Unitary products group DSH, DSV, KSV, R-410A, KSH Installation Instructions Manual

MODELS DSH/KSH/DSV/KSV
R-410A LOW-AMBIENT KI T
Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910)
LOW-AMBIENT KIT
MODELS DSH/KSH/DSV/KSV
R-410A AIR CONDITIONING UNITS
INSTALLATION INSTRUCTIONS
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDLINES
This equipment is a relativ ely complicated apparatus. During installation, oper ation, maintenance or service, individuals may be expose d to certain components or conditions includi ng, but not l imi ted to: ref ri gerant s materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and respon­sibilty of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard.
DANGER indicates an imminently haz­ardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially haz­ardous situation which, if not avoided, could result in death or serious injury.
All wiring must be in accordance with published specifi cations and must be per formed ONLY by qualified service personnel. Johnson Controls will not be responsible for damages/problems resulting from improper connections to the contr ols or appli ca tion of impr oper contr ol si gnals . Failure to follow this will void the manufacturers’ warranty and cause serious damage to property or injury to persons.
, oils,
which it is situated, as well as sever personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual possesses independent training that will en­able them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood t his document a nd any refer enced materi a ls. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.
CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually and instruction will be given, together with a brief explanation.
NOTE is used to highlight additional in­formation which may be helpful to you.
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. While Johnson Controls makes no commitment to up-date or provide current information automatic ally to the manual owner, that information, if applicable, can be obtained by contacting the nearest Johnson Controls service office.
It is the responsibi lity of operating/serv ice personnel as to the applicability of these documents to the equipment in question. If there is any ques tion in the mind of operating/service personnel as to the applicability of these documents, then, prior to working on the equipment, they should verify with the owner whether the e qui pment has been modif ied and if current literature is available.
TABLE OF CONTENTS
4 ……General Information
4 ..…..Damper Installation 6 ……Pressure Control Panel Installation 6 ……Pressure Transducer Installation
Before installing this accessory kit, turn off electrical power to the equipment. Failure to do so could result in electrical shock, resulting in component damage, injury or death.
8 ……Damper Actuator Installation & Wiring 10 ……Actuator Rotation Verific ation 11 ……Interconnection Drawings 13 ……Sequence of Operation 14 ……Schematics
GENERAL INFORMATION
If unit operation is required at outdoor ambient below 45 deg F, the optional Low Ambient Damper kit should be installed to maintain acceptable condensing pressure.
In horizontal units, the damper is installed directly over the intake duct connection. The damper in vertical units is installed over the exhaust duct connection (as illustrated below). The damper position is determined by refrigerant pressure. A direct-coupled electric damper actuator motor drives the damper open or closed, depending on the output signal from a proportional pressure control module. A pressure transducer senses the high-side refrigerant pressure, through a service access port, located on the liquid refrigerant line leaving the condenser. The pressure
controller, complete with terminal connection blocks for wiring, is attached to a field-installed mounting bracket. Appropriate mounting hardware for the pressure control module and the damper actuator motor are provided with the kit. A routing hole is provided in the condenser corner panel, near the actuator mounting location, to allow installation of the plenum-rated cable between the motor and the control module.
A solid-state timer(s) is provided with the damper kit. The timer will bypass the low pressure switch during compressor start-up. The time delay allows the condensing pressure to rise sufficiently for refrigerant flow through the evaporator to be established, thereby eliminating nuisance low-pressure lock-outs.
3
On Dual compressor units, the transducer MUST be connected to the #1 circuit liquid line fitting. Connection to the second stage refrigerant circuit will result in system malfunction.
When installing the transducer, observe all regulations governing the handling and containment of hazardous or regulated materials (refrigerants or lubricants).
DAMPER INSTALLATION HORIZONTAL UNITS (DSH / KSH SERIES)
1) Remove the factory installed duct attachment flanges from the condenser intake opening. Retain the two short (vertical) flanges – these will be used in installation of the damper.
2) The kit contains two long flanges, which reduce the intake opening height to match the damper dimensions. Attach these replacement flanges using the original holes and screws.
3) Re-attach one of the original vertical flanges as close to the edge of the corner post as possible (approx 1/8” from edge of corner).
4) Position the damper casing between the two horizontal flanges surface, and butt the drive end of the damper against the vertical flange at the corner of the unit. Ensure that the damper is orientated as shown – drive shaft at the top of unit.
5) Secure the damper using the self-drilling screws provided (drive screws the holes in the flanges, into the metal damper casing).
6) Attach the remaining vertical flange, opposite the drive end of the casing.
7) Ensure that the damper assembly rotates freely, with little or no resistance, by rotating the drive shaft by hand.
4
VERTICAL UNITS (DSV / KSV SERIES)
1) The kit includes two vertical and two horizontal factory supplied duct flanges.
2) Locate pilot holes at condenser exhaust and line up duct flanges accordingly.
3) Secure flanges using self-drilling sheet metal screws. The horizontal flanges should be flush with the condenser exhaust opening.
4) Position the damper inside the flanges and secure with screws.