Thank you very much for purchasing our Weighing Controller F600AT.
For good performance, and proper and safe use of the F600AT, be sure to read this instruction manual
and properly understand the contents of it before use. Also, carefully keep this instruction manual so
that it can be referred to at any time.
SAFETY PRECAUTIONS
BE SURE TO READ FOR SAFETY
Installation, maintenance and inspection of the F600AT should be performed by personnel having
technical knowledge of electricity.
In order to have an F600AT used safely, notes I would like you to surely follow divide into
"" and "", and are indicated by the following documents. Notes indicated
INTRODUCTION
here are the serious contents related to safely. Please use F600AT after understanding the contents well.
WARNING
This sign forewarns the presence of hazards that could result in serious injury or
fatality when incorrectly handled.
CAUTION
This sign forewarns the presence of hazards that could result in personnel injury or
property damage when incorrectly handled.
I
SAFETY PRECAUTIONS
This sign forewarns the presence of hazards
that could result in serious injury or fatality
when incorrectly handled.
Warning on design
Warning on installation
Warning on wiring
WARNING
● For the entire system to function safely when the F600AT becomes faulty or malfunctions,
provide a safety circuit outside the F600AT.
● Before using the F600AT as described below, make sure to consult with our sales
personnel.
- Use in environments not described in the operation manual.
- Use greatly impacting human lives and assets, such as medical devices, transport devices
entertainment devices, and safety devices.
● Do not modify the F600AT. Doing so may cause fire or electric shocks.
● Do not install in the following environments.
- Places containing corrosive gas or flammable gas.
- Where the product may be splashed with water, oil or chemicals.
● Do not connect a commercial power source directly to the signal input/output terminals.
● Be sure to ground the protective ground terminal.
● The attached AC cable is designed for domestic use in Japan, and its rating is 125V AC, 7A.
For use at voltages exceeding the rating and for overseas use, have a separate AC cable
prepared.
● Before performing the following, make sure that no power is applied.
- Attachment/detachment of connectors of options, etc.
- Wiring/connection of cables to the terminal blocks.
- Connection of the earth cable.
● For connection to the signal input/output terminals, check the signal names and pin
assignment numbers, and then carry out wiring properly.
● Be sure to use crimp contacts for connection to the terminal blocks, and do not to connect
bare wires as they are.
● Be sure to install the attached terminal block cover after wiring to the power input terminals.
Otherwise, electric shocks may result.
● Before applying power, carefully check the wiring, etc.
II
SAFETY PRECAUTIONS
This sign forewarns the presence of hazards
that could result in serious injury or fatality
when incorrectly handled.
Warning during startup and maintenance
This sign forewarns the presence of hazards
that could result in personnel injury or property damage
when incorrectly handled.
Caution on installation
WARNING
● Use at a proper power supply voltage.
● Do not damage the power cord. Doing so may cause fire or electric shocks.
● Do not touch any terminal while applying power. Doing so may cause electric shocks or
malfunctions.
● If the cover of the main body is opened, it may cause an electric shock internally. Even if the
power is off, the internal capacitor is charged. Contact us for internal inspection or repair.
● In the case of smoke, an abnormal smell or strange sound, immediately turn off the power,
and disconnect the power cable.
● As for the batteries used in F600AT, do not at any time dismantle the batteries, change the
batteries shape by subjecting it to pressure or throw the batteries into fires as these may
cause the batteries to explode, catch fire or leak.
Type:CR2477/HFK (old type: CR2477-1HF) made by Panasonic
Voltage:3V
Capacity:1000mAh
CAUTION
● Use the F600AT as it is incorporated in a control panel, etc.
● Do not install in the following environments:
- Locations where temperature or humidity exceeds specifications;
- Locations subjected to drastic temperature fluctuations or icing and condensing;
- Outdoors or locations above 2,000m;
- Locations exposed to direct sunlight;
- Locations subject to dust accumulation;
- Locations with poor ventilation;
- Locations with a lot of salt and metal powder;
- Locations where the main unit is subject to direct vibration and shock.
● Take adequate shielding measures when using at the following locations.
- Near a power line.
- Where a strong electric field or magnetic field is formed.
- Where static electricity, relay noise or the like is generated.
● Install the F600AT as far away from devices generating high frequency, high voltage, large
current, surge, etc., as possible. Also, carry out wiring separately from their power lines. Do
not carry out parallel wiring and common wiring.
● Do not use it, broken down.
III
RoHS-COMPLIANT PRODUCT
This sign forewarns the presence of hazards
that could result in personnel injury or property damage
when incorrectly handled.
Caution on wiring
Caution during startup and maintenance
Caution during transportation
Caution during disposal
CAUTION
● Tighten the screws for the signal input/output terminals at the specified torque.
If they are loose, shorts, fire or malfunctions may occur.
Tightening torque: 0.5N •m
● For sensors, external inputs/outputs, RS-232C and options, use shielded cables.
● The temporary overvoltage applied to the power should not exceed 1500V.
● For turning on/off the power, be sure to keep intervals of 5 seconds or more.
● After power-on, make sure to warm up the F600AT for at least 30 minutes or more before use.
● If the F600AT is not used by the specified method, its protective performance may be
impaired.
● Maintenance
- When performing maintenance, disconnect the power.
- Do not wipe with a wet rag, or with benzine, thinner, alcohol, etc. Doing so may cause
discoloration or deformation of the F600AT. In the case of heavy contamination, wipe off
the contamination with a cloth after dipping it into a diluted neutral detergent and wringing
it well, and then wipe with a soft, dry cloth.
● When the F600AT is shipped, spacers made of corrugated cardboard are used as
cushioning materials.
Though it is factory-designed so that shocks can sufficiently be absorbed, breakage may
result if shocks are applied when the spacers are reused for transportation. If you send the
F600AT to us for repair, etc., take adequate measures against shocks by using polyurethane
materials, etc., separately.
● If you dispose of the product, handle it as industrial waste.
● Remove the lithium batteries used in the F600AT and make sure to dispose them according
to classification of waste collection.
RoHS-COMPLIANT PRODUCT
The parts and attachments (including the instruction manual, packaging box, etc.) used for this unit are
compliant with the RoHS Directive restricting the use of hazardous substances with regard to adverse
effects on the environment and human body.
What is RoHS?
It is an abbreviation for Restriction on Hazardous Substances, which is implemented by the European
Union (EU). The Directive restricts the use of six specific substances in electric and electronic
equipment handled within EU borders. The six substances are lead, mercury, cadmium, hexavalent
chromium, PBB (polybrominated biphenyls), and PBDE (polybrominated diphenyl ethers).
AC power source input connector, DC power source input terminal block,
Analog input/output connector, Signal input/output connector, Frame ground,
Protective ground, RS-232C connector, Option slot
Comparison mode setting,
Comparison inhibiting time/ Judging time/ Completion output time,
Availability of fall compensation/ Fall compensating coefficient/
Average count of fall compensation, Discharge control mode,
Completion signal output mode, Overweight/underweight comparison mode,
HI/LO limit comparison selection,
Near zero comparison selection/ Preset near zero value,
Tare setting selection/ Preset tare value
6. HOW TO SET THE FUNCTIONS ............................................................... 26
For HI/LO limit comparison
(when “HI-LO comp” is selected by comp mode sel.) ,
For final discharge – over weight/under weight comparison
(when “DIS.-O/U” is selected by comp mode sel.) ,
For final discharge – HI/LO limit comparison
(when “DIS.-H/L” is selected by comp mode sel.)
Standard equipment, When the external input/output signals is connected,
When the BCD option is equipped, When the CC-Link option is equipped,
When the DeviceNet option is equipped
20-1. Installation in a Panel ....................................................................... 64
VII
CONTENTS
21. SETTING ITEM LIST ................................................................................ 65
Analog Section, Display Section, Setting section, Communication, Option,
External Input/Output, General Performance
VIII
1. OUTLINE
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
DIGITALINDICATOR
WEIGHING
CONTROLLER
15JAN2008REV.1.00
WEIGHINGCONTROLLER
F600A
F600AT body ・・・1operation manual ・・・1Jumper wire ・・・2AC power cable・・・1
(Only at AC spec.)
[
External input/output connector ・・・1set
Connector : FCN-361J024-AU
Cover : FCN-360C024-B
]
Touch panel display
Status indicator lamp
1-1. Contents of the Package
The packaging box contains the following.
Be sure to check them before use.
1-2. About Connectable Devices
1.OUTLINE
1-3. Appearance Description
1-3-1. Front Panel
1
1.OUTLINE
Weight displayGraph display
AC power source
RS-232C connector
Signal input/output
Analog input/output
connector
Frame ground
Optional slot
Protective ground
connector
input terminal block
*DC spec.
Red (plus)
Black (minus)
DC power source
Notice
- Be aware that the voltage drops depending on the wire thickness and length.
- Never input an AC power source. Doing so will cause a failure.
(Designated when it is shipped)
input terminal block
■ Touch panel display
This is the touch panel display for displaying an indicated value and graph set value and for setting
various setting items of the F600AT. During measurement, a comparison display, hold display and
graph display can be selected according to the function in use.
■ Status indicator lamp
Lamp indicationStatus
Green lightingSteady state
Orange lightingWriting into internal NOVRAM. Do not turn off the power of the F600AT.
Yellow blink
Voltage drop of the internal memory backup battery.
Battery replacement is needed.
■ Prohibition of key operation
Setting of all the key operations or individual key operation ON/OFF is done by "SYSTEM". Please
refer to "9. SYSTEM" on page 34 for details.
1-3-2. Rear Panel
2
■ AC power source input connector/ DC power source input terminal block
About the power cable
- The power cable attached to this product as standard equipment can be used in
the AC100V power supply in Japan. (Official ratings voltage AC125V)
Please use the power cable authorized in the country when you use this product
outside Japan.
- Our company sells following resistance pressure cable AC250V (European
standard product) separately.
Please purchase it from us when you need after confirming its plug shape/voltage.
CA325AC3P-CEE7/7-B2 : CEE7/7 Plug cable (2m)
- AC spec.
Connect with AC power source cable supplied.
AC voltage is 100V to 240V(
+10%, -15%) AC frequency is 50Hz/60Hz.
- DC spec. (Designated when it is shipped.)
1.OUTLINE
Connect DC power source. Voltage input is DC24V (
±15%).
■ Analog input/output connector
Pin No.Signal (6-wire)Signal (4-wire)
1+SIG+SIG
2-SIG-SIG
3+EXC
4+S
5-EXC
6-S
7SHIELDSHIELD
Compatible connector : ETB42-07P
(Connector optional type: CN80)
+EXC
(Connect 3 to 4)
-EXC
(Connect 5 to 6)
3
1.OUTLINE
■ Signal input/output connector
Compatible connector : FCN-361J024-AU
Connector cover: FCN-360C024-B
(Connector & cover optional type: CN50)
A1COMB1COM
A2HH/SP1B2CODE0
A3HI/OVERB3CODE1
A4GO/SP2B4CODE2/KEY_LOCK
A5LO/UNDERB5G/N
A6LL/SP3B6DZ
A7ENDB7TARE ON
A8NZB8TAR E O F F
A9STABB9HOLD/JUDGE
A10ERRB10F/D
A11SI/FB11START
A12SI/FB12STOP
■ Frame ground
Please ground the frame ground terminal to prevent failures due to static electricity.
(The frame and the frame ground terminal are conducted.)
It may be better to remove depending on the environment of the installation location.
■ Protective ground
Be sure to ground the protective ground terminal to prevent electric shocks.
■ RS-232C connector
RS-232C connector to transmit/receive measurement data and status information, etc.
The compatible connector is HOSIDEN-manufactured TCP8080-015267 or equivalent.
Optionally available RS-232C cable (cross) [CA81-232X] is connectable.
■ Option slot
Any one of the following optional boards can be mounted.
- BCD data output
- D/A converter (voltage or current output)
- CC-Link interface
- DeviceNet interface
4
2. CONNECTION
5 mm
Compatible connector : ETB42-07P
Pin No.1
Pin No.7
Loosen.
(Turn counterclockwise.)
Tighten.
(Turn clockwise.)
Pin No.1
Pin No.7
Tighten.
(Turn clockwise.)
Tighten.
(Turn clockwise.)
2-1. Analog Input/Output Terminals Connection
How to connect
1. Strip 5mm of the covering of the wire to be
connected. The size of connectable wires is from
0.21 to 3.31mm
Twist the tip to such an extent that it will not spread out.
3. Loosen the screw with a screwdriver to open the
connection hole.
A Phillips screwdriver 3 to 3.5mm #1 in shaft
diameter is recommended. (Precision screwdriver,
etc.)
2
(AWG12 to 24).
2.CONNECTION
4. Insert the wire into the connection hole so as not to
let the tip spread out.
5. Tighten the screw with the screwdriver.
0.5Nm of tightening torque is recommended.
6. Lightly pull the wire to make sure that it is securely clamped.
7. Insert the wire-connected plug into the F600AT
body, and tighten the screws (two).
5
2.CONNECTION
+IN
-OUT
-IN
Loadcell
+EXC
+S
-S
-EXC
+SIG
-SIG
SHIELD
+OUT
3
4
6
5
1
2
7
+IN
-OUT
-IN
+EXC
+S
-S
-EXC
+SIG
-SIG
SHIELD
+OUT
1
2
3
4
6
5
7
Loadcell
These jumpers MUST be connected.
Notice
The loadcell excitation voltage of the F600AT is 10V. Heating or breakage may occur
unless the loadcells maximum excitation voltage is 10V or more.
2-2. Loadcell Connection
The voltage application of this equipment is 10V, and the maximum current is 120mA, to which up to
four 350Ωloadcells can be connected in parallel.
■ 6-wire connection
The loadcell input of the F600AT is a 6-wire (remote sense) connection. 6-wire shielded loadcell cable
should be used and kept separate from AC or other noise generating wire.
Remote sense lines are used to detect and correct variations in excitation voltage over long cable runs.
■ 4-wire connection
Connect 3 and 4, and 5 and 6 as shown below. Be sure to connect 4 and 6 on the terminal block with the
accessory jumper lines because if the four-wire type is used when 4 and 6 are open, apparent normal
operation is performed, but large errors are made in actuality.
6
2.CONNECTION
R
R
R
R
R
R
+EXC
-SIG
+SIG
-EXC
+EXC
-SIG
-EXC
+SIG
SHIELD
+S
-S
‘n’ (number) loadcells connected in
parallel are considered one unit whose
capacity is ‘n’ x rated capacity of
loadcells (loadcells must have the same
capacity, bridge resistance, and mV/V).
The averaging resistor (R) must be in
same relative ratios with a low
temperature coefficient.
Averaging resistors are not needed if
loadcells were designed for parallel
connection.
Notice
When connecting several loadcells in parallel, loadcell capacity should be higher than
expected load to compensate for mechanical shock or eccentric loading.
R
R
2-3. Connecting Loadcells In Parallel
Some industrial applications require several loadcells connected in parallel (e.g., tank or flow scales).
A summing junction box should be used to facilitate connection and corner correction.
2-4. Strain Gauge Sensor Cable Coloration
Cable colors of sensors may differ from one manufacturer to another (it may even differ from one
model to another for some products). Refer to the sensor manual (or data sheet) and check signal names
and colors in order to connect the cables correctly.
7
2.CONNECTION
Within 6mm
Protective ground
M4
2-5. Power Input Terminal Connection
Connect an AC input cord. The input power source is free in the range of 100 to 240V AC (-15%,
+10%). The frequency is 50/60Hz.
Make connections to the terminal block with a solderless terminal within 6mm in diameter as shown in
the illustration so as not to let the tip of the cable spread out.
1. Make sure that no power is applied.
2. Remove the screws (two), and remove the terminal block
cover.
3. Remove the two screws(“L” and “N”) at the terminal block.
4. Align the solderless terminals with the screw holes, and then
tighten the screws.
5. Install the terminal block cover, and fix it with the screws
(two).
2-6. Protective Ground Connection
The grounding terminal is for prevention of electric shocks.
2
Use an approx. 0.75mm
1. Make sure that no power is applied.
2. Remove the screws(M4) at the protective ground.
3. Align the solderless terminals(M4) with the screw holes, and
then tighten the screws.
thick wire, and be sure to ground.
WARNING
- Connect with no power applied because it may cause an electric shock.
- The attached AC cable is designed for domestic use in Japan, and its rating is 125V
AC, 7A. For use at voltages exceeding the rating and for overseas use, have a
separate AC cable prepared.
- Since the F600AT has no power switch, install a breaker.
8
- Be sure to ground the protective ground terminal to prevent electric shocks.
Do not use other screws than that attached to the main body.
2.CONNECTION
ConverterDisplayPrinter
SI/F
A12
A11
← Inside Outside →
F600AT
Connector
Pan-head machine screw
M2×8 (short) (two)
Nut M2 (four)
Pan-head machine screw
M2×10 (long) (two)
Washer (two)
Case (two)
Screw (two)
2-7. SI/F Connection
The 2-wire serial interface has connective ability for coupling a UNIPULSE printer, external display, etc.
The interface is nonpolarized and up to three external instruments may be connected.
A two-core parallel cable or a cabtyre cable (Wire with covering thickened for construction) may be
used for connection.
When a two-core parallel cable or a cabtyre cable is used, the transmitting distance is approximately
30m. When a two-core shielded twisted pair cable is used, the transmitting distance is approximately
300m.
Do not parallel it with AC lines and high-voltage lines. It may cause of malfunction.
Please refer to "13. AUTOMATIC PRINT" on page 45 for print.
2-8. External I/O Connection
2-8-1. How to assemble the connector
1) Set the connector and screws (two) into the grooves of the case (one side).
2) Cover with the other case, and fit the cases.
3) Tighten the M2×8 pan-head machine screws (two).
Tighten the M2×10 pan-head machine screws (two).
Be aware that washers should be set to the M2×10 pan-head machine screws (two).
9
2.CONNECTION
COM
Spark Killer
Load
F600AT Inside
Spark Killer
DC
Var isto r
Load
AC
Relay
Vext
Supply an external power source for a relay drive power source (Vext).
Output DataTr
0OFF
1ON
- Output Transistor Status
A1
Power Supply
Power Supply
A2 ~ A10
Push
Switch
To rq u e
Switch
Relay
TTL Open Collector
(ON when IN is HI)
F600AT Inside
IN
IN
Open → OFF
Short → ON
- The external element is required to withstand Ic=10mA.
- Leakage from the external element is required to be 100μA or below.
+12V
COM
B1
B2 ~ B12
2-8-2. External output connection
The external output circuit is operated through an open collector.
The open collector output capacity is 50mA and the withstand voltage is up to 30V.
- Equivalent circuit
10
2-8-3. External input connection
A signal is inputted to the signal input circuit by short-circuiting or opening the input terminal and the
COM terminal. Short-circuiting is effected by means of a contact (such as a relay or a switch) or a
noncontact (such as a transistor or an open-collector TTL).
2.CONNECTION
Pin No.Signal name
1
DCD
2
RXD
3
TXD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
Case
F.G.
DCD
DSR
RXD
TXD
DTR
GND
RTS
CTS
1
6
2
3
4
5
7
8
4
3
2
1
6
5
8
7
9
DTR
TXD
RXD
DCD
DSR
GND
CTS
RTS
RI
F600ATPC etc.
Cabling diagram
CA81-232X (optional)
* This connection diagram shows cabling
applicable to the case where your PC is
DTE (data terminal equipment).
For connection with DCE (data circuitterminating equipment), such as a modem
,
use straight type cabling.
* Prepare cabling after reconfirmation of the
connector shape and signal lines (pin
assignments) of the equipment you use.
2-8-4. RS-232C interface connection
This connector connects the RS-232C.
Example of cabling)The following shows an example of connection between DTE-DTE terminals.
This will require modification depending on the equipment to be connected.
For details, see the operation manual of the equipment to be connected.
11
3.SETTING MODE CONFIGURATION
O K
ESCESC
ESC
BACK
BACKBACK
BACK
oror
MODE
ESC
O K
Set value entry from
the ordinary display screen
[Ordinary display screen]
[Mode setting screen]
EACH CODE
Mode Keys
[Set value selection screen]
[Each code setting screen]
Each item
Setting keys
[Set value entry screen]
3. SETTING MODE CONFIGURATION
3-1. F600AT Screen Configuration
12
3-2. About a Setting Call
Operation
Setting call
MODE
by key.
Operation setting
Can be changed
Page 1Page 2Page 3
Example) LOCK2 (Calibration Protection)
This call can be made by the following procedure.
1) Press the key on the ordinary display screen.
2) The mode setting screen appears. Select the mode.
3.SETTING MODE CONFIGURATION
Modes are as follows:
- EACH CODE- COMPARISON- OPERATION
- GRAPH- OPTION- SYSTEM
- CALIBRATION- SEQUENCE MODE- RS-232C
3) The setting function setting screen appears. Select the function.
13
PAGE1
GRAPHIC MODE
(P.33)
TRIGGER LEVEL
(P.33)
X END POINT
(P.33)
Y START POINT
(P.33)
Y END POINT
(P.33)
PAGE2
DRAWING WEIGHT
(P.33)
Ordinary display screen
PAGE1
FINAL
(P.27)
SP1
(P.27)
SP2
(P.27)
CPS
(P.27)
PAGE2
AFFC
(P.27)
OVER
(P.27)
UNDER
(P.27)
PAGE1
COMP MODE SEL.
(P.21)
COMP INH. TIME
(P.21)
JUDGING TIME
(P.21)
COMPLETE OUT T.
(P.21)
AFFC
(P.22)
PAGE2
CPS. COEFFICIENT
(P.22)
AVG. CNT OF AFFC
(P.22)
DIS. CONTROL MODE
(P.24)
COMPLETE SIG. OUT (P.24)
OVER/UNDER COMP. (P.24)
PAGE1
DIGITAL FILTER
(P.28)
ANALOG FILTER
(P.28)
MD (PERIOD)
(P.28)
MD (RANGE)
(P.28)
DISPLAY FREQ.
(P.28)
PAGE2
ZT (PERIOD)
(P.29)
ZT (RANGE)
(P.29)
INDICATE COLOR
(P.29)
BACK LIGHT
(P.30)
PAGE3
HI/LO COMP. SEL
(P.25)
NEAR ZERO COMP
(P.25)
PRESET TARE WGT.1 (P.25)
NEAR ZERO
(P.25)
PRESET TARE WGT.2 (P.25)
PAGE3
DISPLAY SELECT
(P.30)
HI/LO OUT SEL
(P.31)
LOCK1
(P.31)
LOCK2
(P.31)
PAGE1
HH
(P.21)
HI
(P.21)
LO
(P.21)
LL
(P.21)
PAGE1
FINAL
(P.27)
SP1
(P.27)
SP2
(P.27)
CPS
(P.27)
PAGE2
AFFC
(P.27)
HI
(P.27)
LO
(P.27)
Mode setting screen
COMPARISONOPERATIONGRAPHEACH CODE
*2
When “HI-LO COMP” is
selected by COMP MODE SEL
EACH CODE
*2
When “DIS. - O/U” is
selected by COMP MODE SEL.
EACH CODE
*2
When “DIS. - H/L” is
selected by COMP MODE SEL.
FIN
SP2
SP1
CPS
H I
L L
H H
L O
MODE
Mode Keys
FIN
SP2
SP1
CPS
Main display
item
*1
*1 The display item in the main screen changes by the "COMP MODE
SEL." of COMPARISON, and "DISPLAY SELECT" of OPERATION.
*2 The display item in the EACH CODE changes by the "COMP MODE
SEL." of COMPARISON.
3.SETTING MODE CONFIGURATION
3-3. Setting Modes Tree
14
3.SETTING MODE CONFIGURATION
PAGE1
ZERO CAL.
(P.18)
SPAN CAL.
(P.19)
EQUIV. CAL.
(P.18)
BALANCE WGT VALUE((P.18)
MIN. SCALE DIV
(P.18)
PAGE2
NET OVER
(P.19)
GROSS OVER
(P.19)
UNIT DISPLAY
(P.19)
DECIMAL PLACE
(P.18)
DZ REGULATION VAL
(P.20)
CALIBRATION
PAGE1
SEQUENCE MODE
(P.36)
ADJUST FEEDING
(P.36)
AT START NZ CONF.
(P.36)
AT START WV CONF.
(P.37)
ADJ. FEEDING TIME
(P.36)
PAGE2
AZ TIMES
(P.37)
JUDGING TIMES
(P.37)
SEQUENCE MODE
PAGE1
INITIALIZATION
(P.34)
SELFCHECK DSP1
(P.60)
DELFCHECK MEM
(P.60)
SELFCHECK KEY
(P.60)
SELFCHECK EXT
(P.60)
PAGE2
SELFCHECK DSP2
(P.60)
SELFCHECK COM
(P.60)
PASSWORD
(P.34)
LANGUAGE
(P.34)
〔
GROSS/NET
〕 KEY
(P.34)
SYSTEM
PAGE1
COMM. MODE
(P.46)
BAUD RATE
(P.46)
LENGTH
(P.46)
PARITY BIT
(P.46)
STOP BIT
(P.47)
PAGE2
TERMINATOR
(47)
FLOW CONTROL
(P.47)
RS232C
PAGE1
D/A OUTPUT MODE
(P.57)
ZERO OUTPUT
(P.57)
FULLSCALE OUT
(P.57)
D/A OUTPUT
PAGE1
DATA UPDATE RATE
(P.54)
OUTPUT WEIGHT
(P.54)
SELFCHECK
(P.54)
BCD OUTPUT
A setting function
changes by the option.
Refer to attachment for
CC-Link and DeviceNet.
OPTION
PAGE3
[DZ] KEY
(P.34)
[TARE] KEY
(P.34)
[
CURSOR ON/OFF
] KEY
(P.34)
[
START/STOP
] KEY
(P.34)
B4 FUNC. SELECT
(P.35)
15
4.CALIBRATION
Actual Load
Loadcell
Indicated value
F600AT
2.001mV/V - 100.0kg
Rated Outputcapacity
In case of the load
F600AT
Loadcell
Rated output value (mV/V) + Indicated value
A data sheet is attached to a loadcell at the time of purchase.
The data sheet provides data including:
CapacityLoad (in kg, t, etc.)
Rated Outputvoltage (in mV/V)
non-linearity, hysteresis,input resistance,output resistance and zero balance.
Enter the capacity and the rated output value required for equivalent input
calibration into the F600AT.
4. CALIBRATION
Calibration is performed for matching the F600AT to a loadcell. The following two types of calibration
are available for the F600AT.
◇ Actual load calibration
Apply an actual load to the loadcell and enter the actual load value by the keys for calibration.
Calibration is accurately performed with reductions in errors.
◇ Equivalent input calibration
Calibration is performed without an actual load by entering the rated output value (mV/V) and the
capacity (to be indicated) of the strain-gage sensor by the keys. Calibration is easily performed when
no actual load is available.
For example, the gain is automatically determined by entering:
as indicated for a load.
16
4-1. Span Calibration Procedure
Lock2 Release
Unit Setting
Zero Calibration
Calibration Protection
Minimum Scale Division
Span Calibration
Decimal Place
Lock2 Release
Zero Calibration
Calibration Protection
Equivalent Input Calibration
Unit Setting
Minimum Scale Division
Decimal Place
Follow the steps below to perform span calibration.
Release the calibration protection.
Set the unit of the load to be displayed.
Determine the decimal point place of the indicated value.
(Can be omitted if there is no change.)
Enter the minimum value of digital increments.
(Can be omitted if there is no change.)
Set the zero point of the loadcell in no-load condition
(with the loadcell unloaded).
Enter the span (gain) point of the loadcell with a load applied to the
loadcell.
4.CALIBRATION
4-2. Equivalent Input Calibration Procedure
Turn on the calibration protection for preventing misoperation.
Follow the steps below to perform equivalent input calibration.
Release the calibration protection.
Set the unit of the load to be displayed.
Determine the decimal point place of the indicated value.
(Can be omitted if there is no change.)
Enter the minimum value of digital increments.
(Can be omitted if there is no change.)
Set the zero point of the loadcell in no-load condition
(with the loadcell unloaded).
Register the rated output value and capacity of the loadcell.
Turn on the calibration protection for preventing misoperation.
17
4.CALIBRATION
MODE
Twice
[OPERATION]
[LOCK2]
→
→→
MODE
[CALIBRATION]
[MIN. SCALE DIV.]
→
→
Once
→
MODE
[
CALIBRATION
]
[
DECIMAL PLACE
]
→
→
Once
→
→
Once
MODE
[CALIBRATION]
[ZERO CAL.]
→
→
Once
→
MODE
[CALIBRATION]
[EQUIV. CAL.]
→
→
Once
→
About the [BALANCE WGT VALUE] setting
For performing calibration, weight value input can be omitted by setting a weight
value to [BALANCE WGT VALUE] beforehand. [BALANCE WGT VALUE] is ganged
with the weight value inputs of [SPAN CAL.] and [EQUIV. CAL.].
4-3. Calibration Setting
4-3-1. LOCK2 (Calibration value LOCK)
Set values relating to calibration are locked so as not to be changed by misoperation.
Cancel the lock before performing calibration.
Alternatives:[OFF] [ON]
4-3-2. Minimum scale division (Can be omitted if there is no change)
Set the minimum scale division of the indicated value.
Setting range: 001 to 100
4-3-3. Decimal place
Set the decimal point place of the indicated value. Selection can be made from the following.
Alternatives:[NONE] [0.0] [0.00] [0.000]
4-3-4. Zero calibration
Set the zero point in no-load condition.
4-3-5. Equivalent input calibration
Set the rated output value and reading of the sensor.
Rated output value:0.001 to 3.000mV/V
Rated value:00001 to 99999
18
4.CALIBRATION
MODE
[CALIBRATION]
[SPAN CAL.]
→
→
Once
→
MODE
Once
[
CALIBRATION
]
[
NET OVER
]
→→
→
Once
→
MODE
Once
[
CALIBRATION
]
[
GROSS OVER
]
→→
→
Once
→
MODE
Once
[
CALIBRATION
]
[
UNIT DISPLAY
]→→→
Once
→
TARE ON
* It operates it with the net weight (NET) displayed.
YES
NO
RESET
4-3-6. Span calibration
Set the actual load value under an actual load.
Setting range:00001 to 99999 (The decimal point is selectable.)
4-4. Net Over/ Gross Over
When the net weight value or gross weight value exceeds a fixed regulation, an alarm is given by this
function.
NET OVER:00000 to 99999
GROSS OVER:00000 to 99999
The alarm is given when the following conditions are met.
Conditional expressionDisplay
NET OVER
GROSS OVER
Net weight > “NET OVER” set value
Gross weight > “GROSS OVER” set value
4-5. Unit Setting
Set the unit of the load to be displayed.
The display value (calibration value) is not affected by changing the unit.
Alternatives:[NONE] [kg] [t] [g] [N] [lb]
4-6. Tare Subtraction
The net weight is zeroed by this function. The gross weight value is not
changed by this operation.
NET OVER
GROSS OVER
Alternatives:[RESET] [NO] [YES]
: Perform the tare subtraction.
: Go back to the previous screen without executing tare subtraction.
: Reset the tare subtraction.
19
4.CALIBRATION
DZ
* It operates it with the gross weight (GROSS) displayed.
YES
NO
RESET
MODE
Once
[
CALIBRATION
]
[
DZ REGULATION VAL
]
→→
→
Once
→
RESET
4-7. Digital Zero
The gross weight value is zeroed by this function.
Alternatives:[RESET] [NO] [YES]
: Perform the digital zero.
: Go back to the previous screen without executing digital zero.
: Reset the digital zero.
4-7-1. DZ regulation value
By setting the DZ regulation value, the alarm “ZALM” is displayed when operation is performed with
any gross weight value exceeding the range.
Setting range: 0000 to 9999
The displayed “ZALM” can be invalidated by the following method.
DZ reset ....................... Press the key to reset the digital zero.
DZ re-execution.......... Perform digital zero again within the regulation value range.
(Refer to "4-7. Digital Zero" on page 20.)
20
5. COMPARISON SETTING
0
FINAL – SP1
FINAL – SP2
FINAL – CPS
Comparison inhibiting timer
Judging timer
■ Comparison mode setting
Select the comparison mode.
Alternatives:[HI - LO COMP] [DIS. - O/U] [DIS. - H/L]
Explanation of each alternative
HI/LO limit comparison (HI - LO COMP)
The net or gross weight is compared with the set values.
Final discharge – overweight/underweight comparison (DIS. - O/U)
This function is for accurate discharge of the weight value. Overweight/underweight judgment
is made by comparing with the net weight.
Final discharge – HI/LO limit comparison (DIS. - H/L)
This function is for accurate discharge of the weight value. Comparisons are made with the net weight.
High/low limit comparisons are made with the net or gross weight.
5.COMPARISON SETTING
■ Comparison inhibiting time/ Judging time/ Completion output time
Valid in the discharge mode. Comparisons are not made for a fixed time by this function to prevent
inappropriate operation of control and judgment due to mechanical vibrations related to opening and
closing of valves. The length of the completion signal to be output when weighing is completed can
also be set.
COMP.INH.TIMESetting range: 0.00 to 9.99 (sec.)
JUDGING TIMESetting range: 0.00 to 9.99 (sec.)
COMPLETE OUT T.Setting range: 0.00 to 9.99 (sec.)
21
5.COMPARISON SETTING
FINAL – SP1
FINAL – SP2
FINAL – CPS
FINAL
NET
NEAR ZERO
0
Time
STAB output
END output
Completion
ON
ON
Completionl output time setting
OVER
UNDER
output time
Value to be added to or subtracted from the preset fall value.
(D
1
+ D2+ D3・・・・・・DA)
A
× C
■ Availability of fall compensation/ Fall compensating coefficient/
Average count of fall compensation
Variations in fall, which is a major cause of errors in weighing, are automatically compensated by this
Differences (D) between the value set at the final weight and actually weighed value are recorded by
the predetermined number of times (preset number of times) (A) to calculate a mean value, which is
multiplied by the compensating coefficient (C), and the value is added to or subtracted from the preset
fall value.
In order to minimize the errors, the values of D (D
, D2, D3, ... DA) can also be regulated.
1
Setting of automatic fall parameters
AFFCSelect whether or not to use the automatic fall compensating function.
AFFC REGULATION VAL
AVG.CNT OF AFFCSet the number of times of recording the weighed value to calculate a
CPS.COEFFICIENTSet to prevent variations in compensation value through multiplication
22
Set the regulation value to prevent the compensation value from
becoming extremely large (or small). (Each code)
mean value.
by a coefficient of 1 or less.
Example)
TimesActual WeighingError
Average count of AFFC.
CPS
00
← Power ON
120.050+0.05010.500
220.040+0.04020.500
320.070+0.07030.500
420.080+0.080
4 → 0
0.500
+0.240/4 = 0.060
0.060×2/4 = 0.030
→ CPS Value
520.020+0.02010.530
620.000 0.00020.530
720.010+0.01030.530
820.110(+0.110)
← ×3
0.530
920.010+0.010
4 → 0
0.530
+0.040/4 = 0.010
0.010×2/4 = 0.005
→ CPS Value
1019.880(-0.120)
← ×1
0.535
1119.990-0.01010.535
1220.010+0.01020.535
1320.000 0.00030.535
1419.980 0.020
4 → 0
0.535
-0.020/4 = -0.005
-0.005×2/4 = 0.003
→ CPS Value
0.532
Setting CPS coefficient
CPS coefficient can be selected from 1/4, 2/4, 3/4, or 1.
You can get more accurate CPS value by selecting 1 when each weight value is
approximate same in each measuring or by selecting 1/4 to 2/4 when each
weight value fluctuates in each measuring.
5.COMPARISON SETTING
Final20.000
Auto Free Fall Compensation Regulation0.100
Average count of AFFC.4
CPS coefficient2/4
23
5.COMPARISON SETTING
OFF
FEEDING
DISCHARGE
Indeterminate interval (within 50msec.)
F/D (B10)
ON
OFF
Comparison inhibition
Comparison
Indeterminate interval (within 50msec.)
HOLD/JUDGE (B9)
ON
■ Discharge control mode
Valid in the discharge mode. Select FEEDING or DISCHARGE.
By selecting EXTERNAL, switching is carried out between FEEDING and DISCHARGE according to
the level of the input terminal “F/D.”
Alternatives:[FEEDING] [DISCHARGE] [EXTERNAL]
■ Completion signal output mode
Valid in the discharge mode. Select the method of outputting the completion signal.
Alternatives:[JUDGING TIME] [JUD. or STABLE] [JUD. & STABLE]
Explanation of each alternative
JUDGING TIMEThe signal is ON only for the duration of the completion output time after the
JUD. or STABLEThe signal is ON only for the duration of the completion output time after the
JUD. + STABLEThe signal is ON only for the duration of the completion output time after the
judging time has elapsed.
weight value has become stable or the judging time has elapsed.
weight value has become stable and the judging time has elapsed.
■ Overweight/underweight comparison mode
Valid when “DIS.-O/U” is selected by COMP MODE SEL.
Select the method of overweight/underweight comparison.
[COMP.SIG.]Comparisons are made when the completion signal is ON.
[EXT.IN]Comparisons are made when the external judgment input is ON.
[COMP.SIG&H]Comparisons are made when the completion signal is ON, and the weight
value is held.
*
If [EXT.IN] is selected, comparisons are made according to the level of input terminal “HOLD/JUDGE”.
* In the sequence mode (page 40), this setting is ignored, but comparisons are made when the
completion signal is ON, and the weight value is held.
24
5.COMPARISON SETTING
■ HI/LO limit comparison selection
Valid when “HI - LO COMP” or “DIS. - H/L” is selected by COMP MODE SEL.
Select the weight value for HI-HI limit, HI limit, LO limit, and LO - LO limit comparisons.
By selecting [COMP OFF], all comparisons are turned OFF.
Alternatives:[GROSS] [NET] [COMP OFF]
■ Near zero comparison selection/ Preset near zero value
Valid in all comparison modes.
After selecting the weight value for comparisons, if the weight value ≦ preset near zero value, the
status display “NZ” lights, and the “NZ” output turns ON.
By selecting [COMP OFF], the “NZ” output is turned OFF.
NEAR ZERO COMP.: [GROSS] [NET] [COMP OFF] [ABS GROSS]
[ABS NET]
NEAR ZERO:00000 to 99999
NEAR ZERO COMP.Operation near zero
[GROSS]
[NET]
[COMP OFF]Always OFF
[ABS GROSS]
[ABS NET]
ON when gross ≦ near zero setting
ON when net ≦ near zero setting
ON when | gross | ≦ near zero setting
ON when | net | ≦ near zero setting
■ Tare setting selection/ Preset tare value
Valid in all comparison modes.
By turning [PRESET TARE WGT.1] ON, the net changes according to the following expression:
Net = Gross - Preset tare value
(However, if tare subtraction is input, the net weight becomes 0.)
PRESET TARE WGT.1:[OFF] [ON]
PRESET TARE WGT.2:00000 to 99999
25
6.HOW TO SET THE FUNCTIONS
COPY
6. HOW TO SET THE FUNCTIONS
□Code No. selection
Press the /key on the each code setting screen, and specify the code No. you want to set.
Setting range:[0 to 7] [ALL]
When each item is set with the code No. specified as “ALL,” the same set value enters into all of code
0 to 7 on the set item. This function is convenient when there is any item you want to set all code in
common.
□ Code copy
Code can be copied. Press the key on the each code setting
screen. Set source and copy.
Setting range:Source: (0 to 7)
Copy:(0 to 7)
■For HI/LO limit comparison
(when “HI-LO comp” is selected by comp mode sel.)
Setting itemInput range
[HH]±00000 to ±99999
[HI]±00000 to ±99999
[LO]±00000 to ±99999
[LL]±00000 to ±99999
When the weight value > HI-HI limit, the status display “HH” lights, and the signal output “HH/SP1”
turns ON.
When the weight value > HI limit, the status display “HI” lights, and the signal output “HI/OVER”
turns ON.
When the LO limit < weight value < HI limit, the status display “GO” lights, and the signal output
“GO/SP2” turns ON.
When the weight value < LO limit, the status display “LO” lights, and the signal output “LO/
UNDER” turns ON.
When the weight value < LO-LO limit, the status display “LL” lights, and the signal output “LL/SP3”
turns ON.
*1
*1
*1
Select the weight value from net or gross.
*1: Output when the HI/LO limit comparison output is in the “NORMAL” mode.
For the “COMPARATOR” mode, refer to page 31.
26
6.HOW TO SET THE FUNCTIONS
■For final discharge – over weight/under weight comparison
(when “DIS.-O/U” is selected by comp mode sel.)
Setting itemInput range
[FINAL]00000 to 99999
[SP1]00000 to 99999
[SP2]00000 to 99999
[CPS]0000 to 9999
[AFFC]00000 to 99999
[OVER]000 to 999
[UNDER]000 to 999
When the net ≧ final weight – SP1, the status display “SP1” lights, and the signal output “HH/SP1”
turns ON.
*2
When the net ≧ final weight – SP2, the status display “SP2” lights, and the signal output “GO/SP2
turns ON.
*2
When the net ≧ final weight – CPS, the status display “SP3” lights, and the signal output “LL/SP3”
turns ON.
*2
When the net > final weight + over weight, the status display “OVER” lights, and the signal output
“HI/OVER” turns ON.
When the net < final weight – under weight, the status display “UNDER” lights, and the signal output
“LO/UNDER” turns ON.
The fall regulation value “AFFC” relates to the automatic fall compensating function.
*2: Output in the simple comparison mode. For the sequence mode, refer to
page 40.
■For final discharge – HI/LO limit comparison
(when “DIS.-H/L” is selected by comp mode sel.)
Setting itemInput range
[FINAL]00000 to 99999
[SP1]00000 to 99999
[SP2]00000 to 99999
[CPS]0000 to 9999
[AFFC]00000 to 99999
[HI]±00000 to ±99999
[LO]±00000 to ±99999
When the net ≧ final weight – SP1, the status display “SP1” lights, and the signal output “HH/SP1”
turns ON.
When the net≧final weight – SP2, the status display “SP2” lights, and the signal output “GO/SP2 turns
ON.
When the net ≧ final weight – CPS, the status display “SP3” lights, and the signal output “LL/SP3”
turns ON.
When the weight value > HI limit, the signal output “HI/OVER” turns ON.
When the weight value < LO limit, the signal output “LO/UNDER” turns ON.
27
7.OPERATION SETTING
Weight
100mSec
10ms
D
value
7. OPERATION SETTING
■Digital filter
The A/D-converted data is moved and averaged to suppress the instability of the indicated value by this
characteristic. The number of moving averages is selectable in the range of 0 - 256. With an increasing
number, the instability of the indicated value can be suppressed, but the response to input deteriorates.
The input signal from the strain gauge sensor is filtered to cancel unnecessary noise components by this
low-pass filter.
The cutoff frequency is selectable in the range of 2Hz - 8Hz. With an increasing cutoff frequency, the
response accelerates, but noise components may also be displayed.
Alternatives:[2Hz] [4Hz] [6Hz] [8Hz]
■ Motion detect period/ Motion detect range
Set the parameter to detect stability.
When the width of change in weight value falls below the preset range × minimum scale division, and
the state continues for the preset time or more, the weight value is regarded as stable, and the stable
status turns ON.
MD (PERIOD):0.0 to 9.9 (sec.)
MD(RANGE):00 to 99 (CNT)
“D” in the right picture and the range are
compared at each time of A/D conversion, and
when the preset range × minimum scale division
is exceeded, the stable status is turned OFF.
“STAB” is displayed at the upper part of the
unit display section.
The output signal “STAB” turns ON at stable-time.
*
“D” is the difference between the present
weight value and the prior weight value 100ms.
■ Display frequency
Set the frequency of rewriting the display.
The frequency can be set in the range of 1 to 10 times/sec. The internal operation speed does not change.
Setting range: 1 to 10 (times)
28
7.OPERATION SETTING
- Zero tracking automatically takes the zero point at the preset intervals when the
amount of movement of the zero point is less than the preset range × minimum
scale division.
- The period (tracking delay) can be set in the range of 0.1 to 9.9 sec., and the range
(tracking band) can be set in the range of 00 to 99. If the set value is 02, two scale
divisions will result. Also, if the period is set at 0.0 sec. and the range at 00, zero
tracking does not function.
Boundary of zero track
DELAY
Indicated Value
-COUNT
+
0
-
From the point when it returned within the range,
DELAY
+COUNT
BAND
counting will be resumed.
Notice
Since zero tracking should function from the zero point of gross, it does not function if
the indicated value has already exceeded the tracking band. Take the zero point again
by digital zero or zero calibration.
■ Zero tracking period/ Zero tracking range
Slow changes in zero point due to drifting are automatically tracked and compensated by this function.
ZT (PERIOD): 0.0 to 9.9 (sec.)
ZT (RANGE):00 to 99 (CNT)
■ Indicate color
The indicated value display color can be changed.
By setting Comp.(Comparison Result), the indicated value display color changes following the
comparison status.
Alternatives:[Yellow] [Green] [Blue] [Comp.]
【When Comparison mode is “HI-LO COMP”】
OKGreen
HI, LO Yellow
HH, LL Red
【When Comparison mode is “DIS.-O/U”】
NormalBlue
OVER, UNDERRed
【When Comparison mode is “DIS.-H/L”】
NormalBlue
HI, LORed
29
7.OPERATION SETTING
BrightDark
10 min.
60 min.
Light Out
■ Backlight lighting time/ Backlight bright-and-dark time
This function changes the brightness of the backlight when touch screen has not been used for
certain period of time.
The ON time ( lighting time of the backlight) and the Low time ( bright→dark switching time of the
backlight) are set up.
When you use it in the state which a display is always in sight, set the ON time to 0 minutes.
When you want the backlight always bright, set 0 minutes for both the ON time and the Low time.
The backlight is turned bright by touching the panel when the backlight is turned off or it is dark.
Ex.) Set 60 minutes to ON time, 10 minutes to Low time.)
Setting range: 0 to 99 (min.)(with both time)
■ Display table selection
Select the display of set values at the bottom of the weight display screen from three combinations.
The combinations vary with comparison modes.
Alternatives:[F, SP1-3] [F, SP 3, H, L] [F, S P 3 , T, Z]
(* When “DIS.-H/L” is selected)
Explanation of combination in each comparison mode
【For HI/LO limit comparison (when “HI-LO COMP” is selected)】
- HH, H, L, LL(HI-HI limit, HI limit, LO limit, LO-LO limit)
- H, L, T, Z(HI limit, LO limit, Preset TARE, NEAR ZERO)
[SINGLE]Drawing is started by the key, and only one screen is drawn.
[LEVEL]Drawing is started when the drawing weight exceeds the trigger level, or the
]Drawing is started by the key, and drawing is repeated until the
key is input.
key, and only one screen is drawn.
■ Trigger level
Set the graph drawing start level (trigger level) if [LEVEL] has been selected by graphic mode
selection.
Setting range: 00000 to 99999
■ X-axis (time) end point
Set the time to display one screen.The setting range is from 2 sec. to 98 sec. (at intervals of 2 sec.)
The X-axis (time) end point can also be set from the graph screen.
Setting range: 2 to 98 (sec.)
■ Y-axis (load) start point
Set the graph drawing start point. (±00000 to ±99999)
Setting range: ±00000 to ±99999
■ Y-axis (load) end point
Set the graph drawing end point.The Y-axis (load) end point can also be set from the graph screen.
Note) The start point should be smaller than the end point.
Setting range: ±00000 to ±99999
■ Drawing weight selection
Select the weight for drawing.
Alternatives:[GROSS] [NET]
33
9.SYSTEM
GROSS
NET
DZ
TARE ON
CUR.ONCUR.
OFF
START
STOP
9. SYSTEM
■Initialization
All the set values of each setting item are initialized to their factory defaults.
Select the setting item you want to initialize.
Alternatives:[CODE] [COMP.] [OPR.] [CAL.] [etc.]
* If LOCK1/LOCK2 of setting item which you intend to initialize is ON, the initialization cannot be
executed.
■ Password
This setting is for maintenance and inspection. Do not operate.
■ Language
The display language is selectable between Japanese and English.
JPN:JAPANESE
ENG: ENGLISH
■ 〔GROSS/NET〕key
Set OFF/ON of the key operation of / key.
Alternatives:[OFF] [ON]
■ 〔DZ〕key
Set OFF/ON of the key operation of key.
Alternatives:[OFF] [ON]
■ 〔TARE 〕key
Set OFF/ON of the key operation of key.
Alternatives:[OFF] [ON]
■ 〔Cursor ON/OFF〕key
Set OFF/ON of the key operation of / key.
Alternatives:[OFF] [ON]
■ 〔START/STOP〕key
Set OFF/ON of the key operation of / key.
Alternatives:[OFF] [ON]
34
■B4 terminal function selection
When KEY_LOCK terminal function is selected, measurement code that can
be specified from the outside can be specified by CODE0 terminal,CODE1
terminal.
It is limited to CODE number 0 to 3.
Selection of the KEY_LOCK terminal function from the CODE2
terminal function by the B4 Function Selection setting makes the
following effective.
KEY_LOCK:When the terminal is short-circuited,
all key operations are disabled.
9.SYSTEM
35
10.SEQUENCE SETTING
With the near zero confirmation at start time setting “ON,” When the start signal is
input, if the near zero signal is OFF, the feeding gate signal is not turned ON, but a
sequence error results. (Sequence error 4)
10. SEQUENCE SETTING
Operation is performed by following the sequence that weighing is started by inputting the ON edge to
the start signal (external input/output connector pin B11) of the F600AT, and weighing is finished by
the completion signal.
This is valid only in the discharge mode.
Please refer to "11. TIMING CHART" on page 38 for each operation timing.
■ Control mode
Select sequence mode or simple comparison mode.
Alternatives:[SIMPLE COMP.] [SEQUENCE]
■ Adjust feeding/ Adjust feeding time
The setting is valid in the sequence mode.
ADJUST FEEDING:[OFF] [ON]
ADJ.FEEDING TIME:0.00 to 9.99 (sec.)
What is “Adjust feeding”?
If the Net < Final weight – Under weight at the completion signal ON timing (when the judging time
has elapsed after the SP3 signal is turned OFF in the example on P.40), the completion signal is not
turned ON, but the SP3 signal is turned ON for the adjust feeding time.
Adjust feeding is valid only in the “Final discharge – Over weight/Under weight comparison mode”.)
■ Near zero confirmation at start time
The setting is valid in the sequence mode.
Alternatives:[OFF] [ON]
36
■Weight confirmation at start time
When the start signal is input, if
(1) the net ≧ final weight – SP1, or
(2) the final weight – CPS≦0,
the feeding gate signal (SP1, SP2, or SP3) is not turned ON, but a sequence error
results. (Sequence error 5)
((1) is applicable only when the “weight confirmation at start time” setting is ON.)
When the start signal is input, tare subtraction is performed at intervals of these
times.
When the completion signal is turned ON, Over weight/Under weight comparisons
are made at intervals of these times.
The setting is valid in the sequence mode.
Alternatives:[OFF] [ON]
■ AZ times
The setting is valid in the sequence mode.
10.SEQUENCE SETTING
Setting range:00 to 99 times
■ Judging times
The setting is valid in the sequence mode.
Setting range:00 to 99 times
37
11.TIMING CHART
0
NET
Time
OFF
ON
ON
ON
ON
OFF
ON
t3
t2
t1t1
ON
t1: Comparison inhibiting time
COMP.INH.TIME under
COMPARISON
t2: Judging time
JUDGING TIME under
COMPARISON
t3: Completion output time
COMPLETE OUT T. under
COMPARISON
NEAR ZERO
FINAL – SP1
FINAL – SP2
FINAL – CPS
FINAL
NZ output
SP1 output
SP2 output
SP3 output
Comparison
Judging time
STAB output
END output
OVER output
UNDER output
inhibiting time
OVER
UNDER
11.TIMING CHART
11-1. Feed Weighing (In The Simple Comparison Mode)
38
The overweight/underweight comparison timing depends on the OVER/UNDER COMP. setting under
COMPARISON. (It is set at “REGULARLY” in the illustration.)
The END signal output timing depends on the COMPLETE SIG.OUT setting under COMPARISON.
Conditional expression
- NZ outputON when the weight value ≦ preset near zero value
SP1 outputON when the net ≧ preset final weight value – preset SP1 value
-
-
SP2 outputON when the net ≧ preset final weight value – preset SP2 value
SP3 outputON when the net ≧ preset final weight value – preset CPS value
-
- UNDER
- OVER
outputON when the net < preset final weight value – preset underweight value
outputON when the net > preset final weight value + preset overweight value
Select the weight value for near zero comparison from GROSS or NET under COMPARISON setting
menu.
11.TIMING CHART
LO limit
NET
0
Time
t1t1
t2t2
t3t3
NET
GROSS
The near zero signal is used for
discharge completion confirmation
as in the case of feed weighing.
GROSS for high/low limit comparison, and NET for final weight,
before-final-weight,and near zero comparisons.
(In discharge weighing, NET is compared negatively.)
Materials are fed until the HI limit signal is output.
FINAL – SP1
FINAL – SP2
FINAL – CPS
TARE ON input
SP2 output
SP1 output
SP3 output
Comparison
Judging time
LO limit or less
inhibiting time
NZ output
END output
OVER (UNDER)
output
t1: Comparison inhibiting time
COMP.INH.TIME under
COMPARISON
t2: Judging time
JUDGING TIME under
COMPARISON
t3: Completion output time
COMPLETE OUT T. under
COMPARISON
11-2. Discharge Weighing (In The Simple Comparison Mode)
The overweight/underweight comparison timing depends on the OVER/UNDER COMP. setting under
COMPARISON. (It is set at “COMPLETE SIGNAL ON” in the illustration.)
The completion signal output timing depends on the COMPLETE SIG. OUT setting under
COMPARISON.
Conditional expression
- NZ outputON when the weight value ≦ preset near zero value
-
SP1 outputON when the net ≧ preset final weight value – preset SP1 value
SP2 outputON when the net ≧ preset final weight value – preset SP2 value
-
-
SP3 outputON when the net ≧ preset final weight value – preset CPS value
- UNDER
- OVER
outputON when the net < preset final weight value – preset underweight value
outputON when the net > preset final weight value + preset overweight value
Select the weight value for near zero comparison from GROSS or NET under COMPARISON setting
menu.
39
11.TIMING CHART
Comparison
inhibiting time
Judging time
NZ output
0
NET
Time
ON
ON
OFF
t3
ON
ON
ON
ON
t2
t1t1
Hold
t1: Comparison inhibiting time
COMP.INH.TIME under
COMPARISON
t2: Judging time
JUDGING TIME under
COMPARISON
t3: Completion output time
COMPLETE OUT T. under
COMPARISON
OVER
UNDER
FINAL – SP1
FINAL – SP2
FINAL – CPS
FINAL
NEAR ZERO
TARE ON input
START input
STOP input
SP1 output
SP2 output
SP3 output
END output
Completion signal
Judgment output
output time
(OVER or Proper or UNDER)
11-3. Sequence Control
11-3-1. Normal sequence
40
The completion signal output timing depends on the COMPLETE SIG.OUT setting under
COMPARISON.
The overweight/underweight comparison timing is such that the OVER/UNDER COMP. setting under
COMPARISON is ignored, but comparisons are made when the completion output is ON, and the
weight value is held.
Conditional expression
- NZ outputON when the weight value ≦ preset near zero value
* The large/medium/small feeding gate signal is turned ON at the ON edge (OFF → ON) of the START
signal.
- SP1 outputOFF when the net weight ≧ preset final weight value – preset SP1 value
SP2 outputOFF when the net weight ≧ preset final weight value - preset SP2 value
-
SP3 outputOFF when the net weight ≧ preset final weight value – preset CPS value
-
-
UNDER outputON when the net weight < preset final weight value – preset underweight value
-
OVER outputON when the net weight > preset final weight value + preset overweight value
Select the weight value for near zero comparison from GROSS or NET by NEAR ZERO COMP. under
COMPARISON. The sequence mode is valid only in the final discharge mode.
11-3-2. Sequence when the adjust feeding is ON
Completion output time
Adjust feeding time
Judging time
Comparison inhibiting time
Judgment output
END output
SP1 output
ON
ON
ON
ON
ON
Hold
OFF
t2t3t4t1t1t2
START input
STOP input
SP2 output
SP3 output
t1: Comparison inhibiting time
COMP.INH.TIME under
COMPARISON
t2: Judging time
JUDGING TIME under
COMPARISON
t3: Completion output time
COMPLETE OUT T. unde
COMPARISON
t4: Adjust feeding time
ADJ.FEEDING TIME
under SEQUENCE MODE
(OVER)
SP1 output
SP2 output
SP3 output
END output
Comparison inhibiting time
Completion output time
ON
OFF
ON
ON
ON
ON
t3t1t1
t1: Comparison inhibiting time
COMP.INH.TIME under
COMPARISON
t3: Completion output time
COMPLETE OUT T. under
COMPARISON
START input
STOP input
11.TIMING CHART
The completion signal output timing depends on the COMPLETE SIG.OUT setting under
COMPARISON.
The overweight/underweight comparison timing is such that the OVER/UNDER COMP. setting under
COMPARISON is ignored, but comparisons are made when the completion output is ON, and the
weight value is held.
11-3-3. Sequence with no judgment
When the number of JUDGING TIMES under SEQUENCE MODE is 00, overweight/underweight
judgment is not made.
The END signal output timing is such that the COMPLETE SIG.OUT setting is ignored, but it is output
at the OFF edge (ON → OFF) of the final weight signal (SP3 signal).
41
11.TIMING CHART
ON
OFF
ON
ON
ON
ON
START input
STOP input
SP1 output
SP2 output
SP3 output
ERR output
START
AZ times
3 times
TAR E O N
END
Judgment
Fall compensation
Judging times2 times
Average count of automatic
2 times
fall compensation
11-3-4. About the stop signal
When the STOP signal is turned ON, all the signals of the SP1 output, SP2 output and SP3 output are
turned OFF.
If the START signal is turned ON when the STOP signal is ON, a sequence error will result.
For resetting the sequence error, input the stop signal again.
11-3-5. Relationship between AZ times, judging times, and
automatic fall compensation
【Example: AZ times=3, JUDGING times=2, AVG.CNT of AFFC=2】
When the number of AZ times is set at 01, tare subtraction is performed at each time when weighing is
started.
When the number of AZ times is set at 02 to 99, tare subtraction is performed at the intervals of these
times.
When the number of AZ times is set at 00, the AZ function is turned OFF.
When the number of judging times is set at 01, judgment is made at each time when weighing is
finished.
When the number of judging times is set at 02 to 99, judgment is made at the intervals of these times.
When the number of judging times is set at 00, overweight/underweight comparisons are not made.
Since weighed values for automatic fall compensation are sampled at the time of judgment, the
automatic fall compensation does not function when no judgment is made.
42
12.EXTERNAL INPUT/OUTPUT SIGNALS
12. EXTERNAL INPUT/OUTPUT SIGNALS
■External input signals
(1) CODE0 to CODE2 <Level input> (B2, B3, B4)
Input signals to specify codes for weighing externally.
CODE2CODE1CODE0Selected CODE
OpenOpenOpen0
OpenOpenShorted1
OpenShortedOpen2
OpenShortedShorted3
ShortedOpenOpen4
ShortedOpenShorted5
ShortedShortedOpen6
ShortedShortedShorted7
* CODE2 is also usable as a Key LOCK terminal.
(Refer to " ■ B4 terminal function selection" on page 35.)
(2) G/N (GROSS/NET) switching <Edge input> (B5)
The weight value of the main unit and indicator is switched.
The ON edge (OFF → ON) of the external input will result in gross display (GROSS).
The OFF edge (ON → OFF) of the external input will result in net display (NET).
(3) D/Z (Digital zero) <Edge input> (B6)
The ON edge (OFF → ON) of the external input will zero the gross weight.
However, the range that can be zeroed is within the DZ regulation value. Out of this range, zero
will not result, but “ZALM” will light.
(4) TARE ON (Tare subtraction) <Edge input> (B7)
The ON edge (OFF → ON) of the external input will result in immediate tare subtraction to zero
the net weight.
(5) TARE OFF (Tare subtraction reset) <Edge input> (B8)
The ON edge (OFF → ON) of the external input will reset the above tare subtraction. However,
the tare setting is not cancelled.
(6) HOLD (Hold) <Level input> (B9)
As long as the external input is ON, the weight value and comparison are held.
* “HOLD” lights during holding.
* This input terminal can be set to judgment input. It cannot be used for holding in the sequence
mode and when over/under comparison is made by external judgment.
(7) JUDGE (Judgment) <Level input> (B9)
This is valid when over/under comparison is set to external judgment input. (Refer to page 24.)
* This input terminal can be set to HOLD.
43
12.EXTERNAL INPUT/OUTPUT SIGNALS
These are valid when the control is
in the sequence mode.
(Refer to page 42.)
Pulse width:
OFF
ON
OFF
ON
Indeterminate interval
Charge controlDischarge control
< Edge input >< Level input >
50m sec. or more.
(within 50m sec.)
Varies depending on the comparison mode.
(Refer to page 26.)
(8) F/D (Charge/Discharge) <Level input> (B10)
This is valid when charge/discharge selection is external.
OFF will result in charge control, and ON will result in discharge control. (Refer to page 24.)
(9) START (Start) <Edge input>
(10) STOP (Stop) <Edge input, Level input>
■ External output signal
(1) HH/SP1 (Comparison output) (A2)
(2) HI/OVER (Comparison output) (A3)
(3) GO/SP2 (Comparison output) (A4)
(4) LO/UNDER (Comparison output) (A5)
(5) LL/SP3 (Comparison output) (A6)
(6) END (Completion) (A7)
This indicates measurement completion output, which is valid only in the “carving-out” mode.
(7) NZ (Near zero) (A8)
This is near zero comparison output. (Refer to page 25.)
(8) STAB (Stable) (A9)
This turns ON when a stable. (Refer to page 28.)
(9) ERR (Weight error or sequence error) (A10)
This turns ON when a weight error or sequence error occurs.
44
13. AUTOMATIC PRINT
TheF600AT can output an automatic print command to the printer or indicator connected to the SI/F.
The automatic print output timing varies depending on the setting.
13-1. In HI/LO Limit Comparison
The command is output at the ON edge of the stable status when the near zero signal is OFF. If the
automatic print is output, it can next be output after the near zero signal is once turned ON.
13-2. In The Discharge Mode; Simple Comparison Mode
The command is output at each ON edge of the completion signal. The value of the number of judging
times is ignored.
13-3. In The Discharge Mode; Sequence Mode
13.AUTOMATIC PRINT
The command is output at the ON edge of the completion signal at the intervals of judging times. When
the number of judging times is 0, the automatic print is not output.
45
14.RS-232C INTERFACE
14. RS-232C INTERFACE
The RS-232C is an interface to read the indicated value and status of the F600AT and to write
parameters into the F600AT.
This interface is convenient to process controls, totals, records, etc., by connecting the F600AT to a
computer, process controller, sequencer or the like.
Set the RS-232C communication conditions of the F600AT.
■ Communication mode
Alternatives:[HAND SH.] [CONTINUITY] [AT PRINT]
HAND SH.
Communications are carried out according to the commands from the host computer.
Reading of weight values, status and set values, writing of set values, and instructions of operations can
be performed.
CONTINUITY
The displayed weight value and status are transmitted continuously.
AT PRINT
The displayed weight value and status are transmitted at the print timing.
For the print timing, refer to "13 AUTOMATIC PRINT" on page 45.
-LOAD occurred
GROSS OVER occurred
NET OVER occurred
No error
Host
F600AT
RG
RG0000000
Ter minator
CR
: 4
: 3
: 5
: 4
: 2
: 1
: 3
: 1
: 0
: 1
: 0
Weight error
No Weight error
In equivalent input calibration
In span calibration
In zero calibration
In weighing
Host
F600AT
W0
W0 2± 1 000
CR
0
Termin ator
2
Command No.
Parameter No.5-digit parameter (no decimal point)
Sign
Host
F600AT
W0 2± 1 0000CR
Command No.5-digit parameter (no decimal point)
Sign
Host
F600AT
W0
W0 0 0 0 000
CR
0
Parameter code 0 to 7
Ter minat or
Host
F600AT
W0000000CR
Parameter code 0 to 7
- Status read (7-digit)
- Status read (7-digit)
- Parameter read (example: High limit)
- Parameter write (example: High limit)
* When you write in a setup which it is not with the sign, put “0” in the sign digit.
* Please refer to "21 SETTING ITEM LIST" on page 65 for command No. and the number of
set digits.
- Parameter code read
48
- Parameter code write
- Command
- Please refer to "21 SETTING ITEM LIST" on page 65 for command No. of parameter read(write) and parameter digit.
- When the digit is less than five digits, it treats by "0".
Example) Comparison prohibition time read
Host
F600AT
W3
W3 2 0 0 099
CR
2
Terminator
9
Parameter
Sign
Command No.
It sends it back by 0.
SPAN CALIBRATION
NET SELECTION
DIGITAL ZERO RESET
EQUIV. CALIBRATION
ZERO CALIBRATION
GROSS SELECTION
TARE SUBTRACTION
DIGITAL ZERO
PRINT INSTRUCTION
equipment connected to SI/F as desired.
ACCR
CCCR
ECCR
GCCR
ICCR
BCCR
DCCR
FCCR
HCCR
LCCR
TARE RESET
* Refer to below.
* A print instruction is given to the
How to use the CL command (equivalent input calibration execution)
1)
Correct values should previously be set to “equivalent input calibration” and “weight value”.
Therefore, check the rated output and rated capacity of the load cell as in the case of
equivalent input calibration by the touch panel.
Example) It is assumed that the rated output and the rated capacity of the load cell are
2.000mV/V and 100.00kg, respectively.
2) Set the rated input by using the command W83 (equivalent input calibration).
Example) For 100.00kg (assuming that the decimal point is positioned as 0.00), input as
follows:
3) Set the rated capacity by using the command W84 (weight value).
Example) For 100.00kg (assuming that the decimal point is positioned as 0.00), input as
follows:
4) Give the equivalent input calibration execution command (CL).
This allows slope calculation from the currently registered “weight value” and
“equivalent input calibration” value.
W83002000CRLF
Input 2.000mV/V as a value of 2000 with no decimal point.
W84010000CRLF
Input 100.00kg as a value of 10000 with no decimal point.
14.RS-232C INTERFACE
49
14.RS-232C INTERFACE
±
Header
Sign
Ter minato r
GS,
,
,
,
,,
*1
*2*3
*4*5
Weight value (with a decimal point)
14-3-2. Continuous transmission/ Transmission at print-time
The formats of continuous transmission and transmission at print-time are common.
Parameters cannot be read or written.
Header
When the gross weight is displayed, the header becomes “GS”, and the gross weight is transmitted.
When the net weight is displayed, the header becomes “NT”, and the net weight is transmitted.
*1H ....... In holding
O ....... Weight error
S........ Stable
M....... Unstable
*2T........ Zero tracking ON
A ....... Zero tracking OFF
*3For HI/LO limit comparison For final weight (DIS.-O/U)
and final weight (DIS.-H/L)
F........ Comparison OFFG ....... OVER and UNDER OFF
G ....... HI and LO OFFV ....... OVER ON
N ....... HI and LO ONU ....... UNDER ON
H ....... HI ON
L........ LO ON
*4For HI/LO limit comparisonFor final discharge mode
F........ Comparison OFFE ........Completion ON
G ....... HH and LL OFF3 ........ SP3 ON
N ....... HH and LL ON2 ........ SP2 ON
H ....... HH ON1 ........SP1 ON
L........ LL ONG ....... Completion, SP1, SP2, and SP3 OFF
*5N ....... Near zero OFF
Z........ Near zero ON
50
15. BCD DATA OUTPUT (OPTION)
Special-purpose
connector
The BCD data output is an interface to extract the indicated value of the F600AT as BCD data. This
interface is convenient to process controls, totals, records, etc., by connecting the F600AT to a
computer, process controller, sequencer or the like.
The I/O and internal circuits are electrically insulated by photocoupler.
15.BCD DATA OUTPUT (OPTION)
15-1. Connector Pin Assignment
32 pin
No.SignalNo.Signal
A1*COMB1*COM
A2OUT1B2OUT1000
A3OUT2B3OUT2000
A4OUT4B4OUT4000
A5OUT8B5OUT8000
A6OUT10B6OUT10000
A7OUT20B7OUT20000
A8OUT40B8OUT40000
A9OUT80B9OUT80000
A10OUT100B10OUTMinus (Polarity)
A11OUT200B11OUTOVER
A12OUT400B12OUTSTAB
A13OUT800B13OUTSTROBE
A14INBCD Data HoldB14INLogic Switching
A15INNCB15INNC
A16-B16-
Compatible connector: FCN-361J032-AU (manufactured by FUJITSU COMPONENT or equivalent)
Connector cover:FCN-360C032-B (manufactured by FUJITSU COMPONENT or equivalent)
(Connector & cover optional type: CN51)
51
15.BCD DATA OUTPUT (OPTION)
F600AT
Inside
Vcc
+5V
COM
Ve x t
Vceo=30V(max)
Ic =50mA (max)
- Internal transistor status
Output data NegativePositive
0OFFON
1ONOFF
- Output pin level
Output data NegativePositive
0
HL
1
LH
Through logic switching (B14)
Outside
Vcc
F600AT
Inside
IC=
COM
SwitchTransistor
+5V
TTL open collector output
(ON when IN is HI)
Outside
OpenOFF
ShortON
Approx.6mA
Notice
- Do not apply external voltage to the signal input circuit.
- The external element is required to withstand Ic=10mA.
- Leakage from the external element is required to be 30μA or below.
15-2. Equivalent Circuit
- Output
The signal output circuit is operated through a TTL open collector.
- Input
15-3. Signal Input
Logic Switching (B14)
52
The output signal logic is switched. (The strobe signal logic is also switched.)
If open, negative logic will result, and if shorted with COM, positive logic will result.
BCD data hold (A14)
BCD data is held when shorted with COM.
No strobe pulse is output.
15.BCD DATA OUTPUT (OPTION)
BCD data
P. C
ON
BCD data
P. C
ON
BCD data
ON
OFF
STROBE
(DUTY about 50%)
If the update rate is changed, the strobe pulse width is also changed proportionally.
15-4. Signal Output Timing
- P.C
Note: P.C should also be acquired in synchronization with the strobe signal as in the case of
the data signal. (Refer to page 53.)
● HI/LO limit output
ON at stable-time, OFF at unstable-time.
● In the discharge control mode; simple comparison mode
The signal is output at each ON edge of the completion signal. The value of the number of judging
times is ignored.
● In the discharge control mode; sequence mode
The signal is output at the ON edge of the completion signal at the intervals of judging times.
- OVER
The signal is output with +ADC OVER (+LOAD) or -ADC OVER (-LOAD) overflow (NET OVER or
GROSS OVER).
- STROBE
Strobe pulses are output in synchronization with BCD data. For reading the data, use the pulse rising
edge(ON → OFF). The BCD data update rate can be changed by setting.
Note: The logic on the software varies depending on the equipment on the receiving side.
Select the weight value for BCD output. If “INDICATE” is selected, the weight indicated by the
indicator is output.
15-6. Self Check
The BCD input/output status can be checked from bit to bit.
Each input turns green when its ON state is recognized.
Each output turns on when the corresponding button is pressed.
54
16. D/A CONVERTER (OPTION)
Voltage/ Current output terminals:
Terminals to extract voltage or current signals.
0 to +10V and 4 to 20mA can be obtained by the
voltage output and current output, respectively.
+
-
+
-
External equipment
Load resistance:
2kΩ or more
SIG
← Inside Outside →
F600AT
D/A CONVERTER
V OUT
+
-
+
-
External equipment
Load resistance:
350Ω or less
SIG
← Inside Outside →
F600AT
D/A CONVERTER
I OUT
D/A converter is provided for obtaining analog output synchronized with the indicated value of the
F600AT.
The analog output ranges are 0 to +10V output or 4 to 20mA constant-current output.
By using the D/A zero setting and D/A full scale setting functions, analog output can be obtained
between zero (0V, 4mA) and full scale (+10V, 20mA) with respect to the predetermined digital value.
The output circuit and the main unit circuit are isolated. The resolution is 1/10000 to 0 to +10V, and the
conversion rate is 2000 times/sec. The output has an overrange of approx. ±10%FS.
* Either voltage output or current output can be mounted.
16.D/A CONVERTER (OPTION)
- Taking voltage output signals
Connect external equipment (2kΩ or more load resistance) to + and - of the F600AT.
For connection, refer to "Connection of the D/A Converter Options" page 56.
- Taking current output signals
Connect external equipment (350Ω or less load resistance) to + and - of the F600AT.
55
16.D/A CONVERTER (OPTION)
Notice
- The D/A converter is optional.
- Do not apply external voltage because it will break.
- Do not short-circuit the voltage output because a failure will occur.
Also, connecting a capacitive load may cause oscillation.
Notice
- Cable can be from 24 to 14AWG (0.2 to 2.5mm2).
- It is not necessary to solder the cable wires or to fix a solderless terminal.
- If several cables to be inserted to the same hole, twist those cable wires together and
insert.
- Resolution
The D/A converter has a resolution of 1/10000 to 0 to 10V (4 to 20mA).
16-1. Connection of the D/A Converter Options
The terminal block for the D/A converter options is the cage clamp type. Connect according to the
following procedures.
As for wire materials, use parallel 2-core cables, cabtyre cables, or the like.
Connect to the cage clamp type terminal block by using the attached miniscrewdriver.
1) Strip the casing 0.2in (6mm) on the cable to be connected.
Twist the bare wire to fit the terminal hole.
2) Insert the supplied screwdriver into the upper hole and lift
upward.
3) Insert the twisted wires into the lower hole.
4) Pull the screwdriver out from the upper hole.
5) Make sure cable is clamped securely and does not come out
ZERO SCALE:The output is fixed at zero output (0V or 4mA).
FULL SCALE:The output is fixed at full scale (10V or 20mA).
■ Zero output
Set the indicated value for outputting 4mA (0V).
Setting range: 0 ~ 99999
16.D/A CONVERTER (OPTION)
■ Full scale output
Set the indicated value for outputting 20mA (10V).
Setting range: 0 ~ 99999 (However, the preset zero output value should be smaller than
the preset full scale value.)
How to adjust
Adjust the output with the dummy trimmer that appears on the adjustment screen after selecting each
fixed output in the D/A output mode setting and pressing the key.
While monitoring the output value, finely adjust the output with the dummy trimmer the UP/DOWN
・ keys, and press the key to confirm, so that the trimmer position is entered.
*
Pressing the dummy trimmer
* The trimmer adjusting ranges are as follows: voltage; ±1.0V, and current; ±1.6mA.
* The reset key resets the dummy trimmer position to the trimmer center point (0%).
the UP/DOWN
・
keys
continuously performs continuous operation.
57
17.ERROR MESSAGE
17. ERROR MESSAGE
“+LOAD” or “-LOAD”
Voltage exceeding the ADC input range is input.
Check to see if the output voltage of the loadcell exceeds the range, and check the cables for breaks.
This message is also displayed when wiring is incorrect or nothing is connected.
“NET OVER”
The net weight value exceeds the “NET OVER” set value. Check the “NET OVER” set value.
“GROSS OVER”
The gross weight exceeds the “GROSS OVER” set value. Check the “GROSS OVER” set value.
“GRAPH ERR”
[Cause]
The set value of the “Y-axis (load) start point” is larger than the set value of the “Y-axis (load) end
point”.
[Remedy]
Set again so that the “Y-axis (load) start point” becomes smaller than the “Y-axis (load) end point”.
“LOCK IS ON”
[Cause]
Key operation is locked.
[Remedy]
Please make the key operation "ON" referring to following instructions.
" ■ LOCK1/LOCK2" on page 31, " ■〔GROSS/NET〕key" on page 34, " ■〔DZ〕key" on
page 34, " ■ 〔TARE〕key" on page 34, " ■ 〔Cursor ON/OFF〕key" on page 34, " ■ 〔START/
STOP〕key" on page 34.
Moreover, please turn OFF external KEY_LOCK input when KEY_LOCK of B4 Function Selection is
set.
“SEQ. ERR 1”
[Cause]
The stop signal is ON when the weighing start signal is turned ON.
[Remedy]
Turn the stop signal OFF.
58
“SEQ. ERR 2”
[Cause]
The stop signal is turned ON during weighing in sequence control.
17.ERROR MESSAGE
How to reset the sequence error
The sequence error is reset by inputting the stop signal (OFF → ON).
“SEQ. ERR 4”
[Cause]
The near zero signal is OFF when weighing is started.
(On condition that it is set to confirm the near zero signal when weighing is started.)
[Remedy]
First, check the preset near zero value and near zero comparison target.
Next, check to see if:
1. A start was made in spite of incomplete discharge.
2. The start ON timing was too early.
3. Discharged items are jammed.
“SEQ. ERR 5”
[Cause]
1. The SP1 output is ON when weighing is started.
(On condition that it is set to confirm the weight value when weighing is started.)
2. Final weight – CPS ≦ 0.
[Remedy]
First, check the preset SP1 value, preset fall value, and preset final weight value.
Next, check to see if:
1. A start was made in spite of incomplete discharge.
2. The start ON timing was too early.
3. Discharged items are jammed.
4. Another code was selected.
59
18.SELF-CHECK
Star t
ESC
Bright
Dark
Light Out
Trns.
18. SELF-CHECK
Self-check is performed when the setting is called.
■ Self-check DSP1
Check the display to see that it is free from color and display defects, etc. The screen changes from red,
green, blue, horizontal stripes, to vertical stripes. Touching the screen restores the previous screen.
■ Self-check MEM
Check the memory to see that it is free from defects. The result is
displayed in a moment after the key at the lower right of the
screen is pressed. Or, check the version here.
■ Self-check KEY
Check the touch panel to see that it is free from unrecognized parts.
One touched square turns yellow. Pressing the key at the upper
right of the screen restores the previous screen
■ Self-check EXT
Check the operations of the external input/output signals.
Each output turns on when the corresponding key is pressed.
Each input turns green when its ON state is recognized.
■ Self-check DSP2
Check the backlight and status indicator lamp.
The backlight turns bright by pressing "" button, and turns
dark by pressing "" button.
The backlight goes out when the "" button is pressed, and after
that, it recovers when the screen is touched.
The status indicator lamp lights in green and orange alternately.
■ Self-check COM
The data displayed under "Transmit data" is sent by pressing the
key.
Under "Receive data", externally transmitted data is displayed.
60
19. BLOCK DIAGRAM
Lithem
battery
Low-pass
Fillter
SHIELD
FRAME
×100
MPU
+5VI +12VI-9VA +5VD
DigitalIsolation
Power Supply Unit
+9VA
Serial
Port
Port
Port
Serial
Port
Port
Watch
Dog
CPU
32bit
RAM
16kbyte
NOV.RAM
4096bit
LCD
Driver
LCD
Flash
ROM
SI/F
DeviceNet
BCD
256kbyte
+EXC
-EXC
+SIG
-SIG
+S
-S
Analogue
External
SRAM
External
Flash
ROM
Serial
Port
RS-232C
CC-Link
D/A
(DAVorDAI)
Option
Standard
A/D
Converter
Referrence
Voltage
Excitation
Voltage
Control
Input
11Line
Control
Input
9Line
To uc h
Panel
Input
AC IN
FRAME
19.BLOCK DIAGRAM
61
20.DIMENSIONS
Unit: mm
< Front ><Side ><Rear >
<
To p >
Unit: mm
< Front ><Side ><Rear >
<
To p >
20. DIMENSIONS
■ Standard equipment
■ When the external input/output signals is connected
62
■ When the BCD option is equipped
Unit: mm
< Front ><Side ><Rear >
<
Top >
Unit: mm
< Front ><Side ><Rear >
<
Top >
20.DIMENSIONS
■ When the CC-Link option is equipped
63
20.DIMENSIONS
Unit: mm
< Front ><Side ><Rear >
<
Top >
Panel-cut
Panel thickness
92mm
+1
-
0
1.6 to 3.2mm
92mm
+1
-
0
dimensions
■ When the DeviceNet option is equipped
20-1. Installation in a Panel
To install the F600AT into a control panel, use the following procedure.
1. Make a hole in the panel according to the panel-cut
dimensions.
2. Remove the screws (two), and remove the guide rails
from both sides.
* Do not use other screws than those installed to
the F600AT body
3. Fit in the F600AT from the front of the panel.
4. Install from the rear the guide rails having been
removed from both sides in Step 2, and fix them with
the screws (two).
64
21. SETTING ITEM LIST
* L1:Setting that LOCK is controlled by LOCK1
* L2:Setting that LOCK is controlled by LOCK2
* S:Saved in SRAM (Lithium-battery-backed-up)
* N:Saved in NOV.RAM (Saved in non-volatile memory)
EACH CODE (Comparison mode: HI-LO COMP)
21.SETTING ITEM LIST
PAG E
1HH000.00
2HI000.00
1
3LO000.00
4LL000.00
ParameterInitial valueL1 L2 S
CODE0
EACH CODE (Comparison mode: DIS.-O/U)
PAG E
1FINAL000.00
2SP1000.00
1
3SP2000.00
4CPS00.00
5AFFC098.00
2
6OVER0.00
7UNDER0.00
ParameterInitial valueL1 L2 S
CODE0
N
○
〇〇
〇〇
〇〇
〇〇
N
○
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
Alternatives・Setting range
0 ~ 700(R/W)
±00000 ~ ±9999901(R/W)
±00000 ~ ±9999902(R/W)
±00000 ~ ±9999903(R/W)
±00000 ~ ±9999904(R/W)
Alternatives・Setting range
0 ~ 700(R/W)
00000 ~ 9999911(R/W)
00000 ~ 9999912(R/W)
00000 ~ 9999913(R/W)
0000 ~ 999914(R/W)
00000 ~ 9999915(R/W)
000 ~ 99916(R/W)
000 ~ 99917(R/W)
Communication
Command
No.
Communication
Command
No.
EACH CODE (Comparison mode: DIS.-H/L)
PAG E
1FINAL000.00
2SP1000.00
1
3SP2000.00
4CPS00.00
5AFFC098.00
2
6HI000.00
7LO000.00
ParameterInitial valueL1 L2 S
CODE0
N
○
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
Alternatives・Setting range
0 ~ 700(R/W)
00000 ~ 9999911(R/W)
00000 ~ 9999912(R/W)
00000 ~ 9999913(R/W)
0000 ~ 999914(R/W)
00000 ~ 9999915(R/W)
±00000 ~ ±9999902(R/W)
±00000 ~ ±9999903(R/W)
Communication
Command
No.
65
21.SETTING ITEM LIST
COMPARISON
PAG E
ParameterInitial valueL1 L2 S
1COMP MODE SEL.HI-LO COMP
2COMP. INH. TIME0.50sec.
1
3JUDGING TIME1.50sec.
4COMPLETE OUT T.3.00sec.
5AFFCON
6CPS. COFFICIENT1/1
7AVG. CNT OF AFFC4times
8DIS. CONTROL MODEFEEDING
2
9COMPLETE SIG. OUT
10OVER/UNDER COMP.REGULARLY
11HI/LO COMP. SELGROSS
12NEAR ZERO COMP.GROSS
3
13PRESET TARE WGT.1ON
14NEAR ZERO000.00
15PRESET TARE WGT.2000.00
JUDGING
TIME
N
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
Alternatives・Setting range
0:[HI-LO COMP]1:[DIS.-O/U]
2:[DIS.-H/L]
0.00 ~ 9.9932(R/W)
0.00 ~ 9.9933(R/W)
0.00 ~ 9.9934(R/W)
0:[OFF] 1:[ON]
0:[1/1]1:[3/4]2:[2/4]3:[1/4]
1 ~ 937(R/W)
0:[FEEDING]1:[DISCHARGE]
2:[EXTERNAL]
0:[JUDGING TIME]1:[JUD.or STABLE
2:[JUD.& STABLE
]
0:[REGULARLY]1:[COMP. SIG.]
2:[EXT. IN]3:[COMP. SIG&H]
0:[GROSS]1:[NET]2:[COMP OFF
0:[GROSS]1:[NET]
2:[COMP OFF]3:[ABS GROSS]
4:[ABS NET]
0:[OFF]1:[ON]
00000 ~ 999993E(R/W)
00000 ~ 999993F(R/W)
Communication
Command
]
]
No.
31(R/W)
35(R/W)
36(R/W)
38(R/W)
39(R/W)
3A(R/W)
3B(R/W)
3C(R/W)
3D(R/W)
OPERATION
PAG E
1DIGITAL FILTER16times
1
2ANALOG FILTER6Hz
3MD (PERIOD)1.5sec.
4MD (RANGE)10CNT
5DISPLAY FREQ.10times
6ZT (PERIOD)0.0sec.
7ZT (RANGE)00CNT
8
2
9INDICATE COLORYellow
10
11DISPLAY SELECT
12HI/LO OUT SEL
3
13LOCK1OFF
14LOCK2OFF
ParameterInitial valueL1 L2 S
BACKLIGHT
BRIGHT-AND-DARK TIME
BACKLIGHT
LIGHTING TIME
(*) It changes with comparison modes. (Refer to page 30.)
0minute
10minutes
HH,H,L,LL (*)
NORMAL
N
〇〇
〇〇
0:[2Hz]1:[4Hz]2:[6Hz]3:[8Hz
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
0:[NORMAL]1:[COMPARATOR]
〇
〇
Alternatives・Setting range
0:[OFF]1:[2times]2:[4times]
3:[8times]4:[16times]
5:[32times]6:[64times]
7:[128times]8:[256times]
0.0 ~ 9.943(R/W)
00 ~ 9944(R/W)
01 ~ 1045(R/W)
0.0 ~ 9.946(R/W)
00 ~ 9947(R/W)
00 ~ 9948(R/W)
0:[Ye ll ow ]1:[Green]
2:[Blue]3:[Comparison]
00 ~ 994A(R/W)
0:[F, S P 1 - 3]1:[F, S P 3, H , L]
2:[F, S P 3 , T, Z ] (*)
0:[OFF]1:[ON]
0:[OFF]1:[ON]
]
Communication
Command
No.
41(R/W)
42(R/W)
49(R/W)
4B(R/W)
4C(R/W)
4D(R)
4E(R)
66
GRAPH
21.SETTING ITEM LIST
PAG E
ParameterInitial valueL1 L2 S
1GRAPHIC MODECONTINUITY
2TRIGGER LEVEL001.00
1
3X END POINT10sec.
4Y START POINT000.00
5Y END POINT100.00
26DRAWING WEIGHT
NET
OPTION (In case of used BCD OUTPUT)
PAG E
1DATA UPDATE RATE100times
1
2OUTPUT WEIGHTINDICATE
ParameterInitial valueL1 L2 S
OPTION (In case of used D/A OUTPUT)
PAG E
1
1
2
3
ParameterInitial valueL1 L2 S
D/A OUTPUT MODEGROSS
ZERO OUTPUT000.00
FULLSCALE OUT.100.00
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
N
Alternatives・Setting range
0:[CONTINUITY]1:[SINGLE]
2:[LEVEL]
00000 ~ 9999952(R/W)
2 ~ 9853(R/W)
±00000 ~ ±9999954(R/W)
±00000 ~ ±9999955(R/W)
0:[GROSS]1:[NET]
N
Alternatives・Setting range
0:[100times]1:[50times]
2:[20times]3:[10times]
4:[5times]5:[2times]
0:[INDICATE]1:[GROSS]2:[NET]
N
Alternatives・Setting range
0:[GROSS]1:[NET]
2:[ZERO SCALE]3:[FULL SCALE]
00000 ~ 99999
00000 ~ 99999
Communication
Command
No.
51(R/W)
56(R/W)
Communication
Command
No.
Communication
Command
No.
OPTION (In case of used CC-Link)
PAG E
1OCCUPIED STATION4 stations
2SPEED10Mbps
1
3STATION NUMBER1
4WGT SELECT CODEExtinput
ParameterInitial valueL1 L2 S
OPTION (In case of used DeviceNet)
PAG E
1NODE ADDRESS0
2SPEED500kbps
1
3WGT SELECT CODEExtinput
4COMM. MODERead only
ParameterInitial valueL1 L2 S
N
〇〇
〇〇
〇〇
〇〇
N
〇〇
〇〇
〇〇
〇〇
Alternatives・Setting range
0:[1 station]1:[2 stations]
2:[4 stations]
0:[156kbps]1:[625kbps]
2:[2.5Mbps]3:[5Mbps]
4:[10Mbps]
~ 64
1
0:[Network]1:[Extinput]
Alternatives・Setting range
0
~ 63
0:[125kbps]1:[250kbps]
2:[500kbps]
0:[Network]1:[Extinput]
0:[Read only]1:[Write En.]
Communication
Command
No.
Communication
Command
No.
67
21.SETTING ITEM LIST
SYSTEM
PAG E
ParameterInitial valueL1 L2 S
N
Alternatives・Setting range
1INITIALIZATIONCODE
2SELFCHECK DSP1
1
3SELFCHECK MEM
[CODE][COMP.][OPR.]
4SELFCHECK KEY
5SELFCHECK EXT
6SELFCHECK DSP2
7SELFCHECK COM
8PASSWORD00000000 ~ 9999
2
9LANGUAGE JPN
10[GROSS/NET] KEYON
11[DZ] KEYON
12[TARE] KEYON
3
13 [CURSOR ON/PFF] KEYON
14[START/STOP] KEYON
15B4 FUNC. SELECTCODE2
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
CALIBRATION
[CAL.][etc.]
0: [JPN]1:[ENG]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
Communication
Command
No.
69(R/W)
6A(R/W)
6B(R/W)
6C(R/W)
6D(R/W)
6E(R/W)
6F(R/W)
PAG E
ParameterInitial valueL1 L2 S
1ZERO CAL.0
2SPAN CAL.100.00
1
3EQUIV. CAL.3.000mV/V
4BALANCE WEIGHT100.00
5MIN. SCALE DIV.0.01
6NET OVER999.99
7GROSS OVER999.99
8UNIT DISPLAYkg
2
9DECIMAL PLACE0.00
10DZ REGULATION VAL02.00
N
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
Alternatives・Setting range
[OK]
00001 ~ 99999
(VOL.) 0.001 ~ 3.000mV/V
(WEIGHT) 00001 ~ 99999
00001 ~ 9999984(R/W)
001 ~ 10085(R/W)
00000 ~ 9999986(R/W)
00000 ~ 9999987(R/W)
0:[NONE]1:[kg]2:[t]3:[g]
4:[N]5:[lb]
0:[NONE]1:[0.0]2:[0.00]
3:[0.000]
0000 ~ 99998A(R/W)
Communication
Command
No.
Command
Command
83(R/W)
88(R/W)
89(R/W)
68
SEQUENCE MODE
21.SETTING ITEM LIST
PAG E
1
1
2
3
4
ParameterInitial valueL1 L2 S
SEQUENCE MODE
ADJUST FEEDING
AT START NZ CONF.
AT START WV CONF.
5ADJ.FEEDING TIME1.00sec.
6AZ TIMES01times
2
7JUDGING TIMES01times
RS-232C
PAG E
1COMM. MODEHAND SH.
2BAUD RATE9600BPS
1
3LENGTH8BIT
4PARITY BITODD
5STOP BIT1BIT
6TERMINATORCR+LF
2
7FLOW CONTROLOFF
Parameter
SIMPLE COMP.
OFF
OFF
OFF
Initial
valueInitial
value
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
L1 L2 S
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
〇〇
N
Alternatives・Setting range
0:[SIMPLE COMP.] 1:[SEQUENCE]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
0:[OFF]1:[ON]
0.00 ~ 9.9995(R/W)
00 ~ 9996(R/W
00 ~ 9997(R/W)
N
Alternatives・Setting range
0:[HAND SH.]1:[CONTINUITY]
2:[AT PRINT]
0:[1200]1:[2400]2:[4800]
3:[9600]4:[19200]
0:[7bit]1:[8bit]
0:[NONE]1:[ODD]2:[EVEN]
0:[1bit]1:[2bit]
0:[CR]1:[CR+LF]
0:[OFF]1:[RTS/CTS]
Communication
Command
No.
91(R/W)
92(R/W)
93(R/W)
94(R/W)
Communication
Command
No.
D1(R)
D2(R)
D3(R)
D4(R)
D5(R)
D6(R)
DA(R)
69
22.SPECIFICATIONS
22. SPECIFICATIONS
■ Analog Section
Sensor excitation10V DC Output current: Within 120mA
6-wire (Up to four 350Ωload cells can be connected.)
Signal input range-0.2 to 3.0mV/V
Zero adjusting range-0.2 to 3.0mV/V
AccuracyNonlinearityWithin 0.02%FS ±1digit (When 3mV/V is input)
Zero driftWithin 0.25μV/ ℃ RTI
Gain driftWithin 25ppm/ ℃
A/DconverterSpeed100times/sec.
Resolution24bit (binary)
Analog filterBessel type low-pass filter (-12dB/oct)
Cutoff frequency2Hz, 4Hz, 6Hz, 8Hz (Selectable by setting)
CalibrationEquivalent input calibration and actual load calibration
■ Display Section
Display3.5 inch TFT color LCD module (Display area: 71mm×53mm)
320×240 dots
Weight value display5-digit
Sign: Minus sign display
Minimum scale divisionCan be set in the range of 1 to 100.
Decimal point8 8. 8. 8. 8 The display position can be set.
Over scaleA/D converter input over: “LOAD”
A/D converter input minus over :“-LOAD”
Net weight exceeding the “NET OVER” setting:“NET OVER”
Gross weight exceeding the “GROSS OVER” setting:“GROSS OVER”
Unit displayNONE, kg, t, g, N, lb is selectable.
Status displayVarious states of weight are displayed.
■ Setting section
How to setSet by touch panel operation (with a key click buzzer).
External setting can also be made by RS-232C etc..
70
Memory of set valuesInitial valuesNOV RAM (nonvolatile RAM)
Other valuesLithium-battery-backed-up C-MOS RAM
(The memory life is approx. 7 years or more,
which varies depending on the operating conditions
and storage environment.)
Protection of set values Setting operation can be prohibited to prevent changes by misoperation.
(LOCK1, LOCK2)
■ Communication
RS-232C communications interface
Asynchronous communication method
Baud rate1200bps to 19200bps
SI/F (2-wire serial interface)
2-wire serial interface for connecting a UNIPULSE-manufactured printer,
external display, etc.
Asynchronous communication method
Baud rate600bps
■ Option
BCD data outputOpen collector output
The output rate can be changed.
D/A converterVoltage output0 to 10V
Current output4 to 20mA
CC-LinkNumber of occupied stations1, 2, 4 STAT.
Baud rate156k, 625k, 2.5M, 5M, 10Mbps
Station number1 to 64 (when one station is occupied)
1 to 63 (when two station is occupied)
1 to 61 (when four station is occupied)
22.SPECIFICATIONS
DeviceNetBaud rate125k, 250k, 500kbps
Node address0 to 63
■ External Input/Output
External output signalTransistor open collector output. (Emitter = COM terminal)
(9 points)The output turns ON when the transistor turns ON.
External input signalON when shorted with COM terminals by contact (relay, switch, etc.) or
(11 points)non-contact (transistor, TTL open-collector output, etc.)
■ General Performance
Required power supplyAC spec.AC100V to AC240V (+10% -15%)
[
Free power supply 50/60Hz
DC spec.DC24V (±15%)
(Depending on the request at the time of order)
Power consumptionAC spec.18W max
DC spec.18W max
Operating conditionsTemperature Operating temperature range:-10 ℃ to +40 ℃
Storage temperature range: -20 ℃ to +60 ℃
Humidity80%RH or less (non-condensing)
]
Dimensions96W × 96H × 138D (mm) (not including projections)
WeightApprox.1.0kg
71
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.