Unitary products group EB23C, EB20C, EB17C, EB15C, EB12C Technical Manual

...
294135-BTG-B-1207
TECHNICAL
TECHNICAL
GUIDE
GUIDE
DOWNFLOW/UPFLOW ELECTRIC FURNACE
MODELS: EB SERIES
The EB Series Electric Furnace is actually two systems in one. As an air handler, it provides airflow for air conditioning and heat pump cooling requirements. As an electric furnace, its range of heating capacities makes the EB a perfect match for the heating requirements of almost any manufactured home.
WARRANTY
2- year limited parts warranty.
FEATURES
Zero clearance feature allows the EB to be installed where space is a premium.
Pre-painted white front panels provide a scratch resis­tant, attractive, easy to clean appliance finish.
Built-in coil cabinet is design-matched to work in con­junction with Coleman heat pumps and air conditioners, providing ease of installation and highly efficient operat­ing performance.
Air Conditioner and Heat Pump operation ready, all mod­els have a multi-speed blower capable of handling cool­ing and heat pump loads.
Heating package includes specifically designed, long lasting nickel/chrome heat elements.
Universal throw-away filter cleans the air, and is easy to replace.
Accessory blower kit available for larger A/C and HP applications.
As defined by the U.S. Department of Energy, these fur­naces are 100% efficient when used in specified applica­tions.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
294135-BTG-B-1207
Thermostat Wiring Entry
Field Wiring Entry
J
H
B
C
Sub-Base, if Used, Adds 7/8” More to Total Height and 3/8” to width.
E
A
D
19-5/8
1-7/8
A
2-5/8
B
3-1/2
C
J
L
1
5-1/16
5-1/2
5-13/16
1
1-3/4
7-13-16
8-5/8
9-7/16
16-1/2
D
E F
G
51-5/8
H
K
M
N
N
M
L
K
OPTIONAL BOTTOM FIELD
F
G
WIRING ENTRY
ELETRICAL DA TA
MODEL NUMBER EB23C EB20C EB17C EB15C EB12C EB10C
D.O.E.
OUTPUT
CAPACITY
OUTPUT
CAPACITY
ELEMENT
CAPACITY
@ 240 VAC
MOTOR AMPS @ 240 V 4.0 MAXIMUM
CIRCUIT LOAD AMPS @ 240 V
SHIPPING WEIGHTS 868486858483
* Approved for Single Branch Circuit Service Only. Casing or Cabinet must be permanently grounded in accordance with N.E.C. or other applicable codes.
24 VAC
60 Hz.
1 PHASE 230 VAC.
60Hz.
1 PHASE
220 VAC
60Hz.
1 PHASE
BTU 77,000 67,000 56,000 51,000 39,000 34,000
KW 22.6 19.6 16.4 15.0 11.4 10.0
BTU 71,000 61,000 52,000 47,000 36,000 31,000
KW 20.8 17.9 15.2 13.8 10.6 9.1
BTU 65,000 57,000 48,000 43,000 33,000 29,000
KW 19.1 16.7 14.1 12.6 9.7 8.5 KW 21.6 19.2 16.0 14.4 11.2 9.6
AMPS90.080.066.760.046.740.0
CKT 1 47.3 44.0 47.3 44.0 50.7* 44.0* CKT 2 46.7 40.0 23.4 20.0 -- --
FILTER SIZE 16 x 20 x 1
2 Unitary Products Group
294135-BTG-B-1207
EB SERIES BLOWER PERFORMANCE
Static Pressure (Inches of WC) .0 .1 .2 .3 .4 .5 .6 .7 .8
Low Speed Heating Speed Models EB10, 12, 15
Medium Speed Heating Speed Models EB17, 20, 23
Medium High with A-Coil in place
High with A-Coil in place
CFM (STD. Air) 945 936 936 924 915 889 870 813 705
CFM (STD. Air) 1160 1145 1145 1140 1129 1109 1073 1027 935
CFM (STD. Air) 1340 1317 1290 1252 1208 1158 1095 1021 876
CFM (STD. Air) 1573 1534 1490 1435 1369 1309 1237 1135 1019
SUPPLY CIRCUIT WIRE SIZES - 240 VOLT, 60 CYCLE, SINGLE PHASE - FROM N.E.C. TABLE 310-16
MODELS EB23C* EB20C* EB17C* EB15C* EB12C EB10C
Single Branch Circuit Service
Nominal Circuit Load - AMPS 94.0 84.0 70.7 64.1 50.7 44.0 Minimum Wire Size (90ºC) #2 #3 #4 #4 #6 #8 Minimum Wire Size (75ºC) #1 #2 #3 #4 #6 #6 Minimum Wire Size (60ºC) #0 #1 #2 #3 #4 #6 Ground Wire Size #6 #6 #8 #8 #8 #10 Max. Fuse (or C.B.) - AMPS 125 110 90 90 70 60
Dual Branch Circuit Service
Branch Circuit Load - AMPS 47.3 46.7 44.0 40.0 47.3 23.4 44.0 20.1 Branch Circuit Min. Ampacity 59.2 58.4 55.0 50.0 59.2 29.3 55.0 25.2 Minimum Wire Size (90ºC) #6 #6 #8 #8 #6 #10 #8 #10 Minimum Wire Size (75ºC) #6 #6 #6 #8 #6 #10 #6 #10 Minimum Wire Size (60ºC) #4 #4 #6 #6 #4 #10 #6 #10
Ground Wire Size Max. Fuse (or C.B.) - AMPS 60 60 60 50 60 30 60 30
* Requires Jumper Bars (P/N 3500-378P) - Dual Supply for U.S. Only.
T
- Refer to N.E.C. Table 250-95 for non-sheated conductor ground wire.
T
2 Leads +
1 Ground
CKT #1
4 Leads +
2 Ground
CKT #1 CKT #2 CKT #1 CKT #2 CKT #1 CKT #2 CKT #1 CKT #2
#10 #10 #10 #10 #10 #10 #10 #10
2 Leads +
1 Ground
CKT #1
4 Leads +
2 Ground
2 Leads +
1 Ground
CKT #1
4 Leads +
2 Ground
2 Leads +
1 Ground
CKT #1
4 Leads +
2 Ground
2 Leads +
1 Ground
CKT #1
APPROVED
2 Leads +
1 Ground
CKT #1
NOT
LOCATION
Access for servicing is an important factor in the location of any furnace. A minimum of 24 inches should be provided in front of the furnace for access to the heating elements and controls. This access may be provided by a closet door or by locating the furnace 24 inches from a facing wall or partition.
Unitary Products Group 3
FURNACE CLEARANCE
Electric furnace is approved for zero (0) in. clearance to com­bustible material on all or any part of the furnace exterior and the inlet or outlet duct work. For furnaces installed in upflow application, there must be 1” clearance from the outlet duct work for a distance of 3 feet from the supply air opening. Clearances must be provided above the furnace for a mini­mum of 200 sq. inches free opening for return air. For clear­ances other than shown above see paragraph on Return Air.
RETURN AIR
In order for the furnace to work properly, a closet or alcove must have a certain total free area opening for return air.
FOR HEATING ONLY FURNACE
2
Minimum 200 in Use Return Grille 7900-287P/B,
Or any Return Grille with minimum 200 in
FOR A/C AND HP APPLICATIONS (Standard Blower):
Minimum 250 in Use Return Grille 7900-287P/B, 1FG0620BK (hinged), Or Louvered Door 3500-1581, 3500-5851 (bulk pack),
Or any Return Grille with minimum 250 in
FOR A/C AND HP APPLICATIONS (Accessory Blower)
Minimum 330 in Use Return Grille 1RF1025BK, 1FG0125 (hinged), Or Louvered Door 3500-1591, 3500-5861 (bulk pack),
Or any Return Grille with minimum 330 in The return air opening can be located in a closet front door or
a sidewall above the furnace casing, or in a louvered door on the furnace. If opening for the return air is located in the floor, side walls or closet door anywhere below furnace casing height, 6 inches minimum clearance must be provided on the furnace side where return is located to provide for proper air flow.
For Upflow installations, a closet that is 32 inches wide by 30 inches deep with a 30-inch wide door is necessary.
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
2
free area opening.
CAVITY FOR COIL
CIRCUIT BREAKERS
ELECTRIC PANEL
FILTER (IN DOWNFLOW ONLY) *
THERMOSTAT WIRES
U
R
L
* Filter in the front panel of EBL series furnace.
FIELD WIRING PROTECTIVE SHIELD
AIR FILTER
The filter supplied with the furnace is of the throw-away type. Filters need to be cleaned frequently. Shake out all loose dirt, and use vacuum cleaner to clean additionally. This method of cleaning will prolong life of filters. DO change filters often since clean filters not only provide added comfort, better and cleaner environment, but increase the efficiency of the fur­nace as well.
FILTER LOCATION: The furnace's front panel must be removed to gain access to the filter of the downflow furnace. (See Figure 2.) However, the filter for the upflow furnace* is located behind the return air grill, adjacent to the furnace closet or any other location in the return air. For EBL series furnaces air filters (20 x 20 x 1) are located inside the front panel.
Subject to change without notice. Printed in U.S.A. 294135-BTG-B-1207 Copyright © by Unitary Products Group. 2007. All rights reserved. Supersedes: 294135-BTG-A-0607
Unitary P.O. Wichita Products Box KS Group 19014 67204-9014