Unitary products group FEH180, FEH240 Installation Manual

INSTALLATION MANUAL
CONTENTS
GENERAL ....................................3
RENEWALPARTS .............................3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSTALLATION................................4
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
See the following page for a complete Table of Contents.
SPLIT-SYSTEM HEAT PUMPS
INDOOR UNITS
MODELS: FEH180 & 240 ONLY
NOTES, CAUTIONS AND WARNINGS
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
are intended to
are given
are given to
035-16626-000-E-0103
TABLE OF CONTENTS
035-16626-000-D-0502
GENERAL ......................................3
RENEWALPARTS ...............................3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION..................................4
LIMITATIONS...............................4
RIGGING ..................................4
LOCATION .................................4
CLEARANCES ..............................4
VERTICAL/HORIZONTALINSTALLATION ........8
DUCT CONNECTIONS ......................10
REFRIGERANTMAINS ......................11
INSTALLINGREFRIGERANTMAINS ...........11
DRAINCONNECTION .......................11
SUPPLYAIRBLOWERADJUSTMENT..........12
POWERANDCONTROLWIRING..............14
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INDOORCOIL .............................17
FILTERS..................................17
DRAINPAN ...............................17
LUBRICATION .............................17
BELTS ...................................17
LIST OF FIGURES
Fig.#
9 BASE ACCESSORY FEH240 . . . . . . . . . . . . . . . . . . 10
10 SUPPLYAIRPLENUMFEH180................10
11 SUPPLY AIR PLENUM KNOCKOUTS FEH180 . . . . 10
12 SUPPLYAIRPLENUMFEH240 ................10
13 RECOMMENDEDDRAINPIPING...............12
14 TYPICAL MOTOR MOUNTING ASSEMBLY . . . . . . . 13
15 HOLE LOCATIONS FOR PRESSURE DROP
READINGS.................................13
16 CFMVSPRESSUREDROP ...................13
17 UNITDIMENSIONSFEH180 ...................18
18 UNITDIMENSIONSFEH240 ...................19
Pg.#
LIST OF TABLES
Tbl.# Pg.#
1 PHYSICALDATA .............................5
2 UNIT APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . 5
3 FEH180 UNIT SUSPENSION WEIGHTS (LBS) . . . . . . 6
4 FEH240 UNIT SUSPENSION WEIGHTS (LBS) . . . . . . 7
5 ELECTRIC HEATER DIMENSIONS FEH180 & 240 . . 9
Fig.# Pg.#
1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . 3
2 UNIT SUSPENSION MOUNTING FEH180
(HORIZONTAL APPLICATIONS) . . . . . . . . . . . . . . . . . 6
3 UNIT SUSPENSION MOUNTING FEH240
(HORIZONTAL APPLICATIONS) . . . . . . . . . . . . . . . . . 7
4 VERTICAL AND HORIZONTAL APPLICATIONS . . . . 8
5 ELECTRIC HEAT ACCESSORY . . . . . . . . . . . . . . . . . 9
6 RETURNAIRGRILLEFEH180 ..................9
7 RETURNAIRGRILLEFEH240 ..................9
8 BASE ACCESSORY FEH180 . . . . . . . . . . . . . . . . . . . 10
6 SUPPLY AIR BLOWER MOTOR PULLEY
ADJUSTMENT ..............................12
7 SUPPLY AIR PREFORMANCE FEH180 . . . . . . . . . . 14
8 SUPPLY AIR PERFORMANCE FEH240 . . . . . . . . . . 14
9 ELECTRICAL RATINGS INDOOR UNIT - HEAT PUMP
ONLY .....................................15
10 ELECTRICAL RATINGS INDOOR UNIT - HEAT PUMP
WITHELECTRICHEAT .......................16
11 TYPICALFIELDWIRING ......................17
12 FEH180/240 MINIMUM CLEARANCES . . . . . . . . . . . 18
2 UnitaryProductsGroup
035-16626-000-E-0103
GENERAL
Every unit includes a well-insulated cabinet, copper tube/aluminum fin coil with interlaced circuiting arrangement, 1" throwaway filters, centrifugal blower with a fixed pitch sheave, and a blower motor with vari­able pitch sheave. (FEH240 doesn’t ship with Motor & Drive - field installation required).
They also include 2 filter driers, 2 expansion valves and distributors that are only used during the cooling cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and
heating cycles...
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
The controls include 208/230/460 volt transformer, blower motor contactor and relay, and a low voltage terminal block.
The units are shipped in the vertical position ready for field installation. For horizontal installation, the blower module can be repositioned in the field as shown on Page 8 for maximum flexibility.
All forms referenced in this instruction may be ordered from:
Standard Register 2101 West Tecumseh Road Norman, Oklahoma 73069 Toll Free Fax (877) 379-7920
This instruction covers the installation of the indoor unit. For information on the installation and operation of the matching outdoor unit, refer to PN 035-16192-
001. Installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert the installer that personal injury and/or equipment damage may result if the installation proce-
dure is not handled properly.
This product must be installed in strict compli­ance with the enclosed installation instruc­tions and any applicable local, state, and national codes including but not limited to, building, electrical and mechanical codes.
INSPECTION
RENEWAL PARTS
Refer to the Source One Parts Manual for a complete listing of replacement parts on this equipment.
F 1
P R O D U C T C A T E G O R Y
F = S p l i t - S y s t e m H e a t P u m p I n d o o r U n i t
P R O D U C T G E N E R A T I O N
1 = 1 s t G e n e r a t i o n
P R O D U C T I D E N T I F I E R
E H = I n d o o r U n i t
FIGURE 1 - PRODUCT NOMENCLATURE
E
H
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the car­rier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.
1
8 0 A 3
N O M I N A L C O O L I N G
C A P A C I T Y
1 8 0 = 1 5 T o n 2 4 0 = 2 0 T o n
3
V O L T A G E C O D E
3 3 = 2 0 8 / 2 3 0 / 4 6 0 - 3 - 6 0
F A C T O R Y I N S T A L L E D H E A T
A = N o t A p p l i c a b l e
Unitary Products Group 3
035-16626-000-E-0103
INSTALLATION
LIMITATIONS
Theses units must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform with the appropriate national code. Units are designed to meet National Safety Code Standards. If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or the customer’s expense. See Table 2 for application data.
RIGGING
Be careful when moving the unit. Do not remove any packaging until the unit is near its final location.
The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction, a plas­tic bag that covers the entire unit, and strapping that secures the plastic bag to the bottom skid.
These units can be rigged with slings under the bottom skid.
LOCATION
These indoor units are not designed for outdoor instal­lation. They must be located within the building struc­ture, either inside or outside the conditioned space.
The units should be located as close to the outdoor units as practical and positioned to minimize bends in the refrigerant piping.
Units being installed vertically or horizontally can be set directly on a floor or platform, or they can be supported
by metal or wooden beams.
Be careful when attaching the hanger rods. Use a washer with a back-up nut on each rod and tighten down against the cabinet so they will not be allowed to turn or slip.
Units being installed horizontally can be suspended from above. Units being installed horizontally can be suspended from above by using a field installed Hori­zontal Suspension Kit PN# 1HH0451. Refer to Figures 2 and 3 for their location and the individual load on each hanger rod.
Spreader bars should be used to prevent slings from crushing the unit panels and frame.
Before rigging any unit, determine its weight from Table
1.
CLEARANCES
The clearances listed on unit dimensions drawing (Pages 18 and 19) are required for the proper service and operation of the unit.
4 UnitaryProductsGroup
035-16626-000-E-0103
TABLE 1: PHYSICAL DATA
DESCRIPTION
Rows Deep X Rows High 3X32 3X32
Finned Length - inches 54.5 83
Coil
Face Area - square feet 12.11 18.44
Tube (Copper) OD - inches 3/8 3/8
Fins (Aluminum) per inch 13 13
Centrifugal Blower (Forward Curve) - Qty Diameter X Width - inches 18 X 18 - 1 15 X 12 - 2
Blower Motor
1
HP 3 ---
RPM 1750 ---
Quantity per unit 68
Filters (Throwaway)
Size (in) 20 X 20 X 1 20 X 22 X 1
Total Face Area - square feet 16.7 24.1
Unit Weight (lbs)
Motor & Drive
Shipping 425 830
Operating 435 720
3HP --- 90
5HP --- 120 10 KW 63 --- 20 KW 66 126
Accessory Operating Weight (Lbs.)
Electric Heat
30 KW 71 129 40 KW --- 132 50 KW 80 137
Supply Air Plenum 114 150
Return Air Grille 20 15
Base 100 120
1.
Refer to “Blower Motor and Drive Data” table for more information.
UNIT MODEL
FEH180 FEH240
TABLE 2: UNIT APPLICATION DATA
APPLICATION
LIMITATIONS
Voltage Variation (208/230-3-60)
Voltage Variation (460-3-60)
1
1
Ambient Air on Outdoor Coil (Cooling Cycle) - °F 45 115
Ambient Air on Indoor Coil (Cooling Cycle) - °F 68 86
Ambient Air on Outdoor Coil (Heating Cycle) - °F
Ambient Air on Indoor Coil (Heating Cycle) - °F 60 80
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Below 0ºF the control circuit will lock out the compressor and allow the electric heat accessory to cycle at its stand by capacity.
MIN. MAX.
187 253 414 506
2
0
70
Unitary Products Group 5
SUSPENSION
)
CHANNEL
035-16626-000-E-0103
HANGER RODS
(FIELD SUPPLIED)
C
55"
5"
A
3
1-1/2
SECTION
BLOWER SECTION
COIL
B
ELECTRIC HEATER ACCESSORY (40 Lb.)
58-11/16"
D
D
SUPPLY AIR PLENUM ACCESSORY (100 Lb.
FIGURE 2 - UNIT SUSPENSION MOUNTING FEH180 (Horizontal Applications)
(See Table 3 for Suspension Weights).
TABLE 3: FEH180 UNIT SUSPENSION WEIGHTS (LBS)
SUSP'N. POINT W/ 3 HP MOTOR W/ HEATER ACCESS W/ PLENUM ACCESS
A 95 95 85 85 B 120 120 100 100 C 95 115 165 185 D 115 140 185 205
Total Wt. 425 470 535 575
W/ HEATER & PLENUM
ACCESS
6 UnitaryProductsGroup