Unitary products group DAPH Series, DAPH018, DAPH024, DAPH030, DAPH036 Installation Instruction

...
CAUTION
THE ENCL OSED I NST ALL ATION INSTRUCTIONS AND ANY APPL I CABL E
LOCAL, STATE , AND NATIONAL CODES INCLUDING, BUT NOT LIMI T E D
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH
WARNING
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAM AGE.
INCORRECT INSTAL L ATION MAY CREATE A CONDI TION WHERE THE
INSTALLATION
SINGLE PACKAGE AIR CONDITIONERS
ELECTRIC/ELECTRIC, AIR COOLED
INSTRUCTION
MODELS DAPH018 THR U 060, 1-1/2 THRU 5 T ON
GENERAL
Supersedes: 530.46-N2W (498)
(12 AND 13 SEER)
REFERENCE
530.46-N2Z (799)
035-17224-000
Models DAPH units are factory assembled cooling only air condi­tioners designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide electric heat combined with electric cooling.
The units are compl etely assemb led on rigi d, but ea sily remov ­able base rails. All piping, refrigerant charge, and electrical wiring is factor y installed and tested. The units require only electric power and duct co nnecti ons at the po int of i nstall ation.
The electric heaters have nickel-chrome resistance wire ele­ments and utilize single poi nt po wer connection .
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be note d on the carrier’ s fre ight bil l. A se parate request for inspection by the carrier’s agent should be made in writing. Refer to Form 50.15-NM for additional information.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installa tion easier . and/or equipment damage may result if installation procedure is not handled properly.
Cautions are gi ven to pre vent equipment dam age. W arnings are give n to alert installer th at personal inj ury
Additional information on the design, installation, operation and service of this equipmen t is av ailab le in the f ollo wing ref erence forms:
55.70-N1 -General Installation
55.70-N2 -Pre-start & Post-start Check List
511.26-N1.1V -Electric Heater Accessory
REPLACEMENT PARTS
Refer to Replacement Parts Manual for complete listing of replacement parts on this equi pm ent.
All forms referenced in this instruction may be ordered from:
Standard Register 2101 West T ecumseh Road Norman, Oklahoma 73069 T o ll Free FAX: (877) 379-7920
530.46-N2Z
PRODUCT NOMENCLATURE
D A P H
PRODUCT CATEGORY
D = Single Package Air Conditioner (Air Cooled)
PRODUCT GENERATION
P = NEW or Current Design
VOLTAGE CODE
-F = 208/230-1-60
PRODUCT IDENTIFIER
PH = 12 SEER Cooling Models
-T = 208/230-3-60
-W = 460-3-60
-X = 575-3-60
INSTALLATION
LIMITATIONS
These units must be installed in accordance with the following national and local safety codes.
1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).
2. Local plumbing and waste water codes and other applica­ble local codes.
Refer to Table 1 for unit application data an d to Tables 5 and 6 for electric heat application data.
If components are to be added to a unit to meet local codes, they are to be installed at the dealers and/or the customer’s expense.
Size of unit for prop os ed in st al la ti on sh ou ld be ba se d on hea t loss/heat gain calculations made in accordance with industry recognized procedures identified by the Air Conditioning Con­tractors of America.
TABLE 1
Wet Bulb Temperature (°F) of Air on Evapor a to r C o il, Min. / Max.
Dry Bulb Temperature (°F) of Air on Condenser Coil, Min.
1
Utilization range “A” in accord an ce w ith ARI St an da rd 110 .
2
A low ambient accessory is available for operation down to 0°F
3
T1" transformer primary tap must be moved from the 230 volt connec tion to the 208 volt
connection for low voltage applic ations of 208 volt and below.
LOCATION
Use the following guidelines to sele ct a suitable location for these units.
1. Unit is designed for outdoor installation only.
2. Condense r mus t have an unli mite d suppl y of a ir. Where a
3. For ground level installation, a level pad or slab should be
4. For roof top in stallati on, be s ure th e struc ture wil l support
- UNIT APPLICATION DATA
V oltage V ariation
Min. / Max
.1
2
/ Max.
208/230V
3
460V 414 / 504 575V 518 / 630
187 / 253
57 / 72
45 / 120
3
choice of location is possible, position unit on either north or east side of bu il di ng .
used. The thickn ess and size of the pa d or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.
the weight of the unit plus any field installed components. Unit must be installe d on a level roof curb or appropr iate
- F 2 A
0 4
FACTORY
INSTALLED ELECTRIC HEAT
A = No Electric Heat Installed
NOMINAL COOLING
CAPACITY (MBH)
018 = 18,000 BTUH 042 = 42,000 BTU H 024 = 24,000 BTUH 048 = 48,000 BTU H 030 = 30,000 BTUH 060 = 60,000 BTU H 036 = 36,000 BTUH
angle iron frame providing adequate support under the compressor/con de ns er se ction.
5. Maintain level tole ra nc e of unit to 1/8" maxi m um .
RIGGING OR HANDLING
Care must be e xercised when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig unit with slings placed under the unit. Spreader bars of sufficient length should be use d ac ross th e to p of the unit.
BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.
Units may also be moved or lifted with a fork-lift. Slotted openings in the skid are provided for this purpose. Forks must pass completely through the base.
Refer to T able 2 for unit weights and to Figure 1 for approximate center of gravity.
TABLE 2
UNIT SIZE
FRONT
FIG. 1
- UNITS WEIGHTS
SHIPPING
WEIGHT
(lbs.)
018 330 325 89 78 76 86 024 338 333 91 80 78 88 030 340 335 86 83 83 87 036 341 336 92 81 79 89 042 348 343 94 83 80 91 048 376 371 94 89 94 99 060 456 451 127 122 101 106
OF
UNIT
OPERATING
WEIGHT
"A"
1
49
8
(lbs.)
"D"
26
CORNER WEIGHTS
(location, lbs.)
"A" "B" "C" "D"
CENTER OF GRA VITY
"C"
"B"
1
1
23
47
2
4
- CENTER OF GRAVITY
2 Unitary Products Group
CLEARANCES
530.46-N2Z
CONDENSATE DRAIN
All units r equire cer tain clearances for pr oper operation and service. Refer to Figure 6 for the clearances required for combustion, construction, servicing and proper unit operation.
WARNING:Do not permit overhang in g s tructures or shrubs to
obstruct the conden ser air discharge outlet.
DUCT WORK
These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the fol lowing steps:
1. Remove the duc t covers found in the bottom return and supply air duct openings. There are f our (4) screws s ecuring each duct cover (save these screws to use later).
2. Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one .
3. Seal the duct covers with silicone caulking.
Downflow units must have an L-shaped supply duct without any outlets or registers located directly below the supply outlet of the unit.
Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
A condensate tr ap is requi red to be installe d in the co ndensate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install the condensate drain
3
⁄4“ NPTF) to spill into an open drain.
line (
SERVICE ACCESS
Access to all serviceab le compon ents is pro vided by th e fol low­ing remov able panels:
Blower service access
Electrical/filter access
Compressor service ac ce ss
Refer to Figure 6 for location of these access panels and minimum clearance.
THERMOSTAT
The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturers instructions enclosed with the thermostat for general installation procedure. Four, five or six color coded insulated wi res (minimum #18 A WG) shoul d be used to connect thermosta t to uni t. See Figure 3.
POWER AND CONTR OL WIRING
A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.
CAUT I O N : When fastening duct work to the side duct flanges on
the unit, insert the screws through the duct flanges only . DO NOT insert the screws through the casing. Outdoor duct work must be insula ted an d w aterproof ed.
NOTE: Be su re to note supply and return open in gs.
Refer to Figure 6 for information concerning rear and bottom supply and return air duct openings.
FILTERS
Single phase units are shipped without a filter and is the respon­sibility of the installer to secure a filter
or install a Filter/Frame Kit
A filter rack and a filters are stan dard on three phase units. Filters must always be used and must be kept clean. When
filters become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operat­ing costs and wear-and-tear on the uni t an d co ntrols.
(1FF0114).
in the return air ductwork
Field wiring to the unit must conform to pro visions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor termi­nals during starting a nd running cond itions are indicated on the unit Rating Plate and Table 1.
The wiring entering the cabinet must be provided with mechani­cal strain relief.
A fused or HACR breaker disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Electri cal line must be sized proper ly to carr y the load . Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.
COMPRESSORS
Units are ship ped with comp ressor mounting s facto ry-adjusted and ready for operation.
Filters should be checked monthly especially since this unit may be used for both heat in g an d co ol ing.
Unitary Products Group 3
CAUTION: Do Not loosen compressor mounting bolts.
530.46-N2Z
TABLE 3 -
PHYSICAL DATA
DPH
3
1
3
3
4
4
4
1
4
4
(ECM)
1
3
EV APORATOR
BLOWER
EV APORATOR
COIL
CONDENSER
FAN
CONDENSER
COIL
MODELS
018 024 030 036 042 048 060 CENTRIFUGAL BLOWER (Dia. x Wd. in.) 9 x 6 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 F AN MOTOR HP
(Three Speed, Direct Drive)
1
2
1
2
1
2
ROWS DEEP 2223333 FINS PER INCH 13 15 15 13 15 16 16 F ACE AREA (Sq. Ft.) 4.38 4.38 4.38 4.38 4.38 5.63 5.63 PROPELLER DIA. (in.) 22222222222222 F AN MOTOR HP
1
4
1
4
1
4
NOM. CFM TOTAL 1,800 1,800 1,800 1,800 2,400 3,000 3,000 ROWS DEEP 1111111 FINS PER INCH 20 20 20 20 20 20 20 F ACE AREA (Sq. Ft.) 12.9 12.9 12.9 12.9 12.9 16.4 16.4
CHARGE REFRIGERANT 22 (lbs./oz.) 5 / 5 5 / 3 4 / 7 4 / 11 5 / 10 7 / 0 9 / 0
FILTER FACE AREA (Sq. Ft. / Qty. / Size) 2.14 / 1 / 14" x 22"
COMPRESSOR HERMETI C, QTY. = 1 (Type)
= Electrically Controlled Motor
Reciprocating Reciprocating
Scroll Scroll Scroll Scroll Scroll
CONTROL WIRING
THERMOSTAT
** = Minimum wire size of 18 AWG wire shuold be used for all field installed 24 volt wire.
PROGRAMABLE
THERMOSTAT ONLY
* = Only required on units with supplemental electric heat.
UNIT TERMINAL STRIP
**
R
G
*
W1
*
W2 W2
C
R
G
YY
W1
C
NOTE: HEAT ANTI CI PATOR SHOULD BE SET AT
0.25 AMPS FOR ALL MOD-
24 VOL T TRANSFORMER
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper operation after servicing.
1
(ECM)
1
3
REFER TO ELECTRICA L DATA
TABLES TO SIZE THE DISCON-
NECT SWITCH, WIRING &
OVERCURRENT PROTEC-
FIG. 2
- TYPICAL FIELD WIRING DIA G RAM
POWER WIRI NG
REFER TO ELECTRICA L DATA
TABLES TO SIZE THE DISCON-
NECT SWITCH, WIRING &
OVERCURRENT PROTEC-
4 Unitary Products Group
TABLE 4 -
530.46-N2Z
ELECTRICAL DATA (BASIC UNIT)
MAX. FUSE SIZE,
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANS-FORMER
MODEL
DPH
POWER SUPPLY
VOLT AGE
LIMITATIONS
COMPRESSOR
MIN. MAX. RLA LRA
COND .
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
018 208/230-1-60 187 253 7.1 48.0 1.1 2.6 12.5 15 15 .96 40 024 208/230-1-60 187 253 9.3 57.0 1.1 2.6 15.3 20 20 .96 40 030 208/230-1-60 187 253 15.0 72.5 1.1 2.6 22.5 30 30 .96 40 036 208/230-1-60 187 253 17.2 88.0 1.1 3.5 26.1 35 35 .96 40 042 208/230-1-60 187 253 20.0 104.0 1.1 3.5 29.6 40 40 .96 40 030 208/230-3-60 187 253 10.0 63.0 1.1 2.6 16.2 25 25 .96 75 036 208/230-3-60 187 253 11.4 77.0 1.1 3.5 18.9 25 25 .96 75 042 208/230-3-60 187 253 13.9 88.0 1.1 3.5 22.0 30 30 .96 75 030 460-3-60 414 504 5.0 31.0 0.6 1.4 8.3 15 15 .96 75 036 460-3-60 414 504 5.7 39.0 0.6 1.8 9.5 15 15 .96 75 042 460-3-60 414 504 6.4 44.0 0.6 1.8 10.4 15 15 .96 75 036 575-3-60 518 630 4.7 31.0 0.4 1.5 7.8 15 15 .96 75 042 575-3-60 518 630 5.4 34.0 0.4 1.5 8.7 15 15 .96 75 048 575-3-60 518 630 5.8 36.0 0.6 2.0 9.8 15 15 .96 75 060 575-3-60 518 630 6.4 40.0 0.6 2.8 11.4 15 15 .96 75
= Utilization Range “A” in accordance with ARI Standard 110. ➁ = Dual element, time delay type.
SIZE (VA)
Unitary Products Group 5
530.46-N2Z
TABLE 5 -
ELECTRICAL DATA (COOLING / ELECTRIC HEAT)
DPH
POWER SUPPLY
COMPRESSOR
COND .
MOTOR
RLA LRA MODEL NO.
FAN FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MODEL
018 208/230-1-60 9.0 48.0 1.1 2.6
024 208/230-1-60 11.2 60.0 1.1 2.6
030 208/230-1-60 12.0 73.0 1.1 2.6
036 208/230-1-60 17.3 94.0 1.1 3.5
042 208/230-1-60 20.5 120.0 1.1 3.5
030 208/230-3-60 10.0 63.0 1.1 2.6 036 208/230-3-60 10.9 78.0 1.1 3.5 042 208/230-3-60 14.1 110.0 1.1 3.5 030 460-3-60 5.0 31.0 0.6 1.4 036 460-3-60 5.8 40.0 0.6 1.8 042 460-3-60 7.1 54.0 0.6 1.8 036 575-3-60 4.5 32.0 0.4 1.5 042 575-3-60 5.8 44.0 0.4 1.5
048 575-3-60 5.8 36.0 0.6 2.0
060 575-3-60 6.4 40.0 0.6 2.8
= Dual element, time delay type.
= Standard circuit breakers may be used in Canada and on applications
over 60 amps where the heaters are separately fused.
ELECTRIC HEAT ACCESSORY
STAGE
2NH04500506 2NH0450070612
2NH04500506 2NH04500706 2NH04501006
2NH04500506 2NH04500706 2NH04501006 2NH04501506
2NH04500506 2NH04500706 2NH04501006 2NH04501506
2NH04500506 2NH04500706 2NH04501006 2NH04501506
1 2 2
1 2 2 2
1 2 2 2
1 2 2 2
2NH04501025 2NH0450152511
2NH04501025 2NH0450152511
2NH04501025 2NH0450152511
2NH04501046 2NH0450154611
2NH04501046 2NH0450154611
2NH04501046 2NH0450154611
2NH04501058 2NH0450155811
2NH04501058 2NH0450155811
2NH04501058 2NH04501558 2NH04502058 2NH04502558
2NH04501058 2NH04501558 2NH04502058 2NH04502558
1 1 2 2
1 1 2 2
MINIMUM
CIRCUIT
KW
3.8/5.0 *
5.6/7.5 *
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
7.5/10.0 *
11.3/15.0 *
7.5/10.0 *
11.3/15.0 *
7.5/10.0 *
11.3/15.0 *
10.0 **
15.0 **
10.0 **
15.0 **
10.0 **
15.0 **
10.0 ***
15.0 ***
10.0 ***
15.0 ***
10.0 ***
15.0 ***
20.0 ***
25.0 ***
10.0 ***
15.0 ***
20.0 ***
25.0 ***
= KW listed is for 240 volts, use this table for 208 or 230 volts.
*
= KW listed is for 480 volt s, use th is table for 460 volts .
**
= KW listed is for 600 volts, use thi s table for 575 volts.
***
ELECTRIC HEAT
CORRECTION
FACTORS
TOTAL AMPS
18.1/20.8
27.1/31.3
18.1/20.8
27.1/31.3
36.1/41.7
18.1/20.8
27.3/31.3
36.1/41.7
54.2/62.5
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
20.8/24.1
31.3/36.1
20.8/24.1
31.3/36.1
20.8/24.1
31.3/36.1
12.0
18.0
12.0
18.0
12.0
18.0
9.6
14.4
9.6
14.4
9.6
14.4
19.2
24.1
9.6
14.4
19.2
24.1
NOMINAL VOLTAGE VOLTAGE
AMPACITY
25.8/29.3
37.1/42.3
25.8/29.3
37.1/42.3
48.4/55.3
25.8/29.3
37.1/42.3
48.4/55.3
71.0/81.4
26.9/30.4
38.2/43.4
49.5/56.5
72.1/82.5
30.2/30.4
38.2/43.4
49.5/56.5
72.1/82.5
29.3/33.3
42.3/48.4
30.4/34.4
43.5/49.5
30.4/34.4
43.5/49.5
16.8
24.3
17.3
24.8
17.3
24.8
13.9
19.9
13.9
19.9
14.5
20.5
26.6
32.6
15.5
21.5
27.6
33.6
240 480 460 .92
600 575 .92
208 230
MAX.
FUSE
SIZE,
AMPS
30/30 40/45
30/30 40/45 50/60
30/30 40/45 50/60 80/90
35/40 40/45 50/60 80/90
40/40 50/50 50/60 80/90
30/35 45/50
35/35 45/50
35/35 45/50
20 25
20 25
20 25
15 20
15 20
15 25 30 35
20 25 30 35
HACR
BREAKER
KW CAP.
MULT IPLIER
MAX.
SIZE
30/30 40/45
30/30 40/45 50/60
30/30 40/45 50/60 80/90
35/40 40/45 50/60 80/90
40/40 50/50 50/60 80/90
30/35 45/50
35/35 45/50
35/35 45/50
20 25
20 25
20 25
15 20
15 20
15 25 30 35
20 25 30 35
.75 .92
6 Unitary Products Group
TABLE 6 -
OUTDOOR
TEMPERATURE
(F)
65 17.1 19.8 22.5 25.3 28.0 30.7 33.4 33.7 34.1 34.3 34.8 70 11.7 14.9 18.0 21.2 24.4 27.5 30.7 31.3 31.9 32.5 33.1 75 6.3 9.9 13.5 17.1 20.8 24.4 28.0 28.9 29.8 30.6 31.5 80 - - 9.0 13.1 17.2 21.2 25.3 26.4 27.6 28.7 29.9 85 - - - 9.0 13.6 18.1 22.6 24.0 25.4 26.8 28.3 90 - - - 6.8 10.2 13.6 17.0 19.4 21.9 24.3 26.8
95 ----6.89.011.314.818.321.825.3 100 ----5.37.08.812.616.420.324.1 105 ------6.210.414.618.722.9 110 -------8.212.717.221.7 115 -------6.010.815.720.5
530.46-N2Z
SUPERHEAT CHARGING TABLE FOR MODEL DAPH018
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE (F)
55 57 59 61 63 65 67 69 71 73 75
TABLE 7 -
OUTDOOR
TEMPERATURE
(F)
65 33.5 33.7 33.9 34.1 34.3 34.6 34.8 35.1 35.4 35.7 36.0
70 30.5 30.9 31.3 31.6 32.0 32.4 32.8 33.4 34.0 34.6 35.2
75 27.6 28.1 28.6 29.1 29.7 30.2 30.7 31.6 32.5 33.4 34.3
80 24.6 25.3 26.0 26.7 27.3 28.0 28.7 29.9 31.1 32.2 33.4
85 21.6 22.5 23.3 24.2 25.0 25.8 26.7 28.2 29.6 31.1 32.5
90 14.6 16.0 17.4 18.8 20.3 21.7 23.1 25.2 27.3 29.4 31.5
95 7.5 9.5 11.5 13.5 15.6 17.6 19.6 22.3 25.0 27.8 30.5 100 5.9 7.6 9.3 11.1 12.8 14.5 16.2 18.9 21.6 24.2 26.9 105 - 5.7 7.2 8.6 10.0 11.4 12.9 15.5 18.1 20.7 23.3 110 - - - 6.1 7.3 8.4 9.5 12.1 14.6 17.2 19.8 115 -----5.36.18.711.213.716.2
TABLE 8 -
OUTDOOR
TEMPERATURE
(F)
65 21.6 22.5 23.4 24.3 25.3 26.2 27.1 27.5 28.0 28.4 28.8
70 18.0 19.3 20.5 21.7 23.0 24.2 25.4 26.0 26.6 27.1 27.7
75 14.5 16.1 17.6 19.1 20.7 22.2 23.8 24.5 25.2 25.9 26.6
80 11.0 12.8 14.7 16.5 18.4 20.3 22.1 23.0 23.8 24.7 25.5
85 7.4 9.6 11.8 14.0 16.1 18.3 20.5 21.5 22.4 23.4 24.4
90 - 5.6 7.9 10.3 12.6 15.0 17.3 18.8 20.3 21.9 23.4
95 - - - 6.6 9.1 11.6 14.1 16.2 18.3 20.3 22.4 100 - - - 5.4 7.2 9.1 11.0 13.5 16.1 18.7 21.3 105 ----5.36.67.810.914.017.120.3 110 -------8.311.915.519.2 115 -------5.79.814.018.1
SUPERHEAT CHARGING TABLE FOR MODEL DAPH024
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE (F)
55 57 59 61 63 65 67 69 71 73 75
SUPERHEAT CHARGING TABLE FOR MODEL DAPH030
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE (F)
55 57 59 61 63 65 67 69 71 73 75
TABLE 9 -
OUTDOOR
TEMPERATURE
SUPERHEAT CHARGING TABLE FOR MODEL DAPH036
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
(F)
65 6.5 8.5 10.6 12.6 14.7 16.8 18.8 21.3 23.7 26.1 28.6
70 5.4 7.3 9.1 11.0 12.8 14.7 16.6 19.1 21.6 24.2 26.7
75 - 6.0 7.6 9.3 11.0 12.7 14.3 16.9 19.6 22.2 24.8
80 - - 6.2 7.7 9.1 10.6 12.1 14.8 17.5 20.2 22.9
85 - - - 6.0 7.3 8.5 9.8 12.6 15.4 18.2 21.1
90 - - - 5.4 6.5 7.5 8.6 11.6 14.5 17.4 20.4
95 ----5.66.57.410.513.616.619.7 100 -----5.56.39.112.014.917.7 105 ------5.17.810.413.115.7 110 -------6.48.911.313.7 115 -------5.17.39.511.8
55 57 59 61 63 65 67 69 71 73 75
INDOOR WB TEMPERATURE (F)
Unitary Products Group 7
530.46-N2Z
TABLE 10 -
OUTDOOR
TEMPERATURE
(F)
65 24.9 25.4 26.0 26.6 27.2 27.8 28.3 28.6 28.9 29.2 29.5 70 21.6 22.3 23.0 23.7 24.3 25.0 25.7 26.4 27.2 28.0 28.7 75 18.4 19.2 19.9 20.7 21.5 22.3 23.0 24.2 25.5 26.7 27.9 80 15.2 16.0 16.9 17.8 18.6 19.5 20.4 22.0 23.7 25.4 27.1 85 12.0 12.9 13.9 14.8 15.8 16.8 17.7 19.8 22.0 24.1 26.3 90 7.9 8.8 9.8 10.7 11.7 12.7 13.6 16.8 19.9 23.1 26.3
95 - - 5.7 6.6 7.6 8.6 9.5 13.7 17.9 22.1 26.3 100 - - - 5.6 6.4 7.2 8.0 11.7 15.4 19.1 22.8 105 ----5.35.96.69.812.916.119.3 110 ------5.17.810.513.115.8 115 -------5.88.010.212.3
SUPERHEAT CHARGING TABLE FOR MODEL DAPH042
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE (F)
55 57 59 61 63 65 67 69 71 73 75
TABLE 11 -
OUTDOOR
TEMPERATURE
(F)
65 27.6 27.8 28.0 28.1 28.3 28.5 28.7 29.2 29.1 30.3 30.8
70 23.3 223.8 24.3 24.8 25.4 25.9 26.4 27.2 28.0 28.8 29.6
75 19.0 19.8 20.7 21.5 22.4 23.3 24.1 25.2 26.2 27.3 28.3
80 14.7 15.9 17.0 18.2 19.4 20.6 21.4 23.1 24.5 25.8 2.1
85 10.4 11.9 13.4 14.9 16.5 18.0 19.5 21.1 22.7 24.3 25.9
90 6.8 8.3 9.8 11.3 12.9 14.4 15.9 18.2 20.4 22.7 25.0
95 - - 6.3 7.8 9.2 10.7 12.2 15.2 18.4 21.2 24.2 100 - - 5.1 6..4 7.7 8.9 10.2 12.7 15.1 17.6 20.0 105 - - - 5.0 6.1 7.2 8.2 10.1 12.0 13.9 15.8 110 -----5.46.37.68.910.311.6 115 -------5.15.96.67.4
SUPERHEAT CHARGING TABLE FOR MODEL DAPH048
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON
INDOOR WB TEMPERATURE (F)
55 57 59 61 63 65 67 69 71 73 75
8 Unitary Products Group
Loading...