Unique Klasse DSA-0910LG-M, DPA-246LG, DSA-0910LR-M, DPA-246LR Service Manual

SERVICE MANUAL
MULTI-ONE SYSTEM Air Conditioner
Model: DPA-246LR + DSA-0910LR-M
DPA-246LG + DSA-0910LG-M
Caution
: In this Manual, some parts can be changed for improving,
FLOOR STANDING TYPE
Air Conditioner
Model: DPA-246LR / DPA-246LG
CONTENTS
1. SPECIFICA TIONS.....................................................................................................2
2. INST ALLATION GUIDE.............................................................................................3
3. OUTLINE..................................................................................................................13
4. WIRING DIAGRAM.................................................................................................17
5. EXPLODED DIAGRAM..........................................................................................20
6. DIAGRAM OF REFRIGERANT CYCLE................................................................25
7. THE STRUCTURE OF THE CONTROL PANEL..................................................26
8. PCB DRIVING DESCRIPTION..............................................................................29
9. TROUBLESHOOTING............................................................................................32
10. DISASSEMBL Y INSTRUCTION..........................................................................37
Contents
2
1. SPECIFICATIONS
MODEL FLOOR STANDING SPLIT ITEM DPA-246LR/LG DSA-0910LRM/LGM FUNCTION COOLING POWER AC 220~ / 60Hz
CAPACITY
W 7,200 2,300
Btu/h 24,500 7,848 ELECTRICAL Running current A 10.5 3.5 DATA Power input W 2300 660 FAN Type Limited fan Cross flow fan
MOTOR
Capacitor 2µF / 400~450VAC 1.8µF / 400~450VAC
Model IC-9630DWKF6A RP13B-PG REFRIGERANT Control CAPILLARY (R-22) Charge g 1650
CONNECTION
Type Flare
OD(Liquid/Gas) mm(in) 6.35(1/4") / 15.88(5/8") 6.35(1/4") / 9.52(3/8") DIMENSIONS (WXHXD) mm 560 * 1,800 * 302 850 * 280 * 170 NET WEIGHT kg 49 11.5
Multi-One [ DPA-246L(R/G) + DSA-0910L(R/G)-M ]
Type ROTARY
Compressor Model QK191KAF [A] QK134KBH [B]
Capacitor 30µF / 6µF, 450VAC 25µF, 450VAC
Fan type PROPELLER FAN OUT DOOR
Motor
Capacitor 6µF / 400~450VAC
UNIT Model A2935GA010 (1050/ 900/ 600RPM)
Dimension
mm 872 * 675 * 325
(WXHXD)
Net Weight kg 58
3
2. INSTALLATION GUIDE
··Flat and strong place in the room
·No obstacles in front of air in/out grille
· Easy place to connect drain hose to outside of room
· Easy place to connect copper tube with outdoor unit
· Secure enough distance from neighboring objects as
shown below.
· Secure enough distance from neighboring objects as shown below.
· A place no reach of direct ray of sun (if necessary, shield the light)
·No obstacles in front of air in/out grille
·A place having a drain out-let
· Easy place to connect copper tube with indoor unit
· Secure enough distance from neighboring objects as shown
below.
CAUTION : Do not hang the outdoor unit on the wall of building, in case of falling, it may cause a serious trouble and damage.
·
·
·
·
·
·
·
·
·
·
·
CAUTION
· Use designated diameter and thickness of tube.
· Connect all tube as short as possible and fix firmly.
· Less than 3M of the difference of height between indoor and outdoor unit is desirable.
· Fill up more refrigerant if the connection tube is longer than 5M (30g/M).
(The refrigerant volume filled from the factory is suitable for 5M connection)
· Be careful not to let in any dust or motes into the tube when the tube passes the wall.
·
When insulating the connection, use foam rubber or equivalent.
Secure enough space from the neighboring objects as shown below. This is required to operate the unit efficiently.
·
·
·
·
·
·
·
·
·
·
·
30cm
70cm
30cm
70cm
(Outdoor unit)
5cm
(Indoor unit)
1
00cm
5cm
wall
indoor unit
outdoor unit
INSTALLATION PLACE
1
SPACE TO INSTALL
2
4
Detailed Diagram of Installation
3
MMOODDEELL :: DDPPAA--224466LLRR//LLGG
1. Unfasten 3 screws in cover evaporator front.
3. To prevent water drops, cover connection part between pipe suction and connection piping line with insulating material provided with indoor unit.
4. Wind finishing tape around liquid pipe, gas pipe and electric wiring.
2. Open cover evaporator front and disconnect gas pipe and liquid pipe from connection piping line.
Electrical Wire
Liquid Pipe
Vinyl Tape
Heat Insulator
Gas Pipe
5
5. Connect hook of power cable and insert is securely into the fixing part.
6. Check if pan drain is securely positioned at the end of drain hose. If loose, firmly secure it with cable tie.
* In case there is interference with piping line when cover evaporator front is closed, move piping line close to evaporator, close cover
evaporator front and fasten screws.
* Well done. Installation has been completed.
NNaannoo ssiillvveerr aannttiiffuunnggaall ffiilltteerr cclleeaanniinngg
1. Pull forward the front panel 2. Remove the nano silver antifungal filters
3. Clean off dust by vacuum cleaner or soft brush
4. Insert the filter and then close the front panel
7. Fasten 3 screws in cover evaporator front.
6
◇ Wiring and part shapes may differ per product model. Therefore, make sure to refer to wiring diagram
attached to each model for installation. (Refer to wiring diagram attached at the end of the manual.)
1. Connect piping lines by distinguishing between piping lines of standing type A/C and split type A/C. (If connection piping line is long, additionally fill up refrigerant by referring to pressure table. However, make sure that difference in the length of connection piping lines of standing type A/C and split type A/C is within 5m.)
2. Connect the power line of standing type A/C (wiring No. 4 and 5) first before administering air-purge process. After completion of air purging, additionally connect signal line (No. 6) and wiring of split type A/C (No. 1 and 2). Caution is required because there is danger of electric shock during this process.
CCAAUUTTIIOONNBe sure to use designated wires and make it as short as possibleUse an exclusive power supply for the air conditionerUse an electricity leakage interrupter having suitable capacity .Grounding resistance should be under 100 ohms and the grounding wire should be connected firmly to the terminal of
out door unit.
When connecting wires of indoor and outdoor unit, the numbers of terminal block and terminals of connecting wires
should match exactly as shown below.
Terminals of connecting wires should be fixed firmly using wire fixing tool to the same direction of terminal board.
3. For Multi-one model, power is supplied to outdoor unit through power line of the indoor unit of standing type A/C. Therefore, even for cooling operation of split type A/C only, power plug for the indoor unit of standing type A/C must be inserted into power outlet to enable cooling operation.
Make sure to deliver product to customer after completing installation.
MMaaiinn PPoowweerr
TTeerrmmiinnaall BBlloocckk((OODDUU))
SSpplliitt
SSttaannddiinngg
FFlloooorr SSttaannddiinngg AA//CC
SSpplliitt ttyyppee AA//CC
BBrr BBrr BBkk
BBll BBll
11 22 44 55 66
FFlloooorr SSttaannddiinngg AA//CC ppoowweerr lliinnee
SSiiggnnaall lliinnee
Caution in Installation of Multione model
4
7
Air Purging Method
5
◇ The connected piping between indoor and outdoor units contains air inside. Air-purge is the process to remove this
air. Existence of non-condensable gas, such as oxygen or nitrogen gas, inside piping line causes increase of discharge pressure, heating of compressor, degradation of the performance of air conditioner and refrigerant noise, etc. Therefore, air-purge is an essentially required process.
◇ Air purging by refrigerant of outdoor unit (in case length of piping is of 10m or less)
Connect piping lines of indoor and outdoor units. (Service valves of gas and liquid are both closed.) Loosely fasten nuts () for connection of gas service valve (so that the nuts can be unfastened by hand). Remove nut caps (,⑨) and port cap (⑩) of service
valve.
Using a hexagonal wrench, rotate spindle () of liquid
service valve by 90°in anticlockwise direction. Hold the spindle in position for 8 ~ 10 seconds. Rotate it again by 90°in clockwise direction to close. Then, completely fasten nuts (④) for connection of gas service valve.
Press side of the service port () of gas pipe service
valve 2 or 3 times (for 3 seconds per time) to completely remove air from inside the valve.
Completely open gas and liquid service valve spindles
(⑤, ) by using a hexagonal wrench. Close all of nut caps (, ) and port caps (, ⑧) of service valve. Otherwise, refrigerant leakage may occur.
◇ Air purging by vacuum pump (in case length of piping is of 10m of more)
Connect piping lines of indoor and outdoor units. (Service valves of gas and liquid are both closed.)Connect low pressure hose () of manifold gauge to service port (④) of gas service valve.Open valve of the low pressure hose () of manifold gauge, connect vacuum pump as shown in the picture and start purging.Run vacuum pump until gauge pressure reaches [-76cmHg] (for 10 ~ 20 minutes).Close valve of the low pressure hose () or manifold
gauge, wait for 3 ~ 4 minutes and check if scale of
pressure gauge has changed. If scale of pressure gauge
has changed, check connection part to prevent refrigerant
leakage in advance. Turn off vacuum pump and disconnect low pressure hose
(③) of manifold gauge from service valve. Completely open gas and liquid service valves by using a
hexagonal wrench. Close all of nut caps (, ) and port caps (⑦, ) of
service valve. Otherwise, refrigerant leakage may occur.
Low
High
Vaccum pump
ODU
IDU
Pressure gage
Open
Close
Gas
Liquid
ODU
Gas
IDU
Liquid
8
5
6
10
4
9
3
1
2
7
1
3
5
4
7 6
8
2
8
◇ Multi-one model is assembled with solenoid valve inside the system. Therefore, for refrigerant purging, the closed
solenoid valve must be opened. Follow the instructions below.
Connect power line of the indoor unit of standing type A/C to terminal block of outdoor unit. Connect power plug of the indoor unit of standing type A/C to cabinet panel box.Solenoid valve opens with a clicking sound.
(Valve is opened for 1 hour only when supplying power for the first time. _ Supply power again after 1 hour.)
Administer air purging according to the attached [refrigerant purging method] or [purging by vacuum pump].Continuously administer air purging in the same way when connecting frame-type piping.After completion of air-purge, pull out power plug of the indoor unit of split type A/C. Then, connect signal line and split ty pe A/C wiring to
the terminal block of outdoor unit.
Administer test operation.When no abnormalities are detected, finish up piping process (finishing up wiring and insulation materials).
CCoorrrreecctt ccoonnnneeccttiioonn
ooff ppiippiinngg lliinneess ooff
iinnddoooorr aanndd oouuttddoooorr
uunniittss
RReeffrriiggeerraanntt lleeaakkaaggee ffrroomm iinnddoooorr uunniitt dduuee ttoo iinnffeerriioorr aaiirr--ppuurrggee
FFrreeqquueenntt ooccccuurrrreennccee ooff ccllaaiimm ffoorr nnooiissee
SSpplliitt ttyyppee GGaass ppiippee
SSpplliitt ttyyppee
LLiiqquuiidd ppiippee
SSttaannddiinngg ttyyppee
GGaass ppiippee
SSttaannddiinngg ttyyppee
LLiiqquuiidd ppiippee
Air Purging Method
6
9
Check the hose and connection status of manifold gauge. Then, check if there is a pin at the end of low pressure hose (③). Valves of low and high pressure hoses (①,②) must be closed.
Connect hose in the middle of manifold gauge () to refrigerant container (). Refrigerant container must be prepared so that refrigerant can be charged in gaseous state.
While placing low pressure hose of manifold gauge () over the service port of gas service valve (), open the valve of refrigerant container (), slightly open low pressure valve of manifold gauge () and remove air from inside the hose (③). Immediately after removing air, connect and and close the low pressure valve of manifold gauge ().
Start cooling operation of air conditioner.
Open and close low pressure valve () by checking the pressure of manifold gauge. Repeat pressure check and additionally fill up refrigerant according to the pressure listed
Close low pressure valve of manifold gauge () and stop the operation of air conditioner.
After closing the valve of refrigerant container, disconnect manifold gauge and reassemble nut caps and port caps (to prevent refrigerant leakage).
CCaauuttiioonn wwhheenn aaddddiittiioonnaallllyy ffiilllliinngg rreeffrriiggeerraanntt dduurriinngg
uussee
Slight leakage of refrigerant occurs when pin of low
pressure hose is in contact with needle valve of service valve. Refrigerant leakage will be stopped through tightening up.
AAddmmiinniisstteerr rreeffrriiggeerraanntt ffiilllliinngg bbyy rreeppeeaatteeddllyy ccaarrrryyiinngg
oouutt iimmmmeeddiiaattee ooppeenniinngg aanndd cclloossiinngg ooff ppoowweerr pprreessssuurree vvaallvvee (()) ooff mmaanniiffoolldd ggaauuggee sseevveerraall ttiimmeess ((ttoo pprreevveenntt lliiqquuiidd ccoommpprreessssiioonn))..
WWhheenn ccoommpplleetteellyy ddiisscchhaarrggiinngg rreeffrriiggeerraanntt,, iitt mmuusstt
bbee ddoonnee sslloowwllyy ssoo tthhaatt ttoo pprreevveenntt eexxcceessssiivvee lleeaakkaaggee ooff rreeffrriiggeerraattoorr ooiill..
1
2
3
6
4
5
R-22
Additional Filling of Refrigerant
7
10
Changes of low pressure by the temperature differences indoor and outdoor (Multi-One, Basic piping 5m)
[Package single operation]
20 25 30 35 40
21 4.0 4.2 4.6 4.4 4.4 23 4.3 4.4 4.8 4.6 4.6 25 4.5 4.6 5.1 4.8 4.8 27 4.6 4.7 5.2 4.9 5.0 29 4.8 4.9 5.3 5.2 5.3
532 4.9 5.0 5.4 5.3 5.4
DPA-246L
Bypass S/V
Additional
refrigerants
floor standing type - Add extra 30g/m
wall mounted type - No need for extra refrigerants under 15m
On Off
Low pressure
(kg/cm2, G)
Outdoor temperature(℃)
Indoor
Temperature (℃)
*The data are the result of tests at the relative humidity 50%
Split type connecting pipe (B)
Standing type
connecting pipe (A)
◇ When refill the refrigerants, just add the exact quantity by using electronic scale.
(The refill quantity chart is attached on the outdoor fan set.)
◇ Long distance piping specification(Up to 15m piping guaranteed) At 35C outdoor and 27C indoor, the low
pressure of `Multi one model in single operation is 5.2(Kg/cm, G) Add the proper quantity of refrigerants referring the pressure.
◇ The pipes of A and B shall be installed not to exceed 5m in the difference(A-B or B-A)
11
Test Operation and Description of Functions
8
11)) FFiinniisshhiinngg ooppeerraattiioonn
Apply insulation materials after checking for no refrigerant leakage and successful drainage. Take caution not to have product wiring and power line get in contact with piping line without insulation materials or gas service
valve.
Seal off the hole in wall surface with putty placed in the box of installation materials.Wind up finishing tape in upward direction.
22)) IInnssppeeccttiioonnss aafftteerr iinnssttaallllaattiioonn
Check solidity of the place and of location of product installation. Check connection status of piping line and for gas leakage.Check connection status of wiring.Check insulation status of piping line.Check drainage status.Check connection status of flare nuts.
33)) CChheecckkppooiinnttss dduurriinngg tteesstt ooppeerraattiioonn
Check for signal sound (beep~) when supplying power.Check the operation status of remote controller.Check if indoor operation indication lamp has been lit.Check if abnormal noises are generated from indoor and outdoor units.When starting cooling operation for the first time, check if compressor protection function is operated.
44)) DDeelliivveerryy ttoo ccoonnssuummeerr
Explain about manual and instructions of using remote controller to consumer.Explain about how to turn power on/ off, methods of selecting operation mode, methods of wind velocity adjustment and
methods of cleaning filter, etc.
12
Pumpdown (refrigerant recovery)
9
SSttaarrtt ccoooolliinngg ooppeerraattiioonn..
((CChheecckk iiff ccoommpprreessssoorr ooff oouuttddoooorr uunniitt iiss
ooppeerraattiinngg..))
PPuummpp--ddoowwnn ((rreeffrriiggeerraanntt rreeccoovveerryy)) iiss tthhee pprroocceessss ttoo
ccoolllleecctt rreeffrriiggeerraanntt rreemmaaiinniinngg iinn iinnddoooorr uunniitt aanndd
ccoonnnneeccttiioonn ppiippiinngg lliinnee aanndd ssttoorree iitt iinn oouuttddoooorr uunniitt
ffoorr tthhee ppuurrppoossee ooff mmoovviinngg oorr rreeppaaiirriinngg aaiirr
ccoonnddiittiioonneerr..
Loosen nut caps of gas and liquid service valves (, ⑥) and service port cap of gas service valve ().
Connect low pressure hose of manifold gauge () to service port of gas service valve. Low pressure hose valve of manifold gauge () must be closed.
Completely close liquid service valve by rotating it in clockwise direction with a hexagonal wrench.
When low pressure of manifold gauge drops to 0kgf/cm2, completely close gas service valve by rotating it in clockwise direction with a hexagonal wrench.
Immediately stop the operation of air conditioner. (Refrigerant is not being circulated. Therefore breakdown of compressor may occur if air conditioner is not stopped immediately.)
Disconnect manifold gauge and reassemble nut caps and port caps (to prevent refrigerant leakage).
Low High
Pressure
gage
1
2
3
5
4
7
6
8
IDU
ODU
Gas
Liquid
13
3. OUTLINE
1Top side air out / director for fan 7Main controls/Remote sensors 2Front panel (Door) 8Air in antifungal filter 3Bottom side air out / director for fan 9UV sterilization Lamp 4Air in(bottom) 0Remote controller rack 5Air in(top) qAir in nano filter 6Air in(back) wAir in antifungal filter
5
8
9
w
q
6
2
0
7
1
2
4
3
(1) DPA-246LR/LG INDOOR UNIT
11.. NNAAMMEE AANNDD FFUUNNCCTTIIOONN OOFF PPAARRTTSS
14
(2) DPA-246LR/LG INDOOR UNIT OUTLINE AND SECTION
15
(3) DPA-246LR/LG INDOOR UNIT MAIN CONTROL
Temperature Indicator
Room temperature/Desired temperature indicator
Cooling course Indicator
Light to indicate the cooling course.
[Dual/Single/Optimal]
Fan speed indicator
Lights to indicate the fan speed. (Auto/Low/Middle/High/Eco)
Operation mode indicator
Auto/Cooling/Fan/Dehumifier/UV/
Economy/Reservation/Sleep
Temperature setting buttons
Each time you push this button, the temperature varies 1 C up and down within the temperature range of 18 C~32 C.
Cooling course selection button
Press to cycle through the cooling course.
Fan speed setting button
Press to select the fan speed in five steps. "(Auto, Low, Middle, Hige, Eco) "
UV sterilization button
Press to operates UV sterilization.
Turbo button
Press to select super power operation mode.
Mode selection button
Press to cycle through the modes. [Auto/Cool/Fan/Dehumifier]
Remote signal sensor
On/Off button
Press this button once to start operation. Press once again to stop it.
O
O
O
16
Top
Bottom
Power. S
Cooling. C
UV Lamp
Timer
(4) DPA-246LR/LG REMOTE CONTROLLER
Timer
Power. S
Cooling. C
UV Lamp
Top
Bottom
Signal transmitter
Display
Fan speed setting button
Press to select the fan speed in five steps. "(Auto, Low, Middle, Hige, Eco)"
Mode selection button
Press to cycle through the modes. [Auto/Cool/Fan/Dehumifier]
Air swing button
Press this button once to auto operation of flap front. Press once again to stop of flap front.
Turbo button
Press to select super power operation mode
Focus/Wide button
Press to select air direction.
Economy mode button
Press to operates economy mode
Cooling course selection button
Press to cycle through the cooling course.
On/Off button
Press this button once to start operation. Press once again to stop it.
Floor Standing
Temperature setting buttons
Press to raise or lower the desire temperature.
Timer On/Off button, Enter/Cancel timer button
Press to set the unit off or on time. "(0.5,1.5,2,2.5,3,4,5,6,8,10,12,16,20,24)"
Press to enter a timer setting or to cancel timer setting.
Sleep button
Press to set the unit for the sleep mode. (2~4hr)
UV sterilization button
Press to operates UV sterilization
17
(1) INDOOR UNIT
4. WIRING DIAGRAM
18
(2) OUTDOOR UNIT
19
(3) OUTDOOR CONTROL BOX ASSY
NNoo.. PPaarrtt ccooddee PPaarrtt NNaammee EEAA SSppeecc..
1 3104201610 PANEL CONTROL 1 SGCC T0.6 2 3116914000 CAPACITOR DUAL 1 6+30UF 400VAC Φ50 L100 3 3116912100 CAPACITOR SINGLE 1 25UF 400VAC Φ50 L75 4 311359JW00 LABEL [A] 1 ART PAPER, KP-150S 5 311359JX00 LABEL [B] 1 ART PAPER, KP-150S 6 3111201400 CLAMP CAPACITOR 1 SGCC-M-Z22,T0.8(MULTI-ONE) 7 3108912700 TERMINAL BLOCK JOI 1 DA-TB1, DONG-A, 300V/20A 8 3108914400 TERMINAL BLOCK 1 JXO-CH-6P 600V 30A
9 311359JY20 LABEL TERMINAL BLOCK 1 ART PAPER, KP-151S,KP-181S 10 3111101600 CASE OD PCB 1 PP + TALK 20% 11 3114317130 PCB ASSY O/D 1 DPA-246L 12 3112746710 HARNESS COMP "A" 1 UL1015 14AWG 3C*700MM BR,BL,RD 13 3112746810 HARNESS COMP "B" 1 UL1015 14AWG 3C*700MM BR,BL,YEL 14 3112747600 HARNESS PAC S/G 1 UL1015 1C*250MM*AWG20 BK 15 3112747400 HARNESS PCB POWER 1 UL1015 2C*250MM*AWG16 BR,BU 16 3112747500 HARNESS SRAC S/G 1 UL1015 2C*300MM*AWG20 BR,BU 17 3112747300 HARNESS POWER "N" 1 UL1015 1C*200MM*AWG14 BLUE 18 3112747200 HARNESS POWER "L" 1 UL1015 1C*200MM*AWG14 BR 19 3112747000 HARNESS CAPACITOR 1 UL1015 1C*150MM*AWG14 BLUE 20 3112747100 HARNESS CAPA JUMP 1 UL1015 1C*100MM*AWG14 BLUE 21 3112746900 HARNESS COMP S/G 2 UL1015 1C*200MM*AWG14 BR 22 3114801700 HARNESS COIL SENSOR 1 N3SM-KD41-DA28 23 3101200400 CLAMP CORD 2 DA-5N 24 7122401611 SCREW TAPPING 2 T2S TRS 4X16 MFZN 25 7001400811 SCREW MACHINE 1 PAN M4X8 MFZN 26 7122401211 SCREW TAPPING 4 T2S TRS 4X12 MFZN 27 311359KL00 LABEL TER-BLOCK DISPLAY 1 PAC, SRAC 28 311359LK00 LABEL CABLECAUTION 1
20
(1) DPA-246 LR/LG INDOOR UNIT
5. EXPLODED DIAGRAM
21
PARTS LIST (INDOOR UNIT)
(PAGE 1/2)
Part code Part Name Spec. Unit EA Remark
31100A8X00 ASSY INDOOR UNITS DAP-246LR/LG SET 1 1 3110305200 BASE HIPS, GY5502A EA 1 2 31100A9000 ASSY CABINET BODY ASSY,GY5502A EA 1
2-1 3110802300 BODY CABINET PCM,T0.8,GY5502C EA 1 2-2 311009JZ01 ASSY BASE MOTOR SGCC,T1.0 EA 2
3 3111416000 COVER TOP HIPS,GY5502A EA 1 4 3111909800 FILTER AIR BACK HIPS,GY5502A EA 1 5 3111103600 CASE FILTER BACK ABS,GY5502A EA 1 6 3111803000 FAN INDOOR ABS+GF20% EA 2 7 3110701200 BUSHING FAN C3604BD EA 2
8 3118016300 MOTOR IDU (TOP)
IC-9630DWKF6B TOP
EA 1
BLU 2.0UF (860/780/710/670)
9 3118016310 MOTOR IDU (BOTTOM)
IC-9630DWKF6A-1 BOTTOM
EA 1
WHT 2.0UF (860/780/710/670) 10 3111503900 CUSHION MOTOR EPDM EA 6 11 3116601500 SCROLL PLATE HIPS EA 2 12 3112408000 GRILL DISCHARGE HSWR 6B , PI1.5 EA 1 13 3111416500 COVER HOUSING HIPS EA 2 14 3112900400 HINGE DOOR LOWER SGCC,T2.5(HEAT TREATMENT) EA 1 15 3110702000 BUSHING DOOR HINGE POM EA 2 16 31100A9F00 ASSY BOX CONTROL ASSY DPA-246LR/LG EA 1
16-1 3110535900 BOX CONTROL HIPS(V0) EA 1 16-2 3114327400 PCB MAIN 214 X 125MM EA 1 16-3 3114327800 PCB UV LAMP DC12V DUAL LAMP EA 1 16-4 3111416400 COVER BOX CONTROL HIPS(V0) EA 1
17 31100A9900 ASSY FRONT ASSY EA 1
17-1 3114212010 PANEL FRONT HIPS, GY5603A EA 1 17-2 3112202900 FRAME BLADE L HIPS,GY5502A EA 1 17-3 3112203000 FRAME BLADE R HIPS,GY5502A EA 1 17-4 3116503600 BLADE VERTICAL L ABS,GY5502A EA 1 17-5 3116503700 BLADE VERTICAL R ABS,GY5502A EA 1 17-6 3117700400 GEAR FRAME BLADE L POM EA 1 17-7 3117700410 GEAR FRAME BLADE R POM EA 1 17-8 3111416900 COVER FRAME BLADE L HIPS,GY5502A EA 1 17-9 3111417000 COVER FRAME BLADE R HIPS,GY5502A EA 1
17-10 3117700500 GEAR PINION POM EA 1
3111103000 CASE FILTER TOP PP,GY5502A EA 1
17-11
3111910400 FILTER ANTIVIRUS TOP 149*74 EA 1 3111910500 FILTER CARBON TOP 149*74 EA 1
3111910600 FILTER NANO SILVER TOP PE+NANO SILVER EA 1 17-12 3111416600 COVER UV LAMP HIPS,GY5502A EA 1 17-13 3112203200 FRAME UV PP+TALC EA 1 17-14 3114513500 PLATE UV AL,T0.3 EA 1
22
■ PARTS LIST (INDOOR UNIT)
(PAGE 1/2)
Part code Part Name Spec. Unit EA Remark 17-15 3113617800 LAMP UV SLIM UV LAMP OD5.0 6W EA 1 17-16 3113003500 HOLDER UV LAMP SILICON(V0) EA 2
17-17
3107900100 MAGNET FERRITE EA 3
3104504700 PLATE MAGNET SGCC, T0.8 EA 6 17-18 3111416700 COVER DOOR HINGE ABS,GY5502A EA 1 17-19 3112900300 HINGE DOOR TOP SGCC,T2.0 EA 1
18 31100A9H00 ASSY DOOR FRONT ASSY,GY5502A EA 1 18-1 3115502700 WINDOW FRONT T3.2 EA 1 18-2 3112600300 HANDLE DOOR L AL,SV2601BM EA 1 18-3 3112600400 HANDEL DOOR R AL,SV2601BM EA 1 18-4 3111702900 DOOR FRONT HIPS,GY5502A EA 2 18-5 3113003000 HOLDER DOOR TOP ABS,GY5502A EA 1 18-6 3113003100 HOLDER DOOR LOWER ABS,GY5502A EA 1 18-7 3110611300 BRACKET MAGNET SGCC,T0.8 EA 3 18-8 3117500900 EMBLEM KLASSE ABS EA 1
19 31100A9K00 ASSY PANEL DISCHARGE L ASSY,GY5502A EA 1 19-1 3114212200 PANEL DISCHARGE L HIPS,GY5502A EA 1 19-2 3116504000 BLADE LOWER L ABS,GY5502A EA 1
20 31100A9L00 ASSY PANEL DISCHARGE R ASSY EA 1 20-1 3114212300 PANEL DISCHARGE R HIPS,GY5502A EA 1 20-2 3116504100 BLADE LOWER R ABS,GY5502A EA 1
3111103500 CASE FILTER LOWER PP,GY5502A EA 1
21
3111910000 FILTER ANTIVIRUS LOWER 176*77 EA 1 3111910100 FILTER CARBON LOWER 176*77 EA 1 3111910200 FILTER NANO SILVER LOWER PE+NANO SILVER EA 1
22 31100A9G00 ASSY COVER EVAP. FRONT ASSY,GY5502A EA 1 22-1 3111416800 COVER EVAP. FRONT HIPS,GY5502A EA 1 22-2 3111416600 COVER UV LAMP HIPS,GY5502A EA 1 22-3 3112203200 FRAME UV LAMP PP+TALC EA 1 22-4 3114513500 PLATE UV LAMP AL,T0.3 EA 1 22-5 3113617800 LAMP UV SLIM UV LAMP OD5.0 6W EA 1 22-6 3113003500 HOLDER UV LAMP SILICON(V0) EA 2
23 31100A9500 ASSY EVAP. ASSY,DPA-246LR/LG EA 1 23-1 31100A9600 ASSY EVAP. COIL ASSY EA 2 23-2 3118101200 PAN DRAIN TOP HIPS EA 1 23-3 3118101500 PAN DRAIN LOWER HIPS EA 1 23-4 3110611200 BRACKET PLATE EVAP. SGCC,T0.8 EA 1 23-5 31100A9700 ASSY PIPE DISCHARGE ASSY,OD15.88 EA 1 23-6 31100A9800 ASSY PIPE SUCTION (KP-153/183S) ASSY,OD6.35 EA 1 23-7 31100A8L00 ASSY PIPE SUCTION (KP-233S) ASSY,OD9.52 EA 1
24 31100A9J00 ASSY PANEL DISPLAY ASSY,GY5502A EA 1 24-1 3114212400 PANEL DISPLAY TOP HIPS,GY5502A EA 1 24-2 3114212500 PANEL DISPLAY LOWER HIPS,GY5502A EA 1 24-3 3112600500 HANDLE PANEL DISPLAY AL,SPRAY(SV2601BM) EA 1 24-4 3115502800 WINDOW DISPLAY T3.2 EA 1
24-5
3114327700 PCB ASS'Y FRONT DPA-246LR/LG EA 1 3114327600 PCB FRONT 93.5 X 204 EA 1
Loading...
+ 55 hidden pages