3900 Coral Ridge Drive
Coral Springs, FL 33065
Phone: +1- 954-346-2442
Toll Free: 1-800-440-3504
Web site – http://www.unipowerco.com
SAGEON VIGIL PRODUCT MANUAL
GENERAL
Please Note: For your protection, the following information and the product manual
should be read and thoroughly understood before unpacking, installing, or using the
equipment.
UNIPOWER, LLC presents all equipment to the delivering carrier securely packed and in
perfect condition. Upon acceptance of the package from us, the delivering carrier
assumed responsibility for its safe arrival to you. Once you receive the equipment, it is
your responsibility to docu ment any damage the carrier may have inflicted, and to file
your claim promptly and accurately.
1. PACKAGEINSPECTION
1.1 Examine the shipping crate or carton for any visible damage: punctures, dents, and any other
signs of possible internal damage.
1.2 Describe any damage or shortage on the receiving documents, and have the carrier sign their full
name.
1.3 If your receiving freight b ill notes that a Tip-N-Tell is atta ched to your freight, locate it. If th e
Tip-N-Tell arrow has turned even partially blue, this means the freight has been tipped in
transport. Make sure the carrier notes this on your receipt before you sign for the freight.
2. EQUIPMENTINSPECTION
2.1 Within fifteen days, open the crate and inspect the contents for damages. While unpacking, be
careful not to discard any equipment, parts, or manuals. If any damage is detected, call the
delivering carrier to determine appropriate action. They may require an inspection.
*SAVE ALL SHIP PING MATERIAL FOR THE INSPECTOR TO SEE!
2.2 After the inspection has been made, call UNIPOWER. We will determine if the equipment should
be returned to our plant for repair, or if some other method would be more expeditious. If it is
determined that the equipment should be returned to UNIPOWER, ask the delivering carrier to
send the packages back to UNIPOWER at the delivering carrier's expense.
2.3If repair is necessary, we will invoice you for the rep a ir so that you may submit the bill to the
delivering carrier with your claim form.
2.4It is your responsibility to file a clai m with the delivering carr ier. Failure to proper ly file a claim
for shipping damages may void warranty service for any physical damages later reported for
repair.
3. HANDLING
Equipment c an be univer sally he avy or top-hea vy. Use adeq uate huma npo wer or eq uipment for hand ling.
Until the equipment is securely mounted, be careful to prevent the equipment from being accidentally
tipped over.
RECEIVING
INSTRUCTIONS
&
EQUIPMENTINFORMATION
PM990-3002-00, Issue 3 i
SAGEON VIGIL PRODUCT MANUAL
4. NAMEPLATE
Each piece of UNIPOWER equipment is identified by a part number on the nameplate. Please refer to this
number in all correspondence with UNIPOWER.
5. INITIALSETTINGS
All equipment is shipped from our production area fully checked and adjusted. Do not make any
adjustments until you have referred to the technical reference or product manual.
6. SPAREPARTS
To minimize downtime during installation or operation, we suggest you purchase spare fuses, circuit boards
and other recommended components as listed on the Recommended Spare Parts List in the back of the
product manual. If not hing else, we strongly recommend s tocking spare fuses for all systems.
PM990-3002-00, Issue 3 ii
SAGEON VIGIL PRODUCT MANUAL
ISSUE
PAGE (S)
ALTERED
DESCRIPTION OF CHANGE
Issued By
/DATE
3
All
Update UNIPOWER logo & contact information. See PCO#
44433.
WD
6/16/17
ISSUE HISTORY
DOCUMENT SUMMARY
This document explains the installation, operational, maintenance and troubleshooting methods for the
UNIPOWER, LLC SAGEON VIGIL Monitor/Controller.
PROPRIETARY AND CONFIDENTIAL
The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of the
manual or any portion of the manual without the written permission of UNIPOWER, LLC is prohibited.
Data, descriptions, and specifications presented herein are subject to revision by UNIPOWER, LLC without
notice. While such information is believed to be accurate as indicated herein, UNIPOWER, LLC makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its
control, UNIPOWER, LLC hereby disclaims and excludes all warranties, express, implied, or statutory, including
any warranty of merchantability, any warranty of fitness for a particular purpose, and any implied warranties
otherwise arising from course of dealing or usage of trade. The user is solely responsible for determining the
suitability of the product(s) featured herein for user’s intended purpose and in user’s specific application.
Throughout the remainder of this manual, “UNIPOWER” will mean “UNIPOWER, LLC.”
PERSONNEL REQUIREMENTS
Installation, setup, operation, and servicing of this equipment should be performed by qualified persons
thoroughly familiar with this Product Manual and Applicable Local and National Codes. A copy of this manual is
included with the equipment shipment.
power distribution rack
Power Systems Monitor & Controller
RBOC
Regional Bell Operating Company
RFA
rectifier failure alarm
VLVA
very low voltage alarm
Vdc
UBC
volts direct current
Uniform Building Code
TABLE OF ABBREVIATIONS
NEMA
NEC
UL
PM990-3002-00, Issue 3 vi
National Electrical Manufacturers Association
National Electric Code
Underwriters Laboratory
SAGEON VIGIL PRODUCT MANUAL
NUMBER
ANSI C 39.1
Requirements for Electrical Analog Indicating Instruments
ANSI T1.311-1991
DC Power Systems – Telecommunications Environment Protection
1980
ANSI
Measurement and Control Equipment. October 1987
NEC 1993
NEC Handbook 1993, National Fire Protection Association
No Number
OI-28 Standards
No Number
Central Office Telecommunications Equipment Engineering
Standards. December 1984
PUB 77350
U S West Telecommunications Equipment Installation & Removal
Guidelines. June 1990
PE-7-1985
Communications Type Battery Chargers, NEMA/ANSI
STD 487-1980
IEEE Guide For The Protection of Wire-Line Communications
Facilities Serving Electrical Power Stations
TR-EOP-000151
Bellcore Generic Requirements for 24-, 48-, 130-, & 140-Volt
Central Office Power Plant Rectifiers. May 1985
TR-EOP-000154
Bellcore Generic Requirements for 24-, 48-, 130-, & 140-Volt
Central Office Power Plant Control and Distribution. May 1985
Requirements. Issue 4, July 1991
Telecommunication Products and Equipment
TABLE OF REFERENCES
DOCUMENT
ANSI/IEEE C 62.41-
IEC 801-2
TITLE
IEEE Guide for Surge Voltages in Low-Voltage AC Power Circuits,
IEC Electromagnetic Compatibility for Industrial-Process
TR-NWT-000063
TR-TSY-000078
Bellcore Network Equipment-Building System Generic Equipment
Bellcore Generic Physical Design Requirements for
PM990-3002-00, Issue 3 vii
SAGEON VIGIL PRODUCT MANUAL
1 INTRODUCTION
1.1 General Description
1.2 Features
1.3 Specifications
1.1 GENERAL DESCRIPTION
The SAGEON VIGIL is a microprocessor based, single rack space float current battery monitor for
telecommunications applications. The SAGEON VIGIL was designed to be a compact and easy way to
monitor the status of your batteries. It was designed to be used in conjunction with the UNIPOWER Float
Charging Current Probes (FCCP) to monitor the float current of your batteries. The SAGEON VIGIL has
many features (a number of which are specific to power plant monitoring and are not typically used in a
battery monitoring application) which are outlined below:
The SAGEON VIGIL can be used to monitor:
• Battery voltage
• Up to 10 Battery float currents (used in conjunction with the FCCP current probe)
• Temperature: Ambient and two battery strings
When used with the CELL MONITORING EXPANSION, the VIGIL can additionally monitor:
• 48 battery cells (2V nominal cell)
• 4 additional temperatures
• 4 “standard” current transducers
The SAGEON VIGIL has the following alarm and control output relays related to battery monitoring (all
relay contacts rated 60W / 62.5VA):
• Dual Form C contacts for Major and Minor alarms
• Single Form C contacts for the following alarms:
- High volt a ge (HVA)
- Very Low Voltage (VLVA)
- Low Voltage (LVA)
- Fuse alarm (FA)
- High/low current Watchdog alarm (CUR/WD)
- Temperature alarm (TEMP )
- Auxiliary relay (AUX) (user defined)
•Single Form A contacts for the following control functions:
- High volt a ge shutdown (HVSD)
• Front panel LED’s that visually indicate alarm & control status
• Built-in audible alarm
1.2 FEATURES
• Compact single rack space design
• Simple four key access to status, system configuration, calibration, and control functions
• Alphanumeric display: shows measurement data and programming information
PM990-3002-00, Issue 3 1-1
SAGEON VIGIL PRODUCT MANUAL
Shipping and handling
Shipped in a padded box when ordered as a
Humidity
0 to 95 %, non-condensing
• Front panel LED alarm indicators: (Red) MAJOR, FA, VLVA, LVD, HVSD, CUR/WD, RFA, & TA;
(Yellow) MINOR, LVA, CEMF, HVA, ACO, EQ, CTRL-INH, and (Green) Power
• Audible alarm with a user selectable trigger point and cut-out durations
• One “Auxiliary” output relay (user definable ) (over-current)
• User access may be password protected
• Built-in test & calibration modes
• Front panel test points for manual verification of test & calibration data
• Screw terminals for easy connection of users inputs & outputs
1.3 SPECIFICATIONS
1.3.1 Physical Specifications
VIGIL
Width: 19” or 23” (23” with centering brackets)
Height: 1.75” (1U or 1RU)
Depth: 11.0”
Weight: 10.0 lbs.
Cell Monitoring Expansion
Width: 23”
Height: 1.75” (1U or 1RU)
Depth: 9.0”
Weight: 10.0 lbs.
1.3.2 Environmental Specifications (each, VIGIL and Expansion)
Operating temperature
Storage temperature
0°C to +50°C (+32°F to +122°F)
-40°C to +85°C (-40°F to +185°F)
separate item, or installed in rack and prewired to the plant when ordered as part of a
custom power plant
Altitude
Heat dissipation
10,000 feet (3,048 meters)
~150 BTU/hour maximum
Cooling
Seismic
PM990-3002-00, Issue 3 1-2
Natural convection
UBC seismic zone 4 (Calculated response)
SAGEON VIGIL PRODUCT MANUAL
INPUT NAME
MIN.
NOMINAL
MAX.
UNITS
VOLTAGE
0.00
54.20
60.00
VOLTS
FCCP inputs (50mV)
0 - 50
mV
TEMPERATURE
0.000 (0.0°F)
.750 (75.0°F)
2.300 (230.0°F)
VOLTS
INPUT NAME
MIN.
NOMINAL
MAX.
UNITS
CELL VOLTAGE
0.00
2.2
2.55
VOLTS
CURRENT (Transducer)
-4 - 4
VOLTS
TEMPERATURE
0.000 (0.0°F)
.750 (75.0°F)
2.300 (230.0°F)
VOLTS
1.3.3 Electrical Specifications (each, VIGIL and Expansion)
Power/Supply
Input: +24 Vdc @ 400 mA (worst case)
-48 Vdc @ 200 mA (worst case)
Maximum Supply Voltage: 60 Vdc Minimum Supply Voltage: 20 Vdc
Analog Input ranges SAGEON VIGIL
Analog Input ranges CELL MONITORING EXPANSION
1.3.4 General Plant Performance Specifications
The SAGEON VIGIL was designed to operate in accordance with the monitor and control
specifications portion of TR-EOP-000154, for +24 and -48 Vdc Power Plants.
1.3.5 Safety Specifications
Underwriters Laboratory Standards of Safety for Information Technology Equipment (UL 1950) and
the Bellcore Network Equipment-Building System Generic Equipment Requirements
(TR-EOP-000063) were adhered to in all component and wire selection. Particular attention was paid
to safety ratings and OI-28 flammability requirements.
1.3.6 Monitoring Specifications
See PN Drawings and Menu Flow Charts, located in the back of this manual, for electro-mechanical
details and user menu information. All accuracies stated are % of FS.
•The front panel meter of the SAGEON VIGIL is an alphanumeric LCD display. It displays
voltage with 0.1 % accuracy and a display resolution of 0.01V, current readings with +/-0.6%
combined accuracy (VIGIL + FCCP) and a display resolution of 1mA and temperature
readings within 1/2
o
F with a display resolution of 0.1 oF. The CELL MONITORING
PM990-3002-00, Issue 3 1-3
SAGEON VIGIL PRODUCT MANUAL
EXPANSION (if applicable) will display cell voltages with 0.1% accuracy and a display
resolution of 1mV, current transducers within 0.5% and a display resolution of 1A, and
temperature sensors within 1/2
•The information displayed (in the default mode) on the front panel of the SAGEON VIGIL is
battery voltage, FCCP 1 current, and the number of active alarms. When the Load Voltage
channel has been enabled, the front panel will change to show the plant voltage, load voltage,
current, and the number of active alarms. If an ambient temperature sensor is attached, it can
be set up to toggle display with the FCCP 1 on the default screen (CONFIGURE MENU).
Optionally, the sum of the FCCP currents can be shown in place of the FCCP1 current if the
“SUM” feature is selected from the idle display configuration menu.
•Four front panel push buttons provide access to all menus for general channel polling, alarm
status determination, system configuration, calibration, and testing.
•15 analog channels predefined for battery voltage, load voltage, 10 float currents, and three
temperature sensors (ambient & 2 battery string).
•48 analog channels for cell voltage measurement when cell monitoring expansion is ordered.
2V cell voltage nominal only. 4 current transducers and 4 additional temperatures are also
added with the cell monitoring expansion.
•*5 binary fuse alarm (FA) inputs for Charge, Discharge, Sense/Control, Battery, and Spare
used for monitoring fuse and breaker status.
•*16 binary rectifier fail (RFA) inputs for monitoring individual rectifier status (active
low/GND closure).
• *2 binary counter-emf cell inputs for CEMF cell status (active low/GND closure).
• *2 binary inputs: one for LVD alarming and one Controller-Inhibit (active low/GND closure).
• Test jacks for manual confirmation of voltage, current, and temperature readings. Test jacks
are for reference only; proper calibration of the Sageon VIGIL should use measurements at
the screw terminals. E . g . Du e to in ternal inline-protection of the test terminals, a small
voltage drop will be read.
•Built in audible alarm to enunciate a Major or Minor alarm with ACO (Audible Cut-Off), all
user defined.
o
F with a display resolution of 0.1 oF,
1.3.7 Control Specifications
•Equalize (EQ) output, which is user selectable for manual or automatic operation. Manual is
initiated from front keyboard for 1 – 255 hours. Auto is triggered by user adjustable on and
off voltage thresholds and adjustable duration from 0 to 10 hours. See section E
SUB-MENU for setting up equalize.
• High Voltage Shutdown (HVSD) output with user adjustable trigger voltage.
• Restart (RS) output triggered by the Low Voltage alarm threshold to try and automatically
restart any rectifiers that are in “high voltage shutdown.”
PM990-3002-00, Issue 3 1-4
QUALIZE
SAGEON VIGIL PRODUCT MANUAL
The front panel alarm indicators are listed below with their LED indication
FRONT PANEL ALARM INDICATIONS
1.3.8 Alarm Specifications
color, trigger source, and where applicable, the alarm input requirement:
Major Alarm (MAJ)
Fuse Alarm (FA)
Very Low Voltage (VLVA)
Low Voltage Disconnect
(LVD)
High Voltage Shutdown
(HVSD)
Watchdog/Aux /OverCurrent (CUR/WD)
Rectifier Fail (RFA)
Temperature alarm (TA)
Red LED Major alarm indicator
Triggered by FA, VLVA, LVD, HVSD, OC
(over-current) or any two or more minor
alarms; RFA’s, TA’s, CEMF, LVA, HVA,
CTRL INH alarms
Red LED FA alarm indicator
Triggered from charge, discharge, sense,
battery, and spare fuse alarms
(BAT input active/true)
Red LED VLVA alarm indicator
Triggered by user defined voltage threshold
(see Set Thresholds Section 3.4)
Red LED LVD alarm indicator
Triggered by open low voltage disconnect
contactor (GRD input active/true)
Red LED HVSD alarm indicator
Triggered by user defined voltage threshold
(see Set Thresholds Section 3.4)
Red LED CUR/WD alarm indicator
Triggered by Over-current or under-current
thresholds or SAGEON VIGIL internal
default/detect circuitry (front panel reset or
microprocessor failure). The CUR/WD will
flash if the Aux alarm (user configured) is
triggered.
Red LED RFA alarm indicator
Triggered by any one of sixteen individual
rectifier fail (RFA) inputs (GRD input
active/true)
Red LED TA alarm indicator
Triggered by any Hi or Lo temperature alarm
thresholds for Ambient, Battery String 1,
Battery String 2, also triggered by any
temperature differential between strings and
ambient temp.
PM990-3002-00, Issue 3 1-5
SAGEON VIGIL PRODUCT MANUAL
The front panel alarm indicators are listed below with their LED indication
FRONT PANEL ALARM INDICATIONS
Minor Alarm (MIN)
Yellow LED Minor alarm indicator
(GRD true input)
timer expires or another audible alarm
occurs.
stays on until equalize is manually
timer expires), or
stays on until plant voltage rises
red by binary control inhibit input
(GRD true input)
color, trigger source, and where applicable, the alarm input requirement:
Counter-EMF Cell Alarm
(CEMF)
Low voltage Alarm (LVA)
High voltage alarm (HVA)
Audible Cut-off Status
(ACO)
Equalize (EQ) Status
Control Inhibit Status
(INH)
Triggered by any single RFA, CEMF, LV,
HV, or TA alarm
Yellow LED CEMF indicator
Triggered when CEMF Cell 1 or 2 are active
Yellow LED LVA alarm indicator
Triggered by user defined voltage threshold
(see Set Thresholds Section 3.4)
Yellow LED HVA alarm indicator
Triggered by user defined voltage threshold
(see Set Thresholds Section 3.4)
Yellow LED ACO status indicator
Trigger ed by man uall y turning audible alarm
off from Alarm menu. Stays on until ACO
Yellow LED EQ status indicator
Triggered by manually initiating the Equalize
mode (
turned off or manualautomatically when plant voltage falls below
threshold (
above off threshold or auto-timer expires).
Yellow LED CTRL INH status indicator
Trigge
from master controller when SAGEON
VIGIL is used as a secondary controller
PM990-3002-00, Issue 3 1-6
SAGEON VIGIL PRODUCT MANUAL
The SAGEON VIGIL provides both Form-C alarm output relays and Form-A
REMOTE ALARM INDICATIONS
be either ground closures or battery outputs.
1.3.9 Output Relay Specifications
control relays for remote monitoring, audible and visual alarm panels, and
rectifier control requirem ents.
Form-C contactsAlarms
Status
Form-A contacts
Control
The SAGEON VIGIL provides screw
terminals for 13 form-C alarm relay outputs;
all relays except MAJOR and the
WATCHDOG are normally de-energized
Plant alarm outputs are MAJ, MIN, HVA,
LVA, VLVA, FA, LVD, TEMP, CEMF,
and RFA. Two sets of contacts (2 form C)
are provided for Major and Minor alarms
An auxiliary relay (AUX) is provided that
the user can define as a major, minor,
equalize, audible alarm, or any specific
analog or binary input channel alarm. If
triggered the CUR/WD LED will fla sh.
A WATCHDOG (CUR/WD) relay is
provided to enunciate a SAGEON VIGIL
processor failure or a front-panel reset. This
relay also provides the over/under current
alarm.
A control inhibit relay (CTRL INH) is
provided to indicate that the SAGEON
VIGIL is off line due to and active control
inhibit input
A normally open set of contacts is provided
for the Equalize mode output. (See
Equalize mode section for operation details)
A normally open set of contacts is provided
for the rectifier Restart output.
A normally open set of contacts is provided
for the HVSD output.
Note: common control return (CTRL RET)
pins are provided to allow control outputs to
PM990-3002-00, Issue 3 1-7
SAGEON VIGIL PRODUCT MANUAL
2 SAGEON VIGIL INSTALLATION
2.1 Introduction
2.2 Selecting a location
2.3 Cabling Requirements
2.4 Installation procedure outline
2.5 Installation guidelines
2.6 Wiring the SAGEON VIGIL
2.1 INTRODUCTION
These instructions provide general information for installing the SAGEON VIGIL in custom applications
as a stand alone unit. Units ordered as part of custom power plants will be installed, wired, and tested at
the factory. These instructions are meant to be used with the SAGEON VIGIL product drawings PN 1033002-LXX, SD 103-3002-LXX. If the appropriate drawings are not included in this manual, contact
Customer Support at 1-800-440-3504.
If questions or problems arise during installation, please call one of our Field Service technicians at 1-
800-299-3907 for assistance. A name plate on the side of the unit gives the part number and serial number
for the SAGEON VIGIL. Reference these numbers when requesting service.
To install the SAGEON VIGIL you will need:
o Standard installation tools
o Standard small screwdriver for screw terminals (i.e. Xcelite® USA R3322)
o PN and SD drawing sets
o Inline fuses and/or resistors (included)
2.2 SELECTING A LOCATION
Note: This procedure assumes a custom SAGEON VIGIL installation in an existing power plant.
The SAGEON VIGIL should be mounted at eye level for easy access and display viewing. The unit
requires only one rack space for mounting. No precautions are necessary for internal cooling. If the unit
is to be mounted over high heat producing equipment, such as a ferro-resonant rectifier, a heat shield
should be installed between the units.
2.3 CABLING REQUIREMENTS
All connections to the SAGEON VIGIL utilize screw terminal connections. Care should be exercised to
tighten the screws without breaking the wires. Make sure there is no bare wire showing that could
possibly short to other wires. Good electrical contact should be checked for each connection.
Stranded 20 - 24 AWG wire is recommended for screw terminal connections. This type of wire is readily
available in single twis ted p air s , or m ultiple-conductor jacketed cabling to facilitate the typical wiring
associated with this monitor & controller product.
Overall system performance and safety depends on the proper wiring and the installation of inline
protection devices where needed. Cable runs that will utilize overhead cable racks should be plenum
PM990-3002-00, Issue 3 2-1
SAGEON VIGIL PRODUCT MANUAL
rated jacketed cables and carefully routed to protect the wiring to the SAGEON VIGIL.
2.4 INSTALLATION PROCEDURE OUTLINE
WARNING: The SAGEON VIGIL utilizes connections to battery for power and sensing connections that
must include inline protection (fuses or current-limiting resistors) to eliminate potential
hazards to personnel and equipment due to accidentally shorted battery connections.
GENERAL PROCEDURE OUTLINE
Verify the part number on the SAGEON VIGIL conforms to the voltage of the power plant before
installation. The SAGEON VIGIL functions with +/-24 Vdc or +/-48 Vdc input power without
adjustment. Maximum voltage input is 60 Vdc; minimum is 20 Vdc.
Locate the unit as directed in the “Selecting a Location” section and mount with four standard rackmount screws; two of the screws must have “Paint-Cutting” washers installed to assure proper
grounding for ESD protection.
Locate power source and sense points for battery power, battery voltage and load voltage connections.
These connections must be fused at the source with inline protection or utilize a sense and control panel
connection. Ideally, both the battery and ground leads should be protected. The minimum requirement is
a fuse in the battery leg. A separate ground lead should be run to one of the common Plant Ground
(PLANT GND, TB2 pins 2-12 and 21-24) screw terminals. This connection references the SAGEON
VIGIL internal ground to the power plant ground reducing noise levels and providing a convenient plant
ground connection point for ground closures on output relays.
Locate each sense point for measuring battery/plant voltage to determine what type of inline protection
and cable routing is required.
Locate rectifier connections for Equalize, Restart, HVSD inputs, and RFA outputs to determine
connection requirements. The connections for Equalize, Restart, and HVSD MUST all be battery OR
ground closures simultaneously e.g. Equalize CANNOT be a battery closure while HVSD and Restart
are ground closures. This information determ ines the connection to the common “control return” (CTRL
RTN) on the SAGEON VIGIL. The RFA inputs are ground closures.
Note: Determine best cable routing to the rectifier connections. The Equalize, Restart, and HVSD
connections can be “daisy chained” as necessary. The SAGEON VIGIL accepts up to 16 individual RFA
inputs.
Locate fuse alarm (FA IN) connection points. Five individual inputs are provided for Charge,
Discharge, Battery, Sense/Control, and one Spare. Multiple discharge fuse alarms can be “daisy
chained” if desired.
Fuse alarms are battery voltage inputs. Inline fuse protection is recommended if these connections must
utilize overhead cable runs. Determine best cable routing, connection requirements.
Note: Do not use inline resistors for protection on fuse alarms as SAGEON VIGIL internal sensing
circuits will be adversely affected and may fail to register fuse alarms; fuses must be used instead.
PM990-3002-00, Issue 3 2-2
SAGEON VIGIL PRODUCT MANUAL
Two ground closure true inputs are provided for CEMF Cell alarm inputs (CEMF1 & CEMF2). If a
CEMF Cell is included verify it provides the proper input. No inline protection is required for ground
closure type inputs. Determine the best cable routing, connection requirements.
A ground closure true input is provided for a Low Voltage Disconnect (LVD) alarm. If a Low Voltage
Disconnect is included, verify it provides the proper input. No inline protection is required for ground
closure type inputs. Determine the best cable routing, connection requirements.
If Ambient (AMB) and battery temperature (TS1 & TS2) sensors are included, determine the mounting
locations. The ambient sensor should be bolted to a large thermal mass, such as the rack itself, to limit
response to short term changes.
Two battery temperature sensor inputs are provided for up to two battery strings. Sensors are
designed with tin (or tin/lead) plated ring lugs to be connected with battery strap hardware. Sensor
detection circuits are isolated from battery potential. Sensors come with 30 ft. leads, which can be
extended with butt splices if necessary.
Cable runs in excess of 100 ft. may degrade temperature readings due to voltage drops and noise. No
inline protection is required for temperature sensors. Determine best cable routing, connection
requirements.
The alarm output relays are the last consideration. The user must determine the local requirements such
as the presence of a central alarm monitor or separate audible or visual alarm panels. All the output relays
are normally de-energized except the Major and Watchdog alarm, which is energized for fail safe
operation. All relays are rated at 60W, 62.5VA.
All alarm output relays are Form C, and can provide either normally open or normally closed connections.
Ground closure alarms can utilize the Plan t Groun d scr ew term inals for jumpers to the common
connection on the output relays. Determine best cable routing connection requirements.
2.5 INSTALLATION GUIDELINES
The following topics provide guidelines and suggestions to facilitate wiring the SAGEON VIGIL in a fast
and efficient manner, producing a quality installation that looks professional and li mits potential
problems.
Sketch out the wire routing from the SAGEON VIGIL on paper to determine the best routing that allows
the maximum number of wires to be bundled together from the SAGEON VIGIL to the furthermost
possible connection point. Creating wiring bundles facilitates routing and provides protection to
individual wires.
Always use multi-conductor twisted pair or jacketed cables whenever possible. Start cabling from the
SAGEON VIGIL. If same color coded wires must be used repeatedly, use sticky wire labels to uniquely
label each wire. This will greatly speed up the wiring process at the destination end and make
troubleshooting easier.
Familiarize yourself with the screw terminal board layout before starting the wiring process. Refer to
Signal Identifier Label fo r s c rew terminal labelin g located on the top panel of the SAGEON VIGIL.
Develop a wiring progression such as power, analog, fuse alarms, etc. This will help eliminate wiring
errors or missed connections.
PM990-3002-00, Issue 3 2-3
SAGEON VIGIL PRODUCT MANUAL
The SAGEON VIGIL power inputs are protected against reverse polarity. The analog inputs are polarity
sensitive. Reversed connections will not cause any damage but the SAGEON VIGIL w ill be un ab le to
read the input. This requirement can be confusing.
Before starting the general plant wiring, lay any ground jumpers between output relay commons, CTRL
RET, and Plant Grounds that are required. These connections can limit wiring access when added over
the other plant wiring. The SAGEON VIGIL provides pluggable screw terminal blocks for ease of wiring.
Take care to properly insert and seat the terminal blocks after wiring. If front access is required be sure to
leave enough cable length (~3-4 ft) to remove the VIGIL from the rack without disconnecting the
terminal blocks.
2.6 WIRING THE SAGEON VIGIL
The installer should be familiar with the wiring connections to the SAGEON VIGIL. The PN 103-3002LXX and SD 103-3002-LXX drawings should be available for reference to the actual SAGEON VIGIL
connections and typical wiring diagrams.
2.6.1 2Plant Ground
Determine plant ground jumper requirements for output relays from the data information sheet.
“Daisy chain” jumpers with black wire, if possible, from the Plant GRD screw terminals to the
common (C) connection on each relay requiring a ground closure.
2.6.2 Battery
Begin with the power connections to the SAGEON VIGIL running a fused Battery connection to the
BAT pin on the SAGEON VIGIL. Several Ground leads should be run for power and plant ground
connections. The power GRD return and the PLANT GROUND should be jumped together, but use
separate wiring to a central ground point on the power plant to minimize noise pick-up. (See the PN
drawing)
Note: See the PN 103-3002-LXX drawing Table E for SAGEON VIGIL power fusing requirements.
2.6.3 Battery voltage and FCCP inputs
Note: Analog inputs for Plant voltage, Load voltage and temperature sensors should be left open at
the measurement (sense) point on the power plant at installation to facilitate calibration
zeroing, which requires shorting the leads.
Connect the fused Plant Voltage sense leads to the VB+ and VB- terminals on the SAGEON VIGIL,
verifying the proper polarity. (See the PN drawing)
Connect the FCCP sense leads to the FCCP1+ and FCCP- terminals on the SAGEON VIGIL, verifying
the proper polarity. (See the PN drawing)
PM990-3002-00, Issue 3 2-4
SAGEON VIGIL PRODUCT MANUAL
WARNING: Accidental shorting of the sense leads from the FCCP current probes controller may cause
permanent damage to the probe controller. Extreme care must be used when wiring the FCCP probes to
the VIGIL. It is suggested that the connection to the FCCP controller not be made until the twisted pair
cable has been securely seated in the connector housings at both ends.
Connect any additional FCCP sense lead s start ing at FCCP2+ & FCCP2- up to FCCP10+ & FCCP10-.
These inputs must also be connected with the proper polarity. (See the PN and SD drawings for help with
these connections)
Connect the ambient and battery temperature sensors to their respective inputs: AMB (ambient) and TS1
& TS2 for battery temperature sensors. Each sensor requires a connection to power (P), tem peratu re
return (R), and temperature signal input (S). These connections correspond to the red, black, and blue
leads (respectively) of the temperature sensors. (See the PN drawing)
WARNING: Improper temperature sensor connection may damage the sensors. Always verify proper
connections, and avoid shorting leads, especially when connecting to a powered SAGEON VIGIL. The
temperature sensor return lead (RT N) is isolated, and MUST NOT be connected to PLANT
GROUND.
Connect the fused load vo lt ag e sense leads to the VL+ & VL- terminals on the SAGEON VIGIL,
verifying the proper polarity. (See the PN drawing)
This completes the analog input connections. Stop and verify these connections. Go to the Analog
Channel Calibration section next.
2.6.4 Binary Inputs
1
Binary inputs consist of 2 CEMF Cell alarm inputs, 5 Fuse Alarm (FA) inputs, 1 Low Voltage Disconnect
(LVD) Alarm, and 16 Rectifier Fail (RFA) alarms. The Binary inputs require pre-defined inputs for proper
operation. Refer to PN 103-3002-LXX and SD 103-3002-LXX drawings for typical wiring diagrams. (See
the PN drawing)
CEMF Cell alarm inputs require a ground closure input. Verify the CEMF Cell to be monitored can
provide this type of alarm output before proceeding. Alarm leads are connected to the +CEMF1 or
+CEMF2 input terminals. The -CEMF1 and -CEMF2 connections are not required, but can be jumpered
to PLANT GROUND and used with twisted pair cable runs for noise suppression if desired.
Note: UNIPOWER CEMF Cells do not typically provide an alarm output. They do provide a fuse alarm
that can be connected to the spare fuse (SP) alarm input to provide some measure of direct monitoring if
desired.
Fuse Alarm inputs require a battery input. Five Fuse alarm inputs are provided to divide these alarms into
charge (CH), discharge (DIS), battery (BAT), sense/control (S/C), and a spare input (SP) that can be used
as desired (see 2.6.4.1). Route and terminate these connections carefully due to their battery potential
when alarmed.
1
Not applicable for batter y monitor ing applications
PM990-3002-00, Issue 3 2-5
SAGEON VIGIL PRODUCT MANUAL
Note: Plant Ground (PGND) and (GRD) must be connected to the grounded terminal of the batteries for
the fuse alarms to function properly. See PN drawing for typical connections.
The Low Voltage Disconnect alarm input requires a ground closure input. Verify the LVD to be
monitored can provide this type of output before proceeding. The alarm lead is connected to the (LVD)
input terminal.
The Rectifier Fail alarm inputs require a ground closure input. Verify the Rectifiers to be monitored can
provide this type of output before proceeding. The SAGEON VIGIL can monitor up to 16 individual
Rectifier fail alarm leads that are connecte d in sequenc e to the (RFA) input terminals.
The Control Inhibit (INH) input requires a ground closure input. The Control Inhibit (INH) input
relinquishes control functions from the SAGEON VIGIL. When triggered the Control Inhibit will disable
the Rectifier ReStart (RS), Equalize (EQ), and High Voltage ShutDown (HVSD) control output relays.
The SAGEON VIGIL will continue to monitor all input channels and provide alarm condition relay
outputs when Control Inhibit is active. See section 2.6.5 for information about the control relays.
This completes the Binary input connections. Stop and verify these connections. See Enabling Channels
section after the installation wiring is complete.
2.6.5 Control Relays
The SAGEON VIGIL provides three rectifier control outputs: Equalize (EQ), High Voltage Shutdown
(HVSD), and Restart (RS). These Form A, normally open, relay outputs share a common control
connection to CTRL RET. This connection must be tied to the appropriate potential, either plant ground
or battery. Most applications will require a ground closure. In either case, all three outputs MUST utilize
the same common output potential or the user must decide which outputs he can use appropriately.
The Equalize (EQ) output provides an operator initiated manual timer or a voltage initiated automatic
timer. If this control feature is desired, determine if the rectifiers support this function and what type of
input is required. The CTRL RET terminals are common to one another and must be jumpered to the
proper potential. Multiple rectifiers can be daisy chained with a lead from the EQ output. See Fig. 6 of
PN drawing and Setting Up Equalize section in this manual.
The High Voltage Shutdown (HVSD) output provides a triggered output from the user settable HVSD
threshold. If this control feature is desired, determine if the rectifiers support this function and what type
of input is required. The CTRL RET terminals are common to one another and must be jumpered to the
proper potential. Multiple rectifiers can be daisy chained with a lead from the HV output. See Fig. 6 of
PN drawing and Setting Up HVSD & Restart section in this manual.
The Restart (RS) output provides a triggered output from the user settable low voltage LV threshold. If
this control feature is desired, determine if the rectifiers support this function and what type of input is
required. The CTRL RET terminals are common to one another and must be jumpered to the proper
potential. Multiple rectifiers can be daisy chained with a lead from the RS output. See Fig. 6 of PN
drawing and Setting Up HVSD & Restart section in this manual.
2
This completes the Control Output connections. Stop and verify these connections. See Setting
2
Not applicable for battery monitoring ap plications
PM990-3002-00, Issue 3 2-6
SAGEON VIGIL PRODUCT MANUAL
Thresholds section after the installation wiring is complete.
2.6.6 Alarm Output Relays
The output relays all provide Form C relay contacts supporting normally open or normally closed
connections. Two sets of Major and Minor contacts are provided for separate remote monitoring and local
annunciation panels. The Major alarm and CUR/WD relays are normally energized for fail safe operation.
All other relays are normally de-energized. An Auxiliary relay is user programmable. See Programming
the Auxiliary Relay section of this manual. The relays requiring ground closures should have been
jumpered to PLANT GRD at the beginning of the wiring process. Refer to the PN drawing figures for
assistance in wiring the output relays.
The SAGEON VIGIL also supports an internal audible alarm that can be user programmed to trigger from
various alarm outputs. Refer to Setting Up The Audible Alarm section of this m anual for programm ing
instructions.
Verify ground closure jumpers to common (C) terminals on designated output relays and modify
connections if necessary. Ground closure relays should be jumpered to PLANT GND and can be daisy
chained as necessary.
The two Major output relays are normally energized. These outputs are triggered by an FA, VLVA, LVD, HVSD, WD, CUR (over/under-current), or any two RFA’s, TA, CEMF, LVA or HV alarms.
Connections to powered annunciation panels should be kept separate from remote alarm connections.
Make the connection to the normally open (NO) or normally closed (NC) terminals as required. If
necessary the Aux relay can be configured as another Major output relay.
Note: The labels for ALL output relays are provided in the de-energized state. e.g. The NO labeled
contact of the Major alarm relay will be closed during regular operation (no-alarm/relay energized);
likewise, the NC labeled contact of the Major alarm relay will be open.
The two Minor output relays are normally de-energized. These outputs are triggered by a single RFA, CEMF, LV, HV, or TA alarm. Connections to powered annunciation panels should be kept separate from
remote alarm connections. If necessary, the Aux relay can be configured as another Minor output relay.
Make the connection to the normally open (NO) or normally closed (NC) terminals as required.
The other output relays HVA, LVA, VLA, FA, LVD, RFA, TEMP, CEMF, and CUR/WD (WATCHDOG) are generally only used when a remote alarm call-out device is part of the power plant or
with an alarm monitor panel in a large central office. Make the connection to the normally open (NO) or
normally closed (NC) terminals as required.
The Control Inhibit (CTRL INH) relay is triggered by the Inhibit input, which causes to VIGIL to
relinquish control of the power plant. This relay would only be used in a large power plant where the
SAGEON VIGIL was designated as a back up monitor/controller. This relay would confirm the status of
the SAGEON VIGIL. Contact the Factory for information on implementing master/slave control scheme.
The Auxiliary (AUX) relay is a user definable relay and can be configured to trigger of any ONE of any
number of alarms. The Auxiliary relay can be triggered from any (1) of the following: a MAJOR,
MINOR, SINGLE RFA, ANY RFA, PLANT OVER-CURRENT, SINGLE FEED OVER-CURRENT,
ANY OVER-CURRENT, HVSD, CTRL INH, SINGLE FA, STR 2 TEMP DIFF, STR1 TEMP DIFF,
PM990-3002-00, Issue 3 2-7
SAGEON VIGIL PRODUCT MANUAL
System Voltage
Battery terminal
Connection to Expansion
+24V (Battery)
BAT+
0V (Plant GND)
BAT-
-48V (Battery)
BAT-
0V (Plant GND)
BAT+
-24V (Battery)
BAT-
0V (Plant GND)
BAT+
+48V (Battery)
BAT+
0V (Plant GND)
BAT-
LOWN AMB TEMP, HIGH AMB TEMP, LOW BATT TEMP STR 2, LOW BATT TEMP STR1, HI
BATT TEMP STR 2, HI BATT TEMP STR 1 HI LOAD VOLTAGE, HIGH VOLTAGE, LOW
VOLTAGE, VERY LOW VOLTAGE, EXT LVD, CEMF 1, CEMF 2. When triggered the Auxiliary
alarm will flash the CUR/WD LED on the display panel.
This completes the Output Relay connections. Stop and verify these connections. See Programming the
Auxiliary Relay and Setting Up Thresholds section after the installation wiring is complete.
2.7 WIRING THE CELL MONITORING EXPANSION
Note:Refer to the datasheet for specific wiring information. Be sure to add wire color
references as connections are completed. Should actual wiring require any changes update the
datasheet immediately. The PN 103-3002-LXX drawing provides general wiring diagrams for the
typical CELL MONITORING EXPANSION connections, mechanical views, and fusing information.
SD 103-3002-LXX will also be helpful in determining typical wiring connections.
At this point, the installer should have a wiring plan that provides the most efficient cable routing.
The installer should be familiar with the wiring connections to the SAGEON VIGIL. T he PN 1033002-LXX and SD 103-3002-LXX drawings should be available for reference to the actual CELL
MONITORING EXPANSION connections in addition to this manual.
2.7.1 Power
Power should be connected to the BAT+ and BAT- terminals of the 3 position screw terminal block
header located on the rear of the unit. Be careful to observe polarity of the connections. The
SAGEON VIGIL and CELL MONITORING EXPANSION can utilize +/-24Vdc or +/-48Vdc
plant/battery voltage without jumpering or modification. A separate connection to chassis ground
must also be provided at this terminal if paint cutting washers are not used to mount the CELL
MONITORING EXPANSION in the rack at the time of installation. See the following table and Fig.
1 of the PN drawing for connections to power the CELL MONITORING EXPANSION:
+24V System
-48V System
-24V System
+48V System
Table 1. Power supply c onnections
Note: See the PN 103-3002-LXX drawing Table E for SAGEON VIGIL power fusing
requirements.
PM990-3002-00, Issue 3 2-8
SAGEON VIGIL PRODUCT MANUAL
2.7.2 Communications
Use the included telephone style cable (1ft. flat 4 conductor cable with RJ-14 connectors) to
connect the corresponding communications port labeled “IOIOI VIGIL” on the CELL
MONITORING EXPANSION to the “DIGITAL COMMS” port on the SAGEON VIGIL.
Refer to PN 103-3002-XX for more information on the location of the communications ports.
2.7.3 Cell Inputs
Note: Analog inputs for voltage, FCCPs, and current transducers should be left open at the
measurement (sense) point on the power plant at installation to facilitate calibration
zeroing, which requires shorting the leads.
Connect the cell channels to their respective inputs, Cx+ and Cx- (where “x” is the cell
number of the input), while observing polarity of the inputs. Using the supplied wiring
harness will facilitate connection of the cell inputs. See
Note: The cell inputs must be protected with fuses or current limiting resistors. The wiring
harness provided includes current limiting resistors for protection of input channels.
Figure 1:
Figure 1. Cell connections for two 48V battery strings
Note: The standard convention for the direction of current flow is assumed; that is: The flow
direction of the current is OPPOSITE that of the physical movement of electrons.
Connect the current transducers to their respective inputs. Refer to Fig. 7 of the PN drawing for
current transducer connections. Each current transducer requires a connection to +15V, -15V, current
transducer return, current transducer signal, and a connection for a shield wire is provided.
Note: The shield wire should be connected to chassis ground on one side of the cable only.
Typically this connection will be provided via the terminal block at the CELL
MONITORING EXPANSION.
PM990-3002-00, Issue 3 2-9
SAGEON VIGIL PRODUCT MANUAL
Current transducers should come preassembled with all appropriate connections to the
terminal block provided. The following information is provided for reference only in the
event maintenance on the current transducer connections is required. See the PN drawing
for available current transducer kits.
WARNING: Improper current transducer connection may damage the sensors. Always verify
proper connections, and avoid shorting leads, especially when connecting to a
powered CELL MONITORING EXPANSION unit. The current transducer
return lead is isolated, and MUST NOT be connected to PLANT GROUND.
Figure 2. Current transducer connector: Red = +15V, Green = Return, Black = -15V, White = Signal
Connect the temperature sensors to their respective inputs. Each sensor requires a
connection to power (P), temperature return (R), and temperature signal input (S). These
connections correspond to the red, black, and blue leads (respectively) of the temperature
sensors. If the temperature sensor wires have been extended refer to the datasheet for
proper connections. (See Fig. 6 of PN drawing)
WARNING: Improper temperature sensor connection may damage the sensors. Always verify
proper connections, and avoid shorting leads, especially when connecting to a
powered CELL MONITORING EXPANSION unit. The temperature sensor
return lead (RTN) is isolated, and MUST NOT be connected to PLANT
GROUND.
PM990-3002-00, Issue 3 2-10
SAGEON VIGIL PRODUCT MANUAL
Figure 3. Temperature sensor connector: Red = +5V, Blue = Signal, Bl ack = Return
This completes the analog input connections. Stop and verify these connections and update the
datasheet if necessary. Go to the Analog Channel Calibration section next to continue with
commissioning of the CELL MONITORING EXPANSION.
PM990-3002-00, Issue 3 2-11
SAGEON VIGIL PRODUCT MANUAL
3 SAGEON VIGIL OPERATION
3.1 Introduction
3.2 Programming the SAGEON VIGIL
3.3 Enabling Thresholds
3.4 Set Thresholds
3.5 Enabling Thresholds
3.6 Analog Calibration
3.7 Set FCCP Scales
3.8 System Options Menu
3.1 INTRODUCTION
3.1.1 General Description
The SAGEON VIGIL was designed to provide all basic meter/alarm functions for monitoring a battery string in
an extremely compact, single rack space unit. The unit utilizes a microprocessor and alphanumeric display to
provide enhanced functionality. The simple four key front panel allows:
• Polling for status on each input
• Detailed alarm identification
• Enabling/disabling of inputs and outputs
• Zero and Gain calibration for analog channels
• System configuration including alarm thresholds
• Equalize timer set-up and initiation
• Control of output relays
• Test and verification of all functions
The SAGEON VIGIL utilizes simple intuitive menu structures to access any function. Four keys,
“Select”, “Next”, “Previous”, and “Escape” allow the user to move up or down through the menus
or change values with ease. The “Escape” key always allows the user to easily return to the last
menu or all the way back to the default idle screen. References to key presses and/or menus will be
highlighted in bold print.
On the +24/-48v unit, the user selects the operation voltage in software after which the SAGEON
VIGIL automatically defaults to the proper alarm thresholds. No jumpers or switch settings are
required to accommodate voltage changes. The SAGEON VIGIL is by default 48V. The lower right
hand corner of the LCD the start up screen will display the current voltage configuration of the unit.
The SAGEON VIGIL will automati c al ly tim e -out and default to the idle screen from any sub-menu
within 5 minutes. The default idle screen always displays plant/battery voltage (V
alarms. A configuration option allows the screen to also display FCCP 1 current only, ambient
temperature only, the sum of all enabled FCCP currents only, or toggle between FCCP 1 current and
PM990-3002-00, Issue 3 3-1
) and number of
b
SAGEON VIGIL PRODUCT MANUAL
ambient temperature. When the Load Voltage channel is enabled, the Load Voltage (VL) is also
displayed.
LED indicators provide visual indications of alarms, HVSD, Equalize status, and power. Test jacks
allow for manual verification of analog input voltages (VIGIL inputs only). These test jacks are for
reference only and should not be used for gain calibration; measurements for calibration should be
taken at the screw terminals of the analog input channel. The LCD display screen can be configured
to turn off the LCD backlight after a given period of inactivity. Pressing any key will cause the
display to illuminate. A Configuration option can be changed to keep the backlight constantly ON. A
front panel potentiometer VIEW ADJ. allows the user to adjust the display contrast.
The SAGEON VIGIL’s functionality is menu driven. Menu flowcharts are provided in the back of
this manual to help the user find a particular function. There are four main menus below the default
idle display screen: Status, Alarms, Configure, and Test. If the Equalize function has been
enabled, a fifth main menu will appear fo r in it ia tin g th e Equalize mode. The Operations section of
the manual will first explain the menu structure of the SAGEON VIGIL and methods for moving
about within them to reach a desired function. Then each function block will be discussed in a logical
order such as, enabling channels, calibration, setting thresholds, etc.
3.1.2 SAGEON VIGIL Menu Structure
Note: Referring to the menu flowcharts in the back of the manual provides a visual representation of
the material in this section.
As described in the introduction, the SAGEON VIGIL breaks the functional modes of the unit into
four main menus:
1. Status: Polling analog channels
2. Alarms: Detailed alarm information
3. Configure: System custom set-up and calibration
4. Test: System test and verification
5. Equalize
3
: Controls manual equalize functionality
3
A fifth menu is added when the manual equalize timer is selected for use.
PM990-3002-00, Issue 3 3-2
SAGEON VIGIL PRODUCT MANUAL
Status:The Status menu only displays the current status of the analog channels. There are no
sub-menus for other tasks under this main menu.
Alarm:The Alarm menu provides an alarm cut-off control (ACO) of the audible ala rm (if
audible alarm is enabled) and the specific trigger source of each active alarm. The
UP/DOWN keys can be used to scroll through the active alarms. There are no other
sub-menus under this main menu. (The audible alarm can be disabled in the
Configure/System Options menu.)
Configure: The Configuration menu provides sub-menus organized for functionality in custom
configuring the SAGEON VIGIL for the user's application. It also provides menus for
calibrating analog input channels, setting alarm thresho lds, sy stem options, and
network settings.
Test: The Test menu provides the means for testing and troubleshooting analog, binary, and
output channels along with tests to verify LED and Display operation.
Note: If the SAGEON VIGIL has been already been commissioned, testing output relays and binary
input channels will initiate nuisance alarm conditions.
Note: Analog/digital input channels are not continuously polled in “analog test mode”.
3.1.3 Accessing the Menus
The SAGEON VIGIL always defaults to the id le display screen if no key presses occur within 5
minutes from any menu. This prevents the user from inadvertently leaving the unit in a sub-menu
where operation could be impaired, such as a test mode. The display backlight can be configured to
turn off after 5 minutes of inactivity unless there is an active alarm present. This option is selected in
the Configurations/Systems Options menu. The Display will always remain in the lit state when an
alarm is present.
The idle display screen always displays battery voltage, FCCP 1 Current, and the number of active
alarms, if any. A sub-menu selection allows the display to toggle between FCCP 1 and ambient
temperature or to display the sum of all enabled FCCP currents, if desired. When the Load Voltage
channel is enabled the idle screen also display s the Load Vol tag e.
PM990-3002-00, Issue 3 3-3
SAGEON VIGIL PRODUCT MANUAL
The user interface is limited to four push button keys:
Escape: This key is used to return to the last menu. Pressing “Escape” from anywhere within the
menu structure will abort the current activity and return the user to the next higher level in
the menu structure. Multiple presses of the escape key will always bring the user back to
the idle display screen.
Select: This key, as its name implies, is used to select, or access, a particular menu or sub-menu.
The select key is also used within many menus to toggle the status of some parameter, such
as, yes/ no, enable/disable. It is also used to select a variable where the “Next” and
“Previous” keys walk the user through a list of choices and the user presses the “Select”
key for the desired choice.
Next & Previous: These keys provide three functions:
1. The means to move between menu selections in either direct ion from the curre nt
location.
2. Selecting parameter choices within a menu where a predefi ned set of choi ces ex ist fo r a
given parameter and the user must choose one.
3. Calibration, threshold and timer changes. The keys change the displayed value up
(next) or down (prev.) to reach a desired value.
From the idle display menu pressing “Select”, “Next”, or “Previous” brings the user to the Status
menu. From the Status menu the “Next” and “Previous” keys can be used to access any of the main
menus. Once the desired main menu is reached pressing “Select” drops the user down one level
allowing access to any of the sub-menus under that main menu using the “Next” and “Previous” keys
as before to access the desired sub-menu.
The “Escape” key can be used as an exit from any menu. Depending on where the user currently is
in the menu structure one, or more, presses of the “Escape” key may be required to reach the toplevel idle display screen. Pressing the “Escape” from the idle display screen will refresh the display;
this function is useful if an error has occurred in communications between the microprocessor and the
LCD.
3.1.4 Menu Functionality
The main menus group common functions together simplifying access. The following descriptions
highlight the basic functions of each main menu. Menus are presented in the order that they are
accessed in, by pressing the “Next” key, starting at the Status menu.
Note: If any channels have been disabled in the Configure/Enable Channels menu they will not
appear in any subsequent menus, nor will any alarm conditions be triggered from input to that
particular channel.
Status: The status menu provides a means of polling each analog input channel for its current status.
Pressing “Select” when the Status menu appears drops the user down to the first analog
channel. Pressing “Next” progresses the user through the channels in the following order:
PM990-3002-00, Issue 3 3-4
SAGEON VIGIL PRODUCT MANUAL
1. Plant Voltage
2. FCCP 1 current
3. Ambient Temp.
4. Temp. String 1
5. Temp. String 2
6. Load Voltage
7. FCCP Current 2
.
.
.
14. FCCP Current 10
15. PCB Temperature
The last value read before entering the Status menu is displayed for each channel. The
user can update the displayed channel by pressing the “Select” key. Press “Escape” once
to return to the main Select Mode menu. CELL MONITORING EXPANSION channels
appear in their appropriate categories when the unit is connected. The VIGIL will
automatically detect the connect ion and disp lay the enabled exp ans ion chann e ls (C ell input
channels only are enabled by default; other channels, temperature and current transducer
channels must be manually enabled).
Alarms: The Alarm menu provides quick access to detailed alarm identification. The menu is
accessed with the “Next” or “Previous” keys and entered with the “Select” key. The
initial screen displays the current number of active alarms and the status of the audible
alarm cut-off (ACO control will not be displayed if the audible alarm has been disabled in
Configure/System options). Here, the “Select” key toggles the audible alarm on or off
when it is enabled.
The “Next” and “Previous” keys take the user through each active alarm, showing the
source of the alarm; i.e., Alarm 1 of 3: RFA 3; or Alarm 1 of 1: LOW VOLTAGE.
The LED alarm indicators on the front panel provide general information that corresponds
to the detailed alarm information. The LED’s may indicate a fuse alarm and a rectifier fail
alarm currently exist. The Alarm menu tells the user which specific fuse type and
rectifier is in alarm. Pressing “Escape” when completed, will return the user to the main
Select Mode Menu.
Configure: The Configure menu provides all of the sub-menus necessary to custom configure the
SAGEON VIGIL for a particular application. Pressing “Select” when the Configure menu
appears allows access to the configuration menus. “Next” and “Previous” keys are used
to locate the desired sub-menu. Pressing “Select” again accesses the displayed menu. The Configure menu consists of eight standard and one optional sub-menu (Equalize
4
):
Manual Equalize: Optional menu that appears when Timer mode is selected under Systems Options
EQUALIZE MENU. In Timer mode the user can set the desired Equalize time from 1
to 255 hours in the Configure Manual EQ Time menu. The Equalize menu appears first
when enabled so the user can quickly access the time parameter for the manual equalize
4
Not applicable for batter y monitor ing applications
PM990-3002-00, Issue 3 3-5
SAGEON VIGIL PRODUCT MANUAL
mode. Pressing “Next” or “Previous” moves the user to the next/last Configure submenu, “Escape” moves the user back to the main Configure menu.
Enable Thresholds: Lets the user decide which alarm thresholds are active and which are not. The user
presses “Select” to enter the menu, then “Next” or “Previous” to access each alarm
threshold. The “Select” key can be used to toggle each alarm threshold on or off. See
Setting up the Analog Channels section of this manual for more details. Pressing the
“Escape” key when complete returns the user to the Enable Thresholds menu.
Set Thresholds: Permits the user to make changes to each individual alarm threshold. To change an
alarm threshold the user presses “Select” when the desired alarm threshold appears in
sequence using the “Next” and/or “Previous” keys. The alarm's current thresho ld w ill
appear below the alarm threshold's name. The words “Set at” will change to “modify”
when select is pressed then the user presses the “Next” (up) or the “Previous” (down)
keys to adjust the value of the alarm threshold. Once the desired value is displayed the
user presses “Select” again to save the new threshold value which changes the wording
back from “Modify” to “Set at”. If an error is made while in “Modify” pressing “ESC”
will abort the operation and restore the original value. See Setting up the Analog
Channels section of this manual for more details. Pressing “Escape” returns the user to
the Set Thresholds menu under the Configure menu.
Enable Channels: Lets the user to turn off unused channels to simplify access and possible confusion.
Channels that are disabled will not appear in other menus, such as, Set Thresholds,
eliminating possible confusion and confining activity to only pertinent parameters. If a
hardware connection is not made to the rear panel of the SAGEON VIGIL it is suggested
that the channel be disabled in this menu. As before the user enters with the “Select” key
using the “Next” and “Previous” keys to move from channel to channel. Pressing
“Select” toggles the channel on or off. When completed, pressing “Escape” returns the
user to the Enable Channels menu.
Calibrate Zero: Part of analog channel calibration; eliminates measurement errors due to sense lead
length and noise. This menu requires the user to short the measurement leads at the
actual sense point to null out line losses. See Setting up the Analog Channels section of
this manual to use this menu.
Calibrate Gain: Part of analog channel calibration scales the particular channel to accurately read the
input value. The user must measure and verify the input manually first; this measurem ent
should be performed at the sense point of the wire leads. Then the displayed value is
adjusted up or down with the “Next” or “Previous” keys to match the manual reading.
Once set the SAGEON VIGIL automatically scales the input linearly to accurately read
any input value for that channel. See Setting up the Analog Channels section of this
manual to use this menu.
Set FCCP Scales: Before the SAGEON VIGIL can accurately read the various FCCP inputs the
individual FCCP full scale rating must be entered. The VIGIL defaults to a 5.0A full
scale setting for all FCCP inputs. This setting should not be changed when using the
FCCP current probes. The SAGEON VIGIL is configured to use 50mV FCCP inputs
only.
Network:Sets the IP address, Netmask, and Gateway address values for webpage and SNMP
PM990-3002-00, Issue 3 3-6
SAGEON VIGIL PRODUCT MANUAL
network communications. The default IP address is 192.168.10.74. The default netmask
is 255.255.255.0, and the default gateway address is 192.168.10.1.
System Options: Contains several sub-menus for setting system level parameters:
Password: Enables or disables a pre-defined sequence of numbers that will prevent access to
the Configure and output relay Test menus. Once enabled, after 5 min. these
menus will be inaccessible without the password. If the user attempts to enter the
Configure or output relay Test menus they will be prompted for the password.
(See Security section of manual).
Neg. Volts: Toggles NO/YES to place a Negative sign in front of the voltage readings to
correspond with use in -48 volt power plant.
Neg. Amps: Toggles NO/YES to place a Negative sign in front of the current readings to
correspond with use in -48 volt power plant.
Temp. Units: Toggles °C (Celsius) or °F (Fahrenheit) for temperature readings.
Idle Display: Changes idle display screen parameter for current only, ambient temperature
only, or toggling between current and ambient temperature, or the sum of all
FCCP channels.
Audible Alarm: Enables audible alarm in response to major or minor alarms, and sets the ACO
time-out (See Audible Alarm section of manual).
System Voltage: Sets SAGEON VIGIL for use in a +24vdc, -48vdc power plant operation.
Equalize: Enables Equalize mode (See Setting Up Equalize section of manual).
Aux. Relay: Sets up Auxiliary Relay parameters (See Setting up Auxiliary Relay section
of manual).
Backlight Usage: Toggles between having the Backlight turn on with any key press, remain on
constantly, or always off.
SW version: Displays the presently installed software version.
Test: The Test menu provides the various test modes needed to verify the SAGEON
VIGIL operation as installed in a power plant. In the analog or binary test mode
the selected channel is read continuously. The user can also turn output and
alarm relays on or off and perform LED, LCD and audible alert test verifications.
(See appropriate testing section of manual for detailed operating instructions).
Note: Plant/battery monitoring ceases during Analog, Binary, and Output Relay tests.
PM990-3002-00, Issue 3 3-7
SAGEON VIGIL PRODUCT MANUAL
Channels Name
Def ault State
PA SSWORD
OFF
NEG. VOLTS
NO
NEG . AMPS
NO
TEMP UNI TS
°F
IDLE DISP
AMPS
AUD. ALRM MENU
MA JOR ON
MINOR OF F
AC O TIME 30min.
SYS VOL TS
48V
EQUALIZE MENU
NONE EN ABLED
AUX RELAY MENU
NONE EN ABLED
3.2 PROGRAMMING THE SAGEON VIGIL
This section will deal with the Configure menus only. The Configure menu provides all of the menus
necessary to customize the SAGEON VIGIL for the user’s specific requirements. Each sub-menu will be
covered in detail which will enable the user to completely configure the SAGEON VIGIL for their specific
application. The user should read through this material then experiment with the ir un it to b eco me familiar
and comfortable with programming the SAGEON VIGIL. None of the functions under Configure are
capable of damaging the equipment. The only function that could potentially cause a power interruption
would result from setting the HVSD alarm threshold lower than the present plant voltage or setting the
system voltage to +24vdc on a –48vdc plant, this would generate a HVSD alarm; if the HVSD control relay
is connected to an LVD or rectifier control input power interruption could be possible; however, this
functionality is not typically used in a battery monitoring applications.
3.2.1 Factory Default Settings
The VIGIL as shipped from the Factory is initially programmed for use in a very basic power plant.
Many channels and functions are programmed to be initially disabled. This allows the user to install
the VIGIL ready to use with the most basic monitoring and control functions already programmed
into the unit. The user can then add whatever additional channels and functions required to customize
the SAGEON VIGIL for their specific application.
The Configure menu descriptions detail the full implementation for each menu. Since the SAGEON
VIGIL has been factory programmed many of the channels and alarm thresholds will not appear when
the user first enters some menus. Use the following table of Factory settings to determine the initial
status for these menus.
Configuration Defaults
3.3 ENABLING THRESHOLDS
This sub-menu allows the user to disable any analog threshold. Disabling a threshold will disable the
associated alarm. Only the thresholds of enabled channels will appear in this menu. By default all alarm
thresholds are enabled.
PM990-3002-00, Issue 3 3-8
SAGEON VIGIL PRODUCT MANUAL
Enter the “Enabling Thresholds” menu from the Configure menu by pressing “Select”, then press
“Next” until the “Enabling Thresholds” menu appears, then press “Select” again to access the first
threshold. The full list of alarm thresholds appears below in the order they would be accessed using the
“Next” key. Use the “Next” or “Previous” key to walk through the thresholds as shown below; pressing
“Select” to disable the unneeded thresholds. When completed, press “Escape” to return to the ini ti al
“Enabling Thresholds” menu. Use “next” or “Previous” to reach other Configure sub-menus, or
“Escape” again to return to the top Configure menu.
Alarm Thresholds Table
1. High Volt Shut Down 9. Hi Bat Temp 2
2. Very Low Voltage 10. Lo Bat Temp 1
3. Low Voltage 11. Lo Bat Temp 2
4. High Voltage 12. Hi Amb Temp
5. High Current 13. Lo Amb Temp
6. Low Current 14. Str 1 Temp Diff
7. Load Voltage 15. Str 2 Temp Diff
8. Hi Bat Temp 1
3.4 SET THRESHOLDS
The ‘Set Thresholds” menu allows the user to change default thresholds to any desired value. Only the
enabled thresholds will appear in sequence. The SAGEON VIGIL allows thresholds to be set for the
FCCP currents; an over/under-current on any FCCP channel will automatically trigger a major alarm.
The Auxiliary alarm output relay can also be configured to trigger from an over-current threshold (See
section A
UXILIARY RELAY SUB-MENU for setting up the Aux. relay). The table below lists the
SAGEON VIGIL’s default thresholds for 24V, 48V operation.
Enter the “Set Thresholds” menu from the Configure menu by pressing “Select”, then press “Next”
until the “Set Thresholds” menu appears, then press “Select” again to access the first threshold. Use the
“Next” key to walk through the thresholds as shown below. Press “Select” when you reach a threshold
you want to change. When you press “Select”, the screen will change from Set at: (value) to Modify: (value). The user then uses the “Next” (up) or “Previous” (down) to scroll to the desired threshold
value. Once the correct value is displayed, pressing “Select” loads the new value and returns the display
screen to Set at: (new value). The “Next” and/ or “Previous” keys can then be used to select another
threshold. When completed, press “Escape” to return to the initial “Set Thresholds” menu. Use “Next”
or “Previous” to reach other Configure sub-menus, or “Escape” again to return to the top Configure
menu.
PM990-3002-00, Issue 3 3-9
SAGEON VIGIL PRODUCT MANUAL
Alarm Triggering Thresholds
48V PLANT
ALARM THRE S. FROM TO DEFAULT
HVSD: 50.0 V 60.0 V 57.0 V
H igh Voltage: 50.0 V 60.0 V 56.5 V
Low Voltage: 44.0 V 54.0 V 51.5 V
Very Low Voltage: 40.0 V 50.0 V 46.5 V
H igh FCC P current: 0 A 5.0 A 5.0 A
Low FC C P current: 0 A 5.0 A 0.0 A
High Cell Voltage: 0 V 2.42 V 2.55 V
Low Cell Voltage: 0 V 2.00 V 2.55 V
H igh T emp, String 1: 0 F 200 F 95.0 F
Low Temp, String 1: 0 F 200 F 32.0 F
H igh T emp, String 2: 0 F 200 F 95.0 F
Low Temp, String 2: 0 F 200 F 32.0 F
H igh T emp, Ambient: 0 F 200 F 95.0 F
Low Temp, Ambient: 0 F 200 F 32.0 F
Stri ng 1 Temp Diff 0 F 200 F 20.0 F
Stri ng 2 Temp Diff: 0 F 200 F 20.0 F
PM990-3002-00, Issue 3 3-10
SAGEON VIGIL PRODUCT MANUAL
24V PLANT
ALARM THRE S. FROM TO DEFAULT
H igh Voltage Shutdw n: 25.0 V 30.0 V 28.5 V
H igh Voltage: 25.0 V 30.0 V 28.2 V
Low Voltage: 22.0 V 27.0 V 25.7 V
Very Low Voltage: 20.0 V 25.0 V 23.3 V
H igh FCC P current: 0 A 5.0 A 5.0 A
Low FC C P current: 0 A 5.0 A 0.0 A
High Cell Voltage: 0 V 2.42 V 2.55 V
Low Cell Voltage: 0 V 2.00 V 2.55 V
H igh T emp, String 1: 0 F 200 F 95.0 F
Low Temp, String 1: 0 F 200 F 32.0 F
H igh T emp, String 2: 0 F 200 F 95.0 F
Low Temp, String 2: 0 F 200 F 32.0 F
H igh T emp, Ambient: 0 F 200 F 95.0 F
Low Temp, Ambient: 0 F 200 F 32.0 F
Stri ng 1 Temp Diff 0 F 200 F 20.0 F
Stri ng 2 Temp Diff: 0 F 200 F 20.0 F
3.5 ENABLING CHANNELS
The “Enable Channels” menu lets the user select only the channels needed for their application. Removing
unused channels allows the SAGEON VIGIL to scan at a higher rate and the user to access information faster
without scanning through unused channels and thresholds. When Enable Channels is “Selected”, the
“Next” key scrolls through the channels in this order:
Enter the “Enable Channels” menu from the Configure menu by pressing “Select”, then press “Next” until
the “Enable Channels” menu appears, then press “Select” again to acces s the first channel. Use the “Next”
key to walk through the channels as shown above, pressing “Select” to disable the unneeded Channels.
When completed, press “Escape” to return to the initial “Enabling Channels” menu. Use “next” or
“Previous” to reach other Configure sub-menus, or “Escape” again to return to the top Configure menu.
Channel Enable factory defaults
BATTERY VOLTAGE
FCCP 3 CURRENT DISABLED
FCCP 4 CURRENT DISABLED
FCCP 7 CURRENT DISABLED
FCCP 8 CURRENT DISABLED
LOA D V OLTAGE* DISABLED
TEMP STRING 1 DISABLED
SENSE FUSE *
ENABLED
PM990-3002-00, Issue 3 3-12
CHARGE FUSE*
SAGEON VIGIL PRODUCT MANUAL
BATTERY FUSE*
DISABLED
RECT FAIL 2*
ENABLED
RECT FAIL 3*
ENABLED
RECT FAIL 4*
ENABLED
RECT FAIL 6*
ENABLED
RECT FAIL 7*
ENABLED
RECT FAIL 8*
ENABLED
RECT FAIL 10*
ENABLED
RECT FAIL 11*
ENABLED
RECT FAIL 14*
ENABLED
RECT FAIL 15*
ENABLED
RECT FAIL 16*
ENABLED
CEMF CELL 1*
DISABLED
CEMF CELL 2*
DISABLED
SPA RE FUSE * DISABLED
RECT FAIL 1*
RECT FAIL 5*
RECT FAIL 9*
RECT FAIL 12*
RECT FAIL 13*
ENABLED
ENABLED
ENABLED
ENABLED
ENABLED
CTRL INHIBIT* DISABLED
EXTERNAL LVD5 DISBALED
3.6 ANALOG CALIBRATION
The SAGEON VIGIL is properly calibrated upon leaving the factory; however, in the case calibration is
required the next two menus are used to calibrate the analog channel inputs. The first menu, “Calibrate Zero” nulls out any offset due to amplifier zero-offset and/or analog to digital co nverter zero-error. The
second menu “Calibrate Gain” sets up each ch ann el to accura tely read tha t chan nels inpu t. When
completed the SAGEON VIGIL has a zeroed measurement point to reference all othe rs from and a scaling
factor to allow it to read out in amps or degrees as required. Proper calibration is critical to the SAGEON
VIGIL’s performance and customer satisfaction. Properly completed the SAGEON VIGIL should only
require a yearly verification of the measurement accuracy.
Note: Refer to the FCCP manual for float current probe calibration procedure. The FCCP probe must be
calibrated separately from the SAGEON VIGIL.
5
Not typically used in battery monitoring configurations
PM990-3002-00, Issue 3 3-13
SAGEON VIGIL PRODUCT MANUAL
3.6.1 Calibrate Zero
The “Calibrate Zero” menu provides a fast and simple means to null out the analog measurement
sense leads. This process requires the user to short the measurement leads together as close to the
actual measurement point as possible. Fo r this re ason s ense lea ds shou ld be left open at the
measurement end to facilitate this procedure on start-up.
WARNING: Zeroing an analog channel without shorting the measurement leads can dramatically offset
the display measure ment. W hil e no physical damage will result the user may require a
service call, to open, then short and zero the input, in order to restore proper operation.
DANGER: NEVER short analog measurement leads that are connected to their sense points on the
power plant. Personal injury, arcing and damage to inline pr otection devices and/or
equipment may result.
The menu structure provides a prompt: INPUTS SHORTED? CONFIRM? NO that the user
must toggle to YES with the “Next” or “Prev” key before the SAGEON VIGIL will allow the user to
press “Select” and zero the channel as a safety measure.
This procedure assumes a new installation where each analog channel would require a full calibration
before use:
Note: At installation time perform steps 1 to 6 with the input leads shorted. Each channel should
display a value close to zero. Whether it does or not, calibrate the value for zero with its inputs
shorted. Doing so fixes the proper offset values into memory. Once these steps are complete
connect the inputs to their respective sources, repeat steps 1 to 6 for each additional channel
and adjust for the proper levels.
Calibrate Zero Procedure
1. Enter the “Calibrate Zero” menu from the Configure menu by Pressing “Select”, then press
“Next” until the Calibrate Zero menu appears, then press “Select” again to a cce ss the first
channel:
PLANT VOLTAGE
READING: (present value)
2. Short the Plant Voltage sense leads together at the measurement point; the reading will show the
zero offset value.
3. Press “Select” again, and the SAGEON VIGIL will prompt:
INPUT SHORTED?
CONFIRM? NO
4. Verify proper shorting of the input leads then press “Next” or “Previous” to toggle the input to
“YES”
PM990-3002-00, Issue 3 3-14
SAGEON VIGIL PRODUCT MANUAL
5. Press “Select” again and the SAGEON VIGIL will zero the channel and return to the initial
display showing the offset as zero:
6. Only those analog channels that were enabled in the Enable Channels menu will appear in
sequence. Press “Next” to reach the next analog channel; repeat this procedure to zero all the
analog channels. FCCP channels are displayed in mill ivolts (mV) and temps are displayed in
degrees F.
Note: The FCCP 1, sensor 1 output must be zeroed with FCCP 1 input on the Sageon VIGIL;
likewise, the FCCP 1, sensor 2 output must be zeroes with the FCCP 2 input on the Sageon
VIGIL. i.e. the FCCP sensor outputs and VIGIL inputs are calibrated to each other and after
calibration, the channels must not be moved/swapped. This follows for any additional FCCP
inputs.
Note: The temperature sensors by construction do not support shorting at the measurement point.
These channels can only be zeroed at the SAGEON VIGIL input when the standard sensor and
cable assembly are disconnected. In cases where an extension cable was necessary the user
can zero out the extension cable before connection to the actual sensor wiring. BE SURE to
short only the SIG and RTN leads.
PLANT VOLTAGE
READING: 0.00
When all the analog channels have been zeroed, leave the sense leads open to prepare for the
Calibrate Gain procedure. Press “Escape” to return to the initi al “Calibrate Zero” menu. Use
“Next” or “Previous” to reach other Configure sub-menus, or “Escape” again to return to the Save
Configurations menu.
3.6.2 Calibrate Gain
The Calibrate Gain menu allows the user to quickly calibrate any analog channel to provide an
accurate reading scaled for volts, amps, or degrees. Since the overall performance of the SAGEON
VIGIL is tied directly to the accuracy of its measurements carefu l attent ion to det ail is manda tory
when calibrating the SAGEON VIGIL.
The front test jack s provide a convenient means for checking the input with a DVM for comparison
with the SAGEON VIGIL. By performing the zero calibration first any losses due to lead length
should be removed and the test jack accuracy should be quite good. However, during th e in it ial
installation calibration, users should confirm the test jack accuracy by measuring the in p u ts at the ir
source and comparing the results.
A suitable DVM with at least 4-digit accuracy should be used for all analog input measurements.
FCCP and temperature readings will require calculations to acquire the actual amps or temperature
value from the FCCP or temperature sensor test jack volt ag e outputs for ca libra tio n.
See sections 3.6.3 and 3.6.4 before calibrating the gain of FCCP and temperature inputs. To
maximize the accuracy of the FCCP input calibrations certain precautions shou ld be followed.
Temperature inputs require a simple calculation before the gain is adjusted.
PM990-3002-00, Issue 3 3-15
SAGEON VIGIL PRODUCT MANUAL
Calibrate Gain Procedure
1. Enter the “Calibrate Gain” menu from the main Configure menu by Pressing “Select”, then
press “Next” until the Calibrate Gain menu appears, then press “Select” again to access the first
channel:
2. Measure the actual input between the voltage and Com test jacks on the front panel, or at the
measurement source. See below for required FCCP and temperature calibration calculations.
3. Press “Select” again, and the SAGEON VIGIL will prompt:
4. Use “Next” (up) / “Previous” (down) to make the display value match the measured value.
5. Press “Select” again to load the new calib rated val ue. The display will change to confirm the new
calibrated value that was entered:
PLANT VOLTAGE
READS: (current value)
PLANT VOLTAGE
GAIN: (current value)
6. The user can press “Select” again to re-adjust the curre nt calib rat ion valu e, or pres s “Next” to
access the next enabled channel. Repeat the procedure for each active analog channel.
When all the analog channels have been calibrated press “Escape” to return to the initial “Calibrate Gain” menu. Use “next” or “Previous” to reach other Configure sub-menus, or “Escape” again to
return to the top Configure menu.
3.6.3 FCCP Channel Calibration C alculations
In order to calibrate FCCP channels, a suitable load current must be passing through it to use it for
calibration. The load current should be at least 70% or 80% of the full scale rating to get an accurate
calibration. A load connected to a supply through the FCCP transducer may be required to generate
the required current levels during calibration. A multimeter will also be required for FCCP/VIGIL
calibration.
Note: The SAGEON VIGIL is hardware limited to reading only 50mv full-scale rated shunt style
inputs. Battery discharge current can not be monitored with the SAGEON VIGIL using a
FCCP probe. For additional current transducer monitoring capability, see the VIGIL Cell
Expansion unit (103.3002.L21).
PLANT VOLTAGE
READS: (calibrated value)
Note: The FCCP probe and controller must be calibrated prior to and separately from the VIGIL. See
the FCCP manual for the calibration procedure.
The resulting displayed current reading can be verified against the actual input performing the
PM990-3002-00, Issue 3 3-16
SAGEON VIGIL PRODUCT MANUAL
Amps
mV
AmpsmV
AmpsActual3
50
)5(30
_==
F
F
mV
mV
o
o
2.78
10
782
=
following calculation. Measure the actual milli-Volt input on at the screw terminal inputs on the back
of the SAGEON VIGIL for the particular probe being calibrated. The FCCP’s full sca le ra tin g is
5.0A @ 50mV full-scale. Multiply the measured value by the full scale rating and divide the result
by 50 to get the actual current value. This calculated value should agree with the number of amps
passing through the load:
Measured value = 30 mV,
Note: The FCCP probe has a long built in digital filter; the probe requires approximately 30 min. of
settling time for an accurate reading. i.e. Wait 30 min. after probe activation or changes in
current to record/calibrate current values through the FCCP.
3.6.4 Temperature Calibration Calculations
The SAGEON VIGIL utilizes UNIPOWER’s standard tem peratu re sens or assemblies that provide a
calibrated output of 10 mV per degree Fahrenheit. For SAGEON VIGIL Calibratio n the easiest
method is to measure the sensor output on the temperature inputs at the rear of the SAGEON VIGIL.
Reading between the SIG and RTN with a DVM on the milli-volt range provides a voltage that can
be read directly as Degrees Fahrenheit. For example, a reading of 782 mV can be read as 78.2°F for
entry as the calibration value.
This value may also be read on the tip jacks located on the front panel, while the unit is set to
calibration or test mode and the corresponding sensor channel is selected. The VIGIL measures
temperatures from 0°F to 200°F, i.e. voltage ranges from 0 to 2.00 Volts.
3.7 SET FCCP SCALES
The VIGIL can monitor up to 10 FCCP probes. The calibrate zero and gain menus set-up the hardware analog
input channels to accurately read a 50mv FCCP input. In order to display the correct ampere reading for each
particular FCCP the full-scale rating must be entered. The factory default setting is 5.0A for all FCCP scales.
This value should not require modification.
PM990-3002-00, Issue 3 3-17
SAGEON VIGIL PRODUCT MANUAL
3.8 SYSTEM OPTIONS MENU
The system options menu provides eleven sub-menus that include:
1. Enabling a password for access
2. Setting the voltage display polarity for positive or negative readings
3. Setting the current display polarity for positive or negative readings
4. Setting temperature display for °F or °C display
5. Setting idle display for current or current / ambient temperature toggle
6. Setting up the audible alarm
7. Setting the system operation voltage 24V / 48V
8. Setting the Equalize mode for Manual timed or AutoEq.
9. Setting up the Auxiliary relay mode
10. Setting the Backlight to turn on by KEY-PRESS, remain ON constantly, or OFF
always
11. Display the Software revision level
Enter the “System Options” menu from the main Configure menu by pressing “Select”, then use the “Next”
or Previous” keys to locate the System Options menu. Press “Select” again when the “System Options”
menu appears to access the first sub-menu System Password. Use the “Next” key to walk through the
menus in the order shown above. The following procedures assume a new installation and a sequential
procedure through each sub-menu.
3.8.1 System Password Sub-Menu
The system password prevents a user from accessing any of the Configure or Output Relay Test
menus thereby protecting the system configuration from an unauthorized change or unauthorized
trigger of nuisance alarms. When the System Password sub-menu appears, press the “Select” key to
turn the password On or Off.
System Password is: 09191
The system password does not take affect until after 5min. of idle time (without key-presses) From
that point on, any attempt to enter the Configure menu will be preceded by a display screen: ENTER PASSWORD? The user must enter the correct number sequence using the “Next” and “Previous”
to scroll sequentially through the numbers followed by the “Select” key to proceed.
CAUTION: Inadvertent enabling of the Password can not be un-done without the actual password to
gain entry to the System Options sub-menu. Be sure the Password feature is desired
before enabling it. Call Customer Service if password & product manual are lost.
3.8.2 Negative Volts Sub-Menu
The SAGEON VIGIL reads everything as a positive value. In order to display the proper polarity the
user must select positive or negative with this menu. Simply set the polarity to match the plant
voltage polarity using the “Select” key to toggle the Negative Polarity: Yes to No for a positive
polarity power plant. The setting affects all voltage readings.
PM990-3002-00, Issue 3 3-18
SAGEON VIGIL PRODUCT MANUAL
Use the “Next” key to access the next menu.
3.8.3 Negative Amps Sub-Menu
The SAGEON VIGIL reads everything as a positive value. In order to display the proper polarity the
user must select positive or negative with this menu. Simply set the polarity to match the FCCP 1
polarity using the “Select” key to toggle the Negative amps: Yes to No for a positive polarity on
current readings. The setting affects all current readings.
Use the “Next” key to access the next menu.
3.8.4 Temperature Inputs Sub-Menu
The SAGEON VIGIL can display temperature in °F or °C as desired by the user. The Factory
recommendation is to use °F because the temperature sensor output is scaled for Fahrenheit. Reading
in °F will also make the gain calibration somewhat easier when calculating the actual reading which
is explained in the Calibrate Gain menu section. Use the “Select” key to select °F or °C operation.
The setting affects all temperature readings.
Use the “Next” key to access the next menu.
3.8.5 Idle Display Sub-Menu
The main display screen provides an option for displaying Battery 1 Float Current, Ambient
temperature, the sum of all enabled FCCPs currents or toggling between Battery 1 Float Current and
Ambient Temperature every 5 seconds. Use the “Select” key to select AMPS, TEMP, SUM or AMPS/TEMP operation. This selection is in addition to the display of Battery Voltage and active
alarms.
Use the “Next” key to access the next menu.
3.8.6 Audible Alarm Sub-Menu
The SAGEON VIGIL provides an internal audible alarm using a PCB mounted audio transducer. The
user can select the audible alarm to respond to a Major alarm, a Minor alarm, or both. The user can
also set the Audible Cut-Off time to: 30, 60, 90 minutes, or Off. In the Off mode the audible alarm
will continually sound until the alarm condition is corrected. If the 30, 60, or 90 minute ACO time is
selected, the user can disable the audible alarm from the Main Alarm menu. It will remain off for the
selected time unless another alarm occurs. While in ACO the yellow ACO LED will be on and the
Major and Minor LED’s will blink.
The user presses the “Select” key to toggle the On/Off for a major alarm. Then press “Next” to
reach the Minor alarm, which is also toggled On/Off with the “Select” key. Pressing “Next” again
allows the user to use the “Select” key to toggle between 30, 60, 90, or Off for the ACO time. Once
the selections are made pressing “Escape” returns the user to the Audible Alarm menu.
PM990-3002-00, Issue 3 3-19
SAGEON VIGIL PRODUCT MANUAL
Note: The audible alarm transducer is rated at 85 DBA @ 10cm which is loud enough for a small
office or CEV. Offices where the operator may be more the 25 ft. away or there is a high level
of back ground noise should use a separate audible alarm panel operated by an output relay.
(See Aux. Relay 3.7.10)
3.8.7 System Voltage Sub-Menu
This menu selects the operating voltage for the SAGEON VIGIL. The user selects 24v or 48v with
any 103-3002-LXX model (The default is for a 48V plant). The “Select” key toggles between the
choices and resets alarm threshold s to the default thresholds for the new voltage setting.
Note: Changing the plant voltage will load factory defaults for all thresholds and enabled channels.
Use the “Next” key to access the next menu
3.8.8 Equalize Sub-Menu
This menu allows the user to choose an Equalize mode. Use the “Next” (up) / “Prev” (down) keys to
scroll through the options of “Timer” and “Auto Eq.”. Press the “Select” key to enable the desired
mode (s). Both of these modes can be enabled simultaneously.
The Timer and Auto Eq. modes will terminate prematurely should a High Temperature “TA” alarm
occur for Ambient, and if enabled Temp String 1 or Temp String 2. Timer and Auto Eq. equalize
modes will terminate in the presence of a Controller Inhibit signal.
Selecting TIMER enables the manual equalize mode. This causes the “Manual Eq Time” menu to
appear at the top of the Configure menu. Here the user can configure the duration of a manual
equalize cycle from 1-255 hours. Also a top-level “Manual Equalize” menu is added where the user
can press the “Select” key to initiate an equalize cycle. The VIGIL will display the number of
equalize hours elapsed out of the total number of Eq hours.
Pressing select under the AUTO EQ menu when disabled will enable it, and when enabled will
disable it. When enabled the VIGIL displays the Auto Eq. sub-menu. Here the user chooses the
Auto-Eq ON threshold; which is the voltage level that the plant must fall below and then raise above
to trigger an Auto Eq. cycle. Its default is the Low Voltage Alarm Threshold. You can also set the
Auto Eq. OFF threshold; which is the voltage level that the plant must raise above to terminate an
Auto Eq. cycle. Its default is the High Voltage Alarm Threshold. The last setting in this sub -menu is
the Auto Eq. Time, which is a timer from 0 – 10 hours that will terminate the Auto Eq. once the cycle
has started. Its default is one hour. A setting of 0 hours configures the Auto-Eq cycle to only
terminate when the plant voltage exceeds the Auto Eq. OFF threshold or premature termination point
(above) occurs i.e. Auto Eq. shut-off by HVA. Any high temp alarm will abort an Auto-Eq cycle
while in progress.
6
Use the “ESC” and “Next” key to access the next menu.
6
Not typically used for battery monitor ing applications
PM990-3002-00, Issue 3 3-20
SAGEON VIGIL PRODUCT MANUAL
3.8.9 Auxiliary Relay Sub-Menu
The Auxiliary Relay menu allows the user to define the Auxiliary relay as one of the following: an
extra Major or Minor alarm output, an Equalize alarm relay, an Audible alarm relay, or any Alarm
Condition output. If the user “Selects” Alarm Cond, any enabled analog or binary channel's
threshold is made available for the Auxiliary Relay trigger.
The user presses the “Select” key to enter the sub-menu, then “Next” to scroll through the choices.
Pressing “Select” at any point sets the Aux relay to “Energize” when an alarm occurs. Pressing
“Select” again changes it to “De-Energize” (FAIL-SAFE MODE) when an alarm occurs. Pressing
“Select ” third time will disable the Aux relay. When the selection is “Energize” or “De-Energize”
all previous selections are disabled. Pressing “Select” when the Alarm Cond display appears sends
the user to a listing of the enabled analog thresholds and binary channels. The user presses the
“Next” key to scroll through the choices, and the “Select” key to pick one. After making a choice,
press “Escape” to return to the top of the Auxiliary Relay menu.
3.8.10 Backlight Option
The backlight can be configured to turn on only when a key is pressed or to always be on. Pressing
the SELECT key will toggle between “ALWAYS ON”, “KEY ON”, or “OFF” options. When the
backlight is set to “KEY ON” the backlight will turn on when a key is pressed and will extinguish
after 5 minutes of inactivity. The light will also turn on when any alarm condition occurs. The light
will remain on until the alarm extinguishes. When set to “OFF” the backlight will always remain in
the off state.
Use the “Next” key to access the next menu.
3.8.11 About VIGIL
This menu indicates what version of softwa re is in the VIGIL unit. This information is helpful when
contacting Customer Support.
Use the “Next” key to access the next menu.
You can now press “Next” or Previous” to return to any System Options menu. When completed,
press “Escape” again to return to the top of the System Options where “Next” or “Previous“ can be
used to scroll to any Configure menu.
When completed, press “Escape” to return to the “SELECT MODE:” menu. Use “Next” or
“Previous” to reach other menus, or “Escape” again to return to the Idle Display.
PM990-3002-00, Issue 3 3-21
SAGEON VIGIL PRODUCT MANUAL
4 SAGEON VIGIL TEST & VERIFICATION
4.1 Introduction
4.2 Test Analog Channels
4.3 Test Binary Channels
4.4 Test Output Relays
4.5 Test LED’s
4.6 Test LCD
4.7 Test Audible Alert
4.1 INTRODUCTION
The SAGEON VIGIL Test menu provides for comprehensive testing of all input and output functions.
Analog and Binary channels can be continuously monitored to verify operation or troubleshoot the power
plant. The alarm output and control relays can be toggled on & off to verify SAGEON VIGIL or power plant
operation. Testing is provided for the LED display, LCD display, and Audible Alert. These tests turn on all
of the LED’s, LCD segments, or sounds the alert to verify operation.
Caution: The SAGEON VIGIL relinquishes monitoring and control functions while in the test mode. No
alarms are recognized or rectifier control functions initiated while in the Test mode.
The main Test menu is accessed from the idle display screen by pressing “Select”, “Next”, or “Previous” to
access the main menus. Press “Previous” or “Next” until the Select Mode: Test menu appears, then press
“Select” to enter the Test mode. The various test modes are accessed in the following order with the “Next”
key:
1. Analog test mode
2. Binary test mode
3. Output Relay test mode
4. LED ‘LAMP’ test mode
5. LCD test mode
6. Audible Alert test mode
4.2 TEST ANALOG CHANNELS
Press “Select” when the Analog Channels menu appears to enter the analog test mode. The first enabled
analog channel will appear with its current value displayed and updated continuously. The user can press
“Next” or “Previous” keys to move through the list of analog channels. The displayed channel is
continuously monitored until the user moves to another channel.
The analog test mode can be used to troubleshoot the power plant or SAGEON VIGIL connections during
installation. The Test mode can also be used to monitor battery voltage during a battery discharge test,
quickly read and compare FCCP information, or monitor battery and ambient temperature changes.
When completed, press “Escape” to return to the Select Test display. Press “Next” or “Previous” to access
other test modes. Press “Escape” to return to the main menus or the idle display screen.
PM990-3002-00, Issue 3 4-1
SAGEON VIGIL PRODUCT MANUAL
1. Major
7. Temp
13. AUX
2. All
8. Minor
14. EQ
3. VLVA
9. HVA
15. RS
4. LVD
10. LVA
16. HVSD
5. RFA
11. CTRL INH
6. FA
12. CEMF
4.3 TEST BINARY CHANNELS
Press “Select” when the Binary Channels menu appears to enter the binary test mode. The first enabled
binary channel will appear with its current status displayed and updated continuously. The user can press
“Next” or “Previous” to move through the list of binary channels. The displayed channel is continuously
monitored until the user moves to another channel.
The Binary Test mode can be used to verify or troubleshoot the unit during installation/operation.
When completed, press “Escape” to return to the Select Test display. Press “Next” or “Previous” to access
other test modes. Press “Escape” to return to the main menus or the idle display screen.
4.4 TEST OUTPUT RELAYS
Press “Select” when the Output Relays menu appears to enter the output relay test m ode. The first output
relay will appear with its current status “Open” or “Closed” displayed and updated continuously. The output
relays are accessed in the following order using the “Next/Up” key:
Pressing the “Select” key when a specific output relay is displayed will toggle that relay Open (off) or
Closed (on). In the special case of “ALL” relays, all output relays will either be closed or open concurrently.
The user can press “Next” or “Previous” keys to move through the list of output relays channels. The output
relay status will automatically return to its controlled state when the user leaves the output relay test mode.
Note: The front panel alarm LED’s will not indicate relay status in the output relay test mode.
CAUTION: Alarms that are connected to a remote alarm monitor will send false ‘nuisance’ alarm status if
toggled while in the output relay test mode.
Warning: Turning the control relays for Equalize or HVSD on in the test mode will result in the power
plant entering that mode. The power plant rectifiers will be shutdown if the HVSD output
relay is turned on; the rectifiers will also be shut down if the test “ALL” relays option is used.
If the power plant has been commissioned use extreme caution when testing these relays to
make sure that power plant operation will not be adversely affected.
The output relay test mode can be very useful during the power plant test and acceptance to verify operation.
Rectifier response to Equalize, HVSD, and Restart can be checked. External audible or visual monitors can
be tested. Alarm call outs can be verified, etc.
When completed, press “Escape” to return to the Select Test display. Press “Next” or “Previous” to access
PM990-3002-00, Issue 3 4-2
SAGEON VIGIL PRODUCT MANUAL
other test modes. Press “Escape” to return to the main menus or the idle display screen.
4.5 LED TEST MODE
Press “Select” when the display reads LAMP OFF to activate all front panel LED’s at once. All LED’s
should be illuminated. Press “Select” to perform the test again, or press “Escape” at anytime to exit the te s t.
Note: The LED’s test will automatically end after approx. 10 seconds. Press “Select” again, if desired, to
start the test again.
Note: Any LED that is not illuminated indicates a SAGEON VIGIL internal circuitry failure requiring a
service call to repair.
When completed, press “Next” or “Previous” to access other test modes. Press “Escape” to return to the
main menus or the idle display screen.
4.6 LCD TEST MODE
Press “Select” when the display reads “LCDOFF” to activate all of the front panel alphanumeric LCD
segments at once. All of the LCD segments in the 2 by 16 matrix should be on during the test. Each segment
consists of a square of pixels on the screen. Be sure each segment's pixels are on.
Note: The LCD’s test will automatically end after approx. 10 seconds. Press “Select” ag ain, if desired, to
start the test again.
Note: Any LCD segment or pixel that is not illuminated indicates a SAGEON VIGIL internal circuitry
failure requiring a service call to repair.
When completed, press “Next” or “Previous” to access other test modes. Press “Escape” to return to the
main menus or the idle display screen.
4.7 ALERT TEST MODE
Press “Select” when the display reads “ALERT OFF” to activate the internal audible alert buzzer. The
display changes to “ALERT ON”. The Alert should be heard now although it may not be heard in noisy
environments like Central Offi ces.
Note: The Alert test will automatically end after approx. 10 seconds. Press “Select” again, if desired, to
start the test again. No sound coming from the Alert in a quiet environment indicates a SAGEON
VIGIL internal circuitry failure requiring a service call to repair.
When completed, press “Next” or “Previous” to access other test modes. Press “Escape” to return to the
main menus or the idle display screen.
PM990-3002-00, Issue 3 4-3
SAGEON VIGIL PRODUCT MANUAL
5 MAINTENANCE
The SAGEON VIGIL should not require any regular maintenance. Once a year, the analog channel calibration
should be verified against actual measurements. On a 2 to 5 year basis, a complete system test should take place
that checks all alarm and output functions to make sure alarm detection, control functions, and output relays work
properly.
PM990-3002-00, Issue 3 5-1
SAGEON VIGIL PRODUCT MANUAL
(www.unipowerco.com)
6 NETWORK, WEBPAGE, AND SNMP
The SAGEON VIGIL can be monitored remotely via the integral webserver and SNMPv1 agent. Network settings are
configured locally via the VIGIL keypad or via the webpage interface. The default IP address is 192.168.10.74.
6.1 WEBPAGE
Battery voltage, FCCP float current channels, temperature channels, and present alarm status can all be monitored remotely
using the webpage. When using the CELL MONITORING EXPANSION up to 48 battery cells (2V nominal), 4 additional
temperature channels, and up to 4 ‘standard’ current transducer channels can also be monitored.
Note: The default username and password fore the webpage is “admin” and “pw” respectively.
Figure 4. VIGIL webpage
6.2 SNMP
NMS integration can be accomplished using the 115-3006-00.mib file included with the documentation CD.
Trap receivers are enabled and entered through a ‘set’ command via SNMP. The ‘read’ and ‘write’ communities are null by
default, and can be modified via the network settings link at the bo ttom of the webpage. The default username and password
are “admin” and “pw”, respectively.
PM990-3002-00, Issue 3 6-1
SAGEON VIGIL PRODUCT MANUAL
Part Description
Part Numbers
Where Used
Main Processor Board
306-2999-00
+24 or -48 Volt applic at io n s
Display Board
306-3001-04
Keyboard/ LED Assembly
LCD Display
350-8020-00
Alpha numeric 16 x 2 LCD
Display Board Cable
070-4230-07
Ribbon cable J1 to J7
Terminal Block
214-2727-00
12-pos. screw terminal block
Optional equipment:
Temperature Sensor Kit
385-5627-11
30ft. cable. Direct Connect to
contact factory.
Inline fuse, 0.5A Kit
385-2778-11
Protection of VIGIL wiring
Inline Resistor Kit
385-2789-00
Protection of shunt wire
connections
Alternate Scre w Te r minal Block
Pheonix Contact P/N 1850767
Screw terminal block / rear
contact or distr ib u tor .
Analog CELL MONITORING
103-3002-20A
23” Expansion: 48 cells (2V
Part Description
Part Numbers
Where Used
Control Board
306-2998-00
VIGIL Cell Mon. Expansion
Interface board
306-2997-00
VIGIL Cell Mon. Expansion
Mux board (cell)
306-2996-00
VIGIL Cell Mon. Expansion
Screw Terminal Block, 3-pos.
214-2726-03
Power input
connection
Screw Terminal Block, 5-pos.
214-2726-05
Current transducers connection
Screw Terminal Block, 13-pos.
214-2726-13
Analog channels, customer
connection
Communications cable kit
385-8078-12
Communications with SAGEON
VIGIL
Optional equipment:
Temperature Sensor Kit
385-5627-21
30ft. cable. Direct Connect to
temperatures. Longer cable
7 SPARING / ACCESSORIES, OPTIONAL PARTS
SAGEON VIGIL parts can be shipped overnight from the factory for critical replacements if necessary. The
following list of internal parts can be used to order spares or replacements:
VIGIL. Measurement of ambient
or battery string temperatures.
Longer cable lengths available;
EXPANSION
accessable. Prevents having to
remove top terminal block to
access bottom TB screws.
Purchase direct from Pheonix
nominal), 4 temps, 4 current
transducers
connector/Temperature sensors
PM990-3002-00, Issue 3 7-1
VIGIL expansion. Measurement
of ambient or battery string
SAGEON VIGIL PRODUCT MANUAL
lengths available; contact facto ry .
Inline fuse, 0.5A Kit
385-2778-11
Protection of VIGIL wiring
Inline fuse, 2.0A Kit
385-2778-13
Protection of VIGIL wiring
Inline fuse, 3.0A Kit
385-2778-14
Protection of VIGIL wiring
Inline Resistor Kit
385-2789-00
Protection of shunt wire
connections
Current transducer, 200A, open
window
385-5973-200
Battery/Plant current
measurement, 8ft
Current transducer, 400A, open
window
385-5973-400
Battery/Plant current
measurement, 8ft
Current transducer, 600A, open
window
385-5973-600
Battery/Plant current
measurement, 8ft
Current transducer, 200A, split core
385-5974-200
Battery/Plant current
measurement, 8ft
Current transducer 400A, split core
385-5974-400
Battery/Plant current
measurement, 8ft
Current transducer, 800A, split core
385-5974-800
Battery/Plant current
measurement, 8ft
PM990-3002-00, Issue 3 7-2
SAGEON VIGIL PRODUCT MANUAL
8 APPENDIX LISTINGS
8.1 FLOW CHARTS FOR SAGEON VIGIL MENU STRUCTURES
• Appendix A: Main Menus
• Appendix B: Configuration
• Appendix C: Enable Channels Menu
• Appendix D: Enable Thresholds Menu
• Appendix E: Set Thresholds Menu
• Appendix F: Calibrate Zero Menu
• Appendix G: Calibrate Gain Menu
• Appendix H: Set FCCP Scales Menu
• Appendix I: System Options Menu
• Appendix J: Auxiliary Relay Menu
• Appendix K: Test Menu
8.2 REFERENCE DRAWINGS
PN 103-3002-LXX – Part Drawing, SAGEON VIGIL and CELL MONITORING EXPANSION
SD 103-3002-LXX – Schematic Drawing, SAGEON VIGIL and CELL MONITORING EXPANSION
Menu
PM990-3002-00, Issue 3 8-1
SAGEON VIGIL PRODUCT MANUAL
Idle Menus
Select Mode
Description
Idle screen
voltage
Idle screen
voltage
MANUAL
EQUALIZE*
If enabled will show if manual equalization is active, the number of hours
equalization has been both active and the total number of hours.
Main Menu
Submenu
Description
EQ: ON/OFF
0 of XXX Hrs
Main Menu
Status submenu
Description
Temperature reading from the second battery string temperature sensor
(external).
The current reading from FCCP #1
The current reading from FCCP #2
The current reading from FCCP #3
The current reading from FCCP #4
The current reading from FCCP #5
The current reading from FCCP #6
The current reading from FCCP #7
The current reading from FCCP #8
The current reading from FCCP #9
Appendix A: Main Menus
The top level menus of the VIGIL: *This menu will only app ear if enable d. Additional cell mon itoring channels
will also appear if a monitoring expansion is connected.
w/o load
with load
STATUS Shows the latest reading for all enabled analog input channels.
TESTSee appendix K for details. CONFIGSee appendix B for details. ALARMS Shows descriptions for all active alarm outputs.
STATUS Plant Voltage Voltage reading of the Battery or Plant
Ambient Temp* Temperature reading from the ambient temperature sensor (external).
Temp String* Temperature reading from the first battery string temperature sensor (external).
Temp String 2*
Load Voltage* Voltage reading on the load.FCCP 1 FCCP 2*
FCCP 3*
FCCP 4*
FCCP 5*
FCCP 6*
FCCP 7*
FCCP 8*
FCCP 9*
FCCP 10* The current reading from FCCP #10. PCB Temp. The temperature of the VIGIL’s Printed Circuit Board (PCB) Note:
*
Menu will not appear if channel is disabled.
MANUAL
EQUALIZE
Elapsed
Indicates if equalize is currently on or off. The ‘XXX’ represents the number of
hours elapsed on equalize. The “SEL” key toggles equalize on or off.
PM990-3002-00, Issue 3 8-1
SAGEON VIGIL PRODUCT MANUAL
Menu
Submenu
Description
MANUAL EQ
TIME*
SYSTEM
OPTIONS
Submenus allow enabling system password, backlight on/off, aux relay
mapping, choosing equalization/sleep modes.
SET FCCP
SCALES
CALIBRATE
ZEROS
CALIBRATE
GAINS
ENABLE
CHANNELS
SET
Note: * This menu will not exist if the Manual Equalization timer is not
enabled.
Configure Menu
Submenu
Description
MANUAL EQ
TIME*
MANUAL EQ
TIME*
Selecting this menu allows settin g the number of hours a manual equalization
will take to complete.
SYSTEM
OPTIONS
Submenus all ow enabling system password, backlight on/off, aux relay
mapping, choosing equalization/sleep modes.
Appendix B: Configuration Menu
Top level of the CONFIGURE set of menus.
CONFIGURE
NETWORK Configure nework settings: IP address, Netmask, Gateway address, DHCP
THRESHOLDS
ENABLE
THRESHOLDS
Selecting this menu allows setting the number of hours for a manual equalize.
Allows selecting the size of the current FCCPs for all the FCCP inputs.
Allows setting zeros for analog inputs.
Allows setting gains for analog inputs.
Allows enabling/disabling re ading anal og and binary inputs
Allows setting of alarm thresho lds
Enables alarms.
PM990-3002-00, Issue 3 8-2
SAGEON VIGIL PRODUCT MANUAL
Configure Menu
Submenu
Description
ENABLE
CHANNELS
FCCP 3
Enables or disables FCCP 3 input.
FCCP 4
Enables or disables FCCP 4 input.
FCCP 5
Enables or disables FCCP 5 input.
FCCP 6
Enables or disables FCCP 6 input.
FCCP 7
Enables or disables FCCP 7 input.
FCCP 8
Enables or disables FCCP 8 input.
FCCP 9
Enables or disables FCCP 9 input.
FCCP 10
Enables or disables FCCP 10 input.
EXTERNAL LVD
Enables or disables the external low voltage disconnect input .
CEMF CELL 2
Enables or disables the CEMF CELL #2 input.
CTRL INHIBIT
Enables or disables the CTRL IN HIBIT input.
RECT FAIL 2
Enables or disables the rectifier failure # 2 input.
RECT FAIL 3
Enables or disables the rectifier failure # 3 input.
RECT FAIL 4
Enables or disables the rectifier failure # 4 input.
RECT FAIL 6
Enables or disables the rectifier failure # 6 input.
RECT FAIL 7
Enables or disables the rectifier failure # 7 input.
RECT FAIL 9
Enables or disables the rectifier failure # 9 input.
RECT FAIL 10
Enables or disables the rectifier failure #10 input.
RECT FAIL 12
Enables or disables the rectifier failure #12 input.
RECT FAIL 13
Enables or disables the rectifier failure #13 input.
RECT FAIL 14
Enables or disables the rectifier failure #14 input.
RECT FAIL 16
Enables or disables the rectifier failure #16 input.
SPARE FUSE
Enables or disables the spare fuse input.
DISCHG FUSE
Enables or disables the dischg fuse input.
CHARGE FUSE
Enables or disables the charge fuse input.
AMBIENT TEMP
Enables or disables the ambient temperature input.
TEMP STRING 1
Enables or disables the battery strin g 1 temperature input.
TEMP STRING 2
Enables or disables the battery strin g 2 temperature input.
Appendix C: Enable Channels Menu
FCCP 2 Enables or disables FCCP 2 input.
CEMF CELL 1 Enables or disables the CEMF CELL #1 input.
RECT FAIL 1 Enables or disables the rectifier failure # 1 input.
RECT FAIL 5 Enables or disables the rectifier failure # 5 input.
RECT FAIL 8 Enables or disables the rectifier failure # 8 input.
RECT FAIL 11 Enables or disables the rectifier failure #11 input.
RECT FAIL 15 Enables or disables the rectifier failure #15 input.
BATTERY FUSE Enables or disables the battery fuse input.
SENSE FUSE Enables or disables the sense fuse input.
LOAD VOLTAGE Enables or disables the load volta ge input.
Note: Each of these listed channels is either on (enabled), or off (disabled). Note that disabled channels will not appear in
other menus . Plant voltage, FCCP 1 , and PCB Temperature readings are always enab led, and do not show up in this menu.
PM990-3002-00, Issue 3 8-3
SAGEON VIGIL PRODUCT MANUAL
Configure Menu
ENABLE
THRESH.
LOW BAT TEMP S1
Enables/disables the low batte r y string 1 temperature threshold.
HI BAT TEMP S2
Enables/disables the high battery string 2 temperature threshold.
FCCP 2 CURRENT
Enables/disables the FCCP over/under current t hreshold.
LOW VOLTAGE
Enables/disables the low voltage threshold.
Appendix D: Enable Thresholds Menu
SubmenuDescription
HVSD VOLTAGE Enables/disables the high voltage shutdown threshold.
STR 1 TEMP DIFF Enables/disables the battery string 1 temperature Difference threshold
STR 2 TEMP DIFF Enables/disables the battery string 2 temperature Difference threshold
LOW AMB TEMP Enables/disables the low ambient temperature threshold.
HIGH AMB TEMP Enables/disables the high ambient temperature threshold.
LOW BAT TEMP S2 Enables/disables the low battery string 2 temperature threshold.
HI BAT TEMP S1 Enables/disables the high batte r y string 1 temperature threshold .
HI LOAD VOLT AGE Enables/disables the hig h lo a d voltage threshold.
FCCP 1 CURRENT Enables/disables the FCCP over/under current threshol d.
FCCP 3 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 4 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 5 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 6 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 7 CURRENT Enables/disables the FCCP over/under current threshold.
FCCP 8 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 9 CURRENT Enables/disables the FCCP over/under c urrent threshold.
FCCP 10 CURRENT Enables/disables the FCCP over/under current threshold.
HIGH VOLTAGE Enables/disables t he high voltage thres hold.
HIGH CELL VOLTAGE Enables/disables the high cell voltage threshold.
LOW CELL VOLTAGE Enables/disables the low cell volta ge threshold.
VERY LOW VOLTAGE Enables/disables the very low voltage threshold.
PM990-3002-00, Issue 3 8-4
SAGEON VIGIL PRODUCT MANUAL
nfigure Menu
SET
THRESHOLDS
HIGH AMB TEMP
Changes the High Ambient Temperature alarm threshold .
HI BAT TEMP S1
Changes the High Battery String 1 Temperature alarm threshold.
HI/LOW FCCP 1
CURRENT
HI/LOW FCCP 2
CURRENT
HI/LOW FCCP 3
CURRENT
HI/LOW FCCP 4
CURRENT
HI/LOW FCCP 5
CURRENT
HI/LOW FCCP 6
CURRENT
HI/LOW FCCP 7
CURRENT
HI/LOW FCCP 8
CURRENT
HI/LOW FCCP 9
CURRENT
HI/LOW FCCP 10
CURRENT
HIGH VOLTAGE
Changes the High Voltage alarm threshold.
Appendix E: Set Thresholds Menu
Co
HVSD VOLTAGE Changes the High Voltage shutdown alarm threshold.
STR 1 TEMP DIFF Changes the battery string 1 temperature difference alarm threshold.
STR 2 TEMP DIFF Changes the battery string 2 temperature difference alarm threshold.
LOW AMB TEMP Changes the Low Ambient Temperature alarm threshold.
LOW BAT TEMP S1 Changes the Low Battery String 1 Temperature alarm threshold.
LOW BAT TEMP S2 Changes the Low Battery String 2 Temperature alarm threshold.
HI BAT TEMP S2 Changes the High Battery String 2 Temperature alarm threshold.
HI LOAD VOLT AGE Cha nges the Hi gh Load Volt age alarm threshold.
Submenu Description
HIGH CELL VOLTAGE Changes the High Cell Voltage al arm threshold.
LOW VO LT AGE Changes the Lo w Voltage alarm threshold.
LOW CELL VOLTAGE Changes the Low Cell V oltage threshold.
VERY LOW VOLTAGE Changes the Very Low Voltage alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
Changes the FCCP over/under current alarm threshold.
PM990-3002-00, Issue 3 8-5
SAGEON VIGIL PRODUCT MANUAL
Configure Menu
Submenu
Description
CALIBRATE
ZEROS
FCCP CURRENT 1
Remove offset from the FCCP 1 analo g i nput.
AMBIENT TEMP
Remove offset from the "AMBIENT TEMP " ana log input.
TEMP STRING 1
Remove offset from the "TEMP STRING 1" ana l og input.
TEMP STRING 2
Remove offset from the "TEMP STRING 2" ana l og input.
LOAD VOLTAGE
Remove o ffset from the "LOAD VOLTAGE " analog input.
FCCP CURRENT 2
Remove offset from the " FCCP 2" analog i nput.
FCCP CURRENT 3
Remove offset from the " FCCP 3" analog i nput.
FCCP CURRENT 4
Remove offset from the " FCCP 4" analog i nput.
FCCP CURRENT 5
Remove o ffset from the " FCCP 5" analog input.
FCCP CURRENT 7
Remove offset from the " FCCP 7" analog i nput.
FCCP CURRENT 8
Remove offset from the " FCCP 8" analog i nput.
FCCP CURRENT 10
Remove offset from the " FCCP 10" analog input.
Configure Menu
Submenu
Description
CALIBRATE
GAINS
Adjust gai n of the "P LANT VOLTAGE" analog input.
FCCP CURRENT 1
Adjust gai n of the " FCCP CURRENT 1" analog input.
AMBIENT TEMP
Adjust gai n of the "AMBIENT TE MP " analog inp ut .
TEMP STRING 1
Adjust gai n of the "TEMP STRING 1" analog inp ut.
TEMP STRING 2
Adjust gai n of the "TEMP STRING 2 " analog inp ut .
LOAD VOLTAGE
Adjust gai n of the "LO AD VOLTAGE " analog input.
FCCP CURRENT 2
Adjust gai n of the " FCCP CURRENT 2" analog input.
FCCP CURRENT 3
Adjust gai n of the " FCCP CURRENT 3" analog input.
FCCP CURRENT 4
Adjust gain of the " FCCP CURRENT 4" analog input.
Adjust gai n of the " FCCP CURRENT 5" analog input.
FCCP CURRENT 6
Adjust gai n of the " FCCP CURRENT 6" analog input.
FCCP CURRENT 7
Adjust gai n of the " FCCP CURRENT 7" analog input.
FCCP CURRENT 8
Adjust gai n of the " FCCP CURRENT 8" analog input.
Adjust gai n of the " FCCP CURRENT 9" analog input.
FCCP CURRENT 10
Adjust gai n of the " FCCP CURRENT 10" analog input.
Appendix F: Calibrate Zero Menu
PLANT VOLTAGE Remove offse t from the "PLANT V OLTAGE" ana log input.
FCCP CURRENT 6 Remove offset from the " FCCP 6" analog input.
FCCP CURRENT 9 Remove offset fro m the " FCCP 9" analog input.
Appendix G: Calibrate Gain Menu
PLANT VOLTAGE
FCCP CURRENT 5
FCCP CURRENT 9
PM990-3002-00, Issue 3 8-6
SAGEON VIGIL PRODUCT MANUAL
Configure Menu
Submenu
Description
SET FCCP
SCALES
FCCP 2 SCALE
Allows cha nging the ma ximum current rating of the FCCP 2 .
FCCP 3 SCALE
Allows cha nging the ma ximum current rating of the FCCP 3 .
FCCP 4 SCALE
Allows cha nging the ma ximum current rating of the FCCP 4 .
FCCP 5 SCALE
Allows cha nging the ma ximum current rating of the FCCP 5 .
FCCP 6 SCALE
Allows cha nging the ma ximum current rating of the FCCP 6 .
FCCP 7 SCALE
Allows cha nging the maximum current ratin g of the FCCP 7.
FCCP 8 SCALE
Allows cha nging the ma ximum current rating of the FCCP 8 .
FCCP 9 SCALE
Allows cha nging the ma ximum current rating of the FCCP 9 .
FCCP 10 SCALE
Allows cha nging the ma ximum current rating of the FCCP 10.
Configure
Menu
Can choose if backlight stays on, off, or t urns off aft er 5 minute s in the abse nce of
any alarms or keypad input.
SYSTEM
OPTIONS
AUX RE LAY
MENU
Allows selecting an alarm cond ition that will (energize/de-energize) the auxiliary
alarm relay.
EQUALIZE
This menu allows enabling manual equalization and automatic low voltage
TEMP UNITS
Toggle all temperature reading units between °C and °F
NEG. AMPS
Enable/disable the display of a minus sign for all amperage readings.
NEG. VOLTS
Enable/disable the display of a minus sign for all voltage readings.
Appendix H: Set FCCP Scales Menu
FCCP 1 SCALE Allows changing the maximu m current ra ting of the FCCP 1.
Appendix I: System Options Menu
SubmenuDescription
PASSWORD This menu a l lows turni ng the syst em password protection on or off.
ABOUT VIGILShows the software ve rsion of the VIGIL.
BK LIGHT
SYS VOLTS Displays and allows changing the plant volta ge setting.
IDLE DISP Allows choosing FCCP 1, temperature, or toggle between both on the idle screen.
MENU
AUD. ALRM
MENU
equalization.
Allows enabling an audible alarm for a Major, or Minor alarm. Also allows setting
the amount of time the audible confirmation can be disabled in the alarm menu.
PM990-3002-00, Issue 3 8-7
SAGEON VIGIL PRODUCT MANUAL
System Options
Menu
AUX RE LAY
MENU
AUX. RELAY FUNCT
IS: x
Displays whether or not the auxilliary relay function is enabled or
disabled.
Leads to a set of menus for using the auxiliary relay be triggered by any of
a number of different alarm conditions.
‘x’ represents either “enabled”, or “disabled”
Auxiliary Relay
Menu
ALRM COND
MENU
The auxiliary relay maps to the high voltage shutdown alarm.
CTRL. INHIBIT
The auxiliary relay maps to the controller inhibit alarm.
RECT FAIL 1
The auxiliary relay maps to rectifier failure alarm 1.
RECT FAIL 2
The auxiliary relay maps to rectifier failure alarm 2.
RECT FAIL 3
The auxiliary relay maps to rectifier failure alarm 3.
RECT FAIL 15
The auxiliary relay maps to rectifier failure alarm 15.
RECT FAIL 16
The auxiliary relay maps to rectifier failure alarm 16.
ANY RECT FAILU RE
The auxiliary relay maps to any rectifier failure alarm.
SPARE FUSE
The auxiliary relay maps to the spare fuse alarm.
BATTERY FUSE
The auxiliary relay maps to the battery fuse alarm.
SENSE FUSE
The auxiliary relay maps to the sense fuse alarm.
DISCHARGE FUSE
The auxiliary relay maps to the discharge fuse alarm.
CHARGE FUSE
The auxiliary relay maps to the charge fuse alarm.
EXTERNAL LVD
The auxiliary relay maps to the external low voltage disconnect alarm.
CEMF CELL 1
The auxiliary relay maps to the CEMF cell 1 alarm.
CEMF CELL 2
The auxiliary relay maps to the CEMF cell 2 alarm.
The auxiliary relay maps to the battery string 1 temperature difference
alarm.
The auxiliary relay maps to the battery string 2 temperature difference
alarm.
LOW AMB TEMP
The auxiliary relay maps to the low ambient temperature alarm.
HIGH AMB TEMP
The auxiliary relay maps to the high ambient temperature alar m.
LOW BATT TEMP S1
The auxiliary relay maps to the low battery string 1 temperature alarm.
LOW BATT TEMP S2
The auxiliary relay maps to the low battery string 2 temperature alarm.
HI BATT TEMP S1
The auxiliary relay maps to the high batte ry string 1 temperature alarm.
HI BATT TEMP S2
The auxiliary relay maps to the high batte ry string 2 temperature alarm.
HI LOAD VOLTAGE
The auxiliary relay maps to the high load voltage alarm.
FCCP CURRENT 1
The auxiliary relay maps to the FCCP current 1 alarm.
FCCP CURRENT 2
The auxiliary relay maps to the FCCP current 2 alarm.
FCCP CURRENT 3
The auxiliary relay maps to the FCCP current 3 alarm.
FCCP CURRENT 8
The auxiliary relay maps to the FCCP current 8 alarm.
FCCP CURRENT 9
The auxiliary relay maps to the FCCP current 9 alarm.
Appendix J: Auxiliary Relay Menu
SubmenuDescription
ALRM CND x
AUD ALRM x Allows triggering the auxiliary relay if the audible alarm is triggered.
EQUALIZE x Allows triggering the auxiliary relay if equalization is in progress.
MINOR x Allows triggering the auxiliary relay if the minor alarm is active.
M AJ O R x Allows triggering the auxiliary relay if the major alarm is active.
SubmenuDescription
HVSD ALARM
.
.
.
STR 1 TEMP DIFF
STR 2 TEMP DIFF
.
.
.
PM990-3002-00, Issue 3 8-8
SAGEON VIGIL PRODUCT MANUAL
The auxiliary relay maps to the FCCP current 10 alarm.
ANY OVER CURRENT
The auxiliary relay maps to any over current alarm.
HIGH VOLTAGE
The auxiliary relay maps to the high voltage alarm.
LOW VOLTAGE
The auxiliary relay maps to the low voltage alarm.
VERY LOW VOLTAGE
The auxiliary relay maps to the very low voltage alarm.
Select Test
Submenu
ANALOG
CHANNEL
LCD TEST
OFF/ON
Test menu Submenu
Description
ANALOG
CHANNEL
Analog input relays select the battery string 1 temperature voltage
continuously.
Analog input relays select the batte ry string 2 temperature voltage
continuously.
FCCP CURRENT 8*
Analog input relays select the FCCP #8 continuously.
FCCP CURRENT 10
Appendix K: Test Menu
Main Menu
TEST
ALERT OFF/ON Tests buzzer when select is pressed.
LAMP OFF/ON Allows turning on all the LED’s on the front panel when select is pres sed.
OUTPUT RELAYS Allows closing/opening of output relays. See section X.
BINARY INPUTS Allows finding the current stat us of any enab led binar y input. See section X.
AMBIENT TEMP* Analog input relays select the ambient temperature input cont inuously.
TEMP STRING*
TE MP STRING 2*
LOAD VOLTAGE* Analog input relays select the Load voltage continuously.
FCCP CURRENT 1 Analog input relays select the FCCP #1 continuously.
FCCP CURRENT 2* Analog input relays sele ct the FCCP #2 continuously.
FCCP CURRENT 3* Analog input relays sele ct the FCCP #3 continuously.
FCCP CURRENT 4* Analog input relays sele ct the FCCP #4 continuously.
FCCP CURRENT 5* Analog input relays sele ct the FCCP #5 continuously.
FCCP CURRENT 6* Analog input relays sele ct the FCCP #6 continuously.
FCCP CURRENT 7* Analog input relays sele ct the FCCP #7 continuously.
PLANT VOLT AGE Analog input relays select the Plant (battery) voltage continuously.
Description
Allows continuous measurement of any enab l ed analog channel.
Allows one to turn on all the pixels in the L CD when select is pressed.
FCCP CURRENT 9* Analog input relays sele ct the FCCP #9 continuously.
FCCP CURRENT 10* Analog input relays select the FCCP #10 continuously.
PCB Temperature The temperature reading of the VIGIL’s Printed Circuit Board (PCB).
Note: * Will not appear if channel is disabled.
PM990-3002-00, Issue 3 8-9
SAGEON VIGIL PRODUCT MANUAL
Test Menu
Submenu
Description
‘x’ Represents either “CLOSED” (energized), or “OPEN” (de-energized.)
The state of the output relay will toggle when the “select” key is pressed.
Test Menu
Submenu
Description
BINARY
INPUTS
CEMF CELL2
Displays the state of the Counter E le c tro-Motive Force Cell 2 alarm.
Output Relays MAJO R x Indicates if the MAJOR alarm relay is energized.
HVSD x Indicates if the HVSD alarm relay is energized.
RS x Indicates if the RS alarm relay is energized.
EQ x Indicates if the EQ alarm relay is energized.
AUX x Indicates if the AUX alarm relay is energized.
CEMF x Indicates if the CEMF alarm relay is energized.
CTRL INH x Indicates if the CTRL INH alarm relay is energized.
LVA x Indicates if the LVA alarm relay is energized.
HVA x Indicates if the HVA alarm relay is energized.
MINOR x Indicates if the MINOR alarm relay is energized.
TEMP x Indicates if the TEMP alarm relay is energized.
FA x Indicates if the FA alarm relay is energized.
RFA x Indicates if the RFA alarm relay is energized.
EXT LVD x Indicates if the EXT LVD alarm relay is energized.
VLVA x Indicates if the VLVA alarm relay is energized.
ALL x Indicates if all alarm relays are energized.
Note
SENSE FUSE Displa ys the state of the sense fuse alarm.
EXTERN LVD Displays the state of the external low voltage disconnect alarm.
CEMF CELL1 Displays the state of the Counter Electro-Motive Force Cell 1 alarm.
CTRL INHIB Displays the state of the sense fuse alarm.
RFA 16 Displays the state of t he 16th rectifier failure alarm.
RFA 15 Displays the state of t he 15th rectifier failure alarm.
RFA 2 Displays the state of the 2nd rectifier failure alarm.
RFA 1 Displays the state of the 1st rectifier failure alarm.
SPARE FUSE Displays the state of the spare fuse alarm.
BATT FUSE Displays the state of the battery fuse alarm.
DISCH FUSE Displays the state of the discharge fuse alarm.
CHARG FUSE Displays the state of the charge fuse alarm.
Note: Each binary input menu needs to be enabled in order to see it.
…
…
PM990-3002-00, Issue 3 8-10
PROPRIETARY INFORMATION
NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT
PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.
PROPRIETARY INFORMATION
NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT
PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.
PSMC
CURRENT
TRANS.1
CURRENT
TRANS.2
WIRE MARKER LABELS
PROPRIETARY INFORMATION
NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT
PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.
.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.