2: General Description
20 TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
Table 2.8 Settings sub-menu options
Sub-menu Item Description Values Default
User password Protects against unapproved access Enabled / Disabled Disabled
Language Select menu language English / Chinese English
Audio alarm Enable / disable alarm sounds Enabled / Disabled Enabled
Output voltage Define local output voltage 200/208/220/230/240V 230V
Output frequency Define local output frequency
(UPS detects the frequency in 'autosensing')
Autosensing /
50Hz / 60Hz
Autosensing
Power strategy* Define the operating mode Normal / ECO- mode /
Frequency converter
Normal
DC start (Cold start) Start the UPS from batteries, without mains power Enabled / Disabled Enabled
Automatic battery test period Define the frequency of the battery tests 0-31 days 7 days
Auto restart After power outage, the load restart automatically
when mains power is recovered
Enabled / Disabled Enabled
Automatic overload restart The UPS automatically restarts if it shuts-down
due to overload
Enabled / Disabled Enabled
Auto bypass The automatic bypass can be disabled if the
bypass power supply is very unstable.
UPS runs only ‘on-line’ or on-battery.
Enabled / Disabled Disabled
Short circuit clearance When enabled, short circuit can last for 4s before
cutting off the output. If short circuit is removed
during this time, the UPS will continue to run.
When disabled, short circuit will only last
for 100ms before the UPS output is cut off.
Enabled / Disabled Disabled
Bypass voltage low limit When the voltage in the bypass is below this limit,
the UPS changes operating mode
176 ~ 215V 176V
Bypass voltage high limit When the voltage in the bypass is above this limit,
the UPS changes operating mode.
245 ~ 276V 264V
Bypass frequency low limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
40 ~ 49.5 Hz 45 Hz
Bypass frequency high limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
50.5 ~ 70 Hz 55 Hz
HE voltage low limit When the voltage in the bypass is below this limit,
the UPS changes operating mode.
1% ~1 0% 5%
HE voltage high limit When the voltage in the bypass is above this limit,
the UPS changes operating mode.
1% ~ 10% 5%
HE frequency low limit When the frequency in the bypass is below this
limit, the UPS changes operating mode.
1% ~ 10% 5%
HE frequency high limit When the frequency in the bypass is above this
limit, the UPS changes operating mode.
1% ~ 10% 5%
External Battery modules** Define the number of external battery modules. 0 - 97 0
Set running time Reset the UPS running time for tests purposes. Day:hour:minute:second Running time
LCD contrast Change the contrast in the LCD display -5 ~ +5 0
Battery remaining time When enabled, the battery remaining time is
displayed in the menu measurements
Enabled / Disabled Disabled
*
Read section 2.3 before using ECO-mode or converter function.
** Enter the number of ADDITIONAL (external) battery strings. An incorrect entry might degrade the battery operation.