Unitary products group G8C Installation Instructions Manual

INSTALLATION
80% OUTDOOR
AUTOMATIC
INSTRUCTIONS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
BLOWER PERFORMANCE FOR SMALL CHASSIS
OUTDOOR FURNACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
BLOWER PERFORMANCE FOR LARGE CHASSIS
OUTDOOR FURNACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PRE-INSTALLATION INSPECTION . . . . . . . . . . . . . . . . . . . . . . . 3
CODE COMPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FURNACE LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CLEARANCE TO COMBUSTIBLE MATERIALS . . . . . . . . . . . 4
OUTSIDE SLAB INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . 4
COMBUSTION AND VENTILATION AIR . . . . . . . . . . . . . . . . . . . 4
INSTALLATION OF EXHAUST AND INTAKE-AIR HOOD
ASSEMBLIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FURNACE SIZING AND DUCT SYSTEM DESIGN . . . . . . . . . . . 5
A/C USAGE DUCT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RETURN AIR, FILTERS, AND DUCT CONNECTIONS . . . . . . . . 6
RETURN AIR TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . 6
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SERVICE WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL GROUNDING . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
HEAT ANTICIPATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
BLOWER MOTOR SPEED SELECTION . . . . . . . . . . . . . . . . . 9
MOTOR TERMINAL IDENTIFICATION . . . . . . . . . . . . . . . . . 10
BLOWER TIMINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PRE-OPERATIONAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . 12
SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FURNACE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . 13
GAS SHUTOFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
INSTALLATION CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CHECKING GAS INPUT RATE . . . . . . . . . . . . . . . . . . . . . . . 13
HIGH ALTITUDE ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . 13
HOW TO DETERMINE GAS INPUT RATE . . . . . . . . . . . . . . . . 14
CONVERSION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . 14
MINOR INPUT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . 14
MEASURING AIR TEMPERATURE RISE . . . . . . . . . . . . . . . 14
BLOWER REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
IGNITION FURNACES
MODELS: G8C
50 THUR 125 MBH OUTPUT
EFFICI ENCY RATING CERTIFIED
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
035-15881-402 REV. A (1199) 650.67-N2V
650.67-N2V 035-15881-402 REV. A (1199)
GENERAL INFORMATION
NOTE:
The words "shall" or "must" indicate a requirement
which is essential to satisfactory and safe perfor-
IMPORTANT -
These instructions are for the use of qualified individuals specially trained and experienced in installation of this type equipment and related system compo-
nents.
Installation and service personnel are required by some states to be licensed.
Persons not qualified shall not install this equipment nor inter­pret these instructions.
NOTE:
mance.
The words "should" or "may" indicate a recommen­dation or advice which is not essential and not required but which may be useful or helpful.
After installing the furnace, show the user how to turn off the electrical power and gas supply to the furnace. Make sure that the user understands the importance of following all safety rules.
SPECIFICATIONS
*CHASSIS SIZE
BTUH INPUT
Small Large
X 50,000 10” x 7” 30-60 1400 160 1/2
X 75,000 10” x 7” 35-65 1400 165 1/2
X 100,000 10” x 7” 45-75 1400 175 1/2
X 75,000 12” x 12” 30-60 2070 160 3/4
X 100,000 12” x 12” 35-65 2070 165 3/4
X 125,000 12” x 12” 40-70 2070 170 3/4
BLOWER
WHEEL SIZE
TEMPERATURE
RISE ºF
CFM HIGH @
0.5” W.C.
MAX. OUTLET
TEMPERATURE ºF
MOTOR HP
*BLOWER PERFORMANCE FOR SMALL CHASSIS OUTDOOR FURNACES
FACTORY EQUIPPED STANDARD BLOWERS
STANDARD CFM AT EXTERNAL STATIC PRESSURE
Blower Speed .1 .2 .3 .4 .5 .6 .7 .8
HIGH 1612 1560 1508 1453 1400 1330 1261 1186
MEDIUM 1303 1281 1258 1226 1195 1147 1100 1035
LOW 788 786 785 774 763 738 712 668
*BLOWER PERFORMANCE FOR LARGE CHASSIS OUTDOOR FURNACES
FACTORY EQUIPPED STANDARD BLOWERS
STANDARD CFM AT EXTERNAL STATIC PRESSURE
Blower Speed .1 .2 .3 .4 .5 .6 .7 .8
HIGH 2300 2250 2210 2140 2070 2030 1945 1775
MEDIUM HIGH 1660 1645 1620 1605 1585 1515 1480 1360
MEDIUM LOW 1440 1420 1385 1375 1360 1305 1280 1210
LOW 1265 1250 1240 1235 1200 1190 1135 1050
* See Figure 1 to determine chassis size.
2 Unitary Products Group
035-15881-402 REV. A (1199) 650.67-N2V
PRE-INSTALLATION INSPECTION
Inspect the shipping container and furnace for any evidence of shipping damage. If furnace damage is found, notify freight carrier and file claim.
SIDE
B
SIDE
BACK
C
W
L
CODE COMPLIANCE
The furnace described in these instructions is Design Certi­fied by the American Gas Association to be in compliance with the latest edition of American National Standard Z21.47. In Canada, these furnaces are Design Certified by the Cana­dian Gas Association to be in compliance with the latest edi­tion of CAN/CGA2.3. (See Figure 1.)
CHASSIS SIZE
H
A
D
LETTER
A
B
C
D
H
W
L
SMALL
18”
12”
18”
25-5/8”
27-3/16”
23-3/8”
45-3/32”
LARGE
22”
14”
24”
29-7/16”
31”
25”
48”
FIGURE 1 :
FURNACE DIMENSIONS
These furnaces are of the forced air type and are to be installed out of doors only. They are acceptable for either buildings constructed on site, modular, or manufactured (mobile) homes by following the proper codes.
For site-built homes:
This furnace must be installed in accordance with these instructions, and local or state code. In the absence of local codes, follow the latest edition of the standard NATIONAL FUEL GAS CODE - ANSI Z223.1, AND NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 and/or CAN/CGA B149 INSTALLATION CODES when in Canada.
For manufactured (mobile) homes:
This furnace must be installed in accordance with these instructions, and the MAN­UFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24CFR, PART 3280 or, when such stan­dard is not applicable, the STANDARD FOR MANUFAC­TURED HOME INSTALLATION (Manufactured Home Sites, Communities, and Set-Ups), ANSIA225.1, or the CAN/CSA­Z240 MH, Series M86 Canadian Standard for Mobile Homes.
It is important to consult your local code authorities before installation is made. The manufacturer assumes no responsi­bility for equipment installed in violation of any code or regu­lation.
FURNACE LOCATION
This furnace is Design Certified for outdoor installation only, and can be mounted on a slab or roof top. They are suitable for manufactured (mobile) homes when used with a slab only. They are not to be installed within any part of a structure such as an attic, crawl space, closet, etc.
The unit may be installed directly on wood flooring or on class A, B, or C roof covering materials.
DO NOT make any flue or chimney connections to this unit other than the factory provided exhaust and air inlet hood assemblies. DO NOT vent the flue outlet underneath any structure. The flue out­let must not discharge less than two feet away from any window or door, and must also not dis­charge less than three feet from any motor-driven air intake discharging into habitable areas. The flue outlet and combustion air inlet must not be blocked or closed for any reason.
Unitary Products Group 3
650.67-N2V 035-15881-402 REV. A (1199)
CLEARANCE TO COMBUSTIBLE MATERIALS
Proper clearances from the furnace to any combustible mate­rials must be maintained. These required minimum clear­ances are shown below and on a label in the furnace.
Minimum Clearances:
Duct Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 inches
Back: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 inches
Sides: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 inches
Top: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 inches
Bottom. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 inches
In Canada, it is recommended that the outlet duct be pro­vided with a removable access panel. This opening shall be accessible when the furnace is installed in service, and shall allow the observance of smoke or reflected light inside the casing to indicate the presence of leaks in the heat exchanger. The removable access panel when installed, shall provide an adequate seal.
OUTSIDE SLAB INSTALLATION
1. Select a location where water drainage cannot collect around the unit.
2. Provide a level slab extending at least 1" beyond all four sides of the furnace, and air conditioner (if provided as a system). The slab should be at least 3-5" thick and should be isolated from the foundation wall.
3. The location of the unit should be such as to provide proper access for inspection, servicing and clearance from combustibles.
Provide sufficient space around and in front of the furnace for service and cleaning. Allow a minimum of 36 inches from the sides of the furnace for service clearance.
Adequate ventilation and combustion air must be provided to insure satisfactory and safe operation of the furnace. DO NOT make any flue or chimney connections to this unit other than the factory pro­vided exhaust and air inlet hood assemblies. DO NOT vent the flue outlet underneath any structure. The flue outlet and combustion air inlet must not be blocked or closed for any reason. Failure to observe the recommendation could result in asphyxiation.
DO NOT store or use halogen emitting substances in the vicinity of this appliance. Such substances include chlorine based cleaners and swimming pool chemicals, water softening chemicals, de­icing salts and chemicals, cleaning solvents such as carbon tetrachloride or perchloroethylene, halo­gen type refrigerants, printing inks, paint and paint removers, varnishes, hydrochloric acid, cements and glues, and masonry acid washing materials. the air used by the burner for combustion must be free of halogens to avoid possible corrosion to the heating surfaces which could result in asphyxiation.
IMPORTANT -
struction heater to supply heat to an unfinished building dur­ing the finishing phases of construction. This practice exposes the furnace to abnormally low return air tempera­tures which can cause condensation in the furnace or vent leading to premature failure. This practice also exposes the furnace to an abnormally corrosive atmosphere from sources such as paint, varnish and adhesives, which can lead to pre­mature heat exchanger or vent failure.
This furnace is not to be used as a con-
Failure to maintain proper clearances to combusti­ble materials can cause a fire, which could result in damage, death or personal injury.
COMBUSTION AND VENTILATION AIR
INSTALLATION OF EXHAUST AND INTAKE-AIR HOOD ASSEMBLIES
1. Remove the paper wrapped exhaust hood and intake air hood from the heat exchanger compartment. Also locate the envelope containing eleven #10 sheet metal screws needed for the installation. (See Figure 2.)
2. Use four of the screws to attach the exhaust hood assembly to the cabinet, and the remaining seven to attach the intake air hood. (See Figure 2.)
4 Unitary Products Group
The practice also allows foreign materials such as sawdust or sheetrock dust to enter the furnace blower, burner, heat exchanger, motors, and vent system resulting in shorter life of the furnace. Use of this furnace as a construction heater will void the warranty.
035-15881-402 REV. A (1199) 650.67-N2V
EXHAUST HOOD ASSEMBLY
#10 x 3/8 SCREW x4
#10 x 3/8 SCREW x7
INTAKE AIR HOOD
FIGURE 2 :
EXTERNAL VIEW OF FURNACE WITH VENT HOOD ASSEMBLY
FURNACE SIZING AND DUCT SYSTEM DESIGN
The duct system must be installed in conformance with ASHRAE/NFPA 90, Standard for Installation of Warm Air Heating and Air Systems and other applicable local codes. Failure to adhere to proper duct system design standards can reduce airflow, resulting in reduced system performance and possible furnace damage.
Consideration should be given to the heating capacity required and also the air quantity (CFM) required if A/C is to be installed along with the furnace or at some future time. These factors can be determined by calculating the heat loss and heat gain of the home or structure.
If these calculations are not performed and the furnace is oversized, the following may result:
1. Short cycling of the furnace.
2. Wide temperature fluctuations from the thermostat set­ting.
3. Reduced overall operating efficiency of the furnace.
The supply and return duct system must be of adequate size and designed such that the furnace will operate within the designed air temperature rise range and not exceed the max­imum designed static pressure. These values are listed in Table 1:
Tab l e 1 :
STATIC PRESSURE
INPUT
BTUH
50,000 .10 .50
75,000 3.12 .50
100,000 .15 .50
125,000 .20 .50
EXT. STATIC W.C.
MINIMUM MAXIMUM
The return air system must be designed and installed so that negative pressure created by the air circulating fan cannot affect another appli­ance’s combustion air supply (such as a water heater), or act to mix products of combustion with circulating air.
Additional information, values and data necessary for heat loss, heat gain and duct system design may be found in ASHRAE HANDBOOK OF FUNDAMENTALS-1993 EDITION or in other nationally recognized publications recognized by municipal, state, provincial and federal code authorities.
Unitary Products Group 5
Loading...
+ 11 hidden pages