Unitary products group P-HMX12F05701, P-HMX12F08001, P-HMX14F10001, P-HMX20F12001 Installation Instruction

INSTALLATION INSTRUCTION
CONTENTS
INTRODUCTION....................................... 3
HEATLOSS .......................................... 3
LOCATIONOFUNIT.................................... 3
UPFLOWINSTALLATION................................ 4
HORIZONTALINSTALLATION............................ 4
NON-SUSPENDEDINSTALLATION ....................... 5
SUSPENDEDINSTALLATION............................ 5
AIRCONDITIONINGAPPLICATIONS...................... 5
COMBUSTIONAIR..................................... 5
CHIMNEYVENTING.................................... 5
BAROMETRICDAMPERCONTROL....................... 7
FURNACE CONTROLS ................................. 7
ELECTRICALCONNECTIONS............................8
HUMIDIFIER.......................................... 8
OILTANK ............................................ 8
PIPINGINSTALLATION................................. 9
OILFILTER........................................... 9
OILBURNERNOZZLES................................. 9
COMBUSTIONCHAMBER.............................. 10
BURNER ELECTRODES ............................... 10
OILBURNERSETUP.................................. 10
PREPARATIONS:..................................... 10
PROCEDURE:........................................ 11
CIRCULATING AIR BLOWE R ............................ 12
MAINTENANCEANDSERVICE.......................... 13
FURNACE INSTALLATION SET UP. ...................... 13
OPERATING INSTRUCTIONS ........................... 14
WIRINGNOTES...................................... 18
CONTINUOUSFANOPERATION: ........................18
ACCESSORIES:...................................... 18
THERMOSTAT HEATING
CONNECTIONS:...................................... 18
R7184 DETAILED SEQUENCE OF OPERATION .............20
R7184 LED DIAGNOSTIC LIGHT. . . ...................... 22
TROUBLESHOOTING ................................. 22
OIL FIRED WARM AIR FURNACE
P-HMX12F05701 - P-HMX12F08001
(Horizontal or Upflow Model)
P-HMX14F10001 - P-HMX20F12001
(Upflow Only)
Read this complete manual before beginning installation. These instructions must be kept with the furnace for future reference.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT.
035-17473-000-B-1101
WARNING
035-17473-000-B-1101)
INTRODUCTION
Please read these instructions completely and carefully before installing and operating the furnace.
IMPROPER INSTALLATION MAY CREATE A CON­DITION WHERE THE OPERATION OF THE PROD­UCT COULD CAUSE PERSONAL INJURYOR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERA TION,SERVICE OR MAINTENANCE CAN CAUSEINJURYORPROPERTYDAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDI­TIONAL INFORMATION, CONSULTA QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLA­TION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUD­ING BUT NOT LIMITED TO,BUILDING, ELECTRI­CAL AND MECHANICAL CODES.
The furnace must be installed and set up by a qualified contractor.
P*HMX12F05701 and P*HMX12F08001 are oil fired forced air multi-positional furnaces, with an output capacity range of 58,000 BTU/Hr to 79,000 BTU/HR. These furnaces may be installed in the up-flow posi­tion, as well as both horizontal left and right positions.
P*HMX14F10001 and P*HMX20F12001 are oil fired Upflow ONLY furnaces, with an output capacity range of 100,000 BTU/Hr. to 118,000 BTU/Hr.These furnaces shall be installed in the up-flow position only.
All model furnaces are listed with the Canadian Stan- dards Association,(CSA) and comply with both Canadian and American (U.S.) standards for use with No. 1 (Stove) and No. 2 (Furnace) Oil. Please refer to the tables in the appendix for performance and dimen­sional data.
WARNING
WARNING
Thefurnace area mustnot beused asa broomcloset orforanyotherstoragepurposes,as afirehazardbay be created. Never s tore items such as the following on, nearor in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
DO NOT USE GASOLINE, CRANK CASE OIL, OR ANY OIL CONTAINING GASOLINE.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in accordance with local codes.
In the United States of America, the installation of the furnace and related equipment shall be installed in accordance with the regulations of NFPA No. 31,
Installation of Oil Burning Equipment
,aswellasin
accordance with local codes. When installation or application questions arise, regu-
lations prescribed in the National Codes and Local Regulations take precedence over the general instruc­tions provided with this installation manual. When in doubt, please consult your local authorities.
All models are shipped assembled and pre-wired. The furnace should be carefully inspected for damage when being unpacked.
2 UnitaryProductsGroup
HEAT LOSS
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the manuals of the Heating, Refrigera-
tion and Air Conditioning Institute of Canada
(HRAI), or by any other method which is suitable for local conditions, provided the results obtained are in substantial agreement with, and not less than those obtained using the procedure described in their manu­als.
In the United States, Manual J.
titled, "Load Calcula-
tion" published by the Air Conditioning Contractors of Amer ica, describes a suitable procedure for calcu-
lating the maximum hourly heat loss.
LOCATION OF UNIT
The furnace should be located such that the flue con­nection to the chimney is short, direct and consists of as few elbows as possible. When possible, the unit should be centralized with respect to the supply and return air duct work. A central location minimizes the trunk duct sizing. All models may be installed on com­bustible floors.
Minimum installation clearances are listed in Table 1.
035-17473-000-B-1101
Table 1: Clearance to Combustibles
Models: P*HMX12F05701 and P*HMX12F08001
Location Up-flow Horizontal Top 2 in. 2 in. Bottom 0 in. 1 in. S/A Plenum 1 in. 1 in. Rear 1 in. 1 in. Sides 1 in. 1 in. Front
Flue Pipe 9 in. 9 in. Enclosure Closet Alcove
1
24” clearance is required for servicing.
Models: P*HMX14F10001 and P*HMX20F12001
Location Up-flow Top 1 in. Bottom 0 in. S/A Plenum 1 in. Rear 1 in. Sides 1 in. Front
Flue Pipe 4in. measured horizontally or below flue pipe. Flue Pipe 9 in. measured vertically or above flue pipe. Enclosure Closet
1
24” clearance is required for servicing.
9in.
9in.
1
1
NOTE: The recommended installation clearances do not take
intoconsiderationtheclearances necessary to replace the air filter or perform otherroutine maintenance.
9in.
1
Unitary Products Group 3
035-17473-000-B-1101
Table 2: General Specifications
MODEL INPUT OUTPUT NOZZLE BECKETT AF BURNER AIR
P*HMX U.S. GPH BTU/Hr. Delavan BURNER MODEL BURNER HEAD FILTER P*HMX12F05701 0.50 58,000 0.50 / 70°A AF76BO F0 16 x 25 x 1 P*HMX12F08001 0.70 79,000 0.70 / 70°A AF76BO F0 16 x 25 x 1 P*HMX14F10001 0.85 100,000 0.85 / 70°A AF76XN F3 16 x 25 x 1 P*HMX20F12001 1.00 118,000 1.00 / 70° A AF76XN F3 16 x 25 x 1
NOTE: Over-fire draft for all models is -0.02 in Water column. Static Plate Diameter: 3-3/8 inch for AF76BO and 2-
3/4 inc. for AF76XN.
UPFLOW INSTALLATION
These furnace models have been assembled for instal­lation in the up-flow position. Maintain all clearances to combustibles as outlined in Table 1 on page 3. Suggestion; as a measure to prevent fuel oil from accu­mulating in locations other than the combustion cham­ber, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the combustion chamber. Use shims made of noncombustible material.
HORIZONTAL INSTALLATION
The 057 & 080 BTU output model furnaces are assem­bled and shipped ready for installation in the upflow
position. The furnace may be installed in either of the horizontal positions; warm air discharging left or warm air discharging right by following these steps:
1. Rotate the furnace 90° to the desired position.
2. Remove the three nut and washer sets fastening the oil burner assembly to the furnace. Rotate the oil burner assembly to be in the upright position. (Ignition trans­former and / or oil primary control control should be on top).
3. Re-align the oil burner assembly to the combustion chamber (fire-pot), then secure into place with the three
nut and washer sets.
FIGURE 1 : TYPICAL SUSPENDED OPERATION
4 UnitaryProductsGroup
035-17473-000-B-1101
NON-SUSPENDED INSTALLATION
Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requires a clearance of 1 inch. This can be done by using non­combustible materials such as one inch thick channel iron or similar material. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. Use shims made of noncombustible material.
SUSPENDED INSTALLATION
Refer to Figure 1. Maintain clearances to combustibles as outlined in Table 1. Remove the four circular knock­outs on the top panel, and similarly, the four circular knock-outs on the bottom panel. The removed knock­outs allow 3/8 inch treaded road to be inserted through the interior of the furnace. Use care when inserting rods, since the foil backed insulation can be easily ripped and torn away from the panel surfaces. Secure the furnace with 2 inch minimum slotted angle or equiv­alent, as shown in Figure 4. The furnace must be sup­ported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot.
COMBUSTION AIR
If the furnace is installed in a closet or utility room, two ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bath­room). One opening shall be located 6” from the top and bottom of the enclosure at the front of the furnace. Each opening shall have a minimum free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances installed in the room.
For furnaces located in buildings of unusually tight con­struction, such as those with high quality weather strip­ping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well venti­lated attic or with the outdoors shall be provided, using a duct if necessary. The duct opening shall have a free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances to be installed. When a furnace is installed in a full basement, infiltration is normally adequate to provide air for combustion and draft opera­tion. Furnace rooms under 65m³ (700 ft³) should auto­matically be treated as confined space.
The Model CAS-2B-90E Furnace Boot manufactured byFieldControls,Inc.maybeusedwiththefurnaceto obtain combustion air directly from outdoors. Use of this device does not alter the need for ventilation air; however, it does provide a good direct source of com­bustion air and is connected directly to the oil burner.
CHIMNEY VENTING
AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air condition­ing, the furnace shall be installed in parallel with or with the evaporator coil upstream from the furnace to avoid condensation in the heat exchanger. In a parallel instal­lation, the dampers or air controlling means must pre­vent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either sys­tem unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifi­cally approved for such service.
The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evap­orator coil. Refer to Appendix B for recommended wir­ing and electrical connections of the air conditioning controls.
Unitary Products Group 5
The chimney must be sized correctly and be in good repair.If the chimney is oversized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.
If the chimney serves the furnace only, the vent should be sized at 4 inch minimum, 5 inch maximum. If the fur­nace is to be co-vented with other appliances, refer to
CAN/CSA B139, Installation Code For Oil Burning Equipment or NFPA 2 11, Standard for Chimneys, Fire­places, Vents, and Solid Fuel-Burning Appliances for
correct sizing information.
035-17473-000-B-1101
Table 3: Min. Chimney Base Temperatures (°F)
Model Chimney Height (ft.)
P-HMX12F05701 300 400 535 725 P-HMX12F08001 270 330 405 505 P-HMX14F10001 250 300 355 430 P-HMX12F12001 225 300 365 430
P-HMX12F5701 185 200 220 250 P-HMX12F08001 175 185 195 215 P-HMX14F10001 165 185 195 205 P-HMX12F12001 165 185 195 205
Chimneys with Thermal Resistance less than R6
Chimneys with Thermal Resistance greater than R6
IMPORTANT: The chimney must be capable of provid­ing sufficient draft at all times for the safe removal of
the products of combustion.
Table 4: Common Chimney Problems
Key Trouble Diagnostic Remedy
A Top of chimney lower
than surrounding
objects
B Chimney Cap or ven-
C Coping restricts
Key Trouble Diagnostic Remedy
D Obstruction in chim-
E Joist protruding into
F Break in chimney lin-
G Collection of soot at
H Offset Lower light on exten-
I Two or more open-
J Loose-seatedpipein
K Smoke pipe extends
L Failure to extend the
M Loose-fitted clean-
tilator.
opening.
ney
chimney.
ing.
narrow space in flue
opening.
ings to the same
chimney.
flue opening.
into chimney.
length of flue parti-
tion to the floor.
out door.
11 20 28 36
Observation Extend chimney
Observation Remove
Observation Make opening as
Can be found bylight
and mirror reflecting
conditions in chim-
ney.
Lowering a light on an extension cord.
Smoke test - build
smudge fire blocking
off other opening,
watching for smoke
to escape.
Lower light on exten-
sion cord.
sion cord.
Found by inspection
from basement.
Smoke test. Leaks should be
Measurement of pipe
from within or obser-
vation of pipe by
means of a lowered
light.
By inspection or
smoke test.
Smoke test. Close all leaks with
above all surround-
ing objects within 30
feet.
large as inside of
chimney.
Useweighttobreak
and dislodge.
Must be handled by
competent masonry
contractor.
Must be handled by competent masonry
contractor.
Clean out with
weighted brush or
bag of loose gravel
on end of line.
Change to straight or
to long offset.
The least important
opening must be closed, using some other chimney flue.
eliminated by
cementing all pipe
openings.
Length of pipe must be reduced to allow
endofpipetobe
flush with inside of
tile.
Extend partition to
floor level.
cement.
FIGURE 2 : COMMON CHIMNEY PROBLEMS
The chimney should be tested under “winter” condi­tions; doors and windows closed, all other fossil fuel burning appliances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot overcome the competi­tion for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re-evaluate the availability of combustion and ventilation air, and take corrective action.
NOTE: These furnaces are approved for use with L­Vent.
NOTE: Maximum Temperature for L-Vent is 575° F(300
°C).
The flue pipe should be as short as possible with hori­zontal pipes sloping upward toward the chimney at a rate of one quarter inch per foot. The flue pipe should not be smaller in cross section area than the flue collar on the furnace. The flue pipe should connect to the chimney such that the flue pipe extends into, and termi­nates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
See Figure 2 and Table 4 for common chimney prob­lems and their remedies.
6 UnitaryProductsGroup
CAUTION
Thefurnacemustbeconnectedtoafluehavingsuffi­cientdraftat alltimes to ensuresafe andproper oper­ation of the appliance.
The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deterioration during the annual inspection and servic­ing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. Refer to the latest edition of CAN/CSA B-139 for rules governing the installation of oil burning equipment. In the United States, refer to the latest edition of NFPA 31 for regula­tions governing the installation of oil burning equip­ment.
035-17473-000-B-1101
FIGURE 3 : R7184 OIL PRIMARY CONTROL
BAROMETRIC DAMPER CONTROL
This device is used in conjunction with conventional chimney venting. This control (or draft regulator) auto­matically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control can­not function properly. The draft regulator, must be installed within the same room or enclosure as the fur­nace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters (18”) from the fur­nace breaching and installed in accordance to the instructions supplied with the regulator. The flue outlet pressure (measured between the furnace and draft regulator) should be set to - 0.02 in. w.c.
FURNACE CONTROLS
The furnace is controlled by the ST9103 ELECTRONIC FAN TIMER (EFT) combined with an R7184 Oil Pri­mary Control.
These controls provide for add-on air conditioning. The ST9103 EFT is located in a control box mounted to the blower support rails. The R7184 primary control mounts to a 4x4 junction box connected to the oil burner, contains the safety circuits and provides input voltage for the separately mounted ignition transformer on top of the oil burner.
FIGURE 4 : ST9103 EFT
The circulating fan is controlled by the ST9103 EFT. The heat delay-on time is fixed at 30 seconds. This provides a delay between the start of the burner and the start of the circulating fan to reduce the amount of ambient unheated air flowing through the ductwork. The end of the circulating fan cycle is also delayed to remove residual heat from the furnace. There are four delay-off choices, 60, 90, 120 and 150 seconds, which are field adjustable by manipulating the DIP switches on the ST9103 EFT Board.
The cooling delay-on and delay-off times are fixed at 30 seconds each.
The furnace is protected against over-heating by fixed high temperature limits. These controls are factory set and are not field adjustable. If an over temperature condition is detected, one or both limit switches will interrupt power to the oil primary control, which will shut off the oil burner. The circulating fan will continue to operate. The high limit switches will automatically reset when the furnace returns to a safe temperature.
Unitary Products Group 7
035-17473-000-B-1101
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association (CSA). It is factory wired and requires
minimal field wiring. In Canada, all field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA- 70, National Electrical Code, and with local codes and regulations.
Thefurnaceshouldbewiredtoaseparateanddedi­cated circuit in the main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advis­able. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The fur­nace switch (service switch) should be clearly marked, installedinaneasilyaccessibleareabetweenthefur­nace and furnace room entry , and be located in such a manner to reduce the likelihood that it would be mis­taken as a light switch or similar device.
The power requirement for the P-HMX Series model is: 120 VAC, 1 ,60Hz.,12A.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the ST9103 EFT. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto-generating windings of the direct drive motor.
Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wir­ing diagram. Some micro-electronic thermostats require additional controls and wiring. Refer to the ther­mostat manufacturer's instructions.
The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid loca­tions where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, expo­sure to sunlight, heat from inside wall stacks, etc.
For thermostats with heat anticipators, the heat antici­pator should be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure cir-
cuit without first removing one of the two wires. To determine the heating circuit amperage draw:
1. Note and disconnectthe wires from the “R” and “W” ther­mostat terminals.
2. Connect an ammeter between the two disconnected wires from the thermostat.
3. Note the amperage reading.
4. Re-connect the thermostat wires. If the thermostat is serving a combination heating and air conditioning sys­tem, pay particular attention to polarity.
5. When the thermostat is reconnected and re-plumbed, adjust the heat anticipator setting to match the observed amperage reading.
HUMIDIFIER
A humidifier is an optional accessory available through most heating supplies outlets. Installation should be carried out in accordance with the humidifier manufac­turer's installation instructions. Water or water droplets from the humidifier should not be allowed to come into contact with the furnace heat exchanger. Terminals (115 v) are provided on the ST9103 EFT control. Do not use direct drive motor connections as a source of power for 120 VAC humidifiers and humidifier trans­formers.
OIL TANK
Oil storage tanks must be selected and installed in compliance with applicable codes; in Canada, CAN/
CSA-B139, Installation Code for Oil Burning Equip- ment, Section 6 and in the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment
Chapter 2. Observe all local codes and by-laws. In general, the oil tank must be properly supported and
remain stable in both empty and full condition. The oil tank must be fitted with vent and supply pipes to the outdoors. Refer to the above mentioned codes for siz­ing. The vent pipe must be no less than 1¼ inches I.P.S., and terminate with an appropriate vent cap in a location where it will not be blocked. The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery.
If located indoors, the tank should normally be in the lowest level, (cellar, basement, etc.). It must be equipped with a shut-off valve at the tank outlet used for the oil supply. The oil tank must be located as to not block the furnace / room exit pathway. Observe all clearances specified in the above mentioned codes.
,
8 UnitaryProductsGroup
035-17473-000-B-1101
PIPING INSTALLATION
In Canada, the entire fuel system should be installed in accordance with the requirements of CAN/CSA B-139, and local regulations. Use only approved fuel oil tanks piping, fittings and oil filters.
In the United States the installation must be in accor­dance with the requirements of NFPA No. 31 and local codes and regulations.
Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do not use compression fittings.
Pressurized or gravity feed installations must not exceed 3 PSIG. A pressure greater than 10 PSIG may cause damage to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds 11-1/2 feet, it may be necessary to use a pressure-regulating device approved for this purpose.
The P*HMX series furnace may be installed with a one pipe system with gravity feed or lift. The maximum allowableliftonasinglelinesystemis8feet.Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line sys­tem is complex because of the difficulty estimating the pressure drop through each fitting, bend and compo­nent in the line. In general, keep single line systems short as possible. If the furnace is to be installed in a suspended position, a two pipe system may be the bet­ter alternative. Two-stage oil pumps are not available for oil burners featuring the Beckett Clean Cut Fuel Unit. Table 5 tal + vertical) for single and two stage oil pumps. All dis­tances are in feet.
In retrofit applications,where an existing oil line system is in place, a vacuum check will help determine whether a 2-stage oil pump is necessary. The vacuum in a system featuring a single stage oil pump should not exceed 6” Hg. The vacuum in a system featuring a 2-stage oil pump should not exceed 15” Hg. (inches of mercury.
shows the allowable line lengths (horizon-
Table 5: Oil Lines
Copper Tubing Oil Line Lengths
Single Stage 2-Stage
Lift
(feet)
0 53 100 68 100 1 49 100 65 100 2 45 100 63 100 3 41 100 60 100 4 37 100 58 100 5 33 100 55 100 6 29 100 53 100 7 25 99 5 0 100 8 21 83 4 8 100
9 17 68 4 5 100 10 13 52 42 100 12 - - - - - - 37 100 14 - - - - - - 32 100 16 - - - - - - 27 100 18 - - - - - - 22 88
3/8”O.D.
Tubing
1/2”O.D.
Tubing
3/8”O.D.
Tubing
1/2”O.D.
Tubing
For additional information, see the installation informa­tion sheet affixed to the oil burner).
OIL FILTER
All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. For best results, install the oil filter as close to the burner as possible. When using an indoor oil tank, the oil filter may be installed at the tank downstream from the shut-off valve. If firing the furnace under the 0.65 gph rate, a 7 to 10 micron line filter should be installed as close to the oil burner as possible.
OIL BURNER NOZZLES
The P-HMX Series furnace is certified for multiple firing rates, ranging from 58,000 to 120,000 BTU/Hr. By manipulating the oil burner nozzle, flame retention head, and temperature rise, the furnace may be fired at an ideal rate for a wide range of structures.
Table 6: Nozzles
MODEL
P*HMX12F05701 0.50 / 70° A 0.50 / 80° A F0 P*HMX12F08001 0.70 / 70° A ) 0.70 / 80° A ) F0 P*HMX14F10001 0.80 / 70° A 0.80 / 80° A F3 P*HMX20F12001 1.00 / 70° A) 1.00 / 80° A) F3
NOZZLE (Delavan)
STD ALT HEAD
Unitary Products Group 9
035-17473-000-B-1101
COMBUSTION CHAMBER
This furnace is equipped with an efficient cerafelt com­bustion chamber. It is held in place by a retaining bracket.
WARNING
CHECK THE ALIGNMENT OF THE COMBUSTION CHAMBERAND OILBURNER BEFORE FIRING. ITIS POSSIBLE FOR THE COMBUSTION CHAMBER TO SHIFTIS SUBJECTED TOROUGH HANDLINGDUR­ING TRANSIT.
The cerafelt combustion chamber is quite soft initially. After firing, it becomes very brittle. Be sure to do all alignment and positioning adjustments before the first firing.
The combustion chamber should be inspected for dam­age or carbon build-up whenever the oil burner is removed for repairs or routine maintenance.
of air causes "soft" and "sooty" flames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel effi­ciency.
PREPARATIONS:
Drill a ¼” test port in the venting, ideally at least 2 diam­eters (12”) away from the furnace breaching, if venting horizontally from the furnace, or from the flue pipe elbow if venting vertically before reaching the furnace.
(see Figures 6 and 7).
CAUTION
Before operating the furnacecheck burneralignment with combustion chamber. The end cone of the air tubemustbecenteredtotheaccommodatingringpro­videdin thedesign of thecombustionchamber.Adjust as necesssary before
BURNER ELECTRODES
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation.
The electrode tips should be adjusted to a gap of 5/32”, 1/16” ahead of the nozzle, 7/16” above the centerline of the nozzle. The “Z” dimension (front edge of the burner head to the front face) of the nozzle is 1-1/8 inches.
The electrode porcelains should be free of cracks, the electrode tips should be tapered and free of burrs, and the contact rods must be clean and be in firm contact with the ignition transformer contact springs. The elec­trodes must not come into contact with the burner head.
OIL BURNER SET UP
The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack
first firing.
FIGURE 5 : TEST PORT LOCATION FOR SMOKE
TEST VERTICAL
FIGURE 6 : TEST PORT LOCATION FOR SMOKE
TEST HORIZONTAL.
Note A: Locate hole at least 6 inches on the furnace
side of the draft control. Note B: Ideally, hole should be at least 12 inches from
breeching or elbow.
10 UnitaryProductsGroup
Loading...
+ 22 hidden pages