Unipower SLI 15 User Manual

POWERING TECHNOLOGY
USER GUIDE
SLI 15 INVERTER
Manual No. SLI-15-G-3a
sli15-userguide-rev3a-0718.indd
www.unipowerco.com
© 2018 UNIPOWER LLC
All Rights Reserved
UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • sales@unipowerco.com
POWERING TECHNOLOGY
CONTENTS
1 The Display ................................................................................................................................3
2 Startup Sequence and Standby Status ........................................................................................4
3 Operating Modes ........................................................................................................................5
4 Controller Status ........................................................................................................................5
5 Main Menus ...............................................................................................................................6
6 Setting Menus ............................................................................................................................6
7 Status Menu .............................................................................................................................15
8 Info Menu .................................................................................................................................16
Appendix A - Service Menu ...........................................................................................................17
Appendix B - Factory Settings .......................................................................................................19
Manual No. sli-15-G-3a
Page 2
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
1 The Display
Function of keys LEDs for operating status
POWER O.T. FAN FAIL FAULT
<UP> / <DOWN> keys
Use to scroll through menus
<UP> key
<DOWN> key
<ESC> key Use to exit from the current menu
<ENTER> key Use to confirm a selection or value
<ON/OFF> key Use to turn ON or Stand-by (OFF) the unit.
FAN FAIL
O.T.POWER
FAULT
Four front-panel LED’s show inverter status
"POWER" (green)
- The "POWER" LED is lighted on as soon as the unit starts supplying power to the load
- It indicates normal operation.
"O.T." (red)
- When lighted on it indicates that the internal temperature is approaching the thermal shutdown thre
shold. In addition to
the visual indication, the unit sounds audibly.
"O.T." and "FAULT" (red)
- The thermal shutdown threshold has been exceeded.
Note: The thresholds are factory set and not changeable (see "Factory Settings" on "Appendix B").
"FAN FAIL" (red)
- The "FAN FAIL" LED is lighted on when the speed of one of the fan falls below its nominal value.
"FAULT" and "FAN FAIL"
- They are lighted up at the same time if more than one fan has stopped or a general malfunction is detected. The unit continues to works until an OT is detected.
"FAULT" (red)
- "FAULT" LED is lighted on when a general failure happens. (for general fault conditions see table below)
Manual No. sli-15-G-3a
GENERAL FAILURE CONDITIONS
- Failure of at least 2 fans
- Over Temperature
- Output Over Current
(the protective output breaker on front panel, trips and a "Breaker OFF" state is indicated on the display.)
- Output Over Voltage
- Output Under Voltage
- Dc input voltage out of range (UV or OV)
- DC Input Over Current
Page 3
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
2 Startup sequence and the Standby Status
2 Startup sequence and the Standby Status
The STAND BY status shows the DC source is connected; loads are disconnected by two internal relays. As soon as the DC input voltage is applied, "STANDBY…" is displayed. Three operations are possible (see Fig.1): (a) Press <ESC> to enter into the SETTINGS menu's first page, or (b) Press <ENTER> to visualize the configuration mode of the unit. Two screens are presented
automatically within a few seconds. The first (1) shows the mode of the unit (Stand Alone or Parallel mode). In case of Parallel mode the screen tells whether the unit is master or slave. In case of Stand Alone mode the units is always a master The second screen (2) shows if the unit has the optional Static Transfer Switch. Pressing the "ESC" key shows the SETTINGS menu’s first page, or
(c) Press <ON/OFF> to power up the unit. The display shows "STARTING…" and the screen (3) appeares
automatically after a few seconds. Using <UP> / <DOWN> keys it is possible to scroll six screens on the display and visualize the electrical parameters (Vout/Iout, Vout/Freq, Iout/Pout,…). Pressing <ENTER> the screen (1) is visualized for short time, then the display goes back to the previous screen automatically. Pressing <ESC> the SETTINGS menu is displayed.
(2)
(1)
(3)
The STAND BY status shows the DC source is connected; loads are disconnected by two internal relays. As soon as the DC input voltage is applied, "STANDBY…" is displayed. Three operations are possible (see Fig.1): (a) Press <ESC> to enter into the SETTINGS menu's first page, or (b) Press <ENTER> to visualize the configuration mode of the unit. Two screens are presented
automatically within a few seconds. The first (1) shows the mode of the unit (Stand Alone or Parallel mode). In case of Parallel mode the screen tells whether the unit is master or slave. In case of Stand Alone mode the units is always a master The second screen (2) shows if the unit has the optional Static Transfer Switch. Pressing the "ESC" key shows the SETTINGS menu’s first page, or
(c) Press <ON/OFF> to power up the unit. The display shows "STARTING…" and the screen (3) appeares
automatically after a few seconds. Using <UP> / <DOWN> keys it is possible to scroll six screens on the display and visualize the electrical parameters (Vout/Iout, Vout/Freq, Iout/Pout,…). Pressing <ENTER> the screen (1) is visualized for short time, then the display goes back to the previous screen automatically. Pressing <ESC> the SETTINGS menu is displayed.
ENTER
STAND BY…
ESC
To SETTINGS
Menu
ON/OFF
STARTING..…
ENTER
Figure 1
Manual No. sli-15-G-3a
Vgrid = x.x Vac Igrid = x.x A
Page 4
Master Ad.1
Parallel Mode 2
Transfer Switch
….
ESC
To SETTINGS
Menu
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
3 Operating modes
The unit has two operating modes:
- Stand Alone mode: there is only one inverter in the system
- Parallel mode: there are several inverters working in parallel (max. number of parallelable units: 8)
The default mode is Stand-Alone. Trained personnel should set the operating mode before the system starts supplying the load (see SERVICE
menu on "Appendix A"). It is possible but not recommended to change the operating mode while the inverter is operating.
ATTENTION:
incorrect unit setting may lead the system to latch up
Notes
When the unit work in Parallel mode it is not possible to change the following parameters in the
SETTINGS menu: Vout, Iout, Frequency. The access to these parameters is locked to avoid system conflicts (see also Notes on page 8).
4 Controller status
When operating in Parallel mode the controller inside each unit can operate in two modes:
- Master: provides the commands for the whole system of paralleled inverters. There is only one master.
- Slave: it follows the commands of the Master
When working in Stand Alone mode the status of the unit is Master. Controller statuses are assigned automatically and cannot be changed by the user. In case of failure of the
master in a parallel configuration a new master is selected automatically and control of the system of paralleled inverters is transferred automatically to the new master.
Manual No. sli-15-G-3a
Page 5
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
5 Main menus
There are 3 main Menus (Fig.2):
- The SETTINGS menu
- The STATUS menu
- The INFO menu
6 The SETTINGS menu
6.1 Overview
Through this menu it is possible to set several parameters of the unit. To avoid problems make sure you know how the parameters will affect the load. To access the SETTINGS menu contents a 1 For increased protection certain sensitive parameters are protectyed by a 2 Authorized operator must provide.
Settings changeable by Generic operator (1
- Unit Serial Port Address, V
- Protections (AutoRestart or Latched types)
- Display Light (ON/OFF), Time Display Light ON and Key Click
- Autostart, Remote ON/OFF
- New Password 1
Settings changeable by Authorized operator (2
These settings are accessible via the SERVICE submenu whose access is protected by the 2 password.
- Operating mode, 2
ST
level password must be provided.
ST
level password)
, I
out
ST
level only
ND
levelPassword, Restore data, Utility menu, System Time-out.
, Frequency.
limit
ND
level password)
ND
level password that an
ND
level
These settings are contained in the UTILITY submenu contained in the SERVICE submenu (no password needed to access UTILITY from SERVICE, see Fig.2 and also Appendix A).
- Change the Led Status (ON/OFF)
- Set the Buzzer (ON/OFF)
- Set the Fans (ON/OFF) and the Fan Speed
- Read fan Speed, System Temperature, Internal Temperature and Ambient Temperature
NOTE:
- The SERVICE submenu should be accessed by trained personnel only. An error in these settings could seriously damage the system.
- To avoid potential conflicts during the operating procedures, it is preferable to keep the unit in STANDBY status before accessing and acting on the SERVICE submenu.
Manual No. sli-15-G-3a
Page 6
sli15-userguide-rev3a-0718.indd
Loading...
+ 13 hidden pages