Unipower DPB1U SERIES, DPG1U SERIES Operating Manual

POWERING TECHNOLOGY
OPERATING MANUAL
POWER DISTRIBUTION PANELS
DPB1U & DPG1U SERIES
Manual No. DPB-DPG-4
dpb_dpg-man-rev4-0317.indd
www.unipowerco.com
© 2017 UNIPOWER LLC
All Rights Reserved
North America: +1 954-346-2442 • Latin America: +1 954-905-1078 • Europe: +44 1903 768200
POWERING TECHNOLOGY
DPB1U & DPG1U SERIES
OPERATING MANUAL
Contents
1.0 INTRODUCTION ...............................................................................................................4
2.0 FEATURES & OPTIONS ....................................................................................................5
3.0 PRODUCT LINE .................................................................................................................5
4.0 SAFETY & INDUSTRY STANDARDS .............................................................................6
5.0 WARRANTY (summary) ....................................................................................................6
6.0 DESCRIPTION OF OPERATION ......................................................................................7
7.0 SPECIFICATIONS ..............................................................................................................8
8.0 FRONT PANEL DESCRIPTION ........................................................................................8
9.0 BACK PANEL DESCRIPTION ........................................................................................10
10.0 UNP ACKING AND INSPECTION ...................................................................................13
11.0 INSTALLATION ...............................................................................................................14
12.0 SETUP AND TESTING ....................................................................................................16
Manual No. DPB-DPG-4
Page 2
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
DPB1U & DPG1U SERIES
OPERATING MANUAL
FIGURES
Figure 1. DPG1U & DPU1U Front Views ....................................................................................4
Figure 2. Block Diagram ...............................................................................................................7
Figure 3. DPB1U Front Panel View ..............................................................................................8
Figure 4. DPG1U Front Panel View ..............................................................................................8
Figure 5. Back Panel View ..........................................................................................................10
Figure 6. Input Bus Bar Detail ....................................................................................................10
Figure 7. Output Barrier Strip Detail ...........................................................................................11
Figure 8. Alarm Contact & Ground Detail ..................................................................................12
Figure 9. Series Connection of Multiple Panels ..........................................................................14
TABLES
Table 1. Basic Congurations ......................................................................................................5
Table 2. LED State Denitions ....................................................................................................7
Table 3. GMT Fuse Values ...........................................................................................................9
Table 4. Input Cable Lug Sizes & Types ...................................................................................11
Table 5. Alarm Relay Contacts ..................................................................................................12
Table 6. Relay State Denitions ................................................................................................12
Manual No. DPB-DPG-4
Page 3
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
DPB1U & DPG1U SERIES
OPERATING MANUAL
OPERATING MANUAL
DPB1U & DPG1U SERIES
DC POWER DISTRIBUTION PANELS

1.0 INTRODUCTION

These distribution panels provide protected power distribution to telecommunication equipment.
They oer fuse or circuit breaker positions on the A and B sides of the panel. The A and B loads
of the distribution panel are totally independent and isolated from each other. There is a green/red LED for each load to indicate normal operation or an open circuit due to a blown fuse or tripped circuit breaker.
The panels are only 1.75 inches (1 mounting position) high to minimize rack space and can be mounted
in either a 19- or 23-inch relay rack with corresponding brackets. They can be mounted from the
front of the rack with osets every ¼-inch from front to back to align with existing rackmounted
equipment.
Figure 1 shows the two series of panels. The rst is the DPG1U Series which has 10 GMT fused
circuits on both A and B sides. The second is the DPB1U Series with up to 6 circuit breaker circuits on both A and B sides.
DPG1U: GMT Fuse Distribution Panel
DPB1U: Circuit Breaker Distribution Panel

Figure 1. DPG1U & DPU1U Front Views

The panels can be congured for 12, 24 or 48 volts and are polarity neutral. Because the A and B
sides are independent and isolated, they can be congured separately. For example, the A side can be 48V and the B side can be 24V. The voltage and of each side must be congured at the factory..
Each bus (A and B) has a green/red visual alarm and one Form C relay alarm contact for connection
to external audible or visual alarms.
Manual No. DPB-DPG-4
Page 4
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY

2.0 FEATURES & OPTIONS

2.1 The following is a summary of the important features of the Series.
Thin Height: 1.75 inches (1RU) 19 or 23-Inch Rack Mounting Dual A/B Loads Current Capacity: 80 to 150A per Load (Depends on Model)
Operating Voltage: 12, 24 or 48VDC
POLARITY NEUTRAL Red/Green LED Indicators 1 Form C Relay Contacts per bus Protection: GMT Fuses or Magnetic Circuit Breakers Independent and Isolated Loads Input Connections: Crimp Type Lugs Output Connections: Barrier Terminal Strips
2.2 Options. There are two standard options available:
DPB1U & DPG1U SERIES
OPERATING MANUAL
Option S - This option internally links the A bus to the B bus so that a fully congured unit
can be supplied DC from a single feed. The A and B sides must have the same voltage and polarity. Not available with option F.
Option F (special order only) - Fail safe operation for 24 and 48V units. A and B sides with separate feeds operate redundantly so that one feed takes over both sides in case of failure of the other feed. Voltage and polarity of both sides must be the same. Note that this option
requires an extended depth chassis. Not available with option S.

3.0 PRODUCT LINE

The following table shows the basic conguration that are available for each type of panel. ‘x’ denotes the voltage and polarity. Full conguration details are given in section 8.
INPUT
FEEDS
BREAKERS / FUSES
1
2 6 Breakers Each Bus 150 300 DPB1U-Ax-Bx
1
2 10 Fuses Each Bus 80 160 DPG1U-Ax-Bx
MAX. #
6 Breakers 150 150 DPB1U-Ax
12 Breakers 150 150 DPB1U-Ax-Bx-S
10 Fuses 80 80 DPG1U-Ax 20 Fuses 80 80 DPG1U-Ax-Bx-S
AMPS
EACH FEED
TOTAL
AMPS
BASE MODEL
Table 1. Basic Congurations
Manual No. DPB-DPG-4
Page 5
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY

4.0 SAFETY & INDUSTRY STANDARDS

4.1 DPB1U & DPG1U Series power distribution panels meet the following safety requirements:
STANDARD UL60950-1, 2nd Edition
CSA22.2 No. 60950-1, 2nd Edition EN60950-1, 2nd Edition
4.2 DPB1U & DPG1U Series power distribution panels are CE marked to indicate conformance
to the European Union’s Low Voltage, EMC and RoHS Directives.
4.3 Inadvertent short circuiting of the system battery and/or rectier by mis-connection or
other error could be harmful. This product should be handled, tested and installed only by qualied technical persons who are trained in the use of power systems and are well aware
of the hazards involved.
4.4 When operating this Distribution Panels the chassis ground terminal must be connected to
the system frame ground or other proper safety ground for the protection of personnel.
DPB1U & DPG1U SERIES
OPERATING MANUAL
4.5 All connections to the Distribution Panels should be carefully checked for errors before
applying power to them.
4.6 The internal circuits may present an energy hazardous. The top cover should not be removed.
There are no user-serviceable components in these units. Removing the top cover will void the warranty.

5.0 WARRANTY (summary)

DPB1U & DPG1U Series power distribution panels are warranted for two (2) years from date of
shipment against defects in material and workmanship. This warranty does not extend to products which have been opened, altered or repaired by persons other than persons authorized by the manufacturer or to products which become defective due to acts of God, negligence or the failure of customer to fully follow instructions with respect to installation, application or maintenance.
For a complete text of UNIPOWER’s warranty conditions please request a copy from your local Sales Oce.
Manual No. DPB-DPG-4
Page 6
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
BATT.
BATT.
INPUT
INPUT
RET.
CIRCUITS
CIRCUITS
A SIDE B SIDE

6.0 DESCRIPTION OF OPERATION

6.1 Power Distribution Circuits. A simplied schematic diagram of the distribution panels
is shown in Figure 2. The battery input to each load connects to a high-current copper bus bar from which the individual fuses or circuit breakers distribute power to the loads. The return input connects to a similar bus bar to which the individual loads terminate. The A
and B loads are totally independent and isolated with the exception of models incorporating the ‘S’ option.
DPB1U & DPG1U SERIES
OPERATING MANUAL
RET.
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
1 2 3... N N ...3 2 1
LOADS LOADS
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
A SIDE
ALARM
-S OPTION
CIRCUIT
BREAKERS
or
GMT FUSES
-S OPTION
b SIDE
ALARM

Figure 2. Block Diagram

6.2 Alarm Circuits. The alarm circuits detect a tripped circuit breaker or blown and, in this
event, turn on the red part of the LEDs. The alarm circuits also each drive Form C relay contacts. If one or more circuits open or if there is an input power failure, the relays are de-energized and the contacts are used to control external audible or visual alarms. The A
and B alarm circuits are also independent and isolated from each other.
LED STATE MEANINGS
LED State Meaning
Green OK
Breaker Trip
Red
OFF No Input Power
or
Breaker OFF
or
Fuse Blown
Manual No. DPB-DPG-4
Table 2. LED State Denitions
Page 7
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
17.12 (434.9)
1.74
(44.2)
FRONT VIEW
Case depth: 8.94 (227.1)
17.12 (434.9)
FRONT VIEW
1.74
(44.2)

7.0 SPECIFICATIONS

The following specications are typical at 25°C unless otherwise noted.
DPB1U & DPG1U SERIES
OPERATING MANUAL
INPUT / OUTPUT
Panel Capacity ...........................................See Panel Conguration Table
Conguration
DPB1U
ENVIRONMENTAL
Operating T emp. Range .....................................................-10°C to +70°C
Storage T emp. Range ........................................................-40°C to + 85°C
Humidity........................................................0% to 95%, Non-Condensing
Single Bus ..............................................................1 to 12 Breakers
Dual Bus ..........................................................1 to 6 Breakers Each
DPG1U
Single Bus ...........................................................1 to 20 GMT Fuses
Dual Bus .....................................................1 to 10 GMT Fuses Each
Breaker/Fuse Capacity
2
Voltage
1
.............................................................½A to 50A
48V Nominal ..........................................................................42-60VDC
PHYSICAL SPECIFICATIONS
Case Material ......................................................................................Steel
Finish ............................................................................Powder Coat Black
Dimensions
3
, Inches (mm) ................................1.75 H x 19.00 W x 9.00 D
(44.5 x 483 x 229)
Weight ....................................................................... 10.30 lbs. ( 4.67 kg.)
Rack Mounting Width ....................................................... 19 or 23 Inches
24V Nominal ..........................................................................21-30VDC
12V Nominal .......................................................................10.5-15VDC
Polarity.....................................................................POLARITY NEUTRAL
CONNECTIONS
Input Connections.......................................Crimp Type Lug or ¼ - 20 Stud
Output Connections
ALARMS
Alarm Indicator .....................................................Dual-Color LED Per Bus
LED Status Indication ........................................................Green = Normal
Red = Alarm O󰀨 = No Power
Alarm Connections .............................One Form C Relay Contact Per Bus
SAFETY STANDARDS ..............................................UL1950, UL60950-1
1-30A ..................................................Barrier Terminal Strips, No. 6-32
40A-50A ............................................Barrier Terminal Strips, No. 10-32
Chassis Ground Connection..................................................No. 8-32 Stud
Fail Alarm Connections...........................................045” sq. Wirewrap Pins
NOTES: 1. See tables for available breaker & fuse sizes.
2. See Ordering Guide to specify voltage.
3. For units with fail safe option the case depth is 10.44 inches (265mm).
CAS22.2 No.950-1, EN60950-1

8.0 FRONT PANEL DESCRIPTION

The front panel of the DPB1U, shown in Figure 3 below, consists of the A and B sides and a center
section. The A and B sides can each accommodate up to 6 hydraulic magnetic circuit breakers rated from 1A to 50A.
OFFOON
15
OFFOON
15
OFFOON
1
I
2
I
15
OFFOON
15
I
I
OFFOON
3
4
15
OFFOON
15
I
I
5
6
ALARM
A B
OFFOON
15
OFFOON
15
OFFOON
1
I
2
I
15
OFFOON
15
I
I
OFFOON
3
4
15
OFFOON
15
5
I
6
I
A Side Breakers B Side Breakers
Alarm LEDs

Figure 3. DPB1U Front Panel View

The front panel of the DPG1U, shown in Figure 4 below, consists of the A and B sides and a center
section. The A and B sides can each accommodate up to 10 GMT Fuses rated from ½A to 12A.
ALARM
1 10
A Side Fuses B Side Fuses
A B
Alarm LEDs

Figure 4. DPG1U Front Panel View

In both cases the center section has two green/red LEDs, one for the A side (left) and the other for
the B side (right). At the bottom of this center section is a slot for a wallet and designator card. This card permits the recording of each output circuit by number.
Manual No. DPB-DPG-4
Page 8
1 10
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
8.1 DPB1U Conguration Details
Model No.: DPB1U-A -B -C-
DPB1U & DPG1U SERIES
OPERATING MANUAL
CODE VOLTAGE
1 48V 4 24V 6 12V
POLARITY NEUTRAL.
May be connected for Positive or
Negative Ground operation.
Notes: 1. If section B is not used a blank panel is installed at the factory and the “-B” in the
2. The sum of all fuse currents on either side must not exceed 150 Amperes.
3. When the ‘S’ option is specied each side of the panel is limited to 75A.
4. Failsafe (option F) is to special order only and uses a chassis 10.44” depth. Call
model number is not required.
sales to discuss your requirements.
8.2 DPG1U Conguration Details
Model: DPG1U-A-B-C-
CODE VOLTAGE
1 48V 4 24V 6 12V
POLARITY NEUTRAL.
May be connected for Positive or
Negative Ground operation.
Notes: 1. If section B is not used a blank panel is installed at the factory and the “-B” in the model number is not required.
2. The sum of all fuse currents on either side must not exceed 80 Amperes.
3. When the ‘S’ option is specied each side of the panel is limited to 75A.
4. Failsafe (option F) is to special order only and uses a chassis 10.44” depth. Call sales to discuss your requirements.
BREAKERS
CODE AMPS
F 1 G 2.5 H 5
I 10 J 15 K 20 L 25
M 30 N 40 O 50
CODE OPTION
F S
1. 24 or 48V versions only.
2. Voltage and polarity for A & B sides must be the same.
Clear Plastic Rear Safety Cover
(supplied as standard)
(supplied as standard)
CODE OPTION
F S
1. 24 or 48V versions only.
2. Voltage and polarity for A & B sides must be the same.
Fail Safe
Single Bus 20-way ²
Clear Plastic
Rear Safety Cover
1, 2
Fail Safe
Single Bus 12-way ²
1, 2
UNIPOWER recommends Bussman fuses which can be ordered using the part numbers shown.
Manual No. DPB-DPG-4
GMT FUSES (ORDER SEPARATELY)
AMPS PART NUMBER COLOR AMPS PART NUMBER COLOR
½ 401-1500-0010 Red 3 401-1500-0060 Blue ¾ 401-1500-0020 Brown 5 401-1500-0070 Green
1 401-1500-0030 Gray 10 401-1500-0080 Red/White
1
/
1
2 401-1500-0050 Orange DUMMY 401-1500-0100
401-1500-0040 White 12 401-1500-0090 Green/Yellow
3
Table 3. GMT Fuse Values
Page 9
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
Alarm LEDs
A B
ALARM
A Side Breakers B Side Breakers
5
6
3
4
1
2
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
5
6
3
4
1
2
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
17.12 (434.9)
1.74
(44.2)
REAR VIEW
FRONT VIEW
Case depth: 8.94 (227.1)
2.28
(57.8)
Clear Perspex
Safety Cover
0.34”
0.375”
0.65”
0.32”

9.0 BACK PANEL DESCRIPTION

9.1 Back View. Figure 5 shows the back of the DPB1U and DPG1U distribution panel. Inputs
are at the left and right ends of the back panel. Side B outputs are at two rows of barrier
terminal strips on the left side, and side A outputs are the same on the right side. At the
center of the back panel are two spring clamp terminal blocks for the Form C relay contact outputs.
Below these is a chassis ground terminal.
BAT
1 2 3 4 5 6 7 8 9 10
RTN
B Input
¼-20 Studs
9.2 Input Connections. See Figure 6. The DC power inputs to the distribution panels are made
by means of crimp type lugs or direct connection to ¼-20 studs to two copper bus bars on
side A and side B. The upper bus bar is the battery connection (whether + or -) and the lower bus bar is the return (whether + or -).
B Outputs
6-32 Terminal Strip
B SIDE
A SIDE
BAT
RTN
NO-C-NC NO-C-NC
Alarm
Contacts
BAT
1 2 3 4 5 6 7 8 9 10
RTN
Ground
8-32 Stud
6-32 Terminal Strip

Figure 5. Back Panel View

DPB1U & DPG1U SERIES
OPERATING MANUAL
BAT
RTN
A Outputs
A Input
¼-20 Studs
0.625”
0.5”
1.48”

Figure 6. Input Bus Bar Detail

9.3 Crimp Type Lugs. A list of compatible crimp type lugs is shown in the following table
for AWG wire sizes from no. 1 to 8 and one- or two- hole lugs. These lugs can be ordered
directly from the manufacturer, Panduit Corp., using the model numbers shown in table 4.
A standard kit of four two-hole crimp type lugs for no. 6 AWG copper wire is available from
UNIPOWER. Order kit no. 775-1434-0000.
Manual No. DPB-DPG-4
Page 10
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
0.75
0.378
DPB1U & DPG1U SERIES
OPERATING MANUAL
WIRE
AWG
8
6
4
2
1
.25DIA.
HOLES
1 2
1 2
1 2
1 2
1 2
PANDUIT CORP.
PART NUMBER
LCA8-14-L
LCD8-14A-L
LCA6-14-L
LCD6-14A-L
LCA4-14-L
LCD4-14A-L
LCA2-14-Q
LCD2-14A-Q
LCA1-14-E
LCD1-14A-E
UNIPOWER
PART NUMBER
625-1665-0010
625-1665-0110
625-1665-0020 625-1665-0120
625-1665-0030 625-1665-0130
625-1665-0040 625-1665-0140
625-1665-0050 625-1665-0150
Table 4. Input Cable Lug Sizes & Types
9.4 Output Connections. Output connections for A and B loads are shown in Figure 5. There
are 10 sets of barrier terminal strip connections for each side, A and B. The connections
are numbered to correspond with the numbers of the front panel breakers. The upper strip connections are from the battery through the breakers; the lower strip connections are the
returns. Side B is on the left and side A on the right, as shown.
Each terminal is a no. 6-32 screw and is rated at 30 amperes. Wire sizes from no. 10 AWG
up to no. 22 AWG may be used for connections. Figure 7 below shows detailed spacing of the terminals.
When DPB1U is tted with either 40A or 50A breakers the additional load rating is
accomodated by tting adaptors that bridge two barrier strip terminals and provide a single
#10-32 screw. Minimum wire size for these connections is 8 AWG.
A maximum of two high current breakers is allowed on each bus.
(19.1)
0.5
(12.7)
1 2 3 4 5
40-50A LOADS
#10-32

Figure 7. Output Barrier Strip Detail

6 7 8 9 10
1A to 30A
(9.60)
LOADS
#6-32
Manual No. DPB-DPG-4
Page 11
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
A B
ALARM
A Outputs
6-32 Terminal Strip
A Input
¼-20 Studs
BAT
RTN
1 2 3 4 5 6 7 8 9 10
5
6
5
6
3
4
1
2
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
OFFOON
I
15
17.12 (434.9)
1.74
(44.2)
REAR VIEW
FRONT VIEW
Case depth: 8.94 (227.1)
2.28
(57.8)
Clear Perspex
Safety Cover
RELAY
C
OUTPUTS
N.C.
C
N.O.
DPB1U & DPG1U SERIES
OPERATING MANUAL
9.5 Form C Relay Contact Outputs. The center of the back panel has connections to the
Form C relay contact outputs for connection to external audible or visual alarm circuits.
See Figure 8.
B SIDE
A SIDE
BAT
NO-C-NC NO-C-NC
RTN
Ground
Alarm
8-32 Stud
Contacts

Figure 8. Alarm Contact & Ground Detail

Connection is made via two Phoenix Contact spring clamp terminal blocks. “B SIDE” is
for the Form C relay contact of side B and “A SIDE” is for the Form C relay contact of side A. The terminals, viewed from left to right, are the normally open (NO) common (C) and normally closed (NC) contacts, respectively. See table 5 below.
PIN FUNCTION CONTACT SCHEMATIC
NC N.C. (normally closed)
C C (common)
NO N.O. (normally open)
ONTACTS
Table 5. Alarm Relay Contacts
“Normally Closed” and “Normally Open” are dened with the distribution panel powered
and providing power to all outputs, i.e. no circuit breakers tripped AND when the input power is connected to a side (A or B), the Form C relay of that side is energized. If there is either loss of input power, one or more circuit breakers trip or the relay is de-energized,
the normally open contacts close and the normally closed contacts open. See table 6.
RELAY STATE MEANINGS
Relay State Meaning
Energized (N.C. is closed) OK
De-energized
(N.C. is open)
Breaker Trip
Breaker OFF
Fuse Blown
No Input Power
or or
Manual No. DPB-DPG-4
Table 6. Relay State Denitions
Page 12
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
The ratings of the relay contacts are 0.6A at 125VAC or 2A at 30VDC. The spring clamp
terminals accept wire sizes nos. 16 to 26 AWG.
9.6 Chassis Ground Connection. Just below the Form C relay contact terminals is the chassis
ground terminal. This terminal is a no. 8-32 stud with a nut.
NOTE THAT IT IS ESSENTIAL THAT THIS TERMINAL IS CONNECTED TO THE
SYSTEM FRAME GROUND TO ENSURE SAFE OPERATION.

10.0 UNPACKING AND INSPECTION

10.1 This power distribution panel was carefully tested, inspected and packaged for shipment
from our factory . The unit and circuit breakers are shipped separately. Upon receipt of the unit it should be carefully unpacked and inspected for any damage in shipment.
10.2 If there is evidence of damage, do not attempt to test the unit. The freight carrier should
be notied immediately and a claim for the cost of the rectier system should be led with
the carrier for direct reimbursement. Be sure to include the model and serial number of the damaged unit in all correspondence with the freight carrier. Also save the shipping carton
and packing material as evidence of damage for the freight carrier’s inspection.
DPB1U & DPG1U SERIES
OPERATING MANUAL
10.3 UNIPOWER will cooperate fully in case of any shipping damage investigation.
10.4 Always save the packing materials for later use in shipping the unit. Never ship the rectier
system without proper packing.
Manual No. DPB-DPG-4
Page 13
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
80A/150A MAX. FEED

11.0 INSTALLATION

11.1 Mounting. This distribution panel can be mounted in either 19- or 23-inch racks by using
the supplied reversible brackets. Mount it from the front of the rack using the correct osets to align with existing rack-mounted equipment.
The bracket osets are every quarter inch from front to back.
11.2 Power Connections. Input connections should be made with one- or two-terminal crimp
type lugs using copper wire size from no. 1 to 8 AWG, depending on current and wire loop
distance. See Sections 9.2 and 9.3. Output connections are made to the barrier terminal strips. See Section 9.4 and Figure 7.
11.2.1 Single feed models with option S - Although these models have both left and right
side input bus bars tted, it is only necessary to connect the input feed to one side
for correct operation. As the unused side is directly connected to the live input
feed it can be used for supplying additional panels in series. See gure 9 below.
DPB1U & DPG1U SERIES
OPERATING MANUAL
ALM B ALM A
BAT
SIDE A
SIDE B
RTN
BAT
SIDE A
SIDE B
RTN
BAT
SIDE A
SIDE B
RTN
NO-C-NC NO-C-NC
ALM B ALM A
NO-C-NC NO-C-NC
ALM B ALM A
NO-C-NC NO-C-NC
BAT
1 2 3 4 5 6 7 8 9 10
RTN
BAT
1 2 3 4 5 6 7 8 9 10
RTN
BAT
1 2 3 4 5 6 7 8 9 10
RTN
BAT
RTN
BAT
RTN
BAT
RTN
RETURN
BAT
1 2 3 4 5 6 7 8 9 10
RTN
BAT
1 2 3 4 5 6 7 8 9 10
RTN
BAT
1 2 3 4 5 6 7 8 9 10
RTN

Figure 9. Series Connection of Multiple Panels

When deploying panels with option S, either individually or in a chain, the following
must be adhered to so as to meet with UL safety requirements:
a) The maximum load drawn through the breaker/fuse outputs either side of the
panel may not exceed 75A.
b) The current drawn from one panel in the chain to the next is limited to 75A less
the total amount being drawn through the breaker/fuse outputs on all previous panels in the chain.
CAUTION: BOTH PAIRS OF INPUT BUS BARS ARE CONNECTED INTERNALL Y
AND MA Y PRESENT AN ENERGY HAZARD. THE SAFETY COVER MUST BE FITTED WHEN INST ALLATION HAS BEEN COMPLETED TO MINIMIZE RISK.
11.3 Alarm Connections. Form C relay contact output connections are made to the spring clamp
terminal blocks. See Section 9.5. The chassis ground connection is made to the no. 8-32 stud. See Section 9.6. This safety ground connection should be made before operating the panel.
Manual No. DPB-DPG-4
Page 14
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY
DPB1U & DPG1U SERIES
OPERATING MANUAL
11.4 Checking Connections. Carefully check the polarity of input connections to the distribution
panel and output connections to the load before operating the panel. Reverse connections will not harm the distribution panel as it is POLARITY NEUTRAL. However it may cause serious harm to the load. Check to make sure that the chassis safety ground connection is made. Make sure that all connections are clean and secure to minimize contact resistance.
11.5 Rear Safety Cover. Once all of the above have been completed, t the clear plastic safety
cover to the back of the unit using the supplied mounting studs and screws. Instruction for
tting the mounting studs the panel are included in the accessory kit.
Manual No. DPB-DPG-4
Page 15
dpb_dpg-man-rev4-0317.indd
POWERING TECHNOLOGY

12.0 SETUP AND TESTING

12.1 It is not necessary to have the distribution panel mounted in a rack for initial testing. This
can be done on a bench. It is also not necessary to have loads connected to the panel for this testing.
12.2 With the input power source o, connect the input wires to the A side of the distribution
panel. Connect ground to the chassis ground terminal. Insert all fuses into fuse holders or set all circuit breakers to on.
12.3 Turn on the input power source. The A side LED should be green. If it is red, one of the
fuses is blown or a circuit breaker is tripped. If the LED is o, there is no input power to
the unit. Check the output voltage at each set of output terminals with a digital voltmeter.
12.4 With the A side LED green, use an ohmmeter to check the Form C relay contact outputs.
On J4 measure the resistance between pins 1 and 2. This should read “open”. Measure the
resistance between pins 2 and 3. This should read “short”.
DPB1U & DPG1U SERIES
OPERATING MANUAL
12.5 On the A side insert a blown fuse into fuse no. 1 position or trip circuit breaker no. 1. The
A side LED should turn red. On the upper row (side A) of wire wrap terminals, measure the resistance between pins 1 and 2 and between pins 4 and 5. Both should read “open”.
Measure the resistance between pins 2 and 3 and between pins 5 and 6. Both should read
“short”. Replace the blown fuse with a good one or reset the circuit breaker.
12.6 On the A side check each succeeding fuse by replacing it with a blown fuse, or breaker by
tripping it, and verify that the LED turns red. It is not necessary to recheck the Form C
relay contacts.
12.7 Repeat the same tests of Sections 12.2 through 12.6 on the B side of the distribution panel.
Refer to table 5.
12.8 The distribution panel may now be connected to its intended application.
12.9 If the distribution panel did not operate properly in the above tests, go back and double
check the connections and the polarity of the input source to make sure it is correct.
Please note that there are no user serviceable parts inside and that opening the unit will void
the warranty.
If you are unable to resolve any problem call your nearest UNIPOWER sales oce for
support:
US +1 954 346 2442 UK +44 (0)1903 768200
This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for
consequences from printing errors or inaccuracies. Specications are subject to change without notice.
Manual No. DPB-DPG-4
Page 16