Unipower ARE-M02406, ARE-M02425, ARE-M02450, ARE-M02412, ARE-M024100 Product Manual

UNIPOWER, LLC
PM990.1070.24, Issue 12
Product Manual
for
Micro ARE–M Series
24V Float Chargers
Single-Phase Input
3900 Coral Ridge Drive Coral Springs, FL 33065 Phone: +1-954-346-2442 Toll Free: 1-800-440-3504 Web site – http://www.unipowerco.com
Micro ARE-M S eries 24V Chargers, Single P hase Front Matter
i
RECEIVING INSTRUCTIONS
and
GENERAL EQUIPMENT INFORMATION
IMPORTANT SAFETY INSTRUCTIONS
1. SAVE THESE INSTRUCTIONS- This manual contains important safety and operating instructions for the Micro ARE-M Series units.
2. Before using the Micro ARE-M Series unit, read all instructions and cautionary markings on the unit, battery, and products using battery.
3. CAUTION- When used with batteries, use only lead-acid or nickel­cadmium type rechargeable batteries. Other types of batteries may burst causing personal injury and damage.
ATTENTION: Lorsque utilisé avec des accumulateurs, utilisez UNIQUEMENT des accumulateurs acides plomb ou nickel– cadmium RECHARGABLE. AUTRES TYPES DE BATTERIE peuvent causer, éclatement ET BLESSURES personnelles.
Please Note: For your protection, this product manual should be read and thoroughly understood before unpacking, installing, using, or servicing the described equipment.
UNIPOWER, LLC presents all equipment to the delivering carrier securely packed and ready for transport. Upon acceptance of the equipment from us, the delivering carrier assumes responsibility for its safe delivery to you. Once you receive the equipment, it is your responsibility to document any damage to the equipment that was sustained during transport to you and to file your claim with the carrier promptly and accurately.
PACKAGE INSPECTION
Before unpacking the shipment, examine the shipping container for any visible damage: punctures, dents, and any other signs of possible internal damage.
Describe any damage or shortage on the receiving documents and have the carrier’s representative sign his/her full name.
If the receiving freight bill notes that a Tip-N-Tell is attached to your freight, locate the indicator and note the color of the arrow. If the Tip-N-Tell arrow has turned even partially blue, this means the freight has been tipped in transport. Make sure the carrier notes this on your receipt before you sign for the freight.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Front Matter
ii
CAUTION
ATTENTION
EQUIPMENT INSPECTION
Promptly upon receipt of shipment, open the container and inspect the contents for damage; see the unpacking section that follows. If it is necessary to move or otherwise handle the shipment, refer to the Handling section for instructions and warnings.
Unpack the shipment carefully to avoid scratching or otherwise marring the exterior finish. Be careful not to discard any included equipment, parts, or manuals. If damage is detected, call the delivering carrier to determine appropriate action. The carrier may require an inspection.
IMPORTANT: If damage is detected, save all shipping material for the carrier’s representative!
If damage is detected, also notify UNIPOWER, LLC; contact information is in Section 1.5 Product Support UNIPOWER, LLC will determine if the equipment should be returned for repair. If it is determined that the equipment should be returned to UNIPOWER, LLC, ask the delivering carrier to send the packages back to UNIPOWER, LLC at the delivering carrier's expense. Be sure that the equipment is properly packaged for shipment.
If repair is necessary, UNIPOWER, LLC will invoice you for the repair so that you may submit the bill to the delivering carrier with your claim form.
It is your responsibility to file a claim with the delivering carrier. Failure to properly file a claim for shipping damages may void warranty service for any physical damages later reported for repair.
UNPACKING
A charger is shipped attached to a wood skid. This facilitates handling with a lift truck by inserting the forks under the bottom of the skid. A smaller unit is covered by a carton and banded to a skid. A larger unit is bolted to a skid and covered by a shipping carton that is banded to the skid.
Export packaging consists of a crate, a moisture-resistant cover for the charger, and a drying agent. The charger is bolted to the crate.
To unpack:
Do not stand in front of steel bands since they may whip out when cut.
Ne pas se tenir devant les bandes d'acier, lorsque coupées.
Cut the bands and remove carton from the skid.
1. Either remove the unit from the carton or unbolt the unit from the skid.
2. Check the shipping carton, before discarding, for the packing slip and other material, which may
be contained in it.
3. Carefully inspect the charger for shipping damage (i.e. loosened connections or mountings,
dislodged circuit boards). If damage is detected, notify UNIPOWER, LLC; contact information is provided in Section 1.5 Product Support.
STORAGE
If the charger is not to be used immediately, store it (fully packed, if possible) in a clean, dry location protected from physical damage, condensation, and overhead drip.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Front Matter
iii
WARNING
AVERTISSEMENT
MODEL NO. ARE-M02406 SER.NO. APS0719978
AC VOLTS 120/208/240 PH 1 HZ 60 DC VOLTS 26.4
SPEC. 102.1041.00A °T C 50
AC AMPS 2/1.2/1 CELLS 12
DC AMPS 6
TECHNICAL SUPPORT CALL FIELD SERVICE
EMERGENCY
HANDLING
Refer to the product nameplate for the model information and then see the Specifications section for charger dimensions and weight. Use sufficient personnel and power equipment to ensure safe handling.
Crush hazard
The charger can weigh up to 216 lbs. (98 kg). Keep hands and feet from beneath the charger. Use a forklift or other equipment to move or transport the charger.
Use care in handling and unpacking the charger. Refer to the previous sections as needed.
NAMEPLATE
A UNIPOWER, LLC product is identified by a nameplate that includes model number, part number, and serial number information, as appropriate. Please include this information in all correspondence with UNIPOWER, LLC A sample nameplate is shown below.
Risque d'écrasement
Le chargeur peut peser jusqu'à 216 lb. (98 kg). Gardez les mains et les pieds libres du dessous du chargeur. Utilisez un chariot élévateur ou autres équipements pour déplacer ou transporter le chargeur.
INITIAL SETTINGS
All equipment is shipped from the factory fully inspected and adjusted. Read the technical reference or product manual before installing or making any adjustments.
SPARE PARTS
See Table 6-2 Parts Lists to select the spare and replacement parts you want immediately available to minimize downtime should a failure occur.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Front Matter
iv
ISSUE
PAGE(S)
DESCRIPTION
ISSUED BY /DATE
Updated entire manual with new UNIPOWER logo, addresses, & contact numbers. See PCO# 44409
PRODUCT MANUAL ISSUE HISTORY
12 All
WD/ 6/7/17
PRODUCT MANUAL SUMMARY
This product manual provides installation, operation, maintenance, and troubleshooting procedures for the UNIPOWER, LLC Micro ARE-M Series 24V Chargers.
Thank you for purchasing a Micro ARE-M Series 24V Charger. We at UNIPOWER, LLC are proud of the quality of our products and welcome any suggestions to further improve our design to fit your needs.
PROPRIETARY AND CONFIDENTIAL
The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of the manual or any portion of the manual without the written permission of UNIPOWER, LLC is prohibited.
© Copyright UNIPOWER, LLC 2015
DISCLAIMER
Data, descriptions, and specifications presented herein are subject to revision by UNIPOWER, LLC without notice. While such information is believed to be accurate as indicated herein, UNIPOWER, LLC makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, UNIPOWER, LLC hereby disclaims and excludes all warranties, express, implied, or statutory, including any warranty of merchantability, any warranty of fitness for a particular purpose, and any implied warranties otherwise arising from course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific application.
Throughout the remainder of this manual, “UNIPOWER” will mean “UNIPOWER, LLC.”
PERSONNEL REQUIREMENTS
Installation, setup, operation, and servicing of this equipment should be performed by qualified persons thoroughly familiar with this Product Manual and Applicable Local and National Codes. A copy of this manual is included with the equipment shipment.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Contents
v
Table of Contents
1.0 INTRODUCTION ............................................................................................................................................. 1-1
PRODUCT DESCRIPTION ............................................................................................................................ 1-1 1.1
MODEL DESIGNATION ............................................................................................................................... 1-2 1.2
Options ................................................................................................................................................. 1-2
1.2.1
SPECIFICATIONS ......................................................................................................................................... 1-4 1.3
1.3.1 Mechanical ............................................................................................................................................... 1-4
1.3.2 Electrical .................................................................................................................................................. 1-5
1.3.3 Front Panel Displays and Controls ......................................................................................................... 1-8
1.3.4 Environmental .......................................................................................................................................... 1-9
ABBREVIATIONS AND ACRONYMS ........................................................................................................ 1-9 1.4
PRODUCT SUPPORT .................................................................................................................................. 1-10 1.5
2.0 INSTALLATION ............................................................................................................................................... 2-1
INSTALLATION SUMMARY ....................................................................................................................... 2-1 2.1
REFERENCE MATERIAL ............................................................................................................................. 2-2 2.2
Tools and Accessories .......................................................................................................................... 2-2
2.2.1
2.2.2 Selecting and Sizing DC Power Cables ............................................................................................... 2-3
2.2.3 Torque Specifications .......................................................................................................................... 2-4
2.3 MECHANICAL INSTALLATION ......................................................................................................... 2-5
2.4 ELECTRICAL INSTALLATION ............................................................................................................ 2-8
2.4.1 Grounding the Cabinet ........................................................................................................................ 2-9
2.4.2 Installing a User’s AC Electrical Service Panel .................................................................................. 2-9
2.4.3 Connecting AC Input Cables ............................................................................................................. 2-10
2.4.4 Connecting the Battery String ............................................................................................................ 2-10
2.4.5 Connecting an External DC Load ...................................................................................................... 2-11
2.4.6 Connecting Alarm Annunciation ........................................................................................................ 2-12
2.4.7 Connecting the Battery Temperature Probe (Option) ....................................................................... 2-14
3.0 COMMIS SIONING ........................................................................................................................................... 3-1
PREPARATORY STEPS ................................................................................................................................ 3-1 3.1
COMMISSIONING PROCEDURE ................................................................................................................ 3-2 3.2
4.0 SETUP AND OPERATION .............................................................................................................................. 4-1
TURNING ON A COMMISSIONED CHARGER .......................................................................................... 4-1 4.1
TURNING OFF A COMMISSIONED CHARGER ........................................................................................ 4-1 4.2
SETTING UP AND OPERATING A CHARGER .......................................................................................... 4-1 4.3
4.3.1 View Active Alarms .................................................................................................................................. 4-6
4.3.2 View Charger Status ................................................................................................................................ 4-6
4.3.3 Change Operating Mode (Manual Equalization) .................................................................................... 4-7
4.3.4 Change Charger Setup (Configuration) ................................................................................................... 4-8
5.0 CIRCUIT DES CRIPTION ............................................................................................................................... 5-1
6.0 MAINTENANCE ............................................................................................................................................... 6-1
VOLTAGE CHANGES................................................................................................................................... 6-1 6.1
PREVENTIVE ................................................................................................................................................ 6-1 6.2
TROUBLESHOOTING .................................................................................................................................. 6-2 6.3
6.3.1 Service Access .......................................................................................................................................... 6-2
6.3.2 Circuit Board Handling ........................................................................................................................... 6-2
6.3.3 ARE-M Display Codes ............................................................................................................................. 6-3
CHECKING COMPONENTS ......................................................................................................................... 6-6 6.4
12" CABINET ASSEMBLY AND SCHEMATICS ........................................................................................ 6-8 6.5
24" CABINET ASSEMBLY AND SCHEMATICS ...................................................................................... 6-12 6.6
PARTS LIST ................................................................................................................................................. 6-17 6.7
INTERFACE BOARD .................................................................................................................................. 6-19 6.8
Board Interchangeability ................................................................................................................... 6-19
6.8.1
6.8.2 Troubleshooting ................................................................................................................................. 6-20
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Contents
vi
6.8.3 Replacing the Interface Board ........................................................................................................... 6-20
6.9 CONTROL AND DISPLAY BOARD ................................................................................................... 6-22
6.9.1 Replacing the Board .......................................................................................................................... 6-22
6.10 KEYPAD ............................................................................................................................................... 6-23
7.0 OPTIONS AND ACCESSORIES..................................................................................................................... 7-1
LIGHTNING ARRESTER ..................................................................................................................................... 7-1 7.1
BLOCKING DIODE ............................................................................................................................................. 7-2 7.2
OUTPUT MOVS ................................................................................................................................................ 7-3 7.3
DRIP SHIELD .................................................................................................................................................... 7-3 7.4
TEMPERATURE SENSOR .................................................................................................................................... 7-3 7.5
GROUND DETECTION SWITCH .......................................................................................................................... 7-3 7.6
DNP3 COMMUNICATIONS ................................................................................................................................ 7-3 7.7
HIGH INTERRUPT AC BREAKERS ...................................................................................................................... 7-3 7.8
List of Tables
TABLE 1-1 MODEL DESIGNATION ..................................................................................................................... 1-3
TABLE 1-2 SETTABLE PARAMETERS, STANDARD MODELS ...................................................................... 1-8
TABLE 2-1 COPPER WIRE SIZING ...................................................................................................................... 2-4
TABLE 2-2 TORQUE SPECIFICATIONS, STEEL FASTENERS ........................................................................ 2-4
TABLE 4-1 FACTORY DEFAULT SETUP PARAMETER VALUES.................................................................. 4-8
TABLE 4-2 TYPICAL FLOAT/EQUALIZE VOLTAGES ..................................................................................... 4-9
TABLE 6-1 TROUBLESHOOTING CHART ......................................................................................................... 6-4
TABLE 6-2 12" CABINET REPLACEMENT PARTS LIST; 24 VDC MODELS ............................................... 6-17
TABLE 6-3 INTERFACE BOARD SWITCH SETTINGS ................................................................................... 6-19
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Contents
vii
List of Figures
FIGURE 2-1 12" CABINET DIMENSIONS ........................................................................................................... 2-6
FIGURE 2-2 24" CABINET DIMENSIONS ........................................................................................................... 2-7
FIGURE 2-3 ELECTRICAL INSTALLATION, BLOCK DIAGRAM ................................................................... 2-8
FIGURE 2-4 TYPICAL ELECTRICAL ENTRANCE AND BREAKER LOCATIONS ........................................ 2-8
FIGURE 2-5 ELECTRICAL INSTALLATION TERMINALS, 12" AND 24" CABINET MODELS ................... 2-9
FIGURE 2-6 INTERFACE BOARD ...................................................................................................................... 2-13
FIGURE 2-7 ALARM CONNECTIONS DETAIL, INTERFACE BOARD ......................................................... 2-13
FIGURE 3-1 OPERATOR CONTROLS ................................................................................................................. 3-1
FIGURE 4-1 MAIN MENU ..................................................................................................................................... 4-3
FIGURE 4-2 CHARGER STATUS MENU ............................................................................................................. 4-4
FIGURE 4-3 CHARGER OPERATING MODE MENU ......................................................................................... 4-4
FIGURE 4-4 CHARGER SETUP (CONFIGURATION) MENU ........................................................................... 4-5
FIGURE 5-1 BLOCK DIAGRAM, TYPICAL MICRO ARE-M FLOAT CHARGER ........................................... 5-1
FIGURE 6-1 CAPACITOR DISCHARGE BUTTON ......................................................................................................... 6-6
FIGURE 6-2 12" CABINET ASSEMBLY ...................................................................................................................... 6-8
FIGURE 6-3 12" CABINET SCHEMATIC; ARE-M02406, 120/208/240 ...................................................................... 6-9
FIGURE 6-4 12" CABINET SCHEMATIC; ARE-M02412, 120/208/240 ..................................................................... 6-10
FIGURE 6-5 12" CABINET SCHEMATIC, ARE-M02425, 120/208/240 .................................................................... 6-11
FIGURE 6-6 24" CABINET ASSEMBLY .................................................................................................................... 6-12
FIGURE 6-7 24" CABINET SCHEMATIC; ARE-M02450, 120/208/240 .................................................................... 6-13
FIGURE 6-8 24" CABINET SCHEMATIC; ARE-M02450, 480 .................................................................................. 6-14
FIGURE 6-9 24" CABINET SCHEMATIC; ARE-M024100, 120/208/240 .................................................................. 6-15
FIGURE 6-10 24" CABINET SCHEMATIC; ARE-M024100, 480 .............................................................................. 6-16
FIGURE 6-11 COMPONENT LOCATIONS, INTERFACE BOARD.................................................................. 6-21
FIGURE 6-12 CONTROL AND DISPLAY BOARD ............................................................................................ 6-22
FIGURE 7-1 LIGHTNING ARRESTER; 120, 208, 240 AND 480 VAC CONNECTIONS .................................. 7-1
FIGURE 7-2 BLOCKING DIODE ADD ALTERNATIVE .................................................................................... 7-2
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-1

1.0 INTRODUCTION

The purpose of this manual is to provide the reader with the procedures for installing, configuring, operating, and servicing UNIPOWER Micro ARE-M Float Chargers.
Chapter 1 Introduction provides a description of the Micro ARE-M series chargers, the model designation list, and detailed specifications. This chapter also has product support telephone and FAX numbers and the company’s Internet URL where the latest issue of this manual can be found.
Chapter 2 Installation describes mechanical and electrical installation of the charger. Each aspect of the installation is discussed and supporting illustrations are provided.
Chapter 3 Commissioning presents a suggested procedure that can be integrated into or modified by your company’s commissioning procedures.
Chapter 4 Setup and Operation describes charger displays and use of the 4-button keypad. Setup menus are provided to ease navigation through the provided displays. Default setup values are listed.
Chapter 5 Circuit Description includes a block diagram level description of the charger circuitry. Read this chapter before installing, configuring, operating, or servicing the charge.
Chapter 6 Maintenance provides preventive maintenance and troubleshooting information. A troubleshooting chart is included as are component location drawings and schem atics for all charg er models. These drawings are followed by a section containing replacement parts lists. Troubleshooting information for the Interface Board and the Control and Display Board follows the parts lists.
Chapter 7 Options and Accessories furnishes details concerning the accessories available at the time this manual was published.

PRODUCT DESCRIPTION 1.1

The Micro ARE-M series of single-phase, controlled ferroresonant float chargers is intended for utility, communications, and other applications where a source of stable, electrically clean, reliable DC power is needed. Available models provide an output voltage of 24 VDC and an output current from 6-100 amperes, depending upon model. Refer the Model Designation for a list of standard models and options.
Installation is quick and easy. The design accommodates floor, wall, or rack mounting with standard and optional brackets. A mounting method is usually specified on the equipment order so the proper brackets can be supplied.
The charger is configured and operated from the front of the unit. The control section includes a 2-line digital display, 4-button keypad, green AC on LED and a red alarm LED, an AC input circuit breaker, and a DC output circuit breaker. An optional control board offers front panel LED indicators, showing the status of the High Voltage Alarm, Low Voltage Alarm, No Charge Alarm and AC Fail Alarm on the telecom models. For the utility models two additional LEDs show the state of the Positive and Negative ground fault alarms.
Access to internal components for servicing by qualified personnel is through the door comprising the front of the unit. The door is hinged on the left and secured on the right by two fasteners.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-2

MODEL DESIGNATION 1.2

The nameplate on the charger contains an alphanumeric model number. The model number describes the features built into a particular charger. Table 1-1 provides the product characteristic defined by each character in the model number.

1.2.1 Options

Temperature Compensation ............... Slopes adjusted from –0.1mV/cell/C to –10.0mv/cell/C
Lightning Arrester .............................. AC input; prevents equipment damage due to a nearby lightning
strike
Fungicide Treatment .......................... Applied to inside of charger
Drip Shield ......................................... Prevents overhead drops from entering unit
SIS Control Wiring ............................ Excludes ribbon cable and power cables
High Interrupt DC Breakers ............... 10K AIC minimum
Engraved Nameplates ........................ Contact UNIPOWER Applications Engineering
Blocking Diode .................................. Prevents charger faults from shortening the battery plant
High Interrupt AC Breakers ............... 10K AIC minimum
MOVs ................................................. On DC output, prevents equipment damage due to excessive
voltage transients
DNP3 Communications ..................... Allows charger to be controlled and monitored from a remote
location using the DNP3 protocol. See manuals PM990.1074.00
(Installation guide) and PM990.1072.00 (Device Profile) on the
ARE-M webpage at www.unipowerco.com for more information.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-3
DC VOLTAGE & CURRENT
ARE-M02406A (AC Input Voltage: 120V/208V/240V)
ARE-M02412A (AC Input Voltage: 120V/208V/240V)
ARE-M02425A (AC Input Voltage: 120V/208V/240V)
ARE-M02450A (AC Input Voltage: 120V/208V/240V/480V)
ARE-M024100A (AC Input Voltage: 120V/208V/240V/480V)
AC Input Voltage / Breaker
A 120V - 60 Hz Standard Capacity AC Breaker
B 208V - 60 Hz Standard Capacity AC Breaker
C 240V - 60 Hz Standard Capacity AC Breaker
D 480V - 60 Hz Standard Capacity AC Breaker (50 A & 100 A only)
1 120V - 60 Hz High Capacity AC Breaker
2 208V - 60 Hz High Capacity AC Breaker
3 240V - 60 Hz High Capacity AC Breaker
4 480V - 60 Hz High Capacity AC Breaker (50 A & 100 A only)
AC Protection
1 Not Required (Standard)
2 480/240 VAC Input Lightning Arrestor
3 240/208/120 VAC Input Lightning Arrestor
DC Circuit Breaker
1 Standard Capacity AC Breaker/ Standard Capacity DC Breaker
2 Standard Capacity AC Breaker/ High Capacity DC Breaker
3 Standard 480V AC Breaker/ Standard Capacity DC Breaker
4 Standard 480V AC Breaker/ High Capacity DC Breaker
5 High Capacity AC Breaker/ Standard Capacity DC Breaker
6 High Capacity AC Breaker/ High Capacity DC Breaker
7 High 480V AC Breaker/ Standard Capacity DC Breaker
8 High 480V AC Breaker/ High Capacity DC Breaker
A Telecom Standard Capacity AC Breaker/ Standard Capacity DC Breaker
B Telecom Standard 480V AC Breaker/ Standard Capacity DC Breaker
C Telecom High Capacity AC Breaker/ Standard Capacity DC Breaker
D Telecom High 480V AC Breaker/ Standard Capacity DC Breaker
DC Protection
1 None (Standard)
2 MOVs
Blocking Diode
1 None (Standard)
2 Yes (Negative Leg)
Temperature Compensation
1 None (Standard)
2 Battery Temperature Compensation (Temperature Sensor with 25' lead)
Control Wiring
1 Floating Ground (Standard) - PVC
2 Floating Ground Switchboard - SIS
A Telecom - Positive Ground - PVC
B Telecom - Negitive Ground - PVC
Individual Alarm Relays
1 Utility - AC Fail, High Voltage, Rectifier Fail
2 Utility - AC Fail, High Voltage, Rectifier Fail, Hi VDC, Low VDC,
NO Charge, GND+, GND-, Summary
3 Utility - AC Fail, High Voltage, Rectifier Fail, w/Ground Enable Switch
4 Utility - AC Fail, High Voltage, Rectifier Fail, Hi VDC, Low VDC,
NO Charge, GND+, GND-, Summary, w/Ground Enable Switch
A Telecom - AC Fail, High Voltage, Rectifier Fail
B Telecom - AC Fail, High Voltage, Rectifier Fail, Hi VDC, Low VDC,
NO Charge, Summary
Control Board
1 Utility (Standard)
(Discontinued)
2 Uti lity Alarm Lights - AC, Summary Alarm, HVA, LNA, NCA, ACF, GND+, GND-
A Telecom (Standard)
(Discontinued)
B Telecom Alarm Lights - AC, Summary Alarm, HVA, LNA, NCA, ACF
Mounting
1 Wall 19"
3 Relay 19"
4 Relay 23"
5 Floor Mount
6 Floor Mount with Drip Shield
Packaging
1 Domestic (Standard)
2 Export
3
None (For relay rack installation only)
DNP3 Communications Port
1 No Port (Standard)
2 DNP3 Ethernet 4 foot cable
3 DNP3 Ethernet 2 foot cable
4 DNP3 Ethernet 25 foot cable
5 DNP3 Ethernet 50 foot cable
Special Instructions
1 No
2 Yes
ARE-M 2406 A 2 2 1 1 2 1 1 3 1 1 1 1
Base Model
S Build Number
TABLE 1-1 MODEL DESIGNATION
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-4
Cabinet
Size
Depth
Maximum*
Mounting
Depth**
Shipping
Weight*
ARE-M02425
102 (46)

SPECIFICATIONS 1.3

This section provides the mechanical, electrical, and environmental specifications. The charger nameplate is located on the front panel.

1.3.1 Mechanical

Cabinet .................................................... NEMA1; steel with baked powder coat finish
Cable Entrances ...................................... Three; see the dimension drawings in Chapter 2 Installation
Cabinet Dimension and Weight .............. See the following table and dimension drawings in Chapter 2
Installation.
Model
ARE-M02406 ARE-M02412
ARE-M02450 ARE-M24100
12"
24"
Height* Width*
12.25 (311)
24.5
(622)
17
(432)
17
(432)
15
(381)
15
(381)
6
(152)
6
(152)
65 (30)
75(33)
162 (74) 216 (98)
*Cabinet dimension in inches (mm). Does not include mounting brackets or drip s hie ld . W e ig ht in lbs. (kg). ** Dimension from cabinet front to installed rack mounting angle brackets.
Mounting Locations ........................... Wall, relay rack, or floor
Select a location for the charger. The chargers are cooled by natural convection and require at least 3" (76mm) of space below the charger and 3" above the charger.
Mounting Brackets
Supplied ........................................ Wall mount and standard relay rack mount
Optional ........................................ Larger relay rack mount or floor mount
Internal Combustible Materials ......... 94V-1 or better
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-5

1.3.2 Electrical

Model Specific and Related Specifications
Refer to the equipment nameplate for the model number of the Micro ARE-M at hand.
ARE-M02406
DC Output Voltage and Current ............. 26.4V@ 6A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 14 AWG (2.1 mm
Terminal Block Capacity ........................ 24-12 AWG (.21-5.3 mm
2
)
2
)
DC Circuit Breaker ................................. 10A
AC Input Voltage and Current ................ 120V @ 2A, Single Phase
208V @ 1.1A, Single Phase 240V @ 1A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 200 BTU/Hour
ARE-M02412
DC Output Voltage and Current ............. 26.4V @ 12A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 12 AWG (3.3 mm
Terminal Block Capacity ........................ 24-12 AWG (.21-3.3 mm
2
)
2
)
DC Circuit Breaker ................................. 20A
AC Input Voltage and Current ................ 120V @ 4A, Single Phase
208V @ 2.3A, Single Phase 240V @ 2A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 440 BTU/Hour
ARE-M02425
DC Output Voltage and Current ............. 26.4V @ 25A
Ripple
On Battery ......................................... NA
O
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 8 AWG (8.4 mm
Terminal Block Capacity ........................ 14 - 10 AWG (2.1 to 5.3 mm
ff Battery ......................................... 30 mV rms
2
)
2
)
DC Circuit Breaker ................................. 35A
AC Input Voltage and Current ................ 120V @ 8.3A, Single Phase
208V @ 4.7A, Single Phase 240V @ 4.1A, Single Phase
AC Frequency ......................................... 57-63 Hz
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-6
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 660 BTU/Hour
ARE-M02450
DC Output Voltage and Current ............. 26.4V @ 50A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 4 AWG (21.1 mm
Terminal Block Capacity ........................ 14-2/0 AWG (2.1 to 67.4 mm
2
)
2
)
DC Circuit Breaker ................................. 70A
AC Inp ut Voltage and Current ................ 120V @ 16A, Single Phase
208V @ 9A, Single Phase 240V @ 8A, Single Phase 480V @ 4A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
5,000A @ 480V
AC Breaker Interrupt High Capacity ...... 10,000A except 18,000 @ 480Vac
Heat Dissipation...................................... 1150 BTU/Hour
ARE-M024100
DC Output Voltage and Current ............. 26.4V @ 100A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 1 AWG (42.4 mm
Terminal Block Capacity ........................ 14-2/0 AWG (2.1 to 67.4 mm
2
)
2
)
DC Circuit Breaker ................................. 125A
AC Input Voltage and Current ................ 120V @ 33A, Single Phase
208V @ 19A, Single Phase 240V @ 16A, Single Phase 480V @ 8A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
5,000A @ 480V
AC Breaker Interrupt High Capacity ...... 10,000A except 18,000 @ 480Vac
eat Dissipation...................................... 2390 BTU/Hour
H
*Battery: A fully charged battery that has an ampere-hour capacity numerically equal to four times the rated output current of the charger.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-7
Nominal Voltage
Minimum Voltage
Maximum Voltage
120 Vac
106 Vac
132 Vac
208 Vac
184 Vac
228 Vac
240 Vac
212 Vac
264 Vac
480 Vac
424 Vac
528 Vac
General
AC Voltage Range ............................. The AC supply voltage specified in Model Specific and Related
Specifications must be within the following ranges:
Power Factor (Resistive Load) .......... >0.92 at full load
Efficiency (Resistive Load) ............... >87%
DC Regulation Static
Float ......................................... ±0.5% with a fixed load and simultaneous variations1
Equalize ................................... ±1.0% with a fixed load and simultaneous variations1
Dynamic ....................................... ±6% for a step load change of 10 to 90% or 90 to 10% of rated
current; Charger will recover to regulation range within 300 milliseconds; transient behavior will disappear within 500
milliseconds. Current Limiting
Factory Setting ........................... 110% of full rated load
Field Settable ............................. 80-110% of full rated load
Continuous Operation ................ 110% of full rated load maximum
Surge Protection................................. Optional MOVs (metal-oxide varistors) on output terminals
Optional Lightning arrestor on input terminals
Current Walk-In (Soft Start) .............. Less than 15 seconds for output current increase from 0-100%
Alarms
Standard Interface Board ................... 3 alarm relay outputs: AC Fail, Rectifier Fail, and HVSD
Multiple Alarm Interface Board ........ 9 alarm relay outputs: Summary, GND+, GND-, LVA, HVA,
NCA, AC Fail, Rectifier Fail, and HVSD Alarm Indicators
Front Panel ................................. Common red alarm LED and 2-Line LCD display
Optional Indicators..................... Optional front panel indicators, consisting of a red High Voltage
LED, red Low Voltage LED, red No Charger LED, yellow AC
Fail LED on the telecom models, and two additional green
Positive and Negative Ground LEDs on the utility models.
Alarm Relay Contacts ................ Form C, 2A @ 30 Vdc; 0.6A @ 110 Vdc; 0.6A @ 125 Vac
Customer Connections
Connector ................................... One plug-in 3-position terminal block per alarm, compression-
style wire clamp
Wire Size .................................... 12-28 AWG (2.5-0.08 mm
2
)
1
Load, input voltage, frequency, and temperature varied within range for that model. The Float and Equalize voltage regulation
excludes any voltage drop from the blocking diode, if present. PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-8
Model
Float Range
Equalize Range
HVSD Range
ARE-M24 Series
22.2-28.2V
Float-29.4V
24-30.4V

1.3.3 Front Panel Displays and Controls

Display ............................................... LCD, 2 lines x 20 characters, with green LED backlight
Display Accuracy ............................... 1% (voltage, current, or time reading)
Control Modes ................................... Manual float/equalize, use r selectable from keypad
LED Indication Standard ................... Alarm - red; AC power - green
LED Indication Optional ................... HVA, LVA, NCA-red, ACF-yellow, +GND,-GND-green
High Voltage Shutdown
Adjustable ..................................... 2.00-2.53 Vpc (Volts per cell), LED indicator; see table below;
1-30 Sec delay
Fixed Redundant ........................... 2.66 +/-0.08 Vpc
Float/Equalize .................................... State indicated; Equalize remaining time shown
Load Share Active ............................. Chargers operating in parallel with +/-5% of rated output over
10% to 100% of current threshold
Ground Detection
Disconnect Switch (optional) ....... Breaks the connection to the chassis (earth) for troubleshooting
grounds on the dc system or to eliminate interaction with an
external ground detection system
Relay/Lamp Test ................................ Provided in setup routine (password protection available)
Control Adjustments (password protection available)
Float Voltage ................................ 1.85-2.35 Vpc (Volts per cell); see table below
Equalize Voltage .......................... 2.0 -2.45 Vpc; see table below
Manual Equalize ........................... On, Off, Equalize Duration (1-255 hours)
Auto-Equalize
After AC Fail ........................... On, Off, Equalize After (1-7200 minutes), Equalize Duration (1-
255 hours)
Periodic ................................... On, Off, Equalize Duration (1-255 hours)
Current Limit ................................ 80-110% of charger rating
Periodic Equalize .......................... Off, 168-8760 hours
Temp Comp…………………….. 0.1-10 mV/cell/°C
TABLE 1-2 SETTABLE PARAMETERS, STANDARD MODELS
Alarm Adjustments (password protection available)
Low Voltage (LVA) ........................... 1.50-2.20 Vpc; alarm delay 1-300 seconds
Very Low Voltage (VLVA) ............... 1.50-2.20 Vpc; alarm delay 1-300 seconds
High Voltage (HVA) .......................... 2.20-2.50 Vpc; alarm delay 1-300 seconds
No Current .......................................... Up to 30% of rated current; alarm delay 1-300 seconds
Positive Ground Fault ......................... 500-20,000 Ohms; 1-300 seconds delay
Negative Ground Fault ....................... 500-20,000 Ohms; 1-300 seconds delay
Charger Fail ........................................ 1-300 seconds delay
AC Power Fail .................................... 1-300 seconds delay; relay delay fixed at 0.5 seconds
High Battery Temperature (HBTA) ... 0-200 °C; 1-300 seconds delay
Summary............................................. 0-300 seconds delay
Password Protection ................................. Yes, control and alarm settings; 00001-65500
NOTE: All "per cell" voltages are based upon the unit's nominal number of lead-acid cells.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-9
Abbreviation, Acronym Or Symbol
Meaning
ANSI
American National Standards Institute
AWG
American wire gauge
BATT
Battery
CL
current limit
CM
circular mils
EMI
electromagnetic interference
EQ
equalization
ESD
electrostatic discharge
FL
float
HVA
normally energized high voltage alarm
HVSD
high voltage shutdown
NCA (LCA)
No (low) current alarm
LED
light emitting diode
LSD
least significant digit
LVA
low voltage alarm
LVD
low voltage disconnect
NEC
National Electric Code
NEMA
National Electrical Manufacturers Association
PCB
printed circuit board
RFA
rectifier failure alarm
UL
Underwriters Laboratory
Vpc
Volts/Cell

1.3.4 Environmental

Charger Cooling....................................... Natural Convection
Temperature, Operating ........................... 0°C to +50°C (32°F to +122°F); see Altitude
Temperature, Storage ............................... –40°C to +85°C (–40°F to +185°F)
Storage Duration ...................................... One year at specified storage temperature range
Relative Humidity .................................... 0 to 95% non-condensing
Altitude
Operating ............................................ 3,300 ft. (1000 meters)
Derate ................................................ 2°C (3.6°F) for each 990 ft. (300m) over 3300 ft. (1000m)
above sea level
Audible Noise .......................................... <65 dBA measured 5 feet (1.7m) from cabinet vertical
surface

ABBREVIATIONS AND ACRONYMS 1.4

Listed here are many of the abbreviations and acronyms that may appear in this manual.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Introduction
1-10

PRODUCT SUPPORT 1.5

Product support can be obtained using the following addresses and telephone numbers.
UNIPOWER, LLC 3900 Coral Ridge Drive Coral Springs, FL 33065 Phone: +1-954-346-2442 Toll Free: 1-800-440-3504 Web site – http://www.unipowerco.com
When contacting UNIPOWER, please be prepared to provide:
1. The charger model number, spec number, S build number, and serial number - see the equipment
nameplate on the front panel
2. Your company’s name and address
3. Your name and title
4. The reason for the contact
5. If there is a problem with charger operation:
Is the problem intermittent or continuous?
What revision is the firmware?
What actions were being performed prior to the appearance of the problem?
What actions have been taken since the problem occurred?
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-1
WARNING
AVERTISSEMENT

2.0 INSTALLATION

This chapter describes insta ll ing Micro ARE Series 24V Chargers. To contact a UNIPOWER field service technician for assistance, refer to Section 1.5 Product Support.
The charger is fully assembled and tested at the factory. Refer to the Front Matter and Section 2.3 Unpacking for receiving and unpacking instructions and for instructions on moving the equipment to the installation site.
These chargers can be mounted to a wall, in a relay rack, or on a floor. All are furnished with brackets for standard wall or relay rack mounting. Optional floor mounting brackets and extra-wide brackets for wide relay racks are available. Cabinet dimensions and weights are provided in the Specifications section.
Conduit knockouts are located in the cabinet top for AC input cables, DC output cables and alarm wiring. Cables and wires are supplied by the user.
Electrical shock hazard
Hazardous voltage can cause death or serious injury. Remove power from all wires and terminals before working on equipment.
Risque de choc électrique Les tensions dangereuses peuvent causer la mort
ou des blessures graves. Coupez l'alimentation de tous les fils et les bornes avant de travailler sur les équipements.
IMPORTANT: The installation must conform to the National Electrical Code and other applicable industry and local codes.

INSTALLATION SUMMARY 2.1

A typical installation sequence is provided below. References to appropriate sections in this manual are included.
1. Review the list of user-supplied tools and accesso ri es in Section 2.2 Refer ence Ma teria l. Th is section
also contains a table and a procedure for determining battery and distribution cable sizes based on current load and length of run. Refer to the National Electrical Code and other applicable codes to determine AC cable size.
2. Select a location for the charger. The chargers are cooled by natural convection and require at least 3"
(76mm) of space below the charger and 3" above the charger. The charger must be mounted over a non-combustible surface. See Section 2.3 Mechanical Installation.
3. Move the charger to the selected location. See Section 2.3.
4. As appropriate, install charger mounting brackets for a wall, relay rack, or floor. Fasten the charger to
5. Install a user-supplied electrical service panel (as needed) for powering the charger. See Section 2.4
6. Install battery cabling. Route cabling through overhead cable racks between the battery string and the
7. Install customer load supply and return cabling. Connect the cabling to the battery string or directly to
the selected mounting surface or rack.
Electrical Installation. Install AC input conduit and wiring between the user’s AC electrical service panel and the charger.
charger DC output terminals.
the charger, if a battery string is not to be connected to the charger. If the customer load is connected to the battery string, install a circuit breaker or fuse in-line wi th the cabling.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-2
8. Connect user-supplied external alarm annunciators.
9. Commission the charger. See Chapter 3.
10. Set LVA, HVA, HVSD, float voltage, equalization, etc. as needed to satisfy installation requirements.
Test and verify charger setup and operation. See Chapter 4 Setup and Operation.

REFERENCE MATERIAL 2.2

This section contains lists, tables, and methods that are referenced in subsequent procedures. Three subsections comprise the Referenc e Mate rial sec tio n.
Tools and Accessor ies – Read the included list for a preview of the user-supplied items that will be
referenced during the installation and servicing procedures.
Selecting and Sizing DC Power Cables – Proper cable sizing is critical to system performance. This
section provides a formula and table that simplify cable selection.
Torque Specifications – T h e torque spec if ic ation tab le in this subs ec tion is re ferenced in procedures
that include hardware.

2.2.1 Tools and Accessories

To install the charger, the following user-supplied items should be available.
Equipment and personnel to safely transport the charger to the installation site
Mounting brackets and related hardware to securely mount the charger
Overhead wire racks for AC power and distribution cabling
Standard insulated installation tools (e.g. socket set, cable cutters, cable insulation strippers)
Torque wrench to ensure co rre ct tightening of hardware; see Table 2-2 for torque specifications
User-supplied AC electrical service panel with a circuit breaker for the AC feed to the charger
Digital Voltmeter with: 4-1/2 digit display, 1/2% accuracy, and 10M ohms input impedance
Cables and lugs; appropriate crimping tools
Conduit, conduit connectors, and conduit bending tools
Anti-Static Service Kit with static dissipative mat and wrist strap for handling electronic circuit
boards (e.g. Control and Display Board, User Interface Board)
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-3
V
LI
CM
=
2.22
000,55
)5.0(
)50)(25)(2.22(
==CM

2.2.2 Selecting and Sizing DC Power Cables

Protective circuits, overall system performance, and safety depend on the proper sizing of DC cables for ampere ranges and acceptable DC voltage drop. Read the electrical installation section before sizing the DC cables.
Perform the following procedure to determine wire size.
1. Calculate the minimum circular mils (CM) required for copper wire using the following formula:
where:
CM = minimum area of circular mils in the cable I = maximum current (in amps) L = one-way cable length (in feet) V = allowable loop voltage drop (in volts)
Example: Assume a maximum output current of 25 amperes, an allowable loop voltage drop of 0.5 volts, and a distance of 50 feet between the charger and the load.
I = 25 amperes L = 50 feet V = 0.5 volts
11. After calculating the minimum circular mils, select the proper copper wire size from Table 2-2;
always choosing the next larger wire size if the area rating falls between values. For the above example, select 2 AWG (35 mm
2
) wire.
12. Determine the minimum wire size for ampacity according to the code authority having jurisdiction in
your location.
13. Select the larger of the sizes calculated for voltage drop or ampacity.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-4
AWG NO.
IN CM
CAPACITY*
75°C (167°F)
INCHES
INCHES
INCHES
IN POUNDS
FEET
AIR ENCLOSED
14
4,110
15
15
0.064
0.19
0.95
26
5,000
12
6,530
20
18
0.081
0.21
1.05
35
3,000
10
10,380
30
25
0.102
0.24
1.20
49
3,000
8
16,510
45
35
0.146
0.31
1.55
84
3,000
6
26,250
70
45
0.184
0.40
2.00
126
2,000
4
41,740
90
60
0.232
0.45
2.25
190
1,500
2
66,370
125
85
0.292
0.51
2.55
278
1,000
1/0
105,500
170
110
0.373
0.63
3.15
443
1,000
2/0
133,100
195
130
0.418
0.68
3.40
540
1,000
4/0
211,600
270
170
0.528
0.78
3.90
814
1,000
Bolt Size
Inch-Pounds
Foot-Pounds
Newton-Meters
4-40
4.5
0.375
0.51
4-48
5.4
0.450
0.61
6-32
9.0
0.750
1.02
6-40
10.8
0.900
1.22
8-32
17.1
1.425
1.93
8-36
18.0
1.500
2.03
10-24
24.3
2.025
2.75
10-32
27.9
2.325
3.15
1/4-20
59.4
4.950
6.71
1/4-28
70.2
5.850
7.93
5/16-18
118.8
9.9
13.42
5/16-24
129.6
10.8
14.64
3/8-16
216.0
18.0
24.40
3/8-24
248.4
20.7
28.07
7/16-14
324.0
27.0
36.61
7/16-20
378.0
31.5
42.71
1/2-13
540.0
45.0
61.01
1/2-20
594.0
49.5
67.11
9/16-12
756.0
63.0
85.42
9/16-18
864.0
72.0
98.62
TABLE 2-1 COPPER WIRE SIZING
CURRENT CARRYING
SIZE
* Data based on NEC Handbook 2005, Table 310-16 and 310-17 adjusted for 50°C (122°F) ambient temperature.
AREA
OPEN
DIA BARE COND
RHW DIA OVER INS
RHW BEND RADIUS
RHW NET WEIGHT PER 1000 FT
RHW MAX SHIP LENGTHS PER REEL IN

2.2.3 Torque Specifications

Proper Charger performance requires that the hardware employed during installation be tightened securely, but not over tightened. Use a torque wrench to ensure that hardware is tightened to the specification provided in the table below.
TABLE 2-2 TORQUE SPECIFICATIONS, STEEL FASTENERS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-5
CAUTION
ATTENTION

2.3 MECHANICAL INSTALLATION

Install the charger in a location that provides:
A dry, well ventilated, vibration-free environment with temperature and humidity limits as stated in
Section 1.3 Specifications
Sufficient access for installation and servicing
Sufficient ceiling height to permit use of overhead cable trays for distribution wiring
A level, flat floor or a wall capable of supporting the weight of the charger and accepting anchoring
bolts
A non-combustible surface beneath the charger
A pest and varmint free area
Charger dimensions are stated in the Section 1.3 Specifications and shown in Figures 2-1 and 2-2. Charger weight is provided in the Specifications section.
The mounting method (floor, rack, or wall) is usually specified on the order so the necessary brackets are installed on the charger at the factory. Charger wall mounting hardware (1/4-20 screws, lock wash ers and nuts), rack mounting hardware (12-24 screw and nuts) or floor mount hardware (3/8 bolts and anchors) is customer supplied since it must be selected on-site to be appropriate for the mounting surface.
Figures 2-1 and 2-2 show charger mounting bracket locations. Charger mounting options are listed below.
A 12" or 24" cabinet can be mounted in a 19" rack using the supplied rack angle brackets; the wide
bracket option is required for a 23" rack
All cabinets can be fastened to a wall using the supplied rack angle brackets fastened to rear of
cabinet
All cabinets can be free standing on a solid or elevated floor; optional floor mounting brackets are
required
Charger models that output 24 Vdc @ 50A or 100A can have hot cabinet surfaces. Install these models so that top and rear cabinet surfaces are unlikely to be touched by personnel.
Charger models with drip shields are to be placed where the shield is unlikely be in contact with people. The shield should not have anything set upon it.
La surface des cabinets peut être CHAUDE pour les modèles de chargeur avec une sortie de 24 Vdc @ 50A ou 100A. Installez ces modèles dans un endroit ou ils sont peu susceptibles d'être touchés par le personnel.
Les modèles avec un « pare-gouttes » doivent être placées là le dessus est peu probable d'être en contact avec du personnel. Ne rien placer sur le pare-gouttes.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-6
FIGURE 2-1 12" CABINET DIMENSIONS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-7
FIGURE 2-2 24" CABINET DIMENSIONS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-8
User's AC Ele ct rica l Service Panel
ARE Series Float Charger
+ _
Battery Stri n g
+ _
Load
+
_
Single-Phase AC Input
DC Output
Alarm Wires Operator
AC Circuit
DC Circuit
DC Output Cable
AC Input

2.4 ELECTRICAL INSTALLATION

Each charger is internally connected for the nominal AC input voltage stated in the charger’s model number. Refer to the model number on the charger nameplate and Section 1.2 Model Designation to be sure that the charger is intended for your incoming AC line voltage.
If there are sustained AC voltage fluctuations outside the ranges given in the Specifications section of this manual, contact the Field Service Department of UNIPOWER.
A block diagram of a typical charger electrical installation is shown in Figure 2-3. Note that the load is connected to the battery string terminals through a fuse or circuit breaker.
FIGURE 2-3 ELECTRICAL INSTALLATION, BLOCK DIAGRAM
Chargers are furnished with three holes for top conduit entrances; see Figure 2-4. These holes can be enlarged to accommodate 1-1/2” conduit.
Panel
Breaker
Cable
Breaker
All charger connection terminals are accessed by opening the hinged front panel. AC input and DC output power terminals are located on the accessory panel at the right front of the unit. The alarm terminal block is located on the Interface Board at the left front of the unit. AC and DC terminals are shown in Figure 2-5. Connection locations vary with cabinet size.
FIGURE 2-4 TYPICAL ELECTRICAL ENTRANCE AND BREAKER LOCATIONS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-9
Terminal Block, TB1
AC Input, L1
AC Input, L2 or Neutral
AC Circuit Breaker
DC(+) Output
DC(-) Output
DC Circuit Breaker
AC Input, Ground
FIGURE 2-5 ELECTRICAL INSTALLATION TERMINALS, 12" AND 24" CABINET MODELS

2.4.1 Grounding the Cabinet

Ground the charger to the site’s earth/safety ground. Figure 2-5 show the provided ground terminal. Connections must comply with the National Electrical Code and all applicable local codes and ordinances.
1. Open the front panel by loosening the quarter-turn captive screws at the right edge of the panel.
2. Locate the ground terminal near the upper center of the internal panel. It is labeled with a ground
3. Route the user-supplied ground wire through one of the cable entrance holes and connect it to the
4. Connect the other end of the cable to the site’s earth/safety ground.

2.4.2 Installing a User’s AC Electrical Service Panel

The user should furnish an electrical service panel with either a fuse-protected AC disconnect switch or an AC circuit breaker for supplying power to the charger. Before selecting the rating of the protective device and the AC and DC cables sizes, check the equipment nameplate and the Specifications section in Section 1-3 for charger input and output voltage and current. The rating of the protective device on the power circuit feeding the unit must equal or exceed equipment breaker rating. When standard AC circuit
*NOTE: GENERIC; MAY VARY PER SYSTEM
Swing the panel open.
symbol. Internally, this terminal is connected to the charger cabinet/chassis.
ground terminal.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-10
WARNING
AVERTISSEMENT
breakers are provided in the unit, the upstream protection shall not exceed 4 times the rating of the input breaker and shall not exceed 225A. The av ailable fau lt curren t shall not exceed the interrupt rating list in section 1.3.2 for the model being installed. For locations with fault currents in excess of the standard capacity, optional high interrupting circuit breakers are required. Refer to the National Electrical Code (NEC) to select cable sizes.
*Note: 24 inch cabinets require wire rated 75°C or greater.

2.4.3 Connecting AC Input Cables

1. Confirm the required AC input voltage. Refer to the model number on the charger nameplate and to
the Model Designation table 1-1. See the Specifications section 1-3 for AC voltage and current requirements.
A tag in the unit tells the factory voltage setting. If the AC input voltage must be changed, refer to the voltage changeover instructions. Go to Chapter 6 Maintenance and locate the cabinet assembly and schematic for the model at hand. Each schematic has a table and a connector detail drawing showing the needed connections.
2. Determine the AC input cable wire size. Refer to the National Electrical Code and local codes as
necessary. The 24 inch cabinets require wire rated 75°C or greater.
3. At the charger, switch the AC input breaker to off.
4. Locate the conduit entrance hole and install conduit as necessary.
5. Route the AC cable from the user’s AC electrical service panel and into the charger cabinet. Strip the
6. Connect the cable to the AC input terminal block. See Figure 2-5 for connections. The power supply
7. At the user’s AC electrical service panel, set the circuit breaker to off. Connect the AC cable at the

2.4.4 Connecting the Battery String Routing stiff, heavy gauge battery cables can be difficult. Two people may be needed. Exercise extreme

caution to avoid a short circuit across the battery terminals.
Arcing hazard
Arcing can cause equipment damage, load interruptions, and personal injury. Remove watch and jewelry. Use insulated tools, appropriate arc flash personal protective equipment, and extreme caution when working with a battery string. Carefully insulate unterminated battery cable ends. Carefully check connection polarity.
cable ends and install cable lugs, as desired.
electrical circuits are isolated from ground so the AC supply must be connected to terminals TB1-1 and TB1-2 on all models.
service panel.
Risque d'arc Un arc électrique peut causer des dommages sur
les équipements, des interruptions de charge, et des blessures. Retirez vos montres et bijoux. Utiliser des outils isolés, équipement de protection individuelle approprié contre les arc éléctrique, et une prude nc e extrême lorsque vous travaillez avec des batteries. Isoler les extrémités des câbles de batterie. Vérifiez la polarité de connexion.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-11
To connect the battery string:
1. Refer to the Specifications section in Chapter 1 for charger output current and recommended cable
size. Additional cable selection information is provided in Section 2.2 Reference Material. The 24 inch units require wires rated 75°C or greater.
2. At the charger, locate the DC Output conduit entrance and install conduit as necessary.
3. Route the DC cable from the battery (or output load) to the charger and into the cabinet.
4. Switch the DC output circuit breaker to off.
5. Connect the battery leads to the terminal block. See Figure 2-5 for the terminal block location. Mark
the free cable ends with the polarity (+ or -).
6. At the battery, strip the wire ends and ins tall lugs approp ri ate to the b at te r y term inals.
7. Check cable polarity and connect the lugs to the battery (or output load) terminal plates or posts.

2.4.5 Connecting an External DC Load

Load connections depend upon whether the charger is connected to a battery string.
Battery String Connected – Connect the external load to the battery string terminals through a circuit
breaker or fuse.
Battery String Not Connected – Connect the external load to charger DC output terminals.
Read the Warning statements in Section 2.4.4 Connecting the Battery String before proceeding.
To connect a load:
1. Refer to the Specifications section in Chapter 1 for charger output current and recommended wire
size. Refer to the charger nameplate and to the Model Designation table in Chapter 1 for the charger model number. Additional cable selection information is provided in Section 2.2 Reference Material. The 24 inch units require wire rated 75°C or greater.
2. At the charger, locate the DC Output conduit entrance and install conduit as necessary.
3. Route the DC supply and return cables between the load and either the battery or the charger.
4. At the load, connect the supply and return cables. Mark the free cable ends with the polarity (+/-).
5. At the battery string or charger, strip the wire ends and install lugs, as required.
6. Carefully check cable polarity and connect the cables.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-12
ALARM STATE
NORMAL CONDITION
ALARM CONDITION
LVA
De-Energized
Energized
HVA
De-Energized
Energized
HVSD
De-Energized
Energized
NCA
Energized
De-Energized
GND-
De-Energized
Energized
GND+
De-Energized
Energized
RECT FAIL
De-Energized
Energized
AC FAIL
Energized
De-Energized
SUMMARY
De-Energized
Energized

2.4.6 Connecting Alarm Annunciation

Connect user-supplied alarm annunciators to terminal block TB1 on the Interface Board. Refer to Section
1.3 Specifications for alarm relay specifications and for recommended wire size.
As shown by the detail on this page and Figures 2-6 and 2-7, each relay has three connections: common, normally open, and normally closed. The normally open (NO) and normally closed (NC) labels are for an un-powered charger.
To connect alarm annunciators:
1. Open the front panel. Loosen two quarter-turn captive screws at the right edge of the panel. Swing the
panel open.
2. Locate the Interface Board on the left side of the internal panel. See Figures 2-6 and 2-7 for a view of
terminal block TB1 and connector labeling. TB1 consists of either 3 or 9 separate 3-terminal blocks.
3. For each alarm output, strip the wire ends 1/4" to 5/16" and make the needed connections as shown in
Figure 2-7.
Note: If desired, the plug can be pulled straight up and out of the terminal block for wiring. After wiring the plug, insert the plug into the appropriate terminal block.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-13
(OPTIONAL)
RED
P2
CD00041a
Remov able Plug TB1, Interface Board-Mounted Terminal B locks
Customer Alarm Wiri ng
(OPTIONAL) CONTROL BOARD
CHARGER
CHARGER
CHARGER
CONNECTOR (2 PIN)
TEMPERATURE PROBE
EXTERNAL TEMPERATURE PROBE CONNECTOR
CONNECTOR (40 PIN)
BLUE BLACK
CONNECTIONS (4 PIN)
CONNECTIONS (3 PIN)
CONNECTOR (17 PIN)
OPTIONAL CHARGER
FIGURE 2-6 INTERFACE BOARD
FIGURE 2-7 ALARM CONNECTIONS DETAIL, INTERFACE BOARD
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Installation
2-14
CAUTION
ATTENTION

2.4.7 Connecting the Battery Temperature Probe (Option)

When the battery temperature probe option is ordered with the charger, a temperature probe is connected to the charger’s Interface Board and the probe and wires coiled and tied near the Interface Board, behind the front panel.
To connect the battery temperature probe:
1. Open the front panel. Loosen two quarter-turn captive screw s at the right edge of the panel. Swing the
panel open.
2. If not already connected, connect the probe’s three wires into P2, then plug P2 into J2 on the Interface
Board as shown in Figure 2-6.
3. Route the probe to the battery string. Cable length is approximately 25 feet (8m).
4. Determine which battery cell or group of cells will have the highest operating temperature.
5. Determine the charge/discharge status of the battery string. Connecting the probe may result in a
momentary battery string open circuit when the terminal bolt is removed.
DO NOT proceed if the battery string is in a high charge or discharge state.
NE PAS procéder si la batterie est en haute recharge ou en mode décharge.
6. Remove the bolt holding the intercell battery strap in place. Insert the bolt through the battery
temperature probe ring lug, through the strap, and into the battery terminal. Tighten the bolt as recommended by the battery manufacturer.
7. Bundle and secure any excess wire.
During commissioning, enable battery temperature compensation using the front panel keypad and 2-line display. (See Section 4.3.4.2)
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Commissioning
3-1
2-Line
4-Button
DC On/Off
AC On/Off

3.0 COMMISSIONING

This chapter describes configuring, commissioning, and operating an ARE-Series 24V Charger. A front view of a typical charger is shown in Figure 3-1. All operator controls are on the front of the charger.
Display
Keypad
FIGURE 3-1 OPERATOR CONTROLS
The front of the unit has a large, high-contrast 2-line digital display, a 4-button keypad with tactile feedback for positive data entry, two LEDs for charger On/Off and alarm indications, and AC and DC circuit breakers. An optional control board offers front panel indicators, consisting of a High Voltage Alarm, Low Voltage Alarm, No Charger Alarm, AC Fail Alarm on the telecom models, and an additional Positive and Negative Alarm indicators are on the utility models. A microcomputer-based controller manag es charger operation. The keypad and display provide the means for entering charger setup data (e.g. float voltage, high voltage shutdown, and temperature compensation on/off).
IMPORTANT: Press the keypad with your finger. Pressing with a sharp or pointed tool will damage the switch overlay and can damage the switch itself.
The following two sections will describe charger commissioning.
Circuit Breaker
Circuit Breaker

PREPARATORY STEPS 3.1

Perform the following steps prior to actually commissioning a charger.
1. Gather system wiring diagrams, battery data sheets, and other site documentation for ready reference should
it be needed.
2. Check that all installation steps have been completed. Review Chapter 2 Installation. The system can be
commissioned with or without a battery string.
3. If a battery string is connected to the charger, temporarily disconnect any external load connected to the
battery string.
4. Review the steps in Section 3.2 Commissioning Procedure.
5. Become familiar with the operation of the front panel and the setup menus by reading Chapter 4 Setup and
Operation.
6. Read the two statements below to determine whether charger setup parameter values can be displayed and
edited prior to application of AC power to the charger. See Chapter 4 Setup and Operation for setup details. Table 4-1 lists default parameters and values.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Commissioning
3-2
26.4VDC 0.0ADC
ACTIVE ALARMS
Battery String Connected to Charger – The string will power the charger contro lle r if there is at least a
minimal battery charge. The 2-line display, keypad, and Alarm LED will be active. The setup can be edited at the charger front panel without applying AC power to the charger.
No Battery String Connected – When AC power is applied to the charger, the controller will load a
default charger setup. You may then use the front panel to change many of the default parameter values to accommodate the application.
7. Set the AC and DC breakers on the charger front panel to off.
8. Finally, perform the steps in Section 3.2 Commissioning Procedure.

COMMISSIONING PROCEDURE 3.2

This procedure assumes a newly installed system that includes a connected battery string and load. The voltages and currents shown in the screens in this section are examples. They can vary with the charger model, charger setup, connected load, and other factors.
1. Check that the AC and DC circuit breakers on the charger front panel are switched to off.
2. Check that the circuit breaker in the user’s AC electrical service panel is switched off.
3. Check that:
The AC input cable is connected to the correct terminals and that connections are tight
DC load and battery cables are correctly connected and that connections are tight; check polarity as well
Alarm wiring is correct and tight, and that user-supplied alarm annunciators function
The charger chassis is correctly grounded
4. Switch the DC output breaker on the charger front panel to on.
Battery string connected to charger – The filter capacitors
connected across the DC output will be charged by the string. The 2-line display on the front panel should show the battery
FLOAT
voltage and current.
Note: The inrush current may trip the DC breaker. If so,
LCA
close the breaker.
The green AC input ON/OFF LED should be off. The red Alarm LED may be lit since all loads are disconnected, a low current alarm condition and the AC power is off. The low voltage alarm may be activated. The factory-installed or user-edited setup will specify the low current alarm value.
No battery string connected – The 2-line display will not be active. The capacitors will charge when the
AC input breaker is closed in step 6. Both the output current and voltage will build up gradually, provided some load is connected.
5. At the user’s AC electrical service panel, switch the AC circuit breaker On to power the charger.
6. At the charger, switch the AC input breaker on. The DC output current will build up gradually due to the
“walk-in” or “soft-start” characteristic of the equipment. The green AC on/off LED should be on.
The 2-line display will show the Home screen. If an alarm is present, the display will indicate an alarm on the Home screen; pressing the down button will indicate the alarms. The red Alarm LED will be lit if an alarm condition exits. See step 4 for sample displays.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Commissioning
3-3
7. Connect a load of about 10% of charger capacity to the battery terminals through a circuit breaker or fuse. If
a battery string is not connected, wire the load directly to the charger DC output terminals. Refer to the Section 2 Installation as necessary.
8. Refer to Chapter 4 Setup and Operation and use the front panel keypad and menus to:
1) Turn Off battery temperature compensation. (Note: If the float voltage is set at high or low battery
temperature with battery temperature compensation turned on, compensation may adjust the charger voltage by as much as 2 volts.)
2) If not performed previously, configure the charger by editing the factory setup to set the FLoat voltage,
EQualize voltage, and other parameters to accommodate the application.
9. Thoroughly test the setup to ensure that all configurable parameters are correct for the application. Test the
alarm circuits to ensure correct activation and annunciation.
10. Operate the system for 15-20 hours to charge the battery string(s) before placing the system on-line or as
recommended by the battery manufacturer.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Setup and Operation
4-1

4.0 SETUP AND OPERATION

This chapter describes setting up and operating a Micro ARE Series Charger using the 2-line display and 4-button keypad on the charger. See Figure 3-1 for the location of the panel, display, and keypad. The figure also shows the locations of the AC and DC circuit breakers mentioned in sections 4.1 & 4.2.

TURNING ON A COMMISSIONED CHARGER 4.1

1. Set the AC and DC circuit breakers on the front of the charger to off. See Figure 3-1 for the location
of the breakers.
2. At the user’s AC electrical service panel, switch on the appropriate circuit breaker to supply power to
the charger.
3. At the charger, switch the AC circuit breaker on. The m essag e “Starting” will appear and output
current will build up gradually due to the “walk-in” or “soft-start” characteristic of the equipment. During normal ramping LVA and RECTF alarm messages may appear and the alarm LED may flash.
4. At the charger, switch the DC breaker on.
Battery string connected - The filter capacitors connected across the DC output will charge. The
2-line display on the front panel should read the battery voltage. Note: The inrush current may trip the DC breaker. If so, again close the breaker.
No battery string connected - The capacitors will become charged when the AC breaker is closed
in step 4. Both current and voltage will then build up gradually, provided some load is connected.

TURNING OFF A COMMISSIONED CHARGER 4.2

1. At the charger, open the AC circuit breaker on the front panel. While the output voltage and current
are decreasing, an AC Fail alarm message may appear and the alarm LED may flash.
2. Open the DC circuit breaker.
3. If the charger is to be serviced, open the front panel and press the capacitor discharge button for 60
seconds.

SETTING UP AND OPERATING A CHARGER 4.3

Set up and operate the charger using the 2-line alphanumeric display and the 4-button keypad on the front panel. A series of menus provides access to charger status, active alarms, and setup parameter values. Menus are shown in Figures 4-1 through 4-4.
IMPORTANT: Press the keypad with your finger. Pressing with a sharp or pointed tool will damage the switch overlay and can damage the switch itself.
Note: The charger can be set up without AC power being applied if a battery string is connected. The keypad and controller board are powered whenever a battery string is connected to the charger.
The 4-Button Keypad
The four buttons on the keypad are labeled UP, DN (Down), SEL (Select), and ESC (Escape).
UP or DN is pressed to move vertically through a menu. Also, parameter values (e.g. float set point,
low voltage alarm set point, alarm enable/disable) are set using these buttons.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-2
26.4VDC 22.8ADC
28.0VDC 1.7ADC
26.4VDC 0.0ADC
When changing a parameter value using UP or DN, a single press will increment (UP) or decrement (DN) the value. Pressing and holding either button will cause the value to scroll, allowing large value changes to be made quickly.
SEL is pressed to move to the right, to select an operation, or to store parameter value.
ESC is pressed to move to the left or to cancel an operation or parameter value (before the SEL button
is pressed). Generally, pressing ESC will display either a Main Menu screen or the previous screen.
The Home Screen and Menus
The Home screen, shown at right, is the default display. It will first appear when a charger is turned on. Charger output voltage and current and charger operating mode (float or equalize) are
FLOAT
shown in the Home screen. If another screen is displayed and there is no keypad activity for 5-6 minutes (the timeout period), the Home screen will automatically be displayed.
If equalization is enabled, the Home screen will show the charger output voltage and current and the equalization time
Equalize 24hrs left
remaining.
Active alarms will also be displayed in the Home screen. The descriptor for an active alarm will alternate with the charger operating mode in the lower line of the Home screen. If
NCA RECTF
multiple alarms are present, all descriptors will scroll across the display. Alarms and operating mode will alternate in the Home screen until all alarms are cleared. Unacknowledged alarms are indicated by a flashing Alarm LED. A steadily glowing LED indicates that an alarm has occurred and has been acknowledged. Acknowledge alarms by pressing any button on the keypad.
Changing Parameters
1. Push SELe c t, "=" will flash indicating the parameter can be changed.
2. Push UP and DN to change to the required value.
3. Push SELect or ESCape to stop "=" from flashing, and save/abo rt chang e. a. A parameter will not change until SELect is pressed (and “=” stops flashing). b. If ESCape is pressed, parameter value changes will be lost.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-3
Charger Output (V & I) / Mode
Home screen
Active Alarms
See Section 4.3.1
Charger Status
See Section 4.3.2 and Figure 4-2
Operating Mode
See Section 4.3.2 and Figure 4-3
Charger Setup
See Section 4.3.3 and Figure 4-4
The Home screen is part of the Main Menu, which is shown in Figure 4-1. All charger statuses, alarms, and parameters can be accessed from the Main Menu . This menu has five screens: Home, Active
Alarms, Charger Status, Operating Mode, and Charger Setup. Press UP or DN to move from the Home screen to another Main Menu screen. Each of these screens will be briefly described below and
then discussed in detail in subsequent sections.
In all menus:
Press UP or DN to move vertically. Press SEL to move to the right. Press ESC to cancel a selection or move to the left.
FIGURE 4-1 MAIN MENU
The Active Alarms screen will show all cu r rent alarms. If multiple alarms are present, their alarm descriptors will scroll through the screen. Viewing an alarm also acknowledges that alarm.
Press SEL at the Charger Status screen to view charger-operating parameters; see Figure 4-2. Parameter values cannot be changed in this series of screens.
Press SEL at the Operating Mode screen to select float or equalization as the desired operating mode. This menu also contains a relay/lamp test function. See Figure 4-3. If password protection is enabled, a password is required to access these menus.
Press SEL at the Charger Setup screen to change charger setup; see Figure 4-4. If password protection is enabled, a password is required to access these menus.
Note: Each of the procedures in the following sections is complete in that each begins and ends at the Home screen. However, it is not necessary to begin or end at the Home screen to perform a procedure.
Simply use the 4-button keypad to navigate to the next desired screen following the most direct path.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-4
Main Menu
Select Status Screens
Charger Status
Charger Model/Firmware Rev.
From Figure 4-1
Parameter Screens
Note: View Setup
Float Setpoint
Parameter
Equalize Setpoint
values are
LVA Setpoint
read-only in
Battery Temperature
HVA Setpoint
this series of
HVSD Setpoint
menus
NCA Setpoint
Temperature Compensation
CL Setpoint
GND Detect Setpoint
VLVA Setpoint
Periodic Equalize
Hi Bat Temp Setpoint
LVA Delay
HVA Delay
Ground Fault Resistance
HVSD Delay
NCA Delay
CL Delay
Ground Fault Voltages
GND+ Delay
GND- Delay
RFA Delay
ACF Alarm Delay
EQ Alarm Delay
VLVA Delay
HiBatTemp Alrm Delay
Summary Alarm Delay
Alarm Latching
System Alarm Incl.
Summary Alarm Incl.
AC Fail Equalize
AC Fail Equalize duration
Periodic Equalize
Periodic Equalize duration
Main Menu
Mode Screen
Operating Mode
Equalize Mode Enable/Disable
From Figure 4-1
Relay/Lamp Test
In all menus:
Press UP or DN to move vertically. Press SEL to move to the right. Press ESC to move to the left.
-------------------------------------------------------------------------------------------------------------------------------
FIGURE 4-2 CHARGER STATUS MENU
FIGURE 4-3 CHARGER OPERATING MODE MENU
+
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-5
Main Menu
Setup Select Screens
Parameter Screens
Charger Set up
System Setpoints
Change Float Voltage
From Figure 4-1
Change EQ Voltage
Change LVA Voltage
Change HV A V oltage
Note:
Change HVSD Voltage
Parameter
Change NCA Current
values can be
Change CL C urrent
changed in this
Change GND Detection
series of menus.
Change VLVA Voltage
Change HBTA Temperature
Param. Subscreen
Change Alarm Delays
LVA Delay
HVA Delay
System Alarm
LVA Enable/Disable
HVSD Delay
HVA Enable/Disable
NCA Delay
HVSD Enable/Disable
CL Delay
NCA Enable/Disable
+GND Delay
CL Enable/Disable
-GND Delay
GND Enable/Disable
RFA Delay
RECTF Enable/Disable
ACF Delay
ACF Enable/Disable
EQ Delay
EQ Enable/Disable
VLVA Delay
VLVA Enable/Disable
HBTA Delay
HBTA Enable/Disable
Summary Delay
ALARM mode latching
Enable/Disable
Summary Alarm
LVA Enable/Disable
HVA Enable/Disable
HVSD Enable/Disable
NCA Enable/Disable
CL Enable/Disable
GND Enable/Disable
RECTF Enable/Disable
ACF Enable/Disable
EQ Enable/Disable
VLVA Enable/Disable
HBTA Enable/Disable
Temp. Compensation.
TC Enable/Disable
Set TC Coefficient
Auto-Equalize
AC Fail Equalize Enable/Disable
AC Equalize Time/Duration
Periodic Equalize Enable/Disable
Periodic Equalize Duration
Enable-Legacy
Load Shari ng
Load Share Enable/Disable
Enable-Standard
Password
Enable/Disable
New password
Factory Defaults
Power On Defaults
Factory Cal.
Enter Admin Password
FIGURE 4-4 CHARGER SETUP (CONFIGURATION) MENU
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-6
ARE-M 24V-50A UTL
Firmware X.XX
ACTIVE ALARMS

4.3.1 View Active Alarms All active alarms appear in the Active Alarms screen. Multiple alarms will scroll acro ss the scre en. A

flashing Alarm LED indicates unacknowledged alarms. An optional control board offers front panel indicators, consisting of High Voltage Alarm, Low Voltage Alarm, No Charger Alarm, AC Fail Alarm on the telecom models and an additional Positive and Negative Alarm indicators are on the utility models. A steadily glowing LED indicates alarms are present and have been acknowledged. An alarm will remain in the Active Alarms screen until the event causing that alarm is cleared. Enabling password protection will not limit access to this screen.
To view active alarms:
1. At the Home screen, press DN until ACTIVE ALARMS
appears. See Figure 4-1. A * No Alarms * message indicates that there are no active alarms. If alarms are present, the alarm
* No Alarms *
descriptors will appear in, or automatically scroll through, the display and the Alarm LED will glow.
Alarm descriptors are: LVA (Low Voltage Alarm), HVA (High Voltage Alarm), HVSD (High Voltage Shutdown), NCA (No or Low Current Alarm), CL (Current Limit), GND+ (Ground fault to +), GND– (Ground fault to -), VLV (Very Low Voltage), HBTA (High Battery Temperature Alarm), RECTF (Rectifier Fail), ACF (AC Fail), EQ (Equalize), and SUMM (SUMMary).
2. To return to the Home screen, press ESC.

4.3.2 View Charger Status

This series of screens provides read-only access to charger setup parameter values. Enabling password protection will not limit access to these screens.
To view charger status:
1. At the Home screen, press UP or DN until CHARGER STATUS appears. See Figure 4-2.
2. Press SEL to display charger model, type utility (UTL)/telecom (TEL) and firmware revision.
3. Press DN to display the View Setup screen. Press SEL to view the
Float Setpoint screen and then press UP or DN to move through the View Setup parameters. Press ESC at any time to return to the View Setup screen.
4. From the View Setup screen, press DN (or UP) to display the Battery Temperature, Temperature
Compensation, (Time to Next) Periodic Equalize, Ground Fault Resistance, or Ground Fault Voltage screen.
Note: Battery Temperature, Temperature Compensation and High Battery Temperature Alarms
require that Temperature Compensation option 2 is ordered and that the temperature sensor is installed. See Table 1-1 Model Designation for the option location in the charger model number.
5. Press ESC at any time to step back up through the menu hierarchy to the Home screen.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-7
EQUALIZE MODE
28.0VDC 1.7ADC
EQUALIZE MODE

4.3.3 Change Operating Mode (Manual Equalization)

Use this series of screens to manually enable and terminate equalization.
Note: If password protection is enabled, only authorized personnel will be able to change the operating mode.
To enable equalization:
1. At the Home screen press UP or DN until OPERATING MODE appears. See Figure 4-3.
2. Press SEL. The Equalize Mode screen will appear.
3. Press SEL. If the Begin Equalize screen appears, go to step 5. If
SEL to activate
the Enter Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password is displayed and then press SEL. Go to
step 5.
5. At the Begin Equalize screen, press one of the following:
Press SEL to select equalize mode. Go to step 6.
Press ESC to remain in float mode. Go to step 7.
Pressing UP or DN displays the Stay in Float Mode screen; press SEL to stay in float mode. Go
to step 7.
6. At the Equalize Duration screen, press UP or DN to set the duration (1-255 hours or Always On).
Press SEL to store the time.
7. Press ESC to step back up through the menu hierarchy to the Home screen.
To terminate equalization and return to float mode:
1. At the Home screen, press UP or DN until OPERATING MODE
Man. Equalize 24hrs left
appears.
2. Press SEL. If the Equalize Mode screen at right appears, go to step
4. If the Enter Password screen appears, go to step 3.
SEL to terminate
3. At the Enter Password screen, press UP until your password is
displayed and then press SEL. Go to step 4.
4. At the Equalize Mode screen, press one of the following:
Press SEL to terminate (cancel) equalization and go to float mode; go to step 5.
Press ESC to stay in equalize mode. Go to step 5.
Pressing UP or DN displays the Stay in Equalize Mode screen; press SEL to stay in equalize
mode. Go to step 5.
5. Press ESC to step back up through the menu hierarchy to the Home screen.
4.3.4.1 Alarm Relay/Lamp Test
This series of screens is used to test the alarm relays and Alarm LED. Since the alarm relays are being toggled (de-activated and activated ),
2
any attached annunciator (e.g. horn, siren, electronic messaging)
²See section 2.4.6 for the relay state for "NORMAL CONDITION" and "ALARM CONDITION".
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-8
Parameter
Factory Default
Operating Mode (FL/EQ)
Float
Float Setpoint
26.4V
Equalization (EQ)
28.0V
Low Voltage Alarm (LVA)
24.0V
Very Low Voltage Alarm (VLVA)
23.3V
High Voltage Alarm (HVA)
29.0V
High Voltage Shutdown (HVSD)
30.0V
Low Current Alarm (NCA/LCA)
2% of rating
Current Limit (CL)
110% of rating
High Battery Temperture (HBTA)
35°C
Temperature Compensation
Disabled
AC Fail Equalize
Disabled
Periodic Equalize
Disabled
Load Share
Disabled
will be toggled on and off. This test will produce an audible clicking as the relays are switched. The AC fail relay is not toggled.
1. At the Home screen press UP or DN until OPERATING MODE appears. See Figure 4-3.
2. Press SEL. The present operating mode will be displayed.
3. Press DN. If the RELAY/LAMP TEST screen appears, go to step 5. If the Enter Password screen
appears, go to step 4.
4. At the Enter Password screen, press UP until your password is displayed and then press SEL. Go to
step 5.
5. Press SEL to begin the test. Testing will continue until ESC is pressed.
6. Press ESC to step back up through the menu hierarchy to the Home screen.

4.3.4 Change Charger Setup (Configuration)

A default setup (i.e. configuration) is factory-installed. Table 4-1 lists the factory parameter values. Customer parameter values can be loaded if supplied with the order for the charger.
Refer to the menu shown in Figure 4-4 when setting-up a newly installed charger or when changing the setup of an operating charger. The figure shows how to navigate the Charger Setup menu so that you can change operating parameters to accommodate your application.
Note: If password protection is enabled, only authorized personnel will be able to change setup parameter values. When changing multiple values, you will be asked for your password only once during a charger setup session.
TABLE 4-1 FACTORY DEFAULT SETUP PARAMETER VALUES
Some parameters are dependent upon optional features. For example, temperature compensation requires the installation of an optional temperature sensor. Before setting up a charger, refer to Table 1-1 Model Designation and determine which options are installed in the charger at hand. The procedures in this section are a bit more detailed than in the preceding sections. Consequently, several subsections are employed to simplify describing of the setup options available within this menu.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-9
CAUTION
ATTENTION
Battery Type
Float
Equalize
(1.245 Specified gravity
2.17 – 2.22
**
4.3.4.1 System Setpoints, System Alarms, and Summary Alarm
The System Setpoints, System Alarms, and Summary Alarm menu selections, shown in Figure 4-4, are used to change set point voltages and currents, enable and disable system and summary alarms, set alarm delays, and adjust other parameter values. Guidelines for establishing values for some of these parameters are provided immediately below. Following the guidelines is a procedure for accessing and setting parameter values.
The adjustment range of system Setpoints will vary with charger voltage and current capacity. See Section 1.3 Specification for additional information.
For systems with blocking diodes, the Float and Equalize voltage should be set about 0.7 volts above the desired battery voltage to compensate for the diode voltage drop. This offset should be adjusted to obtain the desired output voltage for each installation.
Guidelines
Float and Equalize Voltages
Table 4-2 shows typical float and equalize voltages on a per cell basis for several types of batteries.
Refer to the battery manufacturer’s data sheet for the float and equalization setpoints that best fit your application and battery type. Do not set either float voltage or equalize voltage while the charger is operating in the current-limit mode. Disable battery temperature compensation (see Section 4.3.4.2) before setting the float voltage.
TABLE 4-2 TYPICAL FLOAT/EQUALIZE VOLTAGES
Lead Antimony (1.210 Specific gravity)
Lead Calcium (1.210 Specific gravity)
Nickel Cadmium
Nickel Iron
Lead-Acid, Valve­Regulated (Sealed) (1.300 Specified gravity) (1.290 Specified gravity)
Referez-vous à la fiche technique du fabricant de la batterie pour la tension d’entretien et d'égalisation qui correspondent le mieux à votre application et du type de batterie. Ne pas régler la tension d'e ntr eti en ou d’égalisation lors que le chargeur fonctionne en mode limite de courant. Désactiver la compensation de température de la batterie (voir la section 4.3.4.2) avant de régler la tension d’entretien.
2.15 – 2.17
2.17 – 2.25
1.43
1.50 – 1.55
2.25 – 2.30
2.25 – 2.30
2.33
2.33
1.55
1.60 – 1.65
** **
* Equalize charge is required only if cells have experienced a discharge. ** Additional equalize charging is not r e c ommended after initial equalization. Consult battery manufacturer for particular recommendations.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-10
Note: Lead-calcium alloy grid batteries do not require regular equalizing. Set the equalization voltage to equal the float voltage.
Low Voltage Alarm (LVA)
Set the LVA alarm to a voltage that, if charger output voltage falls below this setting, an alarm will be annunciated.
High Voltage Alarm (HVA)
Set the HVA alarm to a voltage that, if charger output voltage goes above this setting, an alarm will be annunciated.
High Voltage Shutdown Voltage (HVSD)
Set the HVSD alarm to a voltage that, if charger output voltage goes above this setting, the charge will shutdown.
High Voltage Shutdown Reset
Press the SEL on the keypad to reset the HVSD. NOTE: The charger voltage must drop below the HVSD set voltage. In addition if the hardware overvoltage protection has been engaged, two methods can be used to reset the hardware. The first is to remove the wiring harness (J5) from the interface board for 5 seconds, then replace. The second method is to physically disconnect the battery from the charger.
Low Current (No Charge) Alarm (NCA)
Set the NCA alarm to a current that, if charger output current falls below this setting an alarm will be annunciated.
Ground Detection Alarm (GND) - Two pole DC breaker models only
Gives a +GND or –GND alarm when the resistance between the charger output and ground, is below the set point. The Ground Alarm resistance is adjustable. High resistance values are for a very sensitive detection, low values are for less sensitive detection. The ground fault resistance and fault voltages can be monitored using the “Ground Fault Resistance” and “Ground Fault Voltages” submenus as shown in Fig. 4-2.
The resistance value displayed for the set point is the resistance that the system will detect from one output pole to earth with no other current paths from output to earth. The presence of other current paths, intentional or not, can affect the operation of the alarm. Intentional current paths on the output of the unit may be external ground detection systems or ground reference connections in loads. Unintentional current paths may be leakage currents over the battery cases, conductive pollution accumulation on connections, or moisture on cables and connections.
If you have nuisance ground alarm indication and there are no intentional current paths and there are not faults on the DC system (battery, charger, loads, and all interconnecting dc cabling), and all equipment is properly grounded, you may lower the sensitivity of the detection to eliminate the nuisance alarm. If the system has external ground detection, the ground alarm on the charger may be disabled. If the cha rg er’s ground detection circuitry is interfering with the external ground detection, the optional ground detection switch may be turned off. (The optional ground detection switch is a factory-installed option.) NOTE: See section 7.6 for ground detection switch options.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-11
Change Float Voltage
Very Low Voltage Alarm (VLVA)
Set the VLVA alarm to a voltage that, if charger output voltage falls below this setting, an alarm will be annunciated.
High Battery Temperature Alarm (HBTA)
Set the HBTA alarm to a temperature that, if the battery temperature rises above this setting, an alarm will be annunciated. The temperature compensation (option 2) must be purchased and installed in order for this alarm to work. If this option is installed the battery temperature can be found in the “Battery Temperature” menu as shown in Fig. 4-2.
Rectifier Fail Alarm (RECTF)
Gives a RECTF alarm, if enabled, if both an alarm that can cause a rect ifier fa ilur e alarm (REC T) is enabled and the alarm is active.
AC Fail Alarm (ACF)
Gives an ACF fail alarm when the AC power to the charger is missing.
Alarm Mode Latching
In the enable mode this allows alarms to be latched in the alarm state until an operator clears them by pressing any key on the key pad. In the disable mode, the alarms clear once the alarm condition has cleared.
Set Parameter Values
Parameter values access ed from the System Setpoints, System Alarms, and Summary Alarm screens are changed as follows.
1. From the Home screen press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the System Setpoints screen, press one of the following:
Press SEL to set system set point parameters.
Press UP or DN to move to another screen in the Setup Select Screens column. Then press SEL.
3. If a parameter screen appears, see example at right, go to step 5.
If the Enter Password screen appears, go to step 4.
Float = 26.4V
4. At the Enter Password screen, press UP until your password
appears and then press SEL. Go to step 5.
5. At the parameter screen, press UP or DN to display the parameter to be changed. Press SEL.
If changing a parameter value, the on-screen equals sign (=) will flash. Go to step 6.
To change Alarm Delays, again press SEL and go the step 6.
6. Press UP or DN until the desired value (e.g. set point voltage or current, enable/disable, or alarm
delay time) is displayed. Press one of the following:
Press SEL to store the new value. The equals sign will stop flashing.
Press ESC to cancel or abort changes.
7. Press UP or DN to move vertically to the next value to be changed.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-12
8. When all setup parameters have been set, press ESC to return to the higher level menu
9. As needed, repeat the above for each of the three setup select scr een s in this section.
10. When parameters have been set, press ESC to return to the higher level menu or press ESC until the
Home screen appears.
4.3.4.2 Battery Temperature Compensation
Temperature compensation option 2 must installed for compensation to function. See Table 1-1 Model Designation for the option location in the charger model number.
To enable compensation:
1. From the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the System Setpoints screen, press UP or DN until the Temperature Compensation screen
appears.
3. Press SEL. If the Battery Temperature Compensation Screen appears, go to step 5. If the Enter
Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password appears and then press SEL. Go to step
5.
5. At the Compensation disabled screen, press SEL. The equals sign (=) will begin to flash.
6. Press UP to toggle to “enable.” Press one of the following:
Press SEL to store the change. The equals sign (=) will stop flashing. Go to step 7.
Press ESC to cancel or abort compensation. Go to step 10.
7. Press DN to display the Set Temperature Coefficient screen.
8. To change the coefficient, press SEL. The equals sign (=) will flash.
9. Press UP or DN to display the desired mv/Cell/C value. Press SEL to store the new value.
10. Press ESC to return to the Temperature Compensation screen. Either press UP or DN to move to
another Setup Select Screen or press ESC until the Home screen appears.
Note: Refer to the battery manufacturer for the correct temperature compensation value. To disable Temperature Compensation:
1. From the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the System Setpoints screen, press UP or DN until the Temperature Compensation screen
appears.
3. Press SEL. If the Battery Temperature Compensation Screen appears, go to step 5. If the Enter
Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password appears and then press SEL. Go to step
5.
5. At the Compensation enabled screen, press SEL. The equals sign (=) will begin to flash. Press one
of the following:
Press UP to toggle to “disable.” Press SEL to store the change. The equals sign (=) will stop
flashing.
Press ESC for Compensation to remain enabled and return to the higher level screen.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-13
AUTO EQUALIZE
AC Fail Equalize
Periodic Equalize
6. Press ESC to return to the Temperature Compensation screen. Either press UP or DN to move to
another Setup Select Screen or press ESC until the Home screen appears.
4.3.4.3 Auto-Equalize
There are two Auto-Equalize modes: AC Fail Equalize and Periodic Equalize. Both are disabled by default. Both or either may be enabled.
AC Fail Equalize will automatically switch the charger to equalize mode for a user-set time when
there has been no AC input to the charger for a period exceeding a user-set time.
Periodic Equalize causes the charger to switch to equalization mode for a user-set time after a user-set
time in float mode elapses.
To enable one or both Auto-Equalize modes:
1. From the Home screen, press UP or DN until CHARGER SETUP
appears. Press SEL.
SEL to setup
2. At the System Setpoints screen, press UP or DN until the Auto-
Equalize screen appears.
3. At the Auto-Equalize screen, press SEL. If the AC Fail Equalize
= DISABLED
screen appears, go to step 5. If the Enter Password screen appears, go to step 4.
4. At the Enter Password screen, press UP until your password appears and then press SEL. Go to step
5.
5. At the AC Fail, Equaliz e screen, perform one of the following:
To enable AC Fail Equalize, press SEL. The equals sign will flash. Press UP to enable AC Fail,
Equalize and display the AC Fail Equalize after screen. Go to step 6.
To enable Periodic Equalize, go to step 8.
6. At the AC Fail Equalize after screen, press UP to set the timer (1-7200 minutes). Press SEL. The
equals sign will stop flashing.
7. Press DN to display the AC Fail Equalize duration screen. Press SEL. The equals sign will flash.
Press UP to set the time (1-150 hours). Press SEL. The equals sign will stop flashing.
8. Press DN until the Periodic Equalize screen appears.
To enable Periodic Equalize, Press SEL. The equals sign will
= DISABLED
flash. Press UP to display enable Periodic Equalize and display the Periodic Equalize every screen. Go to step 9.
To exit Auto Equalize, go to step 11.
9. At the Periodic Equalize every screen, press UP to set the time (168 to 8760 hours). Press SEL.
10. Press DN to display the Periodic Equalize duration screen. Press SEL. The equals sign will flash.
Press UP to set the time (1-150 hours). Press SEL.
11. Press ESC to return to the Auto-Equalize screen. Either press UP or DN to move to another Setup
Select Screen or press ESC until the Home screen appears.
To disable AC Fail-Equalize:
1. At the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. At the System Setpoints screen, press UP or DN until the Auto-Equalize screen appears.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-14
3. At the Auto-Equalize setup screen, press SEL. The AC Fail Equalize after screen will appear.
4. Press SEL. The equals sign will flash. Press DN until DISABLED appears. Press SEL.
5. Press ESC to return to the Auto-Equalize screen. Either press UP or DN to move to another Setup
Select Screen or press ESC until the Home screen appears.
To disable Periodic Equalize:
1. At the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. At the System Setpoints screen, press UP or DN until the Auto-Equalize screen appears.
3. At the Auto-Equalize setup screen, press SEL. Press UP or DN until the Periodic Equalize screen
appears.
4. Press SEL. The equals sign will flash. Press DN until DISABLED appears. Press SEL.
5. Press ESC to return to the Auto-Equalize screen. Either press UP or DN to move to another Setup
Select Screen or Press ESC until the Home screen appears.
4.3.4.4 Load Share
There are two Load Share modes: Load Share Standard and Load Share Legacy. Select Standard when two or more Micro ARE-Ms, the chargers described in this manual, are to share a load. Legacy is used when a Micro ARE-M is to share a load with an earlier model ARE.
To enable Load Share:
1. From the Home screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2. From the Load Share screen press SEL. The Load Share Disabled screen will appear.
3. Press UP to display the Load Share statuses: press UP for Load Share Standard; press UP again to
display Load Share Legacy.
4. Press SEL to store the new status.
5. Press ESC to return to the Load Share screen. Either press UP or DN to move to another Setup Select
Screen or Press ESC until the Home screen appears.
To disable Load Share:
1. At the Load Share screen press SEL. The Load Share Enabled screen will appear.
2. Press DN until DISABLED appears.
3. Press SEL to store the new status and go to the Load Share screen. Either press UP or DN to move to
another Setup Select Screen or Press ESC until the Home screen appears.
Note: Refer to section 4.3.4.9 for additional Load Share setup information.
4.3.4.5 Password
Password protection allows only authorized personnel to change parameter values in the Operating Mode menu (Figure 4-3) and Charger Setup menu (Figure 4-4). While password protection is disabled
by default, enabling password protection is recommended.
Anyone with access to the charger front panel can view alarms and parameter values in the Active Alarms screen and the Charger Status menu (Figure 4-2). Password protection is not needed since these are read-only displays.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-15
Enter Old Password
Enter New Password
Enter Old Password
Enter New Password
Enter Old Password
Enter New Password
When password protection is enabled, you will be asked for your password only once during a setup session, regardless of the number of setup changes made. After 5-6 minutes of no keypad activity, your setup session will time-out and you will again be asked for your password to change a parameter value.
Any number between 00002 and 65500 can be used as the password. Select a password that is easy to remember but difficult for others to guess. As with any password, secrecy is required for meaningful security. If the password is forgotten, contact UNIPOWER Field Service.
A. Enabling and Setting a Password:
1. At the Home screen, press UP or DN until the CHARGER SETUP appears. Press SEL.
2. At the System Setpoints screen, press UP or DN until the Password scr een ap pea rs.
3. At the Password screen, press SEL to display the Old Password
screen.
None (disabled)
4. Press SEL to display the New Password screen. Press UP to
enable protection. Press UP or DN until the desired password number (00002-65500) is displayed. If UP or DN is pressed and held, the nume rica l d isp la y will scroll.
None (disabled)
5. With the desired password displayed, press SEL to store the
password and return to the Password screen. Either press UP or DN to move to another Setup Select Screen or press ESC until the Home screen appears.
B. Changing a Password:
1. At the Password screen, press SEL to display the Old Password
screen.
None (disabled)
2. Press UP until your old (present) password is displayed and then
press SEL.
3. At the New Password screen, press UP and then either UP or DN
to display your new password.
(New password)
4. With the new password displayed, press SEL to return to the
Password screen. Either press UP or DN to move to another Setup Select Screen or press ESC until the Home screen appears.
C. To Disable Password Protection:
1. At the Password screen, press SEL to display the Old Password
None (disabled)
screen.
2. Press UP and then either UP or DN until your old (present) password is displayed and then press
SEL.
3. At the New Password screen, press DN until “disabled” appears.
(password)
4. Press SEL to return to the Password screen. Either press UP or
DN to move to another Setup Select Screen or press ESC until the Home screen appears.
4.3.4.6 Factory Defaults
Pressing SEL from the Factory Defaults screen will replace any customer setup entries with the factory default values shown in Table 4-1.
1. At the Home screen, press UP or DN until the CHARGER SETUP appears. Press SEL.
2. At the System Setpoints screen, press UP or DN until the Factory Defaults screen appears. Press
SEL.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-16
3. At the Power On Defaults screen, press SEL to return to the factory defaults or press ESC to return
to the System Setpoints screen.
4.3.4.7 Factory Calibration
Factory Calibration is intended for use by factory personnel and is not field accessible. Contact UNIPOWER Service for additional information.
4.3.4.8 Field Calibrations
The only user adjustment on the Interface Board (A1) is load share adjustment R63. No other settings are field adjustable. All other field adjustments are described previously in this chapter.
4.3.4.9 Field Connection and Calibration of Loadshare
Load sharing allows two or more ARE Series and ARE-M Series units connected in parallel to share the load in proportion to their ratings. The power supplies will share the load within 5% of the rating of the largest unit between 10% and 100% of their ratings. The load sharing is connected through the no charge alarm, which disconnects the load sharing should one charger be shut off.
Connections
For load sharing, connect all units which are to share the load to the system bus using equal lengths of properly sized cables. Connect #18 AWG insulated wire from TB2-3 or 4 (LOADSHARE) on the Interface Board (A1) of charger A to TB2-3 or 4 (LOADSHARE) on the Interface Board (A1) of charger B.
Adjustment
The loadshare is set at the factory and normally does not require any adjustment. If adjustment is needed, follow the procedure below.
A. For each unit, turn on only one unit at a time and adjust the output voltage to the desired level. B. Connect a digital voltmeter positive lead to the power supply positive output and the negative
lead to TB2-3 or 4 (LOADSHARE) on the Interface Board (A1). No other connections should be made to these terminals on the interface board.
C. Adjust potentiometer R63 on the interface board for 5.0VDC at zero output current.
For Two Power Supplies
A. Turn on both units. Verify Load sharing is enabled on both units. (See 4.3.4.4) B. Add some load to the system and adjust R63 on the unit with lower output current to match the
output current of the other unit. For best results, the load should be between 50% and 100% of the combined rating of the two units.
For More Than Two Power Supplies
Start by adjusting two of the units then add the rest of the units one at a time, adjusting R63 on each added unit until all units are sharing the load.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single Phase Setup and Operation
4-17
Operational Notes
1. Load sharing is not intended to be effective below 10% of rated output. Operation below 10% may result in unequal outputs or loss of output current form one of the units. It is recommended that where paralleled units are being used to float a battery before the system load is installed, only one unit be left operating.
2. Minor changes in the displayed output current may occur when paralleled units are operated at light loads. This is an indication of the transfer of small currents between units and does not show up at the load.
3. It is possible for hunting to occur if the output voltages are misadjusted. Repeat step A under “Adjustment”.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Circuit Description
5-1
Single-Phase
AC Input
AC
Circuit
Breaker
Power Transformer
Constant Voltage
Ferro Resonant
Electronic
Voltage & Current
Control
High Voltage
Shutdown
Rectifier
Resonant Capacitor
DC Filter
Resonant
Control
Operator Panel
Alarms
Battery and Load
Form C Relay
Outputs to
Customer Alarm
Annunciators
Control and Display Board and Interface Board
DC Circuit Breaker

5.0 CIRCUIT DESCRIPTION

Figure 5-1 is a functional block diagram of a Micro ARE-M series float charger. AC input power is applied through the input circuit breaker to the power transformer. The circuit breaker provides over-current and fault protection in case of malfunction or a short circuit in the input side of the equipment.
The power transformer in a Micro ARE-M Series power supply is of the ferroresonant type. This class of transformer has the output coil on the same leg of the core as the resonant winding. This winding, together with the resonant capacitor, maintains the core at a high level of saturation, resulting in a constant output voltage against changes in the input voltage. The high reactance of this type of transformer provides protection against overload and short circuit of the output.
To improve the output voltage regulation against changes in load and input frequency, the chargers employ a ferroresonant transformer and UNIPOWER controlled-ferro technique, which controls the level of core saturation.
This is accomplished by shunting the resonant circuit with a triac in series with an inductor. The electronic voltage/current control senses the start of the resonant capacitor charge cycle. It also senses the output voltage level, which it compares with a reference voltage. The error signal that results determines the instant the triac turns on to interrupt the capacitor charge cycle and maintain the core saturation at the desired level.
The output current sensing and current limit operation is located on the Interface and Control/Display boards. The output current is sensed by measuring the voltage across a resistive shunt. The Interface and Control/Display boards convert the shunt signal into an output current value. When the output current exceeds the preset level, the c ur rent limit control overrides the voltage control to reduce the output current to the preset value.
Over-voltage protection is located on the Interface and Control/Display boards. If a fault occurs that result in the charger output going to an excessively high output voltage, a high voltage shutdown is initiated. The high voltage shutdown trips the input breaker via the input breaker’s shunt trip coil to turn the unit off. If the excessive high voltage condition persists, a second protection circuit, independent from the first, operates to trip the input breaker and to turn the triac on.
FIGURE 5-1 BLOCK DIAGRAM, TYPICAL MICRO ARE-M FLOAT CHARGER
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Circuit Description
5-2
The power rectifier converts the AC voltage from the transformer into a DC voltage. It consists of silicon diodes arranged in a half-wave circuit. The output of the rectifier is filtered and supplied to the battery and the load through the DC circuit breaker.
The front panel consists of a 2-line digital display, a 4-button keypad, and LEDs (On/Off and Alarm). The display and LEDs are mounted directly to the Control and Display Board. The keypad adheres to the metal front panel of the charger and is connected to the Control and Display Board by short ribbon cable.
Alarm connections for external annunciation of alarms are provided on the Interface Board. The standard board has three alarm relays and the multiple alarm board has nine alarm relays. All outputs are dry-contact form C relays.
Each relay has three connections: common, normally open, and normally closed. The normally open (NO) and normally closed (NC) labels are for an un-powered charger.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-1
WARNING
AVERTISSEMENT
WARNING
AVERTISSEMENT

6.0 MAINTENANCE

This chapter provides preventive maintenance procedures and troubleshooting procedures. Cabinet assembly drawings, schematics, and parts lists for all standard charger models are included in this chapter.
Refer to the replacement parts lists in Table 6-2 when ordering on-hand spare parts and service replacement parts.
Electrical shock hazard
Hazardous voltage can cause death or serious injury. Remove AC input power before servicing. Always use insulated tools. Disconnect battery string before servicing. Battery voltage is on the Interface Board whenever a battery string is connected.
Arcing hazard
Arcing can cause equipment damage, load interruptions, and personal injury. Remove watch and jewelry. Use insulated tools and extreme caution when working with a battery string. Disconnect the battery string before servicing. Carefully insulate unterminated battery cable ends. Discharge filter capacitors before servicing. See Figure 6-1.
Risque de choc électrique Les tensions dangereuses peuvent causer la mort ou
des blessures graves. Coupez l'alimentation de tous les fils et les bornes avant de travailler sur les équipements. Toujours utiliser des outils isolés. Débranchez la batterie avant l'entretien. La tension de la batterie se retrouve sur la carte d'interface quand la batterie est branchée.
Risque d'arc Un arc électrique peut causer des dommages sur les
équipements, des interru pti ons de charge, et des blessures. Retirez vos montres et bijoux utilisés des outils isolés et une prudence extrême lorsque vous travaillez avec des batteries. Débranchez la batterie avant l'entretien. Isoler les extrémités des câbles de batterie. Décharger les condensateurs avant l'entretien. Voir la figure 6-1.

VOLTAGE CHANGES 6.1

Input voltage settings on multiple input voltage units may be changed in the field. To changes the vol tag e, change the jumpers on the terminal blocks as indicated on the wirings diagram for the model. For models with a column for CB1 ratings with the jumper settings, the input circuit breaker, CB1, must be changed if the breaker rating does not match the breaker in the unit. It the model does not have a CB1 rating column, the circuit breaker does not need to be changed. The parts list will allow you to identify a needed circuit breaker. Circuit breakers may be ordered through your UNIPOWER representative. For assistance in finding your UNIPOWER representative, contact Customer Service. For technical assistance in making an input voltage setting change, contact Field Service.

PREVENTIVE 6.2

1. Ensure that a generous supply of cool, dry air is free to circulate through the charger. See Chapter 2
Installation.
2. Clean the equipment. Dust and dirt impeded heat dissipation. Blow out the charger with low-pressure dry
air to remove accumulated dust, dirt and any other contaminants.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-2
3. Check that all connections are clean and tight. Discoloration of terminals or wires is an indication of loose
or corroded connections.
4. Check capacitors (both AC and DC) for leakage, case or seal rupture, etc. All screw connections should be
checked and tightened as needed. DC capacitors over five years old or showing signs of degradation should be removed and checked for excessive leakage and/or replaced.
5. Check the float voltage, equalize voltage, and other configurable settings, using the front panel controls. See
Chapter 4 Setup and Operation.

TROUBLESHOOTING 6.3

Table 6-1 is a troubleshooting chart designed to help a qualified technician diagnose the cause of a charger malfunction. While troubleshooting, refer to the cabinet assembly drawing and the schematic diagram for the charger model at hand. These aids can be found in this chapter. Also provided is a section describing the testing of various electrical components.
For efficient troubleshooting, gather as much information as possible about the malfunction.
1. Read the front panel display and note charger output voltage and current
2. Note whether the front panel On/Off and Alarm LEDs are lighted
3. Note whether the AC or DC breaker trips
4. Measure the AC source voltage
5. Check AC, DC, and alarm wiring
6. Check configurable parameter values to be sure an unintended setup change is not interfering with
equipment operation
7. Note environmental conditions before and at the time of the malfunction (e.g. excessive ambient
temperature, water intrusion, excessive foreign material accumulated on heat sensitive components)
8. Review the equipment’s service history
After gathering data concerning the malfunction, scan the symptoms in the left column of the Troubleshooting Chart, Table 6-1. When the observed symptom is located, read across the table for a possible cause and solution.
The circuits and functions on the Control and Display board and the Interface boa r d are highly integ rated making it difficult to isolate a problem to one of these boards. Board replacement is recommended to repair a control or display related problem.

6.3.1 Service Access

For access to the Interface board, Control and Display board, AC and DC circuit breakers, and connection terminal blocks, loosen two captive screws and open the hinged front panel.
To replace a component inside the charger, such as the transformer or a filter capacitor, remove the top cover. Additional access is provided on 12" cabinets by removing the interface board panel.

6.3.2 Circuit Board Handling

Semiconductors such as ICs (integrated circuits), diodes, and transistors must be protected against damaging electrostatic discharge. A properly grounded wrist strap must be worn whenever a circuit board is handled or touched. A service kit with a wrist strap and static dissipative work mat is available from both mail order and local electronic supply companies.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-3
Always store circuit boards in anti-static bag s.

6.3.3 ARE-M Display Codes

Code Description
STARTING Displays anytime charger resets and starts walking up to the set point voltage
OPEN BREAKER DC breaker is open. Takes ≈1/4 - 1/2 amp to clear
MAXIMUM OUTPUT The charger’s control is delivering the maximum possible output power.
Over Curre nt The charger current output is above the current limit set point. This code could be
produced by a large load change, or a deeply discharged battery.
Current Limit The charger is holding the output current at the current limit set point and the voltage is
below the output voltage set point. This code could be produced by a large load current, or deeply discharged batteries.
Ending Current Limit The charger is current limi ting, but increasing the outp ut voltage to get to the float
voltage set po int.
CANNOT REGULATE The output voltage is above the chargers voltage set point . The charger is t rying to
regulate the voltage output, but does not sense the output voltage drop. Parallel chargers w/o proportional load sharing could cause this code.
EQ Current Limit When the charger is changing from float to equalize, the increase in voltage is causing
the charger to go into current limit. The charger will slowly increase voltage as the load current (typically batteries) decreases.
OC-Cancel Equalize Equalization has caused the charger’s output to exceed the current limit set point. The
charger will attempt to decrease the output voltage to lower the output current. If the charger is unsuccessful, the charger will terminate the equalization mode and return to float. This can be caused by a step load change while in equalization mode
Remote Equalize The charger’s external e qualization input is shorted, so the charger is in Equalization
mode.
HIGH VOLTAGE SHUTDOWN The charger voltage sense was above the High Voltage Shutdown set point. The
charger went into a high voltage shutdown mode to protect the load(s).
SEL to Reset The charger can be reset from a High Voltage Shutdown mode from the keypad by
pressing the SEL button. I f the interfa ce b o ar d has triggered an HVSD, generated by the interface board, the wiring harness connected to J5 on the interface board may have to be removed for 5 seconds then replaced to clear the fault.
AC Fail No AC line input to the charger is currently being detected.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-4
Symptom
Possible Cause (s)
Solution(s)
A. AC breaker trips
1. Short circuit in AC power circuit.
Inspect primary wiring for possible shorts or grounded connections.
2. Input connected for lower voltage.
a. Check position of jumpers. b. Measure input voltage.
3. High voltage shutdown o perating.
Remove load and check for high voltage.
4. Input voltage outside ANS I range.
Measure input voltage.
5. Frequency of supply less than 57 Hz.
Check input frequency.
6. Short in transformer winding.
Visually inspect power transformer primary coils for sig ns of overheating.
B. No DC output.
1. AC power outage.
Check for AC voltage on both sides of
2. Short circuit in DC power circuit.
a. Inspect secondary power wiring
capacitors.
3. Open circuit.
Check all wiring for open or loose
C. Low DC output voltage.
1. Short in resonant circuit.
a. Check triac. c. Check resonant circuit wiri ng.
2. Open sensing leads.
Check wiring fo r co ntin ui t y.
3. Unit in current limit.
Adjust current limit setting.
4. Component failure in interface
Replace interface board.
5. Component failure in control board.
Replace control board.
6. Defective ribbon cable.
Replace ribbon cable.
7. Out of adjustment.
Adjust float voltage.
D. High DC output voltage.
1. Open triac in resonant circuit.
Check triac.
2. Open sensing leads.
Check for D C voltage across Control Board Pins J5-3and J5-6
3. Interface board failure.
Replace interface board.
4. Control board failure.
Replace control board.
E. DC breaker trips.
1. Battery connection reversed.
Check polarity of battery connections.
2. Short circuit in DC power circuit.
a. Inspect secondary power wiring
TABLE 6-1 TROUBLESHOOTING CHART
Consult connection diagram.
the breaker.
and terminals for shorts or grounded connections.
b. Check power charger diodes. c. Check for shor ted DC filter
Check voltage at DC output terminals with a portable meter.
connections.
b. Check resonant capacitor.
board.
and terminals fo r possible shorts or grounded connections.
b. Check power charger diodes and
DC filter capacitors.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-5
Symptom
Possible Cause (s)
Solution(s)
F. Excessive output curre nt.
No current limit.
a. Current limit control improperly
to interface board.
G. Excessive electrical noise or
1. Loose filter connections.
Check wiri ng and bus bars for loose or corroded connections.
2. Open filter capacitor.
Check filter capacitors.
3. Open power diode.
Check power diodes.
4. DC cable routing (excessive noise).
Check broken cable ties.
5. Improperly sized battery.
Check batte ry rating.
6. Preload resistors ON with unit OFF.
Replace Interface board.
H. Oscillations or poor regulatio n.
1. Loose connection.
Inspect circuit boards, connectors, and wiring for loose contacts.
2. Defective triac.
Replace triac.
3. Component failure in Co ntrol and Display board.
Replace Control and Display board.
4. Open power diode.
Check power diodes. Replace as required.
5. Resonant capacitor not grounded.
Check AC capacitor case to ground with ohmmeter.
I. Low output current.
1. Loose connection.
Inspect wiring.
2. Open power diode.
Check power charger diodes. Replace as required.
3. Unit in current limit.
a. Current limit control improperly
board. Replace.
J. Acoustic noise.
1. Loose laminations.
Check air gap areas of power
insulated screwdriver.
2. Cabinet vibration.
Check welds and bolted joints.
K. No 2-line digital display or
1. Control and Display board
Replace part
2. Interface board
Replace part
3. Ribbon cable
Replace part
L. Configur ation (setup) not saved.
Control Board
Replace part
set.
b. Component failure in Control or
Interface board. Replace.
c. Check c onnections from shunt
ripple.
Check with portable meter.
keypad activity. DC output OK.
set.
b. Defecti ve Control and Display
transformer and control reactor with
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-6
CAUTION
ATTENTION
ouverts.
CAUTION – For Service Only: AC and DC breakers
ATTENTION - Pour l’entretien seulement: Les
d’appuyer sur le bouton.
Capacitor Discharge:

CHECKING COMPONENTS 6.4

This section describes methods that can be employed to determine whether a component has failed. A failed component must be replaced with a UNIPOWER approved part. See Table 6-2 Parts List, for component descriptions and UNIPOWER part numbers.
Do Not press this button if either circuit breaker is On
Before performing any of the following tests:
1. Disconnect both the AC power and battery power by switching both circuit breakers off. Note that
battery power will still be supplied to CB2, the DC circuit breaker, and to the Control and Display board and Interface board.
2. Press the Capacitor Discharge button located behind the front panel (door) to discharge filter and
resonant capacitors, if required. See Figure 6-1 for a typical location of the button.
must be open before pressing button.
Press button for 60 seconds.
See the Cabinet Assembly drawings for button location in other models.
Ne pas appuyer sur ce bouton si les disjoncteurs sont
disjoncteurs AC et DC doivent être ouverts avant
FIGURE 6-1 Capacitor Discharge Button
Diodes - First, remove at least one connection to the diode, and then check using an analog ohmmeter to
measure resistance, first cathode to anode and then anode to cathode. A good diode will show low resistance one direction and very high resistance the other direction. A shorted diode will show no or very low resistance both ways. An open diode will show a very high resistance both ways. Suggested scales for these checks are either X10 or X100.
Alternatively, a digital meter with a “diode check” function can be used to test a diode.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-7
Capacitors - First, isolate capacitors and then check with an ohmmeter. Proper scale range will vary as to type of meter and capacitor size. Start with highest range and work down. Reverse leads each time. If the capacitor is good, it will show a deflection towards zero resistance initially, then a steady increase toward infinite resistance. If, however, the capacitor is shorted, it will show zero resistance. If the capacitor is open, it will read infinite resistance.
Resonant Triac - Remove either the MT1 or MT2 triac connection, being careful not to remove gate wire, and check with an ohmmeter. See the drawing below for triac terminals. A good triac will indicate high resistance in both directions.
To check for turn on of the triac, with one lead still disconnected, connect the positive lead of an analog ohmmeter to the anode of the triac (MT2) and the negative lead to the cathode (MT1). The triac should read open or high resistance. Connect the gate to the anode with a jumper. A low resistance reading indicates that the triac is turning on.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-8

12" CABINET ASSEMBLY AND SCHEMATICS 6.5

Note: See Table 6-2 Parts Lists for reference designators and part numbers.
FIGURE 6-2 12" Cabinet Assembly
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-9
FIGURE 6-3 12" Cabinet Schematic; ARE-M02406, 120/208/240
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-10
FIGURE 6-4 12" Cabinet Schematic; ARE-M02412, 120/208/240
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-11
FIGURE 6-5 12" Cabinet Schematic, ARE-M02425, 120/208/240
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-12

24" CABINET ASSEMBLY AND SCHEMATICS 6.6

Note: See Table 6-2 Parts Lists for reference designators and part numbers.
FIGURE 6-6 24" Cabinet Assembly
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-13
FIGURE 6-7 24" Cabinet Schematic; ARE-M02450, 120/208/240
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-14
FIGURE 6-8 24" Cabinet Schematic; ARE-M02450, 480
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-15
FIGURE 6-9 24" Cabinet Schematic; ARE-M024100, 120/208/240
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-16
FIGURE 6-10 24" Cabinet Schematic; ARE-M024100, 480
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-17
Model ARE-M02406 ARE-M02412 ARE-M02425
Voltage 120/208/240 120/208/240 120/208/240
Base Unit 102.1041.00A 102.1042.00A 102.1043.00A
Designator Description 12" Cabinet 12" Cabinet 12" Cabinet
A1 (Utility) Interface PCB 306.3078.24 306.3078.24 306.3078.24 A1 (Ut) (OPT) Interface PCB w/RELAY S 306.3078.24M 306.3078.24M 306.3078.24M A1 (Ut) (OPT) Interface PCB w/GND SWT 306.3078.24G 306.3078.24G 306.3078.24G A1 (Ut) (OPT)
I nterface PCB w/RELAYS&GND SWT
306.3078.24MG 306.3078.24MG 306.3078.24MG A1 (Telecom) Interface PCB 306.3078.24T 306.3078.24T 306.3078.24T A1 (Tel)(OPT) Interface PCB 306.3078.24TM 306.3078.24TM 306.3078.24TM A2 (STD) Control/Display w/o lights N/A N/A N/A A2 (Utility) Control/Display w/lights 306.3077.20 306.3077.20 306.3077.20 A2 (Telecom) Control/Display w/lights 306.3077.10 306.3077.10 306.3077.10 A3 (OPT) DNP3 Communications 385.8335.00 385.8335.00 385.8335.00 C1 Cap, Filter input 450.1350.00 450.1350.00 450.1350.00 C2 Cap, Filter output 450.0860.00 450.1350.00 450.1350.00 C3 Cap, Resonant JC00226 JC00062 JC00062 CB1 Circuit Breaker, 120 input 272.0320.00 JR00751 JR00753 CB1 Circuit Breaker, 208 input 272.0320.00 JR00751 JR00753 CB1 Circuit Breaker, 240 input 272.0320.00 JR00751 JR00753 CB1 Circuit Breaker, 480 input N/A N/A N/A CB1 (Hi Cap) Circuit Breaker, 120 input 272.0117.05 272.0117.10 272.0117.15 CB1 (Hi Cap) Circuit Breaker, 208 input 272.0117.05 272.0117.10 272.0117.15 CB1 (Hi Cap) Circuit Breaker, 240 input 272.0117.05 272.0117.10 272.0117.15 CB1 (Hi Cap) Circuit Breaker, 480 input N/A N/A N/A CB2-2 Pole (Std) Ckt Bkr, output, 2 P Utility JR00209 JR00208 272.0119.35 CB2-2 Pole (Opt) Ckt Bkr, outpu t, 2 P Utility 272.0113.10 272.0113.20 JR00798 CB2-1 Pole (Std) Ckt Bkr, output, 1 Pole Tel N/A N/A N/A CB2-1 Pole (Std) Ckt Bkr, output, 1 Pole Tel 271.0900.10 JR00754 JR00755 CR1 Diode Module JS00485 JS00485 JS00485 CR2 (OPT) Blocking Diode JS00485 JS00485 576.0500.00 E1 (OPT) Lightning Arrester JS00885 JS00885 JS00885 F1,F2,F3,F4 Fuse, Control Wiring Protection Kit 385.1040.00 385.1040.00 385.1040.00 K1 Relay, Hi-Cap AC Breaker only 245.4000.30 245.4000.30 245.4000.30 L1 Reactor, Resonant 141.3501.00 141.3510.00 141.3511.00 L2 Choke, Filter 141.3401.00 141.3401.00 141.3406.00 Q1 Triac JS00826 JS00826 JS00826 R1 Shunt 50mV JM00247 JM00247 JM00248 R2 Resistor, Cap Discharge 680.0450.00 685.0090.00 685.0090.00 R5,6,7 Resistor, DC Load N/A N/A N/A S1 Switch, M embrane 225.4550.00 225.4550.00 225.4550.00 S2 Switch, Cap Discharge JL00038 JL00038 JL00038 S3 (Opt) Switch, Ground Enable (GNDSW) 240.4130.00 240.4130.00 240.4130.00 T1 Transformer, Power 147.4010.00 147.4011.00 147.4012.00 TB1 Terminal Block JL00230 JL00230 JL00918 TB2 Terminal Block N/A N/A N/A TB3 Terminal Block N/A N/A N/A TB4 Terminal Block N/A N/A N/A TC1 (OPT) Thermosensor 385.5627.11 385.5627.11 385.5627.11 Z1 Surge Suppression, CR1 307.2723.01 307.2723.02 307.2723.01

PARTS LIST 6.7

This section contains the parts list for each standard charger model.
TABLE 6-2 12" CABINET REPLACEMENT PARTS LIST; 24 VDC MODELS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-18
Model ARE-M02450 ARE-M02450 ARE-M024100 ARE-M024100
Voltage 120/208/240 480 120/208/240 480
Base Unit 102.1044.00A 102.1071.00A 102.1045.00A 102.1072.00A
Designator Description 24" Cabinet 24" Cabinet 24" Cabinet 24" Cabinet
A1 (Utility) Interface PCB 306.3078.24 306.3078.24 306.3078.24 306.3078.24 A1 (Ut) (OPT) Interface PCB 306.3078.24M 306.3078.24M 306.3078.24M 306.3078.24M A1 (Ut) (OPT) Interface PCB w/GND SWT 306.3078.24G 306.3078.24G 306.3078.24G 306.3078.24G A1 (Ut) (OPT)
Interface PCB w/RELAYS&GND SWT
306.3078.24MG 306.3078.24MG 306.3078.24MG 306.3078.24MG A1 (Telecom) Interface PCB 306.3078.24T 306.3078.24T 306.3078.24T 306.3078.24T A1 (T el)(OPT) I nterface PCB 306.3078.24TM 306.3078.24TM 306.3078.24TM 306.3078.24TM A2 (ST D) Control/Display w/o lights N/A N/A N/A N/A A2 (Utility) Control/Display w/lights 306.3077.20 306.3077.20 306.3077.20 306.3077.20 A2 (Telecom) Control/Display w/lights 306.3077.10 306.3077.10 306.3077.10 306.3077.10 A3 (OPT) DNP3 Communications 385.8335.00 385.8335.00 385.8335.00 385.8335.00 C1 Cap, Filter input 450.1650.00 450.1650.00 450.1650.00 450.1650.00 C2 Cap, Filter output 450.1650.00 450.1650.00 450.1650.00 450.1650.00 C3 Cap, Resonant JC00061 JC00061 JC00117 (2) JC00117 (2) CB1 Circuit Breaker, 120 input 272.0320.25 N/A JR00556 N/A CB1 Circuit Breaker, 208 input JR00753 N/A JR00721 N/A CB1 Circuit Breaker, 240 input JR00753 N/A 272.0320.25 N/A CB1 Circuit Breaker, 480 input N/A JR00761 N/A 272.0112.15 CB1 (Hi Cap) Circuit Breaker, 120 input 272.0116.25 N/A 272.0116.50 N/A CB1 (Hi Cap) Circuit Breaker, 208 input 272.0116.15 N/A 272.0116.30 N/A CB1 (Hi Cap) Circuit Breaker, 240 input 272.0116.15 N/A 272.0116.25 N/A CB1 (Hi Cap) Circuit Breaker, 480 input N/A 272.0118.15 N/A 272.0118.15 CB2-2 Pole (Std) Ckt Bkr, output, 2P U ti l i ty JR00223 JR00223 JR00801 JR00801 CB2-2 Pole (Opt) Ckt Bkr, output, 2P Uti l i ty JR00800 JR00800 JR00801 JR00801 CB2-1 Pole (Std) Ckt Bkr, output, 1 Pole Tel N/A N/A N/A N/A CB2-1 Pole (Std) Ckt Bkr, output, 1 Pole Tel JR00709 JR00709 JR00812 JR00812 CR1 Diode M odule JS00878 JS00878 JS00548 JS00548 CR2 (OPT) Blocking Diode 576.0500.00 576.0500.00 JS00548 JS00548 E1 (OPT) Lightning Arrester JS00885 594.2041.00 JS00885 594.2041.00 F1,F2,F3,F4 Fuse, Control Wiring Protection Kit 385.1040.00 385.1040.00 385.1040.00 385.1040.00 K1 Relay, Hi-Cap AC Breaker only 245.4000.30 245.4000.30 245.4000.30 245.4000.30 L1 Reactor, Resonant 141.3512.00 141.3512.00 141.3513.00 141.3513.00 L2 Choke, Filter 141.3407.00 141.3407.00 141.3408.00 141.3408.00 Q1 Triac JS00826 JS00826 JS00826 JS00826 R1 Shunt 50mV JM00249 JM00249 JM00250 JM00250 R2 Resistor, Cap Discharge 680.0450.00 680.0450.00 680.0450.00 680.0450.00 R5,6,7 Resistor, DC Load 685.0090.00 685.0090.00 685.0090.00 685.0090.00 S1 Switch, Membrane 225.4550.00 225.4550.00 225.4550.00 225.4550.00 S2 Switch, Cap Discharge JL00038 JL00038 JL00038 JL00038 S3 (Opt) Switch, Ground Enable (GN DSW) 240.4130.00 240.4130.00 240.4130.00 240.4130.00 T1 Transformer, Power 147.4013.00 147.4030.00 147.4014.00 147.4031.00 TB1 Terminal Block JL00140 JL00140 JL00140 JL00140 TB2 Terminal Block JL00898 JL00898 JL00898 JL00898 TB3 Terminal Block N/A N/A N/A N/A TB4 Terminal Block N/A N/A N/A N/A TC1 (OPT) Thermosensor 385.5627.11 385.5627.11 385.5627.11 385.5627.11 Z1 Surge Suppression, CR1 307.2723.08 307.2723.08 307.2723.12 307.2723.12 Z2, Z3 (OPT) DC OutputMOVs JA03079-150V JA03079-150V JA03079-150V JA03079-150V
12” Cabinet Replacement Parts List; 24VDC Models, Continued…
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-19
SW1
SW2
Position
Function
Position
Function
0
30 Amperes
0
Not Valid
1
3 Amperes
1
12 Volts
2
6 Amperes
2
24 Volts
3
12 Amperes
3
48 Volts
4
16 Amperes
4
130 Volts
5
25 Amperes
5
260 Volts
6
35 Amperes
6
Not Valid
7
50 Amperes
7
Not Valid
8
75 Amperes
8
Not Valid
9
100 Amperes
9
Not Valid

INTERFACE BOARD 6.8

This section provides Interface Board troubleshooting and replacement information. The Interface Board can be replaced in the field. There are no user-serviceable parts on the board. The board is shown in Figure 6-11. Use caution when servicing or replacing the board since battery voltage is present on the board whenever the battery string is connected to the charger.
The board is available in a number of versions. A Standard Board (A1), an optional Multiple Alarm Board (A1 OPT), and a switchable ground detection is available. (A Standard Board has 3 alarm outputs while the optional Multiple Alarm Board has 9 alarm outputs.) To order a replacement board, refer to Table 6-2 Parts Lists for the Interface Board part number for the charger model at hand.

6.8.1 Board Interchangeability

The Interface Board part number suffix (e.g. 306-3078-24) specifies the compatible charger DC output voltage, 24V in the preceding example. Suffix letters indicate options like multiple alarm relays or switchable ground detection. Install the board in any charger rated for that output voltage, regardless of current output rating. When replacing an Interface Board, set the miniature rotary switch SW1 to the current rating of the charger into which the board will be installed. See Table 6-3.
IMPORTANT: DO NOT change the setting of SW2. It is factory set. If inadvertently changed, set SW2 to the board part number suffix at the “position” shown in Table 6-3. SW2 may not be on all boards.
TABLE 6-3 INTERFACE BOARD SWITCH SETTINGS
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-20

6.8.2 Troubleshooting

1. If the charger is not working properly, there are test points on the Interface Board that can help locate the
problem. TP1 is board common and is used for all other test point voltage measurements. TP2, TP3, and TP4 are the DC-DC power supply outputs. All voltages must be within tolerance for the board to work properly. The board should be replaced is a voltage is incorrect.
TP1 to TP2 should read +120.5Vdc. TP1 to TP3 should read -12 TP1 to TP4 should read +5
0.5Vdc.
0.25Vdc.
2. If the power supply is working correctly the following test points can be measured.
TP1 to TP6 should read between 0 and 3-4 volts depending on charger load.
0V = no load 3-4V = rated output of charger
TP1 to TP7 depends upon the output voltage of the charger.
48V charger: approximately 1.2V TP1 to TP8 should be about the same as TP1 to TP7 (assuming the DC breaker is closed). TP1 to TP9 should be about 2V if there is no ground short. TP1 to TP10 should be about –5V if there is no load share.
3. Check the settings of rotary switches SW1 and SW2.
SW1 is set for the DC current output rating of the charger. SW2 is set for the DC voltage output rating of the charger. (SW2 may not be on all boards)
After the switches are changed, the control must be reset by disconnecting and reconnecting the ribbon cable. (See sections 6.8.1 and 6.9)

6.8.3 Replacing the Interface Board

Use caution when servicing or replacing the board since battery voltage is present on the board whenever the battery string is connected to the charger.
1. Refer to Chapter 4 Setup and Operation and turn off the charger.
2. Loosen the two quarter-turn captive fasteners and open the front panel.
3. At TB1, label each of the removable plugs with the alarm name printed on the circuit board. Pull each plug
up and out of its mating connector.
4. Disconnect the battery temperature sensor from terminal block J2, if present.
5. Disconnect the cabled connectors from the board.
6. Remove the screws securing the board and remove the board. Note the settings of switches SW1 and SW2.
7. On the replacement board, check the settings of SW1 and SW2. See Table 6-5 for proper settings.
8. Fasten the board to the charger using the screws removed above.
9. Install the cabled connectors, alarm plugs, and battery temperature wiring.
10. Turn on the charger and test its operation and setup.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-21
CONTROL BOARD
CHARGER
CHARGER
CHARGER P2
SW1 & SW2
EXTERNAL (OPTIONAL)
BLUE
RED
BLACK
TEMPERATURE PROBE CONNECTOR
CONNECTOR (4 PIN)
TEMPERATURE PROBE
CONNECTOR (3 PIN)
CONNECTOR (17 PIN)
CONNECTOR (40 PIN)
FIGURE 6-11 COMPONENT LOCATIONS, INTERFACE BOARD
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-22
2-Line LCD Display
AC
Alarm LED

6.9 CONTROL AND DISPLAY BOARD

Figure 6-12 shows the Control and Display Board. There are no user-serviceable parts on the board. Board substitution is recommended when troubleshooting.
On/Off
LED
FIGURE 6-12 CONTROL AND DISPLAY BOARD

6.9.1 Replacing the Board

Use caution when servicing or replacing the board since battery voltage is present on the board whenever the battery string is connected to the charger.
1. Refer to Chapter 4 Setup and Operation and turn off the charger.
2. Loosen the two quarter-turn captive fasteners and open the front panel. The board is located on the rear of
the front panel.
3. Disconnect the large ribbon cable to the Interface board. Disconnect the smaller ribbon cable to the keypad.
4. Remove the screws securing the board and remove the board.
5. Fasten the board to the rear of the front panel using the screws removed above.
6. Install the ribbon cables disconnected above.
7. Turn on the charger and test its operation and setup.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Maintenance
6-23

6.10 KEYPAD

The front panel 4-button keypad can be replaced. Be sure a replacement part is on hand before beginning the following procedure.
IMPORTANT: Carefully align the replacement keypad with the 2-line LCD display and LEDs before allowing the keypad to contact the front panel. The replacement keypad cannot be repositioned once its adhesive back has contacted the front panel surface.
Minor misalignment will not affect front panel use. A larger misalignment may interfere with reading the 2 -line display and LEDs.
To replace the keypad:
1. Disconnect the keypad ribbon cable from the Control and Display Board.
2. Carefully lift a corner of the failed keypad and peel the keypad from the front panel. (Note: The hole that
the ribbon cable went through.) Remove any adhesive residue with denatured alcohol or other compatible solvent.
3. Check the alignment of the replacement keypad with the 2-line LCD display and LEDs. Masking tape can
be used to mark the exact location of one edge of the keypad. Achieve vertical and horizontal alignment before proceeding. See the IMPORTANT note above.
4. Peel the protective backing from the replacement keypad.
5. Place the ribbon cable through the hole identified in step 2.
6. Without allowing the keypad to touch the front panel, carefully align the keypad with your alignment
indicators and the 2-line LCD display and LEDs. When aligned, press the keypad against the front panel.
7. Gently press all areas of the keypad against the front panel using only your hand. Be sure the four corners
and four edges have adhered to the front panel.
PM990-1070-24, Issue 12
Micro ARE-M S eries 24V Chargers, Single P hase Options and Accessories
7-1

7.0 OPTIONS AND ACCESSORIES

This chapter contains details about the options and accessories currently available for the charger.

Lightning Arrester 7.1

A surge suppression device connected across the AC service to ground prevents high-energy transients from damaging the equipment.
FIGURE 7-1 LIGHTNING ARRESTER; 120, 208, 240 AND 480 VAC CONNECTIONS
PM990-1070-24, Issue 12
Micro ARE Series 24V Chargers, Single Phase Options and Accessories
7-2
6A through 12A rated Systems
25A through 50A rated Systems

Blocking Diode 7.2

A silicon diode inserted into the negative DC output prevents the flow of reverse current from the battery when the equipment is DC-energized preventing additional battery drain.
For systems with blocking diodes, the Float and Equalize voltage shoudl be set about 0.7 volts above the desired battery voltage to compensate for the diode voltage drop. This offset should be adjusted to obtain the desired output voltage for each installation.
Note: Current drain without the blocking diode is typically less than 100 mA
.
100A rated System
Note: Existing wire for NEG output of DC breaker to NEG DC output terminal is removed and replaced
with blocking diode and 2 wires.
FIGURE 7-2 BLOCKING DIODE ADD ALTERNATIVE
PM990-1070-24, Issue 12
Micro ARE Series 24V Chargers, Single Phase Options and Accessories
7-3

Output MOVs 7.3

The output MOVs protect the charger from externally created voltage transients. The MOVs are connected from each output pole of the charger to the cabinet (earth). If an excessive transient enters the unit on the output cables, the MOVs clamp the voltage to an acceptable level. Repetitive clamping of transients and clamping high energy transients will degrade the MOVs requiring eventual replacement.

Drip Shield 7.4

The drip shield is intended to prevent water from dripping into the unit from the overhead structure indoors. When used, nothing should be set on the perforated top screen of the charger or the drip shield. Placing anything on the top screen may create a fire hazard. When the drip shield is used, personnel should avoid contact with the perforated top screen.

Temperature Sensor 7.5

The temperature sensor is connected to J2 on the interface board as shown in Figure 2-6 and described in Section 2.4.7. This is required for battery temperature compensation and to annunciate a high battery temperature alarm.

Ground Detection Switch 7.6

The Ground Detection Switch is a factory-installed option that allows the operator to easily disable the ground detection by breaking the internal connection from the internal detection system and ground. Breaking the internal ground connection is useful for troubleshooting ground paths on the dc system or eliminating interactions with other ground detection equipment on the system.
Unless other ground detection is in use on the DC system, the ground detection switch should be left in the ON position.

DNP3 Communications 7.7

This allows the charger to be controlled and monitored from a remote location over a 10/100Mbit Ethernet network connection using the popular DNP3 protocol. More information about this protocol can be found at http://www.dnp.org. The DNP3 device profile (PM990.1072.00) and installation guide (PM990.1074.00) can be found on UNIPOWER’s web site at http://www.unipowerco.com.

High interrupt AC breakers 7.8

This option gives the charger an enhanced AC line current interrupting rating of at least 10,000 Amps.