Unitary products group G8C 50, L8C 50 Installation Instructions Manual

INSTALLATION
INSTRUCTIONS
MODELS: G8C 50 THRU 125 INPUT
ALL POSITION AUTOMATIC
IGNITION FURNACES
Supersedes: Nothing 650.66-N2V (9/98)
035-15815-401
& L8C 50 THRU 125 INPUT
GENERAL INFORMATION ......................................1
FURNACE SPECIFICATIONS.................................2
PRE-INSTALLATION INSPECTION........................3
CODE COMPLIANCE ..............................................3
INSTALLATION POSITION......................................3
CONVERSION INFORMATION...............................3
TO CONVERT FROM DOWNFLOW TO UPFLOW
CONFIGURATION ................................................... 4
TO CONVERT FROM UPFLOW TO DOWNFLOW
CONFIGURATION ................................................... 5
FURNACE LOCATION.............................................5
COMBUSTION AND VENTILATION AIR.................6
FURNACE SIZING AND DUCT SYSTEM DESIGN.8
RETURN AIR AND FILTERS ...................................8
GAS PIPING...........................................................10
VENTING (CATEGORY I)......................................12
SIDEWALL VENTING ............................................15
ELECTRICAL WIRING...........................................15
WIRING DIGRAM...................................................17
PRE-OPERATIONAL CHECKS.............................18
SEQUENCE OF OPERATION...............................18
FURNACE OPERATION........................................18
INSTALLATION CHECKS......................................19
SERVICE INSTRUCTIONS....................................21
REPLACEMENT PARTS........................................21
GENERAL INFORMATION
These instructions are for the use of qualified individual specially trained and experienced in installation of this type equipment and related system components.
Installation and service personnel are required by some states to be licensed. Persons not
qualified shall not install this equipment nor interpret these instructions
NOTE: The words "shall" or "must" indicate a
requirement which is essential to satisfactory and safe performance.
The words "should" or "may" indicate a recommendation or advice which is not essential and not requ ired but which m ay be useful or helpful.
NOTE: After installing the furnace, show the user
how to turn off the electric al power and gas supply to the furnace. Make sure that the user understands the importance of following all safet y rules.
FURNACE SPECIFICATIONS
BTUH
INPUT
50,000 17-1/2 10 x 8 30-60 1200 160 1/3 3” 2802-5521 75,000 17-1/2 10 x 8 35-65 1200 165 1/3 4” 2802-5521
75,000 21 10 x 10 30-60 1600 160 1/2 4” 2804-5521 100,000 21 10 x 10 40-70 1600 170 1/2 4” 2804-5521 100,000 24-1/2 (2) 10 x 6 35-65 2000 165 3/4 4” 2805-5521 125,000 24-1/2 (2) 10 x 6 40-70 2000 170 3/4 5” 2805-5521
* All models are supplied with 3” vent connec tions. An installer supplied trans ition to 4” or 5” diameter m ust be used where necessary.
FURNACE
WIDTH
A
BLOWER
WHEEL
SIZE
TEMP.
RISE
°
F
CFM
HIGH @
0.5” W.C.
MAX
OUTLET
TEMP. °F
MOTORHPVENT
DIA.
DOWNFLOW
SUB-BASE
ABCDEFGHJ
17-1/2
21
24-1/2
FIGURE 1 – FURNACE DIMENSIONS AND SPECIFICATION
2
16-1/2
20
23-1/2
20-3/8 20-3/8 20-3/8
20 20 20
16
19-1/2
23
14-1/2
18
21-1/2
18-5/8 18-5/8 18-5/8
15-1/8 18-5/8 22-1/8
19 19 19
PRE-INSTALLATION INSPECTION
Inspect the shipping container and furnace for any evidence of shipping damage.
If furnace damage is found, notify frei ght carrier and file claim.
NOTE: Some models are equipped with a shipping
strap on the blower motor shaft which supports the blower motor during shipping. This strap must be removed before the furnace is operated f or the first time. It can be removed by removing the two fastening screws.
CODE COMPLIANCE
The furnaces described in these instructions are design certified b y the American Gas Ass ociation to be in compliance with the latest edition of American National Standard Z21.47. In Canada, these furnaces are design certified by the Canadian Gas Association to be in compliance with the latest edition of CAN/CGA 2.3.
These furnaces are forced air type and may be utilized for indoor installation in manufactured buildings (modular only), or buildings constructed on site. These furnaces ar e not certified for ins tallation in mobile homes, trailers or recreational vehicles.
The installer must conform to all state, local and provincial building codes when installing these appliances. In the absence of state, local or provin­cial codes, these furnaces and related equipment must be installed in accordanc e with the l atest is sue of the following:
NATIONAL FUEL GAS CODE - ANSI Z223.1 NATIONAL ELECTRICAL CODE, ANSI/NFPA 70.
Applicable codes ta ke precedence over any rec om­mendation made in these instructions.
In Canada, the installer must conform to the CAN/CGA-B149 Installation Codes, the Canadian Electrical Code, Part I, CSA C22.1, local plumbing or waste water codes, and other applicable local codes.
INSTALLATION POSITION
This furnace may be insta lle d in a n upflow, downflow or horizontal position. Depending on the configura­tion shipped from the fac tory, it may be necessary to convert the furnace fr om downflow t o upflow or fr om upflow to downflow configuration. Use conversion instructions starting on Page 3.
CONVERSION INFORMATION
This furnace may be shipp ed in either the upflo w or the downflow configuration. To convert from upflow to downflow or vice-versa it is necessary only to exchange the top and bottom casing caps and to rotate the vent blow er 180 degrees. Us e the s tep by step instructions on next page.
3
FIGURE 2 – UPFLOW/HORIZONTAL FIGURE 3 – DOWNFLOW/HORIZONTAL
CONFIGURATION CONFIGURATION
TO CONVERT FROM DOWNFLOW TO UPFLOW CONFIGURATION
1. Lay the furnace on its back.
2. Remove the front door.
3. Remove the seven she et metal screws that are used to fasten the top cap to the casing. Re­move the top cap and save the screws.
4. Remove the four sheet metal screws that are used to fasten the bottom cap to the casing. Remove the bottom cap and save the screws.
5. Unplug the vent blower wires.
6. Disconnect the pressure hose from the vent blower.
7. Remove the four machine scre ws that f asten t he vent blower to the vent pan and save the screws. Leave the gasket in place on the pan.
8. Remove the two extra machine screws in the vent pan front and save the screws.
9. Rotate the vent blower and transition 180° so
that its outlet points t o the outlet air end of the furnaces as shown in Figure 2.
4
10. Line up the v ent blower m ounting holes with th e holes in the vent pan and screw it into place. Use the same machine screws that held the vent blower in place previously.
11. Install the t wo extra machine screws in the two open holes in the fr ont of the vent pan ( See Fig­ure 2).
12. Plug in the vent motor wires.
13. Plug the pressure hose into the vent blower.
14. Remove the rectangular knockout in the center of the top cap (See Figure 5.)
15. Install the top cap at the same end of the furnace as the vent blower, using the sheet metal screws saved earlier (See Figure 2).
16. Install the bottom cap on the bottom of the furnace using the sheet metal screws saved earlier (See Figure 2).
17. The conversion is now complete. The furnace may now be installed in the upflow positio n or in the horizontal position on either side.
TO CONVERT FROM UPFLOW TO DOWNFLOW CONFIGURATION
1. Lay the furnace on its back.
2. Remove the front door.
3. Remove the seven she et metal screws that are used to fasten the top cap to the casing.
4. Remove the four sheet metal screws that are used to fasten the bottom cap to the casing. Remove the bottom cap and save the screws.
5. Unplug the vent blower wires.
6. Disconnect the pressure hose from the vent blower.
7. Remove the four machine scre ws that f asten t he vent blower to the vent pan and save the screws. Leave the gasket in place on the vent pan.
8. Remove the two extra machine screws in the vent pan front and save the screws.
9. Install the cast aluminum transition on the vent blower, using the three screws supplied on the vent blower (See Figure 4).
13. Plug in the vent motor wires.
14. Plug the pressure hose into the vent blower.
15. Remove the r ound knockout at the right side of the top cap (See Figure 5).
FIGURE 5 – TOP CAP
16. Install the to p cap at t he oppos ite end of furnac e from the vent blower, using the seven sheet metal screws saved earlier (See Figure 3).
17. Install the bottom cap on the bottom of the furnace using the sheet metal screws saved earlier (See Figure 3).
18. The conversion is now complete. The furnace may now be installed in the downflow posit ion or in the horizontal position on either side
FIGURE 4 – VENT BLOWER
10. Rotate the vent blower 180º so that its outlet
points toward the inlet air end of the furnace (See Figure 3).
11. Line up the v ent blower m ounting holes with th e holes in the vent pan and screw it into place. Use the same machine screws that held the vent blower in place previously.
12. Install the t wo extra machine screws in the two open holes in the fr ont of the vent pan ( See Fig­ure 3).
FURNACE LOCATION
This furnace is design certified for installati on as an upflow, downflow furnace or horizontal furnace on either side in an alcove, closet, basement, attic, garage or utilit y room. It is certifie d only for use i n a home constructed on-site or a manufactured home completed at the fin al site. This furnace is not des i gn certified to be installed out doors, in a mobile hom e, trailer or recreational vehicle.
The furnace should be located as close to the chimney or vent as possible and as close to the center of the warm air distribution system as possible.
When the furnace is installed in a residentia l garage it must be located and installed such that it will be protected from damage by vehicles. The furnace must be installed s o that the burners are a m inim um of 18" above the floor.
Clearances to Combustible Materials
Proper clearances f rom the furnace to any c ombus­tible materials must be maintained. These required minimum clearances are shown below and on a label in the furnace.
5
Minimum Clearances – Upflow
Front: ........................................ 2 inches
Back:.......................................... 0 inches
Sides:......................................... 0 inches
Top............................................. 1 inch
B-1 Vent:.................................... 1 inch
Single-wall Vent:........................ 6 inches
Floor........................................... com bus tible
Minimum Clearances – Downflow
Front: ......................................... 2 inches
Back:.......................................... 0 inches
Sides:......................................... 0 inches
Top............................................. 1 inch
B-1 Vent:.................................... 1 inch
Single-wall Vent:........................ 6 inches
Floor........................................... non-c ombustible
For installation on combustible flooring only when installed on the s pecial downflow sub-bas e listed in the Specifications Table on page 2.
Minimum Clearances – Horizontal
Front: ......................................... 2 inches
Back:.......................................... 0 inches
Ends:.......................................... 1 inch
Top............................................. 1 inch
B-1 Vent:.................................... 1 inch
Single-wall Vent:........................ 6 inches
Floor........................................... com bus tible
When the furnace is installed in the horizontal position, line contact is permissible. T he line form ed by the intersection of the top and sides of the furnace may be in contact with combustible material.
Failure to maintain proper clearances to combustible materials can cause a fire, which could result in damage, death or per­sonal injury.
NOTE: This furnace must be installed so the
electrical components are protected from water.
Installations on Combustible Flooring
This furnace may not be installed directly on com­bustible materials in the downflow position. It may be installed directly on floors made of concrete or other­non-combustible m aterials . If it is nec ess ary to install the furnace in the do wnflow position on a c ombusti­ble floor, it is req uired that a combustible su b-base be used. The part number of the correct sub-base accessory is shown in the specification table on Page 2
COMBUSTION AND VENTILATION AIR
Provide ventilation and combustion air in accor­dance with section 5.3, Air for Combustion and Ventilation, of the NATIONAL FUEL GAS CODE, ANSI Z223.1, or applicable provisions of the local building codes. In Canad a, refer to the lat est edition of the CAN/CGA-B149 Installation Code and local codes for specifics.
Adequate ventilation and combustion air must be provided to insure s atisfactory and safe operation of the furnace. Air openings in front panel and top panel must not be ob­structed. Failure to observe this re commen­dation could result in asphyxiation.
Do not install the furnace on its back. Doing so could cause a fire, resulting in damage, injury or death.
Provide sufficient space around and in front of the furnace for service and cleaning. Allow a minimum of 24 inches from the fr ont of the fur­nace for service clear ance. If the furnace is to be installed in a close clearance closet, the door should be of adequate size to allow for removal of the furnace s hou ld it b ecome neces­sary.
6
Do not store or use halogen-emitting sub­stances in the vicinity of this appliance. Such substances include chlorine based cleaners and swimming pool chemicals, wa­ter softening chemicals, de-icing salts and chemicals, cleaning solvents such as car­bon tetrachloride or perchloroethylene, halogen type refrigerants, printing inks, paint and paint removers, varnishes, hydro­chloric acid, cements and glues, and ma­sonry acid washing materials. The air used by the burner for combustion must be free of halogens to avoid possible corrosion to the heating surfaces, which could result in asphyxiation.
This furnace is not to be used as a constr uction heater to supply heat to an unfinished building during the finishing phas es of co nstruc tion. Th is practice exposes the furnace to abnormally low return air temperatures, which can cause con­densation in the furnac e or vent leading to pre­mature failure. This practice also exposes the furnace to an abnormal ly corrosive atmosph ere from sources such as paint, var nish and adhe­sives, which can lead to premature heat ex­changer or vent failure. The prac tic e also allows foreign materials such as sawdust or shee t rock dust to enter the furnace blower, burner, heat exchanger, motors, and vent system resulting in shorter life of the fur nace. Use of th is furnace
as a construction heater will void the war­ranty.
Installations in a Confined Space
A confined space is defined as a space whose volume is less tha n 50 cubic feet per 1000 BTUH of the total input ratings of all appliances installed in the space. If the furnace is to be installed in a confined space such as a small closet or room, provisions must be made for supplying combustion and ventilation air to the space surrounding the furnace. (See Figure 6) . T his a ir must come from the outside or from some larger area in the building which meets the requirements of an unconfined space.
Two openings of equa l area must be provided; one starting within twelve inches of the ceiling and one starting within twelve inches of the floor of the confined space. The upper o pening must alwa ys be above the top of the furnace casing. The lower opening, if in the sidewall, floor or door, shall be located below the level of the burner in the furnace.
Installations in an Unconfined Space
An unconfined space is defined as a space whose volume is more than 50 c u bic f eet per 1000 BTUH of the total input ratings of all appliances installed in the space. In unconfined spaces in a building of conventional fram e, masonry, or metal construction, infiltration is normally adequate to provide air for combustion and ventilation.
In buildings of tight construction, all air must be obtained from outdoors or from spaces communi­cating freely with o utdoors. A permanent o pening or openings having a total free area of not less than one square inch for each 5000 BTUH of furnace input must be provided.
If the furnace is to be installed in a commercial building, a building with an indoor pool, a laundry room, hobby or craft room, or c hem ical s tor age area, all air must be brought in f rom outside as describ ed above.
Further details on suppl ying outdoor air for combus­tion may be obtained from Section 5.3.3 of the National Fuel Gas Code ANSI Z223.1. In Canada, refer to the latest edition of the CAN/CGA-B149 Installation Code and local codes for specifics.
When the furnace is installed in an attic or other insulated space, make sure that all in-
sulation is at least 12” away from furnace combustion air openings. Failure to do this could cause asphyxiation or fire.
If all air is from inside building, the total free area of each opening m ust be at least one square inch f or each 1,000 BTUH of f urnace input but not less than 100 square inches.
If all air is from outdoors, when communicating directly with the outdoors through v ertical ducts, the total free area of each openin g must be at least one square inch for each 4,000 BTUH of furnace input. When communicating directly with the outdoors through horizontal ducts, the total free area of each duct must be at least o ne s q uare inc h f or each 2,000 BTUH of furnace input.
When ducts are used, they must be of the same cross-sectional area as the f ree ar e a of the op eni ngs to which they connect. The minimum dimension of rectangular air ducts must not be less than three inches.
FIGURE 6 – AIR OPENINGS
7
FURNACE SIZING AND DUCT SYSTEM DESIGN
The duct system must be installed in conformance with ASHRAE/NFPA 90, Sta ndard for Installation of Warm Air Heating and Air Systems and other applicable local codes. Failure to adhere to proper duct system design standards can reduce airflow, resulting in reduced system performance and possible furnace damage.
Consideration should be given to the heating capacity require d and also to the air quantity (CFM) required if A/C is to be installed along with the furnace or at some future time. These factors can be determined by calculating the heat loss and heat gain of the home or structure.
If these calculations are not performed and the furnace is oversized, the following may result:
1. Short cycling of the furnace.
2. Wide temperature fluctuations f rom the thermo­stat setting.
3. Reduced overall operating efficiency of the furnace.
The supply and return duct system must be of adequate size and designed such that the furnace will operate within the design ed air temperature ris e range and not exceed the maximum des igned static pressure. These values are listed in the table below.
INPUT BTUH 50,000
75,000 100,000 125,000 Additional information, values and data necessary
for heat loss, heat ga in and duc t system design m a y be found in the ASHR AE HANDBOOK OF FUNDA­MENTALS or in other nationally rec ognized public a­tions recognized by municipal, state, provincial and federal code authorities.
If possible, it is recommended that the supply air duct attached to the furnace be provided with a removable access panel. The opening should be accessible when the furnace is installed in service and should be large enough that smoke or ref lected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover panel for this opening should be attached in such a manner as to prevent leaks.
A/C Usage Duct Systems
1. When a single (common) duct system is used, one of the following methods shall be used: a. A plenum type cooling c oil must be i nstalled
on the air discharge side, or
EXT. STATIC IN. W.C.
MINIMUM MAXIMUM
.10 .12 .15 .20
.50 .50 .50 .50
b. A blower-coil type cooling coil must be in-
stalled in parallel with and isolate d from the furnace, or
c. A self-contained A/C unit m ust be in par allel
with and isolated from the furnace.
Dampers must be installed when coil-blower or self-contained unit is employed to pre­vent conditioned cool air from coming in contact with the heat exchanger to avoid moisture condensation and rust-out. This can allow products of combustion to be cir­culated into the living area by the furnace blower resulting in possible asphyxiation. If dampers are of a manually operated type, a means must be provided to prevent either the furnace or A/C unit from operating un­less dampers are in full heat or cool posi­tion.
If two duct systems are used as could be the case with a coil-blower or a self-contained A/C unit, the furnace and A/C unit should be controlled by a single combination heating and cooling thermostat which will prevent the furnace and A/C unit from operating simultaneously.
If a separate heating and separate cooling thermostat is used, a manually operated electrical interlock switch must be installed to prevent simultaneous operation of both systems and to avoid a possible hazardous condition due to overheating of the condi­tioned space.
RETURN AIR AND FILTERS
Return Air Temperature
This furnace design is to be operated in normal household temperatures. The continuous return air
temperature must not be below 60°F or above 85°F.
Return Air Connection – Upflow
The return air ma y be brought in thr ough the bot tom of the furnace or through one or both sides of the furnace casing. The f urnace casing may be c ut out so that side return air connections may be used. T he furnace is supplied with flanges on the top of the furnace to which the return air duct may be fastened. The casing top is embossed to indicate where to bend the flanges. If a side return is to be used, cut out the side of the casing 14 " high by 16 1/4" wide using the lances in the casing side as a guide. DO
NOT CUT THE OPENING LARGER THAN 14"x 16 1/4". It is not perm issible to cut out the back of the
furnace.
8
Loading...
+ 16 hidden pages