:
II UPS725-02-02 PowerWave 1000 (4.5 - 10 kVA) User Manual UK Dated 13/03/15
3.8.2 Generating a UPS profile and data file 35
3.8.3 Setting up the basic UPS operating parameters 36
3.8.4 Output voltage calibration 36
3.8.5 Managing the UPS data file 37
4 Single Module Operating Procedures
4.1 Single module start-up procedures 38
4.1.1 Normal start-up (utility available) 38
4.1.2 Start-up on battery mode (cold start) 39
4.2 Operator control functions 40
4.2.1 Using the LCD metering function 40
4.2.2 Enable/disable the audible alarm 41
4.2.3 Battery test 41
4.3 Shutdown procedures 42
4.3.1 Normal shutdown (with mains available) 42
4.3.2 UPS shutdown when on battery 42
4.4 Manual load transfer between inverter and bypass 43
4.4.1 Transferring the load from the UPS inverter to the internal bypass 43
4.4.2 Transferring the load from the static bypass back to the UPS inverter 43
5 Parallel UPS System Operating Procedures
5.1 System start-up procedure 44
5.2 Shutdown procedure 46
5.3 Manual load transfer between inverter and bypass 46
5.3.1 Transferring the load from the UPS inverter to the internal bypass 46
5.3.2 Transferring the load from the static bypass back to the UPS inverter 47
6 Maintenance
6.1 Battery replacement 48
7 Troubleshooting
7.1 Introduction 49
7.2 Error codes 49
7.2.1 Audible alarm interpretation aids 50
7.3 Troubleshooting a fault condition 50
7.4 Troubleshooting an operational problem. 51
7.5 UPS Fault handling 51
7.5.1 UPS Overload 51
7.5.2 Output short circuit 51
7.5.3 Inverter/internal over-temperature 52
7.5.4 Inverter over-current and output voltage out of tolerance 52
8 Options
8.1 The importance of UPS management 53
8.2 WAVEMON shutdown and management software 53
8.2.1 Functional description 54
8.2.2 Licensing 54
8.3 SNMP adapters 55
8.4 AS400 (dry contact) card 55
8.5 USE (USB) card 56
8.6 R2E (second RS-232) card 56
9 Specification