Unipower Gravitas X100 Compact Operating Manual

Page 1
OPERA TING MANUAL
DC POWER SYSTEM
Price: $25.00
Manual No. X100-203-1 X100-Man-revA-11-26-03.p65
UNIPOWER T elecom, Division of UNIPOWER Corporation
DIV. OF UNIPOWER CORP. • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, UNITED STATES • Tel: 954-346-2442 • Fax: 954-340-7901 • sales@unipower-corp.com
UNIPOWER EUROPE • Parkland Business Centre, Chartwell Road, Lancing, BN15 8UE, ENGLAND • Tel: +44(0)1903 768200 • Fax: +44(0)1903 764540 • info@unipower-europe.com
© copyright 2003 UNIPOWER Corp.
All Rights Reserved
26
Page 2
ILLUSTRATIONS
FIGURE TITLE PAGE
1 Gravitas X100 Compact, Integrated DC Power System 2 2 Gravitas X100 with Connections 7 3 Gravitas X100 Integral Controller 9 4 Gravitas X100 Simplified Block Diagram 9 5 Gravitas X100 Signal Interface Connections 13
27
Page 3
CONTENTS
SECTION TOPIC PA GE
1.0 Introduction 1
2.0 General Description 1
3.0 Gravitas X100 Summary Features 3
4.0 Summary of X100 System Capability 4
5.0 Rectifier Summary and Specifications 4
6.0 Power Distributi on Section 6
7.0 Controller Section 8
8.0 Safety Warnin gs and Precaution s 10
9.0 Warranty 10
10.0 Unpacking and Inspection 11
11.0 Description of Operation 11
12.0 Installation 12
13.0 Introduction to Control and Monitoring 15
14.0 Integral Contr oller Fr on t Panel Descripti on 15
15.0 Signal Input/Output Connections 16
16.0 Integral Controller LED Indicators 16
17.0 Front Panel Adjustment Potentiometers 16
18.0 Description of Controller Operation 17
19.0 Controller Signal Connections 18
20.0 Battery T emper ature Compensation (Option) 20
21.0 Alarm Enabling 21
22.0 Voltag e and Curr en t M easur em en ts 21
23.0 Maintenance 21
Appendix 1 Gravitas X100 Data Sheet A1
28
Page 4
1.0 INTRODUCTION
This Operating Manual should be read through carefully before installing and operating the Gravitas X100 Integrated DC Power System.
Connection to this system and servicing it must be performed only by qualified technicians who are trained in the installation and operation of electrical power systems. The safety warning described later must be carefully followed.
Unipower Telecom, a division of Unipower Corporation, does not accept responsibility for safety, reliability or performance of these systems if any modifications or repairs are carried out by unauthorized personnel. Unipower Telecom specified replacement parts must be used and must be of the same type and rating to ensure continued protection against risk of fire.
OPERATING MANUAL
GRAVITAS X100 COMPACT,
INTEGRATED DC POWER SYSTEM
Since Unipower Telecom has a policy of continued product improvement, specifications and components of this system are subject to change.
2.0 GENERAL DESCRIPTION
2.1 The Gravitas X100 is a compact, integrated DC power system. See Figure
1. It consists of three high power-density, hot-swap rectifier modules which can produce a total 60 amperes at -48VDC, 99 amperes at +24VDC, or +12V at 100A depending on system configuration. In a 2+1 redundant operation the output currents are 40, 66 and 50 amperes, respectively. There are three standard models of the X100.
2.2 The complete system has a DC distribution panel with up to 5 load cir­cuits which are protected by circuit breakers, GMT fuses or a combination of the two. Optional is a low-voltage battery disconnect. Battery breakers for up to two battery strings can be provided.
1
Page 5
SYSTEM FRONT VIEW
æ
BATTERY
STRING
BREAKER(S)
æ
1 2
1 2
DC LOAD
BREAKERS
æ
GMT
FUSES
æ
3 4
æ
1 4
CONTROLLER
SECTION
æ
2RU
æ
12 3
Figure 1. Gravitas X100 Compact, Integrated DC Power System
RECTIFIER
æ
MODULES
2
Page 6
2.3 The integral controller has LED visual alarms, Form C relay alarms, test points and set-point adjustments including over- and under-voltage adjustments. There is a temperature compensation option.
2.4 The complete Gravitas X100 is only 2RU high (3.47 inches or 88.1mm) and is easily installed by a qualified technician. All connections are at the rear to DIN-rail terminal blocks. The units may be mounted in 19- or 23-inch racks. See Figure 2.
3.0 GRAVITAS X100 SUMMARY FEATURES
u Choice of Hot-Swap Rectifiers u 120 or 230VAC Input u Power Factor Corrected u Class B EMI Input Filter u Up to 60A at -48VDC u Up to 99A at +24VDC u Up to 100A at +12VDC u Up to 4 DC Circuit Breakers plus GMT Fuses u Up to 2 Battery Strings u Up to 2 Battery String Breakers u LV Battery Disconnect Option u Integral Controller u Quick, Easy Installation u Modular Design u Only 2RU (3.47 Inches) High u Only 11.56 Inches (294mm) Deep
3
Page 7
4.0 SUMMARY OF X100 SYSTEM CAPABILITY
Table 4-1 summarizes the Gravitas X100 overall capability for the three standard models.
Table 4-1 X100 System Capability
SYSTEM CAPABILITY
2
X100-48P/60
optional optional optional
55 5
19 19 19
SYSTEM CAP ABILITY
System Voltage -54.4VDC +27.2VDC +13.6VDC System Max. Current 60A 99A 100A System Current, 2+1 40A 66A 50A Input Range, VAC 85-264 85-264 85-264 Rectifier Model RPCP48/20 RPCP24/33 RPCP12/50 Rectifiers Required, max. 3 3 2 Battery String Breakers 1 standard 2 standard 2 standard Low Voltage Disconnect Total No. of DC Loads, max. 1A-50A Breakers (standard) 2 2 2 1A-20A Breakers (standard) 2 2 2 ½A-12A GMT Fuses (option) 4 4 4 Control Features Alarm Outputs 4 standard 4 standard 4 standard Temp. Compensation optional optional optional Rack Height 2RU 2RU 2RU Rack Width, Inches
NOTES:
1. Battery disconnect.
2. Up to 4 loads standard. Up to 5 loads with combination of breakers and optional GMT fuses.
3. 23-Inch mounting brackets can be supplied.
1
3
X100-24P/100
X100-12P/100
5.0 RECTIFIER SUMMARY & SPECIFICATIONS
5.1 The Gravitas X100 rectifiers consist of two or three parallel-connected, hot-swap
rectifier modules. There is a choice of three different modules which give the following maximum system capabilities: -48VDC at 60 amperes, +24VDC at 99 amperes and +12VDC at 100amperes. One rectifier can be used for redundancy with lower system output.
5.2 The -48, +24 and +12 volt outputs are nominal values. The actual adjustment ranges are 45 to 58V, 22.5 to 29V, and 11 to 14.5 respectively; the factory-set outputs are -54.4V, +27.2V, amd 13.6V respectively. Table 5-1 summarizes the key characteristics of the three rectifier module models.
4
Page 8
Table 5-1 Rectifier Module Summary
MODULE MODEL NO.
SPECIFICATIONS RPCP48/20 RPCP24/33 RPCP12/50
Output Voltage, Nom. 48VDC 24VDC 12VDC Output Voltage, Set 54.4V 27.2V 13.6V Output Voltage Range 45-58V 22.5-29V 11-14.5V Output Current, Max. 20A 3 3A 50A Output Watts, Max. 1,088 898 680 Input Range, VAC 85-264 85-264 85-264 Input Power Factor 0.99 0.99 0.99 Input Current, 230VAC 5.6A 5.6A 5.6A 120VAC 10.8A 10.8A 10.8A Inrush Current Limit 50A Pk. 50A Pk. 50A Pk. Input Frequency, Hz 47-63 47-63 47-63 Efficiency 87% 85 % 8 2% Total Regulation, Max. 2.0% 2.0% 2.0%
5.3 Table 5-2 gives th e d etailed specifi cations of the rectifier mod ules .
Table 5-2 Rectifier Module Specifications
INPUT
Voltage Range _______________________ 85-264 or 170-264VAC Power Factor _______________________________________ 0.99 Total Harmonic Distortion, Max. _________________________ 5% Frequency_______________________________________ 47-63Hz Inrush Current Limiting ___________________________50A Peak EMI Filter, Conducted ______________ FCC20780 pt. 15J Curve B
_____________________ EN55022 Curve B Input Immunity, Conducted Fast Transients, Line-Line _________ ±2kV (EN61000-4-4 Level 3) Surges, Line-Line________________ ±1kV (EN61000-4-5 Level 2) Surges, Line-Ground _____________ ±2kV (EN61000-4-5 Level 3)
OUTPUT
Output Voltage Set, 48V Nom. _____________________ 54.4VDC 24V Nom. _____________________ 27.2VDC 12V Nom. _____________________ 13.6VDC Voltage Adjustment Range, 48V Nom. ______________ 45-58VDC 24V Nom. _____________ 22.5-29VDC 12V Nom. _____________ 11-14.5VDC Total Regualtion, Max. ______________________________ 1.0% Holdup Time____________________________________ 20msec. Overvoltage Protection, 48V Out _______________________ 58V 24V Out _______________________ 29V 12V Out ______________________14.5V
5
Page 9
Filtering: Wideband Noise, 20Mhz BW 48V Out, P-P __________________________________ 500mV 24V Out, P-P __________________________________ 250mV 12V Out, P-P __________________________________ 125mV Voice Band Noise ______________________________ <32dBrnC Current Limit __________________________ 105% Rated Current Efficiency _______________________________________ 82-87%
STA TUS INDICA TORS
AC Good ______________________________________ Green LED DC Good ______________________________________ Green LED
ENVIRONMENTAL
Operating Temp. Range ________________________ 00C to +700C Output Current Derating ______________ 2.5%/ Storage Temp. Range _______________________ -40 Humidity_______________________ 0% to 95%, Non-Condensing ES D_________________ Bellcore GR-1089-Core and EN61000-4-2 Cooling ____________________________________ Internal Fans
6.0 POWER DISTRIBUTION SECTION
6.1 Figure 1 shows the top section of the system showing two battery circuit break-
ers (one standard in the 48V model, two standard on the 24 and 12V models). These battery breakers are rated at 80A each. Next are up to two load breakers rated 1A to 50A in positions 1 and 2 followed by two additional load breakers rated at 1A and 20A in postions 3 and 4. An optional 4 (active) position GMT fuse block rated up to 15A each.
0
C, 500C to 700C
0
C to + 850C
6.2 The total number of DC load circuits is five. This means any combination of up to five breakers and fuses ar e available.
6.3 The DC distribution connections are made at the rear of the X100 to DIN-Rail terminal blocks. See Figure 2.
6
Page 10
æ
3.47
(88.1)
ALARMS, FORM C
OUTPUTS AND
TEMP. COMP.
J1 J2
æ
æ
æ
SYSTEM REAR VIEW
1A-20A
LOAD
TERMINALS
17.19
(437)
1A-50A
LOAD
TERMINALS
ææ
BAT 2
IN
æ
3 2 1
AC INPUT
Figure 2. Gravitas X100 Connections
BAT 1 IN
æ
æ
DEPTH:
11.56 (294mm)
ALL DIMENSIONS IN INCHES (mm). All specifications subject to change without notice.
7
Page 11
7.0 CONTROLLER SECTION
7.1 Integral Controller. This controller controls the system rectifier, monitors the
system parameters and has alarms for system failures. See Figure 3. There are eight red LED alarms and four Form C relay outputs to indicate a failure:
Rectifier-Fail
Rectifier-Major
Rectifier-Minor
AC Input
Circuit Breaker or Fuse
Low Voltag e Disconnect
Overvoltage
Undervoltage
Four front-panel voltage-set adjustments are for:
Float Voltag e
Battery Overvoltage
Battery Undervoltage
Temper ature Compensation
Test points for load voltage and current permit external measurement of these values.
7.2 Low-Voltage Battery Disconnect (Option). This battery disconnect has a 100-ampere capacity and connects between the rectifier output bus and the battery. The contactor disconnects the battery from the rectifier and loads when the rectifier bus (and battery) voltage drops to 42.5V for a 48V system, 21.25V for 24V system or 10.6V for a 12V system. When the rectifier bus voltage rises above 49V for a 48V system, 24.5V for a 24V system, or 12.3V for a 12V system, the contactor reconnects the battery to the rectifier bus.
8
Page 12
Figure 3. Integral Controller
Figure 4. Gravitas X100 Simplified Block Diagram
9
Page 13
8.0 SAFETY WARNINGS AND PRECA UTIONS
8.1 This Integrated P ower System m ust be han dled , in stalled an d m aintain ed only by
qualified technical persons who are trained in the installation and use of power systems and are well aware of the hazards involved with these systems.
8.2 WARNING: This power system has hazardous external and internal voltages; the system also has high earth leakage current. The AC input voltage of 85 to 264VACis hazardous, and the output voltages of 45 to 58VDC, 22.5 to 29VDC and 11 to 14.5VDC are hazardous. Touching either input or output terminals while the system is connected and operating could cause serious injury or death. Internal assemblies are also hazardous and should not be touched.
8.3 Covers on internal assemblies should not be removed. There are no user-service-
able components in these assemblies. Removing the covers of these assemblies will void the warran ty.
8.4 Installation connections should be made without input power applied, without battery power applied and without other power sources applied to the load.
8.5 The chassis should be connected to the system frame ground terminal and a three-wire AC power line with ground connection should be used to minimize electrical shock hazard and ensure low EMI (electromagnetic interference).
8.6 This operating manual should be read carefully and understood before attempting installation or testing.
9.0 WARRANTY
All products o f UNIPOWER Telecom, a division of UNIPOWER Corporation, are warr anted for two (2) years from date of shipm ent against defects in material and workmanship. This warranty does not extend to products which have been opened, altered or repaired by persons other than persons authorized by the manufacturer or to products which become defective due to acts of God, negligence or the failure of customer to fully follow instructions with respect to installation, applicati on or maintenance. This warranty is extended directly by the manufacturer to the buyer and is the sole warranty applicable. EXCEPT FOR THE FOREGOING EXPRESS W ARRANTY , THE MANUFA CTURER MAKES NO W ARRANTY , EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED T O , THE W ARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. As the sole and exclusive remedy under this warranty, the manufacturer, at its option, may repair or replace the non-conforming product or issue credit, provided the manufacturer’s inspection establishes the existence of a defect. To exercise this remedy, the buyer must contact the manufacturer’s Customer Service Department to obtain a Return Material Authorization number and shipping instructions. Products returned without prior authorization will be returned to buyer. All products returned for repair must be shipped freight prepaid to UNIPOWER. If the buyer fails to fully comply with the foregoing, the buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property or any other incidental or consequential losses) shall be available to the buyer.
10
Page 14
10.0 UNPACKING AND INSPECTION
10.1 This Gravitas X100 Integrated DC Power System was carefully tested, inspected
and packaged for shipment from our factory. Upon receipt of the unit it should be carefully unpacked and inspected for any damage in shipment.
10.2 If there is evidence of damage, do not attempt to install the unit. The freight carrier should be notified immediately and a claim for the cost of the system should be filed with the carrier for direct reimbursement. Be sure to include the model and serial number of the damaged unit in all correspondence with the freight carri er. Also save the shipping carton and packin g m ateri al as evi d en ce o f damage for the freight carrier’s inspection.
10.3 UNIPOWER Telecom will cooperate fully in case of any shipping damage investi­gation.
10.4 Always save the packing materials for later use in shipping the unit. Never ship the rectifier system without proper packing.
11.0 DESCRIPTION OF OPERA TION
11.1 Block Diagram. A simplified block diagram of the Gravitas X100 is shown in
Figure 4.
11.2 Operation. The AC input of 120 or 230VAC (Fig. 4) goes to each rectifier through individual IFC line card entries. Optional terminal block are GMT filtered out are avaialble. The input of each module has power factor corr ecti on resulting in a pure factor near unity. The outputs of th e modules are connected in parallel with an ORing diode in th e output of each rectifier. This allows rectifier module to be hot-swapped without disturbing the output voltage.
The -48, +24VDC or +12VDC output goes through the LVD contactor and the battery circuit breaker to the battery. The output also goes to the load circuit breakers and then to each load. If the rectifier bus voltage drops below 42.5VDC for a -48 system or 21.25VDC for a +24V system, and 10.6VDC for a +12V system. the LVD contactor opens and disconnects the battery from the system output. This generally happens when there is a failure in the AC input to the rectifiers. When AC input is restored and the rectifier bus voltage rises above 49.0VDC for a
-48V system, 24.5VDC for a +24V system, and 12.3VDC for a +12V system the LVD contactor closes again.
11
Page 15
11.3 Control and Monitoring. The integral controller has inputs from and outputs to each rectifier module. The inputs let the controller monitor the operation o f each rectifier module and detect failure if it occurs. The outputs to the rectifier modules let the controller control the module output voltage. Likewise, there is an input and output from the Low Voltage Disconnect (LVD), an input from the battery and an input from each load break er. These signals r esult in oper ati on o f the alarm LEDs and the Form C relay alarms. The controller also has digital meters to read the load voltage and current. A 50mV shunt is located in the rectifier bus to measure the load current.
12.0 INST ALLATION
12.1 CAUTION: Re-read the Safety Warnings and Precautions in Section 8.0. All power should be OFF for the input and output loads before making connec­tions. Connection of the X100 chassis to frame ground should be made first. If the X100 has been turned on before installation connections, it should be turned off and given a 5-minute waiting period for all internal energy storage capacitors to be discharged.
12.2 Input AC Power Connection. See Figure 2. An unplugged 3-wire AC power line
should be connected into the input terminal blocks or plug IEC connectors. The line, n eutral and ground connections sh ould be carefully f ollowed when making the AC connections. The AC line cable should be sized to safely carry 20 amperes AC.
12.3 Checking Outputs. Turn all output circuit breakers to the OFF position and/or remove all fuses from the GMT fuse-holder. With no loads connected and without the battery connected, plug in or connect the AC input cable to the power source. Be sure to use the correct AC voltage for the rectifier inputs. Observe the DC voltage reading on the test points on the controller panel. The voltage should be approximately 54.4, 27.2, or 13.6VDC (depending on model), which is the factory setting. The current test points should read zero. One by one, turn each output circuit breaker to the ON position and/or insert a GMT fuse and, using a digital voltmeter, measure the DC voltage across the corresponding output terminals. The voltage should again read approximately 54.4, 27.2, or 13.6 volts. After each output is measured, turn OFF that circuit breaker and/or remove the GMT fuse and turn ON and/or insert fuse in th e next one. After measuring the last circuit, turn off that breaker and/or remove the GMT fuse and make sure that all output breakers are in the OFF position and/or all fuses are removed. Next, unplug or disconnect the AC input power source. Before touching any terminals wait 5 minutes for th e internal storage capacitors to discharge.
12
Page 16
J2
INTERFACE CONNECTIONS
PIN
1 MINA - NC Minor Alarm Output - NC 2 MINA - C Minor Alarm Output - C 3 MINA - NO Minor Alarm Output - NO 4 MAJA - NC Major Alarm Output - NC 5 MAJA - C Major Alarm Output - C 6 MAJA - NO Major Alarm Output - NO 7 ACFA - NC AC Fail Alarm Output - NC 8 ACFA - C AC Fail Alarm Output - C
9 ACFA - NO AC Fail Alarm Output - NO 10 RFA - NC Rectifier Fail Alarm Output - NC 11 RFA - C Rectifier Fail Alarm Output - C 12 RFA - NO Rectifier Fail Alarm Output - NO
FUNCTION DESCRIPTION
J1
PIN
1— 2— 3— 4 TCEN Temperature Compensation Alarm Disable Input 5— 6 TC(+) Temperature Compensation Probe (+) Input 7— 8 TC(-) Temperature Compensation Probe (-) Input
9— 10 RVADJ System Remote Voltage Adjust Input 11 — 12 S(-) Control Common Output
FUNCTION DESCRIPTION
Figure 5. Gravitas X100 Signal Interface Connections
13
Page 17
12.4 Controller Section Operation and Settings. At this point, before the final installation connections, read sections 13 through 21, coverin g th e Control Panel operation. Next, go back to sections 19, 20 and 21 and make the signal connec­tions, controller adjustments, temperature compensation adjustment and alarm enabling settings.
W ARNING: Remember to take precautions each time the system is turned on and also when connecting or disconnecting the battery. Remember that the battery has a hazardous voltage at its terminals. Also remember to allow 5 minutes for internal capacitors to discharge after disconnecting the AC input power and the battery.
12.5 Connection to Loads. With input AC power unplugged, the battery disconnected
and no other power sources connected to the loads, make sure that all load circuit breakers are set to the OFF position and/or all GMT fuses are removed.
See Figures 2 and 4. Connect load wires to each set of output terminals, one at a time. Note that the front panel breaker and fuse numbers directly correspond to the output terminal numbers. Be sure to connect the polarities correctly as shown in Figure 4.
12.6 Connection to Battery. With AC input unplugged, remove the three rectifier modules from the system chassis. Make sure all load circuit breakers are in the OFF position and/or all GMT fuses removed. Set the battery circuit breaker to the OFF position. Carefully connect the battery cables to the DIN-Rail battery termi­nals shown in Figur e 2. while observing the correct polarity .
WARNING: Improper polarity of the battery connection may damage the power system. Take precautions when installing the battery and note that the battery cables are “hot” (live).
Set the battery circuit breaker to the ON position and observe the reading on the digital voltmeter on the controller panel or connected to the test points. It should indicate the voltage of the battery, approximately 48, 24, and 12VDC when charged. If the battery is connected with wrong polarity, there will be no reading on the test points.
14
Page 18
12.7 System Turn-On. Perform the following operations:
Put the battery circuit breaker in the OFF position
Plug in the three rectifier modules
Connect the AC power cable to the AC source
Put the battery circuit breaker in the ON position
Check the digital voltmeter reading for the correct voltage
Set each load circuit breaker to the ON position and/or insert each fuse
Note the reading on the controller panel test points. With all loads
connected, the output current should not exceed rated system load for non-redundant operation.
13.0 INTRODUCTION TO CONTROL & MONITORING
13.1 The integral controller is a basic control and monitoring system for the
X100 power system. It controls up to 3 rectifiers, precisely setting the float voltage on all rectifiers simultaneously. It monitors the battery voltage and current by means of front panel test points. See Figure 3.
13.2 Front panel LEDs indicate status and alarm conditions of the monitored functions. Front panel potentiometers permit easy adjustment of the various control voltages. Form C relays also indicate status and alarms.
14.0 INTEGRAL CONTROLLER FRONT PANEL DESCRIPTION
14.1 The panel has a green LED alarm CTR which is normally green but turns
off upon failure of the Control and Monitor System.
14.2 The controller has four terminals V+, V-, I+, I- for reading amperes and volts, the load current and voltage, using external meters. The current test points use an internal 50mV shunt. See Figure 3.
14.3 Voltage adjustment potentiometers VF, OV, UV, and TC. See the definitions in section 17.0.
14.4 Finally, are the LED indicators: LVDA, FA, OVUVA, TCA, MAJA, RFA, MINA, and ACFA. See the definitions in section 16.0.
15
Page 19
15.0 SIGNAL INPUT/OUTPUT CONNECTIONS
See Figure 5. for location and description of input and output signals, including the alarm enable switches. The input and output signal connections are to spring-clamp terminal blocks.
16.0 INTEGRAL CONTROLLER LED INDICA TORS
Red LEDs. (Normally off, failure is red) These are failure alarms indicating the following:
LVDA: Low V oltage Disconnect Alarm
FA: Failure on any circuit br eak er or fuse in th e DC distribution
OVUVA: Battery Overvoltage or Undervoltag e
TCA: T emper atur e Compen sation Alarm
MAJA: Major Alarm
RFA: Rectifi er Fail Alarm
MINA: Minor Alarm
ACFA: AC Fail Alarm
17.0 FRONT PANEL ADJUSTMENT PO TENTIOMETERS
There are four front panel adjustment potentiometers:
VF: Float Voltage set (12 turns)
OV: Battery Overvoltage set (single turn)
UV: Battery Undervoltage set (single turn)
TC: T emperature Compensation set (single turn)
Note that Temperature Compensation is an option.
16
Page 20
18.0 DESCRIPTION OF CONTROLLER OPERATION
18.1 The system controls and monitors up to three rectifier modules. This is accom-
plished by means of a control cable which connects between the rectifier section and controller. Through these connections the controller controls the rectifier output voltage which is preset by the VF (float voltage) adjustment potentiometer.
18.2 The Controller also monitors the AC input and DC output of each of the rectifiers and gives an LED warning and Form C relay contact alarm in case of failure of any one or more of the rectifier modules.
18.3 The Controller also monitors for alarms from the low voltage disconnect and circuit breaker panel. The alarm outputs are Form C relay contacts which can be used for remote or local system alarms.
18.4 Other alarm outputs are for battery overvoltage and battery undervoltage. Th ese are also Form C relay contacts.
18.5 Battery voltage and current are also monitored by the controller. They are read by the front panel test points. When using the front panel test points with an external voltmeter, the system output voltage is read directly from the voltage test points. The current, however, is read as the voltage across the current test points which go to a 50mV shunt. A 50mV shunt voltage corresponds to 100 amperes which is the full scale current. This results in a voltage scale factor of 2 amperes per millivolt.
18.6 The controller initiates a Form C alarm when any one or more circuit breakers have tripped or GMT fuses have blown.
18.7 The controller sen ses the battery voltage and provides LVD (low voltage discon­nect) drop-out and pick-up drive for the LVD contactor.
17
Page 21
19.0 CONTROLLER SIGNAL CONNECTIONS
19.1 See Figure 5. Signal connections to the J1 and J2 spring-clamp terminal blocks
should to be made with wire gauges no. 20-26 AWG. Insulation should be stripped 0.2” from wire end.
Alarm signals are Form C relay contact alarms for the function given. “Normally Closed” (NC) means a “short” between this terminal and the Common (C) termi­nal when the function is operating properly with power applied. “Normally Open” (NO) means an “open” between this terminal and the Common (C) terminal when the function is operating properly with power applied.
19.2 Form C Alarm Outputs.
ACRONYM DESCRIPTION
RFA Rectifier Fail Alarm ACFA AC Fail Alarm MINA Minor Alarm MAJA Major Alarm
19.3 Alarm and Signal Setup.
19.31 General. All signals are preset at the factory, and these values are listed
in the following sections. Where voltages are given, the first one is for a
-48VDC system, the second for a +24V system, and the third for +12V system.
19.32 LVD Dropout and Pickup. The Low-Voltage Disconnect (LVD) is an
option. The trip levels are factory set at -42.5, +21.25, or +10.6VDC dropout and -49.0, +24.5, or 12.3VDC pickup. These are not field adjustable.
19.33 Battery Float Voltage. The voltage is set at the factory at -54.4,
+27.2 or +13.6VDC. If a different nominal value is required, do the following:
Install all rectifiers in the system.
Disconnect the battery and adjust the float voltage (VFL)
potentiometer on front panel to the level required. Do not use the voltage adjustments on the front panel of the rectifier modules.
Reconnect the battery.
18
Page 22
19.34 Battery Overvoltage. The voltage across the battery where the
overvoltage alarm trips is factory set at -57, +28.6, or +14.3VDC. If a different nominal value is required, do the following:
Unplug all rectifiers, disconnect AC, disconnect all loads and the
battery .
With an external variable voltage supply rated 0-60VDC, connect
it across one set of the output load terminals and turn on its associated circuit breaker on the front panel. Be sure to observe the correct polarity.
Bring the voltage up to approximately -55V, +27.5 or +13.3VDC.
Verify that alarm LED (OVUV A) is off.
Verify that the alarm LED goes on when th e voltage is adjusted to
-57.1VDC ± 1%, +28.5VDC ± 1% or +14.3VDC ± 1%.
Readjust the 0V potentiometer on the front panel to set at the
desired level.
Verify that the alarm LED goes red at the set point.
19.35 Battery Undervoltage. The voltage across the battery where the
undervoltage alarm trips is factory set at -43.5VDC, +21.8VDC or + 10.9VDC. If a different value is required, do the following:
Follow the same procedure as described above for overvoltage
alarm setup.
At -55V, +27.5V, or +13.8V verify the alarm LED (OVUVA) is off.
It should turn red when the voltage is adjusted to -43.5 ± 1%,
+21.8VDC ± 1%, or +10.9VDC ± 1%
Readjust the UV potentiometer on the front panel to set at the
desired level.
Verify that the alarm LED goes red at the set point.
19.36 TC Input. This is the optional temperature compensation input from
the temperature compensation probe that comes with this option. The probe is used to measure battery temperature which is used to control the output of the rectifier. There is no polarity reference for connecting the temperature probe. Connection of the probe is to pins 6 and 8 of J1. See Figure 4. See Section 20 for further details on temperature compensation.
19
Page 23
20.0 BATTERY TEMPERATURE COMPENSA TION (OPTION)
20.1 The temperature compensation option comes with a temperature probe and 20-
foot cable. The probe is a thermistor which is connected to J1 pins 6 and 8. There is no polarity for this connection. The probe is used to monitor the tem­perature of the battery and adjust the rectifier output voltage accordingly. As battery temperature increases, rectifier output voltage decreases.
20.2 The change in output voltage with temperature is -3.75mV/0C per battery cell, centered at 250C. For example, for a +100C temperature change from 250C with the rectifier charging a 48V battery, the change in the rectifier output voltage would be:
48
= 24 cells
2
V = 24 cells x 100C change x (-3.75mV/0C) = -900mV = -0.9V
20.3 The probe can be located in several possible places: right on the battery to
detect the battery temperature, near the battery in free air to detect the local ambient temperature, or on the power plant metal frame near the battery.
20.4 If the TC probe is either opened or shorted, the rectifier outputs revert to the float voltage.
20.5 Setting the Temperature Compensation Voltage.
20.51 Make sure that the float voltage was set with the temperature probe
disconnected.
20.52 Before connecting the temperature probe, record the float voltage to
three digits.
20.53 Connect the temperature probe to terminals 6 and 8 of J1.
20.54 With the temperature probe at approximately 250C ambient temperature,
adjust the front panel TC potentiometer until the rectifier output voltage as read on an external voltmeter is exactly the same as the previously recorded float voltage.
20
Page 24
21.0 ALARM ENABLING
21.1 There is only one alarm function that requires enable:
TC Enable (TCEN): Remove jumper from J1 Pin 4 to J1 Pin 6 to enable
the T C function.
21.2 After making the signal connections, controller adjustments, temperature com­pensation adjustment and alarm enable settings of Sections 19 through 21, go back to Section 12.5 to continue the installation procedure.
22.0 VOLTAGE AND CURRENT MEASUREMENTS
22.1 Voltage. The V+ and V- test points on the right front panel permit direct exter-
nal measurement of the battery voltage.
22.2 Current. The I+ and I- test points permit direct external measurement of the load current. A voltmeter across these test points gives a reading of 2 amperes per millivolt.
23.0 MAINTENANCE
No routine maintenance is required on the Gravitas X100 power system except for periodic cleaning of dust and dirt around the rectifier module fans and ventilation holes. A small vacuum nozzle should be used for this.
21
Page 25
ULTRA COMPA CT, 48V, 24V and 12V
INTEGRATED DC POWER SYSTEMS
GRA VITAS X100
æ
2RU
æ
LVD73/23/EEC
KEY FEATURES
u Compact, 2RU High u Fully Integrated System u Hot-Swap Rectifier Modules u Integrated Controller u 100A at +13.6VDC u 99A at +27.2VDC u 60A at -54.4VDC u Pluggable Circuit Breakers u Quick-Connect T erminals u Wide Range AC Input u Less Than 12-Inches (305mm)
Depth
SAFETY CERTIFICATIONS
AGENCY STANDARD
UL UL1950 CUL CSA22.2, No. 950 DEMKO EN60950
DESCRIPTION
Gravitas X100 is an ultra-compact, integrated, DC power system. It consists of up to three high power-density, hot­swap rectifier modules which can produce 60 amperes at
-54.4VDC, 99 amperes at +27.2VDC and two rectifiers for 100A at +13.6VDC. In 2+1 redundant operation the output current is 40 amperes or 66 amperes, respectively for
-54.4VDC & 24.72VDC, or 50 amperes for +13.6VDC.
The system has a DC distribution panel with up to 5 load circuits which are protected by circuit breakers (standard) and GMT fuses (option). A battery breaker is standard and a low-voltage battery disconnect is optional.
The integral controller has LED visual alarms, Form C relay alarms, test points and set-point adjustments including over- and under-voltage adjustments. There is also a temperature compensation option.
The complete Gravitas X100 is only 2RU high (3.47 inches or 88.1mm) and is easily installed by a qualified techni­cian. All power connections are at the rear of the unit to DIN-rail terminal blocks. A comprehensive operating manual explains all the details of operation and installation. The units may be mounted in 19- or 23-inch racks.
TWO-YEAR W ARRANTY
22
PLUGGABLE
CIRCUIT
BREAKERS
A1
www.unipowertelecom.com
Page 26
GRAVITAS X100 SUMMARY FEATURES
u -48, +24, or +12VDC Hot-Swap Rectifiers u 120 or 230VAC Input u Power Factor Corrected u Pluggable Circuit Breakers u Class B EMI Input Filter u Up to 60A at -54.4VDC u Up to 99A at +27.2VDC u Up to 100A at +13.6VDC u 2+1 Redundant Operation
SYSTEM CAPABILITY
2
X100-48P/60
optional optional optional
55 5
19 19 19
SYSTEM CAP ABILITY
System Voltage -54.4VDC +27.2VDC +13.6VDC System Max. Current 60A 99A 100A System Current, 2+1 40A 66A 50A Input Range, VAC 85-264 85-264 85-264 Rectifier Model RPCP48/20 RPCP24/33 RPCP12/50 Rectifiers Required, max. 3 3 2 Battery String Breakers 1 standard 2 standard 2 standard Low Voltage Disconnect Total No. of DC Loads, max. 1A-50A Breakers (standard) 2 2 2 1A-20A Breakers (standard) 2 2 2 ½A-12A GMT Fuses (option) 4 4 4 Control Features Alarm Outputs 4 standard 4 standard 4 standard Temp. Compensation optional optional optional Rack Height 2RU 2RU 2RU Rack Width, Inches
NOTES:
1. Battery disconnect.
2. Up to 4 loads standard. Up to 5 loads with combination of breakers and optional GMT fuses.
3. 23-Inch mounting brackets can be supplied.
1
3
X100-24P/100
X100-12P/100
This controller controls the system rectifier, monitors the system parameters and has alarms for system failures. There are eight red LED alarms which indicate a failure: Major Alarm, Minor Alarm, Fuse or Breaker Alarm, Overvoltage or Undervoltage Alarm, Temperature Compensation Alarm, Rectifier Failure Alarm, and AC Input Failure Alarm.
Four Form C relay outputs give alarms: Major Alarm, Minor Alarm, Rectifier Failure Alarm and AC Input Failure Alarm. Four front-panel voltage-set adjustments are for Float Voltage, Battery Overvoltage, Battery Undervoltage and Temperature Compensation. Test points for load volt­age and current permit external measurement of these values. An option for this controller includes a temperature compensated output from the rectifier.
INTEGRAL CONTROLLER
23
Page 27
RPCP RECTIFIER MODULE SPECIFICATIONS
INPUT
Voltage Range _________________________ 85-264VAC Power Factor _______________________________ 0.99 Total Harmonic Distortion, Max. _________________ 5% Frequency_______________________________ 47-63Hz Inrush Current Limiting ___________________ 50A Peak EMI Filter, Conducted ______ FCC20780 pt. 15J Curve B
______________ EN55022 Curve B
Input Current, 230VAC ______________________ 5.6A
120VAC ______________________ 10.8A
Input Immunity, Conducted
Fast Transients, Line-Line ±2kV (EN61000-4-4 Level 3) Surges, Line-Line ______ ±2kV (EN61000-4-5 Level 3) Surges, Line-Ground ____ ±4kV (EN61000-4-5 Level 4)
OUTPUT
Current & Voltage, 48V Nominal ________ 20@54.4VDC
24V Nominal _______ 33A@27.2VDC 12V Nominal _______ 50A@13.6VDC
Voltage Adjustment Range, 48V Nominal ___ 45-58VDC
24V Nominal ____ 22-29VDC 12V Nominal ___ 11-14.5VDC
Output Power, Rated 48V Nominal ___________ 1,088W
24V Nominal _____________ 898W
12V Nominal _____________ 680W Total Regulation, Max. ________________________ 2% Holdup Time____________________________ 20msec.
Overvoltage Protection, 48V Nominal ___________ 59V
24V Nominal ____________ 29V
12V Nominal ___________14.5V Filtering: Wideband Noise, 20Mhz BW, 48V Nominal, P-P ______________________ 500mV 24V Nominal, P-P ______________________ 250mV 12V Nomial, P-P _______________________ 125mV Voice Band Noise ______________________ <32dBrnC Current Limit __________________ 105% Rated Current Efficiency _______________________________ 82-87%
SAFETY STANDARDS UL 1950, CSA22.2-950, EN60950
ST ATUS INDICA TORS
AC Good ______________________________ Green LED DC Good ______________________________ Green LED
ENVIRONMENTAL
Operating Temp. Range ________________ 00C to +700C Output Current Derating ______ 2.5%/ Storage Temp. Range _______________ -40 Humidity_______________ 0% to 95%, Non-Condensing ES D_________ Bellcore GR-1089-Core and EN61000-4-2 Cooling ____________________________ Internal Fans
0
C, 500C to 700C
0
C to + 850C
æ
2RU
æ
3.47
(88.1)
BATTERY
BREAKER(S)
1 2
æ
ALARMS, FORM C
OUTPUTS AND
TEMP. COMP.
J1 J2
æ
æ
STRING
SYSTEM FRONT VIEW
DC LOAD
BREAKERS
æ
æ
1 2
æ
3 4
12 3
GMT
FUSES
æ
1 4
CONTROLLER
SECTION
SYSTEM REAR VIEW
1A-20A
LOAD
TERMINALS
æ
17.19 (437)
24
1A-50A
LOAD
TERMINALS
ææ
BAT 2
IN
BAT 1 IN
æ
3 2 1
AC INPUT
æ
æ
æ
æ
RECTIFIER MODULES
DEPTH:
11.56 (294mm)
ALL DIMENSIONS IN INCHES (mm). All specifications subject to change without notice.
Page 28
X100 CONFIGURATION GUIDE
SYSTEM
MODEL NO.
X100-48P/60 -54.4VDC@60A 85-264VAC RPCP48/20 3
£
X100-24P/100 +27.2VDC@99A 85-264VAC RPCP24/33 3
£
X100-12P/100 +13.6VDC@100A 85-264VAC RPCP12/50 2
£
HOT-SW AP RECTIFIER MODULES
SYSTEM
OUTPUT, MAX.
INPUT,
VAC
RECTIFIER
MODULES
£ RPCP 48/20 Number Ordered _____ (Include Spares) £ RPCP 24/33 Number Ordered _____ (Include Spares) £ RPCP 12/50 Number Ordered _____ (Include Spares)
BA TTERY PROTECTION
£ 1 Battery String Breaker (Standard for 48V System) £ 2 Battery String Breakers (Standard for 24V and 12V System) £ 1 Extra Battery String Breaker (Option for 48V System) £ Low-Voltage Battery Disconnect (Option)
DC DISTRIBUTION
Up to 4 Breakers (Standard) & Up to 4 GMT Fuses (Option). Total of 5 Max.
1. Breaker ____ A (1A-50A)
2. Breaker ____ A (1A-50A)
3. Breaker ____ A (1A-20A)
4. Breaker ____ A (1A-20A)
£ GMT Fuse Block (Option). Up to 4 Fuses, 48A Max.
BREAKERS & FUSES A V AILABLE
Breakers: 1, 2.5, 5, 10, 15, 20, 25, 30, 40, & 50A GMT Fuses: Order the number required. Maximum total current is 48A.
MAX. NO. OF
MODULES
AMPS BUSSMAN NO. COLOR NO. REQ’D
0.5A GMT- ½ Red
0.75 GMT- ¾ Brown 1 GMT - 1 Gray
1.33 GMT-1 2 GMT-2 Orange
CONTROLLER OPTION
Temperature Compensation
£
BLANK COVERS (FOR UNUSED RECTIFIER SLOTS)
Cover Position: £ 1 £ 2 £ 3 (left to right)
MOUNTING BRACKETS
19-Inch
£
1/3
White
23-Inch
£
AMPS BUSSMAN NO. COLOR NO. REQ’D
10 GMT - 10 Red-White 12 GMT- 12 Green-Yel
25
3 GMT- 3 Blue 5 GMT- 5 Green
0 GMT-Dummy Orange
x100-revC-11-25-03.pdf