MODELS: LA300
LB360
LB480
LB600
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes
clarify or make the installation easier. Cautions
prevent equipment damage. Warnings are given to alert
installer that personal injury and/or equipment damage
may result if installation procedure is not handled properly.
The LA and LB evaporator units are designed for use with the
HA/HB Series condensing units.Units are designed to match
up with LA/LB series Evaporator Blowers to meet ASHRAE
90.1 standards.
Each unit consists of a coil section and a blower section that
are factory assembled and shipped as shown in figures 3 and
4. These sections may be rearranged in the field for other air
discharge patterns. See figures 7, 8 and 9.
The LA and LB evaporator units have 24 volt normally closed
solenoid valves to match the 24-volt control circuits of the
Simplicity
HB360, HB480 and HB600 condensing units.
TM
control board in the HA300 as well as the
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE,
CAUTION and WARNING. Notes
make installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if
installation procedure is not handled properly.
are intended to clarify or
REPLACEMENT PARTS
Refer to parts manual for complete listing of replacement
parts on this equipment.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing.
LIMITATIONS
This unit must be installed in accordance with all national and
local safety codes. If no local codes apply, installation must
conform to the appropriate national code. The unit is
designed to meet National Safety Code Standards. If
components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense. See Table 1 for unit application data.
4Unitary Products Group
66337-YIM-D-0206
INDOOR PRODUCT NOMENCLATURE
L A 300 C 00 A 6 A AA 1
Model #
300
AAAdditional OptionsAA = None
Model Number
Description
Options
LProduct CategoryL = Air Handling Unit
AProduct Identifier
Nominal Cooling
Capacity
MBH
A = R-22 Standard Efficiency 2-Pipe
B = R-22 Standard Efficiency 4-Pipe
300 = 25 Ton
360 = 30 Ton
480 = 40 Ton
600 = 50 Ton
Rows Deep X Rows High4 x 404 x 404 x 504 x 62
Finned Length, Inches93939696
EVAPORATOR
COIL
CENTRIFUGAL
BLOWERS (2 PER UNIT)
FILTERS (THROWAWAY)
OPERATING CHARGE
(LBS R-22)
DRAINABLE HOT WATER
COIL ACCESSORY
NON-FREEZE, STEAM
DISTRIBUTING COIL
ACCESSORY
COMPONENT WEIGHT
Face Area, Feet
Tube (copper) OD, Inches3/83/83/83/8
Fins (Aluminum) per 1 inch16161616
Piping Connections,
Inches
Diameter X Width, Inches (Forward Curved)18 x 1820 x 18
Size and Quantity Per
Model, Inches
Total Face Area / feet
System 149.6530.0837.8346.59
System 2-30.0837.8346.59
Tube (copper) OD, Inches1/21/21/2
Rows Deep222
Fins (Aluminum) per 1 inch12128
Face Area, Feet
Connections (Supply & Return), Inches1 3/8 OD (Copper)1 5/8 OD (Copper)
Tube (copper) OD, inches1 (Outside) 5/8 (Inside)
Rows Deep1
Fins (Aluminum) per 1 inch8
Face Area, feet
Connection, (Brass)
Inches (NPTE)
Basic Unit (Less Motor & Drive)98098012601474
16 x 20 x 2-620 x 20 x 2-320 x 22 x 2--16 x 25 x 2--6
20 x 25 x 21063
25 x 25 x 2--6
2
2
2
Inlet2
Outlet1-1/2
Hot Water Coil150150190190
Steam Coil160160--
25.825.833.341.3
34.742.653.1
21.227.227.2
N/A
18.2
117 (5hp)117 (5hp)--
120 (7.5hp)120 (7.5hp)120 (7.5hp)141 (10hp)
-141 (10hp)141 (10hp)217 (15hp)
6Unitary Products Group
66337-YIM-D-0206
BLOWER MOTOR MOUNTING LOCATIONS
Units are shipped from the factory less motor and drives. The
blower motor and drive packages are ordered and shipped
separately for field mounting. However, the units are shipped
with the motor mounting assembly installed as shown in
1 for the LA300, LB360, LB480 and 2 for the LB600.
MOTOR MOUNTING
CHANNELS AND
MOUNTING PLATE
ARE ALWAYS
SHIPPED IN THIS
LOCATION.
FIGURE 1 - LA300 AN LB360/LB480 FACTORY
MOTOR MOUNTING POSITION
NOTE: The 5HP motors are not inherently protected.
A l t e r n a t i v e P o s i t i o n
1 F o r P i v o t B o l t s
A l t e r n a t e
P o s i t i o n 3
F o r P i v o t B o l t s
A l t e r n a t i v e P o s i t i o n
o t B o l t s
2 F o r P i v
LA300/LB360/LB480 MOTOR MOUNTING
The LA300, LB360 and LB480 ship from the factory with a
motor mounting adapter plate for use with the 7.5 and 10 HP
motors. If a 5 HP motor is used, the adapter is not necessary
and should be removed and discarded.
LB600 MOTOR MOUNTING
The motor mounting plate will accommodate a 10 or 15 HP
motor. One set of boltholes is provided on each end of the
motor mounting plate for either motor. The motor mounting
plate can be raised or lowered to any position on the adjustment screws to adjust the belt tension for the various pulley
settings to cover the complete range of blower speeds.
The physical size of the 15 HP motor reduces the adjustment
range of the motor mounting plate. To maximize this amount
of adjustment, one set of boltholes is provided near the
adjustment screws on each end of the motor mounting plate
(refer to 4).
For some motor/blower wheel arrangements, however, the
motor cannot be mounted in these bolt holes because the
motor terminal box would interfere with one of the blower section panels. To make these motor/blower wheel arrangements possible, a second set of boltholes is provided near
the pivot bolts on each end of the motor mounting plate.
1 5 H P
1 0 H P
1 5 H P
1 5 H P
A d j u s t m e n t
S c r e w ( 2 )
M o t o r M o u n t i n g P l a t e
( S t a n d a r d L o c a t i o n
a s S h i p p e d )
P i v o t B o l t ( 2 )
FIGURE 2 - LB600 FACTORY MOTOR MOUNTING
POSITION
A d j u s t m e n t
S c r e w H o l e s
1 5 H P
1 5 H P
1 5 H P
1 0 H P
FIGURE 3 - LB600 MOTOR MOUNT PLATE
The motors used with the evaporator blower are 3-phase and
can drive the blower wheels from either end of the blower
section. Reversing the direction of rotation can be accomplished by changing the connection of the power supply wiring at the motor terminal box.
NOTE: The 7.5-15 HP blower motors have solid bases
and are not inherently protected. For proper
operation, these motors require overload
heater elements. Please see current product
price pages for overloads.
Unitary Products Group7
The 15 HP drive package requires two different lengths of
belts to vary the blower wheel RPM over the complete range
of rated conditions. When the motor is mounted near the
adjustment screws, the two lengths of belt are interchangeable except for the higher and lower limits of blower wheel
RPM. When the motor is mounted near the pivot bolts, the
shorter length of belt is recommended for the higher blower
wheel Rpm's and the longer length of belt is recommended
for the lower blower wheel Rpm's. See Page 7 for the recommended blower motor locations.
66337-YIM-D-0206
MOTOR MOUNT ARRANGEMENTS
The motor mounting arrangement can be changed to allow
motor access based on the airflow arrangement required.
The recommended motor location for each blower arrangement is as follows.
LA300/LB360/LB480 MOTOR ARRANGEMENTS
The LA300, LB360 and LB480 units are shipped with the
motor mount in location A as shown in 4. If this is the desired
position, the motor mounting assembly is already in the correct position and the motor and drive package can be
installed without modifications.
ADDITIONAL MOTOR ARRANGMENTS FOR LA300/
LB360/LB480
Move the entire motor amounting assembly (both the mounting plate and the channels) so that the mounting plate will be
in the correct location.
1.Rotate the motor mounting plate 180 degrees on the
mounting channels. (For locations B, and D only! Do not
rotate the plate for location C or E.)
M O T O R
M O T O R
M O T O R
M O U N T I N G
M O U N T I N G
C H A N N E L S
P L A T E
FIGURE 4 - LA300/LB360/LB480 MOTOR
LOCATION A
2.Install the motor and drive package.
NOTE: The blower section must be lifted off the evap-
orator section to gain access to the mounting
channel fasteners. Since these sections have
to be repositioned for the arrangements 2
through 10 and 12 of 6, the motor mounting
assembly should be relocated before the two
sections are rejoined.
ARRANGEMENT 1, 4, 8 OR 11
B
A
SEE
NOTES
ARRANGEMENT 3, 5 OR 10
SEE
NOTES
E
NOTE: Since the motor mounting assembly cannot be
FIGURE 5 - LA300/LB360/LB480 MOTOR ARRANGEMENTS
ARRANGEMENT 2, 6 OR 7
SEE
NOTES
D
C
ARRANGEMENT 9 OR 12
SEE
NOTES
C
secured to the panel with the blower openings,
the motor cannot be installed in either of the
normally recommended bottom positions.
8Unitary Products Group
66337-YIM-D-0206
LB600 MOTOR ARRANGEMENTS
The LB600 unit is shipped with the motor mo unt in the standard location as shown in 2.
If this is the desired position, the motor mounting assembly is
already in the correct position and the motor and drive package can be installed without modifications.
RE-LOCATING THE LB600 MOTOR MOUNTING PLATE
The motor mounting plate can be re-located in three alternate
positions:
AL TERNATE POSITION ONE
For locating motor mounting plate in alternate position one,
see 3 and re-locate as follows:
1.Remove pivot bolts from the mounting plate.
2.Remove the mounting plate from the adjustment screws.
3.Rotate mounting plate 180.
4.With pivot bolts removed in Step 1 fasten the mounting
plate to alternate position No. one.
5.Fasten mounting plate to the adjustment screws.
AL TERNATE POSITION TWO
The motor mounting plate, the pivot bolts and the adjustment
screws can be moved into a position similar to the one shown
as standard in 3 but under the other blower scroll. The framework under each blower scroll has the same bolthole
arrangement.
ALTERNATE POSITION THREE
The motor mounting plate, the pivot bolts and the adjustment
screws can be moved into a position similar to the one
detailed in alternate position one but behind the other blower
scroll. The framework behind each blower scroll has the
same bolthole arrangement.
AIR DISCHARGE CONVERSION
LA360/LB360/LB480 AIR DISCHARGE
The LA300 LB360 and LB480 units are shipped for upflow
operation, but may be converted for any of the illustrated air
discharge patterns shown in 7 and 8. Convert as follows:
1.Remove the panels from the blower section.
2.Remove the Phillips machine screws located inside casing corner angles that hold the coil and blower sections
together.
3.Rotate the blower section for the desired air discharge
pattern.
NOTE: Before proceeding to step 4, see the section
on the blower motor mounting locations and
mount the blower motor in the desired position.
4.If accessory heating coils are used, mount heating coil
between cooling coil and blower sections. Screw fastening locations are the same for all sections and heating
accessories. If heating coils are not used, fasten coil
section to blower section with machine screws removed
in step 2.
5.Before replacing panels, see duct connections and drain
connections.
6.Replace panels.
Unitary Products Group9
66337-YIM-D-0206
1
BLOWER
AIR
AIR
EVAPORATOR
COIL
AIR
2
AIR
**
A I R
AIR
4
AIR
AIR
5
**
FIGURE 6 - VERTICAL AIRFLOW ARRANGEMENTS
78
VERTICAL ARRANGEMENTS
AIR
AIR
AIR
3
AIR
*
6
* IF REQUIRED, SOME AIR CAN
BE BROUGHT THROUGH THE
BOTTOM OF THE EVAPORATOR
SECTION.
AIR
*
9
AIR
AIR
AIR
10
AIR
AIR
FIGURE 7 - HORIZONTAL AIRFLOW ARRANGEMENTS
AIR
11
AIR
AIR
AIR
12
AIR
AIR