1Gravitas X100 Compact, Integrated DC Power System2
2Gravitas X100 with Connections7
3Gravitas X100 Integral Controller9
4Gravitas X100 Simplified Block Diagram9
5Gravitas X100 Signal Interface Connections13
27
Page 3
CONTENTS
SECTIONTOPICPA GE
1.0Introduction1
2.0General Description1
3.0Gravitas X100 Summary Features3
4.0Summary of X100 System Capability4
5.0Rectifier Summary and Specifications4
6.0Power Distributi on Section6
7.0Controller Section8
8.0Safety Warnin gs and Precaution s10
9.0Warranty10
10.0Unpacking and Inspection11
11.0Description of Operation11
12.0Installation12
13.0Introduction to Control and Monitoring15
14.0Integral Contr oller Fr on t Panel Descripti on15
15.0Signal Input/Output Connections16
16.0Integral Controller LED Indicators16
17.0Front Panel Adjustment Potentiometers16
18.0Description of Controller Operation17
19.0Controller Signal Connections18
20.0Battery T emper ature Compensation (Option)20
21.0Alarm Enabling21
22.0Voltag e and Curr en t M easur em en ts21
23.0Maintenance21
Appendix 1Gravitas X100 Data SheetA1
28
Page 4
1.0INTRODUCTION
This Operating Manual should be read through carefully before installing and operating
the Gravitas X100 Integrated DC Power System.
Connection to this system and servicing it must be performed only by qualified
technicians who are trained in the installation and operation of electrical power
systems. The safety warning described later must be carefully followed.
Unipower Telecom, a division of Unipower Corporation, does not accept responsibility
for safety, reliability or performance of these systems if any modifications or repairs are
carried out by unauthorized personnel. Unipower Telecom specified replacement parts
must be used and must be of the same type and rating to ensure continued protection
against risk of fire.
OPERATING MANUAL
GRAVITAS X100 COMPACT,
INTEGRATED DC POWER SYSTEM
Since Unipower Telecom has a policy of continued product improvement, specifications
and components of this system are subject to change.
2.0GENERAL DESCRIPTION
2.1 The Gravitas X100 is a compact, integrated DC power system. See Figure
1. It consists of three high power-density, hot-swap rectifier modules
which can produce a total 60 amperes at -48VDC, 99 amperes at +24VDC,
or +12V at 100A depending on system configuration. In a 2+1 redundant
operation the output currents are 40, 66 and 50 amperes, respectively.
There are three standard models of the X100.
2.2The complete system has a DC distribution panel with up to 5 load circuits which are protected by circuit breakers, GMT fuses or a combination
of the two. Optional is a low-voltage battery disconnect. Battery breakers
for up to two battery strings can be provided.
1
Page 5
SYSTEM FRONT VIEW
æ
BATTERY
STRING
BREAKER(S)
æ
1
2
1
2
DC LOAD
BREAKERS
æ
GMT
FUSES
æ
3
4
æ
1 4
CONTROLLER
SECTION
æ
2RU
æ
12 3
Figure 1. Gravitas X100 Compact, Integrated DC Power System
RECTIFIER
æ
MODULES
2
Page 6
2.3The integral controller has LED visual alarms, Form C relay alarms, test
points and set-point adjustments including over- and under-voltage
adjustments. There is a temperature compensation option.
2.4The complete Gravitas X100 is only 2RU high (3.47 inches or 88.1mm)
and is easily installed by a qualified technician. All connections are at the
rear to DIN-rail terminal blocks. The units may be mounted in 19- or
23-inch racks. See Figure 2.
3.0GRAVITAS X100 SUMMARY FEATURES
u Choice of Hot-Swap Rectifiers
u 120 or 230VAC Input
u Power Factor Corrected
u Class B EMI Input Filter
u Up to 60A at -48VDC
u Up to 99A at +24VDC
u Up to 100A at +12VDC
u Up to 4 DC Circuit Breakers plus GMT Fuses
u Up to 2 Battery Strings
u Up to 2 Battery String Breakers
u LV Battery Disconnect Option
u Integral Controller
u Quick, Easy Installation
u Modular Design
u Only 2RU (3.47 Inches) High
u Only 11.56 Inches (294mm) Deep
3
Page 7
4.0SUMMARY OF X100 SYSTEM CAPABILITY
Table 4-1 summarizes the Gravitas X100 overall capability for the three standard models.
Table 4-1 X100 System Capability
SYSTEM CAPABILITY
2
X100-48P/60
optionaloptionaloptional
55 5
191919
SYSTEM CAP ABILITY
System Voltage-54.4VDC+27.2VDC+13.6VDC
System Max. Current60A99A100A
System Current, 2+140A66A50A
Input Range, VAC85-26485-26485-264
Rectifier ModelRPCP48/20RPCP24/33RPCP12/50
Rectifiers Required, max.332
Battery String Breakers1 standard2 standard2 standard
Low Voltage Disconnect
Total No. of DC Loads, max.
1A-50A Breakers (standard)222
1A-20A Breakers (standard)222
½A-12A GMT Fuses (option)444
Control Features
Alarm Outputs4 standard4 standard4 standard
Temp. Compensationoptionaloptionaloptional
Rack Height2RU2RU2RU
Rack Width, Inches
NOTES:
1. Battery disconnect.
2. Up to 4 loads standard. Up to 5 loads with combination of breakers and optional GMT fuses.
3. 23-Inch mounting brackets can be supplied.
1
3
X100-24P/100
X100-12P/100
5.0RECTIFIER SUMMARY & SPECIFICATIONS
5.1The Gravitas X100 rectifiers consist of two or three parallel-connected, hot-swap
rectifier modules. There is a choice of three different modules which give the
following maximum system capabilities: -48VDC at 60 amperes, +24VDC at 99
amperes and +12VDC at 100amperes. One rectifier can be used for redundancy
with lower system output.
5.2The -48, +24 and +12 volt outputs are nominal values. The actual adjustment
ranges are 45 to 58V, 22.5 to 29V, and 11 to 14.5 respectively; the factory-set
outputs are -54.4V, +27.2V, amd 13.6V respectively. Table 5-1 summarizes the
key characteristics of the three rectifier module models.
5.3Table 5-2 gives th e d etailed specifi cations of the rectifier mod ules .
Table 5-2 Rectifier Module Specifications
INPUT
Voltage Range _______________________ 85-264 or 170-264VAC
Power Factor _______________________________________ 0.99
Total Harmonic Distortion, Max. _________________________ 5%
Frequency_______________________________________ 47-63Hz
Inrush Current Limiting ___________________________50A Peak
EMI Filter, Conducted ______________ FCC20780 pt. 15J Curve B
AC Good ______________________________________ Green LED
DC Good ______________________________________ Green LED
ENVIRONMENTAL
Operating Temp. Range ________________________ 00C to +700C
Output Current Derating ______________ 2.5%/
Storage Temp. Range _______________________ -40
Humidity_______________________ 0% to 95%, Non-Condensing
ES D_________________ Bellcore GR-1089-Core and EN61000-4-2
Cooling ____________________________________ Internal Fans
6.0POWER DISTRIBUTION SECTION
6.1Figure 1 shows the top section of the system showing two battery circuit break-
ers (one standard in the 48V model, two standard on the 24 and 12V models).
These battery breakers are rated at 80A each. Next are up to two load breakers
rated 1A to 50A in positions 1 and 2 followed by two additional load breakers
rated at 1A and 20A in postions 3 and 4. An optional 4 (active) position GMT
fuse block rated up to 15A each.
0
C, 500C to 700C
0
C to + 850C
6.2The total number of DC load circuits is five. This means any combination of up to
five breakers and fuses ar e available.
6.3The DC distribution connections are made at the rear of the X100 to DIN-Rail
terminal blocks. See Figure 2.
6
Page 10
æ
3.47
(88.1)
ALARMS, FORM C
OUTPUTS AND
TEMP. COMP.
J1 J2
æ
æ
æ
SYSTEM REAR VIEW
1A-20A
LOAD
TERMINALS
17.19
(437)
1A-50A
LOAD
TERMINALS
ææ
BAT 2
IN
æ
3 2 1
AC INPUT
Figure 2. Gravitas X100 Connections
BAT 1 IN
æ
æ
DEPTH:
11.56 (294mm)
ALL DIMENSIONS
IN INCHES (mm).
All specifications
subject to change
without notice.
7
Page 11
7.0CONTROLLER SECTION
7.1Integral Controller. This controller controls the system rectifier, monitors the
system parameters and has alarms for system failures. See Figure 3. There are
eight red LED alarms and four Form C relay outputs to indicate a failure:
◆Rectifier-Fail
◆Rectifier-Major
◆Rectifier-Minor
◆AC Input
◆Circuit Breaker or Fuse
◆Low Voltag e Disconnect
◆Overvoltage
◆Undervoltage
Four front-panel voltage-set adjustments are for:
◆Float Voltag e
◆Battery Overvoltage
◆Battery Undervoltage
◆Temper ature Compensation
Test points for load voltage and current permit external measurement of these
values.
7.2Low-Voltage Battery Disconnect (Option). This battery disconnect has a
100-ampere capacity and connects between the rectifier output bus and the
battery. The contactor disconnects the battery from the rectifier and loads when
the rectifier bus (and battery) voltage drops to 42.5V for a 48V system, 21.25V
for 24V system or 10.6V for a 12V system. When the rectifier bus voltage rises
above 49V for a 48V system, 24.5V for a 24V system, or 12.3V for a 12V system,
the contactor reconnects the battery to the rectifier bus.
8
Page 12
Figure 3. Integral Controller
Figure 4. Gravitas X100 Simplified Block Diagram
9
Page 13
8.0SAFETY WARNINGS AND PRECA UTIONS
8.1This Integrated P ower System m ust be han dled , in stalled an d m aintain ed only by
qualified technical persons who are trained in the installation and use of power
systems and are well aware of the hazards involved with these systems.
8.2WARNING: This power system has hazardous external and internal voltages;
the system also has high earth leakage current. The AC input voltage of 85
to 264VACis hazardous, and the output voltages of 45 to 58VDC, 22.5 to
29VDC and 11 to 14.5VDC are hazardous. Touching either input or output
terminals while the system is connected and operating could cause serious
injury or death. Internal assemblies are also hazardous and should not be
touched.
8.3Covers on internal assemblies should not be removed. There are no user-service-
able components in these assemblies. Removing the covers of these assemblies
will void the warran ty.
8.4Installation connections should be made without input power applied, without
battery power applied and without other power sources applied to the load.
8.5The chassis should be connected to the system frame ground terminal and a
three-wire AC power line with ground connection should be used to minimize
electrical shock hazard and ensure low EMI (electromagnetic interference).
8.6This operating manual should be read carefully and understood before attempting
installation or testing.
9.0WARRANTY
All products o f UNIPOWER Telecom, a division of UNIPOWER Corporation, are warr anted for two (2) years
from date of shipm ent against defects in material and workmanship. This warranty does not extend to
products which have been opened, altered or repaired by persons other than persons authorized by the
manufacturer or to products which become defective due to acts of God, negligence or the failure of
customer to fully follow instructions with respect to installation, applicati on or maintenance. This
warranty is extended directly by the manufacturer to the buyer and is the sole warranty applicable.
EXCEPT FOR THE FOREGOING EXPRESS W ARRANTY , THE MANUFA CTURER MAKES NO W ARRANTY , EXPRESS OR
IMPLIED, INCLUDING, BUT NOT LIMITED T O , THE W ARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. As the sole and exclusive remedy under this warranty, the manufacturer, at its
option, may repair or replace the non-conforming product or issue credit, provided the manufacturer’s
inspection establishes the existence of a defect. To exercise this remedy, the buyer must contact the
manufacturer’s Customer Service Department to obtain a Return Material Authorization number and
shipping instructions. Products returned without prior authorization will be returned to buyer. All
products returned for repair must be shipped freight prepaid to UNIPOWER. If the buyer fails to fully
comply with the foregoing, the buyer agrees that no other remedy (including, but not limited to,
incidental or consequential damages for lost profits, lost sales, injury to person or property or any other
incidental or consequential losses) shall be available to the buyer.
10
Page 14
10.0UNPACKING AND INSPECTION
10.1This Gravitas X100 Integrated DC Power System was carefully tested, inspected
and packaged for shipment from our factory. Upon receipt of the unit it should
be carefully unpacked and inspected for any damage in shipment.
10.2If there is evidence of damage, do not attempt to install the unit. The freight
carrier should be notified immediately and a claim for the cost of the system
should be filed with the carrier for direct reimbursement. Be sure to include the
model and serial number of the damaged unit in all correspondence with the
freight carri er. Also save the shipping carton and packin g m ateri al as evi d en ce o f
damage for the freight carrier’s inspection.
10.3UNIPOWER Telecom will cooperate fully in case of any shipping damage investigation.
10.4Always save the packing materials for later use in shipping the unit. Never ship
the rectifier system without proper packing.
11.0DESCRIPTION OF OPERA TION
11.1Block Diagram. A simplified block diagram of the Gravitas X100 is shown in
Figure 4.
11.2Operation. The AC input of 120 or 230VAC (Fig. 4) goes to each rectifier
through individual IFC line card entries. Optional terminal block are GMT filtered
out are avaialble. The input of each module has power factor corr ecti on resulting
in a pure factor near unity. The outputs of th e modules are connected in parallel
with an ORing diode in th e output of each rectifier. This allows rectifier module
to be hot-swapped without disturbing the output voltage.
The -48, +24VDC or +12VDC output goes through the LVD contactor and the
battery circuit breaker to the battery. The output also goes to the load circuit
breakers and then to each load. If the rectifier bus voltage drops below 42.5VDC
for a -48 system or 21.25VDC for a +24V system, and 10.6VDC for a +12V system.
the LVD contactor opens and disconnects the battery from the system output.
This generally happens when there is a failure in the AC input to the rectifiers.
When AC input is restored and the rectifier bus voltage rises above 49.0VDC for a
-48V system, 24.5VDC for a +24V system, and 12.3VDC for a +12V system the
LVD contactor closes again.
11
Page 15
11.3Control and Monitoring. The integral controller has inputs from and outputs to
each rectifier module. The inputs let the controller monitor the operation o f each
rectifier module and detect failure if it occurs. The outputs to the rectifier
modules let the controller control the module output voltage. Likewise, there is
an input and output from the Low Voltage Disconnect (LVD), an input from the
battery and an input from each load break er. These signals r esult in oper ati on o f
the alarm LEDs and the Form C relay alarms. The controller also has digital meters
to read the load voltage and current. A 50mV shunt is located in the rectifier bus
to measure the load current.
12.0INST ALLATION
12.1CAUTION: Re-read the Safety Warnings and Precautions in Section 8.0. All
power should be OFF for the input and output loads before making connections. Connection of the X100 chassis to frame ground should be made
first. If the X100 has been turned on before installation connections, it
should be turned off and given a 5-minute waiting period for all internal
energy storage capacitors to be discharged.
12.2Input AC Power Connection. See Figure 2. An unplugged 3-wire AC power line
should be connected into the input terminal blocks or plug IEC connectors. The
line, n eutral and ground connections sh ould be carefully f ollowed when making
the AC connections. The AC line cable should be sized to safely carry 20 amperes
AC.
12.3Checking Outputs. Turn all output circuit breakers to the OFF position and/or
remove all fuses from the GMT fuse-holder. With no loads connected and without
the battery connected, plug in or connect the AC input cable to the power
source. Be sure to use the correct AC voltage for the rectifier inputs. Observe the
DC voltage reading on the test points on the controller panel. The voltage should
be approximately 54.4, 27.2, or 13.6VDC (depending on model), which is the
factory setting. The current test points should read zero. One by one, turn each
output circuit breaker to the ON position and/or insert a GMT fuse and, using a
digital voltmeter, measure the DC voltage across the corresponding output
terminals. The voltage should again read approximately 54.4, 27.2, or 13.6 volts.
After each output is measured, turn OFF that circuit breaker and/or remove the
GMT fuse and turn ON and/or insert fuse in th e next one. After measuring the
last circuit, turn off that breaker and/or remove the GMT fuse and make sure
that all output breakers are in the OFF position and/or all fuses are removed.
Next, unplug or disconnect the AC input power source. Before touching any
terminals wait 5 minutes for th e internal storage capacitors to discharge.
9—
10RVADJSystem Remote Voltage Adjust Input
11—
12S(-)Control Common Output
FUNCTION DESCRIPTION
Figure 5. Gravitas X100 Signal Interface Connections
13
Page 17
12.4Controller Section Operation and Settings. At this point, before the final
installation connections, read sections 13 through 21, coverin g th e Control Panel
operation. Next, go back to sections 19, 20 and 21 and make the signal connections, controller adjustments, temperature compensation adjustment and alarm
enabling settings.
W ARNING: Remember to take precautions each time the system is turned
on and also when connecting or disconnecting the battery. Remember that
the battery has a hazardous voltage at its terminals. Also remember to
allow 5 minutes for internal capacitors to discharge after disconnecting
the AC input power and the battery.
12.5Connection to Loads. With input AC power unplugged, the battery disconnected
and no other power sources connected to the loads, make sure that all load
circuit breakers are set to the OFF position and/or all GMT fuses are removed.
See Figures 2 and 4. Connect load wires to each set of output terminals, one at a
time. Note that the front panel breaker and fuse numbers directly correspond to
the output terminal numbers. Be sure to connect the polarities correctly as
shown in Figure 4.
12.6Connection to Battery. With AC input unplugged, remove the three rectifier
modules from the system chassis. Make sure all load circuit breakers are in the
OFF position and/or all GMT fuses removed. Set the battery circuit breaker to the
OFF position. Carefully connect the battery cables to the DIN-Rail battery terminals shown in Figur e 2. while observing the correct polarity .
WARNING: Improper polarity of the battery connection may damage the
power system. Take precautions when installing the battery and note that
the battery cables are “hot” (live).
Set the battery circuit breaker to the ON position and observe the reading on the
digital voltmeter on the controller panel or connected to the test points. It
should indicate the voltage of the battery, approximately 48, 24, and 12VDC
when charged. If the battery is connected with wrong polarity, there will be no
reading on the test points.
14
Page 18
12.7System Turn-On. Perform the following operations:
◆Put the battery circuit breaker in the OFF position
◆Plug in the three rectifier modules
◆Connect the AC power cable to the AC source
◆Put the battery circuit breaker in the ON position
◆Check the digital voltmeter reading for the correct voltage
◆Set each load circuit breaker to the ON position and/or insert each fuse
◆Note the reading on the controller panel test points. With all loads
connected, the output current should not exceed rated system load
for non-redundant operation.
13.0 INTRODUCTION TO CONTROL & MONITORING
13.1 The integral controller is a basic control and monitoring system for the
X100 power system. It controls up to 3 rectifiers, precisely setting the
float voltage on all rectifiers simultaneously. It monitors the battery
voltage and current by means of front panel test points. See Figure 3.
13.2Front panel LEDs indicate status and alarm conditions of the monitored
functions. Front panel potentiometers permit easy adjustment of the
various control voltages. Form C relays also indicate status and alarms.
14.0 INTEGRAL CONTROLLER FRONT PANEL DESCRIPTION
14.1 The panel has a green LED alarm CTR which is normally green but turns
off upon failure of the Control and Monitor System.
14.2The controller has four terminals V+, V-, I+, I- for reading amperes and
volts, the load current and voltage, using external meters. The current
test points use an internal 50mV shunt. See Figure 3.
14.3Voltage adjustment potentiometers VF, OV, UV, and TC. See the definitions
in section 17.0.
14.4Finally, are the LED indicators: LVDA, FA, OVUVA, TCA, MAJA, RFA, MINA, and
ACFA. See the definitions in section 16.0.
15
Page 19
15.0SIGNAL INPUT/OUTPUT CONNECTIONS
See Figure 5. for location and description of input and output signals, including the
alarm enable switches. The input and output signal connections are to spring-clamp
terminal blocks.
16.0INTEGRAL CONTROLLER LED INDICA TORS
Red LEDs. (Normally off, failure is red) These are failure alarms indicating the following:
◆LVDA: Low V oltage Disconnect Alarm
◆FA: Failure on any circuit br eak er or fuse in th e DC distribution
◆OVUVA: Battery Overvoltage or Undervoltag e
◆TCA: T emper atur e Compen sation Alarm
◆MAJA: Major Alarm
◆RFA: Rectifi er Fail Alarm
◆MINA: Minor Alarm
◆ACFA: AC Fail Alarm
17.0FRONT PANEL ADJUSTMENT PO TENTIOMETERS
There are four front panel adjustment potentiometers:
◆VF: Float Voltage set (12 turns)
◆OV: Battery Overvoltage set (single turn)
◆UV: Battery Undervoltage set (single turn)
◆TC: T emperature Compensation set (single turn)
Note that Temperature Compensation is an option.
16
Page 20
18.0DESCRIPTION OF CONTROLLER OPERATION
18.1The system controls and monitors up to three rectifier modules. This is accom-
plished by means of a control cable which connects between the rectifier section
and controller. Through these connections the controller controls the rectifier
output voltage which is preset by the VF (float voltage) adjustment
potentiometer.
18.2The Controller also monitors the AC input and DC output of each of the
rectifiers and gives an LED warning and Form C relay contact alarm in case of
failure of any one or more of the rectifier modules.
18.3The Controller also monitors for alarms from the low voltage disconnect and
circuit breaker panel. The alarm outputs are Form C relay contacts which can be
used for remote or local system alarms.
18.4Other alarm outputs are for battery overvoltage and battery undervoltage. Th ese
are also Form C relay contacts.
18.5Battery voltage and current are also monitored by the controller. They are read
by the front panel test points. When using the front panel test points with an
external voltmeter, the system output voltage is read directly from the voltage
test points. The current, however, is read as the voltage across the current test
points which go to a 50mV shunt. A 50mV shunt voltage corresponds to 100
amperes which is the full scale current. This results in a voltage scale factor of 2
amperes per millivolt.
18.6The controller initiates a Form C alarm when any one or more circuit breakers
have tripped or GMT fuses have blown.
18.7The controller sen ses the battery voltage and provides LVD (low voltage disconnect) drop-out and pick-up drive for the LVD contactor.
17
Page 21
19.0CONTROLLER SIGNAL CONNECTIONS
19.1See Figure 5. Signal connections to the J1 and J2 spring-clamp terminal blocks
should to be made with wire gauges no. 20-26 AWG. Insulation should be
stripped 0.2” from wire end.
Alarm signals are Form C relay contact alarms for the function given. “Normally
Closed” (NC) means a “short” between this terminal and the Common (C) terminal when the function is operating properly with power applied. “Normally Open”
(NO) means an “open” between this terminal and the Common (C) terminal when
the function is operating properly with power applied.
19.31 General. All signals are preset at the factory, and these values are listed
in the following sections. Where voltages are given, the first one is for a
-48VDC system, the second for a +24V system, and the third for +12V
system.
19.32 LVD Dropout and Pickup. The Low-Voltage Disconnect (LVD) is an
option. The trip levels are factory set at -42.5, +21.25, or +10.6VDC
dropout and -49.0, +24.5, or 12.3VDC pickup. These are not field
adjustable.
19.33 Battery Float Voltage. The voltage is set at the factory at -54.4,
+27.2 or +13.6VDC. If a different nominal value is required,
do the following:
◆ Install all rectifiers in the system.
◆ Disconnect the battery and adjust the float voltage (VFL)
potentiometer on front panel to the level required. Do not use the
voltage adjustments on the front panel of the rectifier modules.
◆ Reconnect the battery.
18
Page 22
19.34 Battery Overvoltage. The voltage across the battery where the
overvoltage alarm trips is factory set at -57, +28.6, or +14.3VDC. If a
different nominal value is required, do the following:
◆Unplug all rectifiers, disconnect AC, disconnect all loads and the
battery .
◆With an external variable voltage supply rated 0-60VDC, connect
it across one set of the output load terminals and turn on its
associated circuit breaker on the front panel. Be sure to observe the
correct polarity.
◆Bring the voltage up to approximately -55V, +27.5 or +13.3VDC.
◆Verify that alarm LED (OVUV A) is off.
◆Verify that the alarm LED goes on when th e voltage is adjusted to
-57.1VDC ± 1%, +28.5VDC ± 1% or +14.3VDC ± 1%.
◆Readjust the 0V potentiometer on the front panel to set at the
desired level.
◆Verify that the alarm LED goes red at the set point.
19.35 Battery Undervoltage. The voltage across the battery where the
undervoltage alarm trips is factory set at -43.5VDC, +21.8VDC or
+ 10.9VDC. If a different value is required, do the following:
◆Follow the same procedure as described above for overvoltage
alarm setup.
◆At -55V, +27.5V, or +13.8V verify the alarm LED (OVUVA) is off.
◆It should turn red when the voltage is adjusted to -43.5 ± 1%,
+21.8VDC ± 1%, or +10.9VDC ± 1%
◆Readjust the UV potentiometer on the front panel to set at the
desired level.
◆Verify that the alarm LED goes red at the set point.
19.36 TC Input. This is the optional temperature compensation input from
the temperature compensation probe that comes with this option. The
probe is used to measure battery temperature which is used to control
the output of the rectifier. There is no polarity reference for connecting
the temperature probe. Connection of the probe is to pins 6 and 8 of
J1. See Figure 4. See Section 20 for further details on temperature
compensation.
19
Page 23
20.0BATTERY TEMPERATURE COMPENSA TION (OPTION)
20.1The temperature compensation option comes with a temperature probe and 20-
foot cable. The probe is a thermistor which is connected to J1 pins 6 and 8.
There is no polarity for this connection. The probe is used to monitor the temperature of the battery and adjust the rectifier output voltage accordingly. As
battery temperature increases, rectifier output voltage decreases.
20.2The change in output voltage with temperature is -3.75mV/0C per battery cell,
centered at 250C. For example, for a +100C temperature change from 250C with
the rectifier charging a 48V battery, the change in the rectifier output voltage
would be:
48
= 24 cells
2
V = 24 cells x 100C change x (-3.75mV/0C) = -900mV = -0.9V
20.3The probe can be located in several possible places: right on the battery to
detect the battery temperature, near the battery in free air to detect the local
ambient temperature, or on the power plant metal frame near the battery.
20.4If the TC probe is either opened or shorted, the rectifier outputs revert to the
float voltage.
20.5Setting the Temperature Compensation Voltage.
20.51 Make sure that the float voltage was set with the temperature probe
disconnected.
20.52 Before connecting the temperature probe, record the float voltage to
three digits.
20.53 Connect the temperature probe to terminals 6 and 8 of J1.
20.54 With the temperature probe at approximately 250C ambient temperature,
adjust the front panel TC potentiometer until the rectifier output voltage
as read on an external voltmeter is exactly the same as the previously
recorded float voltage.
20
Page 24
21.0ALARM ENABLING
21.1There is only one alarm function that requires enable:
◆ TC Enable (TCEN): Remove jumper from J1 Pin 4 to J1 Pin 6 to enable
the T C function.
21.2After making the signal connections, controller adjustments, temperature compensation adjustment and alarm enable settings of Sections 19 through 21, go
back to Section 12.5 to continue the installation procedure.
22.0VOLTAGE AND CURRENT MEASUREMENTS
22.1Voltage. The V+ and V- test points on the right front panel permit direct exter-
nal measurement of the battery voltage.
22.2Current. The I+ and I- test points permit direct external measurement of the
load current. A voltmeter across these test points gives a reading of 2 amperes
per millivolt.
23.0MAINTENANCE
No routine maintenance is required on the Gravitas X100 power system except for
periodic cleaning of dust and dirt around the rectifier module fans and ventilation holes.
A small vacuum nozzle should be used for this.
21
Page 25
ULTRA COMPA CT, 48V, 24V and 12V
INTEGRATED DC POWER SYSTEMS
GRA VITAS X100
æ
2RU
æ
LVD73/23/EEC
KEY FEATURES
u Compact, 2RU High
u Fully Integrated System
u Hot-Swap Rectifier Modules
u Integrated Controller
u 100A at +13.6VDC
u 99A at +27.2VDC
u 60A at -54.4VDC
u Pluggable Circuit Breakers
u Quick-Connect T erminals
u Wide Range AC Input
u Less Than 12-Inches (305mm)
Depth
SAFETY CERTIFICATIONS
AGENCY STANDARD
ULUL1950
CULCSA22.2, No. 950
DEMKOEN60950
DESCRIPTION
Gravitas X100 is an ultra-compact, integrated, DC power
system. It consists of up to three high power-density, hotswap rectifier modules which can produce 60 amperes at
-54.4VDC, 99 amperes at +27.2VDC and two rectifiers for
100A at +13.6VDC. In 2+1 redundant operation the output
current is 40 amperes or 66 amperes, respectively for
-54.4VDC & 24.72VDC, or 50 amperes for +13.6VDC.
The system has a DC distribution panel with up to 5 load
circuits which are protected by circuit breakers (standard)
and GMT fuses (option). A battery breaker is standard and
a low-voltage battery disconnect is optional.
The integral controller has LED visual alarms, Form C relay
alarms, test points and set-point adjustments including
over- and under-voltage adjustments. There is also a
temperature compensation option.
The complete Gravitas X100 is only 2RU high (3.47 inches
or 88.1mm) and is easily installed by a qualified technician. All power connections are at the rear of the unit to
DIN-rail terminal blocks. A comprehensive operating manual
explains all the details of operation and installation. The
units may be mounted in 19- or 23-inch racks.
TWO-YEAR W ARRANTY
22
PLUGGABLE
CIRCUIT
BREAKERS
A1
www.unipowertelecom.com
Page 26
GRAVITAS X100 SUMMARY FEATURES
u -48, +24, or +12VDC Hot-Swap Rectifiers
u 120 or 230VAC Input
u Power Factor Corrected
u Pluggable Circuit Breakers
u Class B EMI Input Filter
u Up to 60A at -54.4VDC
u Up to 99A at +27.2VDC
u Up to 100A at +13.6VDC
u 2+1 Redundant Operation
SYSTEM CAPABILITY
2
X100-48P/60
optionaloptionaloptional
55 5
191919
SYSTEM CAP ABILITY
System Voltage-54.4VDC+27.2VDC+13.6VDC
System Max. Current60A99A100A
System Current, 2+140A66A50A
Input Range, VAC85-26485-26485-264
Rectifier ModelRPCP48/20RPCP24/33RPCP12/50
Rectifiers Required, max.332
Battery String Breakers1 standard2 standard2 standard
Low Voltage Disconnect
Total No. of DC Loads, max.
1A-50A Breakers (standard)222
1A-20A Breakers (standard)222
½A-12A GMT Fuses (option)444
Control Features
Alarm Outputs4 standard4 standard4 standard
Temp. Compensationoptionaloptionaloptional
Rack Height2RU2RU2RU
Rack Width, Inches
NOTES:
1. Battery disconnect.
2. Up to 4 loads standard. Up to 5 loads with combination of
breakersand optional GMT fuses.
3. 23-Inch mounting brackets can be supplied.
1
3
X100-24P/100
X100-12P/100
This controller controls the system rectifier, monitors the system parameters and has alarms
for system failures. There are eight red LED alarms which indicate a failure: Major Alarm, Minor
Alarm, Fuse or Breaker Alarm, Overvoltage or Undervoltage Alarm, Temperature Compensation
Alarm, Rectifier Failure Alarm, and AC Input Failure Alarm.
Four Form C relay outputs give alarms: Major Alarm, Minor Alarm, Rectifier Failure Alarm and AC
Input Failure Alarm. Four front-panel voltage-set adjustments are for Float Voltage, Battery
Overvoltage, Battery Undervoltage and Temperature Compensation. Test points for load voltage and current permit external measurement of these values. An option for this controller
includes a temperature compensated output from the rectifier.
INTEGRAL CONTROLLER
23
Page 27
RPCP RECTIFIER MODULE SPECIFICATIONS
INPUT
Voltage Range _________________________ 85-264VAC
Power Factor _______________________________ 0.99
Total Harmonic Distortion, Max. _________________ 5%
Frequency_______________________________ 47-63Hz
Inrush Current Limiting ___________________ 50A Peak
EMI Filter, Conducted ______ FCC20780 pt. 15J Curve B
AC Good ______________________________ Green LED
DC Good ______________________________ Green LED
ENVIRONMENTAL
Operating Temp. Range ________________ 00C to +700C
Output Current Derating ______ 2.5%/
Storage Temp. Range _______________ -40
Humidity_______________ 0% to 95%, Non-Condensing
ES D_________ Bellcore GR-1089-Core and EN61000-4-2
Cooling ____________________________ Internal Fans
0
C, 500C to 700C
0
C to + 850C
æ
2RU
æ
3.47
(88.1)
BATTERY
BREAKER(S)
1
2
æ
ALARMS, FORM C
OUTPUTS AND
TEMP. COMP.
J1 J2
æ
æ
STRING
SYSTEM FRONT VIEW
DC LOAD
BREAKERS
æ
æ
1
2
æ
3
4
12 3
GMT
FUSES
æ
1 4
CONTROLLER
SECTION
SYSTEM REAR VIEW
1A-20A
LOAD
TERMINALS
æ
17.19
(437)
24
1A-50A
LOAD
TERMINALS
ææ
BAT 2
IN
BAT 1 IN
æ
3 2 1
AC INPUT
æ
æ
æ
æ
RECTIFIER
MODULES
DEPTH:
11.56 (294mm)
ALL DIMENSIONS
IN INCHES (mm).
All specifications
subject to change
without notice.
Page 28
X100 CONFIGURATION GUIDE
SYSTEM
MODEL NO.
X100-48P/60-54.4VDC@60A85-264VACRPCP48/20 3
£
X100-24P/100+27.2VDC@99A85-264VACRPCP24/33 3
£
X100-12P/100+13.6VDC@100A85-264VACRPCP12/50 2
£
HOT-SW AP RECTIFIER MODULES
SYSTEM
OUTPUT, MAX.
INPUT,
VAC
RECTIFIER
MODULES
£ RPCP 48/20 Number Ordered _____ (Include Spares)
£ RPCP 24/33 Number Ordered _____ (Include Spares)
£ RPCP 12/50 Number Ordered _____ (Include Spares)
BA TTERY PROTECTION
£ 1 Battery String Breaker (Standard for 48V System)
£ 2 Battery String Breakers (Standard for 24V and 12V System)
£ 1 Extra Battery String Breaker (Option for 48V System)
£ Low-Voltage Battery Disconnect (Option)
DC DISTRIBUTION
Up to 4 Breakers (Standard) & Up to 4 GMT Fuses (Option). Total of 5 Max.
1. Breaker ____ A (1A-50A)
2. Breaker ____ A (1A-50A)
3. Breaker ____ A (1A-20A)
4. Breaker ____ A (1A-20A)
£ GMT Fuse Block (Option). Up to 4 Fuses, 48A Max.
BREAKERS & FUSES A V AILABLE
Breakers: 1, 2.5, 5, 10, 15, 20, 25, 30, 40, & 50A
GMT Fuses: Order the number required. Maximum total current is 48A.
MAX. NO. OF
MODULES
AMPSBUSSMAN NO. COLOR NO. REQ’D
0.5AGMT- ½Red
0.75GMT- ¾Brown
1GMT - 1Gray
1.33GMT-1
2GMT-2Orange
CONTROLLER OPTION
Temperature Compensation
£
BLANK COVERS (FOR UNUSED RECTIFIER SLOTS)
Cover Position: £ 1 £ 2 £ 3 (left to right)
MOUNTING BRACKETS
19-Inch
£
1/3
White
23-Inch
£
AMPS BUSSMAN NO.COLORNO. REQ’D
10GMT - 10Red-White
12GMT- 12Green-Yel
25
3GMT- 3Blue
5GMT- 5Green
0GMT-DummyOrange
x100-revC-11-25-03.pdf