Unitary products group BECB 090, BECB 120, BCCB 090, BCCB 120 Installation Instruction

INSTALLATION INSTRUCTION
SINGLE PACKAGE HEAT PUMPS
7-1/2 & 10 TON
Supersedes: 511.06-N2W (398)
511.06-N2Z (1298)
MODELS BCCB 090 & 120,
MODELS BECB090 & 120
(9 EER)
208/230/460 VOLT
MODELS ONLY
SAFETY CONSIDERATIONS
Due to system pressure, moving parts and electrical components, installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained, service personnel should install, repair, maintain or service this equipment.
Observe all precautions in the literature, on labels and tags accompanying the equipment whenever working on air conditioning equipment. Be sure to follow all other safety precautions that apply.
Wear safety g lasses and work gloves , and follow all safety codes. Use a quenching cloth and have a fire extinguisher available for all brazing operations.
GENERAL
Model BCB units are single package heat pumps designed for outdoor installation on a rooftop or a slab. Supplemental electric heaters ar e av ai la bl e as field-installed access ori es .
The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation.
The supplemental electric heaters have nickel-chrome elements and utilize single point power connection.
035-16199
208/230/575 V OLT MODELS ONLY
530.18-N3.8V - Motorized Outd oor Ai r Damp er Acc y.
530.18-N3.9V - Manual Outdoor Air D ampe r 0 -35 %
530.18-N3.10V - Manual Outdo or Air D ampe r 0 -10 0%
530.18-N3.5V - Fuse Block Access ory
Renewal Parts:
Refer to the Renew al Parts Manual for complete listin g of
replacement parts on this equipment.
All forms referenced in this ins tru ct io n ma y be orde red from :
Publications Distribution Center Unitary Products Group P.O. Box 1592, York, Pa. 17405
APPROVALS
Design certified by U.L. as follows:
1. For use as a heat pump on ly unit or a heat pump unit with supplemental electric heat.
2. For outdoor installation only.
3. For installation on combustible material.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on t he carrier’s freigh t bill. A sep arate request for inspection by the carrier’s agent should be made in writing. Refer to Form 50.15-NM for additional information.
REFERENCE
Additional information on the design, installation, operation and service of this equipment is available in the following reference forms:
530.18-N9.1V - Electric Heater Acce ssory
530.18-N3.2V - Economizer Accessory
Installer should pay particular attention to the words: make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that per­sonal injury and/or equipment damage may result if installation procedure is not handled properly.
THIS PRODUCT MUST BE INST ALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INST ALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
INCORRECT INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
NOTE, CAUTION
and
WARNING
CAUTION
WARNING
. Notes are intended to clari fy or
511.06-N2W
TABLE OF CONTENTS
General................................................................................1
Inspection.............................................................................1
Reference ............................................................................ 1
Approvals ............................................................................. 1
Nomenclature.......................................................................2
INSTALLATION
Limitations............................................................................ 3
Location ............................................................................... 3
Condensate Drainage Precaution ....................................... 3
Rigging and Handling .......................................................... 3
Clearances........................................................................... 3
Ductwork .............................................................................. 4
Filters ................................................................................... 4
Condensate Drain................................................................4
Service Access..................................................................... 4
Thermostat.................. ........ ........ ........ ........ ........ ........ ........ .4
Power and Control Wiring.................................................... 4
Electric Heaters....... .................. .. .. .. .................. .. .. .. .............4
Compressors......................... .. .. .. .................. .. .. .. .................4
OPERATION
Cooling System.................................................................. 10
Preliminary Operation Cooling........................................... 10
Cooling Sequence of Operation ........................................ 10
Heating Sequence of Operation........................................10
Heat Anticipator Setpoints ..................................................11
Checking Supply Air CFM............. .. .... .... .... .... .... .... .... .... ....11
Defrost Sequence of Operation ......................................... 12
Secure Owner’s Approval .................................................. 13
MAINTENANCE
Normal Maintenance..... .. .................. .. .. .. .................. .. .. .. ... 13
TABLES
No. Description Page
1 Unit Applicatio n Da ta............ .... .... .... .... .... .. 3
2 Electrical Data............................................. 5
3 Physical Data.............................................. 6
4 Point Loads........... .. .. .. .................. .. .. .. ........ 8
5 Supply Air Br Performance................... .... .. 9
6 Accessory Static Resistances .................... 9
7 Blower Motor and Drive Data ..................... 10
8 Heat Anticipator Setting.............................. 11
9 Blower Motor Pulley Adjustment................. 1 1
FIGURES
No. Description Page
1 Center of Gravity......................................... 3
2 Recommended Drain Piping....................... 4
3 Typical Field Wiring..................................... 5
4 Dimensions and Clearances...... .............. ... 7
5 Point Loads........... .. .. .. .................. .. .. .. ........ 8
6 Pressure Drop versus Supply Ai r CF M....... 11
7 Defrost Initia ti on Times....... .. .. .. .................. 12
8 Ambient Modified Time/Temp. Control........ 13
PRODUCT CATEGORY
B = Single Package Heat Pump (Air Cooled)
PRODUCT GENERATION
C = 3rd Generation D = 4th Generation E = 5th Generation
PRODUCT IDENTIFIER
CB = Heat Pump
2 Unitary Products Group
PRODUCT NOMENCLATURE
B C C B A
90 0- T
FACTORY INSTALLED
A = No Heat Installed
NOMINAL COOLING CAPACITY
090 = 7-1/2 Ton 120 = 10 Ton
VOLTAGE CODE
-T = 208/230-3-60
-W = 460-3-60
-X = 575-3-60
HEAT
INSTALLATION
LIMITATIONS
These units must be in stal led in accord ance wit h t he fo llow ing national and lo cal safety codes:
1. National Electrical Code ANSI/NFPA No. 70.
2. Local electr ic utility requirements.
3. Canadian Electrical Code C22.1
4. Canadian Installation Codes CAN1-B149. Refer to Table 1 for Unit Applic ation Data.
If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or the customer’s expense.
Size of unit for proposed install ation should be based on h eat loss/heat g ain calcul ation made according to the meth ods of Air Conditioning Co nt rac to rs of Am eri ca (ACCA).
51 1.06-N2W
OUTDOOR COIL CONDENSATE DRAINAGE PRECAUTION
Condensate will drain from the outdoor coil during the heating and defrost cycles. Normally this condensate may be allowed to drain directly onto the ground/roof. A gravel bed is recommended to prevent mud splashing.
WARNING:The unit should no t be ins talled in an are a where
mud or ice could cause personal injury. Remember that condensate will drip from the outdoor coil during heat and defrost cyc les and that thi s con­densate wi ll freeze when the tem perature of the
°
outdoor air is below 32
F.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any packaging unti l the unit is ne ar the place of installat ion. Rig t he unit by attaching chain or cable slings to the lifting holes provided in the base rai ls. Spre aders, who se length ex ceeds the largest di mension ac ross the uni t, the top of the unit.
be used acros s
MUST
TABLE 1
Min. / Max.*
Utilization range “A” in accordance with ARI Standard 110.
*
- UNIT APPLICATION DATA
Model BCH090 BCH120
Voltage
Variation
Wet Bulb Temperature (°F)
of Air on Indoor Coil,
Min. / Max.
Dry Bulb Temperature (°F)
of Air on Outdoor Coil,
Min. / Max.
208 / 230V 187 / 253
460V 414 / 506 575V 518 / 630
57 / 72 57 / 72
45 / 120 45 / 120
LOCATION
Use the fol lowing guidelin es to select a sui table location f or these units.
1. Unit is designed for outdoor installation on ly.
2. Outdoor coil must have an unlimited supply of ai r.
3. For ground level installation, use a level concrete slab with a minimum t hickness of 4 inch es. The length and width should be at least 6 inches greater than the unit base rails. Do not tie slab to the building foundation.
4. Roof structur e must be able to supp ort the weight of t he unit and its options and/or a ccesso ries. Uni t must be inst alled on a solid level r oof curb or appropriate angle iron frame.
CAUTION: I f a unit is to be inst alled on a roof curb or
5. Maintain level tolerance to 1/2" maximum across the entire length or width of the unit.
special fr ame ot her tha n a Y ORK ro of curb , gasketing must be applied to all surfaces that come in contact with the unit underside.
BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.
Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 54". Remove the nesting brackets from the four corners on top of
the unit. All screws that are removed when taking these brackets off must be repl ac ed on th e un it .
Refer to T a ble 3 for unit weigh ts and to Figure 1 f or approximate center of gravity.
DIM. 7-1/2 Ton 10 T on
A 32" 32-1/2" B 44-3/4" 44"
FIG. 1
- CENTER OF GRAVITY
CLEARANCES
All units req uire certain cle arances for prope r operation and service. Refer to Figure 4 for the clearances required for combustible construct ion, servic ing, and proper unit ope ration.
WARNING:Do not permit overhanging structures or shrubs to
obstruct outdoo r air disc ha rge outlet.
Unitary Products Group 3
511.06-N2W
DUCTWORK
Ductwork should be designed and sized according to the methods in Manu al Q of the Air Conditi oning Contractors of America (ACCA).
A closed return duct system shall be used. This shall not preclude u se of ec onom izers or out door fr esh air intak e. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise.
The supply and retu rn air duct syste ms should be design ed for the CFM and static requirements of the job. They should NOT be sized to matc h the dime nsions of the duct connect ions on the unit.
CAUTION: When fastenin g ductwork to si de duct flanges on
unit, insert screws through duct flanges only. DO NOT insert screw s thr o ug h casing.
Outdoor ductwork must be insulated and wat er­proofed.
Refer to Figur e 4 for inform ation conc erning side and bottom supply and return air duct openings.
FILTERS
2" filters are supplied with each unit. 1" replacement filters may be used with no modification to the filter racks. Fi lters must always be in stal le d a he ad of th e i nd oo r coil and mus t be kep t clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 3.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the 3/4" female co nnection on the unit t o spill into an open drain.
NOTE: The condensate drain line MUST be trapped to provide
proper drainage. See Figure 2.
THERMOSTAT
The room thermostat should be located on an inside wall approximat ely 56" ab ove the fl oor where it will no t be subjec t to drafts, sun exposure or heat from electrical fixtures or appliances. F ollow manufa cturer ’s instructions enclosed wit h thermostat for general installation procedure. Color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. Eight conductors are required.
The subbase on the low voltage thermostat includes an “Emergency Heat” position on the system switch and a pilot light. In the “Emergency Heat” position, the thermostat will provide electric resistance heat only. The compressors will not run. The p ilot lig ht wi ll i ndic ate that t he s witch is on “ EM H T”. Nine conductors are requ ire d fo r thi s ap pl ic at ion.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the National E lectrica l Code, AN SI / NFPA (lates t edition ) and/or local ordinances. The unit must be electrically grounded in accordance with N.E.C . ANSI / NF PA (latest edit ion) or lo cal codes. Voltage tolera nces which must be main tained at the compressor t erminals during star ting and running conditi ons are indicate d on the unit Rating Plate and Table 1.
The internal wiring harness furnished with this unit is an integral part of a UL and C.G .A. desi gn certif ied unit . Field al teratio n to comply with electrical codes should not be required.
A disconnect switch shou ld b e fi eld p rovid ed fo r th e unit. The switch must be separate from all other circuits. Refer to Figure 4 for inst alla tion loc atio ns. I f any of th e wir e sup plie d wi th th e unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Electrica l line must be sized pro perly to carr y the load. USE COPPER CONDUCTORS ONL Y. Each unit must be wired wi th a separate branch ci rcuit fe d direct ly from t he mete r panel a nd properly fused.
CAUTION: When connecting electrical power and control wir-
ing to the un it, w ate rpro of ty pe co nnec tor s MU ST BE USED so that water or moisture cannot be drawn into the unit during normal operati on. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch.
FIG. 2 -
RECOMMENDED DRAIN PIPING
SERVICE ACCESS
Access to all serviceable components is provided by five removable panels:
Compressor co mp ar t ment
Heater compartment
Blower compartment
Main control box
Filter compart me n t
Refer to Figu re 4 for location of these access panels.
4 Unitary Products Group
Refer to Figure 3 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Refer to Table 2 for electrical data.
ELECTRIC HEATERS
Supplemental electric hea ters are availa ble as field-in stalled accessories. Refer to Form 530.18-N9.1V for accessory instruction. These UL and C.G.A. approved heaters are located within the c entral compartment of the unit (see Fig ure 4 for access panel) with the heating elements extending into the supply air chamber. All accessory heater kits contain a single point power kit.
Fuses are su pplied, where required, wi th the accessor y kits. Some KW sizes require fuses and others do not. Refer to the accessory instruction for electrical data.
COMPRESSORS
The compressors are mounted on springs which have been tightened down for shipment only. After the unit is installed, back out th e compr essor b olts unti l the sleeve clears t he top grommet.
51 1.06-N2W
TABLE 2
MODEL
NOTES: 1. Dual eleme nt , tim e de lay typ e.
2. Maximum HACR breaker of the same AMP size is applicable, *Dual numbers indicate amps for compre ssor #1 / #2 resp ect ively.
- ELECTRICAL DATA
POWER SUPPLY
208/230-3-60
090
120
460-3-60 575-3-60
208/230-3-60
460-3-60 575-3-60
COMPRESSOR
(#1 and #2)*
RLA
EACH
14.1
LRA
EACH
130
7.1
5.8
16.7/17.3
150
9.6
8.3
64 52
73 62
OUTDOOR
FAN MOTOR, (#1 & #2)
FLA
EACH
2.3
1.3
1.3
3.5
2.5
2.5
SUPPL Y
AIR
BLOWER
MOTOR,
FLA
TOTAL
UNIT
AMPACITY,
AMPS
MAX.
FUSE
SIZE,
AMPS
1,2
1.5HP 2HP 3HP 1.5HP 2HP 3HP 1.5HP 2HP 3HP
5.7
2.6
2.1
42.0
7.5
3.4
2.7
-
-
-
7.5
3.4
2.7
-
-
-
10.6
4.8
3.9
21.1
17.7
43.8
21.9
18.3
52.8
-
30.0
-
26.5
-
-
-
-
55.9
31.4
27.7
50 25 20
-
-
-
50 25 20
70 35 30
-
-
-
70 40 35
FIG. 3
- TYPICAL FIELD WIRING
Unitary Products Group 5
511.06-N2W
TABLE 3
- PHYSICAL DATA
MODEL
SUPPLY AIR
BLOWER
INDOOR
COIL
OUTDOOR
FANS
(Two Per Unit)
OUTDOOR
COIL
AIR
FILTERS
(SEE NOTE)
CHARGE
NOTE: Filter racks are adapte d fo r 1" or 2" thick filt er s.
CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 12 15 x 12 FAN MOTOR HP (STANDARD) 1-1/2 2 FAN MOTO R HP (ALTERNATE) 2 3 ROWS DEEP 3 3 FINS PER INCH 15 13 FACE ARE A (Sq. Ft.) 7.8 13.4 PROPELLER DIA. (in.) 24 ea. 24 ea. FAN MOT O R HP 1/2 ea. 3/4 ea. NOM. CFM TOTAL 2900 ea. 4400 ea. ROWS DEEP 2 2 FINS PER INCH 13 15 FACE ARE A (Sq. Ft.) 20.0 29.3 QUANTITY PER UNIT (12" X 24" X 2") 2 ­QUANTITY PER UNIT (16" X 24" X 2") 2 3 QUANTITY PER UNIT (18" X 24" X 2") - 2 TOT AL FACE AREA (sq. ft.) 9.3 14.0 REFRIGERANT 22
(lbs./oz.)
BASIC UNIT
Electric Heat (Nominal KW)
Economizer 77 Motorized
Outdoor Air Damper
Roof Mounting Curb 155
BCB
090 120
SYSTEM NO. 1 9/0 11/8 SYSTEM NO. 2 9/0 13/8
WEIGHTS (LBS)
7-1/2 Ton 1050
10 Ton 1400
ACCESSORIES
9 KW 19 18 KW 24 24 KW 27 36 KW 30 54 KW 37
97
6 Unitary Products Group
51 1.06-N2W
RETURN AIR
SUPPL Y AIR
OUTDOOR AIR
OUTDOOR AIR (Economizer)
All dimensions are in inches. They are sub­ject to change without notice. Certified di­mensions will be provided upon request.
UTILITIES ENTRY DATA
HOLE
Knockouts in the bottom of the unit can be located by the slice in the
*
insulation.
KNOCKOUT
SIZE
(DIA.)
A
3/4" 7/8" Bottom*
B2"
Control Wiring
Power Wiring (Side or Bottom)*
USED FOR
Side
DUCT COVERS - Units are shipped with all air duct openings covered. For
side duct applications;
1. Remove and discard the supply and return air duct covers.
2. Connect ductwork to duct flanges on the rear of the unit. For
bottom duct applications;
1. Remove the side supply and return air duct covers to gain access to the bottom supply and return air duct covers.
2. Remove and discard the bottom duct covers.
3. Replace the side duct covers.
E C O N O M IZ E R R A IN H O O D
27"
3-3/4"
DIM "A "
28
ECONOMIZER
31
MO TO RIZED DAMPER
31
M ANUAL DAMPER 0-100%
24
M ANUAL DAMPER 0-35%
Front 24" Back
Left Side (Filter Access) Right Side (Cond. Coil) 24"
Below Unit Above Unit
NOTE: Units and ductwork are approved for zero clearance to combustible materials when equipped with electric he at er s.
1
Units may be installed on combustible flo ors made fr om wood or class A, B or C
roof covering material.
2
Units must be installed oudo or s. Ove rhan gin g str uct ur es or shru bs sho uld not
obstruct outdoor air disch ar ge out let .
3/4" CONDENSATE DRAIN (M UST BE TRAPPED)
A
MINIMUM CLEARANCES
12" (Less Economizer) 36" (With Economizer Outdoor Air Damper)
24" (Less Economizer) 54" (With Economizer)
1
2
20"
72" with 36" maximum Horizontal Overhang (For Outdoor Air Discharge)
(B) POW ER W IRING E N T R Y
71"
L.H. END VIEW
29-5/8"
7"
3-1/2"
4-1/2"
FIG. 4
- DIMENSIONS & CLEARANCES (7-1/2 & 10 TON)
Unitary Products Group 7
511.06-N2W
B
C
A
FIG. 5
TABLE 4
D
4 POINT LOADS
- FOUR AND SIX POINT LOADS
- FOUR AND SIX POINT LOADS (LBS)
UNIT
BCB
090 1,154 231 281 353 289 120 1,504 301 355 460 388
TOTAL A B C D
FRONT
NOTE: These weights are with economizer and 36 kW electric heat.
UNIT
BCB
090 1,154 154 188 211 235 193 173 120 1,504 200 237 272 307 259 229
TOTAL A B C D E F
6 - POINT LOADS (LBS)
A
4 - POINT LOADS (LBS)
F
B
6 POINT LOADS
E
D
C
FRONT
NOTE: These weights are with economizer and 24 kW electric heat.
CENTER OF GRAVITY
8 Unitary Products Group
51 1.06-N2W
TABLE 5 MODEL BCB090
BLOWER
SPEED,
MODEL BCB090
BLOWER
SPEED,
MODEL BCB120
BLOWER
SPEED,
- SUPPL Y AIR BLOWER PERFORMANCE
(7-1/2 & 10 TON)
- (SIDE DUCT APPLICATIONS)
CFM
RPM
975 0.93 1.16 1.08 0.79 1.27 1.18 0.53 1.45 1.35 0.29 1.65 1.54 - - ­1025 1.08 1.21 1.13 0.95 1.34 1.25 0.68 1.54 1.44 0.42 1.75 1.63 0.17 1.97 1.84 1070 1.22 1.32 1.23 1.08 1.46 1.36 0.83 1.68 1.57 0.58 1.89 1.76 0.32 2.11 1.97 1130 1.41 1.43 1.33 1.29 1.57 1.46 1.02 1.83 1.71 0.77 2.04 1.90 - - ­1175 1.61 1.51 1.41 1.49 1.67 1.56 1.23 1.92 1.79 0.96 2.18 2.03 - - ­1220 1.78 1.66 1.55 1.66 1.81 1.69 1.39 2.10 1.96 ------
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
2250 2550 3000 3400 3750
- (BOTTOM DUCT APPLICATIONS)
CFM
RPM
975 0.86 1.16 1.08 0.70 1.27 1.18 0.40 1.45 1.35 0.12 1.65 1.54 - - ­1025 1.01 1.21 1.13 0.86 1.34 1.25 0.55 1.54 1.44 0.25 1.75 1.63 - - ­1070 1.15 1.32 1.23 0.99 1.46 1.36 0.70 1.68 1.57 0.41 1.89 1.76 0.12 2.11 1.97 1 130 1.34 1.43 1.33 1.20 1.57 1.46 0.89 1.83 1.71 0.60 2.04 1.90 - - ­1 175 1.54 1.51 1.41 1.40 1.67 1.56 1.10 1.92 1.79 0.79 2.18 2.03 - - ­1220 1.71 1.66 1.55 1.57 1.81 1.69 1.26 2.10 1.96 - - - - - -
2250 2550 3000 3400 3750
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
- (SIDE DUCT APPLICATIONS)
CFM
RPM
860 1.14 1.40 1.31 0.98 1.58 1.48 0.77 1.80 1.68 0.53 2.05 1.91 0.25 2.31 2.15 915 1.32 1.55 1.45 1.18 1.76 1.64 0.95 1.98 1.85 0.72 2.23 2.08 0.49 2.48 2.31
950 1.51 1.68 1.57 1.37 1.91 1.78 1.15 2.14 2.00 0.91 2.43 2.27 0.67 2.72 2.54 1000 1.69 1.83 1.71 1.57 2.07 1.93 1.35 2.33 2.17 1.14 2.62 2.45 0.92 2.91 2.72 1050 1.89 1.98 1.84 1.78 2.25 2.10 1.57 2.55 2.37 1.35 2.86 2.67 1.12 3.17 2.96 1090 2.08 2.12 1.97 1.97 2.41 2.24 1.78 2.72 2.54 1.55 3.06 2.86 - - -
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
3000 3500 4000 4500 5000
MODEL BCB120
BLOWER
SPEED,
RPM
860 1.01 1.40 1.31 0.80 1.58 1.48 0.54 1.80 1.68 0.23 2.05 1.9114 - - -
915 1.19 1.55 1.45 1.00 1.76 1.64 0.72 1.98 1.85 0.42 2.23 2.08 0.13 2.48 2.31
950 1.38 1.68 1.57 1.19 1.91 1.78 0.92 2.14 2.00 0.61 2.43 2.27 0.31 2.72 2.54 1000 1.56 1.83 1.71 1.39 2.07 1.93 1.12 2.33 2.17 0.84 2.62 2.45 0.56 2.91 2.72 1050 1.76 1.98 1.84 1.60 2.25 2.10 1.34 2.55 2.37 1.05 2.86 2.67 0.76 3.17 2.96 1090 1.95 2.12 1.97 1.79 2.41 2.24 1.55 2.72 2.54 1.25 3.06 2.86 - - -
NOTE: Blower performance includes a wet indoor coil and 2" filters. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. Refer to the Accssory Static ResistancesTable for the resistance of the unit accessories.
TABLE 6
Electric Heaters
- ACCESSORY ST ATIC RESISTANCES*
DESCRIPTION
Economizer 0.02 0.02 0.03 0.05
- (BOTTOM DUCT APPLICATIONS)
CFM
3000 3500 4000 4500 5000
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
= Larger Horsepower Alternate Motor Required.
EXTERNAL STATIC PRESSURE DROP - RESISTANCE, IWG
CFM
2250 3000 4000 5000
1
99 KW
18 KW 24 KW 0.06 0.12 0.21 0.33 36 KW 0.07 0.13 0.23 0.35
2
54 KW
0.06 0.11 0.20 0.31
- 0.15 0.26 0.40
*Deduct these resistance values from the available external static pressure shown in the respective Supply Air Blower Performance Table.
1
9 KW Heater is only available on
7-1/2 Ton Units.
2
54 KW Heater is only available on
10 Ton Units.
Unitary Products Group 9
511.06-N2W
TABLE 7
BASIC
BCB090 975-1220 BCB120 860-1090
* All motors are 1750 RPM, have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in th e moving air, upstream of any heating device.
- BLOWER MOTOR AND DRIVE DAT A
MOTOR*
1.20 56 82.0 3.4 - 4.4 7/8 6.2 1 50.3 A49 1
1.20 56 82.0 3.4 - 4.4 7/8 7.0 1 57.3 A56 1
UNIT
BLOWER
RANGE
(RPM)
HP
1-1/2
2 2
3
SERVICE
FACTOR
FRAME
SIZE
EFFICIENCY
(%)
ADJUSTABLE
MOTOR PULLEY
PITCH
DIA. (IN.)
BORE
(IN.)
FIXED
BLOWER PULLEY
PITCH
DIA. (IN.)
BORE
(IN.)
PITCH
LENGTH
(IN.)
BEL TS
DESIG-
NATION
OPERATION
COOLING SYSTEM
The unit has an air-co oled conden ser and i s factory-c harged with Refrigerant-22.
The compressors are hermetically sealed, internally sprung and mounted to the base with rubber in sulated hold-dow n bolts.
The compre ssors also have inh erent (internal) prot ection. If there is an abnormal temperature rise in a compressor, the protector will open to shut down the compressor.
PRELIMINARY OPERATION COOLING
After installation has been completed, energize the crankcase heaters for at le as t fou r ho urs be fo r e o per at in g u nit. A fter t hi s initial warm-up, the compressors should be given three false starts (ener g iz ed ju st lo ng en ou gh to ma ke a f ew re vo lu ti on s) with 5-7 minutes delay between each start before being put into full time service.
NOTE: Prior to each coolin g season, the cran kcase heaters
must be energized at least 10 hours before system is put into operation.
After the t hermostat is satisfied and opens, all components likewise stop simultaneously .
The reversing valve is energi zed thru th e “Y1” circuit when the subbase is in the co ol ing mode.
The suction line freezestat will cut the compressors out when the suction line temperature drops below 26°F. T his is an automatic reset device.
HEATING SEQUENCE OF OPERATION
The following sequence of operation is based on using a standard YORK heat pump two-stage heating/two-stage cooling thermostat/subbase. Economizer (if supplied) operation is not allowed in the heating mode - howeve r the minimum position does operate.
FIRST STAGE HEAT When the thermostat calls for “heating”, the low voltage control
circuit from “R” to “G” and “W1" (wiring sche matic) is completed to energize the compressors, outdoor fan motors and blower motor (if subbase i s set on auto) simu ltaneously . If the subba se has the indoor fan set on ”on" t he mo tor wil l run a ll of the t ime.
QTY
COOLING SEQUENCE OF OPERATION
When the thermostat calls for “first-stage” cooling, the low voltage control circuit from “R” to “G” and “Y1" (wiring schematic) is com pleted to energiz e compressor #1 an d blower motor simultaneously.
When the thermostat calls for “2nd-stage” cooling, the low voltage control circuit from “R” to “Y2" is completed t o energize compressor #2 and co nd en se r fan motor #2.
10 Unitary Products Group
SECOND STAGE HEAT If the compressors alone can not satisfy the heating
requirement s, second stage hea t will ener gize all th e electri c heat (if supplied) thru the “W2" circuit.
NOTE: On 10 ton units with 54KW heaters, only 36KW of
electric heat can be simultaneously energized with mechanical heat in g. The full 54KW operates in eme r­gency heat mode on ly.
HEA T ANT ICIPATOR SETPOINT S
It is important th at the anticipator setpoi nt b e correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the co rrec t setpoi nt wi ll give shorter “ON” c ycles and may result in the lowering of the temperature within the conditioned space. Refer to Table 8 for the required heat anticipator setting.
TABLE 8
- HEA T ANTICIPA T OR SETT ING
HEATER
KW
9 18 24 36 54
9 18 24 36 54
9 18 24 36 54
VOLTAGE
208/230-3-60
460-3-60
575-3-60
SETTING, AMPS
TH1
(Compr.)
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
1.10
TH2
(Suppl. Ht.)
0.40
0.90
0.90
0.90
0.90
0.40
0.80
0.80
0.80
0.45
0.40
0.80
0.80
0.80
0.45
51 1.06-N2W
NOTE: The tubes must be inserted and held in a position
perpendicu lar to the a ir flo w so th at vel ocity pres­sure will not affect the static pressure readings.
3. Using an inclin ed manomete r, determine the pressure d rop across a d ry indoor coil. S ince the m oisture on an indoor coil may vary greatly, measuring the pressure drop across a wet coil u nder field co nditions would be inaccurate. To assure a dr y coil, the co mpres sors sh ould be deac tiva ted while the test is being run.
4. Knowing the pressure drop acr oss a dry coil, the actual CFM through the unit can be determined from the curve in Figure 10.
WARNING:Failure to properly adjust the total system air quan-
tity can result in extensive blower damage.
CHECKING SUPPLY AIR CFM
The RPM of the supply air blower will depend on the required CFM, the unit acc essories and th e static resistance s of both the supply and the return air duct systems. With this information, the RPM for the supply air blower can be determined from the blower performance data in Table 4.
Knowing the r equired b lower RPM and the bl ower moto r HP, the setting (t ur ns op en ) f or t he su pply air motor pu ll ey ca n b e determined from Table 9.
TABLE 9 -
SUPPLY AIR B LOW ER MOTOR PULLEY
ADJUSTMENT
TURNS
OPEN*
5 975 860 4 1024 906 3 1073 952 2 1122 998 1 1171 1044 0 1220 1090
BELT DRIVE BLOWER All units have belt drive single-speed blower motors. The
variable pi tch pulley on t he blower moto r can be adjusted to obtain the desired supply air CFM. Refer to Table 6 for blower motor and drive data.
Start the supply air blower motor. Adjust the resistances in both the supply and the return ai r duct sy stems to bal ance the a ir distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other tha n th e equipment installer.
T o che ck the supply air C FM after the initial bala ncing has be en completed:
BLOWER DRIVE RANGE (RPM)
BCB090 BCB120
FIG. 6 -
PRESSURE DROP ACROSS A DRY INDOOR
COIL VS SU P PLY AIR CFM
1. Remove two dot plugs from t he filter access and the blower access pane ls as shown in Figure 4.
2. Insert at least 8" of 1/4 inch tubing into each of these holes for sufficient penetra tion into the air f low on both sides of the indoor coil.
Unitary Products Group 11
511.06-N2W
DEFROST SEQUENCE OF OPERATION
LOCKOUT CONTROL
These heat pumps have a unique “ambient modified” time-temperature defrost co ntrol that automati cally adjusts to changes in the outdoor temperature. The defrost control will shorten the defrost initiation time periods above 35°F and will extend the defrost initiation time periods below 35°F. The control is factory set to defrost at 110 minutes (T3), but it can be field adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity.
The curve in Figure 7 shows how defrost initiation times are automatically compensated for changes in outdoor temperature.
EXAMPLE: If the timer is factory set on p in T -3 (110 minutes 35°F outdoor) an d t he outd oo r te mper a tu re c li mb s t o 45°, the time initiation cycle will decrease to every 100 minutes.
If the outdoor temperature drops to 10°F where ice is less li kely to form, the 110 minute interval will extend to every 150 minutes.
Two requirements must be met before a defrost cycle can be initiated.
1. The defrost tim e cy cl e mu st be complete.
2.
The liquid li ne temperature must be less than 28°F.
Defrost will terminate when the liquid line sensor reaches or after 10 minutes. If both or just one circuit defrosts, electric heat is energized.
The defrost ti me cy cl e w i ll r es ta rt 1 0 m in ut es af te r th e st art of the defrost cycle even though the liquid sensor terminated defrost after 3 minu te s.
During trou bleshooting, the defrost tim e can be reduced to 20 seconds by shorting out the SW1 test pins on the module. The pins are 1/2" long, 3/16" apart and are mounted on a white base. See Figure 10.
55°F
Any one of four conditions will put the system into a lock-out condition durin g th e he ating or cooling mode:
1.
The discharge line temperature reaches 255°F (215°F reset) or,
2. The discharge pressure reaches 398 PSIG (310 PSIG reset) or,
3.
The suction line freezestat equals 26°F (38°F reset) or,
4. The low-pressure cut-out equals 7 PSIG (22 PSIG reset).
A lock-out will energize the emergency heat light on the
at
thermostat and the red LED light on the unit relay board. Turning the therm ostat switch to “Off” then back to “On ”, will reset the syst em.
NOTICE TO OWNER: If a lockou t occurs, check f or the following prob lems before
calling a serviceman:
1. Dirty filters.
2. Snow accumulation.
3. Leaf or debris bloc ka ge .
After eliminating the problem, attempt to restart the system as follows:
turn the system switch on the thermostat to its “OFF” position for 10 seconds.
turn it back to its original position.
If the unit doesn’t start, call a serviceman. NOTE: Models with an anti-recycle accessory will have a
5-minute delay be fo re st arting.
FIG. 7 -
12 Unitary Products Group
DEFROST INITIATION TIMES
T2 - 80 MINUTE SETTING
T3 - 110 MINUTE SETTING (Factory Set Point)
SHORTING PEGS TO OVERRIDE TIMER FOR SERVICE
MOVABLE JUMPER WIRE TO CHANGE DEFROST TIMER
FIG. 8
- AMBIENT MODIFIED TIME/TEMPERATURE CONTROL
51 1.06-N2W
T1 - 50 MINUTE SETTING
SECURE OWNER’S APPROVAL
:
When the system is fu nc ti on in g properly , secure the owner’s approval. Show hi m the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust tem­perature settings within the limitations of the system.
MAINTENANCE
NORMAL MAINTENANCE
CAUTION: Prior to any of the following maintenance proce-
dures, shut off all power to the unit to prevent personal injury.
FILTERS - Inspect once a month. Repl ac e di sp os ab le or clean permanent type as necessary. DO NOT replace permanent type with disposab le .
MOTORS - Indoor fan and outdoor fan motors are permanently lubricated and require no maintenance.
OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil s urface or ot her parts in th e air circuit. Cleani ng should be as oft en as necessary to keep coil clean. Use a b rush, vacuum cleaner attachment, or other suitable means. If water is used to clea n co il, be s ure po wer t o the un it is shut off prior to cleaning.
NOTE: Exercise care when clea ning the coil so that the coi l fins
are not damage d. Do not permit the outdoor air discha rge to be obstru cted
by overhanging structures of shrubs.
Unitary Products Group 13
511.06-N2W
14 Unitary Products Group
511.06-N2W
Unitary Products Group 15
Supersedes: 511.06 (398) Subject to change without notice. Printed in U.S.A. Copyright  by Unitary Products Gro up 19 98 . All r i gh ts rese rve d.
Unitary Products Group
5005 York Drive
Norman Oklahoma 73069
Code: SBL, F
511. 06-N2Z
Loading...