Unitary products group DLAS, DGAT, DGAM Installation Instructions Manual

INSTALLATION
INSTRUCTIONS
MODELS DLAS, DGAT AND DGAM
SEALED COMBUSTION
DOWNFLOW GAS FURNACES
(Forced Draft with Direct HSI)
Supersedes: 1973--106/F Rev.1 (1098)
Improper installation, adjustment, service or maintenancecancauseinjuryorpropertydam­age. Please refer to all the instructions of this manual for proper installation procedures. Im­proper installation will void the warranty.
The furnace shall be installed so the electrical components are protected from water.
The furnace is not to be used for temporary heating of buildings or structures under constructions.
1973--106/F Rev.2 (599)
For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park Models
3. Modular Homes & Buildings
DGAT & DGAM MODELS (With Built--in Coil Cabinet)
IMPORTANT: Only individuals having proven experi-
ence with this type of equipment should attempt to per­form set--up.
Properfurnaceset--upandadjustmentis theresponsibil­ity of the retailer/homeowner and is not covered under warranty.
FURNACE SET--UP CHECK LIST
- Has roof jack crown been correctly installed?
- Has furnace gas valve and burner orifice been cor-
rectly converted for L.P. gas where applicable?
- Has furnace gas valve been de--rated for altitudes above 2000 feet where applicable?
- Is gas line outlet pressure properly set for fueltype? (natural gas is 3.5” W.C.; L.P. is 10” W.C.)
- Is primary air properly adjusted per installation in­structions?
- Is cross--over duct installed per home builder and UPG installation instructions?
- Has furnace been operated through a complete heating cycle?
Donot testthe fuel system at morethan 14inch­es water column after furnace has been con­nected to the fuel line. Such testing may void the warranty. Any test run above 14 inches wa­ter column may damage the furnace control valve which could cause an explosion, fire, or asphyxiation.
Improper installation may damage equipment, can create a shock hazard, and will void the warranty.
NOTE: The words “Shall” or “Must” indicate a
requirement which is essential to satisfactory and safe product performance.
The words “Should” or “May” indicate a recommendation or advice which is not essential and not required but which may be useful or helpful.
IMPORTANT: These instructions are primarily in-
tended to assist qualified individuals experienced in the proper installation of heating and/ or air conditioning ap­pliances. Some local codes require licensed installation service personnel for this type of equipment. Read allin­structions carefully before starting the installation.
TABLE OF CONTENTS
LIST OF FIGURES
FURNACE SPECIFICATIONS 3...................
INSTALLATION STANDARDS 4...................
Code Compliance 4...........................
High Altitude Installation 4.....................
Minimum Furnace Clearance 4.................
RETURN AIR REQUIREMENTS 5.................
Closet Installations 5..........................
Air Distribution Systems 5.....................
ROOF JACKS 7.................................
Existing Furnace Replacement 7...............
New Home Installation 7.......................
Installation in Snow Regions 7..................
Locating and Cutting Roof Jack Opening 7.......
Installing Roof Jack in Roof 7..................
DUCT CONNECTORS 10........................
Installation of Screw Attachment
Duct Connector 1 1............................
Installation of Tab Attachment
Duct Connector 1 1............................
Installation of Furnace 12.....................
CONNECTING ROOF JACK TO FURNACE 12.....
Ceiling Rings 13.............................
ELECTRICAL WIRING 13........................
Connect Power Supply Wires 13..............
Connect Thermostat Wires 13.................
Wall Thermostat 14..........................
WIRING DIAGRAMS 15 &16.....................
GAS PIPING 17................................
Installation and Checking of Gas Line 17........
FINAL PROCEDURE 19.........................
Install Furnace Doors 19......................
Finish and Trim 19...........................
Furnace and Air Conditioner Installations 19.....
HIGH ALTITUDE DERA TION CHART 20...........
Natural Gas 20..............................
Propane Gas 20.............................
REPAIR PARTS 21- -22..........................
FIGURE 1 — Furnace Dimensions 3............
TABLE 1 — Minimum Clearances 4.............
FIGURE 2 — Air Distribution Systems 5.........
FIGURE 3 — Closet to Door Clearance — 6” or
greater 6....................................
FIGURE 4 — Furnace to Closet Door Clearance
—1”to6” 6..................................
FIGURE 5 — Furnace to Closet Door Clearance
— Less than 1” 6............................
FIGURE 6 — Standard Roof Jack 8.............
FIGURE 7 — Roof Jack with Removable
Crowns 9....................................
FIGURE 8 — Duct Connector Dimensions 10... FIGURE 9 — Duct Connector Screw
Attachment 11...............................
FIGURE 10 — Duct Connector Tab
Attachment 11...............................
FIGURE 1 1 — Installation of Furnace 12........
FIGURE 12 — Connecting Roof Jack to
Furnace 12.................................
FIGURE 13 — Ceiling Rings 13...............
FIGURE 14 — Field Wiring 13................
FIGURE 15 — Thermostat Wiring for DGAT and
DGAM 14..................................
FIGURE 16 — Thermostat Wiring for DLAS 14..
FIGURE 17 — Wiring Diagram for DGAT 15....
FIGURE 18 — Wiring Diagram for DGAM 16...
FIGURE 19 — Natural Gas Flame 18..........
FIGURE 20 — Propane Gas Flame 18.........
FIGURE 21 — Anti--Backflow Damper 19.......
2
Unitary Products Group
FURNACE SPECIFICATIONS
DGAM — Automatic ignition — with Built--in Coil Cabinet — 4 Ton -- A/C Ready
Model No. Factory Equipped for use with: Input/BTUH Output/BTUH
DGAM056BDF NA TURAL GAS 56,000 46,000 DGAM075BDF NA TURAL GAS 75,000 61,000
DGAT — Automatic Ignition — with Built--in Coil Cabinet — 3 Ton -- A/C Ready
Model No. Factory Equipped for use with: Input/BTUH Output/BTUH
DGAT056BDF NATURAL GAS 56,000 46,000 DGAT070BDF NATURAL GAS 70,000 57,000 DGAT075BDF NATURAL GAS 75,000 61,000 DGAT090BDF NATURAL GAS 90,000 72,000
DLAS — Automatic Ignition — Heating Only — No Coil Cabinet
Model No. Factory Equipped for use with: Input/BTUH Output/BTUH
DLAS056BDF PROPANE 56,000 47,000 DLAS075BDF PROPANE 75,000 62,000
Electrical Specifications
Electrical Power Supply 120Volts—60Hz—1Phase Breaker or Fuse 15 Amp Thermostat Circuit 24Volt—60Hz—40VA Nominal Anticipator Setting .50 Gas Valve Inlet
1
/2”NFPT
59--1/2”
19--1/2”
9--3/4”
10--5/8”
24”
23”
76”
19--1/2”
9--3/4”
24”
23”
10--5/8”
FIGURE 1 -- DLAS, DGAT AND DGAM SERIES FURNACE DIMENSIONS
Unitary Products Group
DGAT & DGAM SeriesDLAS Series
3
INSTALLATION STANDARDS
CODE COMPLIANCE
The installer shall familiarize himself with and comply with all local codes and regulations which govern the in­stallation of this appliance. Local codes and regulations shall take precedent over these regulations where appli­cable. In lieu of local codes, the appliance shall be in­stalled in accordance with one or more of the following standards.
Manufactured homes in the U.S.A.:
1. Federal Manufactured Home Construction & Safety Standard (H.U.D. Title 24, Part 3280)
2. American National Standard (ANSI- -Z223.1, NFPA--54) for gas fired furnaces.
3. Unit electricalwiring and groundingshallcomplywith current CSA standard C22.2 No.148/CAN/CSA-­Z240.6.2 -- Electrical Requirements for recreational vehicles.
Manufactured homes in Canada:
1. CAN/CGA B149 for gas fired furnaces.
2. CSA 22.1 Canadian Electrical Code part 1 for all electrical field wiring.
Recreational Vehicles in U.S.A.:
1. American National Standard (ANSI--119--2/NFPA-­501C) for recreation vehicle installations.
2. Unit electricalwiring and groundingshallcomplywith current CSA standard C22.2 No.148/CAN/CSA-­Z240.6.2 -- Electrical Requirements for recreational vehicles.
Recreational Vehicles in Canada:
1. Unit installation shall comply withcurrent CSA stan­dard CAN/CGA--Z240.4.2 -- Installation Require­ments for Propane Appliances and Equipment in Recreational Vehicles.
2. Unit electricalwiring and groundingshallcomplywith current CSA standard C22.2 No.148/CAN/CSA-­Z240.6.2 -- Electrical Requirements for recreational vehicles.
HIGH ALTITUDE INSTALLATION
Forelevation above2,000feet, deratefurnaceorifice4% foreach1,000 feetof elevation above sealevel. Derating is accomplished by reducing the orifice size. See Derat­ing Chart for orifice size.
CAUTION:
D Never attempt to alter or modify this furnace or any
of its components.
D Neverattempttorepair damagedor inoperable com-
ponents. Such action could cause unsafe operation, explosion, fire and/or asphyxiation.
D If a malfunction has occurred, or if you feel that the
furnace is not operating as it should, contact a quali­fied service agency or gas utility for assistance.
MINIMUM FURNACE CLEARANCES
Access for servicing is animportant factor in thelocation of any furnace. A minimum of 24 inches should be pro­videdin front ofthe furnace for access tothe heating ele­ments and controls. This access may be provided by a closet door or by locating the furnace 24 inches from a facing wall or partition.
These furnaces are design certified for the following minimum clearances from combustible material in al­cove or closet installation:
TABLE 1 — Minimum Clearances
CLOSET ALCOVE
BACK 0” 0” SIDES 0” 0” FRONT 6” 24” TOP 2” 2” ROOF JACK 0” 0” DUCT 0” 0”
4
Unitary Products Group
RETURN AIR REQUIREMENTS
A
CLOSET INSTALLATIONS
Additional Requirements
Additional requirements for floor and ceiling return sys­tem for closet installed sealed combustion heating appliance are given in the next paragraph.
Floor or Ceiling Return Air System
Floororceiling returnairsystem forcloset installeddirect vent forced air heating appliance.
Listed in the next paragraph are the conditions to bemet byMobile HomeManufacturers tohave U.L.acceptance of in--floor or ceiling return air systems of closet installed direct vent forced air heating appliances for Mobile Homes to be sold in the United States.
1. The return--air opening into the closet, regardless of location, is to be sized not less than specified on the appliance’s rating plate.
2. If the return--air opening is located in the floor of the closet (versus the vertical front or side wall), the opening is to be provided with means to prevent its inadvertent closure by a flat object placed over the opening.
3. The cross--sectional area of the return duct system (when located in the floor or ceiling of the mobile home) leading into the closet is to be not less than that of the opening specified on the appliance’s rat­ing plate.
4. The total free area of openings in the floor or ceiling registers serving the return--air duct system is tobe not less than 150% of the size of the opening speci­fiedon theappliance’s rating plate. Atleast onesuch register is to be located where likelihood of its being covered by carpeting, boxes, and other objects is minimized.
5. Materials located in the return duct system have a flame spread classification of 200 or less.
A
Single trunk duct
B*
Dual trunk duct with crossover connector
1
6. Non--combustible pans having one--inch upturned flanges are located beneath openings in the floor re­turn duct system.
7. Wiring materials located in the return duct system conformtoArticle 300--22(b&c)of theNational Elec­tric Code (ANSI C1 / NFPA--70).
8. Gas piping is not run in or through the return duct system.
9. The negative pressure in the closet as determined by test with the air--circulating fan operating at high heatingspeed andthe closet doorclosed is to benot more negative than minus 0.05--inch water column.
10. For floor return systems, themobile home manufac­turer or installer shall affixa prominent marking on or near the appliance where it is easily read when the closet door is open. The marking shall read:
HAZARD OF ASPHYXIATION
DO NOT COVER OR RESTRICT FLOOR
OPENING, or equivalent.
AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system shall be designed sothat thestatic pressure does not exceed the listed static pressure rating on the furnace rating plate.
Three typical distribution systems are illustrated in Fig­ure 2.
Location, size and number of registers should be se­lected on the basis of best air distribution and floor plan of the home.
The Air Temperature Rise is to be adjusted to obtain a temperature rise withinthe range(s) specified onthe fur­nace rating plate.
C
Transition Duct with Branches
Transition duct
Dual trunk duct
Crossover
*B
1
D
Crossover Duct must be centered directly under furnace.
2
Use 12” Diameter Round or equivalent insulated Flex--duct only.
D
3
Terminate Flex--duct (opposite furnace) in the center of the trunk duct.
D
4
Flex--duct material must be pulled tight — No Loops or unnecessary dips — Air Flow may be impeded.
D
FIGURE 2
Unitary Products Group
IR DISTRIBUTION SYSTEMS
4
3
2
Branches
5
Return Air Grille Part No. 7900--286P/A — Almond 7900--287P/A — White
A
250 SQ. IN. MINIMUM FREEAREA
B
Furnace to Closet Door Clearance — Greater than 6 Inches
TheclosetdoorMUSThavea minimumof250 Square Inches offreearea in the upper half of the door.
Ifopeningforreturnairislocated inthefloor or sidewalls and below thetop of the furnace casing:
1. 6 inches minimum clearance must be provided on side where return is located, and
2. 6 inches minimum clearance must be maintained from the front of
50 SQ. IN. MINIMUM FREEAREA
250 SQ. IN. FREEAREA
MINIMUM
furnace.
CLOSET
FURNACE
As an option to the lower grill, an undercut of 2 1/2” will provide 50 Sq. In. of free area.
DOOR
FIGURE 3 — CLOSET TO DOOR CLEARANCE — 6” OR GREATER
Furnace to Closet Door Clearance — Greater than 1 Inch and Less than 6 Inches
A
250 SQ. IN. MINIMUM FREEAREA
B
50 SQ. IN. MINIMUM FREEAREA
250 SQ. IN. MINIMUM FREEAREA
1. The closet door MUST have a minimum of 250 Square In- ches of free area in the upper half of the door and a mini­mumof 50 Square Inches of free area in thelower area of the door. The lower closet door grille may be omitted if an undercut of 2 1/2 Inches is provided in the door.
2. A fully louvered closet door MUST have a minimum of 250 Square Inches of free area in the upper half of the door.
Return Air Closet Door Part No. 7900--7771/C — White
6” or greater — Closet to Door Clearance
As an option to the lower grill, an undercut of 2 1/2” will provide 50 Sq. In. of free area.
FIGURE 4 — FURNACE TO CLOSET DOOR CLEARANCE — 1” to 6”
Furnace to Closet Door Clearance — Less than 1 Inch
250 SQ. IN. MINIMUM FREEAREA
50 SQ. IN. MINIMUM FREEAREA
FIGURE 5 — FURNACE TO CLOSET DOOR CLEARANCE — LESS THAN 1”
6
Thecloset door MUST have three return air grilles. The total free area of the two upper grilles must be a minimum of 250 Square Inches. The total free area of the lower grille MUST be a mini­mum of 50 Sq. In.
Each grille MUST BE ALIGNED directly opposite the corre­sponding return air grille of the furnace door.
Unitary Products Group
ROOF JACKS
FAILURE TO FOLLOW ALL VENTING IN ­STRUCTION CAN RESULT IN FIRE ASPHYXI­ATION, OR EXPLOSION.
CAUTION: Only use the appropriate roof jack.
See Figures 6 & 7 for correct application. Do not exceed the maximum height as determined
from Figures 2 & 3. Installer should allow an addi­tional 1­fully extended against the built-in stop. This pro­vides an additional safeguard against the flue as­semblybeing pulledfromtheroofjackduringtrans­portation or other stress conditions.
EXISTING FURNACE REPLACEMENT
If this furnace replaces an exciting furnace,dothefol­lowing:
1. If a 2
2. After unpacking the roof jack, check the rain caps.
3. Before inserting the roofjack into the furnace top, in-
4. After installing roof jack on furnace top collar,check
5. Use only the pipes provided with the roof jack as-
6. In no case should there be a gap between sections
1
/2” travel before the flue pipe assembly is
nd
roof, roof cap or addition has been made to
the existing roof of the home, remove the old roof
jack completely!... to avoid the possibility of an improperlyinstalledpipe or gaps in the old roof jack, INSTALL A NEW ROOF JACK. Your ceiling and roof height will determine the correct roof jack to use. Refer to the vent selection table, of the furnace installation instructions.
Insure they are not damaged, tilted or crooked. Do not twist, crush or sit on the roof caps during installation.Damagedroof caps will cause improp-
er furnace operation. The furnace will not heat prop­erly and could result in explosion.
spect the furnace flue and combustion air opening for debris or insulation which might have fallen in during pre--installation steps. Do not proceedunless all debris have been cleaned out or removed.
tomake sure thereis nogap in backor side between the pipe collar and the furnace casing top.
sembly. Do not add to or adapt other sheet metal pipes.Donotcut,insertor addotherpipestothis
assembly.
of the flue pipe or the combustion air pipe. If neces­sary to prevent excessive air leakage, the installer shouldseal joints in the combustion air tube withalu­minum type or other suitable sealant.
NEW HOME INSTALLATION
Ifthis furnaceis installedonanewhome do thefollowing:
1. Inspect the furnace top collars for signs of insulation or ceiling debris which might have fallen in during cutting of the ceiling and roof holes. Remove all de­bris before continuing.
2. After unpacking the roof jack, check the rain caps. Insure they are not damaged, tilted or crooked. Do
not twist, crush or sit on the roof caps during installation.Damagedroof caps will cause improp-
er furnace operation. The furnace will not heat prop­erly and could result in explosion.
3. Before inserting the vent pipe into the furnace top, inspect the furnace flue and combustion air opening for debris or insulation which have fallen in during pre--installation steps. Do not proceed unless allde­bris have been cleaned out or removed.
4. After installing roof jack on furnace top collar,check tomake sure thereis nogap in backor side between the pipe collar and the furnace casing top. If neces­sary to prevent excessive air leakage, the installer shouldseal joints in the combustion air tube withalu­minum type or other suitable sealant.
INSTALLATION IN SNOW REGIONS
Whenthe combustion airpipeinlet iscovered orblocked with snow, the furnace will not operate properly due to the depleted combustion air supply.
Therefore, if the furnace will be located in regions where snow accumulation on the roof exceeds 7” or in H.U.D. Snow Load Zones, a roof jack extension (Part No. 7680B6541) is recommended.
LOCATING AND CUTTING ROOF JACK OPENING
To facilitate the proper installation of the roof jack, it is very important that the roof jack opening in the ceiling and roof be on the same vertical center line as the fur­nacefluecollar.SeeFigure8.
Mark this location on ceiling and scribe a circle with a 5” radius (10” diameter) around this mark. Cut opening for roof jack through ceiling and roof. (If furnace was in-
stalled during construction, cover furnace and flue opening to prevent debris from entering flue when hole is cut for roof jack.)
INSTALLING ROOF JACK IN ROOF
(See Figure 6 & 7 for Dimensional requirem ents .)
Insert roof jack into opening in the roof.
The roof jack should be secured to the furnace be­foreroof flange (flashing) is secured tothe roof. This
will insure a better alignment ofthe fluepipe andfurnace fluecollar. Caulk around andunder roofflangeto provide a water tight seal, before securing roof jack flashing to roof.
Unitary Products Group
7
SWIVEL FLASHING
ADJUSTS FROM
0/12 TO 5/12 PITCH
4000--7101/C 4000--7121/C
4000--7141/C 4000--7151/C 4000--7171/C
SLANT FLASHING 3/12 PITCH
4000--6101/A 4000--6121/A
4000--6141/A 4000--6151/A 4000--6171/A
DLAS & COAS Furnaces DGAT, DGAM, COAT, CGAT Furnace
Installation Dimensions Installation Dimensions
Adjustable Height
A
70” to 79” 75” to 86”
83” to 104”
90” to 116”
127” to 157”
Adjustable Height
B
86” to 95” 91” to 102”
99” to 120” 106” to 132” 143” to 173”
FLUE GASES
COMBUSTION AIR
CAULK UNDER FLASHING
19 1/2”
FLUE GASES
COMBUSTION AIR
CAULK UNDER FLASHING
CAULK CAREFULLY ALL AROUND SWIVEL JOINT WITH SEALANT SUPPLIED BY FURNACE MANUFACTURER.
The End of Upper Portion of Roof Jack need
Not extend below the ceiling.
IMPORTANT
SEALROOFJACKFLASHINGTOTHEROOFJACK AND ROOF. THIS IS THE INSTALLER’S RESPONSIBILITY.
A B
76”
19 1/2”
ROOF
59--1/2”
DLAS & COAS Models
WARM AIR DUCT
DUCT CONNECTOR
FIGURE 6 -- STANDARD ROOF JACK
8
FLOOR
DGAT, DGAM, COAT & CGAT Models
DUCT CONNECTOR
WARM AIR DUCT
Unitary Products Group
Loading...
+ 16 hidden pages