATTEMPTING TO TROUBLESHOOT A SYSTEM ALARM, BE AWARE THAT REFRIGERANT CONTAINED IN EACH COMPRESSOR SYSTEM AND HOT WATER OR STEAM FROM HEATING COILS CAN CAUSE SEVERE BURNS. HIGH VOLTAGE AND OPERATING FAN DRIVES ALSO PRESENT HAZARDOUS CONDITIONS. BE AWARE OF THE DANGERS AND CONTACT APPROPRIATE PERSONNEL OR CERTIFIED TECHNICIANS TO SERVICE THE EQUIPMENT.
Pressing the alarm button enters the Alarms menu. If there is an Alarm present, the displayed Alarm will look similar to this example showing time and date of occurrence. Press the
Installation, Operation and Maintenance Manual
Alarm Logger Record>01
15:35 04/05/17
Comp 2 Low Pressure
Alarms 0 1 / 0 1
15:35 04/05/17
Comp 1 Low Pressure
If there are no present alarms the NO ALARMS will be displayed. Pressing the enter button with No Alarms present will enter the Alarm Log. The alarm log simply is a record of the alarms that occurred. A total of 64 previous alarms will be stored into memory. If there are no alarm logs present, the system will not enter the Alarm Logger. Press the Esc button to return to the main status loop.
Changing Set Points, Parameters, And Values
Set points, Parameters, and changeable values are known as Fields. Press the enter button to move the cursor to
the eld for the desired change. Press the (up) or (down) button to change the value within that eld, and then
press the enter button to save the change into memory.
System Status
By default the system remains within the System Status menu loop if no one has accessed the unit for greater than ve (5) minutes. Simply pressing the (up) or (down) buttons, scrolls through the available screens within the System Status menu. Each screen in the Status menu displays the operating conditions or Status of the system. Listed below are the Screens that will appear under System Status for particular setups based on application setup and available options.
U01 Mon 07:21 03/19/17
Return Hum > 55.0%
NO ALARMS
Press ENTER to
enter ALARM LOGS
Subject to change without notice. 120.9-IM (1218)
Return Temp> 74.7 °F Supply Temp> 57.2 °F
One Compressor ON
33
Page 34
This is the home screen within the System Status. If no buttons are pressed within 5 minutes, the displayed screen will revert back to this displayed screen showing Day of the Week, Time of Day and Date. The main readings are also displayed here as well as operating status. The displayed readings may change based on system setup. For instance, if Space Temperature and Space Humidity are selected instead of Return Temperature and Return Humidity, then Space Hum and Space Temp will be displayed. If there are two supply temperature sensors installed, then Supply Temp Avg will be displayed on this page and both Supply Temperature 1 and Supply Temperature 2 will be displayed on another screen.
U01 Blower Status
Supply Blower>ON Start Delay >000sec Minimum Run >000sec Stop Delay >030sec Mode Start >060sec Damper Delay >000sec
This screen displays information about the blower status and all of the time delays for the blower, Fresh Air Damper and Mode Start Delay. The Damper Delay is the time it takes for a Fresh Air Damper to open and will only be displayed if the damper actuator does not have an End Switch for proof that the damper is open. The Mode Start must time out before any modes of operation will occur. The start delay and damper delay take precedence so once the system is on, the start delay must time out and then the damper output is energized. Once the output for the damper is on for the length of the damper delay, then the blower output is energized. Once the blower is on for the length of the mode start delay, then the mode of operation (cooling, heating,
humidication, or dehumidication) will start if required.
Installation, Operation and Maintenance Manual
U01 Air Economizer
Econ Demand > 037.9% Outdoor Temp> 45.7 °F Outdoor Hum > 48.2% Enthalpies: Outdoor>22.3btu/ lb Indoor >29.3btu/lb
Depending on the type of Air Economizer setup, the information displayed on this screen may appear like this or with less information. The output voltage to the actuators will be the air economizer demand divided by 10 so from the displayed value, the Analog Output voltage to the damper actuators will be 3.79 vdc. A damper minimum and maximum output can also be added under Economizer Setup within the Technician Menu which will be discussed later in this manual. When set up as Enthalpy Type, the Outdoor Air Enthalpy must be less than the Indoor Air Enthalpy and the Outdoor Air Temperature must be less than the Outdoor Temperature Set Point for Air Economizer for the system to go into air economizer mode of operation. The Econ Demand will match the Cooling Demand. If a Minimum Damper position set point is added, the dampers will always maintain that position when the system is on and in occupied or set back mode and they will be closed when the system is off or unoccupied.
U01 Cooling Status
Demand> 067.2% Compressor 1 >ON
Subject to change without notice. 120.9-IM (1218)
34
Page 35
Installation, Operation and Maintenance Manual
This screen shows the demand for Mechanical Cooling Compressors and total number of compressors in operation.
U01 Stage Start Delay
Compressor 1>000sec
This screen will only appear if the head pressure control water valve option is installed on water cooled units and if there is a Demand for cooling on the Cooling Status page otherwise this screen is hidden until there is again a demand for cooling.
U01 Minimum ON
Compressor 1>000sec
Any alarms that occur within compressor circuits will bypass the minimum on time(s) for the particular compressor with the alarm. This screen only appears if there is a Demand for cooling on the Cooling Status page otherwise this screen is hidden until there is again a demand for cooling.
U01 Minimum OFF
Compressor 1>000sec
The minimum off time is the amount of time before the particular compressor that has a time greater than zero can restart. This screen only appears if there is a Demand for cooling on the Cooling Status page or the Minimum OFF Delay of one of the compressors is greater than zero, otherwise this screen is hidden until there is again a demand for cooling.
This screen displays the minimum run time required for the compressor. The default is 120 seconds of Run Time. Once the time delay returns to 0 seconds, and if there is no requirement for each particular compressor to be on, the compressor will turn off. Should there be a requirement for the compressor to turn off due to the demand decreasing too rapidly, the compressor must remain on the minimum on time before it can turn off. Typically if something like this occurs where a compressor turns on and then immediately, there is no longer a demand for that particular compressor to run, it indicates that the Proportional Band of the Set Point should be adjusted to prevent short cycling of the compressor(s).
U01 Supply Blower
Press Demand> 79.2% Duct Press > 0.891iwc
This screen shows the status of the supply air blower and duct pressure on units with the Variable Air Volume option.
Subject to change without notice. 120.9-IM (1218)
35
Page 36
Installation, Operation and Maintenance Manual
U01 Liquid Pressure
Liquid Pres 1> 311psi
The Head Pressure/Liquid Pressure control screen shows the liquid pressure for the compressor stage with water cooled units having the Electronic Head Pressure Control option. The default Discharge Pressure Set Point is 325 psig.
U01 Analog Outputs
Mod Heating > 9.6v Air Econo > 0.0v
U01 Unoccupied Override
Duration>000090min Elapsed >000025min Override>On
The Unoccupied Override screen displays the following information and settings. Duration is the time in minutes for to unit to continue to run when it is supposed to be unoccupied. The unit continues to run in the Occupied state during the override time until the Unoccupied Override “Duration” time has “Elapsed”. So the Elapsed time is the amount of time that has passed with the unit operating in the Unoccupied Override period. The Override On/Off/Reset is the setting is the enable point to start or stop the Override time. Once the Override Duration has Elapsed, the Override On returns to Off automatically. Should the occupant(s) wish to vacate before the Override time has elapsed, the Override setting can be set to the Reset position which automatically terminate the Override Duration time and returns the unit to the Unoccupied state.
Main Menu System
The Main Menu is the menu system used to navigate
The Analog Outputs screen displays information about the modulating outputs to control modulated devices. Presently the Marvel controller controls the any of the devices listed within the Analog Output list shown on page 4. Please inquire with a United CoolAir local distributor for additional options desired.
Subject to change without notice. 120.9-IM (1218)
through the controller’s statuses and settings. The following Menu items are available within the Main Menu System: System ON/OFF, System Status (previously documented), System Enables, Set Points, Alarm Set Points, Run Hours, Day Min/Max, Clock Settings, Schedule, Setback, Unocc Control, Change Passwords, Technician Menu, and Factory Menu.
Simply pressing the (up) or (down) buttons, scrolls through the available screens within the System Status menu. Press the (enter) button to enter any of the Sub­Menus listed in the Main Menu. Press the Esc (escape) button to return to the System Status loop.
36
Page 37
Main Menu 01
Installation, Operation and Maintenance Manual
It is also used to re-enable compressors after a Compressor Safety (high pressure, low pressure, digital compressor module alarm) has disabled a compressor.
>>>System ON/OFF <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
Enter into the System ON/OFF to turn the unit ON/OFF Switch to the ON or OFF position.
Main Menu 02
>>>System Status <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The System Status can be entered either by pressing the enter button while this main menu item is displayed or by continuing to press the escape button.
Main Menu 03
Main Menu 04
>>>Set Points <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Set Points sub-menu is used to change any changeable set point other than Alarm Set Points.
Main Menu 05
>>>Alarm Set Points <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
Likewise the Alarm Set Points menu only has Set Points for Alarming Functions. There are no regular set points in this sub-menu.
>>>System Enables <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The System Enables is used to Enable or Disable
Compressors, Heaters, Humidication, and Dehumidication.
Subject to change without notice. 120.9-IM (1218)
Main Menu 06
>>>Run Hours <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
37
Page 38
The Run Hours sub-menu displays the total amount of run hours for each component. The hours counter for each component is resettable if that particular component has been replaced. Press the enter button to move the cursor next to the hours then press up or down to set the function to R for Reset. CAUTION: Do not press the enter button when R appears unless there is truly a need to reset the hours counter of a component, otherwise the Reset is almost instantaneous and cannot be stopped.
Main Menu 07
Installation, Operation and Maintenance Manual
Main Menu 09
>>>Schedule <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
>>>Day Min/Max <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Day Min/Max sub-menu records the highest and lowest Temperatures for Return/Space Temperature and highest and lowest humidity for Return/Space Humidity (if humidity sensor is installed) over a 24 hour period.
Main Menu 08
>>>Clock Settings <<<
/ Scroll Up/Down Enter Selected Menu
The Schedule sub-menus allows customer to congure an
Occupancy Schedule for their system.
Main Menu 10
>>>Setback <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Setback sub-menu allows customers to set their Set­Back schedule so that if full operation is not required, the system can be placed into a Set-Back mode to increase/ decrease the Set Point values to the Set Point Values listed in the Set-Back sub-menu. Set-Back assists with saving energy as it reduces load on the system. During Set Back mode, any interconnected Outdoor Air Dampers remain open until the system goes into Unoccupied mode.
Esc to Previous
The Clock Settings sub-menu allows the customer to adjust time zone, time of day, day of the week, and date.
Subject to change without notice. 120.9-IM (1218)
38
Page 39
Main Menu 11
>>>Unocc Control <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
Installation, Operation and Maintenance Manual
The Technician Menu sub-menu allows Technicians to access the following sub-menus: Fan Settings, System Units (Unit of Measure), Network (sets up network units), Manual Control, Sensor Setup, Digital Inputs, Economizer, Blower VFDs, Change Passwords, and Information. The Technician Menu password is 9995. Once the password is installed, the sub-menu will remain actively open until a
button has not been pressed for ve (5) minutes. After ve
minutes, the password must be reinserted.
Main Menu 14
Unoccupied Control is similar to the Set-Back control with the exception that any interconnected Outdoor Air Damper will close. Typically the Unoccupied Control Set Points are reduced even further to lighten the load on the system even further to assist with saving energy.
Main Menu 12
>>>Change Passwords <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Change Passwords sub-menu allows customers to install a Basic Password to lock out portions of the Main Menu that have adjustable settings. Read Only variables with the Main Menu sub-menus can still be displayed without requiring a password.
>>>Factory Menu <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Factory Menu sub-menu is the application parameters setup area. Please consult United CoolAir Technical Services Department before making any changes within this sub-menu.
SYSTEM ENABLES
This sub-menus allows for enabling and disabling of main system components.
U01 Compressor Enables
Compressor 1>Yes
Main Menu 13
>>>Technician Menu <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
Subject to change without notice. 120.9-IM (1218)
Compressor Enables allows for Enabling and Disabling of installed compressors. Compressor Enables will only appear up to the maximum compressors installed. If a Compressor Fails on High or Low Pressure or a Digital Compressor Fails
39
Page 40
Installation, Operation and Maintenance Manual
on a Module Alarm, the Compressor will be disabled. This is the screen that the compressor must be re-enabled to allow the compressor to restart. If a compressor trips on safety, the compressor must be re-enable on this screen to restart the compressor that tripped.
IMPORTANT: If a compressor tripped on safety, it must be re-enabled before the alarm can be cleared.
U01 Humidity Control
Dehumidify >Yes Humidify >Yes
The Humidity Control Enable screen allows for systems that have a humidity sensor installed to enable or disable
dehumidication. Also if a humidier is installed, it allows for enabling and disabling of humidication.
U01 Heater Enables
Heater 1>Yes Heater 2>Yes Heater 3>Yes Heater 4>Yes
The Heater Enables screens allows for enabling and disabling of heater banks. The amount of heaters displayed on the screen will be up to the total amount of heaters installed.
SET POINTS
The following Set Point Screens are available based on how the system is set up and type of sensors installed. Unlike
in the past where customers only had a single set point available, the Marvel Controller allows for either a single control Temperature Set Point and single control Humidity Set Point or separate control set points for Temperature and Humidity. The standard will be separated set point control. This will be clear in the Set Points sub-menu by seeing the Cool Set Point and Heat Set Point as well as if a humidity sensor is installed, there will be a Dehumidify Set Point
and a Humidify Set Point (only if the Humidier option is
installed).
Explanation of Set Point Screens:
Set Point Set Point is the desired setting that the
customer would like the unit function to
maintain for specic comfort level.
Prop Band Prop Band is the proportional band setting that
over the range of demand 0 to 100% for the
function (cooling, heating, dehumidication, humidication, etc.). Example of the
Proportional Band: For the Return Cooling
Set Point with a Set Point of 72.0˚F and a Proportional Band of 5.0˚F, the Cooling
Demand will be 100% when the Temperature
is at 77.0˚F. It will be 50% Cooling Demand at
74.5 degree.
Unlike previous Marvel Controllers, the Marvel now uses this Proportional Band as total band vs in the past having to divide the band in two and adding or subtracting it from the Set Point. This meant the demand was 100% at ½ of the proportional band.
Dead Band Dead Band is the region of comfort level
that is acceptable and no output adjustment to the Demand for (Cooling, Heating,
Dehumidication, Humidication, etc.) is
required. Setting this to zero means that the controller will continue to output a demand till the Demand required meets the set point.
IMPORTANT: Systems may have Proportional and Integral
control set up within a Set Points function block. Each of the settings above is input to a PID Function Block. Should the Set Point method be set up with a value installed in the
Integral setting, the specic function block of
the Set Points that have a value greater than zero set in the Integral set point will continue to increase or decrease the demand output
Subject to change without notice. 120.9-IM (1218)
40
Page 41
in an effort to maintain the exact set point value. Should a Dead Band setting have a value installed, the output adjustment will remain the same and no updates applied within the Dead Band region above or below the set point. Should the Dead Band setting be a value of 0.0, the output demand shall continue to increase or decrease in an effort to maintain the exact set point value.
NOTE: Though the separate set points are adjustable, there
is a built set point buffer to auto increase or decrease the opposite set point to prevent simultaneous
Cooling and Heating or Humidication and Dehumidication.
CHANGING SET POINTS
To change a Set Points, press the enter button to move
the cursor to the eld of the desired set point change. Press
the (up) or (down) buttons to change the present value of the set point to the newly desired set point. Press the enter button to save the change into memory.
U01 Return Cooling
Installation, Operation and Maintenance Manual
U01 Return Dehumidify Set Points
Setpoint > 50.0% Prop Band> 4.0% Dead Band> 2.0%
U01 Return Humidify Set Points
Setpoint > 45.0% Prop Band> 4.0% Dead Band> 2.0%
Set Points
Setpoint > 73.0 °F Prop Band> 5.0 °F Dead Band> 1.0 °F
U01 Return Heating Set Points
Setpoint > 68.0 °F Prop Band> 2.0 °F Dead Band> 0.0 °F
The above Set Point screens are available with a duct mount Return Temperature and Humidity Sensor. Return Heating Set Points will only appear if heaters are enabled under Factory Menu. Return Dehumidify Set Points will only appear if a duct mount Return Humidity Sensor is installed and Dehumidify is enabled. Return Humidify Set Points will only appear if a duct mount Return Humidity Sensor is
installed as well as the Humidier option and Humidify is
enabled.
U01 Space Cooling Set Points
Setpoint > 73.0 °F Prop Band> 5.0 °F Dead Band> 1.0 °F
Subject to change without notice. 120.9-IM (1218)
41
Page 42
U01 Space Dehumidify Set Points
Setpoint > 50.0% Prop Band> 4.0% Dead Band> 2.0%
U01 Supply Cooling
Set Points
Setpoint > 55.0 °F Prop Band> 2.0 °F Dead Band> 0.0 °F
U01 Supply Heating
Set Points
Installation, Operation and Maintenance Manual
In variable air volume applications in the past with heat pump or cooling/heating applications, it was required to enable a variable for Cool/Heat option for an automatic cooling and heating unit changeover. This placed the Cooling or Heating mode independently on the Return Air Temperature to make the determination of Cooling/Heating mode based on being above or below the Return Air Temperature Set Point. The system then controlled the amount of stages for cooling or heating by the Supply Cooling and Heating Set Points.
This is no longer the case as now the system will work as follows: Should the Heating Set Point remain less than the Cooling Set point, Heating will heat the supply air temperature back to set point and allow the individual VAV
Terminal outlet boxes with their own eld supplied heaters
bring the air temperature of the tenant occupied zone back up to the set point required. Should the Supply Heating Set Point be increased above the Supply Cooling Set Point, the previously mention Cool/Heat enable point is automatically enabled. Once the Supply Heat Set Point is increased above the Supply Cool Set Point, the system then looks to Cool or Heat based on the Return Air Temperature being above or below the Return Cool or Return Heat Set Points. Once the determination is made by the Return Temperature and Return Temperature Cooling and Heating Set Points, The amount of stage applied are based on the Demand for Cooling or Heating by the Supply Cooling and Supply Heating Set Points and Prop Band settings.
If the system does not have heaters, only Supply Cooling Set Points will appear.
Setpoint > 50.0 °F Prop Band> 2.0 °F Dead Band> 0.0 °F
The above Set Point screens are available with a wall mount Space Temperature and Humidity Sensor. Space Heating Set Points will only appear if heaters are enabled under Factory Menu. Space Dehumidify Set Points will only appear if a wall mount Space Humidity Sensor is installed and Dehumidify is enabled. Space Humidify Set Points will only appear if a wall mount Space Humidity Sensor is
installed as well as the Humidier option and Humidify is
enabled.
Subject to change without notice. 120.9-IM (1218)
U01 Air Economizer Set Points
Outdoor Temperature: Setpoint > 60.0 °F Band > 5.0 °F
42
Page 43
Installation, Operation and Maintenance Manual
U01 Water Economizer Set Points
Return Temp > 76.0 °F Water Temp > 66.0 °F Differential > 5.0 °F
The Air Economizer and Water Economizer Set Point screens are used to change the activation points of Airside Economizer and Waterside Economizer operation.
For Air Economizer, the Outdoor Air Temperature must fall below the Outdoor Temperature Set Point minus the band Set Point before Airside Economizer will start. Once in Airside Economizer, as long as there is a demand for cooling or the Outdoor Air Temperature is above the Outdoor Temperature Set point plus the Band Set Point or if the Outdoor Air Enthalpy is worse than the Indoor Air Enthalpy (depending on type of Air Economizer setup) the system will remain in Air Economizer mode of operation. See Airside Economizer sequence for full explanation of operation.
For Water Economizer, the Water Temperature entering the unit must be less than the Return Air Temperature minus the Differential Set Point. If the entering water temperature is greater than the Return Air Temperature minus the differential, the system will only use the Mechanical Cooling Compressors to satisfy the cooling demand.
U01 Space Temperature Set Points
Setpoint > 73.0 °F Prop Band> 2.0 °F Dead Band> 0.0 °F
U01 Return Humidity Set Points
Setpoint > 50.0% Prop Band> 10.0% Dead Band> 2.0%
U01 Space Humidity Set Points
Setpoint > 50.0%
U01 Return Temperature Set Points
Setpoint > 73.0 °F Prop Band> 5.0 °F Dead Band> 1.0 °F
Subject to change without notice. 120.9-IM (1218)
Prop Band> 4.0% Dead Band> 2.0%
As discussed previously, the system could be set up to use single set points to control both cooling and heating modes
or dehumidication and humidication. Shown above, the
system will be at 100% Cooling Demand when the Return Temperature is greater than the Return Temperature Set Point plus the Prop Band setting. The system will be at
43
Page 44
Installation, Operation and Maintenance Manual
100% Heating Demand when the Return Temperature is less than the Return Temperature Set Point minus the Prop Band setting. Shown above, the system will be at 100%
Dehumidication Demand when the Return Humidity is
greater than the Return Humidity Set Point plus the Prop
Band setting. The system will be at 100% Humidication
Demand when the Return Humidity is less than the Return Humidity Set Point minus the Prop Band setting.
The Space Temperature and Space Humidity Set Point screens work the exact same as the Return Temperature and Return Humidity screens. The only difference is type of sensor installed Return is duct mount and Space is wall mount. The other difference is terminology.
U01 Morning Warm-Up Set Points
Setpoint > 80.0 °F Prop Band> 10.0 °F
U01 Morning Cool-Down
Set Points
The Prop Band setting for each is the same as others. If the Return Temperature is less than the Warm-Up Set Point minus the Prop Band, the system will be at 100% heating demand for Morning Warm-Up. If the Return Temperature is greater than the Cool-Down Set Point plus the Prop Band, the system will be at 100% cooling demand for Morning Cool-Down.
U01 Duct Pressure Set Points
Setpoint > 1.000iwc Prop Band> 0.250iwc Dead Band> 0.075iwc
The Duct Pressure Set Point is used in Variable Air Volume applications. Since the fan/blowers modulate, the system uses Proportional and Integral control as a default. The Static Pressure Demand is based on the rate of change over a period of time. The fan/blower tries to maintain the exact set point and when a VAV Terminal Box opens or closed causing a change in pressure within the duct work the fan/blower needs to be increased or decreased to try to maintain the Duct Pressure Set Point.
ALARM SET POINTS
Setpoint > 70.0 % Prop Band> 10.0 %
The Morning Warm-Up screen is the Set Point screen for the heaters to control to during Morning Warm-Up Mode. Morning Warm-Up will terminate after the Warm-Up duration has expired or the Warm-Up Set Point is met.
The Morning Cool-Down screen is the Set Point screen for the compressors to control to during Morning Cool-Down Mode. Morning Cool-Down will terminate after the Cool­Down duration has expired or the Cool-Down Set Point is met.
Subject to change without notice. 120.9-IM (1218)
U01 Return Temperature Alarm Set Points
High Setpoint > 85.0 °F Low Setpoint > 60.0 °F Enable High > Yes Enable Low > No Alarm Delay > 060sec
44
Page 45
Installation, Operation and Maintenance Manual
U01 Space Temperature Alarm Set Points
High Setpoint > 85.0 °F Low Setpoint > 60.0 °F Enable High > Yes Enable Low > No Alarm Delay > 060sec
Depending on the setup, Return Temperature or Space
Temperature, there are specic High and Low Alarm Set
Points both having enable points for high and low alarm. The Enable High and/or Enable Low must be set to Yes in order to the High and/or Low Alarm to trigger when the temperature rises above or falls below the Alarm Set Point. The Temperature must also remain above or below the Alarm Set Point for the Alarm Delay before the Alarm will occur.
U01 Return Humidity Alarm Set Points
U01 Space Humidity Alarm Set Points
High Setpoint > 60.0 °F Low Setpoint > 20.0 °F Enable High > Yes Enable Low > No Alarm Delay > 060sec
Depending on the setup, Return Humidity or Space
Humidity, there are specic High and Low Alarm Set Points
both having enable points for high and low alarm. The Enable High and/or Enable Low must be set to Yes in order to the High and/or Low Alarm to trigger when the humidity rises above or falls below the Alarm Set Point. The Humidity must also remain above or below the Alarm Set Point for the Alarm Delay before the Alarm will occur.
U01 Supply Temperature Alarm Set Points
High Setpoint > 60.0 °F Low Setpoint > 20.0 °F Enable High > Yes Enable Low > No Alarm Delay > 060sec
High Setpoint > 80.0 °F Low Setpoint > 40.0 °F Enable High > Yes Enable Low > Yes Alarm Delay > 060sec
For Supply Temperature there are specic High and Low
Alarm Set Points both having enable points for high and low alarm. The Enable High and/or Enable Low must be set to Yes in order to the High and/or Low Alarm to trigger when the temperature rises above or falls below the Alarm Set Point. The Temperature must also remain above or below the Alarm Set Point for the Alarm Delay before the Alarm will occur.
Subject to change without notice. 120.9-IM (1218)
45
Page 46
Installation, Operation and Maintenance Manual
U01 Duct Pressure Alarm Set Points
High Setpoint > 3.00iwc Low Setpoint > -0.05iwc Enable High > Yes Enable Low > Yes Alarm Delay > 060sec
For Duct Pressure there are specic High and Low Alarm
Set Points both having enable points for high and low alarm. The Enable High and/or Enable Low must be set to Yes in order to the High and/or Low Alarm to trigger when the duct pressure rises above or falls below the Alarm Set Point. The Duct Pressure must also remain above or below the Alarm Set Point for the Alarm Delay before the Alarm will occur.
Run Hours
U01 Run Hours
Life Hours > 008579 Supply Blower > 005502 Compressor 1 > 004105 Compressor 2 > 003790 Compressor 3 > 002420
U01 Run Hours
Heater 1 > 002321 Heater 2 > 002100 Heater 3 > 000000 Heater 4 > 000000
The Run Hours screens above shows Total Run Hours
for specic components installed. The Run Hours section
tracks total Life Hours of the unit, Supply Blower total run hours and total run hours of compressors and heaters. Should a component be replaced for example, Compressor 2 was just replaced. The total run hours for Compressor 2 is capable of being reset to 000000 hours.
To reset the Run Hours of a component, press the enter
button to move the cursor to the eld “blank space” next
to the desired reset. Press the (up) or (down) button and an R will appear. Warning: Make sure the correct component selected is the desired reset required. Should the wrong component be selected and Reset is initiated, the Run Hours of that component will be reset to 0 without a method to set the correct hours of the component back
to the true hours. Once this is veried and the R appears,
press the enter button to conrm the Reset. All digits within Run Hours for that component are reset to 0 hours.
24 Hour Minimum/Maximum Values
Subject to change without notice. 120.9-IM (1218)
U01 24 Hour Period Minimum/Maximum
Min Max Temp > 69.7 °F 73.7 °F
Humid> 46.9% 54.2%
46
Page 47
Installation, Operation and Maintenance Manual
The values recorded for Minimum and Maximum take into consideration the setup for Return Temperature and Humidity or Space Temperature and Humidity. Even though it is not displayed, the recorded value is based on the type of sensor listed in the main status menu Return or Space.
Clock Settings
U01 Date/Time change
Format > MM/DD/YY Date > 03/23/17 Hour > 08:47:45 Day > Thursday
As show in the Date/Time change, the Format of the Date, Present Date, Present Time, and Day of the Week can all be changed. Press the enter button to move the cursor to the eld of the desired change. Press the (up) or (down) button to change the value and then press the enter button to save the change into memory.
Schedule
U01 Schedule Enables
Mon>Yes Tue>Yes Wed>Yes Thu>Yes Fri>Yes Sat>Yes Sun>Yes
In order to add an Occupancy Schedule the Schedule must
rst be enabled. Press the enter button to move the cursor to the Enable eld. Press the (up) or (down)
button to change the value to Yes to Enable the Schedule and No to Disable the Schedule and then press the enter button to save the change into memory.
U01 Schedule
Enable> Yes
U01 Timezone
US EASTERN STANDARD TIME
Update Timezone: No
Press the enter button to move the cursor to the time
zone eld. Select the appropriate time zoned using the
(up) or (down) button to change the value and then press the enter button move the cursor to the Update Timezone. Selecting Yes and pressing the enter button again will save the change into memory.
Subject to change without notice. 120.9-IM (1218)
It is possible to set up for specic days to enable only a
schedule for those particular days of Occupancy. Press the
enter button to move the cursor to the Enable eld for
the desired day. Press the (up) or (down) button to change the value to Yes to Enable the Schedule and No to Disable the Schedule for that day and then press the enter button to save the change into memory.
47
Page 48
Installation, Operation and Maintenance Manual
U01 Schedule Monday (hh:mm)
Occupied > 7:00 Unoccupied > 20:00
Once the Day of the Week has been enabled for the Occupancy Schedule to occur, the screen for that day will appear within the Schedule sub-menu. Simply setting the Occupied and Unoccupied times will allow the controller to follow the schedule for that day of the week. Should Monday and Wednesday have an Occupied Times but Tuesday is disabled, the unit will go into occupied during the occupied start time and then go into unoccupied and remain unoccupied until the occupied start time on Wednesday.
Set Back ON and OFF Times
Should Set Back be enabled under the Set Back Menu, the Set Back Schedule will appear here under the Schedule sub-menu.
Morning Warm-Up
U01 Warm-Up Start Time (hh:mm)
Monday > 6:00 Tuesday > 6:00 Wednesday > 6:00 Thursday > 6:00 Friday > 6:00
U01 Warm-Up Start Time (hh:mm)
Saturday > 6:00 Sunday > 6:00 Duration > 60min
U01 Set-Back Monday (hh:mm)
Setback ON >18:00 Setback OFF>20:00
If Morning Warm-Up is enabled, the Morning Warm-Up Start Time will appear under the Schedule sub-menu for each Day of the Week. There is also a Duration Time in minutes that needs to be set. The Morning Warm-Up then starts at the Warm-Up Start Time for that particular Day and be in Morning Warm-Up Mode until either the Warm-Up Set Point is achieved or until the Duration Time expires.
Morning Cool-Down
U01 Cool-down Start Time (hh:mm)
The Set Back ON is the Start time for the unit to be in the Set Back Mode. The Set Back OFF is the stop time for Set Back Mode. The unit will either go back into Occupied Mode or into Unoccupied Mode depending on how the Schedule is set up. The Set Back Set Points for Cooling, Heating,
Humidication, and Dehumidication all appear under the
Set Back Menu.
Monday > 6:00 Tuesday > 6:00 Wednesday > 6:00 Thursday > 6:00 Friday > 6:00
Subject to change without notice. 120.9-IM (1218)
48
Page 49
Installation, Operation and Maintenance Manual
U01 Cool-down Start Time (hh:mm)
Saturday > 6:00 Sunday > 6:00 Duration > 60min
If Morning Cool-Down is enabled, the Morning Cool-Down Start Time will appear under the Schedule sub-menu for each Day of the Week. There is also a Duration Time in minutes that needs to be set. The Cool-Down then starts at the Cool-Down Start Time for that particular Day and be in Morning Cool-Down Mode until either the Cool-Down Set Point is achieved or until the Duration Time expires.
Set-Back
Under the Set Back sub-menu, the following screens appear to allow set up of the Set Back feature to allow each Mode of Operation to work in the Set Back Mode.
U01 Set-Back Cooling
Setpoint > 76.0 °F Prop Band > 02.0 °F
U01 Set-Back Dehumidification
Setpoint > 55.0% Prop Band> 05.0%
U01 Enable Set - Back Control
Cooling >Yes Heating >Yes
U01 Set-Back Heating
Setpoint > 70.0 °F Prop Band> 02.0 °F
Dehumidify >Yes Humidify >Yes
Enable each of the Modes of Operation that should operate during the Set-Back Mode. The enable points and set points follow the same principle. Cooling will automatically appear. Heating will only appear if heaters are enabled within the
Factory Menu. Dehumidication will appear when either
the Return Humidity or Space Humidity Sensor is enabled,
and Humidication will only appear when either the Return Humidity or Space Humidity is enabled and a Humidier is
installed.
Subject to change without notice. 120.9-IM (1218)
49
Page 50
Installation, Operation and Maintenance Manual
U01 Set-Back Humidification
Setpoint > 45.0% Prop Band> 05.0%
Shown above are the Set-Back screens available for change Set Points for the Modes of operation for Set-Back control.
U01 Enable Unoccupied Control
Blower ON >Yes Cooling >Yes Heating >Yes
U01 Unoccupied Cooling
Setpoint > 78.0 °F Prop Band> 02.0 °F
U01 Unoccupied Heating
Setpoint > 68.0 °F Prop Band> 02.0 °F
Dehumidify >Yes Humidify >Yes
Enable each of the Modes of Operation that should operate during the Unoccupied Control Mode. The enable points and set points follow the same principle. Cooling will automatically appear. Heating will only appear if heaters
are enabled within the Factory Menu. Dehumidication will
appear when either the Return Humidity or Space Humidity
Sensor is enabled, and Humidication will only appear when
either the Return Humidity or Space Humidity is enabled
and a Humidier is installed.
U01 Unoccupied Dehumidification
Setpoint > 58.0% Prop Band> 05.0%
Subject to change without notice. 120.9-IM (1218)
50
Page 51
Installation, Operation and Maintenance Manual
U01 Unoccupied Humidification
Setpoint > 40.0% Prop Band> 05.0%
Shown above are the Unoccupied Control screens available for changing Set Points for the Modes of operation for Unoccupied Control.
CHANGE PASSWORD
U01 Basic Password
Basic >Disable Password >0000
Technician Menu 01
>>>Fan Settings <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Fan Settings sub-menu allows technicians to adjust Time Delays with Fans and Blowers as well as Damper Delays.
Technician Menu 02
>>>System Units <<<
/ Scroll Up/Down Enter Selected Menu
The Change Password screen allows for a Basic Password to be installed for protection of set points and other Main Menu items from unauthorized users. The password must
rst be enabled and then the Password can be changed to
a value between 0 and 9999.
Technician Menu
The Technician Menu is a sub menu of the Main Menu that allows Technicians to access the system for minor adjustments of settings and parameters of the system and
view functions of specic components to troubleshoot/
diagnose problems with components.
Esc to Previous
The System Units sub-menu allows technicians to adjust the type of data displayed as either Imperial or System International.
Technician Menu 03
>>>Network <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Network sub-menu allows technicians to set up the network based on the application primarily from an alarms and unit transfer stand point. It also allows them to set the
Subject to change without notice. 120.9-IM (1218)
51
Page 52
number of days between rotations to the next unit. And allow the system to know in applications with 3 or greater units in a network if any units should remain on continuously without rotating to the off or stand-by position.
Installation, Operation and Maintenance Manual
Technician Menu 06
Technician Menu 04
>>>Manual Control <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Manual Control sub-menu allows technicians the ability to manually turn components on or off, manually adjust modulating output devices, and manually adjust sensor readings all to be able to test a unit and/or system.
Technician Menu 05
>>>Sensor Setup <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
>>>Digital Inputs <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Digital Inputs sub-menu is used to set the direction (normally open or normally closed) any interconnected devices are desired to alarm, be active, or inactive.
IMPORTANT! Please do not adjust factory provided
devices. Primarily only eld provided components should
be adjusted based on the direction the component is active (open or closed).
Technician Menu 07
>>>Economizer <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
Sensor Setup is a sub-menu that allows technicians to
calibrate sensor readings, set up custom sensors, add a eld purchased (consult factory rst) sensor in the event that the
customer has a failed sensor and a critical application that the unit needs to be running that same day and they cannot wait for a factory supplied original sensor. It also allows adjustment of Minimum and Maximum output settings for the Modulating Analog Output devices connected to the controller.
Subject to change without notice. 120.9-IM (1218)
The Economizer sub-menu allows customer to adjust the settings with Airside and Waterside Economizer.
Technician Menu 08
>>>Blower VFDs <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
52
Page 53
Installation, Operation and Maintenance Manual
The settings for Blower VFDs sub-menu are only available with factory provided VFD’s that are interconnected to the controller via Modbus control. It allows technicians to view status and make minimal adjustments to the VFDs.
Technician Menu 09
>>>Change Passwords <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Change Passwords sub-menu under the Technician Menu allows the technician/customer the ability to Enable Basic and or Technician Passwords.
Technician Menu 10
FAN DELAYS
U01 Damper Delays
Unit Start > 015sec Damper Delay > 060sec
U01 Blower Delays
Blower Start >015sec Blower Min ON >030sec Blower Min OFF >030sec Airflow Check >060sec
>>>Information <<<
/ Scroll Up/Down Enter Selected Menu
Esc to Previous
The Information sub-menu provides information about the software version, operating system version and other detailed information about the installed controller.
The Damper Delays and Blower Delays allow adjustment of system delays. The Unit Start delay is the length of time between the Unit ON/OFF switch and when the Damper starts. The Damper Delay is the length of time that the damper output must be on before the Supply Air Blower can start. The Blower Min ON delay is the amount of time that
the blower must be on before it can turn off. The Airow
Check delay is the amount of time that the blower must be on before any mode(s) of operation (Cooling, Heating,
Humidication, and Dehumidication) can start. Once this delay has elapsed, the system is veried for air ow and if the air ow is proven good, the modes of operation and start. If air ow is not proven, the Loss of Airow Alarm
will be posted, no modes of operation will start and the blower output will de-energize. The Blower Min OFF is the amount of time that the blower must remain off once it is de-energized.
Subject to change without notice. 120.9-IM (1218)
53
Page 54
Installation, Operation and Maintenance Manual
SYSTEM UNITS
U01 Units Setup
Unit Type>Imperial
The Units Setup is the screen to apply the type of units preferred Imperial or SI.
NETWORK
U01 Network Setup
Total Units >0 Standby Units >0
U01 Network Setup
Continuous Units
U01>Yes U05>No U02>Yes U06>No U03>Yes U07>No U04>No U08>No
U01 Network Setup
Continuous Units
U09>No U13>No U10>No U14>No U11>No U15>No U12>No U16>No
Enable Rotate >No Rotate Now >No Shift Delay ON >020sec
The Network Setup screens are used to setup interconnected
units in a networking application. Typically this rst screen
will be set up by the factory and normally does not require adjustment(s). Total Units is the Total number of units connected within the networking application. Standby Units is the total number of units to remain in stand-by mode within the total number of units within the network. Enable Rotate allows the units within the Total Units and Standby Unit to rotate on or off within the network. Rotate Now allows technicians to force a Rotation to make sure a unit that is presently operating goes into stand-by mode and brings the next unit required out of stand-by to the on position. Shift Delay is the amount of time between the time a unit presently operating shuts down and goes into stand­by mode and the start of the next unit from the stand-by mode to the on position.
The System Rotations allows technicians or customers to adjust the amount of days between rotating to the next unit in line. The Rotate Time is the time of day in 24-hour format that the unit rotation is supposed to occur.
U01 Network Setup
System Rotations
Between Rotate>007 days Rotate Time >01:00
If the number of units networked is greater than three (3), the screens above for Continuous Units will appear. If any units are supposed to remain on continuously, setting each of the units required to remain on to Yes will allow them to remain on continuously within the existing networked
Subject to change without notice. 120.9-IM (1218)
54
Page 55
Installation, Operation and Maintenance Manual
application. The total amount of units that appear here will match the Total Units in the network.
U01 Network Setup
Rotate on Alarm>Yes Unit OFF>Yes
The Rotate on Alarm will allow the units to shut down when an alarm occurs within a unit that is operating. If a unit shuts down due to an alarm, another unit within the network (if available) will be brought on. Unit OFF when set to Yes will turn off the unit that went into alarm.
U01 Network Setup Alarm Transfers:
SENSOR SETUP
U01 Return Temp
Actual > 073.00 °F Offset > 000.00 °F Custom > Yes Type > 0-10vdc Minimum >-050.00 °F Maximum > 150.00 °F
U01 Supply Temp
Actual> 073.00 °F Offset> 000.00 °F Custom> No
Airflow >Yes Drain Pan >Yes Comp 1 HP or LP >Yes Comp 2 HP or LP >Yes Comp 3 HP or LP >Yes Comp 4 HP or LP >Yes
Setting any of the Alarm Transfers listed above will automatically transfer the unit with alarms to the standby mode and bring the next unit in line within the network out of stand-by to the on position.
The screens above are two variations of setups. The Offset is that calibration adjustment for the sensor.
One of the biggest benets of the Marvel controller is the ability to add a eld replacement sensor when a sensor has
failed and it is imperative to get the unit back up and running immediately. Typically Factory Supplied Sensors are not
custom sensors. If a eld replacement was purchased
locally (Please consult the factory about types before doing so), Setting the Custom to Yes will allow the adjustments for Type of Sensor and Range of sensor (Minimum/Maximum)
to appear. These settings must be congured for the sensor
that was purchased.
Subject to change without notice. 120.9-IM (1218)
55
Page 56
U01 Sensor Filtering
AIN 01>7 AIN 06>5 AIN 02>5 AIN 07>5 AIN 03>9 AIN 08>5 AIN 04>5 AIN 09>5 AIN 05>5 AIN 10>5
Installation, Operation and Maintenance Manual
Analog Output. In the examples above, Analog Output 1 is enabling for ECM Press or ECM Blower for variable air volume duct pressure control. The Minimum Output voltage to the Electronically Commutated Motor is 3.0 volts dc. This means the blower will always be 30% of the maximum when the blower is on. Airside Economizer is enabled on Analog Output 2. The minimum output is adjusted to 2.0 volts dc. This is simply because the type of damper actuators installed is a 2.0 to 10.0 vdc type.
MANUAL CONTROL
The sensor ltering value takes a number of readings over a
period of time and outputs the average value over a period of time for the number of readings. The higher the number, the more readings will be allowed over a period of time.
U01 Analog Output 1
ECM Press
Minimum> 3.0vdc Maximum> 10.0vdc
U01 Analog Output 2
Air Econo
Minimum> 2.0vdc
U01 Manual Dig-Out
01>Compressor 1 >Auto 02>Compressor 2 >Auto 03>Compressor 3 >Auto 04>Compressor 4 >Auto 05>Unassigned 06>Unassigned
U01 Manual Dig-Out
07>Supply Blower >Auto 08>O/A Damper >Auto 09>Unassigned 10>Unassigned 11>Unassigned 12>Water Pump >Auto
Maximum> 10.0vdc
The Analog Output screens above allow for component adjustment of Minimum and Maximum allowable vdc output for that component enabled under that particular
Subject to change without notice. 120.9-IM (1218)
In the screens above for Manual Control, Manual Control allows any of the above devices to be turned on manually. Under Manual Dig-Out, AUTO means that the device will turn on or off based on the demand for the device to be on or off. OFF means that the component will be off until either set to ON or AUTO mode. ON means that the component will be on until either set to the OFF or AUTO position.
56
Page 57
Installation, Operation and Maintenance Manual
U01 Analog Outputs
ECM Press OFF 0.0v Air Econo OFF 0.0v DPC Valve 1 OFF 0.0v Dig Comp 1 OFF 0.0v
Under the Analog Outputs, OFF means the analog output will be modulated up or down automatically based on the demand for the component. Setting the OFF to ON means that the modulation can be increased or decreased between 0.0 and 10.0 vdc based on requirement to test the component.
DIGITAL INPUTS
U01 Dig-Inputs Setup
ECONOMIZER
U01 Economizer Setup
Type: >Air& Mod Water Valve Assist>Enable
Damper Minimum> 000% Damper Maximum> 100%
U01 Economizer Assist
Delay > 15min Start > 100% End > 50% Comps > 3
State Alarm Duct Hi-Lim cl op Fire/Smoke cl op Ext ON/OFF cl op Filter cl op Water Flow cl op
The Digital Inputs Setup screen allows devices such as
Ext ON/OFF (Remote ON/OFF), eld provided Fire/Smoke
Detectors, etc. to be set for the proper switching state. Some
devices can be congure to work on contact closure, other
require open contacts. The Alarm column may be changed
to Alarm on cl or (contact closure) depending on the eld
device installed. IMPORTANT: Never change the Alarm position of the compressor high and low pressure switches unless it is desired to test the digital input for failure. When doing so, please remember to set the Alarm back to the op position.
(Comps-Total comps allowed to assist)
The above screens for Economizer Setup and Economizer Assist allow for setup of the Economizer package. The parameter for Type of Economizer can be set. If mechanical cooling assist is required, Assist can be Enabled so that Mechanical Cooling Compressors can assist economizer mode. CAUTION: Please consult the factory for Assist requirements as not all units may be capable of having compressor run while economizer mode is on).
If the Economizer Type is Airside Economizer, the Minimum output and Maximum outputs can be set for Economizer Dampers to meet fresh air and maximum air
ow requirements. Economizer Assist requires that the
demand for economizer must be equal to the compressor Start Demand for the Delay Time before the compressors can assist. The total number of compressors applied will sequence on with a delay between stages up to the maximum number of compressors allowed to assist as set into the Comps-Total compressor allowed to assist setting. The End setting is the Economizer Demand value set point where compressors will stop assisting and only Economizer mode will operate.
Subject to change without notice. 120.9-IM (1218)
57
Page 58
Installation, Operation and Maintenance Manual
BLOWER VFDS
U01 Duct Pressure
Proportional > 0.030 Integrations > 30sec Derivative > 5sec Cycle Time > 1500msec Low Limit > 30.0% High Limit > 100.0%
The Blower VFDs sub-menus allow for adjustment of the settings for variable air volume duct pressure control settings. Low Limit is the minimum speed in percent that the blowers will operate. The Low Limit must be a minimum of 30% and not less than 30% as the system requires a minimum 30% for proper cooling. The High Limit may be limited to a value less than 100% due to the blower size. Please consult United CoolAir before adjusting these settings.
U01 Enable Passwords
Basic User>0000 Technician>9995
SYSTEM INFORMATION
U01 Information
United CoolAir
Marvel Premium Controller
Version >1.1.00 1 Op
CHANGE PASSWORDS
The Enable Password screens allow for enabling of the Basic and/or Technician Passwords. The passwords can be a value between 0 and 9999. Please record the passwords if installed.
U01 Enable Passwords
Basic User>Disable Technician>Enable
System>4.1.005
U01 Information
United CoolAir
Marvel Premium Controller
Job Number>026479 Op System >4.1.005
The Information Screens above are displayed based on either a Version Number or by a Job Number. If the software is a standard version, the verbiage “Version” will be displayed followed by the version number. Should the system have custom software, the verbiage “Job Number” followed by the United CoolAir Job Number will be displayed. On the last line, the Operating System version is displayed.
Subject to change without notice. 120.9-IM (1218)
58
Page 59
Installation, Operation and Maintenance Manual
U01 Information System Info Board Type> c.pCO Board Size> Large Board Temp> 104 °F PermMem Writes>0005400 Main Status: 150ms 5.6cycles/sec
The last screen within the Information sub-menu provides details about the installed controller.
FIGURE 16 – DIGITAL INPUT TERMINATION REFERENCES
INPUT WIRING
Digital Inputs
The Digital Inputs on the Marvel can accept and perform any of the control functions listed for Digital Inputs on page
4. The digital inputs are designed to work with 24 VAC or 24 VDC. When using the digital inputs with a dc voltage source, a 24 V AC/DC common must be wired to the actual digital input, and must also be the same as the connection to the G0 terminal which is normally referenced to ground. The +24 VDC would then be wired directly to the IDCx or common for the digital input. Refer to Figure 16 – Digital Input Termination References for further details.
Analog Inputs
The Universal Inputs on the Marvel controller are provided for reading any of the listed Universal/Analog Input sensors listed on page 4.
The NTC temperature sensors are connected as shown in Figure 17 – Temperature Sensor Termination References. There is no polarity to the NTC temperature sensors.
FIGURE 17 – TEMPERATURE SENSOR TERMINATION
REFERENCES
Subject to change without notice. 120.9-IM (1218)
59
Page 60
For all other sensor terminations, please refer to the electrical diagrams provided with the units for electrical connections.
Digital Outputs
Relays on a Marvel controller are capable of handling up to 10 Amps Resistive at 1 Amp Inductive loading at 250 VAC to control any of the Digital Output functions listed on page 5. To power a control device (contactor, starter, solenoid coil, etc.) connect the neutral side of the 24 VAC power supply to the control device. Connect the hot side of the 24 VAC power supply through the common C(x) of the digital output relay as shown in Figure 18 – Digital Output Termination References.
Installation, Operation and Maintenance Manual
FIGURE 19 – ANALOG OUTPUT TERMINATION
REFERENCES
OPTIONAL BOARDS
FIGURE 18 – DIGITAL OUTPUT TERMINATION REFERENCES
Analog Outputs
The Analog Outputs on a Marvel controller are capable of providing modulating output voltage of 0 – 10 VDC to control any of the following Analog Outputs listed on page 4. The analogs outputs must be powered externally using 24 VAC. The neutral side of the 24 VAC power supply is connected to terminal VG0. The 24VAC hot side is connected to terminal VG1. Analog Output 1 through Analog Output 6 (Y1 through Y6 respectively) connects to the modulating output for the device being controlled. Refer to Figure 19 – Analog Output Termination References for connection details.
Building Management Systems (BMS Systems)
Several methods of supervisory systems may be used to communicate with the Marvel Main Board which allow for monitoring of the systems readings, changing/offsetting of set points and remotely view alarm status. The following is a list of BMS Systems the Marvel Control can interface with:
BACnet
TM
ModBus® LonWorks® pCOWeb
Subject to change without notice. 120.9-IM (1218)
60
Page 61
Installation, Operation and Maintenance Manual
SYSTEM NETWORKING
Two or multiple units may be networked as shown in Figure
1 previously. The networks are precongured during the
operational testing at the factory using Ethernet Cables.
1. Connect eld supplied Ethernet Cables between
the controllers as shown in Figure 20 – System Networking below.
FIGURE 20 – SYSTEM NETWORKING
a. Network wiring between each unit must be installed
between each unit as follows:
i. Unit 1 connects to Unit 2
ii. Unit 2 to Unit 3
iii. Unit 3 to Unit 4 and so on.
b. Network wiring must be 4 Conductor Minimum 20
AWG shielded cable.
2. Should there be a need to re-order the number of unit
identication, Figure 21 – Adjusting pLAN Addresses
below displays the location and momentary push button access for renumber the plan networking addresses.
a. Simply insert a very small screw drive in through
the momentary pushbutton opening.
b. Depress the button one time and the LEDs shown
at 31 will illuminate to a higher intensity.
c. Once they are brighter, keep pressing the button
until the desired plan address is achieved.
d. Stop depressing the button to save the plan
address into memory.
FIGURE 21 – ADJUSTING PLAN ADDRESSES
Subject to change without notice. 120.9-IM (1218)
61
Page 62
Installation, Operation and Maintenance Manual
3. If the units were ordered from the factory as a
networking system, the following procedure will have already been completed and tested. Each unit must be shared with the Marvel Terminal/Wall Display. In order to do this, disconnect power to all but one unit. Each unit will be updated one at a time.
4. Press the
simultaneously for 5 seconds until the following screen appears.
(up), (down) (enter) and buttons
Display address
setting............ :32
I/O Board address: 01
5. Make sure the display address it set to a 32. On the
present unit being updated, the I/O Board address should automatically appear. If it does not appear, a
-- will appear. Simply position the blinking cursor over the -- by pressing the (enter) it is positioned at this location. Press the up or down button until the pLAN address shown in Figure 20 appears at this location. Press the (enter) button until the next screen appears and then once this screen appears, press the
(enter) button again till the Priv/Shared Screen as
shown appears.
6. Trm1 must be a value of 32 to match the value previously set. If it is not a 32, use the (down) buttons to change the value to a 32 then press the (enter) button to save it into memory. Next, use the value under Priv to make sure that if Pr is displayed, the value must be Sh for Shared and then press the
(enter) button to save it into memory. Continue to press the (enter) button until the blinking cursor is positioned under the NO and use the
to change the value to Yes. Once this is nished, the
main status screen will reappear.
(up) or (down) buttons to change the
(up) or
(up) button
P:01 Adr Priv/Shared Trm1 32 Sh Trm2 None -- Trm3 None -- ok?NO
7. At this point, power this unit down and repeat the previous steps to share each unit with the Marvel Terminal. It is easiest to do one unit at a time making sure that power is applied only to the unit being updated. Once all units have been updated, power can be applied to all units.
Terminal config
Press ENTER To Continue
Subject to change without notice. 120.9-IM (1218)
62
Page 63
NOTES:
Installation, Operation and Maintenance Manual
Subject to change without notice. 120.9-IM (1218)
63
Page 64
Unique Solutions for All-Indoor HVAC Projects
VertiCool Classic
Vertical, 3 - 30 Ton
Portable Cooling and
Heating Units
3-30 Tons
Authorized Distributor:
VertiCool Aurora
Vertical, 3 - 35 Tons
C13-Series Horizontal
2 - 10 Tons
VariCool®
VAV, 9 - 70 Tons
C-Series Horizontal
1 - 15 Tons
Special Configuration
Engineered to Order
VariCool® EZ-Fit
VAV, 12 - 90 Tons
OmegaAir Vertical
100% Outside Air, 1 - 15 Tons
OmegaAir Horizontal,
100% Outside Air, 1 - 15 Tons
LIMITED WARRANTY
United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor (labor not
included). Maintenance items such as lters and belts are excluded
under this limited warranty.
FACTORY TESTED
All units are functionally run tested before shipment to ensure a trouble-free start-up and unit commissioning. Industry proven components are used throughout to enhance system reliability and peace of mind.
Scan to learn more
about all of our
products!
491 East Princess Street, York, PA 17403 Phone: 717-843-4311 Fax: 717-854-4462
email: [email protected] web: www.unitedcoolair.com
Copyright © by United CoolAir Corporation 2018. All rights reserved.
Manufacturer reserves the right to make changes without notice.
120.9-IM (1218)
Loading...