Unitary products group RP007 Series, RP009 Series, RP012 Series, RP018 Series, RP024 Series Installation & Operating Instructions Manual

...
INSTALLATION
INSTALLATION & OPERATING INSTRUCTIONS
FOR RP007 - 060 SERIES
MANUAL
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . .3
PRE-INSTALLATION INSPECTION OF
EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . 4
START-UP AND OPERATION . . . . . . . . . . . . . . . 10
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Complete Table of Contents on following pages.
WATER SOURCE HEAT PUMPS
RP007 TO 060
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes clarify or make the installation easier. Cautions to prevent equipment damage. Warnings alert installer that personal injury and/or equipment dam­age may result if installation procedure is not handled properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
are intended to
are given
are given to
036-21521-001-A-0103
TABLE OF CONTENTS
036-21521-001-A-0103
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PRE-INSTALLATION INSPECTION OF EQUIPMENT . . . . 4
RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CLEARANCES REQUIRED . . . . . . . . . . . . . . . . . . . . . . . . . 6
UNIT MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTRICAL POWER SUPPLY AND CONNECTIONS . . . 6
ROOM THERMOSTAT AND CONTROL WIRING . . . . . . . 7
BLOWER PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . 8
LOOP WATER SUPPLY AND PIPING
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SUPPLY/RETURN PIPING . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSATE DRAIN PIPING . . . . . . . . . . . . . . . . . . . . . 10
WATER REGULATING VALVE – INSTALLATION . . . . . . 10
START-UP AND OPERATION . . . . . . . . . . . . . . . . 10
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
WATER REGULATING VALVE - ADJUSTMENT . . . . . . . 11
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
STANDARD PRODUCT WARRANTY . . . . . . . . . . . . . . . . 17
LIST OF FIGURES
Fig. # Pg. #
1 UNIT MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 TYPICAL SINGLE PHASE WIRING DIAGRAM . . . . . 13
3 TYPICAL THREE PHASE WIRING DIAGRAM . . . . . 14
4 HORIZONTAL MODELS - DIMENSIONS . . . . . . . . . . 15
5 VERTICAL MODELS - DIMENSIONS . . . . . . . . . . . . . 16
LIST OF TABLES
Tbl. # Pg. #
1 GENERAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 OPERATING LIMITS - WATER LOOP
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 BLOWER PERFORMANCE (CFM) . . . . . . . . . . . . . . . 8
5 UNIT WATER PRESSURE DROP . . . . . . . . . . . . . . . 10
6 R-22 REFRIGERANT CHARGE . . . . . . . . . . . . . . . . 12
7 HORIZONTAL MODELS - DIMENSIONS . . . . . . . . . 15
8 VERTICAL MODELS - DIMENSIONS . . . . . . . . . . . . 16
2 Unitary Products Group
036-21521-001-A-0103
PRODUCT NOMENCLATURE
Water Cooled Package Heat Pump and AC Model Number Nomenclature
Product Category
R = Watercooled ID Package,HP
Product Identifier
P = HP, R-22 High Efficiency
Nominal Cooling Capacity - MBH
007 = 0.5 Ton 009 = 0.75 Ton 012 = 1 Ton 018 = 1.5 Ton 024 = 2 Ton 030 = 2.5 Ton 036 = 3 Ton 048 = 4 Ton Heat Type 060 = 5 Ton C00 = No Heat Option
R P 060 C00 V 2 L AB 1
V = Vertical H = Horizontal
AA = None AG = AB + AE AB = Insulated Water Circuit(Not available on cooling only) AH = AB + AF AC = Cooling only (No Reversing Valve) AJ = AC = AD AD = Cupro Nickle Heat Exchanger AK = AC = AE AE = Condensate Overflow Switch w/ Alarm output AL = AC = AF AF = Remote Management Relay Pkg w/ Alarm output
INTRODUCTION
RP units are completely self-contained heating and/or air conditioning units. This equipment employs a water­to-refrigerant heat exchanger to extract (heating cycle) or reject (cooling cycle) heat from/to a circulating water-loop.
All models 1/2 through 5 tons are shipped as factory­charged packages. Horizontal units are designed for suspended ceiling mounting, and are constructed with integral hanger channels. Vertical units are designed for free-standing floor mounting. All units are shipped completely factory wired and pre-piped. Water supply, water outlet, and condensate drain connections are via female threaded pipe fittings.
Each refrigeration circuit includes an adjustable bi-flow expansion valve, liquid line filter drier, and multiple ser­vice gauge ports. External high pressure and low pres­sure protection switches are included in each compressor circuit. Heat Pump models feature a pilot operated, sliding piston type, 4-way reversing valve with a replaceable magnetic solenoid coil.
Product Generation
1 = First Generation
Installation Options
Voltage
1 = 208/230-1-60 2= 208/230-3-60 4 = 460-3-60 5 = 575-3-60
L = Left Hand Return R = Right Hand Return
Airflow
Additional Options
The coaxial water-to-refrigerant heat exchanger, and all water piping within the unit are rated for water side working pressures up to 400 psig. Automatic water flow regulating valves are available as field installed acces­sories.
All units are completely factory wired with all necessary operating controls. A 24 volt control circuit, with over­size transformer, is provided for field connection. Units are designed to operate with conventional thermostat control interface. The reversing valve solenoid coil shall be energized in cooling mode only. A manual reset lock-out relay is provided to disable the compres­sor control circuit in the event of high/low pressure cut­out.
These units are designed for indoor installation only. They are not
intended or approved for outdoor installa-
tion.
Unitary Products Group 3
036-21521-001-A-0103
PRE-INSTALLATION INSPECTION OF EQUIPMENT
All units are factory tested to ensure safe operation and quality assembly. Units are packaged and sealed on wooden skid runners and shipped in first class condi­tion. Torn and broken packaging, scratched or dented panels should be reported to carrier immediately. Inter­nal inspection of all units should be performed prior to installation . Remove all access doors and check for visual defects that can occur during transport. Any problems found internally should be reported to carrier and manufacturer immediately. Refrigerant circuit should be checked to ensure no leaks have occurred during shipment. Install gauge set to high and low pres­sure ports to confirm pressure has been maintained and no leaks have occurred during shipment. Repair any damage prior to installation to ensure safe opera­tion.
NOTE: Record any unit damage on the Bill of Lading and
report to carrier and factory immediately. Shipping and handling damages are not warranty items.
RIGGING
INSTALLATION
Lock all electrical power supply switches in the off position before installing the unit. Failure to disconnect power supply may result in electrical shock or even death.
Only qualified personnel should perform installa­tion and service of this equipment.
Location - To ensure unit operates at maximum effi­ciencies, choose a dry indoor area where the tempera­ture is controlled between 40° F and 115° F. Consideration of surrounding areas should be taken when choosing a location to install the unit. Common vibration and sound levels associated with commercial equipment may be objectionable to people or equip­ment.
Prior to mounting unit, check individual unit weights (page 4) and verify lifting capacity of lifting equipment exceeds weight of units by safe mar­gins. failure to do so may result in unit damage, personal injury or even death.
Failure to allow adequate space between units may result in poor unit performance and possible unit failure.
Install thermostats, supply air ductwork, and return air ductwork (if applicable) so that each unit will operate only in a single cooling or heating zone. In order to assure proper drainage of condensate, horizontal units can be slightly pitched in the same direction as drain pan outlet.
4 Unitary Products Group
036-21521-001-A-0103
TABLE 1: GENERAL DATA
Model Series 007 009 012 018 024 030 036 048 060
Nominal Cooling(Ton) 0.5 0.75 1.0 1.5 2.0 2.5 3.0 4.0 5.0
Cooling Performance
Cooling Capacity (BTUH) 7000 9000 12800 18100 24200 30800 36100 48200 59000
EER 12.4 13.0 12.6 14.4 14.4 13.5 14.2 14.0 12.6
Heating Capacity (BTUH) 8800 10700 14800 20900 27500 35200 41400 56000 72000
COP 4.2 4.4 4.2 4.5 4.6 4.4 4.6 4.6 4.4
Design CFM 200 300 400 600 800 1000 1200 1600 2000
Nominal Water flow (gpm) 1.5 2.25 3.0 4.5 6.0 7.5 9.0 12.0 15.0
Compressor-Type Rotary Rotary Rotary Rotary Recip. Recip. Recip. Recip. Recip.
Number Used 111111111
Air Coil-Type Enhanced Copper Tubes, Enhanced Aluminum Fins
Face Area (sq ft) 1.00 1.00 1.00 1.51 2.56 2.56 2.88 4.38 5.00
Rows/FPI 2/14 2/14 3/14 3/14 3/14 3/14 3/14 3/14 3/14
Water Coil-Type Co-axial
Water Connection Size 1/2" FPT 1/2" FPT 1/2" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 1"FPT
Drain Connection Size 3/4" FPT
Direct Drive Fan-Type Centrifugal, Forward Curved
Number Used 111111111
Diameter x Width (in) 9x4 9x4 9x4 9x6 9x7 9x7 9x7 10x9 10x9
Motor HP/Speed 0.10/3 0.10/3 0.17/3 0.25/3 0.25/3 0.33/3 0.50/3 0.75/3 1.0/3
Filters
HWP - Quantity-Size (in)
VWP - Quantity-Size (in)
Weight
Operating 130 135 155 180 215 235 260 325 345
Shipping 145 150 170 195 230 255 280 345 365
1-14x16x1 1-14x16x1 1-14x16x1 1-16x20x1 1-18x25x1 1-18x25x1 1-20x25x1 2-20x20x1
1-14x16x1 1-14x16x1 1-14x16x1 1-16x20x1 1-18x25x1 1-18x25x1 1-20x25x1
1-16x25x1 1-14x25x1
1-20x20x1 1-20x25x1
1-18x25x1 1-16x25x1
NOTE:
1. Performance calculated in accordance with ARI/ISO Standard 13256-1 for Water Loop application.
2. Cooling capacities are rated at entering air conditions of 80.6°F db / 66.2° F wb, 86° F entering water tempera­ture.
3. Heating capacities are rated at entering air conditions of 68° F db / 59° F wb, 68° F entering water temperature.
TABLE 2: OPERATING LIMITS - WATER LOOP
APPLICATION
COOLING HEATING
Min. Entering Water 50°F
Max. Entering Water 110°F 80°F
Normal Entering Water 60-90°F 50-70°F
1.
Heating operation below 55°F requires insulated water circuit.
Unitary Products Group 5
40°F
1
CLEARANCES REQUIRED
036-21521-001-A-0103
Twenty-four (24) inch clearance is required on all sides of the unit for service access. Service access doors are equipped with lifting handles and are located on all sides of the unit to allow easy servicing of all compo­nents.
UNIT MOUNTING
Vertical units should be mounted level on a vibration absorbing pad(s) to minimize vibration transmission
through the floor structure. It is not necessary to anchor the unit to the floor.
Horizontal units are typically suspended above a ceil­ing by threaded steel rods, securely anchored to the building structure. Units should be supported from the holes in the rail extensions at the four corners, using steel threaded rods having a minimum diameter of 3/8 inch. Four rubber bushings are supplied with the unit to be placed between the unit and the supporting rods to absorb vibration.
3/8" THREADED
ROD (BY OTHERS)
FIGURE 1 : UNIT MOUNTING
DUCT CONNECTIONS
Canvas or other types of flexible collars are recom­mended for connecting the air ducts to the unit. The supply air duct collar can be connected directly to the blower outlet flange. Allowance must be made in the supply duct for removal of the first duct section adja­cent to the unit, for the servicing of the blower and motor assembly. Return air may be ducted to the unit or drawn directly from the ceiling space into the filter.
Supply ducts should be sized for an air velocity of not more than 1000 feet per minute. Return ducts should be sized for a velocity of not more than 700 feet per minute. When the sound level is critical, it is recom­mended that both the supply and return
INTEGRAL SUPPORT
RAIL
WASHER
(BY OTHER)
DOUBLE HEX NUT
(BY OTHER)
ducts be lined with acoustic insulation for the first ten feet closest to the unit. The supply duct should also have at least one elbow or tee upstream of the first out­let connection for good sound attenuation.
ELECTRICAL POWER SUPPLY AND CONNEC­TIONS
Before installing the unit, make sure that the voltage and number of phases on the unit data plate are the same as the available power supply. All wiring and switchgear installed external to the unit must conform to all applicable local codes. The maximum allowable size of fuses or circuit breaker required is shown on the unit data label. Fuses must be of the time delay type.
6 Unitary Products Group
036-21521-001-A-0103
The power supply wiring is to be connected directly to the line side of compressor contactor as shown on the connection wiring diagram. A ground wire must be con­nected to the ground lug marked GND in the electrical control box.
so that constant fan operation can be selected if desired. Heat Pump models require the installation of a heating and cooling thermostat with a dedicated "O" terminal for activating the reversing valve. Wiring between the thermostat and the unit should be 18 Ga. minimum. Appropriate room thermostats can be
ROOM THERMOSTAT AND CONTROL WIRING
ordered as an optional accessory for delivery with the
units if desired. Any single stage 24-volt room thermostat can be used with the “cooling only” models. It is recommended that the thermostat sub-base should include a fan switch,
TABLE 3: ELECTRICAL DATA
MODEL SERIES
007 208-230/1/60 1 @ 2.8 17.7 0.10 0.9 4.35 15
009 208-230/1/60 1 @ 3.4 23.0 0.10 0.9 5.15 15
012 208-230/1/60 1 @ 4.8 26.3 0.17 1.4 7.40 15
018 208-230/1/60 1 @ 6.4 38.0 0.25 1.5 9.5 15
024 208-230/1/60 1 @ 10.4 49.0 0.25 1.5 14.50 20
030
036
048
060
SUPPLY
VOLTAGE
208-230/1/60 1 @ 12.4 61.0 0.33 2.6 18.10 30
208-230/3/60 1 @ 7.7 55.0 0.33 2.6 12.23 15
208-230/1/60 1 @ 15.3 82.0 0.50 3.2 22.33 35
208-230/3/60 1 @ 10.0 68.0 0.50 3.2 15.70 25
460/3/60 1 @ 4.8 34.0 0.50 1.9 7.90 15
208-230/1/60 1 @ 19.0 105.0 0.75 4.9 28.65 45
208-230/3/60 1 @ 14.0 91.0 0.75 4.9 22.40 35
460/3/60 1 @ 5.9 42.0 0.75 2.2 9.58 15
575/3/60 1 @ 4.8 34.0 0.75 1.8 7.80 15
208-230/1/60 1 @ 24.6 132.0 1.00 5.1 35.85 60
208-230/3/60 1 @ 16.0 97.0 1.00 5.1 25.10 40
460/3/60 1 @ 8.2 50.0 1.00 3.2 13.45 20
575/3/60 1 @ 5.0 44.0 1.00 2.6 8.85 15
COMPRESSOR BLOWER
QTY RLA LRA HP FLA
MIN. CCT.
AMPACITY
MAX FUSE /
CCT. BKR. AMP
Unitary Products Group 7
036-21521-001-A-0103
BLOWER PERFORMANCE
A simple method for approximating sufficient air vol-
ume is to measure the difference between the supply All units employ direct-drive blower motors with multi­ple speed taps available. The motors have been selected to deliver the nominal air volume against vary­ing external static pressures when necessary. After installation of the unit, it will be necessary to check the air volume and change the motor speed connection
and return air temperatures. In Heating mode, the air
temperature rise should be in the range of 20ºF to 30ºF.
In Cooling mode, the temperature drop should be
between 15ºF to 25ºF. If values are outside the appro-
priate range, increase or reduce the motor speed as
necessary. accordingly if the air volume is too high or too low. All units are factory-wired with the medium speed winding connected.
TABLE 4: BLOWER PERFORMANCE (CFM)
EXTERNAL STATIC PRESSURE (in w.g.)
UNIT SPEED 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
High - - - - 270 235 195 150 -
007
009
012
018
024
030
036
048
060
Note: Units are shipped pre-wired for Medium speed.
Med - - 260 240 210 175 - - -
Low 225 215 200 180 150 - - - -
High - - 380 360 330 290 240 - -
Med 350 340 325 300 270 235 - - -
Low 285 275 260 240 210 - - - -
High 495 475 450 420 385 345 300 - -
Med 470 455 430 400 365 325 - - -
Low 385 370 355 330 300 - - - -
High - - 705 660 610 555 495 430 -
Med - 700 660 615 565 510 450 - -
Low 690 665 630 585 535 480 - - -
High - - 1005 950 890 820 740 650 -
Med 925 905 875 840 790 730 660 - -
Low - - 780 765 725 660 590 - -
High - - 1170 1120 1060 985 905 810 -
Med 1150 1125 1090 1045 990 925 850 765 -
Low - 975 970 940 905 855 785 - -
High - 1390 1330 1270 1210 1140 1055 960 -
Med 1355 1320 1270 1215 1155 1085 1005 920 -
Low 1200 1190 1170 1130 1085 1020 950 - -
High - - 1990 1915 1835 1750 1660 1550 1415
Med 1880 1860 1820 1770 1710 1640 1550 1450 1320
Low - 1490 1485 1480 1460 1420 1360 1285 1160
High 2340 2280 2210 2140 2070 1990 1895 1790 1660
Med 2040 2030 2005 1970 1925 1860 1785 1700 1590
Low - - 1705 1700 1680 1660 1610 1540 -
All airflow ratings are at lowest voltage rating of dual rating (i.e., 208 volt)
Airflow ratings include resistance of wet coil and clean air filters.
8 Unitary Products Group
036-21521-001-A-0103
LOOP WATER SUPPLY AND PIPING CONNECTIONS
The recommended circulating water supply for heat pump systems is a closed-water loop, utilizing a cool-
ing tower and boiler to maintain the loop temperature within acceptable temperature limits. Typically, the closed loop temperature is maintained above 60° F and below 90° F. All units function independently, either adding heat to the loop (cooling mode) or removing heat from the loop (heating mode).
When utilizing an open cooling tower (evaporative type), chemical treatment is mandatory to ensure that the loop water is free of corrosive minerals. A second­ary heat exchanger between the open cooling tower and the closed water loop may also be used. It is imperative that all air is purged from the closed loop side to prevent condenser fouling.
Dual acting water regulating valves should be used when there is potential for low fluid flow and/or low fluid temperature or high fluid temperature conditions to exist. These water regulating valve assemblies consist of a direct acting valve parallel coupled to a reverse acting valve. The direct acting valve opens in response to an increase in discharge pressure during cooling mode. The reverse acting valve opens in response to a decrease in suction pressure during heating mode.
The heat rejection water source for cooling-only units may be from a municipal supply main, a cooling tower, or a chilled water system. An automatic water flow reg­ulating valve is normally required, except if the inlet water temperature is constant and the flow rate can be pre-set and turned on and off by some other means, such as a dedicated pump circuit or solenoid valve.
Automatic water flow regulating valves, for both heat pump and cooling-only applications, are available as field installed accessories. The valves are installed on the water outlet connection from the unit. Schrader type refrigerant pressure access fittings are included as standard in all units.
SUPPLY/RETURN PIPING
Supply and return piping should be as large as the unit connection sizes (larger on long pipe runs). Never use flexible hoses of a smaller inside diameter than that of the nominal water pipe size. Both supply and return water lines will sweat if subjected to low water tempera­tures. Insulate these lines as necessary to prevent con­densation damage.
Flexible hoses should be used between the unit and rigidly mounted piping to avoid vibration transmission. Teflon tape thread sealant is recommended. Do not overtighten threaded connections. Ball valves should be installed in the supply and return lines for unit isola­tion and water flow balancing. Before final connection to the unit, the supply and return hoses should be con­nected together and the piping system flushed to remove any dirt or foreign material.
Pressure and temperature ports are recommended in both the supply and return lines for system flow balanc­ing. The water flow can be accurately set by measuring the water-side pressure drop through the unit. See the flow versus pressure drop specification table for appli­cation information. Do not exceed the recommended
water flow rates. Damage due to erosion of the water-to-refrigerant heat exchanger could occur.
Unitary Products Group 9
TABLE 5: UNIT WATER PRESSURE DROP
007 009 012 018 024 030 036 048 060
EWT
o
F
50
60
70
85
100
WPD
GPM
(psi)
1.0 0.8 1.35 1.4 1.8 2.1 2.75 2.3 3.5 3.3 4.5 3.6 5.5 2.9 7.5 3.9 9.0 3.6
1.5 2.0 2.25 3.5 3.0 5.3 4.50 5.7 6.0 8.0 7.5 9.0 9.0 7.0 12.0 9.6 15.0 8.8
1.0 0.7 1.35 1.4 1.8 2.0 2.75 2.2 3.5 3.2 4.5 3.5 5.5 2.8 7.5 3.7 9.0 3.5
1.5 1.9 2.25 3.4 3.0 5.1 4.50 5.5 6.0 7.7 7.5 8.7 9.0 6.8 12.0 9.2 15.0 8.5
1.0 0.7 1.35 1.3 1.8 1.9 2.75 2.1 3.5 3.0 4.5 3.3 5.5 2.6 7.5 3.5 9.0 3.3
1.5 1.8 2.25 3.2 3.0 4.8 4.50 5.2 6.0 7.3 7.5 8.2 9.0 6.4 12.0 8.7 15.0 8
1.0 0.7 1.35 1.2 1.8 1.8 2.75 2.0 3.5 2.9 4.5 3.1 5.5 2.5 7.5 3.3 9.0 3.1
1.5 1.7 2.25 3.0 3.0 4.6 4.50 4.9 6.0 6.9 7.5 7.8 9.0 6.1 12.0 8.3 15.0 7.6
1.0 0.6 1.35 1.2 1.8 1.7 2.75 1.9 3.5 2.7 4.5 3.0 5.5 2.4 7.5 3.2 9.0 3.0
1.5 1.6 2.25 2.9 3.0 4.4 4.50 4.7 6.0 6.6 7.5 7.5 9.0 5.8 12.0 7.9 15.0 7.3
GPM
WPD
(psi)
GPM
WPD
(psi)
GPM
UNIT MODEL
WPD
GPM
(psi)
WPD
(psi)
GPM
WPD
(psi)
GPM
WPD
(psi)
036-21521-001-A-0103
WPD
(psi)
GPM
GPM
WPD
(psi)
CONDENSATE DRAIN PIPING
Horizontal Units - The 3/4 FPT drain connection on the unit is NOT internally trapped. The cooling coil com­partment and drain pan are under negative pressure when the blower is running, therefore a P trap MUST be used in the drain line.
It is recommended that a ¾ inch drain line be sloped (¼ inch/foot) all the way to an open drain. Each unit must be installed with its own individual trap, and have the means to flush out the condensate line if neces­sary. If it is not possible to reach an open drain by grav­ity flow, a pump kit, which is available as an accessory, can be mounted close to the unit.
Vertical Units - Each unit utilizes a flexible hose inside the cabinet as a trapping loop. An external P-trap is not necessary.
WATER REGULATING VALVE – INSTALLATION
The water regulating valve is to be installed in the water outlet line, as close as possible to the unit cabi­net (maximum 18 inches distance). The capillary tube from the sensing bellows on the valve(s) must be con­nected to the ¼ inch male flare connection, which is on the refrigerant liquid line in the condenser compart­ment. Connect the capillary tube flare nut directly to the unit male flare fitting. When one is making this connec­tion, it is normal for some refrigerant to escape as the schrader valve core is being opened and the nut is being tightened. Complete the tightening of the nut as soon as possible to minimize the loss of refrigerant. Do not over-tighten.
START-UP AND OPERATION
NOTE: The services of a qualified Refrigeration Service
Mechanic should be employed in the start-up and commissioning of these systems.
Lock all electrical power supply switches in the off position before installing the unit. failure to discon­nect power supply may result in electrical shock or even death.
After completing the installation, and before energizing
the power supply to the unit, the following checks
should be made -
Verify that the electrical supply to the unit is of the correct voltage, and rated for sufficient amperage in accordance with the nameplate values.
Verify that the low voltage wiring between the unit and the thermostat is correct.
Confirm that the water piping is complete and free of leaks.
Check that the water flow rate is correct, and adjust as necessary.
Confirm that the blower wheel rotates freely.
All service access panels are in place and properly secured.
A room thermostat should be used to cycle the unit on and off automatically as required to maintain the room temperature at the set point of the thermostat. The air
10 Unitary Products Group
036-21521-001-A-0103
circulating fan will cycle on and off with the compressor. If desired, the air circulating fan can be run continu­ously.
The units have a lock out relay that will prevent the unit from cycling on the low pressure cut out or the high pressure cut out. If either of these safety devices open, the compressor will not restart when the safety device resets. To restart the compressor after a safety lock out, it will be necessary to interrupt the power to the control circuit. This can be done at the thermostat or at the disconnect switch.
START-UP
1. Set the thermostat to the highest setting.
2. Set the fan switch to the 'AUTO' position, and the thermostat system switch to 'COOL'.
3. Reduce the thermostat setting to approximately 5 degrees below room temperature.
4. The compressor, and the supply air blower, will start. Simultaneously the reversing valve will be energized.
5. After five minutes, verify cooling mode operation by checking for cool air discharge at the supply air outlet.
6. Set the thermostat system switch to the 'OFF' posi­tion. The unit will stop running, and the reversing valve will de-energize.
7. Allow approximately five minutes to allow for sys­tem pressures to equalize.
8. Set the thermostat to its lowest temperature set­ting.
9. Move the thermostat system switch to 'HEAT'.
10. Increase the thermostat setting approximately 5 degrees above room temperature.
11. After five minutes, verify heating mode operation by checking for warm air discharge at the supply air outlet.
12. Adjust the thermostat to maintain the desired space temperature.
13. Check the unit for unusual vibrations, noises, leaks, etc.
WATER REGULATING VALVE - ADJUSTMENT
The water regulating valve needs to be adjusted to maintain a condensing pressure of 170 to 220 PSIG. The valve is adjusted by turning the ¼ inch square shaft on top of the spring housing. Turning the adjust­ing screw counter clockwise will raise the opening pressure and raise the condensing pressure being maintained. Turning the adjusting screw clockwise will lower the opening point and lower the condensing pressure being maintained. If mains water is being used, make sure the valve closes soon after the com­pressor stops. If the flow does not stop after a few min­utes, raise the opening pressure by turning the adjusting shaft counter clockwise until the flow stops.
If the unit is running on mains water, we recommend adjusting the water regulating valve to give 100ºF leav­ing water temperature or 220 PSIG condensing tem­perature. This will give the best compromise between low water flow and high operating efficiency. If the con­denser water is being re-circulated through a cooling tower or a chilled water system, it is recommended that the water regulating valve be set for a lower condens­ing temperature. This will provide higher efficiency, lower operating cost and a lower sound level. The min­imum condensing pressure required for satisfactory expansion valve operation is 170 PSIG.
MAINTENANCE
The air circulating fan motor has bearings that are fac­tory lubricated and sealed for long life. No further lubri­cation is required. The compressor is part of a sealed refrigeration system that does not require any addi­tional lubrication.
Filter changes are required at regular intervals. It is suggested that the filter be checked at 60-day intervals for the first year of operation, until field experience is acquired. If light cannot be seen through the filter, it should be changed. Always replace the filter with the same size of 1-inch thick disposable type of fiberglass filter. (See General Data for listing of required filter sizes.)
The condensate drain pan should be checked annually, and cleaned and flushed as required.
Recording of reference operating parameters is recom­mended (volts, amp draw, water temperature differ­ences, etc.). A comparison of logged data with start-up and annual data is useful as an indicator of general equipment condition.
Unitary Products Group 11
036-21521-001-A-0103
Periodic lockouts are almost always caused by air or water problems. The lockout of the compressor is a normal protective result of insufficient heat transfer. Check for dirt in the water system, insufficient water
TABLE 6: R-22 REFRIGERANT CHARGE
UNIT SIZE
060 5.0 5 lbs. – 8 oz. 5 lbs. – 13 oz.
048 4.0 4 lbs. – 6 oz. 4 lbs. – 9 oz.
036 3.0 3 lbs. – 5 oz. 3 lbs. – 7 oz.
030 2.5 2 lbs. – 12 oz. 2 lbs. – 14 oz.
024 2.0 2 lbs. – 4 oz. 2 lbs. – 6 oz.
018 1.5 1 lbs. – 12 oz. 1 lbs. – 14 oz.
012 1.0 1 lbs. – 6 oz. 1 lbs. – 7 oz.
009 0.75 1 lbs. – 1 oz. 1 lbs. – 1 oz.
007 0.50 10 oz. 10 oz.
CAPACITY
TONS
flow rates, excessive water temperatures, air flow rates (dirty filters), and air temperatures.
HORIZONTAL VERTICAL
12 Unitary Products Group
036-21521-001-A-0103
APPLIES TO ALL 208/230-1-60 SINGLE PHASE MODELS
Note: Solenoid Valve (SV) used
on Heat Pump version only.
FIGURE 2 : TYPICAL SINGLE PHASE WIRING DIAGRAM
Unitary Products Group 13
036-21521-001-A-0103
APPLIES TO MODELS: RP030, RP036, RP048 & RP060
NOTE: Solenoid Valve (SV) used
on Heat Pump version only.
FIGURE 3 : TYPICAL THREE PHASE WIRING DIAGRAM
14 Unitary Products Group
036-21521-001-A-0103
FIGURE 4 : HORIZONTAL MODELS - DIMENSIONS
TABLE 7: HORIZONTAL MODELS - DIMENSIONS
ABCDEF
007 34.50 19.00 15.00 32.25 21.50 2.56 15.00 2.00 12.00 5.75 6.81 10.31 3.75
009 34.50 19.00 15.00 32.25 21.50 2.56 15.00 2.00 12.00 5.75 6.81 10.31 3.75
012 34.50 19.00 15.00 32.25 21.50 2.56 15.00 2.00 12.00 5.75 6.81 10.31 3.75
018 40.00 21.00 16.00 37.75 23.50 2.56 18.00 1.00 14.00 6.50 8.25 10.31 3.75
024 45.00 21.00 18.00 42.75 23.50 2.25 25.00 1.00 16.00 6.50 9.19 10.31 4.81
030 45.00 21.00 18.00 42.75 23.50 2.25 25.00 1.00 16.00 6.50 9.19 10.31 4.81
036 48.00 23.00 20.00 45.75 25.50 2.25 25.00 1.00 18.00 6.50 9.19 10.31 5.88
048 58.00 25.00 20.00 55.75 27.50 2.25 38.99 1.00 18.00 6.00 12.25 11.38 5.13
060 63.00 25.00 20.00 60.75 27.50 2.25 42.00 1.00 18.00 6.00 12.25 11.38 5.13
Unitary Products Group 15
RETURN AIR
GH J LM
K
SUPPLY AIR
N
FIGURE 5 : VERTICAL MODELS - DIMENSIONS
TABLE 8: VERTICAL MODELS - DIMENSIONS
ABC
007 22.50 22.50 33.00 6.81 10.31 2.00 7.81 14.88 12.50 1.25 N/A N/A
009 22.50 22.50 33.00 6.81 10.31 2.00 7.81 14.88 12.50 1.25 N/A N/A
012 22.50 22.50 33.00 6.81 10.31 2.00 7.81 14.88 12.50 1.25 11.50 12.00
018 22.50 22.50 35.00 8.25 10.31 2.00 7.13 16.88 14.50 1.25 11.50 12.00
024 22.50 22.50 45.00 9.19 10.31 2.00 7.13 16.88 23.50 1.25 11.50 12.00
030 22.50 22.50 45.00 9.19 10.31 2.00 6.63 16.88 23.50 1.25 11.50 12.00
036 24.50 24.00 45.00 9.19 10.31 3.00 7.63 18.88 23.50 1.25 12.50 12.50
048 29.50 27.50 52.00 12.25 11.38 3.00 8.63 23.00 28.50 0.75 14.19 14.31
060 29.50 27.50 56.00 12.25 11.38 3.00 8.81 23.00 32.50 0.75 14.19 14.31
Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 2003. All rights reserved. Supersedes: Nothing 036-21521-001-A-0103
Unitary 5005 Norman Products York OK Group Drive 73069
AIR SUPPLY
DE KLMPR
FG
RETURN AIR
OPTIONAL
PLENUM
Loading...