Unitech UT-101 F Operation Manual

Model No. : UT-101 F
z
OPERATION MANUAL
z
UNIVERSAL PROCESS INDICATOR / CONTROLLER
CH-1
AL-1
AL-1
CH-1
AL-2
AL-2
M
O
C
-1
L
A
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
UNIVERSAL INDICATOR/CONTROLLER
F F F F F F F F F F F
zz
INTRODUCTION FRONT PANEL DESCRIPTION TECHNICAL SPECIFICATION INSTALLATION TERMINAL ARRANGEMENT PROGRAMMING FLOW CHART OPERATION 5 ERROR MESSAGE AND TROUBLESHOOTING 8 PANEL CUTOUT 9
zz
CONTENTS
1 2 3 3 4
9REGISTER ADDRESS FOR MODBUS 9CALIBRATION VALUES
INTRODUCTION
Unitech Instrument’s Universal Indicator is designed to accept thermo-couple or RTD or Linear Input and displays the process parameter through a 4 Digit Red LED Display.
The instrument is available in a panel mounted housing which requires a cut out as per Panel cutout Dimensions given later . A variety of power supply options are available for this. The instrument has low drift precision components for long trouble free operation. The instrument is a jumper less system. There are different types of modes such as normal mode, operation mode, configuration mode, setup mode, and change password mode. 4 keys provided can do any change in the mode.
The instrument can be configured for RTD or Thermocouple or Linear input by making changes in configuration mode using 4 keys provided. This instrument can operate with full range for all inputs.
“Sure for service with hi-end versal nology”Uni Tech
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
+91 94273 01436
Sales: Email :
Sales: Email :
Website:
Website:
www.unitechinstrument.com
www.unitechinstrument.com
Sales@unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
PAGE:1
SR
NO
1
zz
DISPLAY
8888
FRONT PANEL DESCRIPTION
*C
*C
AL-1 AL-2
COM.
UT-101 F-F
UT-101 F-F
DESCRIPTION
PV
Seven Segment LED display
SR
2
3
4
5
8
9
10
NO
PV
AL1
AL2
COM
KEY
M
Actual Process Value
Red LED will glow on Relay 1 activation. (If Applicable)
Red LED will glow on Relay 2 activation. (If Applicable)
Red LED will blink when there is communication.
(If Applicable)
PARTICULAR
DESCRIPTION
Press to access the programmable
FUNCTION(M)
Parameter.
(UP)
Press to increase selected digit or value in Programming Mode.
Press to change digit selection or selected
(PASS)
value in Programming Mode.
11
ENTER
Press to accept modified digit or in Programming Mode.
Press to Change Set point Value. Change up
12
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
M
“Sure for service with hi-end versal nology”Uni Tech
Set Point
Website:
www.unitechinstrument.com
and down when decimal dot blinking
Sales@unitechinstrument.com
value
Model No. : UT-101 F
PAGE:2
z
TECHNICAL SPECIFICATION
INPUT
TYPE RANGE RANGETYPE
Technical Specification
Input Type
Special on demand :
Input
Transmitter power supply
Cold junction comp. & Sensor break ind.
Range limits
Accuracy
Input impedance
Indication
Indication
Status indication
z
4 to 20mA -1999 to 9999K-Type T/C -50 to 1200 ºC 0 to 20mA -1999 to 9999J-Type T/C -50 to 750 ºC
0.5 to 2.5V -1999 to 9999R-Type T/C 0 to 1750 ºC 1 to 5V -1999 to 9999S-Type T/C 0 to 1750 ºC 0 to 10VDC -1999 to 9999T-Type T/C 0 to 400 ºC SPECIAL -1999 to 9999E-Type T/C -50 to 500 ºC Cu 53 -50 to 250 ºCRTD PT-100 -50 to 400 ºC
T/C
RTD
Currant
Voltage
200 mV 1000- /300V DC
24 V DC @ 30 mA max, isolated from I/p & O/P.
Software base Automatic.
As per input range Table.
+L+0.1 % of span for inear & RTD , 0.25 % for T/C
>330 K for Voltage ,mV, and T/C, 100 for current.ΩΩ
4 Digit 7 Segment display 0.56”
LEDs for Relay status & Communications
.
K, J, R, S, E, N, T
.
. .
Pt100, Cu53 ( 2wire & 3 wire)
. .
0 ~ 20mA dc , 4~20mA DC
.
.
0-5V/1-5V, 0.5 -2.5V/0- DC10 V
0- & 0- /300/V DC,0-75/75/200 mV 1/10V/100
Resistence
.
.
0-500 Ω , 0-1/5/10 KΩ, 1MΩ
Control Mode
Output
Comunication
Programmable
Parameters
Other
(A) (B)Supply voltage Power consumption
On Off control
Dead Band controls
Relay Output
SSR Output
Retransmition Current & Voltage outputs
Communication Protocol & mathode
Programeble parameter & Connectable number
Wireless comunication
Setpoint / Hysteresis / High scale / Low scale
Relay logic
Display resolution
Programming of parameters
(A) (B) (C)Dimensions Panel cutout Mounting
Operating ambient temperature and humidity
Relay / SSR
High and Low Set point for level applications.
NO - C - NC Contacts , 5A@240 V AC Resistive
1/2/3/4Relays/SSRoutput
24VDC @ 20 mA ,12VDC @ 20 mA
0~20/ 4~20 mA,
Modbus RTU RS- 485/RS- 232 communications.
Baud rate , Node, Parity , nodeaddress , stop bit. & 0-256 unit.
GSM/GPRS base mobile(sms) communications.
Full range as per input selection.
F.S. igh & owH L alarm
-1.999 to 9999 fully configurable for linear input
Through 4 tactile keys
(A) (B) (C)96(H) x 96(W) x 100(D) 92 x 92 Panel mounted
0~50 °C
0~5V, 0~10V, 1~5V DC, fully 3 port isolated
Deadband alarm.
V AC, 50/60 Hz 4 watts maximum(A) 110/230 (B)
Below 90%, non condensing
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
PAGE:3
zz
INSTALLATION
12345678910 PN
SUPPLY
CBA
T/C- T/C-T/C+
RTD
T/C
+
--
z
1. Phase
2. Neutral
3. RTD-Red wire, TC +
4. RTD-White wire, TC-
+mA
4~20mA 0~10VDC
-mA/-V
+V
+TPS
24VDC
-TPS
D+ D-
RS-485
TERMINAL ARRANGEMENT
11 12 13 14 15 16
NC1 C1 NO1
RELAY
+OP -OP
OUTPUT
4-20mA
z
5. RTD-White wire, TC-, -mA, -V
6. +mA [4-20 / 0-20mA]
7. +V [0-10 / 0-5 / 1-5 / 3.5V]
8. +TPS [24VDC]
9. -TPS [24VDC]
10. D+ [RS-485]
11. D- [RS-485]
12. NC
13. C [RELAY]
14. NO
15. OUTPUT [OP+]
16. OUTPUT [OP-]
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
PAGE:4
Mode
-
MODE
PRESS + KEY
M
zz
Configuration
PROGRAMMING FLOW CHART
Mode ModeSelection
COnf
0000
1NP
PT-1
TSP1
LoN
TSP2
LoN
dp
Setup
setp
0000
ZERO
0000
span
1000
SP1
0300
Hys1
Calibration
Mode
CAL
0000
CALZ
CALS
CALL
CALH
Password Protected
CALA
Change
Password Mode
CPAS
oPAS
0000
nPAS
8888
Any New Password
*
*
0001
DEAD
no
nadd
0001
baUd
9600
CTYP
LEAN
oFFS
0005
CA1nV
Password Protected
0002
SP2
0500
HYS2
0002
oFST
0000
oP-L
0000
oP-H
1000
NOTE :
Default Password will be 0000
Protected Parameter Password will be 1111
Password Protected
0006
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
1. CONFIGURATION MODE
This Mode is used to change Input , Relay and Communication Operation Configuration
CONFIGURATION MODE PARAMETER
PAGE:5
CONF
Parameter
Mode
0000
1NP
pt-1
TSP1
L oN
TSP2
L oN
Description
Password for Parameter Setting
Scroll the digit by key, increase by key.
Password for Configuration Parameter
Input Type
Down the type by key or Up by key.
Selection of input of the Instrument.
Alarm 1 Relay Action.
Changethetypeby or key.
LON:
HON:
OFF
OFF
ON
SV
ON
SV-Hyst
SV+Hyst
SV
PV
PV
Alarm 2 Relay Action.
Changethetypeby or key.
Active same as above
Range
Values between
JTC.
: ‘J’ Type Thermo-Couple
4
. TC
: ‘K’ Type Thermo-Couple
R TC.
: ‘R’ Type Thermo-Couple
STC.
: ‘S’ Type Thermo-Couple
TTC.
: ‘T’ Type Thermo-Couple
4-20 : Linear4-20mADC 0-20 : Linear0-20mADC
. : Linear 0.5-2.5 V DC25v
1-5v :Linear1-5VDC
: Linear0-10VDC10v
CTC.
: ‘C’ Type Thermo-Couple
pt-1 : PT-100 (RTD) CU53 : CU-53 COPPER SENSOR ETC.
: ‘E’ Type Thermo-Couple
: Active in Low
LoN
: Active in High
HoN
: Active in Low
LoN
: Active in High
HoN
0000 to 9999
Default Value
0000
Pt-1
(As per Reqd.)
LoN
LoN
: No decimal(1234)
DP
0001
dEAd
Decimal Point Selection
Increase digit by key, decrease by key
Dead Band
Changethetypeby or key.
no
nAdd
Only one relay get operated in this parameter, relay get active on set point 1 value and deactive in set point-2value. Used for Level & Fan control.
Node Address
Increase digit by key, decrease by key
0001
baud
9600
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Device address for Communication
Baud Rate
Change the Rate by or key.
“Sure for service with hi-end versal nology”Uni Tech
Website:
www.unitechinstrument.com
0000
: One decimal(123.4)
0001
: Two decimal(12.34)
0002
: Three decimal(1.234)
0003
: Selected
YES
: Not Selected
no
Values between
4800 : Baud rate 4800 9600 : Baud rate 9600 192K : Baud rate 19200
Sales@unitechinstrument.com
0001
no
00010000 to 0127
9600
Model No. : UT-101 F
PAGE:6
Parameter
pr1t
nonE
CTYP Lean
offs
Ca1n
v
2. SETUP MODE
This Mode is used to Setting the instrument Parameter. To set zero span value, alarm set points with hysteresis, offset etc.
Parameter
Description
Parity
Change the type by or key.
Parity check for Communication
Display Calculation
Note : Factory set value
Offset Factory set Value.
Gain Factory set Value
SETUP MODE PARAMETER
Description
Range
EvEn : Even Parity
odd : Odd Parity
nonE : None
: Linear Type
Lean
sETP
Range
Default Value
none
LeaN
0005
0006
Default Value
Mode
0000
zero
0000
span
1000
SP1
0300
Hys1
0002
SP2
0500
Password for Parameter Setting
Scroll the digit by key, increase by key.
Password for Setup Parameter
Zero or Low Display Value.
Scroll the digit by key, increase by key. Display value at low Calibration point.
Span or High Diaplay Value.
Scroll the digit by key, increase by key. Display value at high Calibration point.
SetPoint#1
Increase digit by key, decrease by key
Activation value for Relay - 1
Hysteresis # 1
Increase digit by key, decrease by key
Value Difference between Activation and De­activation of Relay - 1
SetPoint#2
Increase digit by key, decrease by key
Activation value for Relay - 2
Values between
Values between
Values from to
Values from to
Values from to
0000to9999
4999to9999
4999to9999
0000
0000
0100Values between
999.9000.0
999.9000.0
999.9000.0
030.0
000.2
050.0
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
PAGE:7
Parameter
Hys1
0002
ofst
0000
oP-L
0000
oP-H
1000
Description
Hysteresis # 2
Increase digit by key, decrease by key
Offset to Process Value.
Scroll the digit by key, increase by key.
This value Increase OR Decrease the Display PV
Output Low
Increase digit by key, decrease by key
Process Value at 4 mA signal output.
Output High
Increase digit by key, decrease by key
Process Value at 20 mA Signal output.
Range
Values from to
Values from to
Values from to
Values from to
Default Value
999.9000.0
999.9000.0
999.9000.0
999.9000.0
000.2
000.0
000.0
100.0
3. CALIBRATION MODE
This Mode is used to Calibration of the Instrument.
Parameter
Mode
0000
CALZ
----
CALs
----
CALIBRATION MODE PARAMETER
Description
Password for Parameter Setting
Scroll the digit by key, increase by key.
Password for Calibration Parameter
Calibration Zero.
Apply low signal (from input table) input and press key.
Calibration Span.
Apply High signal (from input table) input and press key.
CAL
Range
Values between
According to Input type.
for Thermocouple(T/C) set 0.0mV for Zero Cali.
According to Input type.
for Thermocouple(T/C) set 42.0mV for E,J,K-T/C for
Span Cali. set 18.0mV for R,S,T-T/C for
Span Cali.
0000to9999
Default Value
0000
----
----
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
PAGE:8
PASSWORD PROTECTED PARAMETER
Parameter
CALL
Strt
CALH
Strt
CALA
0032
4. CHANGE PASSWORD MODE
Description
Calibration Output Low.
Set the output by and key, Press key to fix the desired output.
Calibration Output High.
Set the output by and key, Press key to fix the desired output.
Calibration Ambient.
Set the Ambient by and key, Press keytofixtheambienttemp.
Range
Default Value
----According to output.
----According to Output.
----According to Output.
CPAS
Range
0000to9999
0000to9999
Parameter
oPAS
0000
nPAS
0000
CHANGE PASSWORD PARAMETER
Description
Old Password.
Scroll the digit by key, increase by key.
Existing Password
Values between
New Password.
Scroll the digit by key, increase by key.
New Desired Password
zz
ERROR MESSAGE AND TROUBLESHOOTING
Values between
Symptom Probable Solution
OPEn
Keypad no
function
All LED’s
and display
not light
-Sensor break error
-Sensor not connected
-Keypads are locked
-Keypads defective
-No power to controller
-Control circuit failure
-Replace sensor
-Check the sensor is connected correctly
-Check Keypad continuity?
-Replace keypads
-Check power lines connection
-Check Control Supply Voltages.
Default Value
0000
----
As reqd.
“Sure for service with hi-end versal nology”Uni Tech
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Model No. : UT-101 F
SR NO ANALOG PARAMETERS ABSOLUTE ADDRES ACCESS TYPE
1 PROCESS VALUE 40001 READ ONLY 2 DECIMAL POINT 40002 READ ONLY
3 SETPOINT - 1 40003 READ/WRITE 4 SETPOINT - 2 40004 READ/WRITE 5 RELAY 1 STATUS 40005 READ ONLY
6 RELAY 2 STATUS 40006 READ ONLY
INPUT ZERO-VALUE SPAN VALUE J - T/C 0100-0600 6000-7800
K - T/C 0800-1000 6000-7800 R - T/C 0800-1000 6000-7800
S - T /C 080 0-100 0 6000 -7800 T - T /C 0800-1000 6000-7800
4 - 20 mA 0100-0600 6000-7800 0 - 20 mA 0100-1000 6000-7800
1 - 5 VDC 0100-1000 6000-7800
10 V DC 0100-1000 6000-8000
PT-1 00 9 00-15 00 2000-3000 E - T/C 080 0-100 0 6000 -8000 C - T/C 0800-1000 6000-8000
PAGE:9
zz
REGISTER ADDRESS FOR MODBUS RTU PROTOCOL
zz
CALIBRATION VALUES
*
Add.-503/504,Helix Complex , Opp. Surya Hotel, Sayajigunj, Vadodra-05. Gujrat. INDIA, PH-0265 6623551
+91 94273 01436
Sales: Email :
“Sure for service with hi-end versal nology”Uni Tech
* Span Calibration at 100ºC
Website:
www.unitechinstrument.com
Sales@unitechinstrument.com
Manufacturers of process Controls Instruments Process automaton (PLCs ,HMI , SCADA,servo,drives)
Sure for service with hi-end universal technology
Manufacturers of process Controls Instruments
SMARTCLEAN ROOM INDICATOR
AL-1
AL-2
COM
S.F./R.F.
TEMP. PRES.
-Www.unitechinstrument.com
TEMPRETURE+RH
Temp. Sensor and temp.2 wire transmitter
Single channel universal indicator controller Dual channel universal indicator controller Multy channel temp indicator(4,8,12,16,20) PID and PROFILE controller Temp. Scanner with software (4,,8,12,16,20) data logger with pc software (4,8,12,16,20) Temp.+Rh transmitter (sensor) Temp.+Rh indicator cum controller Humidity sensor/ indicator/ controller
SCADA SOFTWARE
This software gives you access to real time process parameters in numeric and graphical form. It is a pre-engineered software package that provides all benefits of on line data logging and trending, the software can interface with multiple scanners, indicator.pid,plc,and data acquisitions systems using. multidrop Rs485 communication. With the feature of historical data logging function the entire precess history can be recorded for future analysis or validation.
LEVEL
Flow Metering Systems(volume / mass)
Temp. & pressure & vacuum & magnehelic gauge
PH sensor indicator(on line & table top ) Synchronized Digital Clocks / masters and slaves
FLP temp scanner and data loggers with software
Temp.+humidity indicator Controller.
Instruments calibration ( ARC/AMC/validation )
H
FLOW RATE-122.65
RATE-122.65
FLOW
TOT- 12345678.25
AL-4
AL-3
AL-2
AL-1
F
/R F S
.
S
E
R
P . P
M
E
T
TOT- 12345678.25
COM
CH-1
-2 H C
3
­H C
4
­H C
CH-1
2
­H C
3
­H C
-4
H
C
FLOW
Flow : Rate/Totlizer/Comuper/Batch
Orifice Flow Meter ((NG) gas / steam) Steam Flow meter Natural gas & standard gas Flow meter Thermel Dispenser Air Flow Meter Magnetic Flow Meter (water) Ultrasonic Flow Meter
Low cost ½”& 1” Air/Gas Flow meter
Flow indi.& Cont. (4-20 mA & frequency) Flow indicator & Totalizers (universal-i/p) Batch indicator cum controller Natural Gas flow computer (as per AGA3)
- On line temp.& Pressure compensation) Steam flow computer (saturated &superheated)
- On line temp.& Pressure compensation)
SCADA software (Online and Offline Report / Trend / part lading ) for flow analysis
CLEAN ROOM/HVAC /PHARMA
Diffrancial pressure swich and sensor
Temp.+humidity transmitter FLP temp indicator & contr.
AHU control panel with SCADA
Conductivity sensor indicator
Temp.+RH +dp clean room indicator with sensor
Control valve (on/off & modulating)
We can gives all instruments in SS or flame proof panels and box
PRESSURE
Isolator /convertor
C
NITE U
CH-1
CH-2
3
­H C
-4
H
C
UNITECH
High pressurizes tank level indication sys. Differantial pressure type level indicator. Ultrasonic level transmitter & controller
Conductivity level transmitter & contr. Water Level Control systems. Level Switch/Sensor.
Sensor
Temprature
Humidity
Photo sensor
Pressure Vacuum Thayrister
Gas Proxi Ssr
Single/Dual channel indicator contr. Pressure & vacuum transmitter Differantial Pressure transmitter
Hi accurate digital pressure gauge. Loop power indicator (PT/DP) ItoP/EtoPconvertor.
JUMBO DISPLAY
Procces value big indicator
-Display size : 2”,4”,6”,8”,12” Clocks with date and years Production monitoring systems
RPM/MPM indicator controller Alarm annunciator(2 to 200 chnl.) Auto manual station Manual loaders & celebrators
Universal input Signal isolator & convertor & multiplexer Multi channel Signal isolator & convertor & multiplexer Loop powered Signal isolator & square root extractors Equations computation modual & Linearization modual
Convertor
Load cell to mA
Ohms to mA/V
MV to mA
Amp.tomA
OTHERES
Vibration sensors indicators Gas starilizers control systems Bagging controller (cements) Control valves and positioners
We can provide GSM mobile comm. and modbus RTU 232/485 connectivity with pc software in our entire product range.
We provide SCADA software (Online and Offline Report / Trend / part lading ) for flow analysis and data logging systems. We can provide our all instruments in MS or SS panel and also provide in flame proof and weather proof housing. We can accept to make customized instruments & trucky systems (hardware and computer software) as per customers needs.
industrials procces automaton
Total solution provider for Industrials Automaton PLC and HMI and hi speed communications module. SCADA system (standard and customized computer software) Servo Motors & Drives & AC drives / inverter
Unitech Instruments
503/504 Helix Complex.Opp-Surya Hotel,Sayajigunj,
Vadodra-390005,Gujarat ,India
Phone.: 0265-6623551/6553555/2361241
E-mail :salse@unitechinstrument.com,kuntal_unitech@yahoo.com
URL :www.unitechinstrument.com
,
ax.:F
265-6623551
cell no :094273 01436
ACVtomA DCVtomA
Loading...