SPLIT-SYSTEM HEAT PUMPS
INDOOR UNITS
MODELS: FEH180 & 240 ONLY
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words:
NOTE, CAUTION,andWARNING.Notes
clarify or make the installation easier. Cautions
to prevent equipment damage. Warnings
alert installer that personal injury and/or equipment damage may result if installation procedure is not handled
properly.
Every unit includes a well-insulated cabinet, copper
tube/aluminumfincoilwithinterlacedcircuiting
arrangement, 1" throwaway filters, centrifugal blower
with a fixed pitch sheave, and a blower motor with variable pitch sheave. (FEH240 doesn’t ship with Motor &
Drive - field installation required).
They also include 2 filter driers, 2 expansion valves
and distributors that are only used during the cooling
cycle plus a check valve to provide the proper flow of
refrigerant through the unit during both the cooling and
heating cycles...
Improper installation may create a condition
where the operation of the product could
cause personal injury or property damage.
The controls include 208/230/460 volt transformer,
blower motor contactor and relay, and a low voltage
terminal block.
The units are shipped in the vertical position ready for
field installation. For horizontal installation, the blower
module can be repositioned in the field as shown on
Page 8 for maximum flexibility.
All forms referenced in this instruction may be ordered
from:
Standard Register
2101 West Tecumseh Road
Norman, Oklahoma 73069
Toll Free Fax (877) 379-7920
This instruction covers the installation of the indoor
unit. For information on the installation and operation
of the matching outdoor unit, refer to PN 035-16192-
001.
Installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. Notes are intended
to clarify or make the installation easier. Cautions are
given to prevent equipment damage.Warnings are
given to alert the installer that personal injury and/or
equipment damage may result if the installation proce-
dure is not handled properly.
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and
national codes including but not limited to,
building, electrical and mechanical codes.
INSPECTION
RENEWAL PARTS
Refer to the Source One Parts Manual for a complete
listing of replacement parts on this equipment.
F1
P R O D U C T C A T E G O R Y
F = S p l i t - S y s t e m H e a t P u m p
I n d o o r U n i t
P R O D U C T G E N E R A T I O N
1 = 1 s t G e n e r a t i o n
P R O D U C T I D E N T I F I E R
E H = I n d o o r U n i t
FIGURE 1 - PRODUCT NOMENCLATURE
E
H
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident,
the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by
the carrier’s agent should be made in writing.
1
8 0A3
N O M I N A L C O O L I N G
C A P A C I T Y
1 8 0 = 1 5 T o n
2 4 0 = 2 0 T o n
3
V O L T A G E C O D E
3 3 = 2 0 8 / 2 3 0 / 4 6 0 - 3 - 6 0
F A C T O R Y I N S T A L L E D H E A T
A = N o t A p p l i c a b l e
Unitary Products Group3
035-16626-000-E-0103
INSTALLATION
LIMITATIONS
Theses units must be installed in accordance with all
national and local safety codes.If no local codes
apply, installation must conform with the appropriate
national code.Units are designed to meet National
Safety Code Standards.If components are to be
added to a unit to meet local codes, they are to be
installed at the dealer’s and/or the customer’s expense.
See Table 2 for application data.
RIGGING
Be careful when moving the unit. Do not remove any
packaging until the unit is near its final location.
The packaging consists of a bottom wooden skid that
can be lifted with a fork truck from any direction, a plastic bag that covers the entire unit, and strapping that
secures the plastic bag to the bottom skid.
These units can be rigged with slings under the bottom
skid.
LOCATION
These indoor units are not designed for outdoor installation. They must be located within the building structure, either inside or outside the conditioned space.
The units should be located as close to the outdoor
units as practical and positioned to minimize bends in
the refrigerant piping.
Units being installed vertically or horizontally can be set
directly on a floor or platform, or they can be supported
by metal or wooden beams.
Be careful when attaching the hanger rods.
Use a washer with a back-up nut on each rod
and tighten down against the cabinet so they
will not be allowed to turn or slip.
Units being installed horizontally can be suspended
from above. Units being installed horizontally can be
suspended from above by using a field installed Horizontal Suspension Kit PN# 1HH0451. Refer to Figures
2 and 3 for their location and the individual load on
each hanger rod.
Spreader bars should be used to prevent
slings from crushing the unit panels and
frame.
Before rigging any unit, determine its weight from Table
1.
CLEARANCES
The clearances listed on unit dimensions drawing
(Pages 18 and 19) are required for the proper service
and operation of the unit.
4UnitaryProductsGroup
035-16626-000-E-0103
TABLE 1: PHYSICAL DATA
DESCRIPTION
Rows Deep X Rows High3X323X32
Finned Length - inches54.583
Coil
Face Area - square feet12.1118.44
Tube (Copper) OD - inches3/83/8
Fins (Aluminum) per inch1313
Centrifugal Blower (Forward Curve) - QtyDiameter X Width - inches18 X 18 - 115 X 12 - 2
Blower Motor
1
HP3---
RPM1750---
Quantity per unit68
Filters (Throwaway)
Size (in)20 X 20 X 120 X 22 X 1
Total Face Area - square feet16.724.1
Unit Weight (lbs)
Motor & Drive
Shipping425830
Operating435720
3HP---90
5HP---120
10 KW63---
20 KW66126
Accessory Operating Weight (Lbs.)
Electric Heat
30 KW71129
40 KW---132
50 KW80137
Supply Air Plenum114150
Return Air Grille2015
Base100120
1.
Refer to “Blower Motor and Drive Data” table for more information.
UNIT MODEL
FEH180FEH240
TABLE 2: UNIT APPLICATION DATA
APPLICATION
LIMITATIONS
Voltage Variation (208/230-3-60)
Voltage Variation (460-3-60)
1
1
Ambient Air on Outdoor Coil (Cooling Cycle) - °F45115
Ambient Air on Indoor Coil (Cooling Cycle) - °F6886
Ambient Air on Outdoor Coil (Heating Cycle) - °F
Ambient Air on Indoor Coil (Heating Cycle) - °F6080
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Below 0ºF the control circuit will lock out the compressor and allow the electric heat accessory to cycle at its stand by capacity.
MIN.MAX.
187253
414506
2
0
70
Unitary Products Group5
SUSPENSION
)
CHANNEL
035-16626-000-E-0103
HANGER RODS
(FIELD SUPPLIED)
C
55"
5"
A
3
1-1/2
SECTION
BLOWER
SECTION
COIL
B
ELECTRIC HEATER
ACCESSORY (40 Lb.)
58-11/16"
D
D
SUPPLY AIR PLENUM
ACCESSORY (100 Lb.
FIGURE 2 - UNIT SUSPENSION MOUNTING FEH180 (Horizontal Applications)
(See Table 3 for Suspension Weights).
TABLE 3: FEH180 UNIT SUSPENSION WEIGHTS (LBS)
SUSP'N. POINTW/ 3 HP MOTORW/ HEATER ACCESSW/ PLENUM ACCESS