These split-system condensing units are designed to
operate at ambient temperatures down to 40°F. This
accessory will insure safe operation at ambient temperatures down to 0°F. The VLT6000 control monitors the
refrigerant system and will vary the condenser fan
speed based on the discharge pressure. One controller
is required for each fan to be controlled. Therefore, two
accessory kits are required for each unit. This ins truction provides all the necessary information to properly
field-install a low ambient accessor y on the con den sing
units listed in Table 1. Components that are supplied in
the respective accessory are listed in Table 2, and pictured in Figure 1.
*. “X” denotes Model number needed for application.
†. Crankcase Heaters supplied are dependent on accessory
ordered.
473-24615-00X*
ea
1
2 ea025-37425-57530/40 Ton Crankcase Heater
2 ea025-37474-57525/50 Ton Crankcase Heater
VLT6000 Condenser Fan Speed
Control and Enclosure
The 2LA047 series low ambient accessories are
intended for use with the 25-50 T on Split System condensing units only. UPG cannot guarantee proper
operation for any application of this VLT6000 controller for other equipment or applications. Contact your
local branch or distributor for any application related
questions.
Improper installation, adjustment, service or maintenance can cause injury or property damage. Th erefore, only a qualified installer or qualified service
personnel should perform this conversion.
If the unit is connected to power sources, make sure
that all electrical power to the unit has been disconnected.
Unitary Products Group
035-20209-000-A-0904
RED WIRE = 10.0 VDC SUPPLY
BLACK WIRE = COMMON
WHITE WIRE = OUTPUT
1. Disconnect all electrical power to the unit.
2. Remove the condensing unit control box access
panel.
Before installing accessory read all of this installation
instruction.
3. Install the VLT6000 enclosure with the provided
screws. Mounting holes are pr e- pu n c h ed in th e top
rails to locate the enclosure near the condensing
unit control box. See Figure 7.
INSERT WIRING
HARNESS PLUG
¼ In. SAE FEMALE FITTING
WITH SCHRADER VALVE DEPRESSOR
•Perform a leak test on fittings and connections
before putting the system into operation .
MOUNT
TRANSDUCER
VERTICALLY
TEE
TO DISCHARGE
LINE PORT
MOUNT
TRANSDUCER
VERTICALLY
TO
DISCHARGE
LINE
PORT
FIGURE 3 - PRESSURE TRANSDUCER MOUNTING
FIGURE 2 - PRESSURE TRANSDUCER
Do not remove the plastic plugs from the transducers
until they are ready to be installed.
4. Attach the pressure transducers to the connection
tee (provided in accessory). The pressure transducer has a ¼ In. SAE female flare with Schrader
valve depressor for mounting to the tee.
See Figure 2.
•Hand thread the transducer to the tee.
•Tighten and secure the connection.
•Remove the Schrader valve cap from the discharge line port (provided).
•Hand thread the tee to the discharge line port.
•Tighten and secure the connection, making sure
the transducer is mounted vertically. See Figure
3.
NOTE: This procedure must be repeated for each sys-
tem.
5. Attach wiring harness assembly plug to transducer.
See Figure 4. Route sensor wires back to VLT6000
enclosure.
FIGURE 4 - WIRE HARNESS ASSEMBLY
6. Remove VLT6000 enclosure lid.
7. Pass wires through the bushing (provided), using
knock out located in the bottom of the VLT6000
enclosure.
8. Access the VLT6000 control terminal blocks. See
Figure 6.
9. Remove the terminal access cover. See Figure 5.
2Unitary Products Group
035-20209-000-A-0904
FAN MOTOR # 4
VLT6000 ENCLOSURE
FAN MOTOR # 3
FIGURE 5 - VFD66 CONTROL TERMINAL BLOCKS
10. Wire transducers to the VLT6000 control.
See Figure 6.
OUTPUT
POWER
(MOTOR)
TERMINAL
BLOCK
CONTROL
TERMINAL
BLOCK
INPUT
POWER
(MAINS)
TERMINAL
BLOCK
FIGURE 6 - P399 PRESSURE TRANSDUCER
WIRING
•Route power wires, motor leads, and transducer
signal wires through separate knockouts. See
Figure 6.
•Connect White Wire from T ransducer to Terminal
(53) on the VLT6000.
•Connect Black Wire from Transducer to Terminal
(55).
•Connect Red Wire from Transducer to Terminal
(50).
•Connect Bare (shield) Wire from Transducer to
Grounding Terminal.
FAN MOTOR # 2
FAN MOTOR # 1
VLT6000 ENCLOSURE
FIGURE 7 - FAN MOTOR #1 LOCATION
NOTE: All Wiring must comply with prevailing Local
and National wiring codes and ordinances.
11. Cut two lengths of flexible conduit (Field Supplied)
to connect from the VLT6000 Control to the condensing unit control box.
•Conduit #1 should run from the bottom of the
VLT6000 enclosure to the condensing unit control box, using knock outs provided.
•In conduit #1 insert three # 14 Gage wires
marked on both ends (field supplied).
•Conduit #2 should run from the bottom of the
VLT6000 enclosure to the condensing unit control box, using knock outs provided.
•In conduit #2 insert shielded power cable supplied in accessory.
•Allow additional conduit length to remove the
VL T Control enclosure from the top rail and place
on side for servicing.
12. Wire condenser fan motor #1 to the VLT6000 control. See Figure 6, and the SWD in Figure 9. The
VLT6000 must be wired to operate fan motor #1.
Factory installed pressure switches control fan
motor #2.
•Disconnect wire 136/BLK from terminal (T1) on
contactor (M5).
•Disconnect wire 137/BRN from terminal (T2) on
contactor (M5).
Unitary Products Group3