PDUAC3U SERIES
AC POWER DISTRIBUTION UNITS
Manual No. PDUAC3U-3
pduac3u-man-rev3-0317.indd
www.unipowerco.com
© 2017 UNIPOWER LLC
All Rights Reserved
North America: +1 954-346-2442 • Latin America: +1 954-905-1078 • Europe: +44 1903 768200
POWERING TECHNOLOGY
PDUAC3U SERIES
OPERATING MANUAL
Contents
1.0 INTRODUCTION ..................................................................................................................4
2.0 FEATURES & OPTIONS .......................................................................................................5
3.0 PRODUCT LINE ....................................................................................................................5
4.0 SAFETY & INDUSTRY STANDARDS ................................................................................6
5.0 WARRANTY (summary) .......................................................................................................6
6.0 DESCRIPTION OF OPERATION .........................................................................................7
7.0 SPECIFICATIONS .................................................................................................................8
8.0 FRONT PANEL DESCRIPTION ...........................................................................................8
9.0 BACK PANEL DESCRIPTION .............................................................................................9
10.0 UNP ACKING AND INSPECTION ......................................................................................10
11.0 INSTALLATION ..................................................................................................................10
13.0 SETUP AND TESTING .......................................................................................................12
APPENDIX 1 - Extract from UL Test Report ...............................................................................13
Manual No. pduac3u-3
Page 2
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
PDUAC3U SERIES
OPERATING MANUAL
FIGURES
Figure 1. PDUAC3U AC Power Distribution Unit .......................................................................4
Figure 2a. Block Diagram - Single Phase .......................................................................................7
Figure 2b. Block Diagram - Three Phase ........................................................................................7
Figure 3. Front Panel View ............................................................................................................8
Figure 4. Back Panel View ............................................................................................................9
Figure 5. Output Barrier Strip Detail .............................................................................................9
Manual No. pduac3u-3
Page 3
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
PDUAC3U SERIES DC POWER DISTRIBUTION PANELS

1.0 INTRODUCTION

UNIPOWER’s PDUAC3U Series AC power distribution units accept a 3-phase input and provide single phase outputs that are distributed from the phases to ensure load babance on the source. They provide AC distribution and overload protection for up to 12 load circuits
distributed through eld wireable terminal blocks.
There are 3 basic congurations operating from nominal 120VAC, 208VAC or 230VAC outputs respectively. Each of these is available with either 4, 8 or 12 2-pole load circuit
breakers rated at 25A. Model with and without input surge protection are available.
PDUAC3U SERIES
OPERATING MANUAL
OPERATING MANUAL
These panels are only 3RU high and are supplied with brackets that allow mounting in a 19” frame.
.

Figure 1. PDUAC3U AC Power Distribution Unit

Manual No. pduac3u-3
Page 4
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY

2.0 FEATURES & OPTIONS

The following is a summary of the important features of the PDUAC3U Series.
Load Balancing on 3-Phase Source 3RU Rack Height 19” Rack-Mounting
Mates with UNIPOWER rectier systems
Terminal Block Connections| 3 Phase Input - Single Phase Output
120VAC, 208VAC or 230VAC Output
Input Surge Protection (OPTION)

3.0 PRODUCT LINE

3.1 StandardCongurations
PDUAC3U SERIES
OPERATING MANUAL
The following table lists the 18 available standard congurations of the PDUAC3U series.
MODEL NUMBER
PDUAC3U-120-04 PDUAC3U-120-08 8 x 25A PDUAC3U-120-12 12 x 25A PDUAC3U-208-04 PDUAC3U-208-08 8 x 25A PDUAC3U-208-12 12 x 25A PDUAC3U-230-04 PDUAC3U-230-08 8 x 25A PDUAC3U-230-12 12 x 25A PDUAC3U-120-04-SP PDUAC3U-120-08-SP 8 x 25A PDUAC3U-120-12-SP 12 x 25A PDUAC3U-208-04-SP PDUAC3U-208-08-SP 8 x 25A PDUAC3U-208-12-SP 12 x 25A PDUAC3U-230-04-SP PDUAC3U-230-08-SP 8 x 25A PDUAC3U-230-12-SP 12 x 25A
Notes:
1. Alternative ratings are available, consult factory.
SURGE
PROTECTION
NO
YES
NOMINAL
AC INPUT
120/208VAC
3-phase
4 wire + GND
120/208VAC
3-phase
4 wire + GND
230/400VAC
3-phase
4 wire + GND
120/208VAC
3-phase
4 wire + GND
120/208VAC
3-phase
4 wire + GND
230/400VAC
3-phase
4 wire + GND
NOMINAL
OUTPUT
120VAC
Line-Neutral
208VAC
Line-Line
230VAC
Line-Neutral
120VAC
Line-Neutral
208VAC
Line-Line
230VAC
Line-Neutral
AC
OUTPUTS
4 x 25A
4 x 25A
4 x 25A
4 x 25A
4 x 25A
4 x 25A
1
Manual No. pduac3u-3
Page 5
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY

4.0 SAFETY & INDUSTRY STANDARDS

4.1 PDUAC3U Series power distribution panels meet the following safety
requirements:
STANDARD UL60950-1, 2nd Edition
CSA22.2 No. 60950-1, 2nd Edition EN60950-1, 2nd Edition
4.2 PDUAC3U Series power distribution units (PDU) are CE marked to indicate conformance to the European Union’s Low Voltage Directive.
4.3 These PDUs operate at voltages that could potentially be hazardous. Furthermore, inadvertent short circuiting by mis-connection or other error could be harmful. This product should be handled, tested and installed only
by qualied technical persons who are trained in the use of power systems
and are well aware of the hazards involved.
PDUAC3U SERIES
OPERATING MANUAL
4.4 All connections to the PDU should be carefully checked for errors before applying power to them.
4.5 The internal voltages may be at hazardous potentials. The top cover should not be removed. There are no user-serviceable components in these units.
Removing the top cover will void the warranty.
5.0 WARRANTY(summary)
PDUAC3U Series PDUs are warranted for two (2) years from date of shipment against defects in material and workmanship. This warranty does not extend to products which have been
opened, altered or repaired by persons other than persons authorized by the manufacturer or to products which become defective due to acts of God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance.
For a complete text of UNIPOWER’ s warranty conditions please request a copy from your
local Sales Oce.
Manual No. pduac3u-3
Page 6
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
CB12
CB11
CB10
CB9
CB8
CB7
CB6
CB5
CB4
CB3
CB2
CB1
CB1
CB12
CB11
CB10
CB9
CB8
CB7
CB6
CB5
CB4
CB3
CB2
CB1
CB1

6.0 DESCRIPTION OF OPERATION

6.1 Power Distribution Circuits. Simplified schematic diagrams of the
distribution panels is shown in Figure 2. The inputs from each phase and Neutral connect to a internal copper bus bars from which the circuit breakers distribute power to the loads, either one phase and neutral for each circuit
(gure 2a) or two phases for each circuit (gure 2b) where neutral is not
distributed. This latter provides a 208VAC output.
PDUAC3U SERIES
OPERATING MANUAL
25A
CB12
25A
CB11
25A
CB10
25A
CB9
25A
CB8
25A
CB7
25A
CB6
25A
CB5
25A
CB4
25A
CB3
25A
CB2
25A
GND
L3 L2 L1
N
N
L1
L1 L2
(Option SP)
L3
PE
N
L2
L3
Figure 2a. Block Diagram - 4-wire 3-phase to single phase L-N
L3 L2 L1
N
GND
L1 L2
(Option - SP)
L3
PE
N
Figure 2b. Block Diagram - 3-wire 3-phase to two phase L-L (208V)
N
L1
L2
L3
25A
CB12
25A
CB11
25A
CB10
25A
CB9
25A
CB8
25A
CB7
25A
CB6
25A
CB5
25A
CB4
25A
CB3
25A
CB2
25A
N
N
L2 L3 N
L1 N
L3
N
N
L1 L2 N
L3 N
L2
N
L1 N
L3 N
L2 N
L1
L3
L1 L3 L2 L2 L1 L3 L2
L1
L2 L1 L3 L3 L2 L1 L3
L2 L1 L3 L2 L1 L3 L2 L1
Manual No. pduac3u-3
Page 7
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
(OPTION)

7.0 SPECIFICATIONS

The following specications are typical at 25°C unless otherwise noted.
PDUAC3U SERIES
OPERATING MANUAL
INPUT/OUTPUT
Input Voltage............................3-phase, 120/208 or 230/400VAC
4 wire & GND
Input Current...............................................100A Max. per phase
Load Circuit Breakers
-04 ...............................................................................4 x 25A
-08 ...............................................................................8 x 25A
-12 .............................................................................12 x 25A
Output Voltage Range
-120 .......................................................................85-132VAC
-208 .....................................................................180-264VAC
-230 .....................................................................180-264VAC
Frequency........................................................................47-63Hz
REGULATORY
Safety Certications....................................................UL60950-1
CSA22.2 No. 60950-1 2nd Ed. EN60950-1 2nd Ed.
Line Conducted Emissions .................FCC20780 pt.15J Curve A
EN55022 Class A
Fast Transient Immunity ..........................................EN61000-4-4
Surge Immunity .......................................................EN61000-4-5

8.0 FRONT PANEL DESCRIPTION

The front panel of the PDUAC3U, shown in Figure 3 below, consists of two sections.
The left section contains the output circuit breakers; there are 4, 8 or 12 tted
depending on the exact model. They are each rated at 25A as standard. The right section accommodates an optional surge protection feature. When this option is
not tted blanking panels are installed.
ENVIRONMENTAL
Operating Temp. Range .........................................-20°C to 50°C
Storage Temp. Range ...........................................-40°C to +85°C
Humidity..........................................0% to 90%, Non-Condensing
PHYSICAL SPECIFICATIONS
Case Material/Finish ............................ Steel/Black Powder Coat
Dimensions, Inches (mm) .........................5.1h x 16.75w x 11.5d
(43.2 x 425.5 x 292.1)
Rack Mounting................................................19” or 23”, 3U High
Weight ...................................................................23lbs (10.5Kg)
FIELD WIRING CONNECTIONS
Input (L1, L2, L3, N, GND).....Cable Compression, #2AWG max.
Output (L & LN) ..................................................No. 6-32 Screws
Output (Ground) .................................................No. 8-32 Screws
Manual No. pduac3u-3
CB1 CB2 CB3 CB4
I/
ON
I/
ON
I/
ON
O/
OFF
O/
OFF
O/
25A
OFF
25A
25A
CB6
CB5
I/
ON
I/
ON
O/
OFF
O/
OFF
25A
25A
LOAD DISTRIBUTION BREAKERS
CB7 CB8 CB9 CB10
I/
I/
ON
O/
O/
OFF
25A
25A
(4, 8 or 12 x 25A)
ON
I/
ON
OFF
O/
OFF
25A

Figure 3. Front Panel View

Page 8
CB11 CB12
I/
I/
ON
I/
ON
O/
OFF
O/
OFF
25A
25A
ON
I/
ON
O/
OFF
O/
OFF
25A
25A
AC SURGE PROTECTION
SPD
L1 L2 L3 NPE
V20-CV20-CV20-C C25-B+C
INPUT
N-PE
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
(Banks 2 & 3)
CONNECTIONS
(Bank 1)
0.375

9.0 BACK PANEL DESCRIPTION

9.1 Back View. Figure 4 shows the back of of the PDUAC3U. Inputs are at the left hand end. The outputs are to the right of this and consist of three barrier strips with
associated ground screws. There are sucient connections for connecting to a total of 3 rectier shelves, each with 4 separate AC inputs.
PDUAC3U SERIES
OPERATING MANUAL
AC INPUT
LOAD CONNECTIONS
LOAD CONNECTIONS

Figure 4. Back Panel View

9.2 Input Connections. The AC power inputs to the PDU are made through the ve
compression terminal blocks marked GND, N, L1, L2 & L3. The recommended cable size for these connections is #2AWG.
9.3 Output Connections. Output connections are shown in Figure 4. There are 3 sets of barrier strip terminals. The connections are numbered to correspond with the numbers of the front panel breakers. Each barrier strip is intended for making output
connections to a single rectier shelf. Above the barrier strips are separate screws
which are used to make the ground connections.
Barrier strip connection use No. 6-32 screws. Recommended wire size is #10AWG.
Figure 5 below shows detailed spacing of the terminals.
(9.53)
0.65
(16.5)
Manual No. pduac3u-3
0.32

Figure 5. Output Barrier Strip Detail

The ground connections use No. 8-32 screws. The recommended wire size for these
connections is #10AWG. Note that it is important to use separate wires for each ground connection to the rectier shelf.
Page 9
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY

10.0 UNP ACKING AND INSPECTION

10.1 This PDUAC3U Series PDU was carefully tested, inspected and packaged for
shipment from our factory . Upon receipt of the unit it should be carefully unpacked and inspected for any damage in shipment.
10.2 If there is evidence of damage, do not attempt to test the unit. The freight carrier
should be notied immediately and a claim for the cost of the rectier system should be led with the carrier for direct reimbursement. Be sure to include the model and
serial number of the damaged unit in all correspondence with the freight carrier. Also save the shipping carton and packing material as evidence of damage for the freight carrier’s inspection.
10.3
UNIPOWER will cooperate fully in case of any shipping damage investigation.
10.4 Always save the packing materials for later use in shipping the unit. Never ship the unit without proper packing.
PDUAC3U SERIES
OPERATING MANUAL

11.0 INSTALLATION

11.1 Mounting. This PDU can be mounted in 19-inch racks by using the supplied
brackets. Mount it from the front of the rack using the correct osets to align with
existing rack-mounted equipment.
11.2 Input Connections. Input connections should be made with stripped end wire of
size #2AWG. See Section 9.2.
Connections should be made according to the source voltage as follows:
120VAC Line-Neutral
Connect each phase to L1, L2 & L3 respectively. Connect neutral to N.
208VAC Line-Line
Connect each phase to L1, L2 & L3 respectively. Connect neutral to N.
230VAC Line-Neutral
Connect each phase to L1, L2 & L3 respectively. Connect neutral to N.
11.3 Output connections are made to barrier strip connectors and grounding screws. See Section 9.3 and Figure 5.
Manual No. pduac3u-3
Page 10
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
PDUAC3U SERIES
OPERATING MANUAL
Each output provides a single phase voltage of 120VAC, 208VAC or 230VAC
depending on the model. Models with 4 output breakers tted use CB1-4, those
with 8 breakers use CB1-8 and those with 12 breakers use CB1-12.
The internal wiring of the PDU ensures that the phases are distributed as evenly
across the outputs as possible. Make ALL connections to each rectier shelf from
a single barrier strip even if the system does not initially have a full compliment
of rectiers. This will ensure proper load balancing across the input phases and also allow rectiers to be added at a later date without the need to install additional
cables.
11.4 Checking Connections. Carefully check the input connections to the PDU and output connections to the load before operating the panel. In particular pay attention to the input wiring as described in section 11.2. Incorrect connections will not harm the PDU but may cause serious harm to the load. Check to make sure that the safety ground connections is made. Make sure that all connections are clean and secure
to minimize contact resistance.
11.5 UL Requir ements. The following should be adhered to when installing this PDU:
Elevated Operating Ambient - If installed in a closed or multi-unit rack assembly,
the operating ambient temperature of the rack environment may be greater than
room ambient. Therefore, consideration should be given to installing this PDU in an environment compatible with the maximum specied ambient temperature.
Reduced Air Flow - Installation of this PDU in a rack should be such that the amount
of air ow required for safe operation of this PDU is not compromised.
Mechanical Loading - Mounting of this PDU in the rack should be such that a
hazardous condition is not achieved due to uneven mechanical loading.
Circuit Overloading - Consideration should be given to the connection of this
PDU to the supply circuit and the eect that overloading of the circuits might have
on overcurrent protection and supply wiring. Appropriate consideration of PDU nameplate ratings should be used when addressing this concern.
Reliable Earthing - Reliable earthing of this rack-mounted PDU should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).”
Manual No. pduac3u-3
Page 11
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY

13.0 SETUP AND TESTING

13.1 It is not necessary to have the PDU mounted in a rack for initial testing. This can be done on a bench. It is also not necessary to have loads connected to the panel for this testing.
13.2 With the input power source o, connect the input wires to the PDU. Set all circuit
breakers to on.
13.3
Turn on the input power source. Check the output voltage at each set of output
terminals with a digital voltmeter.
13.4 Switch o all circuit breakers and disconnect the AC source.
13.5 The PDU may now be connected to its intended application.
13.6 If the distribution panel did not operate properly in the above tests, go back and
double check the connections to make sure it is correct.
PDUAC3U SERIES
OPERATING MANUAL
Please note that there are no user serviceable parts inside either the modules or the shelves
and that opening either will void the warranty. If you are unable to resolve any problem
call your nearest UNIPOWER sales oce for support:
US +1 954 346 2442 UK +44 1903 768200
technical.support.repair@unipowerco.com
This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for
consequences from printing errors or inaccuracies. Specications are subject to change without notice.
Manual No. pduac3u-3
Page 12
pduac3u-man-rev3-0317.indd
POWERING TECHNOLOGY
PDUAC3U SERIES
OPERATING MANUAL
APPENDIX1-ExtractfromULTestReport
Standard: UL 60950-1, 2nd Edition, 2011-12-19 (Information Technology Equipment -
Safety - Part 1: General Requirements)
CSA C22.2 No. 60950-1-07, 2nd Edition, 2011-12 (Information Technology
Equipment - Safety - Part 1: General Requirements) Certication Type: Component Recognition CCN: NWGQ2, NWGQ8 (Information Technology Equipment Including Electrical
Business Equipment) Product: AC Power Distribution Unit Model: AC Power Distribution Unit: Models PDUAC3U-200, PDUAC3U-LOW,
PDUAC3U-HIGH and PDUAC3U-xxx-yy-SP
where ‘xxx’ represents the input single or three phase voltage, ‘yy’ represents
other options that do not aect safety.
Rating: PDUAC3U-230-yy-SP
230/400Vac, 100A per phase, 50-60Hz, 3ph, 4W+G;
Output: 200-240Vac, max. 20A per output (L-N, 4 outputs per phase)
PDUAC3U-120-yy-SP
120/208Vac, 100A per phase, 50-60Hz, 3ph, 4W+G;
Output: 100-130Vac, max. 20A per output (L-N, 4 outputs per phase)
PDUAC3U-208-yy-SP
120/208Vac, 100A per phase, 50-60Hz, 3ph, 4W+G;
Output: 200-240Vac, max. 20A per output (L-L, 4 outputs per phase)
Model PDUAC3U-200
200-240Vac, 40A, 50-60Hz, Single Phase
Output: 240Vac, 50-60Hz, CB1-4: 12A; CB5: 4A CB6: 8A;
120Vac, 50-60Hz, CB7: 4A GFI, CB8A, CB9, CB10: 4A
Output Total Max Amps: 32A (per leg)
Model PDUAC3U-HIGH
200-240Vac, 64A, 50-60Hz, Single Phase
Output: 240Vac, 50-60Hz, CB1-4: 12A; CB5: 4A; CB6: 8A;
120Vac, 50-60Hz, CB7: 4A GFI, CB9-10: 8A
Output Total Max Amps: 51.2A (per leg)
Model PDUAC3U-LOW
200-240Vac, 64A, 50-60Hz, Single Phase
Output: 240Vac, 50-60Hz, CB1-4: 12A; CB5: 4A;
120Vac, 50-60Hz, CB8A: 4A, CB9, CB10: 8A
Output Total Max Amps: 51.2A (per leg)
Manual No. pduac3u-3
Page 13
pduac3u-man-rev3-0317.indd
Loading...