7 Status Menu .............................................................................................................................15
8 Info Menu .................................................................................................................................16
Appendix A - Service Menu ...........................................................................................................17
Appendix B - Factory Settings .......................................................................................................19
Manual No. sli-15-G-3a
Page 2
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
1 The Display
Function of keys LEDs for operating status
POWER O.T. FAN FAIL FAULT
<UP> / <DOWN> keys
Use to scroll through menus
<UP> key
<DOWN> key
<ESC> key
Use to exit from the current menu
<ENTER> key
Use to confirm a selection or value
<ON/OFF> key
Use to turn ON or Stand-by (OFF) the unit.
FAN FAIL
O.T.POWER
FAULT
Four front-panel LED’s show inverter status
"POWER" (green)
- The "POWER" LED is lighted on as soon as the unit starts
supplying power to the load
- It indicates normal operation.
"O.T." (red)
- When lighted on it indicates that the internal temperature is
approaching the thermal shutdown thre
shold. In addition to
the visual indication, the unit sounds audibly.
"O.T." and "FAULT" (red)
- The thermal shutdown threshold has been exceeded.
Note: The thresholds are factory set and not changeable
(see "Factory Settings" on "Appendix B").
"FAN FAIL" (red)
- The "FAN FAIL" LED is lighted on when the speed of one of
the fan falls below its nominal value.
"FAULT" and "FAN FAIL"
- They are lighted up at the same time if more than one fan
has stopped or a general malfunction is detected. The unit
continues to works until an OT is detected.
"FAULT" (red)
- "FAULT" LED is lighted on when a general failure happens.
(for general fault conditions see table below)
Manual No. sli-15-G-3a
GENERAL FAILURE CONDITIONS
- Failure of at least 2 fans
- Over Temperature
- Output Over Current
(the protective output breaker on front panel,
trips and a "Breaker OFF" state is indicated on
the display.)
- Output Over Voltage
- Output Under Voltage
- Dc input voltage out of range (UV or OV)
- DC Input Over Current
Page 3
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
2 Startup sequence and the Standby Status
2 Startup sequence and the Standby Status
The STAND BY status shows the DC source is connected; loads are disconnected by two internal relays.As soon as the DC input voltage is applied, "STANDBY…" is displayed. Three operations are possible (see Fig.1): (a)Press <ESC> to enter into the SETTINGS menu's first page, or(b)Press <ENTER> to visualize the configuration mode of the unit. Two screens are presented
automatically within a few seconds. The first (1) shows the mode of the unit (Stand Alone or Parallelmode). In case of Parallel mode the screen tells whether the unit is master or slave. In case of StandAlone mode the units is always a master The second screen(2) shows if the unit has the optional StaticTransfer Switch.Pressing the "ESC" key shows the SETTINGS menu’s first page, or
(c)Press <ON/OFF> to power up the unit. The display shows "STARTING…" and the screen(3) appeares
automatically after a few seconds. Using <UP> / <DOWN> keys it is possible to scroll six screens on thedisplay and visualize the electrical parameters (Vout/Iout, Vout/Freq, Iout/Pout,…). Pressing <ENTER>the screen (1) is visualized for short time, then the display goes back to the previous screenautomatically.Pressing <ESC> the SETTINGS menu is displayed.
(2)
(1)
(3)
The STAND BY status shows the DC source is connected; loads are disconnected by two internal relays.
As soon as the DC input voltage is applied, "STANDBY…" is displayed.
Three operations are possible (see Fig.1):
(a) Press <ESC> to enter into the SETTINGS menu's first page, or
(b) Press <ENTER> to visualize the configuration mode of the unit. Two screens are presented
automatically within a few seconds. The first (1) shows the mode of the unit (Stand Alone or Parallel
mode). In case of Parallel mode the screen tells whether the unit is master or slave. In case of Stand
Alone mode the units is always a master The second screen (2) shows if the unit has the optional Static
Transfer Switch.
Pressing the "ESC" key shows the SETTINGS menu’s first page, or
(c) Press <ON/OFF> to power up the unit. The display shows "STARTING…" and the screen (3) appeares
automatically after a few seconds. Using <UP> / <DOWN> keys it is possible to scroll six screens on the
display and visualize the electrical parameters (Vout/Iout, Vout/Freq, Iout/Pout,…). Pressing <ENTER>
the screen (1) is visualized for short time, then the display goes back to the previous screen
automatically.
Pressing <ESC> the SETTINGS menu is displayed.
ENTER
STAND BY…
ESC
To SETTINGS
Menu
ON/OFF
STARTING..…
ENTER
Figure 1
Manual No. sli-15-G-3a
Vgrid = x.x Vac
Igrid = x.x A
Page 4
Master Ad.1
Parallel Mode 2
Transfer Switch
….
ESC
To SETTINGS
Menu
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
3 Operating modes
The unit has two operating modes:
-Stand Alone mode: there is only one inverter in the system
-Parallel mode: there are several inverters working in parallel (max. number of parallelable units: 8)
The default mode is Stand-Alone.
Trained personnel should set the operating mode before the system starts supplying the load (see SERVICE
menu on "Appendix A").
It is possible but not recommended to change the operating mode while the inverter is operating.
ATTENTION:
incorrect unit setting may lead the system to latch up
Notes
When the unit work in Parallel mode it is not possible to change the following parameters in the
•
SETTINGS menu: Vout, Iout, Frequency. The access to these parameters is locked to avoid system
conflicts (see also Notes on page 8).
4 Controller status
When operating in Parallel mode the controller inside each unit can operate in two modes:
-Master: provides the commands for the whole system of paralleled inverters. There is only one master.
-Slave: it follows the commands of the Master
When working in Stand Alone mode the status of the unit is Master.
Controller statuses are assigned automatically and cannot be changed by the user. In case of failure of the
master in a parallel configuration a new master is selected automatically and control of the system of
paralleled inverters is transferred automatically to the new master.
Manual No. sli-15-G-3a
Page 5
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
5 Main menus
There are 3 main Menus (Fig.2):
-The SETTINGS menu
-The STATUS menu
-The INFO menu
6 The SETTINGS menu
6.1 Overview
Through this menu it is possible to set several parameters of the unit. To avoid problems make sure you
know how the parameters will affect the load.
To access the SETTINGS menu contents a 1
For increased protection certain sensitive parameters are protectyed by a 2
Authorized operator must provide.
Settings changeable by Generic operator (1
-Unit Serial Port Address, V
-Protections (AutoRestart or Latched types)
-Display Light (ON/OFF), Time Display Light ON and Key Click
-Autostart, Remote ON/OFF
-New Password 1
Settings changeable by Authorized operator (2
These settings are accessible via the SERVICE submenu whose access is protected by the 2
password.
-Operating mode, 2
ST
level password must be provided.
ST
level password)
, I
out
ST
level only
ND
levelPassword, Restore data, Utility menu, System Time-out.
, Frequency.
limit
ND
level password)
ND
level password that an
ND
level
These settings are contained in the UTILITY submenu contained in the SERVICE submenu (no password
needed to access UTILITY from SERVICE, see Fig.2 and also Appendix A).
-Change the Led Status (ON/OFF)
-Set the Buzzer (ON/OFF)
-Set the Fans (ON/OFF) and the Fan Speed
-Read fan Speed, System Temperature, Internal Temperature and Ambient Temperature
NOTE:
-The SERVICE submenu should be accessed by trained personnel only. An error in these settings
could seriously damage the system.
-To avoid potential conflicts during the operating procedures, it is preferable to keep the unit in
STANDBY status before accessing and acting on the SERVICE submenu.
Manual No. sli-15-G-3a
Page 6
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
6.2 Navigating the SETTINGS menu
Figure 2
SETTINGS menu
STATUS menu
INFO menu
>>2nd level Password >> SERVICE submenu
UTILITY submenu
To know the unit configuration (Stand-Alone, Parallel Mode, Master,…)
To get info about the unit's Part Number, Serial Number and Firmware revision number.
To set the programmable unit parameters
umbers co
second point, ma
submenu items
SETTINGS menu
>> 2nd level Password >> SERVICE submenu
To set the programmable unit parameters
STATUS menu
To know the unit configuration (Stand-Alone, Parallel Mode, Master,…)
INFO menu
To get info about the unit's Part Number, Serial Number and Firmware
revision number.
Figure 2
Idle for the sub-menu
UTILITY submenu
SETTINGS Menu - - >
1.0
Navigator
Gives the current position on the menu and sub menu map
X.0 : shows the main menu start page.
X = 1 for SETTINGS menu
X = 2 for STATUS menu
X = 3 for INFO menu.
X.1 or X.2 or X.3 etc.
numbers coming after the point indicate any 1
X.1.1 or X.1.2 or X.1.3 etc.
n
Manual No. sli-15-G-3a
ming after the
ST
level submenu items
rk any 2
ND
level
Page 7
sli15-userguide-rev3a-0718.indd
Example:
ST
POWERING TECHNOLOGY
SETTINGS Menu - - >
1.0
1
level submenu
"……" - - >
1.1
"……" - - >
1.2
2ND level submenu
"……" - - >
1.1.1
"……" - - >
1.1.2
Figure 3
Manual No. sli-15-G-3a
Page 8
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
6.3 Structure of the SETTINGS menu
(*)
d
ENT/
SETTINGS Menu - - >
1.0
STATUS
INFO Menu
Password
****
ESC
ESC
Up/
Down
Sub- Menu
st
1
Level
Set Address
Set Vout
Set Limit
Set Frequency
Protections
1
Display light
Key Click
AUTO-START
Remote ON/OFF
Service
New password
Transfer Switch
Set Voltage Mask
Set RMS Voltage
Tolerance
Set Frequency
Tolerance
Set Restore Time
Transfer Switch
Operat. Mode
Manual Switch
2
Figure 4
(*)
ENT/
Sub- Menu 3 Level
ESC
V Mask = xx (%)
Vrms Tol.= xx (%)
F Tol.=xx (%)
Time = xx sec.
Mode X
Connected ON/OFF
r
Protections
1
For the Protections operating procedure, please see page 12.
2
For the Tranfer Switch operating procedure, please see page 13.
Manual No. sli-15-G-3a
ENT/
ENT/
Sub- Menu
nd
ESC
1
Level
2
Input UV
Input OV
Input UC
Output UV
Output OV
Output OC
ENT/
Sub- Menu
ESC
rd
Level
3
Input UV:
Restart xx Times
Input OV:
Restart xxTimes
Input OC:
Restart xx Times
Output UV:
Restart xx Times
Output OV:
Restart xx times
Outpu OC:
Restart xx Times
Sub- Menu
th
ESC
4
Level
Input UV:
Wait Time xx Sec
Input OV:
Wait Time xx Sec
Input OC:
Wait Time xx Sec
Output UV:
Wait Time xx Sec
Output OV:
Wait Time xx Sec
Output OC:
Wait Time xx Sec
Figure 4.1
Page 9
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
6.4 SETTINGS menu: access and submenus
6.4 SETTINGS menu: access and submenus
You can access the SETTINGS menu starting from the STAND BY… status just by pressing the <ESC> key or, alternatively, the <ENTER> key: see Fig.1 on page 3. The access is protected by the 1
ST
level password. The default password is “0000”. To insert the "0" character press the <ENTER> key on front panel. With the <UP> and <DOWN> keys you can scroll all the sub-menus listed in Fig.4. Use<ENTER> to selectone of them.
The sequence of the 1
ST
level submenus with the setting parameters isdescribed below(PROTECTIONS
and SERVICE submenus are addressed on the following pages).Use <UP> and <DOWN> keys to set the "xx" parameters at the desired value. Then press <ENTER> to
confirm.
Set Ilimit - - >
1.3
Ilimit = x x .x A p k
1.3.1
- To set the maximum current delivered by the unit
- Setting range:
230Vac models: 1Apk to 8Apk with 0.1A resolution
115Vac models: 0Apk to 14Apk with 0.1A resolution
- Factory setting:
230Vac models: 8 Apk
115Vac models: 14 A
p
k
<ENT>
<ENT>
<ENT>
<ENT>
<ENT>
<ENT>
Set Address - - >
1.1
Address= xx - - >
1.1.1
SET Address
- To set the serial port address (Address = "xx").
- The address must be set only when the serial
communication in parallel configuration is used. Otherwise
you can leave the default value.
- Available address range: from 1 to 32
- Default address: 1
Set Backlight Time lenght
Light X
1.6.1
- The back light time lenght can be set from 2 to 60 sec.
- Factory setting: 20sec.
Display Light - - >
1.6
Set Key Click ON/OFF
Key clic k - - >
1.7
Key Click ON/OFF
1.7.1
- To enable the audible "click" when a key is pressed
- Factory setting: "Click ON"
SET Frequency
f = xx.xx Hz
1.4.1
- Setting range: 47Hz to 63Hz
-
Factory setting:
230Vac models: 50Hz
115Vac models: 60Hz
Set frequ e nc y - - >
1.4
You can access the SETTINGS menu starting from the STAND BY… status just by pressing the <ESC> key
or, alternatively, the <ENTER> key: see Fig.1 on page 3.
The access is protected by the 1
ST
level password. The default password is “0000”. To insert the "0"
character press the <ENTER> key on front panel.
With the <UP> and <DOWN> keys you can scroll all the sub-menus listed in Fig.4. Use <ENTER> to select
one of them.
ST
The sequence of the 1
level submenus with the setting parameters is described below (PROTECTIONS
and SERVICE submenus are addressed on the following pages).
Use <UP> and <DOWN> keys to set the "xx" parameters at the desired value. Then press <ENTER> to
confirm.
SET Vout
Set Vo u t - - >
1.2
- To set the Vout value as follows:
230Vac models: from 200Vac to 240V ac with 0.1V resolution
115Vac models: from 100Vac to 121 V ac with 0.1V resolution
-Remote ON ⇒It is possible to turn ON /OFF the unitremotely provided that a switch or relay is connectedbetween pins 6 and 7 of the signal connector on the backside of the unit. Refer to the Installation Manual".
-Factory Setting: Remote "OFF"
<ENT>
Autostart -- >
1.8
AutostartON/OFF
1.8.1
Auto-Start ON ⇒the unit starts up as soon as the DC inpu
t
source connection is made. In this case there is no nee
d to
press the <ON/OFF> key on front panel.Auto-Start OFF⇒The unit starts up only after <ON/OFF>
key
has been pressed.Factory setting: Auto-Start OFF
Password****
1.11.1
new password digits use the <UP> and <DOWN> keys.Factory setting: "0000"
NewPassword -->
1.11
<ENT>
NOTES
The following settings are not accessible when the current configuration unit mode is the Parallel mode.
That is to avoid conflicts within the system. Set Vout , Set I
LIMIT
, Set Frequency, Set Remote ON/OFF.
If the user wants to make changes when operating in Parallel mode, he unit must first of all set to StandAlone mode using the following procedure (to be repeated for each unit working in parallel):
1. Set the unit to Stand-alone mode:
•on the SETTINGS menu select the SERVICE submenu. Press <Enter> to confirm the choice.
•Insert the 2nd level password (default password is “1111”; use the <UP> and <DOWN> keys to select
the digits. Press <Enter> to confirm.
•Select the OPERATING MODE submenu and press <Enter>.
•Change "Mode = 2"(parallel mode) into "Mode =0"(stand-al
one mode). Use the <UP> key to insert the
character "0".
2. Change the Vout, I
LIMIT
, Frequency and Remote ON/OFF settings like explained before.
3. After the changes are done restore the parallel mode with the same procedure described in step 1.
It is strongly recommended to set all units with identical Vout, I
LIMIT
, Frequency and Remote ON/OFF values
when working in parallel.
ON/OFF
1.9.1
- Remote ON ⇒ It is possible to turn ON /OFF the unit
remotely provided that a switch or relay is connected
between pins 6 and 7 of the signal connector on the back
side of the unit. Refer to the Installation Manual".
- Factory Setting: Remote "OFF"
<ENT>
Set Autostart Mode
Autos tart - - >
1.8
Autostart ON/OFF
1.8.1
-
Auto-Start ON ⇒ the unit starts up as soon as the DC inpu
t
source connection is made. In this case there is no nee
d to
press the <ON/OFF> key on front panel.
-
Auto-Start OFF⇒ The unit starts up only after <ON/OFF>
key
has been pressed.
-
Factory setting: Auto-Start OFF
Set New Password
Password ****
1.11.1
- This option allows to change the current password. To set the
new password digits use the <UP> and <DOWN> keys.
- Max. Password length: 4
-
Factory setting: "0000"
New Password - - >
1.11
<ENT>
Set Remote ON/OFF
Rem o te O N/OFF - - >
1.9
Manual No. sli-15-G-3a
Page 11
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
6.5 SETTINGS menu: the PROTECTIONS submenu
6.5 SETTINGS menu: the PROTECTIONS submenu
enu
6.5 SETTINGS menu: the PROTECTIONS submenu
Sub- Menu 4 Level
th
Input UV: Wait Time xx Sec
Input OV:
Wait Time xx Sec
Input OC:
Wait Time xx Sec
Output UV:
Wait Time xx Sec
Output OV:
Wait Time xx SecOutput OC:Wait Time xx Sec
Sub- Menu
Protections
ENT/
ESC
Sub- Menu
Restart xx Times Output UV: Restart xx Times Output OV: Restart xx times
Output OC:Restart xx Times
ENT/
ESC
ENT/
ESC
2 Level
nd
Input UV
Input OV
Input UC Output UV Output OV Output OC
ENT/
ESC
n
u
3 Level
rd
Input UV: Restart xx Times
Input OV:Restart xxTimes Input OC:
Figure 5
Each type of protection listed on the table in Fig.5 (I
Output OC) , can be customized from the front panel.
After selecting an item listed in the PROTECTIONS submenu (Fig. 5) it is possible to choose between two
types of protection mode: "Restart mode” or "Latch up mode".
Restart mode
The unit tries to restart a certain numbers ("xx"
Set "xx" from 1 to 10 using <UP>
Set "xx" >10 and press the <ENTER> to hav
and <DOWN> keys. Press <Enter> to confirm. Factory setting = 5 times.
ENT/
Sub- Menu
ESC
rd
3 Level
Input UV:
Restart xx Times
Input OV:
Restart xxTimes
Input OC:
Restart xx Times
Output UV:
Restart xx Times
Output OV:
Restart xx times
Output OC:
Restart xx Times
Sub- Menu
ENT/
th
ESC
4 Level
Input UV:
Wait Time xx Sec
Input OV:
Wait Time xx Sec
Input OC:
Wait Time xx Sec
Output UV:
Wait Time xx Sec
Output OV:
Wait Time xx Sec
Output OC:
Wait Time xx Sec
e the unit continuously try to restart.
Manual No. sli-15-G-3a
Page 12
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
6.6 SETTINGS menu: the TRANSFER SWITCH submenu
enu
With the TRANSFER SWITCH submenu you can set t
and define the tolerance of electrical parameters such
STS.
Use <UP> and <Down> keys to set the "xx" parameters
SET Voltage Mask
The Voltage Mask defines the range of Vout values for which the STS does not operate.
The Voltage Mask limits are expressed as a percentage “xx” of the Vout (see Set Vout on page 8).For
instance, if you set Vout =230Vac and the Voltage Mask
outside the 184-276Vac range (voltage mask width in Fig.7).
The settable percentage range is 15% to 50%
Example
Assuming that the current setting for STS mode is the ON
the load), and that the output voltage is within the
(the load connected to the inverter). Otherwise, w
commutes the load to the grid (which is the
The check of the Vout is made on its peak values.
To
SETTINGS
M
ENT/
ESC
Transfer Switch
Up/
Down
Sub- Menu
rd
Level
2
Set Voltage Mask
Set RMS Voltage
Tolerance
Set Frequency
Tolerance
Set Restore Time
Transfer Switch
Operat. Mode
Manual Switch
Up/
Down
Figure 6
he Static-Transfer Switch (STS) operation mode for
as voltage and frequency for the operation with the
at the desired value. To confirm: press <ENTER> .
V. Mask = xx %
1.12.2
ENT
Set Vo lta g e - - >
Mask (%)
1.12.1
ENT/
Sub- Menu
rd
ESC
Level
3
V Mask = "xx" (%)
Tolerance= "xx" (%)
V
RMS
F Tolerance="xx" (%)
Time = "xx" sec.
Mode "X"
Connected to the grid
Not Connected
Connected to the Inverter
at 20% then the STS will activate only Vout falls
of Vout. Factory setting: 15%
limits of the voltage mask, then the STS remains open
hen the Vout lies beyond the voltage mask limits, the STS
secondary or back-up source in this case).
-Line mode (the inverter is the primary source for
Voltage Mask Width
Figure 7
The AC Grid Voltage drops into the "Set Voltage Mask "
⇒the STS does not operate.
The AC Grid Voltage drops OUT of the " Voltage Mask Width"
⇒ the STS operates.
Manual No. sli-15-G-3a
Page 13
sli15-userguide-rev3a-0718.indd
SET Vrms
POWERING TECHNOLOGY
ENT
Set RMS Voltage - - >
Tolerance 1.12.2
Vrms Tol . = xx %
1.12.2.1
The STS can operate not only based on the peak value of Vout but also based on the RMS value. With the
"Set V
" screen you can define a percentage “xx” of the Vout within which the STS does not operate.
RMS
For instance, if Vout =230Vac and V
=10% then the STS is activated only if the output RMS value V
RMS
RMS
falls outside the 253-207Vac range.
The percentage range is 5% to 50% of Vout. Factory setting: 10%
SET Frequency Tolerance
ENT
Set Frequency - - >
Tolerance (%) 1.12.3
F To l. = x x %
1.12.3.1
- With this screen you can define the max. frequency over which the STS is activated.
- The allowed range is 1 to 10% of the nominal frequency set by the SETTINGS menu (see pag.8: SET
frequency screen). Factory setting: 2%
Example
If the frequency is set on 50Hz in the SETTINGS menu and the Frequency tolerance is set at 3% then the
STS changed state only if the frequency of the primary source exceeds 51.5Hz or falls below 48.5 Hz.
SET Restore Time
Set Restore Time
(sec) - - >
1.12.4
ENT
Time = xx sec.
1.12.3.1
The Restore Time is the time “xx” elapsed after the STS is activated and before the STS attempts to restore
the previous mode. During this time the STS checks the system parameters (Vout, V
, Frequency,...) to
GRID
verify if they all have returned to the normal range, so that the load can be switched back safely to the
primary source.
The Restore time range is 10 - 7200 sec with in increments of 5 seconds. Factory setting: 10seconds.
Set Transfer Switch Mode
ENT
Trans fer S w itc h - - >
Operat. Mode1.12.5
Mode X
1.12.5.1
The STS can operate in the following modes:
- Mode 0 ("X"=0): ):" OFF Mode": the STS is NOT CONNECTED.
- Mode 1 ("X"=1): On Line mode: the STS normally remains open (the load is connected to the inverter
output), and connects the load to the grid when it closes.
- Mode 2 ("X"=2): Off Line mode: the STS normally remains closed (the load is connected to the grid),
and connects the load to the inverter when it is opens.
- Mode 3 ("X"=3): Manual mode: the STS status is configured by Set Manual Switch screen.
Factory setting: Mode 1 (On-Line mode)
Manual No. sli-15-G-3a
Page 14
sli15-userguide-rev3a-0718.indd
Set Manual Switch
POWERING TECHNOLOGY
The MANUAL SWITCH submenu is enabled by the selecting the Mode 3 (Manual mode) setting in the
TRANSFER-SWITCH-MODE submenu.
ENT
Man u al s w itc h - - >
1.12.6
Connected to grid
1.12.6.1
Not Connected
1.12.6.2
Connected to the inverter
1.12.6.3
With this setting it is possible to force the STS to be connect the load to the grid to the inverter or to
maintain the load disconnected.
7 The STATUS menu
SETTINGS
UP/
DOWN
STATUS Menu - - >
2.0
UP/
DOWN
1st Level
Sub- Menu
ENT
Master Ad. "X"
Parallel mode
ESC
Master (or Slave)
Master Ad.1
Parallel Mode 2
Parallel (or Stand - Alone)
INFO Menu
Figure 8
The STATUS menu shows:
-the current status (Master or Slave)
-the current configuration mode (Stand Alone mode or Parallel mode)
-the serial port address
Serial port
address
Manual No. sli-15-G-3a
Page 15
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
8 The INFO menu
SETTINGS
UP/
DOWN
STATUS Menu
UP/
DOWN
INFO Menu - - >
3.0
UP/
Down
ENT/
1st Level
ESC
Sub- Menu
Part Number
Serial number
Firmware
Figure 9
Up/
Down
ENT/
2nd Level
ESC
Sub- Menu
SLI-xx-xxx
1500VA 3.1.1
SN xxxxxx
Week xx Year xx
DC-DC
xxxx-xxxx 3.3.1
DC-AC
xxxx-xxxx 3.3.2
Controller
xxxx-xxxx 3.3.3
Transfer Switch
xxxx-xxxx 3.3.4
With the INFO menu you can obtain information about:
- Model Number : SLI - xx - xxx
Factory
description code
Vinput
Vout (230 or 115Vac)
(48 or 24)
- Serial Number: factory serial number, including manufacturing week & year
- Firmware revision
DSP Software release for the DC-DC stage
DSP Software release for the DC-AC stage
DSP Software release for the Controller stage
Manual No. sli-15-G-3a
Page 16
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
Appendix A : The SERVICE menu
The access to the SERVICE submenu should be reserved to authorized operators only because it allows tooperate on critical system parameters.
To get the access at the SERVICE submenu you have to enter the SETTINGS menu with the 1
ST
level
password (default password: "0000"), select the sub-menu SERVICE and insert the 2
ND
level password
(default password: "1111"). Once entered the SERVICE submenu it is possible to conduct the following tasks:
1.Change the operating mode
-Stand-alone mode (default mode) ⇒ set the "X" = 0 on the 2
ND
Level Sub- Menu on Fig.A.1
-Parallel mode⇒set the "X" = 2 on the 2
ND
Level Sub- Menu on Fig.A.1
d
t
d
d
Appendix A : The SERVICE menu
The access to the SERVICE submenu should be reserved to authorized operators only because it allows tooperate on critical system parameters.
To get the access at the SERVICE submenu you have to enter the SETTINGS menu with the 1
ST
level
password (default password: "0000"), select the sub-menu SERVICE and insert the 2
ND
level password
(default password: "1111"). Once entered the SERVICE submenu it is possible to conduct the following tasks:
1.Change the operating mode
-Stand-alone mode (default mode) ⇒ set the "X" = 0 on the 2
ND
Level Sub- Menu on Fig.A.1
-Parallel mode
⇒set the "X" = 2 on the 2
ND
Level Sub- Menu on Fig.A.1
SERVICE Menu (ReservedArea)
2
n
d
Level
Sub- Menu
Mode = "X"
1.10.1.1
NewPassword
**** Restoring
1.10.3.1
1
st
Level
Sub- Menu
Operate Mode
1.10.1
New password
1.10.2Restore E2Data 1.10.3 Utility1.10.4 System Time Out 1.10.5
ENT/
ESC
ENT/
ESC
ENT/
ESC
1
s
t
level
sub-menu
2
n
d
level
sub-menu
ServicePassword ****
Service -->
1.10
UP/
Down
STATUS Menu
(*)
Restart "xx" Times
1.10.5.1
INFO Menu
Up/
Down
Wait Time"xx" sec
1.10.5.2
2
n
d
Level
Sub- Menu
ON/OFF Buzzer ON/OFF Led LCDON/OFF Led Power ON/OFF Led O.T.ON/OFF Led Fan Fault ON/OFF Led Fault ON/OFF FansSet Fan SpeedRead Fan Speed Read SystemTempRead Internal TempRead Ambient Temp
(*) Utility Menu
Up/
Down
Fig.A.1
Appendix A : The SERVICE menu
The access to the SERVICE submenu should be reserved to authorized operators only because it allows to
operate on critical system parameters.
To get the access at the SERVICE submenu you have to enter the SETTINGS menu with the 1
password (default password: "0000"), select the sub-menu SERVICE and insert the 2
(default password: "1111").
ND
level password
ST
level
Once entered the SERVICE submenu it is possible to conduct the following tasks:
-Stand-alone mode (default mode) ⇒ set the "X" = 0 on the 2
-Parallel mode
⇒ set the "X" = 2 on the 2
1. Change the operating mode
ND
Level Sub- Menu on Fig.A.1
ND
Level Sub- Menu on Fig.A.1
SETTINGS Menu
STATUS Menu
INFO Menu
SERVICE Menu (Reserved Area)
s
1
level
sub-menu
2
n
level
sub-menu
Service - - >
(*) Utility Menu
1. Change the 2
Define a new password for the "SERVICE" Menu. The password length is 4 digits. Use the <UP> and
Fig.A.1
ND
level Password
<DOWN> keys to type the characters on the display. Press <ENTER> to confirm.
2. Restore the factory settings
With this option you can restore all the factory settings (see "Appendix B").
1.10
ENT/
ESC
Up/
Down
Service
Password ****
UP/
Down
n
2
Level
Sub- Menu
ON/OFF Buzzer
ON/OFF Led LCD
ON/OFF Led Power
ON/OFF Led O.T.
ON/OFF Led Fan Fault
ON/OFF Led Fault
ON/OFF Fans
Set Fan Speed
Read Fan Speed
Read System Temp
Read Internal Temp
Read Ambient Temp
ENT/
ESC
st
1
Sub- Menu
Operate Mode
New pas sword
Restore E2
Data 1.10.3
Utility 1.10.4
System Time
Out 1.10.5
Select the items "Restore E2 data" and press <ENTER>. The screen "Restoring" appears on the display.
Press <ENTER> to restore the factory settings.
Level
1.10.1
1.10.2
Up/
Down
ENT/
2
ESC
Sub- Menu
Mode = "X"
1.10.1.1
New Password
****
Restoring
1.10.3.1
Restart "xx"
Times
1.10.5.1
Wait Time
"xx" sec
1.10.5.2
n
Level
(*)
Manual No. sli-15-G-3a
Page 17
sli15-userguide-rev3a-0718.indd
3. UTILITY
POWERING TECHNOLOGY
This submenu is reserved to manufacturer’s perso nnel for testing the operative condition of the LED’s
and fans, as well as to monitor the temperature. We recommend you do not change the factory settings
in this submenu.
4. SET THE TIME OUT
The Time Out is the time waited by the unit before attempting to start again after a general fault is
occurred.
Restart mode
The "Restart Mode" can be the "Restart xx times" mode or the "Restart always" mode.
The unit tries to restart a certain numbers ("xx") of times, after which the unit latches up.
Set "xx" from 1 to 10 using <UP> and <DOWN> keys. Press <Enter> to confirm. Factory setting = 5
times.
Set "xx" >10 and press the <ENTER> to have the unit continuously try to restart.
The default protection mode for all protections is Restart 5 times.
Wait Time
The Wait Time is the time between two restart attempts (only for the "Restart xx times" mode).
The Wait Time can be defined in the following range: 2sec to 60sec. Factory setting = 5 sec.
Manual No. sli-15-G-3a
Page 18
sli15-userguide-rev3a-0718.indd
POWERING TECHNOLOGY
Appendix B: factory settings
FACTORY SETTINGS TABLE
(values on brackets refer to the 115Vac Inverter Version)
SETTINGS MENU
Options Default assignaments
-Password0000
-Vout230Vac (115Vac)
-Frequency50Hz (60Hz)
-Ilimit8Apk (14Apk)
-Display light length20 sec.
-Key click ON/OFFON
-Auto-start ON/OFFAuto-start OFF
-Remote ON/OFFRemote OFF
-
PROTECTIONS MENU (Sub-Menu of SETTINGS MENU)
-ModeAuto-restart (all protections)
-Restart Attemps5 times
-Wait Time (between 2 attemps)5 sec.
TRANSFER SWITCH MENU (Sub Menu of SETTINGS MENU)
-Voltage Mask15% Vout
-RMS Voltage Tolerance10% Vout
-Frequency Tolerance2% of nominal frequency
-Restore Time10 sec.
-Operat. Mode"On-Line " = "Mode 1"
SERVICE MENU (Sub-Menu of SETTINGS MENU)
-Password1111
-Operat. Mode"Stand-alone" = "Mode 0"
System Time-out
-ModeAuto-restart
-Restart Attemps5 times
-Wait Time (between 2 attemps) 5 sec.
This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for
consequences from printing errors or inaccuracies. Specications are subject to change without notice.
Manual No. sli-15-G-3a
Page 19
sli15-userguide-rev3a-0718.indd
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.