Unipower SAGEON Site Monitor Application Note

UNIPOWER, LLC
Sageon™ Site Monitor (SSM)
Application Note
AN103-4012-00, Issue 3
Sageon Site Monitor (SSM) Application Note
RECEIVING INSTRUCTIONS
&
GENERAL
Please Note: For your protection, the following information and the product manual should be read and thoroughly understood before unpacking, installing, or using the equipment.
UNIPOWER, LLC presents all equipment to the delivering carrier securely packed and in perfect condition. Upon acceptance of the package from us, the delivering carrier assumed responsibility for its safe arrival to you. Once you receive the equipment, it is your responsibility to document any damage the carrier may have inflicted, and to file your claim promptly and accurately.
1. PACKAGE INSPECTION
1.1 Examine the shipping crate or carton for any visible damage: punctures, dents, and any other signs of
possible internal damage.
1.2 Describe any damage or shortage on the receiving documents, and have the carrier sign their full name.
1.3 If your receiving freight bill notes that a Tip -N-Tell is attac hed to your frei ght, locate it. If the Tip-N-
Tell arrow has turned even partially blue, this means the freight has been tipped in transport. Make sure the carrier notes this on your receipt before you sign for th
2. EQUIPMENT INSPECTION
2.1 Within fifteen days, open the crate and inspect the contents for damages. While unpacking, be careful
not to discard any equipment, parts, or manuals. If any damage is detected, call the delivering carrier to determine appropriate action. They may require an inspecti on.
*SAVE ALL SHIP PING MATERIAL FOR THE INSPECTOR TO SEE!
2.2 After the inspection has been made, call UNIPOWER. We will determine if the equip ment should be
returned to our plant for repair, or if some other method would be more expeditious. If it is determined that the equipment should be returned to UNIPOWER, ask the delivering carrier to send the packages back to UNIPOWER at the delivering carrier's expense.
2.3 If repair is necessary, we will invoice you for the repair so that you may submit the bill to the
delivering carrier with your claim form.
2.4 It is your responsibility to file a clai m with the delivering carrier. Failure to properly file a claim for
shipping damages may void warranty service for any physical damages later reported for repair.
3. HANDLING
Equipment can be universally heavy or top-heavy. Use adequate humanpower or equipment for handling. U ntil the equip ment is securely mounted, be care ful to prevent the equipment from b eing accidentally tipped over.
4. NAMEPLATE
Each piece of UNIPOWER equipment is identified by a part number on the nameplate. Please refer to this number in all correspondence with UNIPOWER.
5. INITIAL SETTINGS
All equipment is shipped from our production area fully checked and adjusted. Do not make any adjustments until you have referred to the technical reference or product manual.
EQUIPMENT INFORMATION
e freight.
AN103-4012-00, Issue 3 i
Sageon Site Monitor (SSM) Application Note
Page(s) Altered
Updated UNIPOWER logo & contact information. See PCO# 44448.
WD 6/26/17
6. SPARE PARTS
To minimize downtime during installation or operation, we suggest you purchase spare fuses, circuit boards and other recommended components as listed on the Recommended Spare Parts List in the back of the prod uct manual. If nothing else, we strongly recommend stocking spar e fuses for a ll systems.
Issue
3 All
Description Issued by / Date
PROPRIETARY AND CONFIDENTIAL
The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of the manual or any portion of the manual without the written permission of UNIPO WER, LLC is prohibited.
© Copyright UNIPOWER, LLC 2015
DISCLAIMER
Data, descriptions, and specifications presented herein are subject to revision by UNIPOWER, LLC without notice. While such information is believed to be accurate as indicated herein, UNIPOWER, LLC makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, UNIPOWER, LLC hereby disclaims and excludes all warranties, express, implied, or statutory, including any warranty of merchantability, any warranty of fitness for a particular purpose, and any implied warranties otherwise arising from course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific application.
Throughou t the remainder of this manual, “UNIPOWER” will mean “UNIPOWER, LLC.”
PERSONNEL REQUIREMENTS
Installation, setup, operation, and servicing of this equipment should be performed by qualified persons thoroughly familiar with this Product Manual and Applicable Local and National Codes. A copy of this manual is included with the equipmen t shipment.
Table of Contents
1.0 Introduction ............................................................................................................................................... 1
2.0 Applications ............................................................................................................................................... 1
3.0 Example Installation .................................................................................................................................. 1
4.0 System Configuration ................................................................................................................................ 2
5.0 Electrical Specification .............................................................................................................................. 2
6.0 Physical Specification ............................................................................................................................... 3
AN103-4012-00, Issue 3 ii
Sageon Site Monitor (SSM) Application Note
4 C/O RELAY
CONTACT
OUTPUTS
HVAC
INVERTERS
GENERATOR
SEN
SEN
SEN
V
I
f
V I f
FUEL
LEVEL
FUEL
POWER PLANT
DIESEL
SSM
12 DIGITAL
INPUTS
8 ANALOG
INPUTS
Expansion module
cable to SCU
4 C/O RELAY
CONTACT
OUTPUTS
4 C/O RELAY
CONTACT
OUTPUTS
HVAC
INVERTERS
GENERATOR
SEN
SEN
SEN
V
I
f
V I f
FUEL
LEVEL
FUEL
POWER PLANT
DIESEL
SSM
12 DIGITAL
INPUTS
8 ANALOG
INPUTS
Expansion module
cable to SCU

1.0 INTRODUCTION

The Sageon Site Monitor (SSM) is an auxiliary module for the SageonDC Power Plant. The SSM provides additional I/O for the power plant enabling users to monitor the status of additional equipment through the Sageon system. The SSM includes twelve digital inputs and eight analog inputs for monitoring devices such as site security (door and window magnetic switches), AC Inverter status and alarms, Generator status (fuel level, oil pressure), and HVAC status and alarms. Also included are four voltage free (dry), Form C control output relays. The control relays can be automatically activated in response to an event on any of the SSM digital or analog input (configurable by the user), or operated manually fro m a PC running SageView.

2.0 APPLICATIONS

The SSM provides a simple, integrated solution to many common application challenges elimina ti n g the nee d t o purchase separate monitoring equipment. Using the remote communication capabilities and SageView software, the Sageon system can be remotely monitored, allowing the appropriate response to site events.
Typical applications include:
Integration of site alarms
Integration of Inverter status
Individual load monitoring
Integration of auxiliary equipmen t status

3.0 EXAMPLE INSTALLATION

In this example the auxiliary site e quipment is integrated into the site monito r. The I/O for this application include:
Analog Inputs
Generator fuel level
Generator output voltage, current, and frequency
Inverter out put volta ge, current , and frequency
Digital Inputs
Window and door opening sensors
HVAC alarms
Digital Outputs
NOC alarm generation
Local alarms
Strobe lights
AN103-4012-00, Issue 3 1
Sageon Site Monitor (SSM) Application Note

4.0 SYSTEM CONFIGURATION

The SSM is e as ily c on fig ured usin g the Sa geV ie w pro gra m inc lud ed wit h eac h Sa geo n DC Power Plant. The Site Monitor configuration screen is pictured below and provides a simple, intuitive user interface.
Each input has a user-de fined label field (up to 8 characters) to describe its function. If a label field is left blank, the corresponding input is treated as not used. Analog input fields al so include a two-character field for the description of the units of measure as well as high and low alarm thresholds. Scaling factor for analog inputs are set-up for 0 volts (0% F.S.) to 4 volts (100% F.S.). The type of digital input source (normally open or normally closed) is user definable by selecting the appropriate check box. Each discrete output can be automatically generated based on any combination of discrete and analog inputs.

5.0 ELECTRICAL SPECIFICATION

Analog inputs
Number of inputs: 8 Input Range : 0 to +4Vdc Full Scale,
Over-voltage and reverse polarity protected. Configuration: Scaling factor, lo w and high alarm levels are user programmable. Electrical Isolation: Non-isolated. Each analog input source must be isolated.
Digital inputs
Number of inputs: 12 Source type: Voltage free (dry) contact closure Active state: User defined (active open or active closed) Electrical Isolation: Non-isolated. Each digital input source must be isolated.
Digital outputs
Number of outputs: 4 Output type: Voltage free (dry) 1 Form C relay contacts Output rating: 1A@30VDC
General
Power Source: Self powered from the Sageon Interface Board Plant Connection:16 conductor cable to the Sageon Interface Board Maximum Distance: 30 feet (9.14 meters)
AN103-4012-00, Issue 3 2
Sageon Site Monitor (SSM) Application Note

6.0 PHYSICAL SPECIFICATION

Module Dimensions (approx): 5.11” x 9.37” x 3.14” (130 x 238 x 80) (DxWxH)
AN103-4012-00, Issue 3 3