INSTALLATION
(AIR COOLED)
MANUAL
CONTENTS
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 4
AGENCY APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SPLIT-SYSTEM
AIR CONDITIONER
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes
clarify or make the installation easier. Cautions
to prevent equipment damage. Warnings
alert installer that personal injury and/or equipment damage may result if installation procedure is not handled
properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
are intended to
are given
are given to
MODEL: LA120
035-18525-001-B-0203

TABLE OF CONTENTS
035-18525-001-B-0203
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . .3
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . .4
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
AGENCY APPROVALS . . . . . . . . . . . . . . . . . . . . . . .4
INSPECTION 4
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VERTICAL / HORIZONTAL INSTALLATION . . . . . . . . . . 8
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
REFRIGERANT MAINS . . . . . . . . . . . . . . . . . . . . . . . . . . 9
POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . 10
SUPPLY AIR BLOWER ADJUSTMENT . . . . . . . . . . . . . 11
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
EVAPORATOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DRAIN PAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
BELTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
LIST OF FIGURES
Fig. #
1. UNIT SUSPENSION MOUNTING LA120 (HORIZONTAL
APPLICATIONS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. VERTICAL AND HORIZONTAL APPLICATION . . . . . . 8
Pg. #
Fig. # Pg. #
8. FIELD WIRING DIAGRAMS FOR POWER SUPPLY . 12
9. FIELD WIRING DIAGRAM COOLING
(COOLING ONLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
10. TYPICAL MOTOR MOUNTING ASSEMBLY . . . . . . . 13
11. HOLE LOCATIONS FOR PRESSURE DROP
READINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
12. PRESSURE DROP ACROSS A DRY
EVAPORATOR COIL VS. SUPPLY AIR CFM . . . . . . 14
13. BLOWER PERFORMANCE CURVE . . . . . . . . . . . . . 15
14. UNIT DIMENSIONS AND CLEARANCES . . . . . . . . . 16
LIST OF TABLES
Tbl. #
1. PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. APPLICATION LIMITATIONS . . . . . . . . . . . . . . . . . . . 5
3. LA120 UNIT SUSPENSION WEIGHTS (LBS) . . . . . . . 7
4. ELECTRIC HEATER DIMENSIONS FA120 . . . . . . . . . 9
5. ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . 11
6. SUPPLY AIR BLOWER MOTOR PULLY
ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7. BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . 14
8. SUPPLY AIR BLOWER PERFORMANCE 1, 2 . . . . . 15
9. ACCESSORY STATIC RESISTANCE (IWG)
(TO BE INCLUDED WITH DUCT SYSTEM
STATIC RESISTANCE) . . . . . . . . . . . . . . . . . . . . . . 16
Pg. #
3. VERTICAL AND HORIZONTAL APPLICATION . . . . . . 8
4. SUPPLY AIR PLENUM ACCESSORY . . . . . . . . . . . . . 9
5. BASE ACCESSORY (VERTICAL ONLY) . . . . . . . . . . . 9
6. RECOMMENDED DRAIN PIPING . . . . . . . . . . . . . . . 10
7. RETURN AIR GRILLE ACCESSORY (VERTICAL) . . 10
2 Unitary Products Group

035-18525-001-B-0203
NOMENCLATURE
YORK SPLIT INDOOR PRODUCT NOMENCLATURE
L A
120 C 0 0 A 2 A A A 1 A
Model # Model Number Description Options
L Product Category L = Air Handling Unit-Cooling F = Air Handlng Unit-Heat Pump
A Product Identifier
Nominal Cooling
120
C Heat Type C = Cooling Only
00
A Airflow Options A = None
2Voltage 6 = 208/230-460-3-60
A Factory Options
AA Special Options
1 Generation
AStyle A = Style A B = Style B
*NOT AVAILABLE IN HEAT PUMP
Capacity
MBH
Nominal Heating
Capacity
A = R-22 Standard Efficiency 2-Pipe
B = R-22 Standard Efficiency 4-Pipe
090 = 7-1/2 Ton
120 =10 Ton
150 = 12-1/2 Ton
180 = 15 Ton
240 = 20 Ton
00 = No Heat Installed
A = None
B = Disconnect
AA = None
AC = Technicoat Coil
st
1 = 1
Generation 2 = 2ndGeneration
Unitary Products Group 3

GENERAL
This completely assembled unit includes a well-insulated cabinet, a DX cooling coil with copper tubes and
aluminum fins, 1 expansion valve, 1 distributor, throwaway filters, a centrifugal blower, a blower motor contactor and a small holding charge of Refrigerant-22. A
blower motor with adjustable drive is factory mounted
on every unit.
035-18525-001-B-0203
This product must be installed in strict compliance with the enclosed installation instructions
and any applicable local, state, and national
codes including but not limited to, building,
electrical and mechanical codes.
Supplemental resistance heaters, a supply air plenum,
a return air grille and a base are available as accessories for field installation.
The unit is shipped in the vertical position with a vertical air discharge. The blower section can be repositioned as shown in Figure 2 for horizontal applications.
SAFETY CONSIDERATIONS
Installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes
to clarify or make the installation easier. Cautions
given to prevent equipment damage. Warnings
given to alert installer that personal injury and/or equipment damage may result if installation procedure is not
handled properly.
Improper installation may create a condition
where the operation of the product could cause
personal injury or property damage.
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
property damage. refer to this manual for
assistance or additional information, consult a
qualified installer, service agency.
are intended
are
are
RENEWAL PARTS
Refer to parts Manual for complete listing of replacement parts on this equipment. The forms referenced in
this instruction may be ordered from:
Standard Register
2101 West Tecumseh Road
Norman, Oklahoma 73069
Toll Free TEL: 877-318-7920
Toll Free FAX: 877-379-7920
This instruction covers the installation and operation of
evaporator blower units. For information on the operation of the matching condensing unit, refer to Form
035-18506-001.
AGENCY APPROVALS
Design certified by UL as follows:
1. For use as a cooling coil/air handler only.
2. For indoor installation only.
INSPECTION
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident,
the extent of damage should be noted on the carrier's
freight bill. A separate request for inspection by the
carrier's agent should be made in writing.
4 Unitary Products Group

035-18525-001-B-0203
TABLE 1: PHYSICAL DATA
DESCRIPTION
Rows Deep 3
Rows High 32
Evaporator
Coil
Blower
Filters
1
2
Electric
Heaters
Centrifugal
Operating Charge (Refrigerant-22) Lbs. - Oz. 5-8
Weight (Lbs.)
Accessory
Weights (Lbs.)
1.
Refer to data in Table 8 for complete motor specifications.
2.
Filters are throwaway type 2” filters may be used, if required by removing the 1” filter retaining angles provided in the filter rack.
Finned Length (in.) 54.5
Fins / Inch 13
Tube O. D. (in.) 3/8
Face Area (Sq. Ft.) 12.1
Wheel Dia. X Width (in.) 18 X 18
Qty. & Size (in.) (6) 20 X 20 X 1
Face Area (Sq. Ft.) 16.7
Shipping 439
Operating 399
10 KW 66
16 KW 70
26 KW 74
36 KW 77
Supply Air Plenum 144
Base 65
Return Air Grille 19
Horizontal Suspension 68
Steam Coil 149
Hot Water Coil 135
UNIT MODEL
LA120
TABLE 2: APPLICATION LIMITATIONS
Power
Supply
208/230-3-60 187 252
460-3-60 432 504
1.
Utilization Range”A” in accordance with ARI Standard 110.
Unitary Products Group 5
Voltage
Var iat ion
Min. Max. Min. Max. Min. Max. Min. Max.
1
Supply Air Range
CFM
2800 6800 65/67 96/72 - 77
Entering Air Temperatures, ºF
Cooling-db/wb Heating-db