Unitary products group P-HMX12F05701, P-HMX12F08001, P-HMX14F10001, P-HMX20F12001 Installation Instruction

INSTALLATION INSTRUCTION
CONTENTS
INTRODUCTION....................................... 3
HEATLOSS .......................................... 3
LOCATIONOFUNIT.................................... 3
UPFLOWINSTALLATION................................ 4
HORIZONTALINSTALLATION............................ 4
NON-SUSPENDEDINSTALLATION ....................... 5
SUSPENDEDINSTALLATION............................ 5
AIRCONDITIONINGAPPLICATIONS...................... 5
COMBUSTIONAIR..................................... 5
CHIMNEYVENTING.................................... 5
BAROMETRICDAMPERCONTROL....................... 7
FURNACE CONTROLS ................................. 7
ELECTRICALCONNECTIONS............................8
HUMIDIFIER.......................................... 8
OILTANK ............................................ 8
PIPINGINSTALLATION................................. 9
OILFILTER........................................... 9
OILBURNERNOZZLES................................. 9
COMBUSTIONCHAMBER.............................. 10
BURNER ELECTRODES ............................... 10
OILBURNERSETUP.................................. 10
PREPARATIONS:..................................... 10
PROCEDURE:........................................ 11
CIRCULATING AIR BLOWE R ............................ 12
MAINTENANCEANDSERVICE.......................... 13
FURNACE INSTALLATION SET UP. ...................... 13
OPERATING INSTRUCTIONS ........................... 14
WIRINGNOTES...................................... 18
CONTINUOUSFANOPERATION: ........................18
ACCESSORIES:...................................... 18
THERMOSTAT HEATING
CONNECTIONS:...................................... 18
R7184 DETAILED SEQUENCE OF OPERATION .............20
R7184 LED DIAGNOSTIC LIGHT. . . ...................... 22
TROUBLESHOOTING ................................. 22
OIL FIRED WARM AIR FURNACE
P-HMX12F05701 - P-HMX12F08001
(Horizontal or Upflow Model)
P-HMX14F10001 - P-HMX20F12001
(Upflow Only)
Read this complete manual before beginning installation. These instructions must be kept with the furnace for future reference.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT.
035-17473-000-B-1101
WARNING
035-17473-000-B-1101)
INTRODUCTION
Please read these instructions completely and carefully before installing and operating the furnace.
IMPROPER INSTALLATION MAY CREATE A CON­DITION WHERE THE OPERATION OF THE PROD­UCT COULD CAUSE PERSONAL INJURYOR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERA TION,SERVICE OR MAINTENANCE CAN CAUSEINJURYORPROPERTYDAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDI­TIONAL INFORMATION, CONSULTA QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLA­TION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUD­ING BUT NOT LIMITED TO,BUILDING, ELECTRI­CAL AND MECHANICAL CODES.
The furnace must be installed and set up by a qualified contractor.
P*HMX12F05701 and P*HMX12F08001 are oil fired forced air multi-positional furnaces, with an output capacity range of 58,000 BTU/Hr to 79,000 BTU/HR. These furnaces may be installed in the up-flow posi­tion, as well as both horizontal left and right positions.
P*HMX14F10001 and P*HMX20F12001 are oil fired Upflow ONLY furnaces, with an output capacity range of 100,000 BTU/Hr. to 118,000 BTU/Hr.These furnaces shall be installed in the up-flow position only.
All model furnaces are listed with the Canadian Stan- dards Association,(CSA) and comply with both Canadian and American (U.S.) standards for use with No. 1 (Stove) and No. 2 (Furnace) Oil. Please refer to the tables in the appendix for performance and dimen­sional data.
WARNING
WARNING
Thefurnace area mustnot beused asa broomcloset orforanyotherstoragepurposes,as afirehazardbay be created. Never s tore items such as the following on, nearor in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
DO NOT USE GASOLINE, CRANK CASE OIL, OR ANY OIL CONTAINING GASOLINE.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in accordance with local codes.
In the United States of America, the installation of the furnace and related equipment shall be installed in accordance with the regulations of NFPA No. 31,
Installation of Oil Burning Equipment
,aswellasin
accordance with local codes. When installation or application questions arise, regu-
lations prescribed in the National Codes and Local Regulations take precedence over the general instruc­tions provided with this installation manual. When in doubt, please consult your local authorities.
All models are shipped assembled and pre-wired. The furnace should be carefully inspected for damage when being unpacked.
2 UnitaryProductsGroup
HEAT LOSS
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the manuals of the Heating, Refrigera-
tion and Air Conditioning Institute of Canada
(HRAI), or by any other method which is suitable for local conditions, provided the results obtained are in substantial agreement with, and not less than those obtained using the procedure described in their manu­als.
In the United States, Manual J.
titled, "Load Calcula-
tion" published by the Air Conditioning Contractors of Amer ica, describes a suitable procedure for calcu-
lating the maximum hourly heat loss.
LOCATION OF UNIT
The furnace should be located such that the flue con­nection to the chimney is short, direct and consists of as few elbows as possible. When possible, the unit should be centralized with respect to the supply and return air duct work. A central location minimizes the trunk duct sizing. All models may be installed on com­bustible floors.
Minimum installation clearances are listed in Table 1.
035-17473-000-B-1101
Table 1: Clearance to Combustibles
Models: P*HMX12F05701 and P*HMX12F08001
Location Up-flow Horizontal Top 2 in. 2 in. Bottom 0 in. 1 in. S/A Plenum 1 in. 1 in. Rear 1 in. 1 in. Sides 1 in. 1 in. Front
Flue Pipe 9 in. 9 in. Enclosure Closet Alcove
1
24” clearance is required for servicing.
Models: P*HMX14F10001 and P*HMX20F12001
Location Up-flow Top 1 in. Bottom 0 in. S/A Plenum 1 in. Rear 1 in. Sides 1 in. Front
Flue Pipe 4in. measured horizontally or below flue pipe. Flue Pipe 9 in. measured vertically or above flue pipe. Enclosure Closet
1
24” clearance is required for servicing.
9in.
9in.
1
1
NOTE: The recommended installation clearances do not take
intoconsiderationtheclearances necessary to replace the air filter or perform otherroutine maintenance.
9in.
1
Unitary Products Group 3
035-17473-000-B-1101
Table 2: General Specifications
MODEL INPUT OUTPUT NOZZLE BECKETT AF BURNER AIR
P*HMX U.S. GPH BTU/Hr. Delavan BURNER MODEL BURNER HEAD FILTER P*HMX12F05701 0.50 58,000 0.50 / 70°A AF76BO F0 16 x 25 x 1 P*HMX12F08001 0.70 79,000 0.70 / 70°A AF76BO F0 16 x 25 x 1 P*HMX14F10001 0.85 100,000 0.85 / 70°A AF76XN F3 16 x 25 x 1 P*HMX20F12001 1.00 118,000 1.00 / 70° A AF76XN F3 16 x 25 x 1
NOTE: Over-fire draft for all models is -0.02 in Water column. Static Plate Diameter: 3-3/8 inch for AF76BO and 2-
3/4 inc. for AF76XN.
UPFLOW INSTALLATION
These furnace models have been assembled for instal­lation in the up-flow position. Maintain all clearances to combustibles as outlined in Table 1 on page 3. Suggestion; as a measure to prevent fuel oil from accu­mulating in locations other than the combustion cham­ber, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the combustion chamber. Use shims made of noncombustible material.
HORIZONTAL INSTALLATION
The 057 & 080 BTU output model furnaces are assem­bled and shipped ready for installation in the upflow
position. The furnace may be installed in either of the horizontal positions; warm air discharging left or warm air discharging right by following these steps:
1. Rotate the furnace 90° to the desired position.
2. Remove the three nut and washer sets fastening the oil burner assembly to the furnace. Rotate the oil burner assembly to be in the upright position. (Ignition trans­former and / or oil primary control control should be on top).
3. Re-align the oil burner assembly to the combustion chamber (fire-pot), then secure into place with the three
nut and washer sets.
FIGURE 1 : TYPICAL SUSPENDED OPERATION
4 UnitaryProductsGroup
035-17473-000-B-1101
NON-SUSPENDED INSTALLATION
Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requires a clearance of 1 inch. This can be done by using non­combustible materials such as one inch thick channel iron or similar material. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. Use shims made of noncombustible material.
SUSPENDED INSTALLATION
Refer to Figure 1. Maintain clearances to combustibles as outlined in Table 1. Remove the four circular knock­outs on the top panel, and similarly, the four circular knock-outs on the bottom panel. The removed knock­outs allow 3/8 inch treaded road to be inserted through the interior of the furnace. Use care when inserting rods, since the foil backed insulation can be easily ripped and torn away from the panel surfaces. Secure the furnace with 2 inch minimum slotted angle or equiv­alent, as shown in Figure 4. The furnace must be sup­ported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot.
COMBUSTION AIR
If the furnace is installed in a closet or utility room, two ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bath­room). One opening shall be located 6” from the top and bottom of the enclosure at the front of the furnace. Each opening shall have a minimum free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances installed in the room.
For furnaces located in buildings of unusually tight con­struction, such as those with high quality weather strip­ping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well venti­lated attic or with the outdoors shall be provided, using a duct if necessary. The duct opening shall have a free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances to be installed. When a furnace is installed in a full basement, infiltration is normally adequate to provide air for combustion and draft opera­tion. Furnace rooms under 65m³ (700 ft³) should auto­matically be treated as confined space.
The Model CAS-2B-90E Furnace Boot manufactured byFieldControls,Inc.maybeusedwiththefurnaceto obtain combustion air directly from outdoors. Use of this device does not alter the need for ventilation air; however, it does provide a good direct source of com­bustion air and is connected directly to the oil burner.
CHIMNEY VENTING
AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air condition­ing, the furnace shall be installed in parallel with or with the evaporator coil upstream from the furnace to avoid condensation in the heat exchanger. In a parallel instal­lation, the dampers or air controlling means must pre­vent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either sys­tem unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifi­cally approved for such service.
The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evap­orator coil. Refer to Appendix B for recommended wir­ing and electrical connections of the air conditioning controls.
Unitary Products Group 5
The chimney must be sized correctly and be in good repair.If the chimney is oversized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.
If the chimney serves the furnace only, the vent should be sized at 4 inch minimum, 5 inch maximum. If the fur­nace is to be co-vented with other appliances, refer to
CAN/CSA B139, Installation Code For Oil Burning Equipment or NFPA 2 11, Standard for Chimneys, Fire­places, Vents, and Solid Fuel-Burning Appliances for
correct sizing information.
035-17473-000-B-1101
Table 3: Min. Chimney Base Temperatures (°F)
Model Chimney Height (ft.)
P-HMX12F05701 300 400 535 725 P-HMX12F08001 270 330 405 505 P-HMX14F10001 250 300 355 430 P-HMX12F12001 225 300 365 430
P-HMX12F5701 185 200 220 250 P-HMX12F08001 175 185 195 215 P-HMX14F10001 165 185 195 205 P-HMX12F12001 165 185 195 205
Chimneys with Thermal Resistance less than R6
Chimneys with Thermal Resistance greater than R6
IMPORTANT: The chimney must be capable of provid­ing sufficient draft at all times for the safe removal of
the products of combustion.
Table 4: Common Chimney Problems
Key Trouble Diagnostic Remedy
A Top of chimney lower
than surrounding
objects
B Chimney Cap or ven-
C Coping restricts
Key Trouble Diagnostic Remedy
D Obstruction in chim-
E Joist protruding into
F Break in chimney lin-
G Collection of soot at
H Offset Lower light on exten-
I Two or more open-
J Loose-seatedpipein
K Smoke pipe extends
L Failure to extend the
M Loose-fitted clean-
tilator.
opening.
ney
chimney.
ing.
narrow space in flue
opening.
ings to the same
chimney.
flue opening.
into chimney.
length of flue parti-
tion to the floor.
out door.
11 20 28 36
Observation Extend chimney
Observation Remove
Observation Make opening as
Can be found bylight
and mirror reflecting
conditions in chim-
ney.
Lowering a light on an extension cord.
Smoke test - build
smudge fire blocking
off other opening,
watching for smoke
to escape.
Lower light on exten-
sion cord.
sion cord.
Found by inspection
from basement.
Smoke test. Leaks should be
Measurement of pipe
from within or obser-
vation of pipe by
means of a lowered
light.
By inspection or
smoke test.
Smoke test. Close all leaks with
above all surround-
ing objects within 30
feet.
large as inside of
chimney.
Useweighttobreak
and dislodge.
Must be handled by
competent masonry
contractor.
Must be handled by competent masonry
contractor.
Clean out with
weighted brush or
bag of loose gravel
on end of line.
Change to straight or
to long offset.
The least important
opening must be closed, using some other chimney flue.
eliminated by
cementing all pipe
openings.
Length of pipe must be reduced to allow
endofpipetobe
flush with inside of
tile.
Extend partition to
floor level.
cement.
FIGURE 2 : COMMON CHIMNEY PROBLEMS
The chimney should be tested under “winter” condi­tions; doors and windows closed, all other fossil fuel burning appliances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot overcome the competi­tion for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re-evaluate the availability of combustion and ventilation air, and take corrective action.
NOTE: These furnaces are approved for use with L­Vent.
NOTE: Maximum Temperature for L-Vent is 575° F(300
°C).
The flue pipe should be as short as possible with hori­zontal pipes sloping upward toward the chimney at a rate of one quarter inch per foot. The flue pipe should not be smaller in cross section area than the flue collar on the furnace. The flue pipe should connect to the chimney such that the flue pipe extends into, and termi­nates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
See Figure 2 and Table 4 for common chimney prob­lems and their remedies.
6 UnitaryProductsGroup
CAUTION
Thefurnacemustbeconnectedtoafluehavingsuffi­cientdraftat alltimes to ensuresafe andproper oper­ation of the appliance.
The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deterioration during the annual inspection and servic­ing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. Refer to the latest edition of CAN/CSA B-139 for rules governing the installation of oil burning equipment. In the United States, refer to the latest edition of NFPA 31 for regula­tions governing the installation of oil burning equip­ment.
035-17473-000-B-1101
FIGURE 3 : R7184 OIL PRIMARY CONTROL
BAROMETRIC DAMPER CONTROL
This device is used in conjunction with conventional chimney venting. This control (or draft regulator) auto­matically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control can­not function properly. The draft regulator, must be installed within the same room or enclosure as the fur­nace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters (18”) from the fur­nace breaching and installed in accordance to the instructions supplied with the regulator. The flue outlet pressure (measured between the furnace and draft regulator) should be set to - 0.02 in. w.c.
FURNACE CONTROLS
The furnace is controlled by the ST9103 ELECTRONIC FAN TIMER (EFT) combined with an R7184 Oil Pri­mary Control.
These controls provide for add-on air conditioning. The ST9103 EFT is located in a control box mounted to the blower support rails. The R7184 primary control mounts to a 4x4 junction box connected to the oil burner, contains the safety circuits and provides input voltage for the separately mounted ignition transformer on top of the oil burner.
FIGURE 4 : ST9103 EFT
The circulating fan is controlled by the ST9103 EFT. The heat delay-on time is fixed at 30 seconds. This provides a delay between the start of the burner and the start of the circulating fan to reduce the amount of ambient unheated air flowing through the ductwork. The end of the circulating fan cycle is also delayed to remove residual heat from the furnace. There are four delay-off choices, 60, 90, 120 and 150 seconds, which are field adjustable by manipulating the DIP switches on the ST9103 EFT Board.
The cooling delay-on and delay-off times are fixed at 30 seconds each.
The furnace is protected against over-heating by fixed high temperature limits. These controls are factory set and are not field adjustable. If an over temperature condition is detected, one or both limit switches will interrupt power to the oil primary control, which will shut off the oil burner. The circulating fan will continue to operate. The high limit switches will automatically reset when the furnace returns to a safe temperature.
Unitary Products Group 7
035-17473-000-B-1101
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association (CSA). It is factory wired and requires
minimal field wiring. In Canada, all field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA- 70, National Electrical Code, and with local codes and regulations.
Thefurnaceshouldbewiredtoaseparateanddedi­cated circuit in the main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advis­able. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The fur­nace switch (service switch) should be clearly marked, installedinaneasilyaccessibleareabetweenthefur­nace and furnace room entry , and be located in such a manner to reduce the likelihood that it would be mis­taken as a light switch or similar device.
The power requirement for the P-HMX Series model is: 120 VAC, 1 ,60Hz.,12A.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the ST9103 EFT. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto-generating windings of the direct drive motor.
Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wir­ing diagram. Some micro-electronic thermostats require additional controls and wiring. Refer to the ther­mostat manufacturer's instructions.
The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid loca­tions where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, expo­sure to sunlight, heat from inside wall stacks, etc.
For thermostats with heat anticipators, the heat antici­pator should be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure cir-
cuit without first removing one of the two wires. To determine the heating circuit amperage draw:
1. Note and disconnectthe wires from the “R” and “W” ther­mostat terminals.
2. Connect an ammeter between the two disconnected wires from the thermostat.
3. Note the amperage reading.
4. Re-connect the thermostat wires. If the thermostat is serving a combination heating and air conditioning sys­tem, pay particular attention to polarity.
5. When the thermostat is reconnected and re-plumbed, adjust the heat anticipator setting to match the observed amperage reading.
HUMIDIFIER
A humidifier is an optional accessory available through most heating supplies outlets. Installation should be carried out in accordance with the humidifier manufac­turer's installation instructions. Water or water droplets from the humidifier should not be allowed to come into contact with the furnace heat exchanger. Terminals (115 v) are provided on the ST9103 EFT control. Do not use direct drive motor connections as a source of power for 120 VAC humidifiers and humidifier trans­formers.
OIL TANK
Oil storage tanks must be selected and installed in compliance with applicable codes; in Canada, CAN/
CSA-B139, Installation Code for Oil Burning Equip- ment, Section 6 and in the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment
Chapter 2. Observe all local codes and by-laws. In general, the oil tank must be properly supported and
remain stable in both empty and full condition. The oil tank must be fitted with vent and supply pipes to the outdoors. Refer to the above mentioned codes for siz­ing. The vent pipe must be no less than 1¼ inches I.P.S., and terminate with an appropriate vent cap in a location where it will not be blocked. The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery.
If located indoors, the tank should normally be in the lowest level, (cellar, basement, etc.). It must be equipped with a shut-off valve at the tank outlet used for the oil supply. The oil tank must be located as to not block the furnace / room exit pathway. Observe all clearances specified in the above mentioned codes.
,
8 UnitaryProductsGroup
035-17473-000-B-1101
PIPING INSTALLATION
In Canada, the entire fuel system should be installed in accordance with the requirements of CAN/CSA B-139, and local regulations. Use only approved fuel oil tanks piping, fittings and oil filters.
In the United States the installation must be in accor­dance with the requirements of NFPA No. 31 and local codes and regulations.
Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do not use compression fittings.
Pressurized or gravity feed installations must not exceed 3 PSIG. A pressure greater than 10 PSIG may cause damage to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds 11-1/2 feet, it may be necessary to use a pressure-regulating device approved for this purpose.
The P*HMX series furnace may be installed with a one pipe system with gravity feed or lift. The maximum allowableliftonasinglelinesystemis8feet.Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line sys­tem is complex because of the difficulty estimating the pressure drop through each fitting, bend and compo­nent in the line. In general, keep single line systems short as possible. If the furnace is to be installed in a suspended position, a two pipe system may be the bet­ter alternative. Two-stage oil pumps are not available for oil burners featuring the Beckett Clean Cut Fuel Unit. Table 5 tal + vertical) for single and two stage oil pumps. All dis­tances are in feet.
In retrofit applications,where an existing oil line system is in place, a vacuum check will help determine whether a 2-stage oil pump is necessary. The vacuum in a system featuring a single stage oil pump should not exceed 6” Hg. The vacuum in a system featuring a 2-stage oil pump should not exceed 15” Hg. (inches of mercury.
shows the allowable line lengths (horizon-
Table 5: Oil Lines
Copper Tubing Oil Line Lengths
Single Stage 2-Stage
Lift
(feet)
0 53 100 68 100 1 49 100 65 100 2 45 100 63 100 3 41 100 60 100 4 37 100 58 100 5 33 100 55 100 6 29 100 53 100 7 25 99 5 0 100 8 21 83 4 8 100
9 17 68 4 5 100 10 13 52 42 100 12 - - - - - - 37 100 14 - - - - - - 32 100 16 - - - - - - 27 100 18 - - - - - - 22 88
3/8”O.D.
Tubing
1/2”O.D.
Tubing
3/8”O.D.
Tubing
1/2”O.D.
Tubing
For additional information, see the installation informa­tion sheet affixed to the oil burner).
OIL FILTER
All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. For best results, install the oil filter as close to the burner as possible. When using an indoor oil tank, the oil filter may be installed at the tank downstream from the shut-off valve. If firing the furnace under the 0.65 gph rate, a 7 to 10 micron line filter should be installed as close to the oil burner as possible.
OIL BURNER NOZZLES
The P-HMX Series furnace is certified for multiple firing rates, ranging from 58,000 to 120,000 BTU/Hr. By manipulating the oil burner nozzle, flame retention head, and temperature rise, the furnace may be fired at an ideal rate for a wide range of structures.
Table 6: Nozzles
MODEL
P*HMX12F05701 0.50 / 70° A 0.50 / 80° A F0 P*HMX12F08001 0.70 / 70° A ) 0.70 / 80° A ) F0 P*HMX14F10001 0.80 / 70° A 0.80 / 80° A F3 P*HMX20F12001 1.00 / 70° A) 1.00 / 80° A) F3
NOZZLE (Delavan)
STD ALT HEAD
Unitary Products Group 9
035-17473-000-B-1101
COMBUSTION CHAMBER
This furnace is equipped with an efficient cerafelt com­bustion chamber. It is held in place by a retaining bracket.
WARNING
CHECK THE ALIGNMENT OF THE COMBUSTION CHAMBERAND OILBURNER BEFORE FIRING. ITIS POSSIBLE FOR THE COMBUSTION CHAMBER TO SHIFTIS SUBJECTED TOROUGH HANDLINGDUR­ING TRANSIT.
The cerafelt combustion chamber is quite soft initially. After firing, it becomes very brittle. Be sure to do all alignment and positioning adjustments before the first firing.
The combustion chamber should be inspected for dam­age or carbon build-up whenever the oil burner is removed for repairs or routine maintenance.
of air causes "soft" and "sooty" flames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel effi­ciency.
PREPARATIONS:
Drill a ¼” test port in the venting, ideally at least 2 diam­eters (12”) away from the furnace breaching, if venting horizontally from the furnace, or from the flue pipe elbow if venting vertically before reaching the furnace.
(see Figures 6 and 7).
CAUTION
Before operating the furnacecheck burneralignment with combustion chamber. The end cone of the air tubemustbecenteredtotheaccommodatingringpro­videdin thedesign of thecombustionchamber.Adjust as necesssary before
BURNER ELECTRODES
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation.
The electrode tips should be adjusted to a gap of 5/32”, 1/16” ahead of the nozzle, 7/16” above the centerline of the nozzle. The “Z” dimension (front edge of the burner head to the front face) of the nozzle is 1-1/8 inches.
The electrode porcelains should be free of cracks, the electrode tips should be tapered and free of burrs, and the contact rods must be clean and be in firm contact with the ignition transformer contact springs. The elec­trodes must not come into contact with the burner head.
OIL BURNER SET UP
The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack
first firing.
FIGURE 5 : TEST PORT LOCATION FOR SMOKE
TEST VERTICAL
FIGURE 6 : TEST PORT LOCATION FOR SMOKE
TEST HORIZONTAL.
Note A: Locate hole at least 6 inches on the furnace
side of the draft control. Note B: Ideally, hole should be at least 12 inches from
breeching or elbow.
10 UnitaryProductsGroup
035-17473-000-B-1101
The test port will allow flue gas samples to be taken and stack temperatures to be measured.
Before starting the burner, check the burner alignment with the combustion chamber (fire pot), check that the correct nozzle is tightened into place, and that the burner electrodes are properly positioned.
PROCEDURE:
Start the burner and allow it to run at least ten minutes. Set the air shutter to give a good flame visually. The air supply to the burner is controlled by the air shutter on the left side of the burner, and the bulk air band. To adjust, loosen the bolt on the movable shutter. Move the shutter gradually until a good flame (visually) has been achieved. Re-snug the bolt.
Check the initial draft setting as the furnace warms up. Thedraftmaybemeasuredatthetestport.Inmost cases, the pressure drop between the test port and the oil burner is negligible. The test port draft reading may be interpreted as the “over fire draft” reading. The draft should be set to - 0.02 inches w.c.
Check the oil pump pressure. All P-HMX furnaces are designed to be operated at 100 PSIG.
After reaching steady state, take a smoke test. If not indicating a trace, set the combustion air controls to provide a trace.
When the trace smoke has been established, measure the CO ing will range between 11.5% to 13.5% or the O ing approximately 3.3%.
Open the end air shutter (or open the bulk air band if necessary) until the CO age points, or, if measuring O reading increases 2 or 3 percentage points.
Take another smoke test; it should now be zero smoke. If the smoke test reads zero, tighten up the end air shutter, and bulk air band.
Re-test the draft, and the CO the settings have not shifted.
SMOKE TEST NOTE: If oily or yellow smoke spots are found on the smoke
test filter paper, it is usually a sign of unburned fuel. This indicates poor combustion. This type of problem may be caused by excess draft, excess air, or contami­nated fuel. Do not ignore this indicator.
2 or O2 in the flue gas. Typically, the CO2 read-
2 read-
2 readingdrops1or2percent-
2 content, until the O2
2 or O2 to be certain that
STACK TEMPERATURE:
Stack temperature will vary depending on fuel input, circulating air blower speed, and burner set up, etc. In general, stack temperature should range between 350°F to 450°F, but could be as high as 550°F, assum­ing that the combustion air is approximately room tem­perature (65°F - 70°F). In general, lower stack temperature indicates greater efficiency; however, excessively low stack temperature can lead to conden­sation forming in the chimney and / or venting. Sulphur and similar contaminants in the fuel oil will mix with condensation to form acids. Acids and resultant chemi­cal salts will cause rapid deterioration of the chimney and venting components, and may attack the furnace.
If the flue gases are below the range, it may be neces­sary to slow down the blower fan. If the flue gases are above the range, the blower fan may require speeding up. Stack temperature varies directly with the system temperature rise. System temperature rise is the differ­ence between the furnace outlet temperature and fur­nace inlet temperature as measured in the vicinity of the connection between the plenum take-offs and the trunk ducts. Typical temperature rise values range between 65°F and 85°F.
If the venting from the furnace to the chimney is long, or exposed to cold ambient temperatures, it is advis­able to insulate the venting with a removable, non-com­bustible, wrap-around type insulation to reduce stack temperature loss. The venting should be inspected annually to ensure that it is intact.
WARNING
IF THE FURNACE FAILS TO IGNITE, CHECK THE OIL TANK FUEL GAUGE. IF THE FUEL GAUGE SHOWS THAT OIL IS PRESENT, PRESS THE RESET BUTTON ONCE ONLY FAILS TO IGNITE, CONTACT YOUR SERVICE CONTRACTOR.
. IF THE BURNER
CAUTION
Unitary Products Group 11
ALL FURNACE CONTROLS ARE SENSITIVE AND SHOULDNOT BE SUBJECTED TO TAMPERING. IF PROBLEMSPERSIST, CALL YOUR SERVICECON­TRACTOR.
035-17473-000-B-1101
CIRCULATING AIR BLOWER
These furnaces are equipped with direct drive blower systems. Direct drive blower speed adjustments are not normally required in properly sized extended ple­num duct systems. The motor RPM and air CFM deliv­ery will vary automatically to accommodate conditions within the usual range of external static pressures typi­cal of residential duct systems. Under-sized duct sys­tems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over- amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem.
Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagram in Figure 9 or the wiring diagram label affixed to the furnace. THE NEUTRAL
WIRE (normally the white wire) IS NEVER MOVED TO ADJUST THE BLOWER SPEED.
FIGURE 7 : HEATING MODE “BLOWER OFF”
TIMINGS, ST9103
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The sim­plest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to con­nect the selected motor speed with a pig tail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnec­tion of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape.
If the joining of the blower speed wiring is done in the furnace junction box, tape off both ends of the unused wire.
The circulating fan start-up is delayed 30 seconds in the heating mode.
The circulating fan start-up is delayed 30 seconds in the cooling mode. The “fan off” is delayed 30 seconds in the cooling mode.
The “fan off” heating delay may be field adjusted by manipulating the dip switches. See Figure 7.
WARNING
DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYSBE CONNECTEDTOTHEMOTOR'S DES­IGNATED NEUTRAL TERMINAL.
CAUTION
DISCONNECTTHE POWER SUPPLY TOTHE FUR­NACE BEFORE OPENING THE BLOWER ACCESS DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURETO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECT­EDLY, CREATING A RISK OF DEATH OR PER­SONAL INJURY.
Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformers. The unused motor taps auto­generate sufficiently high voltages and may damage accessory equipment. Use the terminals provided on the ST9103 EFT.
12 UnitaryProductsGroup
CAUTION
Do not start the burner or blower fan unless the blower access door is securely in place.
MAINTENANCE AND SERVICE
Routine Maintenance By Home Owner
Other than remembering to arrange for the annual pro­fessional servicing of the furnace by the service or installation contractor, the most important routine ser­vice performed by the home owner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced monthly. The furnace is factory equipped with a semi-permanent type filter. If the filter is damaged, replace with filters of the same size and type.
During the routine service, inspect the general condi­tion of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advice your service or installation contractor.
Annual Service By Contractor
CAUTION
The combustion chamber is fragile. use care when inspecting and cleaning this area.
The heat exchanger should be inspected periodically and cleaned if necessary. if cleaning is necessary, SHUT OFF POWER TO THE FURNACE and remove the burner. Using a stiff brush with a wire handle, brush off scale and soot from inside the drum and flue pipe. To clean the radiator, remove the round covers on the inner radiator access pipes located on the front panel between the oil burner and the flue pipe.
Awirebrushcanbeusedtoloosendirtanddebrison the inside surfaces of the radiator. Clean out all accu­mulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Replace the clean­out covers.
035-17473-000-B-1101
Most direct drive blower motors are permanently lubri­cated by the motor manufacturer. These motors will have no oil ports. If the blower motor does contain oil ports, under normal operating conditions it will not require oiling for the first two years. Oil sparingly (a few drops) in each oil port with SAE 20 non-detergent oil. Oiling is most easily done with a "tele-spout" oilier. This oilier has a long flexible plastic spout. DO NOT OVER­LUBRICATE. Excess oil causes premature electric motor failure.
Inspect the blower fan. Clean it if necessary. Oil Burner Maintenance: Follow the instructions of the
oil burner manufacturer. (See oil burner manufacturer's instructions supplied with furnace). The oil burner noz­zle should be replaced annually. We recommend that the oil filter be changed on an annual basis.
The venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent pipe and fittings. The barometric damper should open and close freely.
All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan con­trol functions should be checked to ensure that all fan speeds are operating properly.
FURNACE INSTALLATION SET UP
The furnace must be set up as the final step in the installation.
A. THE OIL BURNER MUST BE SET UP FOL-
LOWING THE PROCEDURES OUTLINED IN OIL BURNER SET UP ON PAGE 11.
B. THE P-HMX12F057011 AND P-HMX12F08001
SHOULD OPERATE WITHIN A TEMPERA­TURE RISE OF 50°F TO 85°F; THE P-HMX14F10001 AND P-HMX20F1201 SHOULD OPERATE WITHIN A TEMPERA­TURE RISE OF 65°F TO 80°F. TO DETERMINE THE TEMPERATURE RISE, MEASURE THE SUPPLY AIR AND RETURN AIR TEMPERA­TURES WHEN THE FURNACE HAS REACHED STEADY STATE CONDITIONS. THIS IS THE POINT AT WHICH THE SUPPLY AIR TEMPER­ATURE STOPS INCREASING RELATIVE TO THE RETURN AIR TEMPERATURE. THE FUR­NACE MAY HAVE TO RUN 10 TO 15 MINUTES TO REACH STEADY STATE CONDITIONS. THE MEASUREMENTS MAY BE MADE WITH DUCT THERMOMETERS OR THERMOCOU­PLES USED IN CONJUNCTION WITH MULTI­METERS WITH TEMPERATURE MEASURE­MENT CAPABILITIES.
Unitary Products Group 13
035-17473-000-B-1101
The return air should be measured at a point where the thermometer will be well within the air stream near the furnace return air inlet.. Actual location is not particu­larly critical; however, avoid locations where the tem­perature readings could be affected by humidifier bypass ducts, the inside radius of elbows, etc.
The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet. Usually, the side mid-point of the supply air plenum take-off is ideal, providing it is out of the line of sight to the heat exchanger. If the thermometer is within the line of sight of the heat exchanger, the supply air readings may be skewed by radiant heat from the heat exchanger. If the plenum take-off is unsuitable, the supply air tempera­ture may be measured within the first 18 inches of the first segment of supply air trunk duct.
If the temperature rise is outside the recommended range, it may be adjusted by selecting alternate circula­tion fan motor speeds. If the temperature rise is too high, speed the fan up. If the temperature rise is too low, slow the fan down.
C. Keep in mind that the stack temperature varies
directly with the temperature rise. The higher the temperature rise, the higher the stack tempera­ture will be, resulting in lower efficiency. The lower the temperature rise, the lower the stack temperature will be, which, in some cases, may allow condensation to form in the chimney and other vent parts.
D. Test the high limit control to ensure that it is oper-
ating correctly. This may be done by temporarily removing the circulator fan heating wire or neu­tral wire. Turn of electrical power to the furnace before working with the motor wires. Be sure to protect any removed wires from shorting out on metal furnace parts. If the high limit test is suc­cessful, shut off the electrical power to the fur­nace, restore the proper motor wiring. Then restore power to the furnace.
E. Operate the furnace through a minimum of three
full heating cycles. During this time, check for fuel oil leaks, gross air leakage from the supply air ductwork, unusual noises originating any­where within the heating system which may cause some concern or annoyance to the home owner, etc.
F. Be sure that the home owner is familiar with the
furnace.The home owner shouldbe awareof the location of electrical circuit breaker or fuse, the
location of any electrical switches controlling the furnace, the location of the oil tank shut-off valve and how to operate the valve. The home owner should know where the oil tank gauge is located and how to read it.
It would be beneficial to review safety issues with the home owner, such as the danger of storing combusti­bles too close to the furnace, hanging anything on the furnace vent pipe, and especially the dangers of indis­criminately pressing the burner reset button.
IMPORTANT: Be sure that the home owner knows where the burner reset switch is located, and is aware that the reset switch is not to be activated more than once without a look for the cause of the problem, (lack of fuel, etc.). Be sure that the homeowner knows when to quit trying to start the furnace during these condi­tions and who to call for emergency service.
OPERATING INSTRUCTIONS
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply.
To Light Unit
Set the thermostatabove room temperature to call for heat. The burner will start. NOTE: If the furnace has been off for an extended period of time, it may be necessary to press the RESET button on the primary combustion control relay, (once only pressing the reset button does not start the fur­nace, refer to Appendix C, Troubleshooting.
After 30 seconds , as the furnace becomes warm, circulation fan will start.
The furnace will continue to run until the thermostat call for heat is satisfied.
Set the thermostat below room temperature. The oil burner will stop.
The air circulation blower will continue to run for 60, 90, 120 or 150 seconds after the oil burner has stopped, depending on the dip switch settings.
To Shut Down Unit
Set the thermostat to the lowest possible setting.
Set the manual switch (if installed) in the Electrical Power Supply Line to "OFF".
NOTE:
Ifthefurnaceistobeshutdownforan extended period of time, close the oil supply valve to the oil burner.
). If
14 UnitaryProductsGroup
035-17473-000-B-1101
WARNING
donot attempt tostartthe burnerwhenexcess oil has accumulated, when the furnace is full of vapour, or when the combustion chamberis very hot. never burn garbage or paper in the furnace, and neverleave paper or rags around the unit.
Table 7: Becket AF Oil Burner Set-Up
BECKETT AF SERIES OIL BURNERS
FURNACE
MODEL P-HMX12F05701 58,000 AF76BO 0.50 / 70° A 100 PSIG 0.50 GPH F0 3-3/8 in. P-HMX12F08001 79,000 AF76BO 0.70 / 70° A 100 PSIG 0.70 GPH F0 3-3/8 in. P-HMX14F10001 100,000 AF76XN 0.85 / 70° A 100 PSIG 0.85 GPH F3 2-3/4 in. P-HMX20F12001 118,000 AF76XN 1.00 / 70° A 100 PSIG 1.00 GPH F3 2-3/4 in.
In the United States, the R. W. Beckett “AF” Burner may be equipped with Beckett’s “Inlet Air Shut-Off”, Beckett Part No. AF/A 5861, to increase efficiency. It reduces the amount of air passing through the oil burner, combustion chamber, breaching, etc. up the chimney between burner cycles.
NOTE: THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP.
OUTPUT
BTUH
BURNER
MODEL NOZZLE
PUMP
PRESSURE
FLOW RATE HEAD
STATIC
PLATE
T able 8: Blower Performance Table
Furnace
Model
P-HMX12F05701 P-HMX12F08001
P-HMX14F10001 1/2 G10 - DD 55°-85°F 7.7
P-HMX20F12001 3/4 G12 - 10 DD 45°-75°F 12.5
Motor
HP
1/2 G10- DD 55°-85°F 77
Blower
Temp.
Rise
( ∆T)
Motor
Tip: These formulae will assist with the design of the duct work
CFM
OutputBonnet
()()
FLA
CFM
Speed
High 1368 1298 1223 1144 1046 938
Medium - High 1318 1256 1178 1108 1007 909
Medium - Low 1173 1132 1071 993 909 816
Low 856 833 791 748 692 610
High 1593 1493 1410 1321 1226 1110
Medium - High 1485 1410 1341 1258 1146 1035
Medium- Low 1182 1158 1135 1074 996 896
Low 810 802 785 750 703 633
High 2008 1977 1915 1867 1801 1715
Medium - High 1819 1802 1759 1724 1662 1588
Medium - Low 1734 1698 1680 1644 1588 1510
Low 1501 1491 1470 1428 1385 1319
RiseeTemperaturSystemx
External Static Pressure - Inches w.c.
0.20 0.30 0.40 0.50 0.60 0.70
RiseeTemperaturSystem
==
OutputBonnet
CFMx
085.1085.1
Unitary Products Group 15
035-17473-000-B-1101
FIGURE 8 : GENERAL DIMENSIONS (P-HMX SERIES)
20,500
20,000
Flue Pipe
C
H
14,000
22.125 31,000
22,000
Table 9: general dimens ions (inches)
Cabinet Plenum Openings Flue Filter Ship
Return Air (perm) Weight
Side FxG
Bottom Diam.
Height
H
WidthADepthBHeight
C
Supply Air
DxE
P*HMX12F05701 & P*HMX12F08001
22 31 49½ 20½ x 20 14 x 22 14 x 22 5 42 16 x 25 x 1 190
P*HMX14F10001 & P*HMX20F12001
22 31 58-1/8 20½ x 20 14 x 22 n / a 6 46½ 16 x 25 x 1 250
.
(lb.)
16 UnitaryProductsGroup
035-17473-000-B-1101
FIGURE 9 : WIRING DIAGRAM - OIL FURNACE WITH ST9103A EFT & R7184A CONTROL
Unitary Products Group 17
035-17473-000-B-1101
WIRING NOTES:P-HMX SERIES OIL FURNACE
CONTINUOUS FAN OPERATION:
The ST9103 EFT has provisions to run the blower motor continuously on a speed lower than the cooling or heating speeds. On a call for cooling, the fan motor will switch to cooling speed, and on a call for cooling, the fan will switch to heating speed, each over-riding the continuous low speed fan.
To obtain continuous low speed fan, route a 16 gauge stranded, type TEW, 105°C wire from the C nal on the ST9103 EFT to the low speed or medium low speed motor terminal. Both wire ends will require ¼ inch quick connects, (also known as “Faston” connec­tors or ¼” spade connectors). For additional control over the continuous low speed fan circuit, an SPST toggle switch may be wired in series between the motor terminal and the ST9103 EFT terminal. The con­tinuous low speed fan operation operates at 115 vac. Use appropriate wiring methods to prevent electrical shock.
ONT Termi-
WARNING
The HUM terminals provide power to a line voltage humidifier or humidifier step down transformer when the oil burner motor is operating.
THERMOSTAT HEATING CONNECTIONS:
The thermostat connections “R” and “W”, or “Rh” and “W” connect to the “R” and “W” screw terminals shown on the left hand side of Figure 10, on the ST9103 EFT located in the control box mounted to the blower mounting rails
TURN OFF ELECTRICAL POWER TO THE FUR­NACE WHEN SERVICING OR ALTERING FUR­NACE WIRING.
FAILURETODOSOMAYRESULTINSEVEREPER­SONALINJURY,PROPERTY DAMAGE OR DEATH.
ACCESSORIES:
The ST9103 EFT has provisions for supplying 115 volt power to an electronic air cleaner (EAC) as well as 115 volts to a line voltage humidifier or humidifier step down transformer. Both sets of terminals are ¼ inch quick connect type, rated at 1 A each.
TheEACterminalsprovidepowertoanelectronicair cleaner whenever the heating or cooling speeds are activated. Power is not speed is activated. If the electronic air cleaner must run during continuous low speed fan operation, wire the EAC into the furnace L1 terminal.
provided when the continuous
FIGURE 10 : THERMOSTAT CONNECTIONS
ST9103A
NOTE: All thermostat wires for both heating and cool­ing connect to the furnace at this point. A factory installed wiring harness connects the heating control functions to the R7184A oil primary control.
Figure 7,on page 12, shows the detail of the timed “Blower Off” dip switch settings. Figure 10 shows the dip switch location along the bottom edge of the control board, just above the “Honeywell” label.
NOTE: The Honeywell R8184G may be used in place of the R7184A. The R8184G is an intermittent ignition control whereas the R7184A is an interrupted ignition control. the R8184G continues to provide a spark dur­ing the entire burner cycle whereas the R7184A dis­continues the spark after the flame has been proved. The R8184G does not have the diagnostic led features found on the R7184A oil primary controls.
18 UnitaryProductsGroup
035-17473-000-B-1101
R7184 DETAILED SEQUENCE OF OPERATION
A. SAFETY CHECK IS MADE FOR FLAME (4 SECOND
DELAY).
1. When flame is not present, the R7184 will apply power to the burner motor and ignition trans­former.
2. When flame is present, the control remains in the idle state.
B. CONTROL ENTERS THE TRIAL FOR
IGNITION STATE.
C. CONTROL MONITORS THE BURNER FLAME.
1. When flame is present, the control enters ignition carryover state. (Continues to spark for 10-30 seconds).
a Provides continuous spark after flame is
sensed to assure that burner remains lit. b Turns on LED diagnostic light. c Startscarryover timer.
•Flame and call for heat are monitored.
Ιf flame is lost and lockout timer has not expired, R7184 will return to trial for i gnition state.
•If flame is lost and lockout timer has expired, R7997 will enter the recycle state.
•Recycle timer starts.
•Burner motor and igniter are turned off.
•LED diagnostic light flashes slow.
•Returns to idle state when recycle timer expires (60 seconds).
•Carryover timer expires.
•Enters run state.
•Igniter turns off.
Combustion continues until thermostat is satisfied or R7184 detects a loss of flame and enters into Recycle Mode.
Thermostat is satisfied - call for heat is terminated:
•R7184 shuts off burner motor.
•LED diagnostic light is off.
•R7184 returns to idle state.
Unitary Products Group 19
035-17473-000-B-1101
IDLE STATE
THERMOSTAT CALLS FOR HEAT
SAFETY CHECKFOR FLAME
NO FLAME
BURNER MOTOR STARTS
FLAME
SEQUENCE
OPERATION
REMAINS IN IDLE STATE
R7184
R7997
of
TRIAL F OR IGNITION
BURNER FLAME MONITORED
FLAME
CARRYOVER STATE
Provides Continuous Spark
LED Diagnostic Light On
Start Carryover Timer
FLAME
CARRYOVER TIMER EXPIRES
FLAME
RUN STATE
IgnitorTurns Off
THERMOSTAT SATISFIED
R7184 SHUTS OFF
R7997 SHUTS OFF:
Burner Motor
LED Diagnostic Light
NO FLAME
FLAME LOST
FLAME LOST
LOCKOUT STATE
R7997:
R7184
Shuts off burner motor
Shuts off ignitor
Fast Flashes LED
diagnostic light.
TO EXIT LOCKOUT
PRESS RESET
RECYCLE TIMER START S
R7184
R7997:
Shuts off burner motor
Shuts off ignitor
Slow Flashes LED
diagnostic light.
RECYCLE TIMER EXPIRES
(60 SECONDS)
RETURNS TO IDLE STATE
FIGURE 11 : SEQUENCE OF OPERATION
20 UnitaryProductsGroup
Table 10: ST9301A Detailed Sequence of Operation
Mode Action System Response HEAT Thermostat calls for heat. ("W" termi-
nal is energized).
Thermostat ends c all for heat. ("W" terminal is de-energized).
Burner fails to light. Oil primarly control locks out wit hin lockout timing (30 seconds).
Established flame fails. Burner motor is de-energized and oil primary control goes into recycle mode.
COOL Thermostat beginscall for cool.(G and
Y terminals are energized). Thermostat ends call for cool. (G and
Y terminals are de-energized).
FAN Thermostat begins call for fan. (G ter-
minal is energized). Thermostat ends call for fan. (Y termi-
nal is de-energized). Limit switch string opens. a Oil primary control shuts off burner.
ST9103A closes oil primary control T-T connections. Ignition system and R7184A and R8184G oill primary control start the furnace. Oil flows as long as the oil primary control senses flame. Burner motor is energized and heat “fan on” delay timing begins. When timing is complete (30 seconds), the circulator fan is energized a t heat speed.
R7184A or R8184G oil primary control is de-energized, terminating the burner cycle. Heat “fan off” delay timing begins. Length of delay depends on ST9103A dip switch settings. When timing is complete, the circulator fan is de-e nergized. ST9103A returns to standby mode. (Oil primary control and circulator fan are off, unless continuous fan operation is selected at the thermostat).
Burner motor is de-energized. (Even though thermostat is still calling for heat). If circulator fan has started it continues through the selected heat (fan off” delay period.
If the selected heat “fan off” delay timing is longer than the recycle delay timing, the circulator fan continues to run through the next trial for ignition.
Cooling contactor is energized immediately. Circulator fan is energized at cool speed.
Cooling contactor is de-energized immediately. Circulator fan turns off immediately.
Circulator fan is energized immediately at cooling spe ed.
Circulator fan is de-energized immediately.
b Circulator fan is energized immediately at heat speed. c ST9103A opens oil primary control T-T connections. d Circulating fan runs as long as limit string stays open. If there is a call for cooling or a fan, the circulating fan switches from heating to cool-
ing speed.
035-17473-000-B-1101
LIMIT
FAN Continuous circulating fan is con-
EAC Electronic Air Cleaner is connected Electronic air cleaner (EAC) connections are energized when the heat or cool speed
HUM Humidity control is connected. Humidifier connections are energized when the oil burner motor is energized.
Limit switch string closes (with existing call for heat).
Limit switch string closes (without existing call for heat).
nected.
a ST9103A begins heat “fan off” delay sequence. b Circulating fan turns off after the selected heat “fan off” timing. c ST9103A re-closes oil primary control T - T connections. d Oil primary control is energized, initiating burner light-off. a Circular fan turns off when heat “fan off” delay time is complete. bNormal operation resumes; ST9103A control is in standby mode awaiting next ther-
mostat command. Circulating fan is energized when there is no call for heat, cool, or fan.
If fan operation is required by a call for heat, cool, or fan, the S T9103A switches off the continuous fan speed tap before energizing the other fan speed.
of the circulator fan is energized. E AC connections are not energized when the optionional continuous fan termnal is energize d.
Unitary Products Group 21
035-17473-000-B-1101
R7184 LED DIAGNOSTIC LIGHT
The LED diagnostic light has several functions. It indi­cates the state or mode in which the oil burner is oper­ating. It will also indicate fault conditions, and help determine cad cell resistance while the burner is oper­ating.
NORMAL CONDITIONS:
The LED diagnostic light will turn on when the burner enters the carryover state; the point at which ignition spark is on, and will remain on through the run state, where the ignition spark is terminated but the burner continues to fire.
The LED diagnostic light will turn off at the end of the burner cycle as the R7184 enters the idle state, and will remain off until the next heating cycle.
FAULT CONDITIONS:
If the LED diagnostic light is flashing quickly; 1 Hz (1/2 second on / 1/2 second off), the R7184 is in the lockout state. To exit the lockout state, press the reset button.
If the LED diagnostic light is flashing slowly; ¼ Hz (2 seconds on / 2 seconds off), the R7184 is in the recycle state. This indicates that flame sensing was lost after the lockout timer expired during the ignition carryover state. The R7184 will return to the idle state within 60 seconds.
CAD CELL CONDITION:
If the LED diagnostic light is off, the cad cell is not sensing flame.
TROUBLESHOOTING
IMPORTANT:
Due to the potential hazard of line voltage, only a trained, experienced service technician should perform the troubleshooting procedure.
PRELIMINARY STEPS: Check the diagnostic light for indications of burner con-
dition. Refer to R7184 LED
DIAGNOSTIC LIGHT section
for details.
CAUTION
To prevent damage to the R7184, do not use an iron coretransformerignitiontestertocheckouttheR7997 ignitor.Iron core transformerignitiontesters can dam­age solid state ignitors.
CAUTION
When simulating a callfor heat atthe R7184, discon­nectat leastonethermostatleadwire from theT1 -T2 terminalsofthe R7184topreventdamage tothether­mostat. Neglecting this procedure may burn out the heat anticipator of a standard 24 cause harm to components within a micro-electronic thermostat.
VAC thermostat, or
If the LED diagnostic light is on, the cad cell is sensing flame, or viewing ambient light.
The resistance of the cad cell may be checked while theR7184isintherunstate
by pressing the reset but­ton. The LED diagnostic light will flash the following code:
Before checking the R7184, perform these preliminary checks, (repair or replace controls as necessary):
check the power supply; fuse box or breaker, any service switches, all wiring connections, and burner motor reset button (if equipped).
check the limit switches to ensure that the switch contacts are closed.
Table 11: Cad Cell Resistance
Flashes Resistance in Ohms
1 Lessthan 400 2 Between 400 - 800 3 Between 800 - 1600 4 Between 1600 - 5000
22 Unitary Products Group
check the electrode gap and position.
check the contacts between the R7184 and the electrodes.
check oil supply (tank gauge).
check the oil nozzle, oil filter, and oil valves.
check the piping or tubing to the oil tank.
check the oil pump pressure.
035-17473-000-B-1101
Check Oil Primary Control and Ignitor
If the trouble does not appear to be in the burner or ignition hardware, check the oil primary control and the ignitor by using the following equipment:
• screwdriver.
• voltmeter (0 - 150
VAC)
• insulated jumper wires with both ends stripped.
Preliminary Checks:
Make sure that limit switches are closed and that contacts are clean.
Check for line voltage power on the oil primary control black and white leadwires.
Refer to R7184 Troubleshooting for further infor­mation.
CAUTION
Electrical Shock Hazard. Troubleshootingis donewiththesystem powered. Be
careful to observe all necessary precautions.to pre­vent electrical shock or equipment damage.
R7184A Troubleshooting
CONDITION: Burner motor does not start when there is a call for heat.
Procedure Status Corrective Action
1. Check that the l imit switches are closed and con­tacts are clean. This includes the burner motor reset button.
2. Check for line voltage power at the oil primary con­trol. Voltage should be 120 vac between the black and white lead wire on the oil primary control.
3. Check indicator light with burner off, no call for heat (no flame).
4. Shield cad cell from external light. Indicator light turns
5. Jumper thermostat (T-T) terminals on R7184A
Important:
First remove one thermostat leadwire.
-- --
-- --
Indicator light is on. Cad cell or controller is defective, sees external light, or
connections are shorted. Go to s tep 4.
Indicator light is off. Go to step 5.
Eliminate external light source or permanently shield cad
off. Indicatorlight stays
on.
Burner starts Trouble in thermostat or limit circuit. Check thermostat or
Burner does not start
cell.
Replace cad cell with new cad cell and recheck.
If indicator light does not turn off, remove yellow lead­wires from R7184A and r e check.
If indicator light is still on, replace the R7184A control.
If the indicator light turns off, replace cad cell bracket assembly.
limit wiring connections. If connections are clean and tight, check thermostat for continuity.
Disconnect the line voltage power and open line switch. Check all wiring connections. Tighten any loose connections and recheck. If burner does not start, replace R7184A. .
Unitary Products Group 23
035-17473-000-B-1101
R7184A Troubleshooting (continued from previous page)
CONDITION: Burner starts t hen locks out on safety with indictor light flashing at 1 hz rate (1/2 second on, 1/2 second off)
Procedure Status Corrective Action
1) Check th limit switches are closed and contacts are clean. -- --
2) Check for line voltage power at the oil primary control. Voltage should be 120 vac. (nominal)
3) Check indicator light with burner off, no call for heat (no flame). Indicator light is on. Cad cell or controller is defective, sees external light, or connec-
4) Shield cad cell from external light. Indicator light turns off. Eliminate external light source or permanently recheck.
5) Jumper thermostat (T - T) terminals on R7184A
Important
First remove one thermostat leadwire.
6) Reset oil primary contro l by pushing in and releasing red reset button.
7) Listen for spark after burner turns on (after 2 second delay). Ignition is off Spark ignitor could be defective. Check for line voltage at ignitor ter-
8) Check indicator light after flame is established, but before oil pri­mary control locks out.
9) Check for cad cell sighting for view of flame: Disconnect line voltage power and open line switch. Unplug cad cell and clean cad cell face with soft cloth. Check sight­ing for clear view of flame. Replace cad cell in socket. Reconnect line voltage power and close line switch. Start burner.
10) Check cad cell. Disconnect line voltage power and open line switch. Remove existing cad cell and replace within new cad cell. Disconnectall wires from thermostat terminals to ensure that there is no call for heat. Reconnect line voltage power and close line switch. Expose new cad cell to bright light such as a flashlight.
11)Check cad cell bracket assembly.
Disconnect line voltage power and open line switch.
Remove cad cell wires from quick connect connectors on the R7184 and leave control leadwires open.
Apply power to device.
Place jumper across cad cell terminals after burner motor turns on.
NOTE: Restricted Mode - (Limited Reset): In order to limit the accumulation of unburned oil in the combustion chamber, the control can be reset only 3 times, after which, the control locks out. The reset count returns to zero each time a call for heat is successfully completed. To reset from
NOTE: Disable function: Pressing and holding the reset button will disable all functions until the button is released. The R7184 will restart at the beginningof the normal heat cycle on Safety Check
Restricted Mode: Press and hold the reset button for 30 seconds. When the LED flashes twice, the device has reset.
-- --
tions are shorted. Go to step 4.
Indicator light is off. Go to Step 5.
Indicator light stays on. Replace cad cell with new cad cell and recheck.
Burner starts. Trouble in thermostat or limit circuit. Check thermostat or limit wir-
Burner does not start. Disconnect the line voltage power and open line switch.
Indicator light stops flashing.
Indicator light contin­ues to flashat 1 Hz rate.
Ignition is on. Go to step 8. Ignition is on but no oil
is being sprayed into the combustion cham­ber.
Indicator light is on until the control locks out and starts flashing during lockout.
Indicator light stays off. Go to step 9. Burner locks out. Go to step10. Burner keeps running System is OK
Indicator light is on. Remount control onto burner housing. Go to step 6. Indicator light is off. Go to step 11.
If indicator light does not turn off, remove cad cellleadwiresfrom R7184 and recheck. If indicator light turns off, replace cad cell bracketassembly. If indicator light does not turn off, replace controller.
ing connections.
Check all wiring connections. Tighten any loose connections and recheck. If burner does not start, replace R7184A.
Go to step7.
Verify that the control is not in restrictedmode.(See notesat end of this table.) If not in restricted mode, replace R7184A.
minals. If line voltage is not present, replace R7184.
Check oil supply, and oil ine valve. Check for filter blockage or seized oil pump.
Replace R7184A.
Indicator light is on. Replace cad cell bracket assembly.
24 Unitary Products Group
Table 12: System & General Troubleshooting
035-17473-000-B-1101
Problem Possible Cause
Furnace will not start
Furnace will not start without first pushing oil primary control reset button.
(Happens on frequent basis)
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.
Thermostat not calling for heat.
No power to furnace.
Thermostat faulty.
Oil primary control faulty.
Photo Cell wiring shorted or room light leaking into photo cell compartment.
Open safety switch.
No fuel oil.
Cloggednozzle.
Cloggedoil filter.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner motor.
Photo Cell (Cad Cell) defective.
Remedy
Check thermostat and adjust. Also, check thermostat for accuracy; if it is a mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit breaker. also look for any other hand operated switch, such an old, poorly located furnace switchwhich was not removed during furnacereplace­ment.
Remove thermostat wires from R7184 control termi­nals T1-T2. Place a jumper across T1-T2. If furnace starts, replace thermostat, thermostat sub-base (if equipped), or both.
Check reset button on oil primary control. Remove thermostat wires from oil primary control terminals T1­T2. Check for 24v across T-T. If no voltage is present, check for 115vto oil primary control. If 115v is present, go to Table 10.
Check photo cell (cad cell) wiring for short circuits. Also, check for room light leaking into cad cell com­partment. Repair light leak if necessary. See Table10.
Check for open limit or auxiliary limit. also, check inter­nal wiring connections; loose connectors, etc.
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Table 2 as a guide.
Replace oil tank filter or in-line filter if used.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor.If burner motor is cutting out on
over-load, determine why. Replace if necessary. If cad cell is dirty, clean it. (Determine why cad cell is
getting dirty). If cad cell is poorly aimed, realign it. NOTE: the photo cell shuld have a resistance of 100Kin absence of light; a maximum of 1500in the presence of light. Ensure that room light is not leaking the cad cell compartment. (See diagnostic light section).
Unitary Products Group 25
035-17473-000-B-1101
Table 12: System & General Troubleshooting (Continued)
Furnace starts but cuts out requiring manual resetting the oil protector reset button.
Oil burner sputtering at nozzle.
No fuel oil
Cloggednozzle.
Cloggedoil filter.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner motor.
Water or contaminants in oil.
Frozen oil line.
Electrodes out of adjustment or defective.
Poor transformer high voltage connections or defective transformer.
Fuel oil filter clogged.
Defective oil pump.
Fuel oil line partially clogged or contains air.
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rat­ing plate or Table 2 as a guide.
Replace oil tank filter or in-line filter if used.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.
Check oil fuel lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary.
Drain fuel oil storage tank, replace fuel oil. (Consult with fuel oil supplier).
Gently warm oil line. Insulate oil line. (Outdoor piping size may require increase diameter).
Check electrode settings. Check electrodes for dirt buildup or cracks in porcelain.
Check contacts between ignition transformer and elec­trodes. If OK, replace ignition transformer.
Replace fuel oil storage tank filter and / or fuel oil in­line filter.
Check burner motor / fuel oil pump coupling. Check oil pump pressure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists replace oil line.
Excessive fuel oil consumption
Too much smoke.
System temperature rise too high.
Poor “fan off” delay timing selection (fan stops too soon).
Fuel oil leak.
Stack temperature too high.
Thermostat improperly adjusted or in poor location.
Insufficient combustion air adjustment at oil burner, or improper draft pressure.
Heat exchanger partially clogged.
System temperature rise ideally should not exceed 85°F.Check for clogged air filters. Check blower fan for excess dirt build-up or debris. Speed up blower fan if necessary.
Check “fan off” delay timing setting. Use a duct therm­meter in the supply air plenum take-off or first few inches of the suply air trunk duct. Ideally, the fan will shut at a temperature90° - 100°F. Manipulate the dip switch settings to come as close as possible to this “fan off” temperature.
Check fuel oil line for leaks. Repair or replace if neces­sary.
Check stack temperature. Stacktemperatures will nor­mally range from 350° to 450°F. Check draft regulator. Draft should be set to 0.02 in w.c.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If the thermostat is being influ­enced by drafts, sunlight, duct work, etc., relocate to more suitable location.
Adjust the oil burner combustion air band and draft regulator to gain the highest practical CO
practical O Up.
Check for soot build-up in heat exchanger flue pas­sages, especially in the outer radiator.
contentin the flue gases.See Burner Set
2
or lowest
2
26 Unitary Products Group
Table 12: System & General Troubleshooting (Continued)
035-17473-000-B-1101
Soot building up on blast tube (end coning).
Furnace will not warm home to desired temperature
Poor alignment betweenoil burner blast tube and combustion chamber.
Flame impingement caused by Incorrect nozzle angle.
Defective combustion chamber.
Air flow blocked or dirty air filter.
Thermostat adjustments or location.
Insufficient air flow.
Defective high limit control.
Under-sized nozzle.
Blower fan motor stopping intermittently on overload.
Burner motor stopping intermittently on overload.
check alignment. Blast tube should be centered with fire pot burner opening. Oil burner head should be 1/4 inch back from the inside surface of the combustion chamber.
Check nozzle size and angle. (See Table 2). Check distance from head to inside surface of the combus­tion chamber.
Check combustion chamber. Repair or replace.
Clean or replace air filter.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator etting if necessary. If the thermostat is being influ­enced by drafts, sunlight, duct work, etc. relocate to more suitable location.
Check all dampers. Open closed dampers, including registers in unused rooms. check system temperature rise. If temperature rise is too high, speed up blower fan.
Test high limit function of all limit switches. Use a duct thermometer to assess accuracy of limit control. Check for obstructions to air flow around limit switch bi-metal elements. Replace control if necessary.
Check nozzle. If problem is not caused by air flow problems, use larger nozzle, if permitted by rating plate.
Check blower fan motor amperage draw. Check motor ventilation ports, clean if necessary.Replace motor if necessary.
Check burner motor. Replace if necessary.
Home does not heat evenly Improper distribution of heat.
Air flow blocked or dirty air filter.
Supplyair temperaturetoo hot.
Insufficient air flow.
This is not likely to be a furnace problem. Balance duct system.
Clean or replace air filter.
Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.
Unitary Products Group 27
035-17473-000-B-1101
HOME OWNER’S REFERENCE TABLE
Installation Contractor:
Model No. Serial No. Date Installed Contractor Address
Postal Code: Telephone No.
Service Contractor if different from installation contractor
Service Tech Telephone No. After Hours No.
Fuel Supplier
Oil Supplier Telephone No. After Hours No.
28 Unitary Products Group
NOTES
035-17473-000-B-1101
Unitary Products Group 29
035-17473-000-B-1101
NOTES
30 Unitary Products Group
NOTES
035-17473-000-B-1101
Unitary Products Group 31
035-17473-000-B-1101
Heating and Air Conditioning
Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright© by Unitary Products Group 2001. All rights reserved. Supersedes: 035-17473-000-A-900 035-17473-000-B-1101)
Loading...