United cool air C13-Series Installation, Operation And Maintenance Manual

C13-Series
Installation, Operation and Maintenance Manual
Effective August 2018
Air-Cooled, Water-Cooled, Chilled Water and Heat Pump
Horizontal
Contents
Installation, Operation and Maintenance Manual
C13-Series
Contents � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3 Wiring Diagram � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4 Important Notice� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5 Use of Symbols� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5 C13-Series Air-Cooled Package � � � � � � � � � � � � � � � � � � � 6 C13-Series Water-Cooled Package� � � � � � � � � � � � � � � � � 7 General Information � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
Inspection Of Equipment � � � � � � � � � � � � � � � � � � � � � � � � 8 Handling � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8 Location � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8 Mounting And Setting In Place� � � � � � � � � � � � � � � � � � � � 8
Installation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9 Split Systems � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9 Separation Of Sections � � � � � � � � � � � � � � � � � � � � � � � � � � 9 Interconnecting Refrigerant Tubing � � � � � � � � � � � � � � � 10 Single Package Unit Wiring� � � � � � � � � � � � � � � � � � � � � � 13 Split System Wiring � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13 Duct Connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13 Pressure Switches � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
High Pressure � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13 Low Pressure � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
Water-Cooled Condensing Units � � � � � � � � � � � � � � � � � 13
Water-Cooled Condenser� � � � � � � � � � � � � � � � � � � � � � � 13 Water Piping and Connections� � � � � � � � � � � � � � � � � � � 13 Hook Up � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14 Water Connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
Condensate Drain Connection � � � � � � � � � � � � � � � � � � � 14 Maintenance Procedures� � � � � � � � � � � � � � � � � � � � � � � � 15 Filters� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15 Cleaning The Water-Cooled Condenser� � � � � � � � � � � � 15 Blowers � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 16 Blower Motors� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 17 Blower Speed Adjustment � � � � � � � � � � � � � � � � � � � � � � � 17 Blower Motor Lubrication � � � � � � � � � � � � � � � � � � � � � � � 17 Belts� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Refrigerant Systems� � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Evaporator And Air-Cooled Condenser Coils � � � � � � � 18 Minimum Service Access � � � � � � � � � � � � � � � � � � � � � � � 18 Application Data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Hard Start Kit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Sequence Of Operation � � � � � � � � � � � � � � � � � � � � � � � � � 19 Cooling Sequence Of Operation � � � � � � � � � � � � � � � � � � 19 Heating Sequence Of Operation (Other Than Heat
Pump) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 19 Heat Pump Heating Sequence Of Operation � � � � � � � � 20
Options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20 Condensate Pump � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20 Thermostat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21 Checking Hot Gas Bypass Valve� � � � � � � � � � � � � � � � � � 21 Adjustment Of Hot Gas Bypass Valve � � � � � � � � � � � � � 22 Microprocessor Controller � � � � � � � � � � � � � � � � � � � � � � 22 Humidier � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22 Electric Heat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22 Electric Reheat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22 Steam Coil� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22 Hot Water Coils� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 23 Flooded Condenser � � � � � � � � � � � � � � � � � � � � � � � � � � � � 23 Buck/Boost Transformer � � � � � � � � � � � � � � � � � � � � � � � � 23 Chilled Water Valves Or Hot Water Valves � � � � � � � � � � 24 Head Pressure Control Valves � � � � � � � � � � � � � � � � � � � 24 Economizer Operation (Airside) � � � � � � � � � � � � � � � � � � 24
Economizer Operation � � � � � � � � � � � � � � � � � � � � � � � � � 24
Economizer Operation – (Waterside) � � � � � � � � � � � � � � 24 Condensing Section Outdoor Modication Kit � � � � � � 24 Split Condenser / Condensing Sections � � � � � � � � � � � 24 C13-Series Air-Cooled Condenser/ Condensing Section
With Outdoor Modication Kit� � � � � � � � � � � � � � � � � � � � 25 Vertical Stacking Unit� � � � � � � � � � � � � � � � � � � � � � � � � � � 26 Troubleshooting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 28 Limited Warranty � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 32 Limited Warranty for Hermetic Compressors � � � � � � � 33 Limited Warranty Condensing Section � � � � � � � � � � � � 34 Limited Warranty for Hermetic Compressors � � � � � � � 35 Air-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 36 Start-Up Procedures (R-410a Systems)� � � � � � � � � � 36–37 Air-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 38
Start-Up Procedures � � � � � � � � � � � � � � � � � � � � � � � � � � 38 Cooling Mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39 Electrical� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39 Heating Mode (Optional) � � � � � � � � � � � � � � � � � � � � � � � 39
Water-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 40 Start-Up Procedures (R-410a Systems)� � � � � � � � � � � � � 40 Start-Up Procedures (R-410a Systems) Continued:� � 41
Optional Heating Start Up: � � � � � � � � � � � � � � � � � � � � � � 41
Water-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 42
Start-Up Procedures � � � � � � � � � � � � � � � � � � � � � � � � � � 42 Cooling Mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 43 Electrical� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 43 Heating Mode (Optional) � � � � � � � � � � � � � � � � � � � � � � � 43
Basic Model Designation� � � � � � � � � � � � � � � � � � � � � � � � 44
Subject to change without notice. 10.20-IM (0818)
Installation, Operation and Maintenance Manual
C13-Series
Wiring Diagram
United CoolAir provides a wiring schematic for each unit produced� To retrieve the diagram for your unit please visit www�unitedcoolair�com, on your computer or mobile device, scroll to the footer section or Home/industry-resources, enter your serial number in the Serial Search eld and press return to retrieve your product-wiring diagram.
Your serial number is a combination of the year, month and sequential order of build date�
This action will return the Model number, Job Number and the wiring diagram for viewing as well as downloading�
NOTE: Only units shipped since November 2016 are available on the site, for older units please contact the factory directly at 717-843-4311�
Subject to change without notice. 10.20-IM (0818)
Installation, Operation and Maintenance Manual
C13-Series
Important Notice
This manual is the property of the owner�
Please be sure to leave it with the owner when you leave the job�
Use of Symbols
This publication includes warnings, cautions and information icons that point out safety related issues or conditions as well as other pertinent information relative to a safe installation, service or maintenance situation� The following icons should be interpreted as follows:
ELECTRICAL HAZARD
WARNING
CAUTION
INFORMATION
The electrical hazard icon indicates the presence of an electrical hazard which could result in electrical shock or death�
The warning icon indicates a potentially hazardous situation which could result in death or serious bodily injury if not avoided�
The caution icon indicates a potentially hazardous situation which may result in minor or moderate injury if not avoided�
The information icon indicates a situation that may result in equipment or property damage� The information provided alerts the reader to relevant facts and/or conditions�
Subject to change without notice. 10.20-IM (0818)
Installation, Operation and Maintenance Manual
C13-Series Air-Cooled Package
W
S
T R
½
C13-Series
Clearance Hole for
⅜" Hanging Rod
TYP 8 PLS
P
G
H
V
Evap
Return
Evaporator
Section
B
L M N 1 1
Evap
Supply
Air
FRONT RIGHT
Z X Y
Air
J
TOP
F
K
Condensing
Section
1
Service Clearance
All Sizes
Left Side 36"
Right Side 36
Field Installation Power & Control Wiring
Elect Box
Motor & Blower
Access Panel
D E 5
Elect Box
Motor & Blower
Access Panel
A
Cond
AA
AB AC
Tons A B C D E F G H J K L M N P Q R S T V W X Y Z AA AB AC AD
2–3 78 56 22 44 34 119⁄16 20 1 59 7 25 1011⁄16 91⁄16 3¼ 57 40½ 1¾ 30½ 91⁄16 3½ 24 35⁄16 13¼ 119⁄16 7 111⁄16 19
4–5 86 64 25 46 40 13 9⁄16 25 0 67 81⁄16 31½ 123⁄8 91⁄16 3 65 42½ 1¾ 36½ 91⁄16 3½ 32 35⁄16 123⁄8 139⁄16 81⁄16 111⁄16 22
6–8 108½ 70½ 32 63 45½ 18¾ 31½ ¼ 73½ 65⁄8 39½ 161⁄16 613⁄16 15⁄8 71½ 59½ 1¾ 42 91⁄16 3½ 24 11⁄16 1811⁄16 16 97⁄16 111⁄16 29
Air
Out
REAR LEFT
Cond
Air
In
Figure 1: Dimension Drawing
Subject to change without notice. 10.20-IM (0818)
AD
1⅛
C
Coil
Access
Panel
Refrigerant
Quick-Connect
Access Panel
Coil
Access
Panel
Condensate
Drain
Filter
Access
Installation, Operation and Maintenance Manual
C13-Series Water-Cooled Package
W
S
T
AG
½
C13-Series
Clearance Hole for
⅜" Hanging Rod
TYP 8 PLS
P
G
H
Evap
Air
Cond
Section
TOP
Service Clearance
All Sizes
Left Side 36"
Right Side 36
Field Installation Power & Control
1 AK
F
K
Wiring
Elect Box
Motor & Blower
Access Panel
Evaporator
Section
B
L M N
Evap
Return
Air
FRONT RIGHT
Supply
J
Out
AJ
In
AH
AE
EAF 5
Elect
Box
Tons B C E F G H J K L M N P Q R S T W AE AF AG AH AJ AK
2–3 56 22 34 119⁄16 20 1 59 7 25 1011⁄16 91⁄16 3¼ 57 40½ 1¾ 30½ 3½ 50 16 12½ 6¼ 91⁄8 13 Ø⅞
4–5 64 25 40 13 9⁄16 25 0 67 81⁄16 31½ 123⁄8 91⁄16 3 65 42½ 1¾ 36½ 3½ 56 16 12½ 6½ 115⁄8 13 Ø11⁄8
6–8 70½ 32 45½ 18¾ 31½ ¼ 73½ 65⁄8 39½ 161⁄16 613⁄16 15⁄8 71½ 59½ 1¾ 42 3½ 56½ 20 16½ 71⁄8 10½ 17 Ø13⁄8
Access Panel
REAR LEFT
Figure 2: Water Cooled Dimension Drawing
Subject to change without notice. 10.20-IM (0818)
Compressor
1⅛
Refrigerant
Quick-Connect
Access Panel
Coil
C
Access
Panel
Condensate
Drain
Filter
Access
Water Piping
In & Out
Installation, Operation and Maintenance Manual
General Information
C13-Series
Inspection Of Equipment
Upon receipt of the unit, inspect for visible or concealed
damage. Report any damage to the carrier, and le a
damage claim�
Handling
To facilitate handling, the unit is set on a wooden skid so that it may be picked up with a two-wheel hand truck or fork lift� Under no circumstances should the unit be “walked” on the corners of the skid� Use dolly trucks or pipe rollers to move the unit to its proper location�
Location
Unit can be installed either as a complete package or split
into two sections. It can be either oor mounted or ceiling
mounted�
Before unit is installed, a thorough study should be made of the structure� Careful consideration must be given to location of wiring, condensate disposal, ductwork and accessibility to the unit for maintenance and servicing� It is necessary that a minimum clearance space be allowed on each side of the unit to accommodate maintenance and servicing�
This minimum clearance must be 36" for all units. Attention must also be given to oor, ceiling or wall load limitations
(See Figure 2)� Location should also provide for condensate removal, trapping and disposal�
Discharge Air from condenser coil should be deected
away from supply air to condenser, to prevent recirculation� See also “Condensing Section Outdoor
Modication Kit” on page 27.
CAUTION
Unit should not be located in space subject to freezing temperatures�
Mounting And Setting In Place
Units can be shipped as an integral package with a tie rail attached to both sides of the unit at each of the four mounting channels�
If unit is not to be split but is to be hung, do not remove
tie rail. Use eld supplied (3/8" minimum diameter) hanging
rods, with proper washers and locknuts, then elevate unit to the exact location where it is to be installed� Fasten the rods
securely to the supporting structure. Install eld supplied
vibration isolation as required� Level unit�
If unit is to be oor mounted and not separated, do not remove tie rails� Locate on a level pad and secure as necessary� Field supplied unit isolation can be installed as required�
Subject to change without notice. 10.20-IM (0818)
Installation
Installation, Operation and Maintenance Manual
C13-Series
1� Air conditioner is shipped assembled and ready for
operation�
2� Unit contains a full charge of R-410a refrigerant�
3� Install unit so that controls and side panels are
accessible to the operator and maintenance personnel�
4� Run the condensate drain line by following the
guidelines on page 11�
5� Electrical Wiring
a� Once the unit is installed, refer to the wiring
diagrams which are provided on the backside of the control box covers�
b� Units are completely internally wired at the factory
for commonly rated supply voltages� Check unit data tags for required voltage, wire and fuse sizing� The factory wiring terminates in two boxes; one each in the evaporator and condensing sections� These control boxes are located behind the outer access panels� Each is supplied with an individual control box cover with a wiring diagram attached inside�
c� All the units are provided with terminal blocks�
d� The power wiring to the unit is to be brought through
one of the available holes for the unit electrical power connection(s)�
e� The control wiring is brought through the holes
provided in the unit�
f� Supply wiring must comply with all National or Local
codes� The power supply must be suitably fused for wire protection�
g� Use copper conductors only� The unit must be earth
grounded using the ground lug provided in the electrical box� Metal conduit is not an acceptable ground�
h� Run the low voltage wiring from the thermostat to the
unit� Connect to low voltage terminal block supplied� See “Thermostat” under “Options”, page 20�
Wire Size1 AWG� Gauge
Note:
1� Solid, Class II copper wire
2� Based on a voltage drop of 1�2 volts per wire�
3� Total wire length is from unit to room thermostat, and
back to unit�
FIGURE 3: Control Wire Sizes
Select a location to install the thermostat to avoid vibration, drafts, sun exposure, or internal heat sources� Use an inside wall�
Split Systems
If the unit was ordered for a split system application each
section will contain male resealable refrigerant ttings. Install the mating female ttings and eld supplied tubing per the
instructions that follow� Note that Optional Interconnect Kits are required for each circuit and external Hot Gas Bypass circuit�
Separation Of Sections
If the unit is to be installed as a split system, the following steps must be carefully followed in performing the separation�
1� Remove evaporator access panel�
2� Using an open-end wrench and turning counter-
clockwise, disconnect the female half of the self­sealing couplings on both the suction and discharge lines� These are located in the bottom left area of the evaporator section� When there is a hot gas bypass option, that connection is to the right of the self-sealing coupling connections� There is one suction line, one liquid line, and one hot gas by-pass line (option) for each compressor�
22 20 19 18 16
40 120 150 190 305
Maximum Wire Length2 Feet
Subject to change without notice. 10.20-IM (0818)
Installation, Operation and Maintenance Manual
C13-Series
INFORMATION
Two circuit units have 2 groups of couplings� It’s a good idea to label or mark the various connections on both the evaporator and condensing sections BEFORE DISCONNECTING THE COUPLINGS to eliminate the possibility of intermixing the circuits when the interconnecting tubing is installed� The suction and discharge lines in the evaporator section will now be dangling, be careful not to damage the tubing connections� Do not disconnect the male half of the self-sealing couplings, which are still attached to the bulkhead of the condensing section�
3� Remove the unit top tie piece*, removing only those
screws which attach the top piece to the two top panels� (*If unit is already shipped split, these are not included�)
4� Remove control box access panels from the evaporator
section and the condensing section by removing the screws at the top and bottom of each access panel�
5� Disconnect and discard the wires which run between
the two internal control boxes� Single circuit units will have two low voltage wires to be disconnected, dual units will have 3 low voltage wires� See Wiring Diagram on the inside of the evaporator control box access panels for disconnecting power wiring�
6� Remove the two unit tie rails attached to the unit
mounting rails on each side of the unit�
7� Carefully pull the evaporator section away from the
condensing section�
8� Verify that the self-sealing couplings are completely
disengaged and not leaking refrigerant�
The sections may now be moved to their individual locations
for installation (either oor-mounted or hung).
Interconnecting Refrigerant Tubing
After the separated sections have been installed, the eld
supplied interconnecting tubing can be run, using the self­sealing couplings supplied in the optional interconnecting tubing kit� For dual circuit units, two kits are supplied� It is recommended that some refrigerant oil be placed on the coupling threads (Item (10), Figure 5), to facilitate threading� The following instructions apply:
1� Hand thread the female halves of the self-sealing
couplings (supplied with the interconnect tubing kit) onto the male couplings (fastened to the unit, Item (5), Figures 4 and 5)� Turn union nut (Item (11), Figure
5), approximately 1 to 1-1/2 turns� This is to make sure that the interconnecting tubing will be routed and
brazed with the self-sealing couplings in their nal proper location, so that there will be no difculty when the nal coupling assembly is made.
2� If there is a hot gas bypass option, connect that
coupling the same way�
3� Run the interconnecting tubing required�
5
4
Figure 4: Disconnect/Connect Self-Sealing Coupling Figure 5: Install/Service Self-Sealing Coupling
Subject to change without notice. 10.20-IM (0818)
10
Coupling Threads
10
13
5
12
13
Metal
15
Seal
14
Rubber
Seal
4
11
Union Nut
Installation, Operation and Maintenance Manual
C13-Series
Always follow accepted industry practices for sizing lines based on line length and elevation differences�
Max� total equivalent line length = 100 ft� (a)
Max� elevation difference between Evap� and Cond� = 40 ft� (a) (b)
Tons Suction Line Liquid Line
2 Ton 3/4 1/2 3 Ton 7/8 1/2 4 Ton 1-1/8 1/2 5 Ton 1-1/8 5/8 6 Ton (2) 7/8 (2) 1/2 8 Ton (2) 1-1/8 (2) 1/2
a� Contact the factory for installations with elevation
differences greater than 40 feet or total equivalent line lengths greater than 100 feet� Alternate line
sizes and specic refrigerant components may be
required�
b� If condensing section is 20 feet or more above the
evaporator include an oil separator for each circuit�
Systems not ordered from the factory to be installed as a split system will contain Female Fittings on the evaporator section� Interconnect kit(s) must be ordered indicating that a Male / Female Kit is required�
United CoolAir Corporation’s C13-Series horizontal units are
provided with unique self-sealing ttings on the refrigerant lines between sections. These ttings or couplings allow the
two-section unit to be separated and reconnected without loosing refrigerant charge�
When installed as a split system, an interconnect kit is required for each refrigerant circuit or hot gas bypass line�
If the unit is dened as a split system when ordered, the ttings will be male ttings on both sections. The interconnect kit will then consist of the matching female ttings. An interconnect kit is required for the eld to connect refrigerant
lines between both sections� Refrigerant piping between the
sections is eld supplied.
The interconnect kit also contains four (4) Schrader ttings.
The installer can place at least one in each refrigerant line or at the end of the refrigerant line� These enable the refrigerant line to be evacuated and charged as needed based on size and length�
In some situations, the desired refrigerant line size may
differ from the self-sealing tting size provided. The line size should be reduced or enlarged at the self-sealing ttings as
necessary
The drawing below illustrates a typical piping arrangement
A� Male self-sealing ttings on unit sections
B� Refrigerant piping between sections (eld-supplied)
C� Female self-sealing ttings in interconnect kit (4)
D� Schrader ttings in interconnect kit (4)
A
Evaporator
Section
A
D
C
D
C
D
B
D
B
C
C
A
Condensing
Section
A
FIGURE 6: Guidelines for Interconnecting Tubing Sizing
5� Disconnect and discard the wires which run between
the two internal control boxes (Item (9), Figure 5)� Single circuit units will have two low voltage wires to be disconnected, dual and triple units will have 3 low voltage wires� See Wiring Diagram on the inside of the evaporator control box access panels (Item (7), Figure
3) for disconnecting power wiring�
6� Remove the two side cross-member angles (Item (1),
Figures 3 and 5; and Item (2), Figure 4)�
7� Carefully pull the evaporator section away from the
condensing section� Double check that the self-sealing couplings are completely disengaged�
The sections may now be moved to their individual locations,
either oor-mounted or hung.
INFORMATION
NOTE: Installations may be made with up to 100 feet equivalent line lengths by installing the recommended tube sizes (See Figure 6) and adding the necessary additional refrigerant, R-410a for the
eld installed line set. (See Step 7, page
10)� For equivalent line lengths greater than 100 ft�, contact the factory for line sizing and additional refrigerant circuit accessories required�
Subject to change without notice. 10.20-IM (0818)
11
Installation, Operation and Maintenance Manual
C13-Series
INFORMATION
IMPORTANT! On units with more than one refrigerant circuit, be careful not to inter­mix liquid, suction and/or hot gas lines of the various circuits� If the connections were labeled before disconnecting the couplings, this should not be a problem� The 6 Ton and 8 Ton units have 2 circuits (with 2 suction line couplings and 2 liquid line couplings)�
CAUTION
When brazing tubing to the self- sealing couplings, use a water-soaked wet rag, running water bath or chill blocks on the quick-connects to prevent overheating the valves and damaging the seals� Always
apply heat toward the eld installed
refrigerant line� Do not apply heat toward the coupling valve and seal�
INFORMATION
NOTE: The interconnect tubing kit (Figure
6) contains a sufcient number of Schrader
access valves to permit installation of one Schrader in each end of both the liquid
and suction lines of the eld supplied
tubing� Each interconnecting line (suction, liquid, or hot gas) must have at a minimum
one Schrader access tting. However for
short lengths of tubing, only one Schrader in each line is necessary�
4� The suction line should be pitched downward to the
compressor, sloping approximately 1/4" every ten feet
to facilitate oil return�
5� “P” traps (eld supplied) are required for all suction
line risers every 15 feet� When the evaporator is above the condensing section, an inverted “P” trap should be incorporated as close as possible to the evaporator
(this minimizes oodback/oil slugging during the off
cycle)� If the condensing section is more than 40 feet
above the evaporator, consult the factory for specic
refrigeration components�
6� Install the Schrader valve ttings into the tubing before
brazing the couplings onto the ends of the tubing� Use
a 1/4" hole to mount the valve. Clean and debur the
tubing before doing any brazing to ensure that no chips or debris are left in the refrigerant circuit� Remove the Schrader valve cap and core before doing any brazing�
7� Leak check line sets with nitrogen at 500 psig� After
brazing the tubing to the self-sealing coupling halves, evacuate each line to 300 microns� Check to make sure that each line holds a vacuum after removal of the vacuum pump (indicating no leaks) (micron level should not go above 500 microns within 10 minutes)� Add the appropriate charge of R- 410a Refrigerant using the Schrader valves� Wipe off coupling seals and threaded surfaces with a clean cloth to prevent the inclusion of dirt or foreign material into the system (See Figure 5)� Lubricate rubber seal (Item (14)) and metal seal (Item (15)) in the male halves (Item (5)) with refrigeration oil� Thread coupling halves together by hand to insure proper mating of threads� Continue to hand-thread each half-coupling to its mating half until resistance is felt (approximately 1-1/2 to 1-3/4 turns)� Complete the connection of the mating half-couplings with a wrench� The suction line couplings will be totally engaged after an additional 5-1/2 to 5-3/4 turns� The liquid line couplings will be totally engaged after an additional 4-1/2 to 4-3/4 turns�
8� Refrigerant piping shall be insulated in accordance with
local codes and / or applicable ASHRAE Standards� Insulation exposed to weather shall be suitable for outdoor use� Provide protection from water and shielding from solar radiation as necessary�
9� Add R-410A refrigerant to the system to compensate
for the additional interconnecting tubing as follows:
a� For 3/8" liquid line – add 0.6 oz. per foot
b� For 1/2" liquid line – add 1.2 oz. per foot
c� For 5/8" liquid line – add 1.8 oz. per foot
Subject to change without notice. 10.20-IM (0818)
12
Installation, Operation and Maintenance Manual
C13-Series
Single Package Unit Wiring
If the system is to be installed as a single package unit route the low voltage wiring through the appropriate hole in the condensing section� A single power supply can be routed through the appropriate hole in the condensing section� The unit is factory wired internally for the evaporator� Refer to the unit data tag for power wiring minimum circuit ampacity and maximum fuse size� Power wiring must be wired through over current protective devices such as a circuit breaker or fused disconnect as required by the National Electric Code� A method to dis- connect main power such as a non-fused service disconnect must be installed within sight of the unit�
Split System Wiring
If the unit was ordered for a split system application (condensing section remote from the evaporator section) each section will require separate power supplies� Route these through the appropriate holes for each section� Power wiring must be wired through over circuit protective devices such as a circuit breaker or fused disconnect as required by the National Electric Code� A method to disconnect main power such as a non-fused service disconnect must be installed within sight of the unit� Route the low voltage wiring through the appropriate holes in the evaporator section� Run the interconnecting low voltage wiring out of the evaporator section and through the appropriate hole in the condensing section�
INFORMATION
NOTE: Make sure to use the appropriate gauge of low voltage wire based on the total wire length so that no more than a 1�2 volt drop is experienced�
Duct Connection
It is recommended to use a ex collar or other means to
isolate any unit vibration from being transmitted to the duct or structure�
Ductwork and plenums shall be insulated in accordance with applicable ASHRAE standards or local codes�
Pressure Switches
High Pressure
This switch shuts the unit down in the event of excessive high pressure in the discharge line� A manual reset is required at the high pressure switch�
Low Pressure
This switch shuts the unit down in the event of excessive low pressure in the suction line�
INFORMATION
NOTE: The low pressure switch(es) are connected to lock-out relay(s)� If the unit goes off on low pressure, the lock-out relay(s) must be reset by switching the thermostat to the “OFF” position and then back to the “COOL” position� Refer to the separate instructions for any units that incorporate a microprocessor for control�
INFORMATION
NOTE: Microprocessor controlled units do not incorporate a lock out relay� After resolving the high or low pressure situation reset the microprocessor as required� Consult separate manual for microprocessor control�
Water-Cooled Condensing Units
Water-Cooled Condenser
The condenser is a tube-in-tube, chemically-cleanable
conguration. The inner tube carries the water and the outer
tube the refrigerant�
Water Piping and Connections
Do not reduce the water pipe sizes from the factory connections on the unit� Both the water inlet and outlet
of the condensing section should be equipped with eld
supplied shut off ball valves� This is needed for shutdown of water supply during long periods of unit shutdown and/or condenser removal, if required�
INFORMATION
The condensate drain line should not be connected to the condenser outlet,
as ooding is likely to occur. Provisions
should be made for ease of piping cleaning by using plugged tees at all turns, rather than ordinary elbows�
Subject to change without notice. 10.20-IM (0818)
13
Installation, Operation and Maintenance Manual
C13-Series
Hook Up
Each refrigerant circuit requires 3 gallons per minute (GPM) of water per ton of refrigeration� If the unit does not have water regulating valves or head pressure control valves
eld supplied balancing valves may be required. For future
reference when cleaning is needed, record details on temperatures entering and leaving the heat exchanger and the pressure drop as a new installation during the initial unit start-up� See “Cleaning The Water-Cooled Condenser” on page 13�
Water Connection
Install and connect a fresh water strainer (eld supplied) to
the water inlet line� Strainer should be readily accessible for periodic cleaning� Shut-off valves on both strainer inlet and outlet are recommended to facilitate cleaning�
CAUTION
High inlet water temperature or low water
ow rate may result in nuisance tripping of
the high pressure switch�
CAUTION
Water-cooled units with a glycol cooling
uid will require a higher GPM / Ton ow
rate� Contact the factory for details�
Condensate Drain Connection
Units are equipped with two 3/4" IPS drains; one for the
evaporator condensate; one for the condensing section� All units require evaporator section drains to be installed� Heat pumps and water cooled condensing units also always require the installation of a condensing section drain� Units with air-cooled condensers need a condensing section drain when units are installed in areas which may permit rain to enter� It is EXTREMELY IMPORTANT that the lines attached to these connections contain a trap, to ensure positive draining� It is highly recommended that the trap be primed with water prior to start-up�
The drain lines must be trapped because the coils are located on the negative sides of the blowers� The purpose of the condensate trap is to neutralize the negative pressure created within the cabinet by the blower�
This negative pressure can vary from less than 1" up to 2" column. The condensate trap must be of sufcient depth in water column to permit the condensate to ow from the drain
pan (See Figure 7)�
The “A” dimension must equal or exceed the negative static pressure developed by the supply air blower� If it does not,
the condensate will not drain properly and may overow the drain pan. The trap must be at least 2-1/2" deep to maintain
a water seal under all operating conditions, especially during blower start-up�
INFORMATION
NOTE: Optional Head Pressure Control Valve(s) should be incorporated into the
unit circuit(s) if the cooling uid will be less
than 65°F
WARNING
Water cooled units are for use with fresh water application only� Do not use for brackish water or salt water unless appropriate condenser has been installed as an option�
Subject to change without notice. 10.20-IM (0818)
Unit
"A"
2-1/2"
Figure 7: Condensate Trap Installation
14
Loading...
+ 31 hidden pages