The instrument shall be designed according to safety standard of Safety Requirements for
Electronic Measurement Products (IEC61010-1). The manual includes guaranteeing safety
status of instruments for safe use, warnings and safety statutes which must be executed by
users. Please read following instructions before use:
LCD will display warning symbol if measured voltage exceeds AC 30V. Be sure to operate
carefully and finger also cannot longer than testing pen.
It is not allowed to measure voltage which is higher than permissible input value.
Please inspect instrument and testing pen before use. Measurement is not allowed under
following circumstances: Nude testing pen, damaged shell without LCD.
It is not allowed to operate the instrument for wet surface or hand of operator.
It is not allowed to open cell cover during measurement.
Guarantee power off for instruments when opening cell cover.
Instruments cannot meet safety standards until use with testing pen together. Be sure to
replace testing pen with the same model and electric dimension if testing pen shall be
replaced due to damage.
Instruments cannot be exposed in wet locations with strong light, high temperature.
Please clean instrument shell by wet cloth or cleaner.
Please store after drying when instrument is wet.
Warning
Please read the operation manual especially safety content carefully before using instruments!
12
Safety Mark
Please refer to manual for important safety marks.
HV danger
Grounding
Duplex insulation (for Class II safety equipment)
Battery under-voltage
+
2Characteristics
UT240 series of digital three-phase forcipiform power/harmonic meter is a portable intelligent
power/harmonic measuring instrument. It has integrated functions such as ampere meter,
voltmeter, power measurement instrument and harmonic analysis meter, etc. With powerful
measurement and data treatment software, instrument consists of voltage, current, power and
harmonic channels and micro single-chip machine system. It can be used for measurement,
calculation & display of parameters such as voltage, current, active power, apparent power,
inactive power, power factor, phase location angle, electric energy statistics, frequency, phase
sequence, total harmonic distortion rate and harmonic components, etc with stable performance
and convenient operation. It is especially suitable to measurement & repair of site power
equipment and power supply wires as well as evaluation of electric energy quality of power grid.
With portable forcipiform structure, the instrument has little volume and light weight. User can
carry with it to facilitate measurement. Such series of digital forcipiform three-phase power/
harmonic meters are also your ideal choice for three-phase power measurement and quality an
alysis of electric energy.
Please design and produce according to international standard of EN61010-1 and international
safety code of EN61010-2-032 by abiding by safety standard of duplex insulation of CAT
600V strictly.
Adopt power measurement system which consists of chips by new high-performance and
large-capacity chip microprocessor and the latest special high-precision chips used for power
measurement with high integration level and reliable performance.T hey c an b e u sed t o r ealize
multiplex control, complex calculation and measurement display functions of power/harmonic
measurement system by large-capacity software.
Input measurement of three-phase three-wire, three-phase four-wire and single-phase wires
Measurement of true effective value
To measure active power, inactive power and apparent power which contains harmonics for
20 times correctly
To measure total harmonic distortion rate of voltage/current signals for at most 20 times and
harmonic components of various orders correctly
To provide USB communication record interface and special WINDOWS window image
software.
Note: UT241 has no this function.
To facilitate instrument operation by automatic range conversion circuit and panel key.
3Technical specifications
Tolerance limit: (a% of reading + word quantity); Warranty period: 1 year
Ambient temperature: 23 5
Ambient humidity: 45~75%RH
34
AC voltage (true effective value)
Range
The maximum permissible overload protection voltage:600V(r.m.s)
Frequency
RangeAccuracy
~
AC current (true effective value)
RangeAccuracy
The maximum permissible overload protection current: 1000A
The minimum measurement current is 10A.
The minimum measurement voltage is 45V.
Measurement current is less than 10A or
measurement voltage is less than 45V.
Resolution
Testing conditions: (50Hz~60Hz)
ACV: The minimum value is 30V and the maximum
value is 500V.
Testing conditions: (50Hz~60Hz)
ACV: The minimum value is 50V and the maximum
value is 500V.
Other functions:
Display: 4 bits of LCD with the maximum counting of 9,999 and multiplex display
Range selection: Automatic rangelOver-range display: OL
Automatic shutdown function: Machine will power off automatically for operation failure within
period designated by measurement ending (except electric energy gear); Automatic power-off
period also shall be set under setup mode.
Measurement function of the maximum/minimum value (of voltage, current, active power and
inactive power measurement)
Measurement function of total three-phase power
Measurement of total harmonic distortion rate and single-harmonic component
Data retention function
White backlight function
Storage function: The maximum value is 999 groups for single/continuous record of data
readback
User's Manual--------------------------------------------------------------1 manual
Alkaline battery------------------------------------------------------------ 4 batteries
(Red, black, blue and yellow) testing wires ------------------------4 wires
(Red, black, blue and yellow)------------------------------------------ 4 wires
Tool kit and colorful box------------------------------------------------- 1 respectively
USB communication interface wire ----------------------------------1 (only for UT242/243)
Optic disk -------------------------------------------------------------------1 (only for UT242/243)
4 Instrument Layout
4-1 Front elevation of instrument (Figure 1)
1. Current clamp mouth
2. Trigger
3. POWER key
4. key
5. MENU key (electric energy function selection key)
6. LOAD key
7. SELECT key (phase location selection key and total power measurement selection key)
8. key
9. V3 end (the 3rd phase location of measurement input end)
10. V2 end (the 2nd phase location of measurement input end)
11. V1 end (the 1st phase location of measurement input end)
12. COM end: public end
13. MAX/MIN key
14. CLEAR/ key (summation key)
Red black blue
yellow
15. SAVE key
16. HARM key (harmonic function selection key)
17. UT241: HOLD key;UT242/243:LIGHT/HOLD key
18. UT241: LIGHT key; UT242/243:USB key
19. LCD 20. (Red, black, blue and yellow) testing pens
POWER
Press POWER key for a long time for bootstrap and restore function gear during
previous power-off automatically after bootstrap. Press the key for a short time under
bootstrap status for power-off.
HOLD(UT241)
Press the key for a short time to keep display data;
HOLD/LIGHT(UT242/243)
Press the key for a short time to keep display data or press backlight ON/OFF key for a long
period.
MENU
Function menu selection key: Please select active power (kW)+voltage(V)+current(A),
apparent power (kVA)+voltage(V)+current(A), inactive power(kVar)+voltage(V)+current(A),
power factor (COS )+voltage (V)+ current(A), reverse power factor (SIN )+voltage(V)
+current(A), phase location angle( )+voltage(V)+current(A), frequency(Hz)+voltage(V)
+current(A), electric energy(kWh)+active power(kW)+statistic period and phase sequence
judgment in sequence. (Only UT243 has this function.)
HARM
Press the key for a short time to enter into harmonic measurement mode with switchover
circulation for total voltage harmonics to total wave distortion rate, total voltage harmonics to
fundamental wave distortion rate, voltage harmonics, total current harmonics to total wave
distortion rate, total current harmonics to fundamental wave distortion rate and current
harmonics.Press the key for a long time to alter harmonic frequency mode temporarily under
harmonic mode for invalidation after power-off.
1314
LIGHT(UT241)
Press backlight ON/OFF key for a long time.
USB UT242/UT243
Press USB communication ON/OFF key for a long time.
LOAD
Press LOAD key for a short time once to enter into single LOAD data status and
press it again to exit LOAD status.
Press LOAD key for a long time to enter into continuous circulation LOAD data status
and press it again to exit LOAD status.
SELECT
Phase A, B & C and total phase power selection key
SAVE
Press the key for a short time once to record data.
To record data continuously when pressing SAVE key for a long time and press it for a
short time to exit continuous SAVE status.
LCD will display FULL symbol to show that RAM is full of data when displaying data save
quantity of 999. Next group of data cannot be saved until pressing CLEAR key for a long time
to eliminate data in RAM.
/CLEAR
Press key for a short time during measurement in active power/apparent
power/inactive power function gear to calculate and save power for the 1st phase of
currently measured measurement result. Measure the 2nd phase of power and press
key again to calculate and save the 2nd phase of data power. Measure the 3rd
(As shown in Figure 5), connect V1 end/red testing pen, V2 end/blue testing pen
and COM end/black testing pen to every firing line of three-phase load respectively
during load measurement of three-phase three-wire system. V3 end/yellow testing pen also
cannot be measured.
Figure 4 Power measurement of three-phase four-wire system
1718
Figure 5 Power measurement of three-phase three-wire system
(As shown in Figure 6), connect one of V1, V2 & V3 ends which correspond to 3 phase locations
and 2 testing pens of COM end to firing line and zero line of measured wires during
measurement of 2 single-phase wires.
Figure 6 Power measurement of single-phase two-wire system
1920
4
As shown in Figure 7-1, please select SELECT key to
select the 1st phase location when adopting three-phase
four-wire system for load so as to display active power,
voltage and current of phase location 1.
As shown in Figure 7-2, please press key to
measure total three-phase power. Current measured power
of the 1st phase location also shall be calculated and
saved.
As shown in Figure 7-3, please press SELECT key to
select the 2nd phase location of 2. It also can display
active power, voltage and current of phase location of 2.
As shown in Figure 7-4, please press key to
measure total three-phase power. Current measured
power of the 2nd phase location also shall be calculated
and saved.
As shown in Figure 7-5, please press SELECT key to
select the 3rd phase location. It also can display active
power, voltage and current of phase location of 3.
As shown in Figure 7-6, please press key to measure
total three-phase power. Current measured power of the 3rd
phase location also shall be calculated and saved.
As shown in Figure 7-7, total three-phase active power
can be displayed by pressing SELECT key finally.
Measurement operation of the 1st and 2nd phase locations is
the same as that of three-phase four-wire system. As shown in
Figure 7-8, total three-phase active power can be displayed by
pressing SELECT key after tripping the 3rd phase location of
measurement.
5 The maximum range is 600kW for single-phase active power to display OL symbol if
exceeding the range. The maximum range is 1,800kW for total three-phase active power.
It also will display OL symbol if exceeding the range.
6 Display will show MAX symbol by pressing MAX/MIN key so as to display the maximum
active power, voltage and current during measurement. Please press MAX/MIN key to
show MIN symbol on LCD and display the minimum active power during measurement.
Please press MAX/MIN key so that MAX and MIN symbols flicker together. It
can display current value and record the maximum value and the minimum value at the
same time during measurement. Please press the key for a long time to exit the
maximum/minimum value mode.
2122
Figure 7-6
Figure
Figure
Note:
1 Please do not measure AC voltage of more than 600 v.r.s and AC current of 1000A( v.r.s).
2ke y do es no t eff ect wi thout sig nal inp ut or du ring sin gle-phase dis play of O L sym bol.
3 Only current measurement value can be calculated and saved. The maximum value and
the minimum value cannot be calculated or saved.
4 Total power cannot be measured until under active power, apparent power and inactive
power gears.
7.2 Apparent power (kWA)+Voltage(V)+Current (A)
1 Please press MENU to select Apparent power (kWA)+Voltage (V)+Current (A) gear;
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user
shall measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
As shown in Figure 8-1, please press SELECT key to select
the 1st phase location of 1 for three-phase four-wire
system of load. It can display apparent power, voltage and
current of phase location of 1.
As shown in Figure 8-2, please press key to measure
total three-phase power. Current measured power of the 1st
phase location also shall be calculated and saved.
As shown in Figure 8-3, please press SELECT key to select
the 2nd phase location. It also can display active power,
voltage and current of phase location of 2.
As shown in Figure 8-4, please press key to measure
total three-phase power. Current measured power of the 2nd
phase location also shall be calculated and saved.
As shown in Figure 8-5, please press SELECT key to select
the 3rd phase location. It also can display active power,
voltage and current of phase location of 3.
As shown in Figure 8-6, please press key to measure
total three-phase power. Current measured power of the 3rd
phase location also shall be calculated and saved.
As shown in Figure 8-7, total three-phase active power can
be displayed by pressing SELECT key finally.
2324
Figure
Figure
Figure
Figure
Figure
Measurement operation of the 1st and 2nd phase locations
is the same as that of three-phase four-wire system. As
shown in Figure 8-8, total three-phase apparent power can
be displayed by pressing SELECT key after tripping the 3rd
phase location of measurement.
5 The maximum measuring range is 600kWA for single-phase apparent power to display
OL s ymbol if e xceeding th e ra nge. T he m aximum ra nge is 1 ,800KWA fo r to tal th ree-phase
apparent power. It also will display OL symbol if exceeding the range.
6 Display will show MAX symbol by pressing MAX/MIN key so as to display the maximum
active power, voltage and current during measurement. Please press MAX/MIN key to show
MIN symbol on LCD and display the minimum active power during measurement. Please
press MAX/MIN key so that MAX and MIN symbols flicker together. It can
display current value and record the maximum value and the minimum value at the same time
during measurement. Please press the key for a long time to exit the maximum/minimum
value mode.
Note:
Please do not measure AC voltage of more than 600 r.m.s and AC current of 1000A(r.m.s).
1 Press MENU key to select inactive power (kWar)+voltage(V)+current(A)
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user
shall measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
4 As shown in Figure 9-1, please press SELECT key to select the
1st phase location of 1 for three-phase four-wire system of
load. It can display apparent power, voltage and current of phase
location 1.
As shown in Figure 9-2, please press key to measure
total three-phase power. Current measured power of the 1st
phase location also shall be calculated and saved.
As shown in Figure 9-3, please press SELECT key to select
the 2nd phase location. It also can display active power, voltage
and current of phase location of 2.
As shown in Figure 9-4, please press key to measure
total three-phase power. Current measured power of the 2nd
phase location also shall be calculated and saved.
2526
Figure
Figure
Figure
Figure
As shown in Figure 9-5, please press SELECT key to select
the 3rd phase location. It also can display active power,v oltage
and current of phase location of 3.
As shown in Figure 9-6, please press key to measure
total three-phase power. Current measured power of the 3rd
phase location also shall be calculated and saved.
As shown in Figure 9-7, total three-phase active power
can be displayed by pressing SELECT key finally.
Measurement operation of the 1st and 2nd phase locations
is the same as that of three-phase four-wire system. As
shown in Figure 9-8, total three-phase inactive power can be
displayed by pressing SELECT key after tripping the 3rd
phase location of measurement.
5 The maximum measuring range is 600kWar for single-phase inactive power to display
OL symbol if exceeding the range. The maximum range is 1,800KWar for total three phase active power. It also will display OL symbol if exceeding the range.
6 Display will show MAX symbol by pressing MAX/MIN key so as to display the maximum
active power, voltage and current during measurement. Please press MAX/MIN key to show
MIN symbol on LCD and display the minimum active power during measurement. Please
press MAX/MIN key so that MAX and MIN symbols flicker together. It can
display current value and record the maximum value and the minimum value at the same
time during measurement. Please press the key for a long time to exit the maximum/
minimum value mode.
Note:
Please do not measure AC voltage of more than 600 r.m.s and AC current of 1000A (r.m.s).
7.2Power factor cos( ) + Voltage (V)+ Current (A)
1 Press MENU to select gear of Power factor (cos( ) + Voltage (V)+ Current (A) ;
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user
shall measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
4 As shown in Figure 10-1, please press SELECT key to select
the 1st phase location of 1 for load of three-phase four-wire
system. It also can display power factor (cos( )), voltage (V)
and current (A) for phase location 1.
2728
Figure
As shown in Figure 10-2, please press SELECT key to select
the 2nd phase location when adopting three-phase four-wire
system for load so as to display active power, voltage and
current of phase location of 2.
Please press SELECT key to select the 3rd phase location
of 3 for load of three-phase four-wire system. It also can
display power factor (cos( )), voltage (V) and current (A) for
phase location of 3.
Measurement operation of the 1st and 2nd phase locations is the same as that of three-phase
four-wire system after tripping the 3rd phase location of measurement.
5 There is no measurement function of the maximum/minimum value for this function gear.
Note:
Please do not measure AC voltage of more than 600V r.m.s and AC current of 1000A r.m.s .
1 Press MENU to select gear of Phase location angle ( )+ Voltage (V)+ Current (A) ;
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user
shall measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
4 As shown in Figure 11-1, please press SELECT key to select
the 1st phase location of 1 for three-phase four-wire system
of load. It also can display apparent power, voltage and current
of phase location of 1.
Please press SELECT key to select the 2nd phase location of
2 shown in Figure 11-2. It also can display apparent power,
voltage and current of phase location of 2.
Please press SELECT key to select the 3rd phase location of
2 shown in Figure 11-3. It also can display apparent power,
voltage and current of phase location of 3.
Measurement operation of the 1st and 2nd phase locations is the same as that of three-phase
four-wire system after tripping the 3rd phase location of measurement.
2930
Figure
Figure
Figure
5 There is no measurement function of the maximum/minimum value for this function gear.
Note:
Please do not measure AC voltage of more than 600V r.m.s and AC current of 1000A r.m.s .
7.6 Voltage frequency (Hz)+Voltage (V)+Current (A)
1 Press MENU key to select gear of frequency + voltage + current ;
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user
shall measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
4 As shown in Figure 12-1, please press SELECT key to select
the 1st phase location of 1 for three-phase four-wire system
of load. It also can display apparent power, voltage and
current of phase location of 1.
Please press SELECT key to select the 2nd phase location
of 2 shown in Figure 12-2. It also can display apparent
frequency, voltage and current of phase location of 2.
Figure
Figure
Please press SELECT key to select the 3rd phase location of
3 shown in Figure 12-3. It also can display frequency, voltage
and current of phase location of 3.
As shown in Figure 13, please press SELECT key to select
phase locations of 123 to display current power of
measured load for corresponding phase locations, current
statistic period and current accumulated electric energy on
LCD.
Figure
Measurement operation of the 1st and 2nd phase locations is the same as that of three-phase
four-wire system after tripping the 3rd phase location of measurement.
5 There is no measurement function of the maximum/minimum value for this function gear.
Note:
1 It is not allowed to measure AC voltage of more than 600V r.m.s and AC current of
1000A r.m.s .
2 Not frequency of current signals but that of voltage signals shall be measured.
7.6Electric energy (kWh)+Active power (kW)+Time (h:m:s)
1 Press MENU key to select gear of electric energy (kWh)+active power(kW)+time (h:m:s) ;
2 Jaw shall be fixed to measured conduits in corresponding phase locations. That is, user shall
measure a certain phase of three-phase circuit so that jaw is on corresponding conduit.
3 Please refer to Figure 4, 5 & 6 of UT240 manual for wiring of three-phase four-wire system,
three-phase three-wire system or single-phase two-wire system.
3132
Accumulated electric energy increases gradually with time. User can press HOLD key to lock
measurement value and measurement time display when reading electric energy for a certain
period. However, instrument will continue to accumulate measurement time. Please press HOLD
key once again after reading data to continue to measure accumulated electric energy.
Measurement time display will turn to current measurement time value and electric energy
function will not stop until function conversion to positions of other gears. The maximum testing
quantity of electric energy is 9999kWh . Display will show OL s ymbol a fter e xceeding th e
value. The maximum statistic period of electric energy also cannot exceed 99 hours.
4 There is no measurement function of the maximum/minimum value for this function gear.
5 Press CLEAR key to reset time and accumulated electric energy to begin counting &
measurement again.
1 As shown in Figure 14, press MENU to select gear of voltage (V)+voltage (V)+voltage
1 As shown in Figure 15, 16 &17, instrument will display phase sequence detection result for
load loop of three-phase four-wire system.
(V) . Insert red testing pen into V1 jack, blue testing pen into V2 jack, yellow
testing pen into V3 jack and black testing pen into COM jack and connect 4
testing pens to measured power, three-phase load and grounding end.
2 Positive sequence layout is shown in following figure. As shown in Figure 18, LCD can
display positive sequence detection result when connecting V1,V 2 and V3 jacks t o
Phase A, B & C if three-phase voltage exceeds 50V.
4 LCD will display default phase detection result if certain phase of voltage is less than 50V or
without signal for three-phase four-wire system load. As shown in Figure 20, symbols of
Phase location
corresponding phases will not be displayed on LCD.
A, B & C
Detection result
Positive sequence
3 Inverted sequence layout is shown in following figure. As shown in Figure 19, LCD can
display inverted sequence detection result when connecting V1 , V2 and V3
jacks to Phase A, B & C if three-phase voltage exceeds 50V.
Figure 20
Default phase of the 2nd phase
Note:
Detection voltage range of positive and inverted sequence is 30V~500V. Voltage range without
Press HARM key for circulation switchover of following harmonic measurement functions. 3
frequency modes, namely, AUTO , 50Hza nd 60Hzc an b e s elected f or a ll h armonic
measurement functions respectively.U ser c an p ress H ARM k ey f or a l ong t ime t o a lter f requency
mode temporarily during measurement. (Instrument will restore default mode after power-off.)
Default frequency mode also can be set under setup mode. (Please refer to Clause 9.3: Default
frequency mode setup for SE3 harmonic function for difference of 3 frequency modes.)
8.1 Total voltage harmonics for full wave distortion rate (V THD-R
It will measure and display effective value of total harmonics of single-phase voltage to full
wave distortion rate, harmonic order and corresponding orders of harmonic voltage for load of
three-phase four-wire system.
Measurement steps: Press HARM key to enter into measurement mode of total voltage
harmonics to total wave distortion rate firstly after bootstrap and connect voltage signal of
measured phase to voltage input end of instrument by probe and connect zero wire to COM
end. As shown in Figure 14, connect phase wire to any port of V1/V2/V3 and press SELECT
key so that measurement port can be consistent with input port.
3738
As shown in Figure 21, LCD will display current harmonic order (with auxiliary display in left
lower corner), total voltage harmonics for full wave distortion rate (with auxiliary display in right
lower corner) and effective value of harmonic voltage (with main display in the middle)
respectively.
Figure 21
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various voltage harmonic components correspondingly.
8.2 Total voltage harmonics for fundamental wave distortion rate
It will measure and display effective value of total harmonics of single-phase voltage to
fundamental wave distortion rate, harmonic order and corresponding orders of harmonic
voltage for load of three-phase four-wire system.
Measurement steps: Press HARM key to enter into measurement mode of total voltage
harmonics to total wave distortion rate firstly after bootstrap and connect voltage signal of
measured phase to voltage input end of instrument by probe and connect zero wire to COM
end. As shown in Figure 20, connect phase wire to any port of V1/V2/V3 and press SELECT
key so that measurement port can be consistent with input port. As shown in Figure 22, LCD
will display current harmonic order (with auxiliary display in left lower corner), total voltage
harmonics for full wave distortion rate (with auxiliary display in right lower corner) and effective
value of harmonic voltage (with main display in the middle) respectively.
Figure 22
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various voltage harmonic components correspondingly.
3940
8.3 Voltage harmonics
It will measure and display effective value of various harmonics of single-phase voltage to
fundamental wave distortion rate, harmonic order and corresponding orders of harmonic
voltage for load of three-phase four-wire system.
Measurement steps: Press HARM key to enter into measurement mode of voltage harmonic
components after bootstrap and connect voltage signal of measured phase to voltage input end
of instrument by probe and connect zero wire to COM end. As shown in Figure 20, connect
phase wire to any port of V1/V2/V3 and press SELECT key so that measurement port can be
consistent with input port. As shown in Figure 23, LCD will display current harmonic order (with
auxiliary display in left lower corner), effective value of harmonic voltage (with main display in
the middle) and percentage of effective value of harmonic component for effective value of
fundamental wave (with auxiliary display in right lower corner) respectively.
Figure 23
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various voltage harmonic components and percentage for
fundamental wave correspondingly.
8.4 Total current harmonics for full wave distortion rate
It will measure and display effective value of total harmonics of single-phase current to full wave
distortion rate, harmonic order and corresponding orders of harmonic current under the mode.
Measurement steps: As shown in Figure 24, please press HARM key to enter into measurement
mode of total current harmonics for full wave distortion rate firstly after bootstrap. Please loosen
binding clip and clamp them into current loop cables of measured phase, and loosen and
guarantee excellent closing of binding clip.
Figure 24
4142
As shown in Figure 25, user can press SELECT key to select No. of any measurement port to
display current harmonic order (with auxiliary display in left lower corner), total current
harmonics to full wave distortion rate (with auxiliary display in lower right corner) and effective
value for harmonic current (with main display in the middle) on LCD respectively.
Figure 25
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various current harmonic components.
8.5 Total current harmonics for fundamental wave distortion rate
It will measure and display effective value of total harmonics of single-phase current to
fundamental wave distortion rate, harmonic order and corresponding orders of harmonic current
under the mode.
Measurement steps: As shown in Figure 24, please press HARM key to enter into measurement
mode of total current harmonics for full wave distortion rate firstly after bootstrap. Please loosen
binding clip and clamp them into current loop cables of measured phase and loosen and
guarantee excellent closing of binding clip. As shown in Figure 26, user can press SELECT key
to select No. of any measurement port to display current harmonic order (with auxiliary display
in left lower corner), total current harmonics to full wave distortion rate (with auxiliary display in
lower right corner) and effective value for harmonic current (with main display in the middle) on
LCD respectively.
Figure 26
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various current harmonic components.
4344
8.6 Current Harmonics
It will measure and display effective value of total harmonics of single-phase current to
fundamental wave distortion rate, harmonic order and corresponding orders of harmonic
current under the mode.
Measurement steps: As shown in Figure 24, please press HARM key to enter into measurement
mode of total current harmonics for full wave distortion rate firstly after bootstrap. Please loosen
binding clip and clamp them into current loop cables of measured phase and loosen and
guarantee excellent closing of binding clip. As shown in Figure 27, user can press SELECT key
to select No. of any measurement port to display current harmonic order (with auxiliary display
in left lower corner), effective value of harmonic current (with main display in the middle) and
percentage of effective value of current harmonic component to fundamental wave (with auxiliary
display in right lower corner) on LCD respectively.
Figure 27
User can press key to increase harmonic order or press key to reduce harmonic order. It
also will display effective value of various current harmonic components.
User can press SELECT key for bootstrap and entry into setup mode. User can set automatic
power-off time (SE1), automatic backlight OFF time (SE2) and default frequency mode of
harmonic function (SE3) under setup mode. User also can press SELECT key for a short time
for SE1 & SE2 switchover and SE2 setup functions.
User shall press SAVE key to save setup and enter into normal measurement mode after setup.
He also can press CLEAR key for a short time under setup mode to restore ex-factory default
setup. He also shall press SAVE key for saving.
9.1 Setup of SE1 automatic power-off time
As shown in Figure 28, user can press SELEST key for bootstrap and entry into setup mode.
User also can press SELECT key for switchover to SE 1 setup.
Automatic power-off time can be set as follows by pressing UP or DOWN key:
1 10m: 10 minutes
2. 20m: 20 minutes
3. 30m: 30 minutes
4. OFF: Automatic power-off function is OFF.
4546
Figure
9.2 Setup of automatic OFF time of SE2 backlight
As shown in Figure 29, user can press SELEST key for bootstrap and entry into setup mode.
He also can press SELECT key for switchover to SE 2 setup.
Automatic backlight OFF time can be set as follows by pressing
UP or DOWN key:
1 10s: 10 seconds
2. 20s: 20 seconds
3. 30s: 30 seconds
4. OFF: Without automatic backlight OFF
9.3 Setup of default frequency mode of SE3 harmonic function
As shown in Figure 30, user can press SELEST key for bootstrap and entry into setup mode.
He also can press SELECT key for switchover to SE 3 setup.
Default frequency mode of harmonic function is as follows by
pressing UP or DOWN key:
1. 50Hz can be used as current signal frequency for fixed
measurement;
2. 60Hz can be used as current signal frequency for fixed
measurement;
3. AUTO: Actual frequency of current measurement signal
can be gained automatically for measurement;
symbol shows on LCD means that load voltage of battery is less than the minimum
voltage to guarantee measurement tolerance limit and instrument will prompt battery
replacement. Please replace battery according to following steps:
(1) Cut off testing circuit for testing pen, press POWER key for power-off and remove testing
pen from input jack.
(2) Open cell cover of instrument and remove old battery and replace 4 new batteries of 1.5V.
Please pay attention to polarity of anode and cathode. New and old batteries also cannot
be mixed.
(3) Inset the cell cover;
11 Maintenance
(1) Cleaning shell: Please clean the surface by dipping soft cloth or sponge by clean water.
Figure 31
Warning
Guarantee instrument power-off and ensure that testing pen is not connected to any measured
circuit before replacing battery and opening rear cover of instrument to avoid electric shock. Be
sure that rear cover has been tightened or not before using instrument. Only battery of the same
model or electric dimension can be replaced.
4748
(2) It is strictly prohibited to dip instrument into water to avoid damage of testing instrument.
(3) Please dry and store instruments if they are wet.
(4) Please submit instruments to qualified repair personnel or designated repair department
for calibration or repair if required.