Uninterruptible Power Supplies PowerWAVE 3000, PowerWAVE 3000TP User Manual

22
PowerWAVE 3000/TP
(10 & 20 kVA)
User Manual
:
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 III
:
Document Control
ISSUE DATE REVISION SUMMARY
TS_604_00 28/06/17 Applied changes from TS_604_00B mark-up and issued as new release document
TS_604_01 05/01/18 Updated specification - heat dissipation
:
Uninterruptible Power Supplies Ltd has taken every precaution to produce an accurate, complete and easy to understand manual and will therefore assume no responsibility nor liability for direct, indirect or accidental personal or material damage due to any misinterpretation of or accidental mistakes in this manual.
© 2017 Uninterruptible Power Supplies Ltd
This manual may not be copied nor reproduced without written permission of Uninterruptible Power Supplies Ltd.
USEFUL CONTACTS
www.upspower.co.uk UPS Limited web site
service@upspower.co.uk Service department – booking service, fault reporting etc.
technical@upspower.co.uk Technical queries
sales@upspower.co.uk Hardware sales
servicesales@upspower.co.uk Extended warranty agreements etc
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 I
Table of Contents
Safety 1
1.1 Description of symbols used in this manual 1
1.2 User precautions 1
1.3 Declaration of Safety conformity and CE marking 2
General Description 3
2.1 Introduction 3
2.2 PowerWave PW3000/TP Model range 4
2.3 Functional description of operation 4
2.3.1 PowerWave PW3000/TP Module block diagram 4
2.3.2 UPS Module operating modes 6
2.3.3 UPS System operating modes 8
2.3.4 Optional operating mode settings 9
2.3.5 Multi-module parallel system operation 9
2.4 PowerWave PW3000/TP User controls 10
2.5 UPS Control panel 12
2.5.1 Status LED indicators 12
2.5.2 LCD Display 12
2.5.3 UPS Control panel operator keys 14
2.5.4 LCD Menu navigation 14
2.5.5 Main Menu 14
2.5.6 Status sub-menu 15
2.5.7 Event Log sub-menu 15
2.5.8 Measurements sub-menu 15
2.5.9 Control sub-menu 16
2.5.10 Identification sub-menu 18
2.5.11 Settings sub-menu 18
2.6 Warranty 22
2.7 Extended Warranty 22
2.8 Additional Service/Maintenance Support 22
Installation 23
3.1 Introduction 23
3.2 Taking receipt of the UPS 23
3.2.1 Site transportation 24
3.3 Unpacking 24
3.4 Storage 25
3.5 Planning the installation (site considerations) 25
3.5.1 Clearances 26
3.6 Planning the installation (cabling considerations) 26
3.6.1 General requirements 26
3.6.2 UPS Cable and fuse sizing 27
3.6.3 Power cabling for a parallel system 27
3.6.4 UPS Terminal block connection details 28
3.6.5 Input/bypass supply configuration options 28
3.7 Connecting the UPS power cables 29
3.7.1 Power cabling procedure 29
3.7.2 Three phase dual input cabling details 30
3.7.3 Three phase single input cabling details 31
3.7.4 Single phase dual input cabling details 32
3.7.5 Single phase single input cabling details 33
3.8 Battery cabling procedure 34
3.8.1 Internal battery connections 34
3.8.2 External battery cabinet cabling procedure 35
3.9 Multi-cabinet configuration and paralleling cables 35
3.10 Optional remote monitoring and control facilities 35
Operating procedures 36
4.1 Introduction 36
4.1.1 Operating procedure summary 36
4.2 Single module start-up – with mains supply 37
4.3 Single module start-up – without mains supply 37
4.4 Single module – changing the operating mode 38
4.5 Single module shut down – with mains supply present 38
4.6 Single module shutdown – with UPS on battery 38
4.7 Single module – using the internal maintenance bypass 39
4.8 Parallel module system procedures 40
4.9 Parallel system start-up 41
4.10 Parallel system – changing the operating mode 41
4.11 Parallel system – start/stop one module 42
4.12 Parallel module complete system shut-down 43
4.13 External Maintenance Bypass operation 44
4.14 Operating a frequency changing system 45
4.14.1 Frequency changer – starting the UPS 45
4.14.2 Frequency changer – stopping the UPS 45
4.15 Emergency Stop 46
Maintenance 47
5.1 Introduction 47
5.2 System calibration 47
5.3 User responsibilities 47
5.4 Routine maintenance 47
5.5 Battery testing 48
5.6 Battery maintenance 48
5.7 Battery disposal and recycling 48
Troubleshooting 49
6.1 Contacting Service 49
6.2 Fault identification and rectification 50
6.2.1 Troubleshooting without an error message 50
6.2.2 Troubleshooting based on error message 50
Options 52
7.1 Back-feed protection 52
7.2 Emergency Power-OFF (EPO) 53
7.3 Computer communication options. 53
7.3.1 USB Port 53
7.3.2 RS232 Port.RS232 and USB Communication options 54
7.4 Serial Network Management (SNMP) card 54
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 III
:
7.5 AS400 Interface card 55
7.6 UPS Monitoring and automated control software 56
7.6.1 The importance of UPS management 56
Specifications 57
:
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 1
1
Safety
1.1 Description of symbols used in this manual
1.2 User precautions
WARNING: The warning symbol is used where there is danger of an electrical shock, equipment damage or
personal-injury.
CAUTION: The caution symbol is used to highlight important information to avoid possible equipment malfunction or damage.
WARNING: Keep this manual with the UPS for future reference.
WARNING: The UPS and peripheral equipment must be installed and commissioned by suitably qualified and
trained personnel who are aware of the potential shock hazards.
WARNING: Do not attempt to install this UPS system until you are satisfied that ALL the safety instructions and hazard warnings contained in this manual are read and fully understood.
WARNING: High leakage current! Ensure that the UPS has been correctly earthed before you connect the mains power supply!
WARNING: This UPS must not be started-up or put into use without having first been commissioned by a fully trained engineer authorised by the manufacturer.
WARNING: This UPS must be serviced by qualified personnel. You run risk of exposure to dangerous voltages by opening or removing the UPS-covers! Uninterruptible Power Supplies Ltd will assume no responsibility nor liability due to incorrect operation or manipulation of the UPS.
WARNING: The PowerWave PW3000/TP is a Class A UPS product (according to EN 62040-3). In a domestic environment the UPS may cause radio interference. In such an environment the user may be required to undertake additional measures.
1: Safety
1.3 Declaration of Safety conformity and CE marking
The PowerWave PW3000/TP UPS system is designed and manufactured in accordance with Quality Management Systems standard EN ISO 9001. The CE marking indicates conformity to the EEC Directive by the application of the following standards in accordance with the specifications of the harmonized standards:
• 2006/95/EC Low voltage directive
• 2004/108/EC Electromagnetic Compatibility directive (EMC)
Standards as reference:
• EN-IEC 62040-1 – Uninterruptible power supply (UPS). Part 1-1: General and safety requirements for UPSs used in accessible areas by end users.
• EN-IEC 60950-1 – IT equipment. Safety. Part 1: General requirements
• EN-IEC 62040-2 – Uninterruptible power supply (UPS). Part 2: EMC requirements
• EN-IEC 62040-3 – Uninterruptible power systems (UPS). Part 3: Performance and test requirements
• 2011/65/EU – Restriction of the use of certain hazardous substances (RoHS) DIRECTIVE
The supplier's responsibility is excluded in the event of any modification or intervention in the product carried out be the customer.
Table 1.1 Standards
Product Standards Standards
Safety EC/EN 62040-1 EC/EN 60950-1
Electromagnetic Compatibility (EMC) IEC/EN 62040-2 (C1) IEC/EN 61000-4-2
IEC/EN 61000-4-3 IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6 IEC/EN 61000-4-8 IEC/EN 61000-2-2
RoHS EN50581:2012 EN50581:2012
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 3
2
General Description
2.1 Introduction
Congratulations on your purchase of the PowerWave PW3000/TP UPS.
Continuous power availability is essential in today’s dynamic IT and process-related work environments. It is equally important that any installed power protection system is sufficiently resilient and adaptable to handle any changes brought about by the introduction of new server technologies, migration and centralization.
Such demands are well met by the PowerWave PW3000/TP UPS system which provides the foundation for continuous power availability of network-critical infrastructures both in enterprise data centres, where business continuity has paramount importance, and in process control environments where manufacturing continuity is essential.
Reliability and quality standards
By using a unique modular construction and incorporating the latest technological developments in power engineering, the PowerWave PW3000/TP represents a completely new generation of transformerless 3 phase UPS-System. Its advanced double conversion VFI (Voltage and Frequency Independent) topology responds fully to both the highest availability and environmentally friendly requirements compliant with IEC 62040-3 (VFI-SS-111) standards. A full UPS Specification is contained in Chapter 8 of this manual.
Uninterruptible Power Supplies Ltd specialises in the installation and maintenance of Uninterruptible Power Systems; and this powerful UPS is just one example of our wide range of state-of-the-art power protection devices that will provide your critical equipment with a steady and reliable power supply for many years.
Key features
In addition to its high reliability, upgrade ability, low operating costs and excellent electrical performance the key features of the PowerWave PW3000/TP include the following:
• Energy savings thanks to 93% AC-AC efficiency, 97% efficiency in ECO mode
• Low harmonic distortion (< 5% THDi) and active power factor correction (0.99 input PF) eliminates interference from other network equipment
• Paralleling and redundancy capability – up to 4 units can be connected in parallel to increases the overall system capacity and availability.
• Integrated automatic and manual bypass simplifies maintenance and reduces need for external switchgear.
• Frequency converter operation to convert 50 to/from 60 Hz
• Compact solution that can achieve 5-16min runtime with internal batteries
• Supports different wiring schemes: three-phase and single-phase input as well as single and dual input feed
• Matching external battery cabinet available for extended autonomy time
2: General Description
2.2 PowerWave PW3000/TP Model range
The PowerWave PW3000/TP range comprises 10kVA and 20kVA UPS models, contained in identically sized cabinets. Depending on the required autonomy time, the UPS batteries can be housed within the UPS cabinet (with various battery arrangements) or housed in a purpose designed and matching battery cabinet which can be installed adjacent to the UPS cabinet to form an aesthetically pleasing suit. Although the UPS produces a single-phase a.c. output, it can be connected to either a single or three phase input supply. It can also be used in a frequency changer role with 50Hz/60Hz input/output or vice versa.
Up to four UPS cabinets can be connected in parallel to increase the overall system output capability or introduce a level of module redundancy to further enhance the system availability
Table 2.2 PowerWave PW3000/TP Cabinet specifications
2.3 Functional description of operation
This section describes:
• The internal operation of an individual UPS power module at block-diagram level
• The various operational modes of an individual UPS power module
• UPS system operational modes – ‘On-line’ versus ‘Off-line’ system operation
• Multi-module system operation and paralleling considerations
2.3.1 PowerWave PW3000/TP Module block diagram
Figure 2.1 PowerWave PW3000/TP UPS block diagram
UPS Mains input supply
The UPS mains input can be connected to a 3ph+N or 1ph+N supply. It is connected to the Rectifier/DC Converter via the ‘Mains 1’ (M1) input breaker and a fuse on the Input RFI Filter. If a single phase input supply is used, the three input line terminals are linked together and the contacts of the input breaker (M1) are effectively paralleled.
Key Point: In a parallel system ALL the connected modules must be of the same output rating – i.e. it is not permissible to combine 10kVA and 20kVA cabinets in a parallel system.
10kVA 20kVA
Maximum power connection kW/kVA 9.0/10 18/10
UPS Cabinet Dimensions (WxHxD) mm 350 x 890 x 712 350 x 890 x 712
UPS Cabinet Weight excluding batteries kg 56 66
UPS Cabinet Weight including batteries (5 mins /16 mins) kg 117 / 177 187 / NA
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
Maintenance Bypass Line Maintenance Bypass Switch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
BATTERY
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 5
2: General Description
UPS Bypass input supply
A single phase bypass supply is connected directly to the Maintenance Bypass Switch and also to the bypass side of the static switch, via the ‘Mains 2’ (M2) breaker and a fuse on the Input EMI Filter. In a standard installation the bypass input terminals are usually linked to the mains input supply L1 terminal, so only one mains supply feed is required. This is often referred to as a ‘Single Feed’ input configuration, as opposed to a ‘Dual Feed’ input where a separate bypass supply is used. (See paragraph 3.7 for details concerning ‘Single Feed’ & ‘Dual Feed’ supply configurations.)
Battery charger
The battery charger can be powered from either the Mains Input or Bypass Input supply, and charges the internal (or optional external) batteries when either of these supplies is present. It’s power source is selected by a relay which automatically switches over to the Bypass Input supply when the Mains Input is not available. The charger is rated at 2A but can be increased to 4A if required, depending on battery topology.
Rectifier / DC Converter
The Rectifier / DC Converter produces a controlled DC voltage for the Inverter input. This can be sourced either from the UPS Mains input supply (AC) of from the battery (DC). An automatic changeover switch ensures that the two sources are never connected to the Rectifier /DC Converter simultaneously, with the UPS Mains input always being accepted as the preferred source provided it remains within specified limits.
Power Inverter
A single phase Inverter converts its DC input from the Rectifier / DC Converter into the required UPS output AC supply. The output voltage is tightly regulated using advanced PWM techniques and the output frequency is similarly controlled. Usually, the inverter operates at the same frequency as the UPS input/bypass supply; however, the UPS can be operated in a frequency-changing mode whereby the input and output frequencies are different – e.g. 50Hz/60Hz input/output. Note that when used as a frequency-changer, the UPS bypass circuit is automatically inhibited.
Static switch
The static switch block contains two static switches connected across a load transfer relay, one is connected to the bypass supply and the other to the inverter output. When the load is transferred between the bypass and inverter the appropriate static switch turns on for a brief period to maintain the load supply while the load transfer relay operates. The microprocessor system automatically controls the load transfer between inverter/bypass sources as dictated by local conditions (e.g. overload) and provides a means of performing a manual load transfer.
Output relay
The output relay is used to connect/disconnect the UPS output in a parallel module system, and enables the UPS to be quickly isolated from the system in the event of a UPS fault.
Maintenance bypass switch
The Maintenance Bypass Switch connects the UPS AC Output terminals directly to the Bypass Input and provides a means of temporarily supplying the load from the raw mains while the UPS is otherwise shut-down for maintenance repair. It operates in a make-before-break fashion to ensure the load is supported during the transfer.
In order to protect the UPS inverter, the load must be transferred to the static bypass supply before the Maintenance Bypass Switch is closed – this is performed automatically when the Maintenance Bypass Switch access cover is removed.
When the load is connected via the maintenance bypass the UPS can be shut down safely for repair, with the only remaining live areas within the UPS being the input/output power connections and isolators.
UPS AC Output (load) supply
Figure 2.1 shows that the UPS output (Load Supply) can be provi
ded through one of three power paths depending on the
UPS operating mode – the criteria for operating under each of these UPS modes is described in 2.3.2:
• From the inverter, via the inverter-side static switch and output relay
• From the static bypass line via the bypass-side static switch and output relay
• From the maintenance bypass line via the maintenance bypass switch
2: General Description
2.3.2 UPS Module operating modes
All the diagrams in this section depict a single UPS cabinet. Where two or more cabinets are operating as a parallel system they will always adopt the same operating mode due to their parallel control logic signals.
Load on Inverter
Figure 2.2 Load on inverter
This is the normal operating mode and the only one that provides the load with continuously processed and backed-up power. In this mode, the mains supply is converted to controlled DC by the Rectifier/DC Converter then converted back to the rated AC output voltage by the Inverter and connected to the load via the inverter side of the static switch.
The inverter output frequency is synchronised to the bypass supply provided it remains within preset limits; and if these limits are exceeded, or if the bypass supply fails altogether, the inverter frequency control reverts to a free-running oscillator that will produce a constant 50Hz (or 60Hz) UPS output.
Load on Battery
Figure 2.3 Load on battery
If the mains supply fails, the rectifier will shut down and the battery will provide an alternative DC power source for the inverter via the DC converter. The yellow ‘Battery’ led will illuminate on the control panel to indicate that it is on load and a ‘ON BATTERY’ status indication will be displayed on the LCD, accompanied by an audible alarm.
In the case of a dual feed input – if the bypass supply remains live the inverter frequency will remain synchronised to the
bypass provided it stays within its preset limits.
In the case of a single feed input – the bypass supply will fail at the same time as the mains supply and under these
circumstances the inverter frequency will revert to a free-running oscillator that will produce a constant 50/60Hz output.
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
Maintenance Bypass Line Maintenance Bypass Switch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
BATTERY
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
BATTERY
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
Maintenance Bypass Line Maintenance Bypass Switch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 7
2: General Description
Some installations include a standby generator which is designed to start-up automatically and provide an alternative UPS power input within a short period following a mains failure. Once the UPS input power is restored from the standby generator, the rectifier and charger will resume normal operation.
Battery discharge operation
As the battery discharges, various options are available to automate the load shut-down process, as described in Chapter 8 of this manual.
A SHUTDOWN IMMINENT alarm indicates when the battery is almost exhausted, with approximately 3 minutes autonomy time remaining, and if a data protection application is installed it will begin its automatic PC shut down routine at this point. When the battery reaches its fully discharged voltage the UPS will attempt to transfer the load to the bypass supply but if the bypass supply is unavailable then the UPS will totally shut down.
Load on Bypass
Figure 2.4 Load on bypass
In the ‘load on bypass’ mode the UPS AC Output is connected to the unprocessed static bypass line via the bypass side of the static switch.
During normal operation the load will be transferred from the inverter to the static bypass line in the event of an inverter fault, output overload, or loss of system redundancy due to a failed module in a parallel module system. Load transfer can also be initiated manually via the UPS control panel.
Depending on the reason for the load being transferred to bypass (i.e. manually transferred or transferred due to a fault), The Rectifier/DC Converter and Inverter power blocks might turn off or remain running.
Load on Maintenance Bypass
Figure 2.5 Load on maintenance bypass
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
Maintenance Bypass Line Maintenance Bypass Switch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
BATTERY
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
MaintenanceBypass Line Maintenance Bypa ssSwitch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
BATTERY
2: General Description
In this mode of operation the manually closed maintenance bypass switch connects the UPS AC Output directly to the unprocessed bypass supply. This is used to keep the load supplied, albeit without any power protection, whilst allowing the remainder of the UPS system to be shut down for service repair.
To prevent possible inverter damage, it is important that the inverter output and maintenance bypass lines are never connected in parallel. Therefore when transferring from the ‘load on inverter’ mode to the ‘load on maintenance bypass’ mode it is important that the load is first transferred to the static bypass (‘load on bypass’ mode) before the maintenance bypass switch is closed.
2.3.3 UPS System operating modes
The previous section described the internal operating modes of an individual UPS module: but UPS systems are also categorised according to the way in which they are used at a ‘system’ level; and are typically described as being an ‘on­line’, ‘off-line’ or ‘line interactive’ UPS system. The PowerWave PW3000/TP can be operated in all three categories.
On-line operation
When used as an ‘on-line’ UPS system, the PowerWave PW3000/TP UPS normally operate in its ‘load on inverter’ mode and will automatically change over to ‘load on bypass’ in the event of an inverter fault or overload. The bypass-side static switch will transfer the load to the bypass supply without interruption (transfer time = 0).
If the transfer is due to an overload the UPS will attempt to switch back to the ‘load on inverter’ mode if the overload clears while on bypass, and the inverter returns to normal operation. An ‘on-line’ system therefore provides the highest degree of load protection and is always recommended if the critical load will not tolerate even a very brief supply interruption.
If the load fails to successfully re-transfer to inverter three times within ten minutes, further transfer attempts will be locked out – the load will remain on bypass and a warning message will appear on the LCD screen.
Off-line and line interactive operation (HE / ECO mode)
When the PowerWave PW3000/TP is used as an ‘off-line’ or ‘line-interactive’ UPS system it normally operates in the ‘load on bypass’ mode with the load being supplied through the static bypass supply; however the rectifier/DC Converter and battery charger are still powered up to maintain battery charging, and the inverter section is enabled and on standby.
Figure 2.6 ECO (Off-line) mode of operation
If the bypass input supply fails, the static switch will automatically transfer the load to the inverter within 3-5ms; and if the rectifier’s mains input supply is missing when the transfer takes place the inverter will operate immediately from battery power (‘load on battery’ mode). When the bypass supply returns to normal, the load automatically transfers back to the static bypass line (‘load on bypass’ mode) and the inverter returns to its standby operation.
An ‘off line’ system is a slightly more efficient than an ‘on-line’ system due to the reduced rectifier/inverter losses during normal operation, and for this reason it is sometimes referred to as the ‘High Efficiency (HE)’ or ‘Economy ECO’ mode.
WARNING: always follow the operating instructions in this manual when starting or shutting down the UPS.
RECTIFIER /
DC CONVERTER
INPUT
EMI
FILTER
OUTPUT
EMI
FILTER
POWER
INVERTER
STATIC SWITCH
Mains
Input
External
Battery
(Option)
Bypass
Input
UPS AC Output
Static Bypass Line
M1
M2
Maintenance Bypass Line Maintenance Bypass Switch
Automatic Batt. Switch
Output
Relay
CHARGER
Charger Relay
BATTERY
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 9
2: General Description
2.3.4 Optional operating mode settings
The above descriptions refer to the UPS operation in what can be considered to be a ‘standard’ installation. However, the operation can be modified to suit local conditions, or particular load supply requirements, by adjusting the selected values in the LCD SETTINGS sub-menu, as shown in Figure 2.17.
Note: These settings are password-protected and can only be changed by authorised service personnel.
Auto Restart
If the input mains supply fails, and no bypass mains supply is available, the UPS will operate on-battery and shut down when the battery reaches its end of discharge voltage, or immediately if the battery is disconnected. The Auto restart setting determines whether or not the UPS restarts automatically following the return of the input mains.
The default value for Auto restart is [Enabled]. This means that if the UPS shuts down following a mains failure it will restart automatically and return the load to the inverter when the mains supply returns. If Auto restart is [Disabled] the UPS will have to be restarted manually.
Note: If the UPS shuts down due to an overload, an automatic restart can be [
Enabled
] or [
Disabled
] by setting the
separate
Automatic overload restart
parameter.
Auto Bypass
In a ‘standard’ installation the load will be transferred to the bypass supply (if available) if the inverter shuts down due to an overload, inverter fault or a fully discharged battery when operating on battery power. However, in areas where the mains supply is unstable the automatic transfer to bypass function can be inhibited by setting the Auto bypass to [Disabled].
Note: If
Auto bypass
is [
Disabled
] the UPS will shut down (and drop the load) when it is operating on battery power
and the battery reaches its end of discharge voltage.
Short Circuit Clearance
This parameter determines how the UPS reacts to a short circuit on its output.
If a short circuit is detected the inverter will limit its output current to 100% by reducing its output voltage – once the short circuit is cleared the output current will fall below 100% and the output voltage will return to normal.
By default the Short circuit clearance is set to [Disabled], and in this case the inverter will continue to supply 100% load for 100 ms. After this time the UPS is shut down if its output voltage is still <50%
If Short circuit clearance is [Enabled], the inverter short circuit clearance time is extended to 4 seconds.
2.3.5 Multi-module parallel system operation
To expand the overall UPS system rating, up to four PowerWave PW3000/TP UPS cabinets can be connected together to operate as a parallel UPS system. This is achieved by connecting each cabinet’s output power terminals in parallel at an external load distribution panel and linking together the parallel control bus in each cabinet to effectively provide a common parallel control bus. The parallel control bus cable is connected to a socket located near the top rear of the cabinet which is covered by a blanking plate when not used (item 12 in Figure 2.7).
It is essential that any installed UPS power protection system can be expanded to meet a growing load demand without compromising the existing load supply. This situation is easily managed by a PowerWave PW3000/TP system which makes it possible to add a further cabinet to an existing UPS system without disrupting the load supply.
Note: Every PowerWave PW3000/TP cabinet is supplied with all the features required for parallel operation to eliminate
any need for time-consuming or expensive upgrading on site.
WARNING: This mode is recommended only if the connected load equipment can tolerate a power interruption of up to 3 to 5 ms during the transfer period. The ‘on-line’ mode must always be used for critical load protection.
2: General Description
‘Capacity’ versus ‘redundant module’ system
The paralleled UPS modules can be operated as either a capacity or redundant module system. The difference between
the two is that a ‘capacity’ system is rated such that ALL the UPS modules are required to furnish the specified full load power, whereas a ‘redundant-module’ system is designed with one (or more) UPS module over and above that required to supply the full load.
In a redundant-module system it is therefore possible to lose one (or more) UPS module without disrupting the load, whereas this is not the case in a capacity system, where the loss of one UPS module would automatically transfer the load to the bypass supply.
Parallel control bus
All the UPS modules within are connected to a parallel control bus which carries various inter-module control signals used for frequency synchronisation, load sharing etc. By using sensing signals passed over the parallel control bus, each module can electronically compare its own frequency and output current with that of its neighbouring module and carry out fine adjustments to achieve balanced conditions.
2.4 PowerWave PW3000/TP User controls
The following illustrations show the location of the PowerWave PW3000/TP power switches and fused isolators that are used when operating the equipment. The control panel is described in paragraph 2.5 and the various optional input/output connecting facilities are described in Chapter 7.
Figure 2.7 PowerWave PW3000/TP Controls identification
1414
10/20 kVA Front View 10 kVA Back View 20 kVA Back View
1
2
3
4
5 5
6
7
8
9
10 11
12
14
5
6
7
8
9
10 11
13
14
17 17
13
12
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 11
2: General Description
Figure 2.8 PW3000/TP Matching battery cabinet
1
Operator Panel LCD Display
2
Operator Panel LEDs
3
Operator Panel Control Keys
4
Ventilation inlets
5
Power terminal block cover
6
Mains and Bypass input supply circuit breakers
7
Backfeed protection connection terminals
8
Cooling extractor fans
9
AS400 Interface slot
10
Emergency Power Off (EPO) contact
11
RS232 port / USB port
12
Parallel port (for parallel control bus cable)
13
SNMP Interface slot
14
Maintenance Bypass Isolator cover plate
15
Battery fuses
16
Battery terminal connection cover
17
Wheel, support brackets and brakes
Battery Cabinet Front View
4
Battery Cabinet Back View
16
15
4
17
17
17
17
2: General Description
2.5 UPS Control panel
The UPS Control panel contains four status LED indicators, an LCD display and a row of selection keys which include an ON/OFF key and three navigation keys. The navigation keys are used in conjunction with various monitoring and configuration menus.
2.5.1 Status LED indicators
The four LEDs located along the top of the UPS Control panel indicate the UPS operating status and may FLASH or remain constantly OFF or ON. Under some circumstances all five LEDs will illuminate in turn in a ‘rotating’ sequence.
The following table illustrates the LED states for various operating conditions – an ‘X’ indicates that the state is undefined and depends on the failure or warning mode.
Table 2.3 Status LED interpretation
2.5.2 LCD Display
A complete overview of the UPS operating status including the input, output, battery and load parameters is provided by the LCD display.
Under normal operating conditions the display shows white text on a blue back-light but under fault conditions this changes to dark text on an orange back-light, accompanied by an audible warning, as shown in the adjacent table.
Default Screen
During start up the LCD Display shows a ‘Welcome’ logo screen for around 5 seconds while the UPS initialises then changes to the ‘default status’ screen shown is Figure 2.10. The ‘default status’ screen is shown automatically during normal operation if the control panel keys are not operated for 15 minutes.
UPS STATUS NORMAL (green) BATTERY (amber) BYPASS (amber) FAULT (red)
Bypass Mode / with no output power FLASH X
Bypass Supply abnormal FLASH
Bypass Mode / with output power ON X
UPS Turning ON SEQUENCE SEQUENCE SEQUENCE SEQUENCE
On-line mode ON X
On-battery mode ON ON X
ECO mode (HE Mode) ON ON X
Battery Test mode SEQUENCE SEQUENCE SEQUENCE SEQUENCE
Fault mode XON
Warning XXXFLASH
Status
LCD
Selection
LEDs
Display
Keys
Figure 2.9 UPS Control Panel
UPS Condition Buzzer Status
Active failure Continuous
Active warning Beep once per second
UPS on Battery Beep every four seconds
Low Battery Beep every second
On Bypass Beep every two minutes
Overload Beep twice per second
Table 2.4 Audible warnings
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 13
2: General Description
The default screen provides the following information:
• UPS input parameters – including an indication of the mains/bypass input voltage, and frequency
• UPS status – a symbolic indication of the UPS operating mode and fault/abnormal conditions. A list of status symbols is described in Table 2.5.
• Battery status – including the battery voltage and a graphical indication of the available battery charge
• Load status – graphical and numerical percentage indication of the connected UPS load
• UPS output – including an indication of output voltage, frequency and load power (W)
Default Screen status symbols
Table 2.5 Default Screen status symbols
Symbol Status Description
ON-LINE UPS is operating with the load supplied by the inverter.
ON BATTERY UPS is operating from battery power, usually due to a mains failure.
ON BYPASS UPS is operating with the load supplied from the bypass mains power.
Note: if there is a bypass supply failure while the UPS in on bypass, it will not transfer to ON LINE or ON-BATTERY mode unless it is operating in the ECO-mode – also known as High Efficiency (HE) mode.
ECO Mode (HE mode)
UPS is operating with the load supplied from the bypass mains power. In case of bypass mains failure, the UPS transfers to ON LINE mode or ON BATTERY mode and the load is supplied continuously.
ECO-mode can be enabled/disabled through the control panel Settings
menu or the UPS monitoring/control software.
CONVERTER mode UPS is set to operate with a different input and output frequency – either
50Hz-60Hz or 60Hz-50Hz. In case of input mains power failure, the bypass is inhibited and UPS transfers to ON BATTERY mode.
WARNING UPS is operating in the presence of an abnormal condition that does not
call for the UPS to be shut down. See the Troubleshooting chapter for details.
FAULT The UPS has experienced a fault condition. It may disconnect the load
or transfer the load to bypass depending on the type of failure. In all cases, there will be a constant alarm and the LCD back-light will become red. See the Troubleshooting chapter for details.
OVERLOAD UPS is overloaded. The load should be reduced to <90% of the UPS
rated capacity in order to stop the alarm.
BATTERY TEST UPS is performing a battery test.
BATTERY
DISCONNECTED
UPS battery is disconnected or defective – accompanied by an alarm.
Mains
288V
v v v
HZ
HZ
W
v
100%
220 220 220
220
50
9000
50
Output
Battery
UPS Status
Mains and
Bypass Input
Information
UPS Output
Information
Load
Information
Information
Figure 2.10 LCD Panel Default Screen
!
2: General Description
14 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
2.5.3 UPS Control panel operator keys
Table 2.6 UPS Control panel operator keys
2.5.4 LCD Menu navigation
All the UPS control, monitoring and configuration functions are actioned through a series of menus displayed on the LCD and navigated using the control panel keys described in Table 2.6.
2.5.5 Main Menu
As shown in Figure 2.11, the main (top level) menu is accessed from the Default screen by pressing the UP key for greater than 1 second. It presents 6 options; Status, Event log, Measurements, Control, Identification and Settings which can be scrolled through using the UP/DOWN keys.
Each Main Menu option has an associated sub-menu which can be accessed by briefly pressing the SELECT key.
To return to the Default screen from any point in the menu tree, you must press the ON/OFF key for less than one second.
Each of the Main Menu options is described below.
Operator
KEY
Function Operation
Power ON / OFF
EXIT MENU
Press for 1s to turn ON the UPS. Press for >3s to turn OFF the UPS or change the UPS operating mode between ‘on­line’ and ‘on-bypass’. Press for <1s to exit a menu and return to the default status screen.
SCROLL UP From the default status screen, press for >1s to access the Main Menu.
Within a sub-menu press for <1s to scroll UP through the current menu options.
SCROLL DOWN From default status screen, press for <1s to access the Status sub-menu.
Within a sub-menu press for <1s to scroll DOWN through the current menu options.
SELECT / EDIT This key is used when editing the value of a parameter in the setup/configuration
menu screens. If pressed for less than one second it accepts the entered value and if pressed for more than one second it saves the setting and exits the screen.
Key Point: In the following description of the menu navigation system the keys will be described as ON/OFF, UP, DOWN and SELECT.
CAUTION: When pressing the ON/OFF button to exit a menu take care not to hold the key pressed for longer than 3 seconds otherwise it will turn off the inverter and transfe r the load to bypass.
Mains
288V
v v v
HZ
HZ
W
v
100%
220 220 220
220
50
9000
50
Output
>1s
<1s
Measurements
Event Log
Status
Identification
Control
Settings
Figure 2.11 Menu navigation – Main Menu
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 15
2: General Description
2.5.6 Status sub-menu
The Status sub-menu is slightly different from the other sub­menus in that it can be accessed from two points: by selecting the Status option in the Main Menu or directly from the Default screen by briefly pressing the DOWN key. The Status Sub-menu shows the following:
Alarm
Displays a list of any active alarms (an alarm history can be obtained via the Event Log menu described below). Normal indication is <No alarm>
Battery
The Battery menu displays:
• Battery Volt: <XXX V>
• Battery charge regime (e.g. <floating>)
• Charge level: XX%
Status and running time
This menu displays:
• Status: <Line Mode / Combo 3/1> Indicates 3ph input and 1ph output and UPS is on-line
• Para Num: <X> Indicates the number of parallel modules
• Running Time: <XXXX:XX:XX:XX> Indicates the time for which the module has been running (Days: Hrs: Mins: Secs)
2.5.7 Event Log sub-menu
The Event Log displays a date/time stamped list of the 50 most recent warning and fault events. Fault events are identified by a corresponding event code. To access the Event Log you must highlight the Event Log option in the Main Menu then press the SELECT key for longer than one second. This offers two further sub-menu options, from which you can choose to view either Warnings or Faults. Once accessed, using the SELECT key, you can scroll through the log entries using the UP/DOWN keys. To exit the Event Log screen you must press the ON/OFF key for less than one second.
2.5.8 Measurements sub-menu
The Measurements menu allows various UPS operating parameters to be observed, as shown in Figure 2.13.
To access the Measurements sub-menu you must highlight the Measurement option in the Main Menu then press the SELECT key for longer than one second. This opens the Measurements sub-menu screen which allows you to scroll through and observe the monitored parameters using the UP/DOWN keys.
To exit the Measurements sub-menu either press the UP key for longer than one second to return to the Main Menu or press the ON/OFF key for less than one second to return to the default screen.
Mains
288V
v v v
HZ
HZ
W
v
100%
220 220 220
220
50
9000
50
Output
Alarm
Battery
Status and
running time
>1s
Status Sub-menu
<1s
<1s
Measurements
Event Log
Status
Identification
Control
Settings
Figure 2.12 Menu navigation – Status Menu
Output power (W) Output power (VA) Output current (A) Load percentage (%) Output voltage (V) Output frequency (Hz) Input voltage (V) Input frequency (Hz) Bypass voltage (V) Bypass frequency (Hz) Battery voltage (V) Battery capacity (%) DC Bus voltage (V) Temperature (deg. C)
<1s
Measurements
Event Log
Status
Control
Identification
Settings
Figure 2.13 Menu navigation – Measurements
2: General Description
16 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
2.5.9 Control sub-menu
The Control menu allows various UPS operating features to be set.
There are two versions of the Control sub-menu depending on whether the UPS is operating as a single module installation or is part of a parallel module system. The single module version is shown in Figure 2.14 and the multi-module version in Figure 2.15.
To access the Control sub-menu you must highlight the Control option in the Main Menu then press the SELECT key for longer than one second. This opens the Control sub-menu which allows you to scroll through the monitored parameters using the UP/DOWN keys.
To modify a parameter you must:
1. Highlight the parameter in the Control sub-menu using the UP/DOWN keys.
2. Press the SELECT key for less that a second to access the available parameter values.
3. Highlight the wanted parameter value using the UP/DOWN keys then press the SELECT key for longer than one second to select the chosen value and return to the Control sub-menu.
4. To exit the Control sub-menu either press the UP key for longer than one second to return to the Main Menu or press the ON/OFF key for less than one second to return to the default screen.
Table 2.7, below, provides details of the available settings and the default values.
Measurements
Event Log
Control
Buzzer mute
UPS Battery test
Clear EPO Status
Reset fault state
Clear event log
Reset: no
Identification
Settings
Restore factory
settings
Buzzer mute: no
Status: battery test ok Schedule battery test: no
Status: fault active Rest fault: no
Total events:50 Clear event log: no
Status
<1s
Figure 2.14 Menu Navigation – Control Menu (single module installation)
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 17
2: General Description
Measurements
Event Log
Control
Buzzer mute
UPS Battery test
Clear EPO Status
Reset fault state
Clear event log
Reset: no
Identification
Settings
Restore factory
settings
Buzzer mute: no
Status: battery test ok Schedule battery test: no
Status: battery test ok Schedule battery test: no
Status: fault active Rest fault: no
Total events:50 Clear event log: no
Status
Turn OFF Single
UPS
Single UPS Turn off: no
Parallell UPS
battery test
<1s
Figure 2.15 Menu Navigation – Control Menu (multi-module installation)
2: General Description
18 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
Table 2.7 Control sub-menu options
2.5.10 Identification sub-menu
The Identification menu allows access to the UPS model data, serial number and firmware revision details, as shown in Figure 2.16. This information is often requested when seeking assistance from the manufacturer or service agent.
To access the Identification sub-menu you must highlight the Identification option in the Main Menu then press the SELECT key for longer than one second. This opens the Identification sub-menu screen which allows you to scroll through the stored data using the UP/DOWN keys.
To exit the Identification sub-menu either press the UP key for longer than one second to return to the Main Menu or press the ON/OFF key for less than one second to return to the default status screen.
2.5.11 Settings sub-menu
The Settings menu allows various UPS operating parameters to be configured, as shown in Figure 2.17. Some settings can impact on the UPS performance, others can enable and disable functions within the UPS (see also paragraph 2.3.4).
To access the Settings sub-menu you must highlight the Settings option in the Main Menu then press the SELECT key for longer than one second. This opens the Settings sub-menu screen which allows you to scroll through the available options using the UP/DOWN keys.
To exit the Settings sub-menu either press the UP key for longer than one second to return to the Main Menu or press the ON/OFF key for less than one second to return to the default status screen.
Control Description Values Default
Buzzer Mute Mute the audible warning alarm No / Yes No
*Turn OFF Single UPS Allows an individual module to be turned off.No /YesNo
UPS Battery Test Initiate test of the batteries of a single UPS Schedule / No / Yes No
*Parallel UPS battery test Initiate test of the batteries of a group of UPS’s Seg1 and Seg2: On /Off On / Off
Clear EPO status Reset the UPS from emergency power off status No / Yes No
Reset Fault state Reset warning and alarming status and buzzer No / Yes No
Clear Event Log Reset all the events from the log file No / Yes No
Restore factory setting Restores default settings, EPO polarity and locks
the DC start-up
No / Yes No
*Only relevant to multi-module installation
WARNING: Inappropriately configured settings in this menu could result in reduced load protection or UPS performance. This menu set-up or modified only by a qualified service engineer.
Type/Model: UPS PW3000/TP 10kVA
UPS firmware: XXXX_XX
Serial Number: XXXXXXXX
Measurements
Event Log
Status
Control
Identification
Settings
<1s
Figure 2.16 Menu Navigation – Identification
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 19
2: General Description
Important notes:
Password
Enter the password using the UP, DOWN and SELECT keys. If the User Password option is disabled the Password entry screen will be bypassed.
Frequency changer configuration
To configure the UPS as a frequency changer, ensure the inverter is turned OFF, select the Output frequency and set the Power strategy to <Converter>. Then totally shut down the UPS, and turn OFF the input mains power. The new configuration will activate when the UPS is next powered up.
External battery modules
A standard 10kVA module uses 1 battery string and a 20kVA module uses 2 strings. In each case the number entered in the ‘External battery modules’ menu should be set to <0> for a standard module and increased to equal the number of any optional external battery strings connected to the UPS.
HE frequency high limit <+05% (52.5Hz)>
HE frequency low limit <-05% (47.5Hz)>
HE voltage high limit <+05% (241.5V)>
Bypass frequency low limit <-10% (<45.0Hz)>
Bypass voltage high limit <264V>
Measurements
Event Log
Control
Automatic battery tests period <7 days>
Automatic overload restart <enabled>
Auto restart <enabled>
Auto bypass <disabled>
Identification
Settings
Status
Short circuit clearance <disabled>
Bypass voltage low limit <176V>
Language <English>
Password: <****>
User Password <disabled>
Audio alarm <enabled>
Output voltage <230V>
Output frequency <50Hz>
Power strategy <normal>
DC start <enabled>
Battery remaining time <enabled>
Set running time Day: 0001 Time: 00.00.00
External battery module <0>
Set running time
LCD Contrast <0>
Bypass frequency high limit <+10% (<55.0Hz)>
HE voltage low limit <-05% (218.5V)>
<1s
Figure 2.17 Menu Navigation – Settings
Key Point: Depending on
the installed firmware, some menus use the term HE (High Efficiency) or ECO (Economy). These terms are synonymous and refer to the Off-line mode of operation described in paragraph 2.3.3.
The Password entry screen will be skipped if the USER PASSWORD setting has be set to <disabled>
2: General Description
20 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
Table 2.8 Settings sub-menu options
Sub-menu Item Description Values Default
User password Protects against unapproved access Enabled / Disabled Disabled
Language Select menu language English / Chinese English
Audio alarm Enable / disable alarm sounds Enabled / Disabled Enabled
Output voltage Define local output voltage 200/208/220/230/240V 230V
Output frequency Define local output frequency
(UPS detects the frequency in 'autosensing')
Autosensing /
50Hz / 60Hz
Autosensing
Power strategy* Define the operating mode Normal / ECO- mode /
Frequency converter
Normal
DC start (Cold start) Start the UPS from batteries, without mains power Enabled / Disabled Enabled
Automatic battery test period Define the frequency of the battery tests 0-31 days 7 days
Auto restart After power outage, the load restart automatically
when mains power is recovered
Enabled / Disabled Enabled
Automatic overload restart The UPS automatically restarts if it shuts-down
due to overload
Enabled / Disabled Enabled
Auto bypass The automatic bypass can be disabled if the
bypass power supply is very unstable. UPS runs only ‘on-line’ or on-battery.
Enabled / Disabled Disabled
Short circuit clearance When enabled, short circuit can last for 4s before
cutting off the output. If short circuit is removed during this time, the UPS will continue to run. When disabled, short circuit will only last for 100ms before the UPS output is cut off.
Enabled / Disabled Disabled
Bypass voltage low limit When the voltage in the bypass is below this limit,
the UPS changes operating mode
176 ~ 215V 176V
Bypass voltage high limit When the voltage in the bypass is above this limit,
the UPS changes operating mode.
245 ~ 276V 264V
Bypass frequency low limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
40 ~ 49.5 Hz 45 Hz
Bypass frequency high limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
50.5 ~ 70 Hz 55 Hz
HE voltage low limit When the voltage in the bypass is below this limit,
the UPS changes operating mode.
1% ~1 0% 5%
HE voltage high limit When the voltage in the bypass is above this limit,
the UPS changes operating mode.
1% ~ 10% 5%
HE frequency low limit When the frequency in the bypass is below this
limit, the UPS changes operating mode.
1% ~ 10% 5%
HE frequency high limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
1% ~ 10% 5%
External Battery modules** Define the number of external battery modules. 0 - 97 0
Set running time Reset the UPS running time for tests purposes. Day:hour:minute:second Running time
LCD contrast Change the contrast in the LCD display -5 ~ +5 0
Battery remaining time When enabled, the battery remaining time is
displayed in the menu measurements
Enabled / Disabled Disabled
*
Read section 2.3 before using ECO-mode or converter function.
** Enter the number of ADDITIONAL (external) battery strings. An incorrect entry might degrade the battery operation.
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 21
2: General Description
Example: How to change the rated output voltage
Settings Menu (changing output voltage)
This example shows the steps necessary to change the UPS output voltage from its default 230V setting to 220V.
1. Gain access to the Main Menu and, using the UP/DOWN keys, scroll through to ‘Settings’ (A).
2. Press the SELECT key (<1s) to access the Settings sub-menu, starting at ‘Password’ or ‘Language’ (B). Note that if the ‘User Password’ parameter has been set to <disabled> the ‘Password’ entry screen will be bypassed and you will be taken straight to the ‘Language’ option.
3. Enter the password if required then press the SELECT key.
4. Using the UP/DOWN keys, scroll through the Settings sub-menu to ‘Output voltage,’ then press the SELECT key (<1s) to access the ‘Output voltage’ change screen (C). Note that this may require password access if ‘set’.
5. The values shown in the change screen will initially flash.
6. Change the indicated value using the UP/DOWN keys to select the required voltage (220V) then press the SELECT key for greater than one second to accept the change (D).
7. This will take you back to the Settings sub-menu where 220V will now be displayed in the Output voltage screen (E).
8. Continue scrolling through the Settings sub-menu using the UP/DOWN keys, and exit to the main Settings menu by pressing the UP key for greater than one second; or exit back to the Default Screen by briefly pressing the ON/OFF key.
Language <English>
Password: <****>
User Password <disabled>
Audio alarm <enabled>
Output voltage <230V>
Output frequency <50Hz>
Output voltage <230V>
Output voltage <220V>
Output voltage <220V>
<1s
<1s
<1s
<1s
>1s
Settings
Measurements
Event Log
Status
Control
Identification
<1s
A
B
C
D
E
The Password entry screen will be bypassed if the USER PASSWORD setting has be set to <disabled>
2: General Description
22 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
2.6 Warranty
The PowerWave PW3000/TP UPS is supplied with a limited warranty that the UPS and its component parts are free from defects in materials and workmanship for a period of one year from the date of original commissioning or fifteen months from the date of original delivery, whichever is the sooner. This warranty is the only warranty given and no other warranty, express or implied, is provided.
This warranty is invalidated if the UPS is put into use without having been commissioned by a fully trained and authorised person. This warranty does not apply to any losses or damages caused by misuse, abuse, negligence, neglect, unauthorised repair or modification, incorrect installation, inappropriate environment, accident, act of God or inappropriate application.
If the UPS fails to conform to the above within the warranty period then Uninterruptible Power Supplies Ltd. will, at its sole option, repair or replace the UPS. All repaired or replaced parts will remain the property of Uninterruptible Power Supplies Ltd.
As a general policy, Uninterruptible Power Supplies Ltd does not recommend the use of any of its products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect it’s safety or effectiveness. Uninterruptible Power Supplies Ltd does not recommend the use of any of its products in direct patient care. Uninterruptible Power Supplies Ltd will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Uninterruptible Power Supplies Ltd that the risks of injury or damage have been minimized, the customer assumes all such risks and the liability of Uninterruptible Power Supplies Ltd is adequately protected under the circumstances
THE UPS SYSTEM MAY CONTAIN BATTERIES WHICH MUST BE RE-CHARGED FOR A MINIMUM OF 24 HOURS EVERY SIX MONTHS TO PREVENT DEEP-DISCHARGING. BATTERIES THAT HAVE BEEN, FOR WHATEVER REASON, DEEP-DISCHARGED ARE NOT COVERED BY THE WARRANTY.
2.7 Extended Warranty
The Standard Warranty may be enhanced by protecting the UPS with an Extended Warranty Agreement (maintenance contract). An Extended Warranty Agreement enhances the standard warranty by providing the following:-
• Regular preventative maintenance inspections.
• Guaranteed speed of response to operational problems.
• 24 hour telephone support.
• Fully comprehensive (excluding batteries) cover.
• Contact the Service Support Hotline on 0800 731 3269 for further details.
2.8 Additional Service/Maintenance Support
In addition to providing support for the PowerWave PW3000/TP, Uninterruptible Power Supplies Ltd can provide maintenance and support of a wide range of different UPS products.
If you are interested in an extended warranty for your PowerWave PW3000/TP, or any other UPS you may have, please complete the enquiry form shown opposite and return or FAX to:
Uninterruptible Power Supplies Ltd. Woodgate Bartley Wood Business Park Hook Hampshire RG27 9XA
Tel: 01256 386700
0800 731 3269 (24 Hr.)
Fax: 01256 386701
Email: service@upspower.co.uk
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 23
3
Installation
3.1 Introduction
This chapter contains essential information concerning the unpacking, positioning, installing and cabling of the PowerWave PW3000/TP UPS.
3.2 Taking receipt of the UPS
The UPS cabinet and accessories are delivered on purpose designed pallets that are easy to off load and move using a forklift or suitable pallet jack.
The packing container protects the UPS from mechanical and environmental damage during transit. This protection is further increased by wrapping the PowerWave PW3000/TP UPS with a plastic sheet.
Upon receiving the UPS you should carefully examine the packing container for any sign of physical damage.
Ensure that the received UPS equipment corresponds to the description indicated in the delivery note. The package should contain:
WARNING: All cabling operations must be supervised by an authorised electrician or other suitably qualified person. All installation and operating procedures must be carried out in strict accordance with the instructions contained in this manual. Uninterruptible Power Supplies Ltd will take no responsibility for any personal injury or material damage caused by the incorrect installation, cabling or operation of this product.
WARNING: Once the UPS equipment is installed it must be commissioned by an engineer approved by Uninterruptible Power Supplies Ltd before it is powered-up. Uninterruptible Power Supplies Ltd will take no responsibility for any personal injury or material damage caused by the application of electrical power to this equipment before it has been fully commissioned.
CAUTION: Observe the following precautions when off-loading and moving the UPS:
Always keep the packages in an upright position.
Do not drop the equipment.
Due to the fitted high-energy batteries and heavy weight, do not stack the pallets.
CAUTION: Claims for visible shipping damage must be no tified to th e carrier immediately on receipt. Other shipping damage claims must be filed immediately when found and the carrier mu st be informed within a maximum of 7 days following receipt of the equipment. If shipping damage is discovered, store all packing materials for further investigation.
1 x PowerWave PW3000/TP UPS 1 x User manual
1 x Parallel cable 1 x Parallel port cover plate
1 x power terminal jumper kit (6-hole) 2 x M5x12 HEX screw
4 x Cable glands 1 x Monitoring Software CD
3: Installation
24 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.2.1 Site transportation
Please observe the following precautions when you transport the UPS equipment between its off loading site and the intended installation (or storage) location.
3.3 Unpacking
Figure 3.1 Unpacking and positioning the PowerWave PW3000/TP
1. Using a forklift, move the unit to the location where it is to be installed.
Note: The UPS has wheels to make final positioning easy after it has been unpacked, but these are not suitable for
moving the unit over long distances.
CAUTION: Potential dangers:
If the UPS/battery cabinet is tilted by more than 10° it could cause internal damage. If tilting occurs, do not connect the UPS to the mains electrical supply.
The weight of the UPS/battery cabinet can cause serious personal injury and/or structural damage to the surrounding area if dropped in transit. Always take extreme care when moving the equipment.
CAUTION: Storage:
The UPS should be stored in the original packing and shipping carton.
The recommended storing temperature for the UPS is between +5°C and +40°C (+35°C for batteries).
The UPS and the batteries must be protected from high humidity, which should not exceed 95% RH (non-condensing).
386mm
8mm diameter (4 places)
329mm
1 2 3
4
5
6
Mounting brackets
Mounting brackets
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 25
3: Installation
2. Cut the wrappers and remove the packing carton by pulling it upwards.
3. Remove the protection packaging from the sides and top of the unit then remove the side mounting brackets securing the unit to the pallet. Retain the packaging materials for possible future shipment of the UPS.
4. Using the wooden piece removed from the top of the UPS as a ramp, carefully slide the UPS off the pallet to its final position.
5. Reattach the side mounting brackets to increase the cabinet stability.
6. If desired, the mounting brackets can be fixed to the floor using M8 bolts.
3.4 Storage
UPS Cabinet
If you plan to store the UPS cabinet prior to use it should be held it in a clean, dry environment with an ambient temperature between -5°C to +60°C (max +35°C for batteries) and RH <95%. The UPS should preferably be stored in the original packing and shipping carton, but if the packing container is removed you must take measures to protect the UPS from dust.
Battery
The UPS uses sealed, maintenance-free batteries whose storage capacity depends on the ambient temperature. It is important not to store the batteries for longer than 6 months at 20°C, 3 months at 30°C, or 2 months at 35°C storage temperature without recharging them.
For longer term storage the batteries should be fully recharged every 6 months @20°C.
3.5 Planning the installation (site considerations)
A certain amount of pre-planning will help ensure a smooth and trouble-free installation of the UPS system. The following guidelines should be taken into account when planning a suitable UPS location and operating environment.
1. The UPS is designed for indoor installation only.
2. The route to the installation location must allow the equipment to be transported in an upright position.
3. The floor at the proposed installation site and en-route from the off-loading point must be able to safely take the weight of the UPS and battery equipment plus fork lift during transit.
4. Locations with high ambient temperature, moisture or humidity must be avoided.
a) The installation site humidity should be <90% non-condensing. b) The prescribed ambient temperature is 0°C to +40°C. An ambient temperature of 20°C is recommended to
achieve a long battery life. c) Any requested cooling air flow must be available. The air entering the UPS must not exceed +40°C. d) The air conditioning system must be able to provide a sufficient amount of cooling air to keep the room within the
prescribed temperature range.
5. The following environmental conditions should also be considered:
a) Fire protection standards must be respected. The floor material should be non-flammable. b) The location must be free of dust and corrosive/explosive gases. c) The location must be vibration free. d) A minimum clearance of 50cm is required on the sides of the equipment to allow the free passage of cooling air
WARNING: Water condensation may occur if the UPS is unpacked in a very low temperature environment. In this case, you must wait until the UPS is fully dried inside and outside before proceeding with the installation to avoid possible electric shock hazard and equipment malfunction.
CAUTION: Sealed batteries must never be stored in a fully or partially discharged state. Extreme temperature, under-charge, overcharge or over-discharge will destroy batteries!
Charge the battery both before and after storing.
Always store the batteries in a dry, clean, cool environment in their original packaging.
If the packaging is removed protect the batteries from dust and humidity.
3: Installation
26 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.5.1 Clearances
The following notes are applicable to both the UPS and external battery cabinet.
The cabinet is force ventilated with extractor fans mounted on the back panel drawing cooling air through the inlet grills on the front of the unit. Sufficient space must be provided at the back and sides of the cabinet to permit adequate air-flow.
Rear access is required for connecting the power and control cables, and also to operate the UPS power switches. If direct rear access is not available, sufficient space must be provided at the side of the cabinet to allow the operator to reach around the cabinet to operate the power switches.
Note: Full access is required to both sides of
the cabinet for maintenance. The UPS cabinet is mounted on wheels, so if the installation does not afford direct side access the UPS connecting cables should be of sufficient length to allow the cabinet to be moved forward to offer unhindered side access when required.
We recommend the following minimum clearances:
• Rear access (X): a minimum of 500mm for unrestricted airflow
• Side (Y): a minimum of 500mm for free airflow, but may need increasing to 1000mm to afford rear access for
operating the equipment power switches if direct rear access is not available (see also the note above)
• Front (Z): allow a minimum of 1000mm for maintenance access and the safe passage of personnel
3.6 Planning the installation (cabling considerations)
3.6.1 General requirements
The information in this section should help with the preparation and planning of the UPS power cabling.
It is the customer’s responsibility to provide all external fuses, isolators and cables that are used to connect the UPS input and output power supplies. The UPS input and bypass terminals should be connected to the utility mains supply through a suitable LV-Distribution board containing a circuit breaker or fused isolator to provide both overload protection and a means of isolating the UPS from the mains supply when required. Similarly, the UPS AC output terminals should be connected to the load equipment via a suitably fused load distribution board.
Input neutral grounding
A permanently connected input neutral is required to enable the rectifier to operate correctly and allow the UPS to function properly when operating on battery. The input neutral must also be grounded to permit correct operation when the UPS is running on battery.
and connected to the UPS at all times. DO NOT use, a 4­ard on a TN-S system.
UPS
UPS
Battery
Cabinet
XX
Y
Y
ZZ
Front
Front
Clearance (mm) X Y Z
Minimum ~500 500~1000 1000
Figure 3.2 UPS & Battery cabinet clearance requirements
0V
230V
UPS
Figure 3.3 Permanent, grounded input neutral
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 27
3: Installation
3.6.2 UPS Cable and fuse sizing
3.6.3 Power cabling for a parallel system
In order to achieve equal load sharing between the UPS cabinets in a parallel system, the length of the input cables from the input distribution board to each cabinet should be as equal as possible, with a maximum difference of 20%. This also applies to the UPS output cables. Each module should be connected to an output circuit breaker located on a switch panel no further than 20 meters from the cabinets.
External maintenance bypass
Figure 3.4 External bypass circuit
An external maintenance bypass facility, such as that shown in Figure 3.4, can be installed to increase the system flexibility. This circuit allows an individual module to be isolated from the system, for repair or total replacement, by opening its input fused isolator and Output Breaker. It also allows the total system to be bypassed by closing the System Bypass Breaker and opening the System Output Breaker; which in turn allows testing of the entire parallel system.
When such an external maintenance bypass is used it is crucial that the UPS modules are all operating on bypass (or internal maintenance bypass) before the System Bypass Breaker is closed, to avoid the possibility of module damage. For this reason it is usual to incorporate some form of safety interlocking mechanism around the external breakers.
Key Point: The information in figures 3.8 and 3.9 is given for guidance only:
Fuse and Cable recommendations are to IEC 60950-1:2001.
All external fuses, isolators and power cables must be rated and installed in accordance with the prescribed IEC standards or local regulations: – e.g. BS7671: 2008 incorporating amendment No.1:2011.
External DC Cables and battery fuses are bespoke to the installation.
UPS 1 UPS 2 UPS 3 UPS 4
MAINS / BYPASS
System Output Breaker
System Input Breaker
UPS 1 Input/bypass Isolator
UPS 2 Input/byp Isolator
UPS 3 Input/byp Isolator
UPS 4
Input/byp
Isolator
UPS 1 Output
Breaker
UPS 2
Output
Breaker
UPS 4
Output
Breaker
UPS 3
Output
Breaker
To Load Dist. Panel
System Bypass
Breaker
3: Installation
28 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.6.4 UPS Terminal block connection details
The input, output and external battery power cables are connected to a terminal block rail located on the back of the UPS cabinet, behind a removable cover which is secured to the cabinet by four screws. Figure 3.5 shows the power terminal block connection details.
MAINS 1 – is connected to the UPS input mains supply and can be configured for either a single-phase or three-phase input supply.
MAINS 2 – is connected to the UPS bypass mains supply. This is a single-phase connection and it can either be linked to MAINS 1 (single input configuration) or connected to a dedicated bypass mains supply (dual input configuration). Note that the neutral connections for MAINS 1 and MAINS 2 are linked within the UPS.
The various MAINS 1 / MAINS 2 input configurations are described in paragraph
3.6.5
OUTPUT – The UPS AC output terminals
should be connected to the load distribution panel via a circuit breaker or fused isolator.
PARALLEL JP – JP1/JP2 is used to configure the UPS for parallel operation. By default, the UPS is shipped with a link connected between JP1 and JP2 which configures the UPS for use as a stand-alone unit (single module).
BATTERY – The battery terminals are used to connect the UPS cabinet to an external battery cabinet, where used.
3.6.5 Input/bypass supply configuration options
As mentioned above, the UPS input mains (MAINS 1) and bypass mains (MAINS 2) can be connected in several supply configurations. These can be described as:
Three phase dual input – Three phase mains input (L1,L2,L3) and separate single phase bypass input (M2)
Three phase single input – Three phase mains input (L1,L2,L3) with the bypass line (M2) linked to (L1)
Single phase dual input – Single phase mains input (L1,L2,L3 linked) and separate single phase bypass line (M2)
Single phase single input – Single phase mains input linked to the bypass input (L1,L2,L3,M2 all linked)
The input configuration is selected by fitting links to the power terminal block Mains 1 and Mains 2 connections. A ‘jumper kit’ comprising four screws, four spacers and a small busbar with 6­holes, is shipped with the UPS module to enable the UPS input supply connections to be linked accordingly. When installed, the jumper bar should be fitted to connections along the centre of the terminal block with the spacers as shown in Figure 3.6 and secured firmly in place by the required screws. Link details for all four configurations are shown in figures 3.8 to 3.11).
Note: If only the three left-most screws are required to be fitted,
the bar can be cut to length.
CAUTION: If the UPS is to be installed as part of a parallel PW3000TP system the link between JP1-JP must be removed.
CAUTION: The UPS is usually shipped with its internal batteries already connected.
L1
L2 N M2 GND
L3 GND N L
N JP1
GND
JP2
B+ GND
B-
MAINS 1
(Input)
MAINS 2 (Bypass)
OUTPUT PARALLELJPBATTERY
Internal link
Figure 3.5 Power terminal block connections
Figure 3.6 Power terminal jumper
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 29
3: Installation
3.7 Connecting the UPS power cables
Safety notes
Please ensure you read and understand the following safety notes before you begin the UPS electrical installation.
1. Do not commence this procedure until the UPS mechanical installation has been completed.
2. All the cable installation procedures detailed below must be supervised by a qualified electrician.
3. Do not connect the UPS if there is water or moisture present.
4. When carrying out any work on the UPS power cables or terminals, you must ensure that the UPS input and output supplies are isolated and locked out at their respective distribution boards. Warning notices should be posted to prevent any inadvertent operation of the UPS mains supply isolators.
5. Once the electrical installation is completed the UPS must be commissioned by an engineer authorised by the manufacturer before it is brought into use.
6. When installing the UPS cables ensure that the connection procedures are performed under the following conditions:
a) No mains voltage is present at the UPS mains (or bypass) distribution board terminals. b) All loads are disconnected at the load distribution board and the UPS is fully shut down and voltage-free. c) The UPS Maintenance Bypass Isolator is open (OFF).
3.7.1 Power cabling procedure
Figure 3.7 Power terminal connections
To prepare for power cabling:
1. Remove the terminal block cover (1) to gain access to the terminal block connections.
2. All power cables enter the UPS through cable glands (2) fitted to the bottom of the terminal box. The holes used for the glands are fitted with blanks when the unit is shipped. Fit the supplied glands to suit the cable installation.
3. Connect the protective earth (GND) cables between the UPS power terminal block and each of the following:
a) input mains distribution panel b) bypass mains distribution panel (if separate) c) UPS output distribution panel d) external battery cabinet (if used)
4. Connect the power cables to the terminal block according to the desired input configuration, as described in Figure 3.8 to Figure 3.11.
WARNING: Opening or removing the UPS-covers will create a risk of exposure to dangerous voltages if power is connected to the UPS.
WARNING: Do not apply electrical power to the UPS before it has been commissioned.
Key Point: The power terminal block, shown in detail in Figure 3.5, can accept cables up to 16mm² in the 10kVA
unit. In the 20kVA unit the maximum terminal size is 35mm² but due to manipulation restrictions in the cable box we recommend using flexible cable with a maximum cable size of 25mm². Note that the input neutral and bypass neutral terminals are linked at the terminal block.
Key Point: The tables in Figure 3.8 to Figure 3.11 show the maximum current ratings for the cables and protective devices that must be provided by the customer. The chosen cables/protective devices must meet the required local standards and installed in accordance with codes of practice
1
2
3
3: Installation
30 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.7.2 Three phase dual input cabling details
Figure 3.8 Three phase dual input diagram with recommended cable and fuse sizing
MAINS DISTRIBUTION BOARD
Ext. BATT CAB UPS CABINET
RECTIFIER
INVERTER
STATIC SWITCH
LOAD DISTRIBUTION BOARD
L1 L2 L3 N GNDM2 N
L1 L2 L3 N GNDGND
GND
GNDGND M2 N
L N GND
L N GND
JP1 JP2
GND
B+
B-
GND
B+
B-
Fuse B
Cable B
Fuse A
Cable A
Cable C
Cable D
Fuse D
UPS Mains Supply
(3 x 380/400/415V)
UPS Bypa ss Supply
(1 x 220/230/240V)
WIRING NOTES
1. Connect the supply neutral to the bypass neutral terminal (Mains 2 (N)). DO NOT connect the supply neutral to the input neutral terminal (Mains 1 (N)) as there is a possibility that the bypass current could return through, and overload, the smaller cable of Mains
1.
2. Connect the three-phase mains input cable to L1,L2,L3 and the bypass input cable to M2.
3. Connect the battery cables to the external battery cabinet if used (see paragraph 3.8).
4. Remove the link between JP1 and JP2 if the module is part of a parallel module system.
5. Connect the output terminals to the output breaker/load distribution board. The load distribution breakers should have a leakage current protective function to suit to the UPS voltage and current ratings.
10kVA 20kVA
Cable A 16 A 33 A
Cable B 48 A 90 A
Cable C 48 A 90 A
Cable D Bespoke
Safety Earth
max 16 mm
2
max 25 mm
2
Note: @400V/230V nominal input.
L1
L2
N
M2
GND
L3 GND N L
NJP1
GND
JP2
B+
GND
B-
MAINS 1
(Input)
MAINS 2 (Bypass)
OUTPUT PARALLELJPBATTERY
Internal link
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 31
3: Installation
3.7.3 Three phase single input cabling details
Figure 3.9 Three phase single input diagram with recommended cable and fuse sizing
MAINS DISTRIBUTION BOARD
Ext. BATT CAB UPS CABINET
RECTIFIER
INVERTER
STATIC SWITCH
LOAD DISTRIBUTION BOARD
L1 L2 L3 N GNDM2 N
L1 L2 L3 N
GND
GNDGND
L N GND
L N GND
JP1 JP2
GND
B+
B-
GND
B+
B-
Fuse A
Cable A
Cable B
Cable C
Cable D
Power
terminal
jumper
Fuse D
UPS Mains Supply
(3 x 380/400/415V)
WIRING NOTES
1. Connect the supply neutral cable to the bypass neutral terminal (Mains 2 (N)), which is also connected to the mains input neutral terminal within the UPS. There is no need to connect the input mains neutral (Mains 1 (N)).
2. Install the power terminal jumper between the Mains 1 (L1) and Mains 2 (M2).
3. Connect the mains input cable to L1, L2, L3.
4. Connect the battery cables to the external battery cabinet if used (see paragraph 3.8).
5. Remove the link between JP1 and JP2 if the module is part of a parallel module system.
6. Connect the output terminals to the output breaker/load distribution board. The load distribution breakers should have a leakage current protective function to suit to the UPS voltage and current ratings.
10kVA 20kVA
Cable A 16 A
(48 A on L1)
33 A
(90 A on L1)
Cable B 48 A 90 A
Cable C 48 A 90 A
Cable D Bespoke
Safety Earth
max 16 mm
2
max 25 mm
2
Note: @400V/230V nominal input.
JP1
JP2
L1
L2
N
M2
GND
L3 GND N L
N
GND
B+ GND
B-
MAINS 1
(Input)
MAINS 2 (Bypass)
OUTPUT PARALLELJPBATTERY
Internal link
3: Installation
32 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.7.4 Single phase dual input cabling details
Figure 3.10 Single phase dual input diagram with recommended cable and fuse sizing
MAINS DISTRIBUTION BOARD
Ext. BATT CAB UPS CABINET
RECTIFIER
INVERTER
STATIC SWITCH
LOAD DISTRIBUTION BOARD
L1 L2 L3 N GNDM2 N
GNDL NL N
GND
GNDGND
L N GND
L N GND
JP1 JP2
GND
B+
B-
GND
B+
B-
Fuse A
Cable A
Fuse B
Cable B
Cable C
Cable D
Fuse D
UPS Mains Supply
(1 x 220/230/240V)
Power
terminal
jumper
UPS Bypa ss Supply (1 x 220/230/240V)
WIRING NOTES
1. Connect the input neutral cables to Mains 1 (N)
and Mains 2 (N).
2. Install the power terminal jumper between
Mains 1 (L1, L2, L3).
3. Connect the input line cable to Mains 1 (L1).
4. Connect the bypass line cable to Mains 2 (M2).
5. Connect the battery cables to the external battery
cabinet if used (see paragraph 3.8).
6. Remove the link between JP1 and JP2 if the
module is part of a parallel module system.
7. Connect the output terminals to the output
breaker/load distribution board. The load distribution breakers should have a leakage current protective function to suit to the UPS voltage and current ratings.
10kVA 20kVA
Cable A 48 A 90 A
Cable B 48 A 90 A
Cable C 48 A 90 A
Cable D Bespoke
Safety Earth
max 16 mm
2
max 25 mm
2
Note: @400V/230V nominal input.
L1
L2
N
M2 GND
L3
GND
N L
N
GND
B+ GND
B-
JP1
JP2
MAINS 1
(Input)
MAINS 2
(Bypa ss)
OUTPUT PARALLELJPBATTERY
Internal link
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 33
3: Installation
3.7.5 Single phase single input cabling details
Figure 3.11 Single phase single input diagram with recommended cable and fuse sizing
MAINS DISTRIBUTION BOARD
Ext. BATT CAB UPS CABINET
RECTIFIER
INVERTER
STATIC SWITCH
LOAD DISTRIBUTION BOARD
L1 L2 L3 N GNDM2 N
L N
GND
GNDGND
L N GND
L N GND
JP1 JP2
GND
B+
B-
GND
B+
B-
Fuse A
Cable A
Cable B
Cable C
Cable D
Fuse D
UPS Mains Supply
(1 x 220/230/240V)
Power
terminal
jumper
WIRING NOTES
1. Connect the supply neutral cable to the bypass
neutral terminal (Mains 2 (N)), which is also connected to the mains input neutral terminal within the UPS. There is no need to connect the input mains neutral (Mains 1 (N)).
2. Install the power terminal jumper between
Mains 1 (L1, L2, L3) and Mains 2 (M2).
3. Connect the input line cable to Mains 1 (L1).
4. Connect the battery cables to the external battery
cabinet if used (see paragraph 3.8).
5. Remove the link between JP1 and JP2 if the
module is part of a parallel module system.
6. Connect the output terminals to the output
breaker/load distribution board. The load distribution breakers should have a leakage current protective function to suit to the UPS voltage and current ratings.
10kVA 20kVA
Cable A 48 A 90 A
Cable B 48 A 90 A
Cable C 48 A 90 A
Cable D Bespoke
Safety Earth
max 16 mm
2
max 25 mm
2
Note: @400V/230V nominal input.
JP1
JP2
L1
L2
N
M2
GND
L3
GND
N
L
N
GND
B+ GND
B-
MAINS 1
(Input)
MAINS 2
(Bypa ss)
OUTPUT PARALLELJPBATTERY
Inter nal link
3: Installation
34 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.8 Battery cabling procedure
Safety Notes
3.8.1 Internal battery connections
Figure 3.12 UPS Cabinet internal batteries
The UPS cabinet internal batteries are mounted on three shelves at the bottom of the cabinet and connected together as shown. All connections are accessible from the front of the cabinet after removing the front panel. Each battery string consists or 24 x 12V batteries connected in series to provide a nominal battery voltage of 288V; and two battery strings, each containing 24 batteries, can be housed and connected in parallel to increase the battery capacity.
Normally, internal batteries are shipped securely fitted to the cabinet battery trays and fully connected, and no further action is required when connecting the UPS power cables.
WARNING: Opening or removing the UPS/Battery enclosure covers will create the risk of exposure to dangerous voltages if power is connected to the UPS. Battery replacement and connections should only be carried out by electrically qualified personnel.
If the UPS is delivered without batteries, Uninterruptible Power Supplies Ltd is not responsible for any damage or malfunction caused to the UPS by the incorrect storage, installation or connection of batteries by third parties.
Final battery connection must be supervised by the commissioning engineer. Do not attempt to complete the battery wiring or close any battery isolator before the system has been commissioned.
Connection
points
Connection points
1 x 24 Batteries 2 x 24 Batteries
Main +ve Disconnect
Main -ve Disconnect
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 35
3: Installation
3.8.2 External battery cabinet cabling procedure
Where an external battery cabinet is installed it contains additional battery strings (each comprising 24 x 12V batteries) which are connected in parallel with the UPS internal batteries.
1. Disconnect the UPS internal batteries at the ‘Main + Disconnect’ and ‘Main – Disconnect’ points shown in Figure 3.12.
2. Open the fuse isolator on the back of the battery cabinet (see Figure 2.8).
3. Remove the terminal block cover on the back of the battery cabinet to gain access to the main terminal block.
4. Connect the protective earth cable (GND) between the battery GND terminal on the UPS terminal block (see Figure
3.8 to Figure 3.11) and the GND terminal on the battery cabinet terminal block.
5. Connect the battery positive (B+) and negative (B-) terminals on the UPS terminal block (see Figure 3.8 to Figure
3.11) to the corresponding B+ and B- terminals on the battery cabinet terminal block.
6. Reconnect the UPS internal batteries at the ‘Main + Disconnect’ and ‘Main – Disconnect’ that were disconnected
earlier.
7. Refit the battery cabinet terminal block cover. Do not close the battery fuses on the battery cabinet until the system has been commissioned.
3.9 Multi-cabinet configuration and paralleling cables
1. Ensure the cable link is removed from JP1-JP2 on the UPS terminal block (see Figure 3.8 to Figure 3.11).
2. For all modules, remove the parallel port cover plate on the rear of the UPS (see item 12 in Figure 2.7).
3. Connect a parallel bus cable (25-pin, 3m cables supplied) between the parallel ports of each UPS in a daisy chain.
4. Fit the modified parallel port cover plate (supplied) to the rear of the UPS, taking care not to trap the cables.
3.10 Optional remote monitoring and control facilities
Fit and connect any optional equipment following the instructions in Chapter 7.
• Back-feed protection - see page 52
• Emergency Power-OFF (EPO) - see page 53
• Computer communication options. - see page 53
• Serial Network Management (SNMP) card - see page 54
• AS400 Interface card - see page 55
• UPS Monitoring and automated control software - see page 56
Key Point: This section is required only if an external battery cabinet is installed.
WARNING: Do not close the fused isolators in the battery cabinet before the UPS system is commissioned.
Key Point: This section is required only if two (or more) cabinets are connected as a parallel system.
36 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4
Operating procedures
4.1 Introduction
The PowerWave PW3000/TP UPS system must be commissioned by a fully trained field service engineer authorised by Uninterruptible Power Supplies Ltd. before it is put into use.
The commissioning engineer will:
• Connect the UPS batteries
• Check the UPS mechanical and electrical installation, and operating environment
• Check the UPS cabinet parallel configuration settings
• Check the correct installation of any optional equipment
• Perform a controlled UPS start-up and functionally test the system for correct operation and configuration
• Carry out customer operator training and equipment handover
4.1.1 Operating procedure summary
A typical PowerWave PW3000/TP installation is shown in Figure 4.1.
This chapter contains the following procedures:
• Paragraph 4.2 Single module start-up – with mains supply
• Paragraph 4.3 Single module start-up – without mains supply
• Paragraph 4.4 Single module – changing the operating mode
• Paragraph 4.5 Single module shut down – with mains supply present
• Paragraph 4.6 Single module shutdown – with UPS on battery
• Paragraph 4.7 Single module – using the internal maintenance bypass
• Paragraph 4.8 Parallel module system procedures
• Paragraph 4.9 Parallel system start-up
• Paragraph 4.10 Parallel system – changing the operating mode
• Paragraph 4.11 Parallel system – start/stop one module
• Paragraph 4.12 Parallel module complete system shut-down
• Paragraph 4.13 External Maintenance Bypass operation
• Paragraph 4.14 Operating a frequency changing system
• Paragraph 4.15 Emergency Stop
WARNING: Uninterruptible Power Supplies Ltd. accepts no responsibility for the equipment or the safety of any personnel when operating this equipment before it has been properly commissioned. The manufacturer's warranty is immediately invalidated if power is applied to any part of the UPS system before it has been fully commissioned and handed over to the customer.
WARNING: Before you operate this equipment you should understand the location and function of the UPS controls, as described in Chapter 2.4 and Chapter 2.5, together with all associated external switchgear and distribution panels.
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 37
4: Operating procedures
4.2 Single module start-up – with mains supply
Use this procedure to start a single module UPS system from a completely powered down condition.
1. Check that all the loads connected to the UPS are turned off.
2. Close the external UPS Input/bypass Isolators as required to connect power to the UPS.
3. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
4. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and will then display the default screen on the LCD.
5. On the UPS Control Panel, press the ON/OFF key for more than one second.
a) The alarm buzzer will sound and the UPS will start. b) After a few seconds, the UPS will switch to its ‘on-line’ mode.
6. Check that the LCD indicates the ‘on-line’ status and no warning alarms are present.
7. The UPS is now fully operational and providing protected output power.
8. You can now switch on the loads. (If possible, turn on the loads sequentially to prevent a UPS overload occurring due to combined inrush currents.)
4.3 Single module start-up – without mains supply
If there is no mains supply present, you can use this procedure to start a single module UPS system using battery power (also described as a ‘cold start’).
1. Check that all the loads connected to the UPS are turned off.
2. Close the external UPS Input/bypass Isolators as required to connect power to the UPS.
3. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
4. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) Nothing will happen if the input supplies are not present.
5. On the UPS Control Panel, press the ON/OFF key for more than one second.
a) The fans will start running. b) The UPS will perform a self-test and will then display the default menu on the LCD.
6. Press the ON/OFF key again for more than one second.
a) The alarm buzzer will sound and the UPS will start. b) After a few seconds, the UPS will switch to its ‘on-battery’ mode.
7. Check that the LCD indicates the ‘on-battery’ status and no warning alarms are present other than those associated with the ‘battery on load’ status.
8. The UPS is now fully operational and providing protected output power, but the battery is on load and discharging (with the accompanying alarms).
9. You can now switch on the loads. (If possible, turn on the loads sequentially to prevent a UPS overload occurring due to combined inrush currents.)
a) If the UPS is left to run in this condition sufficiently long, the battery will fully discharge and the UPS will shut down
with the loss of the output supply.
b) If the mains supply is restored while the UPS is ‘on-battery’ it will automatically switch to ‘on-line’ mode.
Key Point: When starting the UPS in this manner the batteries will immediately begin to discharge. If you want to sustain power to the load it is important that the mains supply is restored before the UPS shuts down due to the battery reaching its ‘end of discharge’ voltage.
4: Operating procedures
38 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.4 Single module – changing the operating mode
When the UPS is turned on you can quickly switch between its various operating modes as shown below:
4.5 Single module shut down – with mains supply present
Use this procedure to totally shut down a single module UPS system and its connected load.
1. Switch off the individual load items.
2. If the UPS is operating in ‘on-bypass’ mode go to step 4.
3. On the Control Panel, press the ON/OFF key continuously for more than three seconds.
a) The alarm buzzer will sound. b) The UPS will transfer to ‘on-bypass’ mode and its output will remain live through the (unprotected) bypass supply.
Note: If the bypass has been disabled through the Settings menu, when you press the
ON/OFF
key for more than
three seconds to shut down the UPS the unit will change from ‘on-line’ to ‘on-battery’ mode (see below).
4. On the back of the UPS cabinet, open the input breakers M1 and M2 (position OFF).
a) Power will be removed from the UPS output terminals b) The fans will stop. c) After a few seconds the UPS LCD display will power down.
5. To totally isolate the UPS, open the UPS Input/bypass Isolators and, where used, open the external battery cabinet fuses/isolator.
4.6 Single module shutdown – with UPS on battery
1. Turn off the individual load items.
2. On the Control Panel, press the ON/OFF key continuously for more than three seconds.
a) The alarm buzzer will sound for three seconds b) The output power will be immediately cut-off. c) The fans will stop. d) After a few seconds the UPS LCD display will power down.
3. To totally isolate the UPS, open the UPS Input/bypass Isolators and, where used, open the external battery cabinet fuses/isolator.
From To Action
ON-LINE ON-BYPASS
*Press the ON/OFF key for 3 seconds.
ON-BYPASS ON-LINE Press the ON/OFF key for 3 seconds.
ON-BYPASS ON-BATTERY Isolate the mains/bypass power supply.
ON-BATTERY ON-LINE Restore the mains.bypass power supply.
* If the bypass is disabled in the
SETTINGS
menu, when operating in the ON-LINE mode pressing the ON/OFF key for
three seconds will switch the UPS ON-BATTERY mode.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 39
4: Operating procedures
4.7 Single module – using the internal maintenance bypass
The inbuilt maintenance bypass circuit allows the UPS to be powered down while maintaining the load through the (unprotected) bypass supply.
Transferring the load from UPS to the internal Maintenance bypass
1. Check the SETTINGS menu to ensure that the [Auto Bypass] is enabled – see paragraph 2.6.5.
2. If the UPS is operating in the ‘on-line’ mode, press the ON/OFF key on the Control Panel continuously for more than three seconds.
a) The alarm buzzer will sound. b) The UPS will transfer to ‘on-bypass’ mode and its output will remain live through the bypass supply.
3. Remove the Maintenance Switch cover plate on the back of the UPS.
4. Switch the Maintenance Switch from ‘UPS’ to ‘BPS’.
a) The load is now powered from the unprotected UPS bypass supply via the Maintenance Switch. b) The UPS can now be powered down (e.g. for repair) by opening the input breakers M1 and M2 (position OFF) on
the back of the UPS together with the external battery cabinet fuses/isolator (where used).
Transferring the load from the internal Maintenance bypass to the UPS
1. If an external battery cabinet is used, check that the fuses/isolator on the back of the battery cabinet is closed and any circuit breaker connected in the battery line is closed.
2. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and will then display the default menu on the LCD.
3. Switch the Maintenance Switch from ‘BPS’ to ‘UPS’.
4. Refit the Maintenance Switch cover plate on the back of the UPS.
a) The UPS will now be running with the load on bypass.
5. On the UPS Control Panel, press the ON/OFF key for more than one second.
a) The alarm buzzer will sound and the UPS will start. b) After a few seconds, the UPS will switch to its ‘on-line’ mode.
6. Check that the LCD indicates the ‘on-line’ status and no warning alarms are present.
7. The UPS is now fully operational and providing protected output power.
CAUTION: This mode is normally used only by fully trained UPS service engineers when gaining internal access to the UPS. It is not required during normal UPS operation or use.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
WARNING: Even with the UPS input breakers M1 and M2 open, potentially lethal voltages are still present within the unit.
4: Operating procedures
40 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.8 Parallel module system procedures
Figure 4.1 External maintenance bypass circuit
In a parallel module system each module will be connected to individual external module input and output isolators. together with a System Output Breaker that connected the combined modules’ output to the load distribution panel. It is also likely that the system will include a ‘wrap-around’ maintenance bypass circuit, comprising a System Input Breaker and System Bypass Breaker, similar to that shown in Figure 4.1.
Before using the parallel module system operating procedures given below you should familiarise yourself with any site­specific external switching arrangements and modify the procedures accordingly.
Key Point: The UPS commissioning engineer will explain the function of any external power isolators and maintenance bypass operation during the system handover.
UPS 1 UPS 2 UPS 3 UPS 4
MAINS / BYPASS
System Output Breaker
System Input Breaker
UPS 1 Input/bypass Isolator
UPS 2 Input/byp Isolator
UPS 3 Input/byp Isolator
UPS 4
Input/byp
Isolator
UPS 1
Output
Breaker
UPS 2
Output
Breaker
UPS 4
Output
Breaker
UPS 3
Output
Breaker
To Load Dist. Panel
System Bypass
Breaker
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 41
4: Operating procedures
4.9 Parallel system start-up
Use this procedure to start a multi-module parallel UPS system from a completely powered down condition.
1. Check that all the loads connected to the UPS are turned off.
2. Check that the individual modules’ Output Breakers and the System Output Breaker are all open.
On each module in turn
3. Close the external UPS Input/bypass Isolators as required to connect power to the UPS.
4. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
5. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and then display the default menu on the LCD.
6. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
System start-up
7. On the UPS Control Panel of ANY module, press the ON/OFF key for more than one second.
a) The alarm buzzer will sound and ALL the UPS modules will start. b) After a few seconds, ALL the UPS modules should switch to the ‘on-line’ mode simultaneously.
8. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
9. On any one of the UPS modules, press the ON/OFF key continuously for more than three seconds.
a) All UPS modules will transfer to ‘on-bypass’ mode simultaneously.
10. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
11. Close the output breaker on ALL modules to parallel the UPS output.
12. On any one of the UPS modules, press the ON/OFF key continuously for more than three seconds.
a) All the UPS modules will switch to the ‘on-line’ mode.
13. Close the System Output Breaker, to connect the UPS output to the load distribution panel.
14. The parallel UPS system is now fully operational and providing protected output power.
15. You can now switch on the loads. (If possible, turn on the loads sequentially to prevent any UPS overloads occurring due to combined inrush currents.)
4.10 Parallel system – changing the operating mode
When the parallel system is turned on and operational you can quickly switch between its various operating modes as shown below:
From To Action
ON-LINE ON-BYPASS
*Press the ON/OFF key for 3 seconds on ANY module.
ON-BYPASS ON-LINE Press the ON/OFF key for 3 seconds on ANY module.
ON-BATTERY ON-LINE Restore the mains.bypass power supply.
* If the bypass is disabled in the
SETTINGS
menu, when pressing the ON/OFF key for three seconds the UPS will go
from ON-LINE to ON-BATTERY mode.
4: Operating procedures
42 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.11 Parallel system – start/stop one module
If a parallel system includes a redundant module, you can use this procedure to stop or start an individual module without affecting the UPS critical load power.
To turn OFF one module
1. From the default screen, press the DOWN key for one second to access the Main Menu.
2. Scroll to the ‘Turn OFF Single Module’ screen, as shown [A].
3. Press the SELECT key.
a) The cursor will flash on NO.
4. If you want to turn OFF the module use the UP/DOWN keys so that the cursor indicates YES, then select it by pressing the SELECT key for more than one second [B].
5. The UPS module will turn OFF without affecting the rest of the system.
6. To isolate the shut-down module open its external input and output breakers and isolate the external battery cabinet fuses if used.
To turn on the module
1. Ensure the module’s external Output Breaker is open.
2. Close the external UPS Input/bypass Isolators as required to connect power to the UPS.
3. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
4. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and will then display the default menu on the LCD.
5. On the UPS Control Panel, press the ON/OFF key for more than one second.
a) The alarm buzzer will sound and the UPS will start. b) After a few seconds, the UPS will switch to its ‘on-line’ mode.
6. Check that the LCD indicates the ‘on-line’ status and no warning alarms are present.
7. Close the module’s external Output Breaker.
8. The UPS is now fully operational and providing protected output power in parallel with the other system modules.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
Measurements
Event Log
Control
Buzzer mute
Identification
Settings
Turn OFF Single
UPS
Single UPS Turn off: no
yes
<1s
Figure 4.2 Turning of one module in a parallel system
A
B
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 43
4: Operating procedures
4.12 Parallel module complete system shut-down
Use this procedure to totally shut-down and power off multi-module UPS system
1. Turn off the individual load items.
2. Open the System Output Breaker.
3. Open the individual UPS Output Breakers.
If the modules are ‘on-line’
4. On the Control Panel of ANY on-line module, press the ON/OFF key continuously for more than three seconds. For ALL modules:
a) The alarm buzzer will sound. b) The UPS will transfer to ‘on-bypass’ mode and its output will remain live through the (unprotected) bypass supply.
5. Go to step 9.
If the modules are ‘on-bypass’
6. Go to step 9.
If the modules are ‘on-battery’
7. On the Control Panel of ANY module, press the ON/OFF key continuously for more than three seconds. For ALL modules:
a) The alarm buzzer will sound for three seconds b) The output power will be immediately cut-off. c) The fans will stop. d) After a few seconds the UPS LCD display will power down.
8. Go to step 9.
All Modes
9. On the back of each UPS cabinet in turn, open the input breakers M1 and M2 (position OFF).
a) Power will be removed from the UPS output terminals b) The fans will stop. c) After a few seconds the UPS LCD display will power down.
10. To totally isolate the modules, open the external mains/bypass power Input Isolators and, where used, open the external battery cabinet fuses/isolator.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
4: Operating procedures
44 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.13 External Maintenance Bypass operation
An external maintenance bypass circuit, such as that shown in Figure 4.1, allows the UPS system to be totally powered down while maintaining the load supply through the (unprotected) bypass supply.
Transferring the load from the UPS to the external bypass
1. On the Control Panel of ANY module, press the ON/OFF key continuously for more than three seconds. For ALL modules:
a) The alarm buzzer will sound. b) The UPS will transfer to ‘on-bypass’ mode and its output will remain live through the (unprotected) bypass supply.
2. Close the external System Bypass Breaker.
3. Open the System Output Breaker.
4. The load is now powered entirely through the (unprotected) external maintenance bypass supply.
To shutdown the UPS modules
5. Open the individual modules’ Output Breakers.
6. On the back of each UPS cabinet in turn, open the input breakers M1 and M2 (position OFF).
a) Power will be removed from the UPS output terminals b) The fans will stop. c) After a few seconds the UPS LCD display will power down.
7. To totally isolate the UPS modules, open the UPS Input/bypass Isolators and, where used, open the external battery cabinet fuses/isolator.
Transferring the load from the external bypass to the UPS
On each UPS module in turn
1. Close the external Input/bypass Isolators as required to connect power to the UPS.
2. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
3. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and will then display the default menu on the LCD.
4. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
System start-up
5. On the UPS Control Panel of ANY module, press the ON/OFF key for more than one second.
a) The alarm buzzer will sound and ALL the UPS modules will start. b) After a few seconds, ALL the UPS modules should switch to the ‘on-line’ mode simultaneously.
6. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
7. On any one of the UPS modules, press the ON/OFF key continuously for more than three seconds.
a) All UPS modules will transfer to ‘on-bypass’ mode simultaneously.
8. Check that no abnormal conditions are shown on any of the modules’ LCD panel.
9. Close the external Output Breaker on ALL modules to parallel the UPS output.
10. Close the System Output Breaker, to connect the UPS (‘on-bypass’) output to the load distribution panel.
11. Open the external System Bypass breaker.
12. On any one of the UPS modules, press the ON/OFF key continuously for more than three seconds.
13. All UPS modules will transfer to ‘on-line’ mode simultaneously.
CAUTION: This mode is normally used only by fully trained UPS service engineers, for example when repairing/ replacing a UPS system, and is not generally required during normal UPS system operation or use.
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 45
4: Operating procedures
14. The parallel UPS system is now fully operational and providing protected output power.
4.14 Operating a frequency changing system
In a frequency changing system the UPS output frequency is different to its input frequency and therefore it is not possible to implement any form of bypass circuit.
4.14.1 Frequency changer – starting the UPS
1. Check that all the loads connected to the UPS are turned off.
2. Close the external UPS Input/bypass Isolators as required to connect power to the UPS.
3. If an external battery cabinet is used, close the fused isolator on the back of the battery cabinet together with any circuit breaker connected in the battery line.
4. On the back of the UPS cabinet, close the input breakers M1 and M2 (position ON).
a) The fans will start running. b) The UPS will perform a self-test and will then display the default menu on the LCD.
5. In the case of a multi-module system repeat the above procedure for ALL modules
6. On the UPS Control Panel, press the ON/OFF key for more than one second (on ANY module in a multi-module system).
a) The alarm buzzer will sound and the UPS will start. b) After a few seconds, the UPS (system) will switch to its ‘on-line’ mode.
7. Check that the LCD indicates the ‘on-line’ status and no warning alarms are present.
8. The UPS is now fully operational and providing protected output power.
9. You can now switch on the loads. (If possible, turn on the loads sequentially to prevent any UPS overloads occurring due to combined inrush currents.)
4.14.2 Frequency changer – stopping the UPS
Use this procedure to totally shut down a frequency changer system and its connected load.
1. Turn off the individual load items.
2. On the Control Panel, press the ON/OFF key continuously for more than three seconds (on ANY module in a parallel system).
a) The alarm buzzer will sound for three seconds b) The output power will be immediately cut-off. c) The fans will stop. d) After a few seconds the UPS LCD display will power down.
3. To totally isolate the UPS, open the UPS Input/bypass Isolators and, where used, open the external battery cabinet fuses/isolator.
WARNING: With the UPS shut down allow at least 5 minutes for the UPS DC capacitors to discharge before gaining internal access.
4: Operating procedures
46 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.15 Emergency Stop
Details for the Emergency Power Off (EPO) circuit operation is given in Paragraph 7.2.
If the EPO circuit is activated it must be cleared through an LCD menu before the UPS can be returned to normal use.
To clear an EPO operation
1. From the default screen, press the DOWN key for one second to access the Main Menu.
2. Scroll to the ‘Clear EPO Status’ screen, as shown [A].
3. Press the SELECT key.
a) The cursor will flash on NO.
4. If you want to clear the EPO status use the UP/DOWN keys so that the cursor indicates YES, then select it by pressing the SELECT key for less than one second [B].
5. The EPO status will now be cleared.
6. Scroll back to the default LCD display.
Measurements
Event Log
Control
Buzzer mute
Clear EPO Status
...............
Identification
Settings
..............
<1s
Figure 4.3 Clearing the EPO operation
A
B
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 47
5
Maintenance
5.1 Introduction
5.2 System calibration
To ensure optimum UPS operation and continuous, efficient protection of the connected load, it is recommended that the system’s operating parameters are checked every six months and recalibrated where necessary. The batteries should also be checked every six months, depending on the ambient temperature.
5.3 User responsibilities
As there are no user-serviceable parts contained within the UPS, the maintenance required by the user are minimal apart from keeping the equipment clean and monitoring the working environment to ensure it is kept cool and dust-free. This will maximise the useful working life and reliability of the UPS and its batteries.
5.4 Routine maintenance
It is essential that the UPS system and batteries receive regular preventative maintenance inspection. When the UPS is commissioned, the commissioning field service engineer will attach a service record book to the UPS which will be used to log the full service history of the UPS.
Preventative maintenance inspections involve working inside the UPS which contains hazardous AC and DC voltages and should only be performed by authorised service personnel.
During a preventative maintenance inspection the field service engineer will check:
• Site/environment conditions
• Integrity of electrical installation
• Cooling airflow
• Rectifier operation and calibration
• Inverter operation and calibration
• Static switch operation
• Battery status
• Load characteristics
• Integrity of alarm and monitoring systems
• Operation of all installed optional equipment
Preventative maintenance inspections form an integral part of all Extended Warranty Agreements (maintenance contracts) offered by Uninterruptible Power Supplies Ltd.
WARNING: The UPS contains hazardous voltages even when switched off. WARNING: Do not remove the UPS covers unless you are electrically qualified and trained on the
equipment type by the manufacturer (Uninterruptible Power Supplies Ltd) or one of its service agents.
WARNING: There are no user-serviceable part contained within the UPS. WARNING: Any operation described in this chapter that requires internal access to the UPS or external
battery cabinets must be performed by authorised service personnel.
5: Maintenance
48 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
5.5 Battery testing
The battery test takes approximately 3 minutes and should be performed only if:
• There are no alarm conditions
• The battery is fully charged
• The mains input supply is present
Battery testing can be performed from the Operator Control Panel and carried out independently of the operating mode (‘on-line’ or ‘on-bypass’) and whether or not the load is connected.
5.6 Battery maintenance
The UPS batteries should be replaced under the following conditions:
• If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded
• When the discharging time is less than 50% of specified after full charged
When replacing the batteries, the complete battery string should be replaced with the same number and type of batteries. Individual batteries should not be replaced.
If the UPS is not used for a period of time the batteries should be charged at least every 4-6 months. When healthy, the batteries will charge to 80% in approximately 10 hours, however it is recommended that the batteries are charged for 48 hours after long term storage.
5.7 Battery disposal and recycling
Batteries contain dangerous substances that will harm the environment if carelessly discarded and should be disposed of in accordance with local recycling recommendations
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 49
6
Troubleshooting
6.1 Contacting Service
Please collect the following information before calling the After-Sales Service Department:
• UPS model number and serial number
• Date on which the problem occurred
• LCD/LED display information, buzzer alarm status
• Mains power condition, load type and capacity, environment temperature, ventilation condition
• Information on external batteries (battery capacity, quantity)
Uninterruptible Power Supplies Limited has a service department dedicated to providing routine maintenance and emergency service cover for your UPS. If you have any queries regarding your UPS please contact us.
We recommend that your UPS is protected by an Extended Warranty Agreement. These agreements assist us in caring for your UPS correctly, ensuring that it is well maintained and attended to promptly should any problems occur.
IMPORTANT NOTE
Certain alarm conditions may ‘latch-on’ even after the cause of the alarm is no longer present. For example, if there is a brief mains failure during unattended operation the MAINS FAIL alarm will activate and it may still indicate a fault condition even after the mains supply has returned to normal. Similarly, a LOAD ON BYPASS alarm might have been caused by an inverter overload
If any alarm appears, the first action to take is to attempt to RESET it.
If the alarm indication resets then it was probably caused by a transient condition; the UPS has responded correctly and no further action is required. Investigative action is necessary if it is not possible to reset the alarm, or if the alarm is repetitive, which may require assistance from the UPS Limited Service Department.
Uninterruptible Power Supplies Ltd. Woodgate Bartley Wood Business Park Hook Hampshire RG27 9XA
Tel: 01256 386700
0800 731 3269 (24 Hr.)
Fax: 01256 386701
Email: service@upspower.co.uk
6: Troubleshooting
50 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
6.2 Fault identification and rectification
6.2.1 Troubleshooting without an error message
6.2.2 Troubleshooting based on error message
Display Possible Cause Remedy
No indication on LCD display. No warning tone even though system is connected to mains power supply.
No input voltage Check the building wiring and input cable.
Check that the external Input/bypass Isolator is closed.
Bypass LED ON even if the power supply is available.
Inverter not switched on Press the POWER-ON key to turn on UPS and switch
to ‘on-line’ mode.
Battery LED ON and audible alarm sounding
Input voltage and/or frequency out of tolerance
Check that the external Input/bypass Isolator is closed
Check availability of input power source.
Check the building wiring and input cable.
Emergency supply period shorter than nominal value
Batteries not fully charged or defective
Charge the batteries for at least 12 hours and then check capacity.
Display Possible Cause Remedy
Inv Overload Failure
Alarm code:42
Overload. Check the loads / remove non-critical loads.
Check if some loads have failures.
Byp Overload Failure
Alarm code:43
Overload. Check the loads / remove non-critical loads.
Check if some loads have failures.
Output short-circuit
Alarm code:31
Short circuited output. Remove all the loads.
Turn off the UPS.
Check if UPS output and loads are short-circuited.
Ensure short circuit is removed before turning on the system again.
Heatsink Over Temperature Fault Alarm code:81
Inside temperature of UPS is too high.
Ensure the UPS is not overloaded, the air vents are not blocked and the ambient temperature is not too high. Wait for 10 minutes for the UPS to cool down before turning it on again. If failed, contact the service centre.
DC BUS over-voltage
Alarm code:21
UPS internal fault. Contact UPS supplier.
DC BUS under-voltage
Alarm code:22
UPS internal fault. Contact UPS supplier.
DC BUS unbalanced
Alarm code:23
UPS internal fault. Contact UPS supplier.
DC BUS softstart failure
Alarm code:25
UPS internal fault Contact UPS supplier.
INV over-voltage
Alarm code:32
UPS internal fault. Contact UPS supplier.
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 51
6: Troubleshooting
INV under-voltage
Alarm code:33
UPS internal fault. Contact UPS supplier.
INV under-voltage
Alarm code:33
UPS internal fault. Contact UPS supplier.
Display Possible Cause Remedy
52 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
7
Options
7.1 Back-feed protection
Figure 7.1 Backfeed protection option
An external isolation contactor can be fitted in the UPS bypass supply line as shown in Figure 7.1 to protect the UPS against back-feeding in the event of a critical static switch failure.
The external contactor magnetic ‘trip’ coil is connected to the backfeed contactor control terminals located behind a small cover on the back of the UPS.
An AC contactor rated at 100A minimum should be used – for example a three phase contactor of 3x 40A rating with the three poles wired in parallel. The trip coil should be rated according to bypass supply.
External magnetic contactor
Neutral Line
Bypass Line
Mains/
Bypass
Supply
Terminals
Internal board
OUT
IN
Backfeed inactive
Relay N/C
UPS CABINET
Backfeed Terminals
TRIP
BACKFEED
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 53
7: Options
7.2 Emergency Power-OFF (EPO)
Figure 7.2 Emergency Power OFF
An external Emergency Power OFF (EPO) circuit can be connected to the UPS to enable it to be shut down remotely in an emergency situation. By default the external EPO circuit requires a normally closed contact which shuts down the UPS when opened. A link must be fitted to the EPO connector located on the back of the UPS if the EPO facility is not used, as shown above in Figure 7.2.
7.3 Computer communication options.
Figure 7.3 RS232 and USB Communication options
A USB and an RS232 port are provided to enable communication between the UPS and a remote computer/station. Only one communication port can be active at a time and the priority is given to the USB port.
When appropriate power management software, such as WAVEMON, is installed, the computer can continuously monitor the input mains voltage and UPS status, and display a message in response to any UPS system changes.
In the event of a power failure, and a predicted UPS shutdown due to low battery autonomy, the WAVEMON monitoring system will save the existing load data before initiating a shutdown of the load equipment.
7.3.1 USB Port
To establish communication between the UPS and a computer, connect the USB cable that is supplied with the UPS between the UPS USB port and the USB port on the computer. The USB port is compliant with USB 1.1 protocol.
Key Point: Although the EPO facility is normally (factory) set to be a normally-closed contact, it can be reconfigured through the USB/RS232 port to be a normally-open contact. However, such a change must be carried out by an approved service engineer.
EPO
RS232 USB
7: Options
54 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
7.3.2 RS232 Port.RS232 and USB Communication options
Figure 7.4 RS232 Pin assignment
To establish a communication link between the UPS and a computer, connect one end of the serial communication cable that is supplied with the UPS to the RS-232 port on the UPS and the other end to the RS- 232 port on a computer. The cable pins for the RS-232 communication port are described in Figure 7.4.
7.4 Serial Network Management (SNMP) card
Figure 7.5 SNMP connection options
Simple Network Management Protocol (SNMP) is a world-wide, standardised communication protocol that can be used to monitor any network-connected device via a simple control language and display the results in an application running within a standard web browser. The SNMP adaptor requires a PC with terminal connections, and least one Ethernet network connection.
The optional SNMP card fits into the ‘Intelligent Slot’ located on the back of the PowerWave PW3000/TP, as shown in Figure 7.5. Alternatively, SNMP connectivity can be implemented using an external SNMP adapter connected to the UPS RS232 output, as shown.
An SNMP/Ethernet adapter contains an RJ-45 connector which allows it to be connected to the network using a standard network cable. Once connected, the UPS-Management software agent, which is already installed in the SNMP adapter, then monitors the UPS operating parameters and outputs its data in SNMP format to the connected network. In a multi­module UPS system the SNMP interface can communicate ‘system-wide’ data or data for an individual UPS module.
SNMP card installation
The UPS does not have to be shutdown before installing a communication card:
1. Remove the two screws that protect the Intelligent Slot of the UPS.
2. Insert the SNMP card into the slot.
3. Secure the SNMP card in position using the screws removed in step 1.
Note: For more information on the SNMP Cards, see the SNMP User's Manual.
Pin Signal Description I/O
2 TXD Transmit to external device Output
3 RXD Receive from external device Input
5 GND Ground (tied to chassis) Input
ETHERNET
External SNMP Adapter
Internal SNMP Card
SNMP MONITOR
RS232
SNMP Slot
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 55
7: Options
7.5 AS400 Interface card
Figure 7.6 AS400 Pin assignment
The optional AS400 Interface card fits into the ‘AS400’ slot located on the back of the PowerWave PW3000/TP. The card provides five UPS status/alarm outputs and monitors three switched inputs via two 7-way Phoenix terminal blocks.
The card also contains an RS232 interface which can be used to configure the card’s operation. Using some basic terminal communication software, such as Hyper terminal, it is possible to change both the function and polarity of the relay; for example, to select an individual switch segment to be Normally-Open or Normally-Closed, and immediate/ delayed operation. Detailed operating instructions are included in the option package.
RS232 Interface
The inbuilt RS232 interface is accessed via an RJ45 connector located adjacent to the I/O terminal blocks. An RJ45 to 9­way D-Type adapter cable is provided with the equipment to allow connection to a computer’s serial port.
AS400 Alarm outputs
The switched outputs are configured as 5 segments:
The card’s internal volt-free contacts are rated at 250VAC/8A, 30VDC/8A, 110VDC/300mA, 220VDC/120A, and the terminal block accommodates cables in the range 0.5 mm² to 1.5 mm².
WARNING: The RJ45 connector must only be used for RS232 applications. If it is connected to a network switch it may damage the UPS and/or network equipment.
Segment 1 Terminal 9-2 Utility (mains) Failure
Segment 2 Terminal 10-3 Battery Low
Segment 3 Terminal 11-4 General Alarm
Segment 4 Terminal 12-5 Bypass Status
Segment 5 Terminal 13-6 Summary Alarm
AS400 Slot
1234567
891011121314
12345
6
7
8
S1S2S3S4S5
GND
91011121314
Internal Relays
AS400 CARD
7: Options
56 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
AS400 Inputs
The switched inputs are configured as 3 segments:
AS400 Interface Card installation
The AS400 Interface Card should be installed and configured by the commissioning engineer.
7.6 UPS Monitoring and automated control software
7.6.1 The importance of UPS management
The utility supply is inevitably unreliable every now and then; and assuring continuous power to all the facilities connected to it can be a difficult task. The situation is further complicated if worldwide systems are managed via a Local Area Network (LAN) or Wide Area Network (WAN). However, by using the PowerWave PW3000/TP UPS system in conjunction with purpose-designed network management tools, a systems administrator can take measures to back-up data and prevent system errors or data loss even in the event of a relatively long utility supply outage. In the case of an abnormal utility supply, suitable UPS management software will also enable a system administrator to monitor all concerned networks from a central point and identify bottlenecks at an early stage.
Despite extensive system monitoring, serious damage can still occur if an administrator fails to intervene in a timely manner, so it is important that the installed UPS software will react automatically in such a case and shut down the supplied system in a safe and controlled manner.
Uninterruptible Power Supplies Ltd considers it important to have a complete solution for its UPS systems, and offers its customers a number of remote control and monitoring tools to provide optimum protection.
SNMP monitoring/control software
Working in conjunction with the adapter card described above, Uninterruptible Power Supplies Ltd offer suitable monitoring and control software with SNMP functionality for NetWare, OS/2 and all Windows NT systems on INTEL and ALPHA network platforms.
Segment 6 Terminal 8-1 User Configurable
– Battery Mode Shutdown (Default) – Any Mode Shutdown – Emergency Power Off – Remote ON/OFF
Segment 7 Terminal 14-1 Reserved for UPS ON Signal
(Switch On UPS)
Segment 8 Terminal 7-1 Reserved for UPS OFF Signal
(Switch OFF UPS)
1234567
8
GND
USER SW2
USER SW1
USER SW3
91011121314
AS400 CARD
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18 57
8
Specifications
10kVA
10kVA
+5 min battery
10kVA
+16 min battery
20kVA
20kVA
+5 min battery
GENERAL
Output power factor 0.9 0.9
Rated output power (@ pf=0.8) 10 kVA 20 kVA
Rated output power (@ pf=1.0) 9 kW 18 kW
Weight 56 kg 117 kg 177 kg 66 kg 187 kg
Dimensions WxHxD 350x890x712 350x890x712 350x890x712 350x890x712 350x890x712
Colour Pantone Process Black C
Topology True on-line double conversion
INPUT CHARACTERISTICS
Nominal input voltage 1ph + N: 220 / 230 / 240 VAC 3ph + N: 380 / 400 / 415 VAC
Input voltage tolerance 1ph + N: 110-276 Vac 3ph + N: 190-486 Vac
Power factor >
0.99
Input power at rated output (no batt charging)
9.68 kW 19.35 kW
1Ph Input current at rated output (no batt charging)
44.4A / 42.5A / 40.7A
(@ 220V / 230V / 240V)
88.9A / 85.0A / 81.5A
(@ 220V / 230V / 240V)
3Ph Input current at rated output (no batt charging)
14.9A / 14.1A / 13.6A
(@ 380V / 400V / 415V)
29.7A / 28.2A / 27.2A
(@ 380V / 400V / 415V)
Input power at rated output (max batt charging)
10.99 kW 20.43 kW
1Ph Input current at rated output (max batt charging)
50.5A / 48.3A / 46.2A
(@ 220V / 230V / 240V)
94.9A / 90.8A / 87.0A
(@ 220V / 230V / 240V)
3Ph Input current at rated output (max batt charging)
16.9A / 16.0A / 15.4A
(@ 380V / 400V / 415V)
31.7A / 30.1A / 29.0A
(@ 380V / 400V / 415V)
Input current THD <5% linear load, <7% non-linear load
Frequency range 45-55 Hz for 50 Hz system / 55-65 Hz for 60 Hz system
Frequency tolerance ±2%
NOTE: Technical specifications are subject to change without notice
8: Specifications
58 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
OUTPUT CHARACTERISTICS
Rated output voltage 220 / 230 / 240 Vac
Voltage tolerance ±2%
Voltage distortion
2% linear load, 5% non-linear load
Overload capability (linear load) 5 minutes: 105%~110%; 1 minute: 110%~130%;
10 seconds: 130%~150%; 2 seconds >150%
Nominal frequency 50 or 60 Hz ±0.1 Hz
Crest factor 3:1
EFFICIENCY (230V / 50Hz)
100% Load Up to 93%
In ECO mode (HE mode) Up to 97%
BATTERY
Inbuilt batteries No Yes Yes No Yes
Number of batteries 1 x 24 2 x 24 2 x 24
Battery capacity 9 Ah 9 Ah 9 Ah
Charger current 4A 4A 4A 4A 4A
Recharge time 3h to 90% 8h to 90% 8h to 90%
AUTONOMY TIMES (MINS) (Half load / Full load)
UPS Internal Batteries 16 / 5 41 / 16 16 / 5
UPS +1 Battery cabinet 41 / 16 59 / 28 92 / 42 16 / 5 42 / 16
UPS +2 Battery cabinet 92 / 42 118 / 49 150 / 60 42 / 16 60 / 27
UPS +3 Battery cabinet 150 / 60 180 / 80 213 / 90 60 / 27 90 / 42
UPS +4 Battery cabinet 213 / 90 245 / 103 246 / 132 90 / 42 118 / 53
ENVIRONMENTAL
Protection rating IP20
Audible noise 55 dB Measured at 1 metre from the front of the UPS on 100% load and fully charged batteries.
Storage temperature -15°C to +60°C for UPS; 0°C to +35°C for battery
Operating temperature 0°C to +40°C
Relative humidity 0-95% (non condensing)
Altitude (above sea level) 1000m without de
-rating
COMMUNICATIONS
User interface Menu-driven LCD display
Communication card options Network interface (SNMP card), Dry contact (AS400 card), USB / RS232 Computer interface
STANDARDS
Safety IEC/EN62040-1
EMC IEC/EN62040
ROHS EN50581:2012
Performance IEC/EN62040-3
Manufacturing ISO 9001:2008, ISO 14001:2004
HE AT D ISSI PATIO N
Airflow From front to back
Heat dissipation with 100% linear load
669 W / 2282.7 BTU 1207 W / 4118.5 BTU
Heat dissipation with 100% non­linear load (i.a.w. 62040-3)
669 W / 2282.7 BTU 1207 W / 4118.5 BTU
Air-flow (25° -30°) with 100% non­linear load
133 m³/h 240 m³/h
Heat dissipation with no load 160 W 170 W
10kVA
10kVA
+5 min battery
10kVA
+16 min battery
20kVA
20kVA
+5 min battery
Loading...