The EB Series Electric Furnace is actually two systems in
one. As an air handler, it provides airflow for air conditioning
and heat pump cooling requirements. As an electric furnace,
its range of heating capacities makes the EB a perfect match
for the heating requirements of almost any manufactured
home.
WARRANTY
2- year limited parts warranty.
FEATURES
•Zero clearance feature allows the EB to be installed
where space is a premium.
•Pre-painted white front panels provide a scratch resistant, attractive, easy to clean appliance finish.
•Built-in coil cabinet is design-matched to work in conjunction with Coleman heat pumps and air conditioners,
providing ease of installation and highly efficient operating performance.
•Air Conditioner and Heat Pump operation ready, all models have a multi-speed blower capable of handling cooling and heat pump loads.
•Heating package includes specifically designed, long
lasting nickel/chrome heat elements.
•Universal throw-away filter cleans the air, and is easy to
replace.
•Accessory blower kit available for larger A/C and HP
applications.
•As defined by the U.S. Department of Energy, these furnaces are 100% efficient when used in specified applications.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
294135-BTG-B-1207
Thermostat
Wiring
Entry
Field
Wiring
Entry
J
H
B
C
Sub-Base, if
Used, Adds 7/8”
More to Total
Height and
3/8” to width.
E
A
D
19-5/8
1-7/8
A
2-5/8
B
3-1/2
C
J
L
1
5-1/16
5-1/2
5-13/16
1
1-3/4
7-13-16
8-5/8
9-7/16
16-1/2
D
E
F
G
51-5/8
H
K
M
N
N
M
L
K
OPTIONAL BOTTOM FIELD
F
G
WIRING ENTRY
ELETRICAL DA TA
MODEL NUMBEREB23CEB20CEB17CEB15CEB12CEB10C
D.O.E.
OUTPUT
CAPACITY
OUTPUT
CAPACITY
ELEMENT
CAPACITY
@ 240 VAC
MOTOR AMPS @ 240 V4.0 MAXIMUM
CIRCUIT LOAD
AMPS @ 240 V
SHIPPING WEIGHTS868486858483
* Approved for Single Branch Circuit Service Only.
Casing or Cabinet must be permanently grounded in accordance with N.E.C. or other applicable codes.
Access for servicing is an important factor in the location of
any furnace. A minimum of 24 inches should be provided in
front of the furnace for access to the heating elements and
controls. This access may be provided by a closet door or by
locating the furnace 24 inches from a facing wall or partition.
Unitary Products Group3
FURNACE CLEARANCE
Electric furnace is approved for zero (0) in. clearance to combustible material on all or any part of the furnace exterior and
the inlet or outlet duct work. For furnaces installed in upflow
application, there must be 1” clearance from the outlet duct
work for a distance of 3 feet from the supply air opening.
Clearances must be provided above the furnace for a minimum of 200 sq. inches free opening for return air. For clearances other than shown above see paragraph on Return Air.
RETURN AIR
In order for the furnace to work properly, a closet or alcove
must have a certain total free area opening for return air.
FOR HEATING ONLY FURNACE
2
Minimum 200 in
Use Return Grille 7900-287P/B,
Or any Return Grille with minimum 200 in
FOR A/C AND HP APPLICATIONS (Standard Blower):
Minimum 250 in
Use Return Grille 7900-287P/B, 1FG0620BK (hinged),
Or Louvered Door 3500-1581, 3500-5851 (bulk pack),
Or any Return Grille with minimum 250 in
FOR A/C AND HP APPLICATIONS (Accessory Blower)
Minimum 330 in
Use Return Grille 1RF1025BK, 1FG0125 (hinged),
Or Louvered Door 3500-1591, 3500-5861 (bulk pack),
Or any Return Grille with minimum 330 in
The return air opening can be located in a closet front door or
a sidewall above the furnace casing, or in a louvered door on
the furnace. If opening for the return air is located in the floor,
side walls or closet door anywhere below furnace casing
height, 6 inches minimum clearance must be provided on the
furnace side where return is located to provide for proper air
flow.
For Upflow installations, a closet that is 32 inches wide by 30
inches deep with a 30-inch wide door is necessary.
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
CAVITY
FOR
COIL
CIRCUIT
BREAKERS
ELECTRIC
PANEL
FILTER (IN
DOWNFLOW
ONLY) *
THERMOSTAT
WIRES
U
R
L
* Filter in the front panel of EBL series furnace.
FIELD WIRING
PROTECTIVE
SHIELD
AIR FILTER
The filter supplied with the furnace is of the throw-away type.
Filters need to be cleaned frequently. Shake out all loose dirt,
and use vacuum cleaner to clean additionally. This method of
cleaning will prolong life of filters. DO change filters often
since clean filters not only provide added comfort, better and
cleaner environment, but increase the efficiency of the furnace as well.
FILTER LOCATION: The furnace's front panel must be
removed to gain access to the filter of the downflow furnace.
(See Figure 2.) However, the filter for the upflow furnace* is
located behind the return air grill, adjacent to the furnace
closet or any other location in the return air. For EBL series
furnaces air filters (20 x 20 x 1) are located inside the front
panel.