Sageon Site Monitor (SSM) Application Note
RECEIVINGINSTRUCTIONS
&
GENERAL
Please Note: For your protection, the following information and the product manual should be read
and thoroughly understood before unpacking, installing, or using the equipment.
UNIPOWER, LLC presents all equipment to the delivering carrier securely packed and in perfect
condition. Upon acceptance of the package from us, the delivering carrier assumed responsibility for
its safe arrival to you. Once you receive the equipment, it is your responsibility to document any
damage the carrier may have inflicted, and to file your claim promptly and accurately.
1. PACKAGEINSPECTION
1.1 Examine the shipping crate or carton for any visible damage: punctures, dents, and any other signs of
possible internal damage.
1.2 Describe any damage or shortage on the receiving documents, and have the carrier sign their full name.
1.3 If your receiving freight bill notes that a Tip -N-Tell is attac hed to your frei ght, locate it. If the Tip-N-
Tell arrow has turned even partially blue, this means the freight has been tipped in transport. Make
sure the carrier notes this on your receipt before you sign for th
2. EQUIPMENTINSPECTION
2.1 Within fifteen days, open the crate and inspect the contents for damages. While unpacking, be careful
not to discard any equipment, parts, or manuals. If any damage is detected, call the delivering carrier
to determine appropriate action. They may require an inspecti on.
*SAVE ALL SHIP PING MATERIAL FOR THE INSPECTOR TO SEE!
2.2 After the inspection has been made, call UNIPOWER. We will determine if the equip ment should be
returned to our plant for repair, or if some other method would be more expeditious. If it is determined
that the equipment should be returned to UNIPOWER, ask the delivering carrier to send the packages
back to UNIPOWER at the delivering carrier's expense.
2.3If repair is necessary, we will invoice you for the repair so that you may submit the bill to the
delivering carrier with your claim form.
2.4It is your responsibility to file a clai m with the delivering carrier. Failure to properly file a claim for
shipping damages may void warranty service for any physical damages later reported for repair.
3. HANDLING
Equipment can be universally heavy or top-heavy. Use adequate humanpower or equipment for
handling. U ntil the equip ment is securely mounted, be care ful to prevent the equipment from b eing
accidentally tipped over.
4. NAMEPLATE
Each piece of UNIPOWER equipment is identified by a part number on the nameplate. Please refer to
this number in all correspondence with UNIPOWER.
5. INITIALSETTINGS
All equipment is shipped from our production area fully checked and adjusted. Do not make any
adjustments until you have referred to the technical reference or product manual.
EQUIPMENTINFORMATION
e freight.
AN103-4012-00, Issue 3 i
Sageon Site Monitor (SSM) Application Note
Page(s)
Altered
Updated UNIPOWER logo & contact information. See
PCO# 44448.
WD
6/26/17
6. SPAREPARTS
To minimize downtime during installation or operation, we suggest you purchase spare fuses, circuit
boards and other recommended components as listed on the Recommended Spare Parts List in the back
of the prod uct manual. If nothing else, we strongly recommend stocking spar e fuses for a ll systems.
Issue
3 All
Description Issued by / Date
PROPRIETARY AND CONFIDENTIAL
The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of
the manual or any portion of the manual without the written permission of UNIPO WER, LLC is prohibited.
Data, descriptions, and specifications presented herein are subject to revision by UNIPOWER, LLC without
notice. While such information is believed to be accurate as indicated herein, UNIPOWER, LLC makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its
control, UNIPOWER, LLC hereby disclaims and excludes all warranties, express, implied, or statutory,
including any warranty of merchantability, any warranty of fitness for a particular purpose, and any implied
warranties otherwise arising from course of dealing or usage of trade. The user is solely responsible for
determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific
application.
Throughou t the remainder of this manual, “UNIPOWER” will mean “UNIPOWER, LLC.”
PERSONNEL REQUIREMENTS
Installation, setup, operation, and servicing of this equipment should be performed by qualified persons
thoroughly familiar with this Product Manual and Applicable Local and National Codes. A copy of this manual
is included with the equipmen t shipment.
3.0 Example Installation .................................................................................................................................. 1
4.0 System Configuration ................................................................................................................................ 2
The Sageon Site Monitor (SSM) is an auxiliary module for the Sageon DC Power Plant. The SSM provides
additional I/O for the power plant enabling users to monitor the status of additional equipment through the
Sageon system. The SSM includes twelve digital inputs and eight analog inputs for monitoring devices such as
site security (door and window magnetic switches), AC Inverter status and alarms, Generator status (fuel level,
oil pressure), and HVAC status and alarms. Also included are four voltage free (dry), Form C control output
relays. The control relays can be automatically activated in response to an event on any of the SSM digital or
analog input (configurable by the user), or operated manually fro m a PC running SageView.
2.0 APPLICATIONS
The SSM provides a simple, integrated solution to many common application challenges elimina ti n g the nee d t o
purchase separate monitoring equipment. Using the remote communication capabilities and SageView software,
the Sageon system can be remotely monitored, allowing the appropriate response to site events.
Typical applications include:
• Integration of site alarms
• Integration of Inverter status
• Individual load monitoring
• Integration of auxiliary equipmen t status
3.0 EXAMPLE INSTALLATION
In this example the auxiliary site e quipment is integrated into the site monito r. The I/O for this application
include:
Analog Inputs
• Generator fuel level
• Generator output voltage, current, and frequency
• Inverter out put volta ge, current , and frequency
Digital Inputs
• Window and door opening sensors
• HVAC alarms
Digital Outputs
• NOC alarm generation
• Local alarms
• Strobe lights
AN103-4012-00, Issue 3 1
Sageon Site Monitor (SSM) Application Note
4.0 SYSTEM CONFIGURATION
The SSM is e as ily c on fig ured usin g the Sa geV ie w pro gra m inc lud ed wit h eac h Sa geo n DC Power Plant. The
Site Monitor configuration screen is pictured below and provides a simple, intuitive user interface.
Each input has a user-de fined label field (up to 8 characters) to describe its function. If a label field is left blank,
the corresponding input is treated as not used. Analog input fields al so include a two-character field for the
description of the units of measure as well as high and low alarm thresholds. Scaling factor for analog inputs
are set-up for 0 volts (0% F.S.) to 4 volts (100% F.S.). The type of digital input source (normally open or
normally closed) is user definable by selecting the appropriate check box. Each discrete output can be
automatically generated based on any combination of discrete and analog inputs.
5.0 ELECTRICAL SPECIFICATION
Analog inputs
Number of inputs: 8
Input Range : 0 to +4Vdc Full Scale,
Over-voltage and reverse polarity protected.
Configuration: Scaling factor, lo w and high alarm levels are user programmable.
Electrical Isolation: Non-isolated. Each analog input source must be isolated.
Digital inputs
Number of inputs: 12
Source type: Voltage free (dry) contact closure
Active state: User defined (active open or active closed)
Electrical Isolation: Non-isolated. Each digital input source must be isolated.
Digital outputs
Number of outputs: 4
Output type: Voltage free (dry) 1 Form C relay contacts
Output rating: 1A@30VDC
General
Power Source: Self powered from the Sageon Interface Board
Plant Connection:16 conductor cable to the Sageon Interface Board
Maximum Distance: 30 feet (9.14 meters)
AN103-4012-00, Issue 3 2
Sageon Site Monitor (SSM) Application Note
6.0 PHYSICAL SPECIFICATION
Module Dimensions (approx): 5.11” x 9.37” x 3.14” (130 x 238 x 80) (DxWxH)
AN103-4012-00, Issue 3 3