Unitary products group 1SP0452, 1SP0451, 1SP0450 Installation Instructions Manual

035-16650-001-A-0202
ACCESSORY KIT INSTALLATION INSTRUCTIONS
SUPPLY AIR PLENUM ACCESSORY
MODELS, 1SP0450, 1SP0451, 1SP045
FOR 5 THRU 15 TON SPLIT SYSTEM INDOOR UNITS AND
7-1/2 THRU 15 TON SPLIT-SYS TEM HEAT PUMP INDOOR UNITS
TABLE 1: PLENUM ACCESSORY REFERENCE
PLENUM ACCESSORY MODEL # INDOOR UNIT MODEL #
1SP0450 K*EU060 K*BU060
1SP0451
K*EU090,120 K*ES120 F*EH090,120 K*BU090,120 K*BS120 F*HP*90,120
LA090 FA090 LF-07 FF-07
K*EU180 F*EH180 K*BU180 F*HP*180
1SP0452
LA120 FA120 LF-10 FF-10
GENERAL
Each plenum is fully insulated and finished to match the exte­rior of the indoor unit. All joints are gasketed to provide air tight seals.
These accessories can be applied with either vertical or hori­zontal units that will be located in the conditioned space. They are designed for “free blow” operation and should never be applied with supply air ductwork.
Their double deflection metal grilles can be adjusted to vary the throw, spread and drop of the supply air per Table 2.
The Model 1SP0452 plenum accessory has knockouts for both the power and the control wiring and these knockouts will always be used because all of the field wiring must be routed through the plenum panel.
1SP0450 - Two Sect ion Grille 1SP0451 -Shown 1SP0452 - Five Section Grille
INSTALLATION
SUPPLY AIR PLENUM ACCESSORY MODEL 1SP0450 SUPPLY AIR PLENUM ACCESSORY MODEL 1SP0451
This accessory consists of 5 panels, a support angle and all screws necessary for assembling the plenum and for securing it to the unit.
For front air discharge on a vertical unit, assemble the panels as shown in Figure 1, using the No. 10 x 1-1/4" tapping screws. Attach the support angle to the bottom of the plenum with the No. 10 x 1/2" tappingscrews.Positionthe plenum on top of the unit. Drill 5/32" holes through the unit cabinet using the holes in the mounting flange and the support angle as templates. Secure the plenum to the unit with the No. 10 x 1/2" tapping screws.
NOTE: Electric Heat is not U.L. approved with the
Supply Plenum Accessory.
Unitary Products Group
035-16650-001-A-0202
L
S
REAR PANEL
Mounting Flange (Part of Rear Panel)
(2) END PANELS
1/2" Ref.
SUPPORT ANGLE
TOP PANEL
GRILLE PANE
BASIC UNIT
FIGURE 1 : PLENUM ACCESSORY MODELS 1SP0450
& 1SP0451 (VERTICAL UNIT WITH FRONT AND REAR AIR DISCHARGE)
For rear airdischarge on a vertical unit, assembly and mount­ing of plenum shall be the same as outlined above except the plenum must be positioned with the grille panel overhanging the rear of the unit.
For horizontal air discharge on a horizontal unit, assemble the panels as shown in Figure 2, using the No. 10 x 1-1/4" tapping screws. Attachthe support angles shown with the No. 10 X 1/2" tapping screws.
SUPPORT ANGLE
(2) END PANELS
TOP PANEL (Top for Vertical Unit)
Position the plenum on top of the unit. Remove one of the end panels from the plenum for access to the flanges inside. Drill 5/32" holes through the unit cabinet using the holes in the plenum flanges as templates. Secure the plenum to the unit with the No. 10 x 1/2" tapping screws.
NOTE: The other end panel may be removed for easy
access to the flanges on the opposite end of the plenum.
WIDE TOP PANEL
GRILLE PANEL
REAR PANEL
BASIC UNIT
FIGURE 3 : PLENUM ACCESSORY MODELS 1SP0452
(VERTICAL UNIT WITH FRONT OR REAR AIR DISCHARGE)
For rear air discharge on a vertical unit, rotate the blower sec­tion 180° (end to end)before installing the plenum as outlined above.
For horizontal air discharge on a horizontal unit, assemble the panels as shown in Figure 4 using the No. 10 x 1" tapping screws.
NARROW TOP PANEL
(2) END PANEL
BASIC UNIT
MOUNTING FLANGE (Part of Bottom Panel)
BOTTOM PANEL (Rear for Vertical Unit)
1/2" Ref.
FRONT PANEL (Narrow Top Panel for Vertical Unit)
GRILLE PANEL
TOP PANEL (Rear for Vertical unit)
BASIC UNIT
(2) END PANELS
FIGURE 2 : PLENUM ACCESSORY MODELS 1SP0450
&1SP0451 (HORIZONTAL UNIT WITH HORIZONTAL AIR DISCHARGE)
Position the plenum over the supply air opening and secure to the unit per the same procedure as outlined above for a vertical installation.
SUPPLY AIR PLENUM ACCESSORY MODEL 1SP0452
This accessory consists of 6 panels and all the screws neces­sary for assembling the plenum and for securing it to the unit.
For front air discharge on a vertical unit, assemblethe panels
GRILLE PANEL
BOTTOM PANEL (Wide Top Panel for Vertical Unit)
FIGURE 4 : PLENUM ACCESSORY MODEL 1SP0452
(HORIZONTAL UNIT WITH HORIZONTAL AIR DISCHARGE)
Position the plenum over the supply air opening and secure to unit per the same procedure as outlined above for a verti­cal installation.
as shown in Figure 3 using the No. 10 x 1" tapping screws.