Gravitas X100 is an ultra-compact, integrated, DC power system. It consists of up to
three high power-density, hot-swap rectier modules which can produce up to 66 amperes
at -54.4VDC, 99 amperes at +27.2VDC or 100 amperes at +13.6VDC. In 2+1 redundant
operation the output current is up to 44 amperes at -54.4VDC, 66 amperes at +27.2VDC or
100 amperes at +13.6VDC.
The system has a congurable DC distribution panel with options of up to 10 load circuits
protected either by GMT fuses or circuit breakers. Two battery breakers and a low-voltage
battery disconnect are included as standard. The system also has a temperature probe for
temperature compensated output from the rectiers and an optional second probe can be
used to monitor external temperature.
The intelligent control and supervisory unit communicates directly with the rectiers to
monitor and control their function. The system can be controlled by software from a remote
PC via the Ethernet LAN port, using an on-board WEB server which can be accessed by
any standard Java enabled WEB browser.
X100 SERIES
INSTALLATION & OPERATING MANUAL
The complete Gravitas X100 is only 2RU high (3.47inches or 88.1mm) and is easily installed
by a qualied technician. All connections are at the rear to terminal blocks. The unit may
be mounted in a 19 or 23 inch rack.
.
Manual No. x100-5a
Figure 1 - X100 Compact Integrated DC Power System
Page 4
x100-man-Rev5a-0214.indd
2.0 FEATURES & OPTIONS
2.1 Standard Features
2RU High System Unit
Remote Control & Monitoring via TPC/IP Ethernet LAN
Fully Integrated System
Up to 66A at -54.4VDC
Up to 99A at +27.2VDC
Up to 100A at +13.6VDC
Wide Range AC Input
Up to 10 DC Load Circuits
Circuit Breakers or GMT Fuses
Quick and Easy Installation
Universal 19/23-Inch Mounting Brackets
SNMP reporting and Error Trapping
X100 SERIES
INSTALLATION & OPERATING MANUAL
2.2 Options & Accessories
Additional Probe for External Temperature Measurement (‘T’ Option)
Various AC Line cords and DC cable sets
3.0 SAFETY WARNINGS
3.1The X100 Compact DC Power System operates at voltages that could potentially
be hazardous. Furthermore, inadvertent short circuiting of the system battery and/
or rectier by misconnection or other error could be harmful. This product should
be handled, tested and installed only by qualied technical persons who are trained
in the use of power systems and are well aware of the hazards involved.
3.2When operating the X100 the chassis ground terminal must be connected to the
system frame ground or other proper safety ground for the protection of personnel.
3.3
All connections to the X100 should be carefully checked for errors before applying
power to it.
3.4This equipment is intended only for installation in a “RESTRICTED ACCESS
Manual No. x100-5a
LOCATION”
Page 5
x100-man-Rev5a-0214.indd
4.0 WARRANTY (summary)
X100 Series DC power systems are warranted for two (2) years from date of shipment
against defects in material and workmanship. This warranty does not extend to products
which have been opened, altered or repaired by persons other than persons authorized by
the manufacturer or to products which become defective due to acts of God, negligence or
the failure of customer to fully follow instructions with respect to installation, application
or maintenance.
For a complete text of UNIPOWER’ s warranty conditions please request a copy from your
local Sales Ofce.
5.0 UNPACKING AND INSPECTION
5.1This X100 DC power system was carefully tested, inspected and packaged for
shipment from our factory . Upon receipt the unit should be carefully unpacked and
inspected for any damage in shipment.
X100 SERIES
INSTALLATION & OPERATING MANUAL
5.2 If there is evidence of damage, do not attempt to install the unit. The freight
carrier should be notied immediately and a claim for the cost of the X100 should
be led with the carrier for direct reimbursement. Be sure to include the model and
serial number of the damaged unit in all correspondence with the freight carrier.
Also save the shipping carton and packing material as evidence of damage for the
freight carrier’s inspection.
5.3 UNIPOWER will cooperate fully in case of any shipping damage investigation.
5.4 Always save the packing materials for later use in shipping the unit. Never ship the
system or the rectier modules without proper packing.
Manual No. x100-5a
Page 6
x100-man-Rev5a-0214.indd
6.0 GENERAL SPECIFICATIONS
6.1 Inputs
Supply Voltage: 85-264VAC Single Phase
Each rectier position is supplied via an individual
A 3-phase supply may be connected provided that the voltage presented to each
individual rectier position does not exceed 264VAC.
Supply Current: Max 17A input @ 85-264VAC per rectier input.
Battery Input: Direct connection to DC output bus or via protection
Digital alarm inputs: Volts free contact input*
*Volts free contacts are internally pulled up to 5V with reference to rectier negative
sense, these lines should not be tied to anything other than volts free contacts or
oating opto-coupler outputs.
T emperature probes: Sensor with output current proportional to temperature.
X100 SERIES
INSTALLATION & OPERATING MANUAL
pair of screw terminals.
breakers.
6.2 Outputs
Breaker Distribution: Up to 8 circuits, maximum 50A per circuit.
Fuse Distribution: Up to 10 circuits, maximum 12A per circuit.
Alarm Relay Contacts: Form C, 1A max at 30VDC.
Ethernet: 10/100 Base T
6.3 Protection
Supply Input: Each rectier is individual fused internally.
Battery: 100A Magnetic Circuit Breaker.
Output Distribution: According to installed circuit breakers or fuses.
Bulk DC Bus: Rectier Current Limiting / Battery Breaker.
Manual No. x100-5a
Page 7
x100-man-Rev5a-0214.indd
X100 SERIES
INSTALLATION & OPERATING MANUAL
6.4 Safety
The X100 system is compliant with UL60950-1, EN60950-1, CSA22.2-60950-1 and
all other derivatives of the core IEC60950-1 standard 2nd Edition when installed
correctly within a restricted access environment.
The X100 system is CE marked to indicate conformance to the European Union’s
Low Voltage and EMC Directives.
6.5 EMC
The X100 complies with the following Norms when correctly installed.
Conducted Emissions: EN55022, level A
Radiated Emissions: EN55022, level A
ESD: EN61000-4-2, level 4, criterion A - 8kV contact, 15kV
air.
Radiated Immunity: EN61000-4-3, level 3, criterion A - 10V/m.
Surges (power ports): EN61000-4-5, level 1, criterion A - 500V
6.6 Environmental
Operating Temperature: -40°C to 50°C
Storage Temperature: -40°C to 75°C
Humidity: 0% to 95% Non-Condensing
6.7PhysicalSpecication
Case Material: Steel
Finish: Clear Passivated
Dimensions: 3.47H (88.1) x 17.2W(437) x 12.8D(325)
Rack Width: 19” or 23” using dual purpose kit supplied.
NOTE: Mid-mount is recommended when used in
Manual No. x100-5a
free space.
Page 8
x100-man-Rev5a-0214.indd
7.0 FRONT PANEL DESCRIPTION
LOAD
16 LED
HOT-SWAP RECTIFIER MODULES
DC DISTRIBUTION
DC DISTRIBUTION
OPTION A – MINIATURE CIRCUIT BREAKERS
X100 SERIES
INSTALLATION & OPERATING MANUAL
BATTERY
BREAKERS
DC DISTRIBUTION
1-8 CIRCUIT BREAKERS
CURRENT
DISPLAY
STA TUS & ALARM
OPTION B – GMT FUSES
10 GMT FUSES
OPTION C – BULK FEED CIRCUIT BREAKERS
1-4 CIRCUIT BREAKERS
MATRIX
7.1 From left to right there are 3 rectier slots. Each slot can accept one rectier from the
7.2 Above rectiers is the distribution and display section. There are 3 types of DC
Manual No. x100-5a
Figure 2 - Front Panels with Bezel Removed
RADIAN Series rated up to 1200W output power. Only identical model rectiers of
appropriate output voltage may be installed at the same time. For example, a nominal
-48V system may contain between 1 and 3 model RPCP48/22-Z OR between 1 and
3 model RPCM48/15-Z but not a mixture of the two types.
distribution depending on the option that has been specied.
7.2.1 Option A provides up to 8 DC load circuits with miniature circuit breaker
protection. Each circuit may be specied with a breaker of maximum rating
30A.
7.2.2 Option B provides a total of 10 DC load circuits with GMT fuse protection.
Each circuit can employ a maximum fuse rating of 12A.
Page 9
x100-man-Rev5a-0214.indd
7.2.3 Option C provides up to 4 bulk DC load circuits with circuit breaker
ETHERNET
DC LOAD TERMINALSBATTERY TERMINALS
J2
RESERVED FOR
ETHERNET
DC LOAD TERMINALSBATTERY TERMINALS
J2
RESERVED FOR
protection. Each circuit may be specied with a breaker of maximum rating
50A.
7.3 To the right of the DC distribution section is a display section.
7.3.1 Current Meter – displays the total system load current.
7.3.2 16 LED Matrix – provides visual indication of a variety of status and alarm
condition. Full details can be found in section 9.
8.1 In the centre, viewed from the rear, is a bank of screw terminal block for the DC
load connections.
When options A or B have been specied one terminal pair is provided for feed and
return for each circuit installed; 1-8 for circuit breakers, 10 for GMT fuses.
When option C has been specied 4 pairs of bulk terminal blocks are tted to provide
one pair for feed and return for each circuit installed, from 1 to 4.
Note that the return (RTN) terminals are NOT internally connected to chassis
ground.
Manual No. x100-5a
Page 10
x100-man-Rev5a-0214.indd
X100 SERIES
INSTALLATION & OPERATING MANUAL
8.2 To the right are two pairs of terminal blocks for making connections to one or two
strings of batteries. Batteries are connected to the internal system bus via two
magnetic circuit breakers on the front of the unit, each rated at 100A. These circuit
breaker provides two functions.
8.2.1 In the rst instance they enable the user to disconnect the batteries from the
system for maintenance, replacement or other purposed.
8.2.2 The second function is to protect the batteries against excessive charge or
discharge current. Note that charge current is normally managed by the
built-in digital controller.
8.3 T o the left of the DC load terminals there is a 9-way D sub connector marked RS232
mark J3.
This connector provides a ‘console’ only function to UNIPOWER service personnel
and should not be connected to for any other purpose.
8.4 Immediately to the left of the RS232 connector is a bank of 18 Spring Clamp T erminals
designated J2. These terminals provide connections for the battery temperature
compensation probe, additional external temperature probe, the relay alarm outputs
and one auxiliary digital input. They are described in detail in section 10.
8.5 T o the left is the Ethernet TCP/IP connector J1. This connection uses a standard RJ45
Network connector . It is used to connect either to a Local Area Network or directly
to a PC with network connection, the latter using a standard cross-over cable.
The primary means of setting up the X100 unit is via it’ s built-in WEB server , which
is accessed using a WEB browser via this Ethernet TCP/IP connection.
8.6 To the bottom right hand side of the unit are the AC input terminals. Three pairs
of screw terminals designated L1, N1, L2, N2, L3 & N3 provide for connection of
individual AC supplies to each of the installed rectiers. In addition there are three
safety ground connections just below. Once installed a plastic insulator provides
protection against accidental touching of the live AC terminals.
IMPORTANT NOTE: DO NOT CONNECT THE UNIT SUCH THA T MORE THAN
264VAC WILL BE P RESENT BETWEEN THE LIVE AND NEUTRAL TERMINALS
OF ANY ONE INLET SOCKET. SUCH CONNECTION MAY BE HAZARDOUS,
WILL DAMAGE THE UNIT AND INVALIDATE THE WARRANTY.
Manual No. x100-5a
Page 11
x100-man-Rev5a-0214.indd
9.0 CURRENT METER & LED INDICATORS
Figure 4 - Current Meter and LED Indicators (showing MAJ & FUSE alarms)
During normal operation only the green PWR LED is displayed along with an reading of
the load current.
The LED indicators provide visual indication of both status and alarm conditions as described
below:
PWR – GREEN – Indicates that the unit has power.
FLT – GREEN – Indicates that the unit is in ‘Float’ mode.
EQU – YELLOW – Indicated that the unit is in ‘Equalisation’ mode.
BTST – YELLOW – Indicates that a battery test is in progress.
MAJ – RED – Indicates a ‘Major’ (Immediate Response) alarm condition.
MIN – RED – Indicates a ‘Minor’ (Scheduled response) alarm condition.
ACF – RED – Indicates an AC supply failure.
RFA – RED – Indicates a Rectier module failure.
OTA – RED – Indicates that the one or more of the monitored temperatures is
too high.
OVA – RED – Indicated that the system Bus Voltage is too high.
UVA – RED – Indicates that the system Bus Voltage is too low.
EVA – RED – Indicates that the system Bus Voltage is nearing the point at
which the battery LVD will be opened.
LVD – RED – Indicated that at least one of the two LVD contactors is open.
FUSE – RED – Indicates that a monitored fuse or breaker is open.
CHKB – RED – Indicates that there is a battery fault.
COMM – RED – Indicates an I²C communications failure.
X100 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x100-5a
Page 12
x100-man-Rev5a-0214.indd
10.0 MAKING CONNECTIONS TO THE X100
10.1 DC Load Connections
The DC load distribution connections at the rear left of the unit are clearly marked
as follows:
10.1.1 Option A – 1-8 miniature circuit breaker.
Terminals marked 1-8 are used for breakers marked 1-8 respectively. Each
circuit has a FEED and a RETURN (RTN) connection. Terminals marked
9 and 10 are not used.
10.1.2 Option B - GMT Fuses.
Terminals marked 1-10 are used for fuse marked 1-10 respectively. Each
circuit has a FEED and a RETURN (RTN) connection.
X100 SERIES
INSTALLATION & OPERATING MANUAL
10.1.3 Option C - 1-4 bulk circuit breaker.
To allow for the possibility of individual load circuits providing in excess of
30A this conguration uses two pairs of screw terminals linked together by
a small bus bar for each circuit. T erminals marked 1&2, 3&4, 5&6 and 7&8
respectively are used for Breakers 1 to 4 respectively. Terminals marked 9
and 10 are not used.
Note that in the case of -48VDC system the ‘feed’ terminals ar e at a negative potential
with respect to the ‘r eturn’ terminals. In the case of +24VDC and +12VDC systems
the ‘feed’ terminals are at a positive potential with respect to the ‘r eturn’ terminals.
When connecting to the DC load terminals it is important to ensure that the cables
used are adequately sized to carry the expected load current for the circuit in question.
The maximum current rating for the individual load terminals is 30A for options A
and B or 50A for option C, but where long cable runs to the load are expected care
should be taken to avoid unacceptable cable voltage drop; this is most likely to occur
at currents in excess of 20A if only a single feed and return cable are employed. It
is recommended that for circuits where a 20A or greater breaker is tted pairs of
feed and return cables are installed.
Manual No. x100-5a
Page 13
x100-man-Rev5a-0214.indd
X100 SERIES
INSTALLATION & OPERATING MANUAL
10.2 Battery Connections
The X100 can be connected to two separate battery strings through the battery
two pairs of IMO ER35 terminal blocks. These terminals accept cables in the
range 10AWG to 2AWG. A minimum cable size of 4AWG is recommended when
employing only the internal 100A circuit breakers for protection (see section 8.2).
If a battery string is separately provided with a lower rated circuit breakers or fuse
then smaller gauge cables may be used as appropriate.
10.3 Alarm Relay and Battery Temperature Probe Connections – J2
Connection to the Form-C alarm relay outputs is made through the 18-way spring
clamp terminal connector . There are a total of 4 relay outputs with Normally Open,
Normally Closed and Common Contacts available for connection. The individual
relay contact sets are fully isolated and may be oated from GROUND by up to 100V.
Maximum contact current and voltage are 1A and 30V (DC or AC) respectively.
This connector accepts wire sizes from #28AWG to #10AWG.
The alarm relays are designated K1 to K4. K1 and K2 are pre-programmed for
MAJOR and MINOR alarm conditions by default. K3 and K4 are not programmed
for any alarm function by default and may be programmed using the Alarm CongurationWEB page described later in section 12.
Connection of the supplied battery temperature probe, if required, is made using
terminals 1 and 2 of this same spring clamp terminal connector . An optional external
temperature probe may also be connected using terminals 3 and 4. Terminals 5 and
6 allow connection of a volt free contact closure input.
J2 CONNECTIONS
TERMINAL FUNCTIONTERMINAL FUNCTION
1BATT. TEMP. PROBE +10K2 - MIN ALARM - N/C
2BATT. TEMP. PROBE -11K2 - MIN ALARM - COM
3EXT. TEMP. PROBE +12K2 - MIN ALARM - N/O
4EXT. TEMP. PROBE -13K3 - FREE ALARM - N/C
5AUX. 3 CONTACT14K3 - FREE ALARM - COM
6AUX. 3 CONTACT15K3 - MREE ALARM - N/O
7K1 - MAJ ALARM - N/C16K3 - FREE ALARM - N/C
8K1 - MAJ ALARM - COM17K3 - FREE ALARM - COM
9K1 - MAJ ALARM - N/O18K3 - MREE ALARM - N/O
Note that terminal 1 is to the left when viewed from the rear of the system.
The X100 is connected to a TCP/IP LAN (Local Area Network) or directly to a PC
using connector J1. This is a standard RJ45 network connector allowing connection
of any generally available Ethernet cable. Note that if the X100 is to be connected
directly to a PC rather than a LAN then a cross-over Ethernet cable will be required.
J3 CONNECTIONS
TERMINAL FUNCTION
1TX +
2TX 3RX +
4Not Used
5Not Used
6RX 7Not Used
8Not Used
Table 2 - Ethernet Connector Pin-Out
10.5 RS232 Console
This connector is reserved for UNIPOWER factory use.
Manual No. x100-5a
Page 15
x100-man-Rev5a-0214.indd
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.