Unitech UT-1404 Operation Manual

Model No. : UT-1404
z
OPERATION MANUAL
z
CLEAN ROOM INDICATOR TEMP+HUMIDITY (RH)
Model No. : UT-1404
LO
HI
LO
HI
22.3
35.8
UP/ACK.
PASS
COM.
ENTER
B
%
C
COM
AL 1
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
F F F F F F F F F
zz
INTRODUCTION FRONT PANEL DESCRIPTION TECHNICAL SPECIFICATION INSTALLATION TERMINAL ARRANGEMENT PROGRAMMING FLOW CHART OPERATION 5 ERROR MESSAGE AND TROUBLESHOOTING 8
CONTENTS
1 2 3 3 4
8REGISTER ADDRESS FOR MODBUS
zz
The UNITECH “HVAC TEMP+RH Indicator : UT-1404” is specially designed to indicate the Room Temp & HUMIDITY of process areas. The large 3 digit, 1.0” high LED display is easy to read, even from a distance, which can help the user to monitor the Temp and to take necessary actions to maintain the room conditions as per the requirement or application.
It has internal keypad to programming the instrument. It has Stainless steel Face plate, which is designed for wall mount Clean Room indication where you need easy mounting mechanism. This instrument enables you to measure the Temp & Humidity in the following fields:
INTRODUCTION
HVAC (Heating, ventilation, Air conditioning, cooling) Pharmacy industry. Blood stations, pharmacies. Horticultural and cultivation of plants.
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
PAGE:1
2
3
zz
FRONT PANEL DESCRIPTION
5
LO
1
HI
LO
HI
22.3
35.8
COM.
B
%
C
4
CAUTION
THE PRODUCT CAN BE MOUNTED ON TILTED OE HORIZONTAL
INSTALLATION MOUNTING PRECAUTIONS
PANEL USING THE MOUNTING CLAMPS SUPPLIED. PROPER
SPACE MUST BE AVAILABLE AT THE BACK OF THE PANEL FOR
INSTALLATION AND MAINTENANCE ACTIVITY.
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULT
IN INSTRUMENT DAMAGE
KEY PAD
PASS
UP/ACK.
ENTER
MODE
NO DISPLAY
1
2
3 4
5
KEY
888
Low
High Com.
Sensor
PARTICULAR
MODE/
M
FUNCTION
ENTER
UP/INCREMENT
DESCRIPTION
Seven Segment LED displays of Temp & RH
Red LED will glow on low Process values of ºC,%Rh
Red LED will glow on high Process values of ºC,%Rh. Red LED will blink when there is a Communication.
Internal T+RH Sensor if applicable.
DESCRIPTION
Press to access the programmable
Press to accept modified digit or in Programming Mode.
Press to increase selected digit or value in
value
ACK.
Programming Mode. & ackl. Buzzer sound
Press to change digit selection or Pass
PASS
selected value in Programming Mode.
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
PAGE:2
z
FDA 21 CFR part 11 - GAMP-4 compatible. Microcontroller based indicator with inbuilt Temperature & RH measurement in single enclosure. Incorporates highly stable built-in or Remorte Temp.+ RH sensor. 3 Digit, 0.80" bright LED display for displaying RH & Temperature. Process parameter Hi and Low tatus indication For channels, if applicable. User selectable set limits for process value violation. Inbuilt buzzer to audible process value violation. Password protection for calibration and programming mode. Software Calibration for 2 channels. MODBUS RTU multi drop RS-485 serial communication for PLC, SCADA, etc. Programmable devise address, baud rate, (max no. of device is 1-256). Remote programmable from master device. User programmable offset correction. Compact, All Stainless Steel enclosure with 35 mm depth for installation in prefab panels. Brick and modular wall mounting and flush mounting. FDA21 CFR part 11 compliance data logging software available
Technical data
Input
Indication
Range
Accuracy
Comunication
Programmable
Parameters
Other
Supply voltage Power consumption
Operating ambient temperature and humidity
Flame
Proof
Technical Specification
Material of constructions
TECHNICAL SPECIFICATION
z
LEDs. S both
.Ex. Flameproof model available for Hazardous applications.
Nos. of input
Temperatures input
Humidity input
Transmitter power supply
Temperatures
Humidity
Status indication
Temperatures
Humidity
Display Resolution
Temperatures
Humidity
Communication Protocol
Programmable parameter
Read /write parameter Read: Procces value ,decimal point. Write: Hi Low set point.
No. of slave ID
Set point / High scale / Low scale
Programming of parameters
Alarm logic
Mounting
MOC
Gas group
Enclose certification
Display glass
Degree protection
Cable entery
2 nos .(TEMP + RH )
Integral Or Remote (external)
Integral Or Remote (external)
24V/5V DC @ 30 mA max, isolated from I/p & O/P.
Channel-1 : 3 digit Seven segments 1.0” RED display.
Channel-2 : 3 digit Seven segments 1.0” RED display.
3-LEDs for visual alarms & LED for 485-comm.
0 to 60.0 with decimal point.
0 to 99.9 % with decimal point.
0.1 for Temp. & Rh
+10.25 % on FS Response time : sec
+ Response time : 4 sec2.5 % for 10 to 90 % RH rest of 3%
Modbus RTU RS- 485 Isolated communications. Baud rate , Parity , Node address , stop bit.
Total 1-256 unit.
Full range as per input selection.
Through 4 tactile keys (with password protections)
Full Scale hi OR Full scale Low
Bricks and modules wall Flush panel mounting.
Full S S 316 plate and box , back side wall mounting M S covers. 24 V DC @ 4 watts maximum
- 0~50 °C
I IIA IIB as per IS 2148/1981
Enclosure is certifies by C.M.R.I. dhanbad
Clear glass thognet type A as per Is 2206
IP 65 as per IS 2147 Aluminum alloy
5x3/4“ET
°C
- Below 90%, non condensing
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
PAGE:3
zz
INSTALLATION
Terminal Detail
z
VDC -
COMM. RS-485
COM +
COM -
TERMINAL CONNECTION
VDC +
SUPPLY
24VDC
CAUTION WIRING CONSIDERATION
SHIELDED TWISTED PAIR WIRE IS USED FOR ALL ANALOG I/P, PROCESS SENSORS, RTD, THERMOCOUPLE, DC mV-mA, VOLT DC, LINEAR INPUT AND COMMUNICATION
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULT IN INSTRUMENT DAMAGE
z
VDC +
SUPPLY
24VDC
COM +
COMM. RS-485
POWER SUPPLY : 24VDC Supply Voltage.
VDC -
COMMUNICATION : RS-485 interface Terminal
COM -
CAUTION LINE VOLTAGE
THIS PRODUCT IS SUITABLE FOR CONNECTION 110/230VAC, 50HZ OR 12/24 VDC MAIN POWER SUPPLY. IT IS USER RESPONSIBILITY TO PROVIDE PROPER PROTECTION FOR THE PRODUCTS ELECTRICAL PROTECTION .
WHEN APPLYING POWER TO VARIOUS INSTRUMENTS, MAKE SURE SUFFICIENT CURRENT IS SUPPLIED. OTHERWISE THE INSTRUMENTS MAY NOT START UP DUE TO THE VOLTAGE DROP.
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULT IN INSTRUMENT DAMAGE
NOTE : FOR INTERNAL SENSOR TEMP / RH / DP TERMINALS ARE NOT AVAILABLE
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
PAGE:4
Mode
Selection
MOD
M
zz
Configuration
PROGRAMMING FLOW CHART
Change
Password Mode
CPS
oPS
000
nPS
888
Any New Password
*
oFt
Mode
COn
000
Tt1
LoN
Tt2
HoN
rt1
LoN
rt2
Setup
Mode
set
000
ts1
03.0
tH1
00.2
ts2
05.0
tH2
*
Password Protected
HoN
nAd
001
bud
96h
bud
96h
Prt
non
00.2
rs1
03.0
rH1
00.2
rs2
05.0
rH2
00.2
ztp
00.0
000
TML
1.0
zrh
00.0
srh
10.0
ofr
000
rML
1.00
WARNING
PROGRAMMING PARAMETER SHOULD BE ACCESSED ONLY
INJURY
BY PERSONNEL WHO ARE TECHNICALLY COMPETENT TO DO
SO. LOCAL REGULATIONS REGARDING ELECTRICAL & SAFETY
MUST BE OBSERVED
FAILURE TO COMPLY WITH THESE INSTRUCTION COULD BE
RESULT IN SERIOUS INJURYORDEATH
stp
10.0
Password Protected
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
LtM
030
E-mail :
sales@utplindia.in
Model No. : UT-1404
1. CONFIGURATION MODE
This Mode is used to change Alarm and Communication Operation Configuration
CONFIGURATION MODE PARAMETER
PAGE:5
CON
Parameter
CON
000
Tt1
LoN
TS2
HoN
rt1
&
rt2
Description
Password for Parameter Setting
Scroll the digit by key, increase by key.
Password for Configuration Parameter
Alarm 1(Light) Indication. [Temp]
Change the type by or key.
LON:
HON:
OFF
ON
OFF
SV+Hyst
ON
SV-Hyst
SV
SV
PV
PV
Alarm 2 Action. [Temp]
Change the type by or key.
Active same as above
If Applicable.
Alarms - 1 & 2 Action for [RH]
Increase digit by key, decrease by key
If Applicable.
Range
Values between
LoN
HoN
LoN
HoN
LoN
HoN
: Active in Low
: Active in High
: Active in Low
: Active in High
: Active in Low
: Active in High
000 to 999
Default Value
000
LoN
LoN
LoN
nAd
001
UNT
MM
bud
96h
prt
non
Node Address
Increase digit by key, decrease by key
Device address for Communication
Pressure Unit
Change the type by or key.
Not Applicable in this Instrument
Baud Rate
Change the Rate by or key.
Parity
Change the type by or key.
Parity check for Communication
Values between
:PASCAL
PA
:mmWC
MM
48h : Baud rate 4800 96h : Baud rate 9600 192 : Baud rate 19200
Evn : Even Parity odd : Odd Parity non : None
001000 to 255
MM
96h
non
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
2. SETUP MODE
This Mode is used to Setting the instrument Parameter. To set zero span value, alarm set points with hysteresis, offset etc.
PAGE:6
Parameter
SET
000
ts1
03.0
tH1
00.2
ts2
05.0
SETUP MODE PARAMETER
Description
Password for Parameter Setting
Scroll the digit by key, increase by key.
Password for Setup Parameter
Alarm - 1 setpoint [Temp]
Scroll the digit by key, increase by key. Display value at low Calibration point.
Alarm - 1 Hysteresis. [Temp]
Scroll the digit by key, increase by key. Display value at high Calibration point.
Alarm - 2 setpoint. [Temp]
Scroll the digit by key, increase by key. Display value at low Calibration point.
sET
Range
Values between
Values between
000to999
/99to999
/99to999
/99to999
Default Value
000
03.0
00.2Values between
05.0Values between
tH2
100
rs1
03.0 rH1
00.2
rs2
05.0 rH2
100
Alarm - Hysteresis.2[Temp]
Scroll the digit by key, increase by key. Display value at high Calibration point.
Alarm - 1 setpoint [RH]
Scroll the digit by key, increase by key. Display value at low Calibration point.
Alarm - 1 Hysteresis. [RH]
Scroll the digit by key, increase by key. Display value at high Calibration point.
Alarm - 2 setpoint. [RH]
Scroll the digit by key, increase by key. Display value at low Calibration point.
Alarm - Hysteresis.2[RH]
Scroll the digit by key, increase by key. Display value at high Calibration point.
/99to999
/99to999
/99to999
/99to999
/99to999
00.2Values between
03.0Values between
00.2Values between
05.0Values between
00.2Values between
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
PAGE:7
Parameter
ztp
00.0
stp
10.0
oft
000
tML
1.00
Description
Zero Value. [Temp]
Scroll the digit by key, increase by key. System Value, don’t change.
Span Value. [Temp]
Scroll the digit by key, increase by key. System Value, don’t change.
Offset to Process Value. [Temp]
Scroll the digit by key, increase by key.
This value Increase OR Decrease the Display PV
System Parameter.
Scroll the digit by key, increase by key.
System Value, Don’t Change.
Range
Values between
Values between
/99to999
/99to999
to
/99
/99
to
999
999
Default Value
00.0Values between
10.0Values between
000
1.0
zrh
00.0
srh
10.0
ofr
000
rHL
1.0
LtM
030
Zero Value. [RH]
Scroll the digit by key, increase by key. System Value, don’t change.
Span Value. [RH]
Scroll the digit by key, increase by key. System Value, don’t change.
Offset to Process Value. [RH]
Scroll the digit by key, increase by key.
This value Increase OR Decrease the Display PV
System Value. [RH]
Scroll the digit by key, increase by key.
System Value, Don’t Change.
System Gain Value.
Scroll the digit by key, increase by key.
System Value, Don’t Change.
Values between
Values between
Values between
/99to999
/99to999
to
/99
/99
/99
to
to
999
999
999
00.0Values between
10.0Values between
000
1.0
030
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
Model No. : UT-1404
4. CHANGE PASSWORD MODE
PAGE:8
CPS
Range
000
000
to
to
Parameter
oPS
000
nPS
000
CHANGE PASSWORD PARAMETER
Description
Old Password.
Scroll the digit by key, increase by key.
Existing Password
Values between
New Password.
Scroll the digit by key, increase by key.
New Desired Password
zz
ERROR MESSAGE AND TROUBLESHOOTING
Values between
Symptom Probable Solution
999
999
Default Value
0000
----
As reqd.
OPn
Keypad no
function
All LED’s
and display
not light
-Sensor break error
-Sensor not connected
-Keypads are locked
-Keypads defective
-No power to controller
-Control circuit failure
-Replace sensor
-Check the sensor is connected correctly
-Check Keypad continuity?
-Replace keypads
-Check power lines connection
-Check Control Supply Voltages.
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Website:
www.utplindia.in
E-mail :
sales@utplindia.in
SR NO PARAMETERS ABSOLUTE ADDRESS ACCESS TYPE
1 TEMP. PROCESS VALUE 40001 READ ONLY 2 RH PROCESS VALUE 40002 READ ONLY 3 SETPOINT 1 LOW 40003 READ / WRITE 4 SETPOINT 1 HIGH 40004 READ / WRITE 5 SETPOINT 2 LOW 40005 READ / WRITE 6 SETPOINT 2 HIGH 40006 READ / WRITE
Model No. : UT-1404
PAGE:09
zz
zz
REGISTER ADDRESS FOR MODBUS RTU PROTOCOL
DEFAULT COMMUNICATION DETAILS
BAUD RATE
PARITY
DATABIT
STOP BIT
NODE ADDRESS
9600
NONE
8
1
1
Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara Ph : +91 7046223333
Sales:
+91 94273 01436
Sure for service with hi-end versal nologyUni TechSure for service with hi-end versal nologyUni Tech
Website:
www.utplindia.in
E-mail :
sales@utplindia.in