Uninterruptible Power Supplies Minipower Plus Rack User Manual

Uninterruptible Power Supply
Minipower Plus Rack
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
User Manual
Uninterruptible Power Supplies Ltd has taken every precaution to produce an accurate, complete and easy to understand manual and
will therefore assume no responsibility nor liability for direct,
indirect or accidental personal or material damage due to any
This manual may not be copied nor reproduced without written
permission of Uninterruptible Power Supplies Ltd.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
© 2006 Uninterruptible Power Supplies Ltd
Document Control
ISSUE DATE REVISION SUMMARY
1.0 01-08-06 General manual consolidation re-issue
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Table of Contents
Safety 1-1
Description 2-1
Introduction 2-1 Warranty 2-1 Extended Warranty 2-2 Additional Service/Maintenance Support 2-2
Installation 3-1
Introduction 3-1
Receipt of the UPS 3-1
Nameplate 3-1 Unpacking 3-1 Batteries 3-2 Storage 3-2
UPS 3-2
Battery 3-2 Positioning 3-3 Front Panel 3-4 Single Cabinet UPS Installation 3-4 Expansion of Autonomy 3-6
Operation 4-1
Commissioning 4-1 Operation 4-1 Operating Principles 4-2 Operating Modes 4-3
Mains Operation 4-3
Battery Operation 4-3
Bypass Operation 4-3 Basic Operation 4-4
Switch On 4-4
Switch Off 4-4 Displays and Alarms 4-5
Warning Signals 4-6 Customising the Operating Mode 4-7
Button Functions 4-7
Service Mode 4-7 Accessing the Menus 4-8
Main Menu 4-8
UPS Status 4-8
UPS Setup 4-9
Events 4-13
Programming 4-13
Tools 4-14 Diagnostic Software 4-14
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 i
Maintenance 5-1
Introduction 5-1 User Responsibilities 5-1 Routine Maintenance 5-1
Troubleshooting 6-1
Potential Problems and Solutions 6-1 Contacting Service 6-2
Options 7-1
Specifications 8-1
ii UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
1

Safety

BEFORE ATTEMPTING TO INSTALL OR START UP THIS UPS THE USER MUST ENSURE THAT THE SAFETY INSTRUCTIONS IN THIS MANUAL ARE CAREFULLY READ AND OBSERVED BY TECHNICALLY COMPETENT PERSONNEL. KEEP THIS MANUAL WITH THE UPS FOR FUTURE REFERENCE.
THIS UPS MUST NOT BE STARTED UP OR PUT INTO USE WITHOUT HAVING BEEN COMMISSIONED BY A FULLY TRAINED AND AUTHORISED PERSON.
ALL SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL. DO NOT ATTEMPT TO SERVICE THE UPS YOURSELF.
BY OPENING OR REMOVING THE UPS-COVERS YOU RUN RISK OF EXPOSURE TO DANGEROUS VOLTAGES!
UNINTERRUPTIBLE POWER SUPPLIES LTD WILL ASSUME NO RESPONSIBILITY NOR LIABILITY DUE TO INCORRECT OPERATION OR MANIPULATION OF THE UPS.
HIGH LEAKAGE CURRENT! MAKE SURE THAT THE EARTHING IS CARRIED OUT CORRECTLY BEFORE YOU CONNECT THE MAINS POWER SUPPLY!
The MINIpower PLUS Rack model 1.25 - 5kVA IS CLASS A - UPS­PRODUCT (ACCORDING TO EN 50091-2).
IN A DOMESTIC ENVIRONMENT IT MAY CAUSE RADIO INTERFERENCE. IN SUCH AN ENVIRONMENT THE USER MAY BE REQUIRED TO UNDERTAKE ADDITIONAL MEASURES.
ALL THE INFORMA TION CONT AINED IN THIS MANUAL IS PROVIDED AS A GUIDE AND IS SUBJECT TO CHANGE WITHOUT NOTICE FOR PRODUCT UPGRADING.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 1-1
1-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
2

2.1 Introduction

Description

Congratulations on your purchase of the MINIpower PLUS. Your new UPS incorporates the latest technological developments in power engineering. High reliability , upgrade ability , low operating cost and excellent electrical performance are only some of the highlights of this innovative UPS solution.
Uninterruptible Power Supplies Ltd. specialises in the design, building, installation and maintenance of Uninterruptible Power Systems. This compact and powerful UPS is just one example of our wide range of state of the art power protection devices and will provide your critical equipment with a steady and reliable power supply for many years.
The criteria and methods which are used in the design, manufacture, and maintenance of Uninterruptible Power Supply systems are certified to International Standard ISO 9001/EN 29001. A full UPS Specification is given in Chapter 8 of this manual.
The MINIpower PLUS UPS is supplied with a limited warranty that the UPS and its component parts are free from defects in materials and workmanship for a period of one year from the date of original commissioning or fifteen months from the date of original delivery, whichever is the sooner. This warranty is the only warranty given and no other warranty, express or implied, is provided.

2.2 Warranty

This warranty is invalidated if the UPS is put into use without having been commissioned by a fully trained and authorised person. This warranty does not apply to any losses or damages caused by misuse, abuse, negligence, neglect, unauthorised repair or modification, incorrect installation, inappropriate environment, accident, act of God or inappropriate application.
If the UPS fails to conform to the above within the warranty period then Uninterruptible Power Supplies Ltd. will, at its sole option, repair or replace the UPS. All repaired or replaced parts will remain the property of Uninterruptible Power Supplies Ltd.
The UPS may contain batteries which must be re-charged for a minimum of 24 hours every six months to pr event deep- discharging. Batteries that have been, for whatever reason, deep-discharged are not covered by the warranty.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 2-1

2.3 Extended Warranty

The standard warranty may be enhanced by protecting the UPS with an Extended Warranty Agreement (maintenance contract).
An Extended Warranty Agreement enhances the standard warranty by providing the following:-
Regular preventative maintenance inspections
Guaranteed speed of response to operational problems
24 hour telephone support
Fully comprehensive (excluding batteries) cover
Contact the Service Support Hotline on 0800 731 3269 for further details.

2.4 Additional Service/Maintenance Support

In addition to providing support for the MINIpower PLUS UPS, Uninterruptible Power Supplies Ltd. are able to provide maintenance and support on a wide range of different UPS products.
If you are interested in an extended warranty for your MINIpower PLUS UPS, or any other UPS you may have, please complete the enquiry form overleaf and return or FAX to:
Uninterruptible Power Supplies Ltd. Bacchus House Calleva Park Aldermaston Berkshire RG7 8EN
Tel: 0118 981 5151
0800 773 3269 Fax: 0118 981 5152 Email: service@upspower.co.uk
2-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Fax to: 0118 981 5152
www.upspower.co.uk
Uninterruptible Power Supplies Ltd. Bacchus House Calleva Park Aldermaston Berkshire RG7 8EN
Tel: 0118 981 5151
Name: ............................................................................................
Job Title: ............................................................................................
Company: ............................................................................................
Address: ............................................................................................
............................................................................................
............................................................................................
............................................................................................
Post Code ............................ ... ... ..........................................................
Tel. ............................................................................................
Fax. ............................................................................................
E-mail ............................................................................................
Please contact me to discuss:
Extended Warranty options for my MINIpower PLUS UPS Extended warranty options for my UPS System as below:
Manufacturer:...................................................................
Model Nº:..........................................................................
Rating kVA:..................... ... ... ... .........................................
Replacement Batteries......................................................................
Other ..................................................................(please specify)
Thank you for your enquiry, which will receive our prompt attention.
If you need to contact us immediately call free on,
Freefone 0800 731 3269
or E-mail us on service@upspower.co.uk
www.upspower.co.uk
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 2-3
2-4 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
3

3.1 Introduction

Installation

This chapter contains all the necessary information for the correct unpacking, positioning, cabling and installation of the MINIpower PLUS UPS.
ALL THE OPERA TIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED PERSONNEL. UNINTERRUPTIBLE POWER SUPPLIES LTD. WILL TAKE NO RESPONSIBILITY FOR ANY LOSS, PERSONAL OR MATERIAL DAMAGE CAUSED BY INCORRECT CABLING, OPERATIONS OR ACTIVITIES WHICH ARE NOT CARRIED OUT AS PER THE INSTRUCTIONS CONTAINED IN THIS MANUAL.

3.1.1 Receipt of the UPS

The packing container of the UPS protects it from mechanical and environmental damage. To increase its protection the MINIpower PLUS UPS is wrapped with a plastic sheet.

3.2 Unpacking

Upon receiving the UPS, carefully examine the packaging and the UPS for any sign of physical damage.
Ensure that the received UPS corresponds to the description indicated in the delivery note.

3.1.2 Nameplate

The technical specifications of the MINIpower PLUS UPS are provided on the attached nameplate.
When unpacking the UPS observe the “FRAGILE” and “ARROW” indications on the packaging.
Perform the following steps to unpack the UPS:
Cut the wrappers and remove the packaging by pulling it upwards.
Remove the plastic cover from the UPS.
Remove the UPS from the pallet.
Retain the packaging materials for future shipment of the UPS.
Examine the UPS for any sign of damage. Notify your supplier immediately if damage is apparent.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 3-1

3.3 Batteries

3.4 Storage

The standard batteries for the UPS are sealed, maintenance free, internally mounted and will typically be connected when the UPS is commissioned.
The battery life depends very much on the ambient temperature. A temperature range between +18° and +23°C will achieve the optimum battery life.
If the UPS is delivered without batteries, Uninterruptible Power Supplies Ltd. is not responsible for any damage or malfunctioning caused to the UPS by the incorrect installation or connection of batteries by third parties.

3.4.1 UPS

If you plan to store the UPS prior to use, store it unpacked in a clean dry environment with a temperature between -20°C to +50°C and humidity of less than 90%.
If the packing container is removed, protect the UPS from dust.

3.4.2 Battery

The UPS is equipped with sealed, maintenance-free batteries, whose storage capability depends on ambient temperature. It is therefore important not to store the UPS longer than 6 months at 20°C, 3 months at 30°C and 2 months at 35°C storage temperature without a battery recharge.
For longer term storage make sure that the battery is fully recharged every 6 months.
SEALED BATTERIES MUST NEVER BE STORED IN A DISCHARGED OR PARTIALLY DISCHARGED STATE.
EXTREME TEMPERATURE, UNDER- AND OVERCHARGE AND OVERDISCHARGE WILL DESTROY BATTERIES!
Before and after storing, charge the battery. Always store the batteries in a dry, clean, cool environment in their original
packaging. If the packaging is removed protect the batteries from dust and humidity.
3-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06

3.5 Positioning

Min 100mm
The MINIpower PLUS is a compact and light UPS and can easily be moved to its final position.
The UPS should be located where:
Humidity and temperature are within prescribed limits.
Fire protection standards are respected.
Cabling can be performed easily.
Access is available for service or periodic maintenance.
Required cooling air flow is possible.
The site air conditioning system has sufficient capacity.
Dust or corrosive/explosive gases are absent.
The site is vibration free.
Minimum 200 mm space is required above the UPS for proper cooling.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 3-3
Figure 3.1: Ventilation Clearances

3.6 Front Panel

1. Alphanumeric Display
2. Exit function or silence acoustic signal
3. Scroll backwards or increase value
4. Scroll forwards or decrease value
5. Confirm function or access menu
6. ON/OFF switch
7. Multicolour operating status indicator (green/yellow/red)
1. Input/Output cables
2. Input/Output plug
3. Input fuse
4. RS232 serial interface (9-pin female)
5. Logic signals outlet (9-pin male)
6. Autonomy expansion connectors
Figure 3.2: Front Panel

3.7 Single Cabinet UPS Installation

Figure 3.3: Electrical Connections
3-4 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
1. Wire up the Input-Output connector using insulated cable (min. 2.5mm
2
).
2. Insert the connector into the
plastic housing and secure using the screws supplied. Secure the wires to the housing using the cable grip.
3. Remove plug cover by removing
its screws.
4. Put the Input-Output connector
into the plug [9] on the rear of the UPS, and secure to its case using the screws supplied (Figure 3.3).
5. Check all UPS loads are OFF and connect them to the output socket.
6. Insert the power supply plug into a power outlet adequate for the voltage and current required.
Figure 3.4: Cabling
The UPS is fitted with protection against incorrect connections. This is indicated by its red warning light, lit without flashing, and the continuous sounding of its internal buzzer. Should you note this signal immediately after switching the UPS on, switch it off and remove the power supply plug immediately.
For 1250/2500/3750/5000 Versions Since current dispersion towards earth of all t he loads merges in the UPS protection wire (earth wire), for safety reasons, it is essential to check that the sum of these currents does not exceed 2.7 mA, according to standard EN 50091-1-1.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 3-5

3.8 Expansion of Autonomy

The UPS is complete with connections for additional battery cabinets. One or more extra battery cabinets can be fitted to a single cabinet UPS as follows:
1. Loosen screws 1 and 2, but do not unscrew them completely.
2. Slide the protective casing so that the connectors
located inside the box are completely accessible.
3. Tighten the screws to secure the metal protection.
4. Connect the battery cabinet to the UPS using the
dedicated cables.
5. Use the plaited conductor supplied to safeguard
a good contact with earth.
Ensure the UPS has been switched off and disconnected from the mains supply before proceeding with connections
Figure 3.5: Terminals
Figure 3.6: External Battery Cabinet Connectors
3-6 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
4
~
=
~
=
=
=
OUTPUT
FILTER
OUTPUT
BYPASS
INVERTER
POWER FACTOR
CORRECTION
POWER
MODULE
BATTERY
CHARGER
VOLTAGE BOOSTER
INPUT
FILTER
BATTERIES
BATTERIES
INPUT
POWER
MODULE
RS232
INTERFACE
REMOTE
CONTROL
MICRO
PROCESSOR
LOGIC

4.1 Commissioning

Operation

The MINIpower PLUS UPS is a high quality electronic machine that must be commissioned by a fully trained and authorised Uninterruptible Power Supplies Ltd. field service engineer before being put into use.
The commissioning of the UPS involves the connection of the UPS and battery, the checking of the electrical installation and operating environment of the UPS, the controlled start-up and testing of the UPS and customer training.
ANY MINIpower PLUS SYSTEM NOT COMMISSIONED BY AN UNINTERRUPTIBLE POWER SUPPLIES LTD. FIELD SERVICE ENGINEER MUST BE CONSIDERED AN ELECTRICAL HAZARD AND UNINTERRUPTIBLE POWER SUPPLIES LTD. ACCEPTS NO RESPONSIBILITY FOR ITS SAFE OPERATION OR THE SAFETY OF ANY PERSONNEL. ADDITIONALLY, THE MANUFACTURER'S WARRANTY IS IMMEDIATELY INV ALIDA TED IF THE UPS IS PUT INT O USE BEFORE IT HAS BEEN CORRECTLY COMMISSIONED.

4.2 Operation

Figure 4.1: Block diagram
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-1

4.3 Operating Principles

When the mains supply is present, the input voltage is filtered and rectified by a special input stage (power factor corrector) which optimises the use of the mains supply , so that the power factor becomes practically unitary , and compensates for any voltage fluctuations. This stage supplies the inverter even in conditions of very low mains voltage.
This feature is particularly important with very low loads: with a load of around 50% nominal load, mains operation is possible as low as about 100V without reverting to battery power. This enables more “intelligent” management of the switchover to battery power, minimising use of the batteries.
The mains voltage is rectified and then supplied to a high frequency inverter to produce the ‘clean’ sinusoidal output voltage, with very low distortion. A rapid, synchronised by-pass circuit assists during overloads above the inverter’s capacity , for example when certain, high start current, peripherals are switched on.
Should the mains voltage fail or be subject to excessive sag, a booster stage is automatically activated.This employs the batteries and safeguards the supply of power to the output inverter, and thus to the load, without any break. The circuitry is a passing neutral type, i.e. the mains supply neutral is common through to the inverter output.
During normal operation, a sensor verifies the difference in potential between the neutral wire and the earth wire: should this be excessive, it will activate the input protection and switch the UPS to battery mode, signalling the anomaly. It is, however, possible to modify the parameters of the software so that only signalling is provided, if preferred.
All the UPS functions are supervised in “real time” by a microprocessor that also controls and memorises certain operating parameters, in addition to managing an RS232 UPS-computer interface.
The UPS keeps the operator informed regarding its operating status using:
An alphanumeric display
A status indicator
An acoustic alarm
The combination of these signals enables rapid and intuitive understanding of its operating status and recognition of any problems in the power supply .
4-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06

4.4 Operating Modes

There are three main operating modes
Mains operation
Battery operation
Bypass operation

4.4.1 Mains Operation

This is the normal operating condition:
The mains supply is converted to DC by the power factor corrector
The inverter reconstructs a sinusoidal voltage from the DC supply
The output filter provides smoothing of the output voltage
The batteries are continually charged

4.4.2 Battery Operation

When there is a mains power failure, the UPS automatically switches over to battery mode.
The voltage of the batteries is increased by the “booster” circuit
The inverter constructs an alternating voltage from the battery DC supply
The output filter provides smoothing of the output voltage

4.4.3 Bypass Operation

The bypass circuit excludes the UPS and connects the input directly to the output. The switchover takes place in a synchronised manner to ensure the correct output voltage is always supplied, preventing the risk of a break in power or excess voltage.
Operation of the by-pass circuit can be customised, to meet the specific demands of the application, by means of a dedicated menu (Config. UPS, By-pass) which provides many options (automatic, disabled, by-pass in load waiting mode, etc.) in order.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-3

4.5 Basic Operation

4.5.1 Switch On

Press button
Display shows
The status indicator shows starting (red, yellow, green)
The display shows the operating status

4.5.2 Switch Off

With the UPS operating normally (example)
Press button for a few seconds
The acoustic warning signal sounds repeatedly and the UPS switches off after 5 seconds.
4-4 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06

4.6 Displays and Alarms

The main messages provided by the alphanumeric display in the three different operating modes are shown below.
UPS On Mains Indicates normal operating status, when mains
IN xxxV Indicates the UPS input voltage and the RMS
voltage is present.
On Battery Indicates that there is no mains power and the
UPS is using its batteries to supply power.
On By-pass Indicates that by-pass operation has been
turned on: the output of the UPS is connected directly to the mains.
power absorbed by the mains. This message is not displayed during battery operation.
OUT xxxV/x,xKW (xx%) The current power is also given as the
percentage of the total power that the UPS is able to supply.
Batt. xx,x’ Indicates the state of charge of the batteries in
a chart format and the autonomy available in a numeric format
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-5

4.6.1 Warning Signals

Indication and Sound
Solid Green
No Sound
Fast flashing Green UPS on Mains
Solid Yellow
Short intermittent sound (every 20sec)
Fast flashing Yellow
No Sound
Fast flashing Red
Short, fast intermittent sound
Solid Red
Continuous sound
Message Description
UPS on Mains IN xxxV
No sync mains xx.xHz
UPS on Batteries MAINS ABSENT
UPS on Bypass Load is connected directly to the
Normal operation. Mains OK and load within limits.
Frequency of the output voltage not synchronised with the input voltage. Possible casues:
- PLL disabled
- Input frequency outside limits Battery operation
mains supply via the bypass.
Module failure
Switch off the UPS and contact your service centre Overload Reduce the connected load until it is within the UPS capactiy.
UPS error or failure
ATTENTION! We recommend you switch off the ups and contact your service centre
Flashing Red
(1 flash/10 s) Flashing Red
Alternating short long Alternating short, long intermittent sound
Flashing Red Short with pause
RESERVE AUTONOMY!
OUT OF REDUNDANCY!
Above 90% of MAX load
Autonomy reserve. During battery operation
- Incorrect battery connection
- Incorrect Neutral Consumption by the load is
above the redundancy that has been set. Power board redundancy is not guaranteed in case of failure
Press ESC to silence the acoustic signal. The signal will be silenced or enabled each time this button is pressed.
4-6 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06

4.7 Customising the Operating Mode

4.7.1 Button Functions

The buttons on the front panel of the UPS are used to access various menus
Button Function
Exit a function without modifying it
Go up a menu level
Exit the main menu and return to status display
Silence the buzzer
Select previous function
Increase a value
Select a new item within the function (e.g. go from
Select next function
Reduce a value
Select a new item within the function (e.g. go from
DISABLED to ENABLED)
ENABLED to DISABLED)
Confirm a value
Access an item in the menu
Go down a menu level
Some menus contain more than four lines: use the and buttons to scroll through items that are not displayed.

4.7.2 Service Mode

All the settings and programming described below can be done even when the UPS is switched off. Press the button to enter UPS “Service” mode in order to access the Display menu. Press the button to exit this mode.
Alternatively, the UPS will automatically exit the function and switch off if it does not receive manual or serial commands.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-7

4.8 Accessing the Menus

4.8.1 Main Menu

With UPS operating normally, (example)
Press . Display shows the Main Menu:
and to select the chosen section:

4.8.2 UPS Status

UPS Status UPS Setup Events Programming Tools
UPS Info Output Input Batteries History Data Misc
and to select the chosen section:
UPS Info.
Mod POut Max SWVer. S/N Installed Modules Faulty Modules
xxxx xxxx xxxx xxxxxxxxxx x x
Output
Power Appar .Pow. V RMS I RMS Peak Current Frequency I Crest factor Power fact.
xxxxx xxxx xxxx xxxx xx xx x x
Name of UPS Max. potential active power (W) Software Version Serial Number Number of Power Modules fitted Number of Faulty Power Modules
Active Power (W) Apparent Power (VA) Voltage (V rms) Current (A rms) Current (A) Frequency (Hz) Peak current/rms current Power Factor
4-8 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Input
Power Appar .Pow. V RMS I RMS Peak Current Frequency I Crest factor Power fact.
Batteries
Voltage Residual Cap. Discharge Count Usage Cal.
Ext. KB units Ext Chargers
History Data
UPS Ontime BoosterOnTime DrainedOut N. Booster Int. Bypass Interv. OverheatCount
xxxxx xxxx xxxx xxxx xx xx x x
xxxxx xxxx xxxx xxxx dd/mm/yyhh:mm
xx xx
xxxxx xxxx xxxx xxxx xxxx xxxx
Active Power (W) Apparent Power (VA) Voltage (V rms) Current (A rms) Current (A) Frequency (Hz) Peak current/rms current Power Factor
Battery terminal Voltage (V) Percentage battery charge Number of discharge cycles Hours on battery power Day/Month/Year/Time of battery calibration Number of external battery KBs Number of external battery chargers
Hours of UPS operation Hours in Booster mode Number of complete battery discharges Number of Booster mode operations Number of Bypass interventions Number of Thermal protection triggers
Misc.
Int. Temp. Ext Temp. Fan Speed.

4.8.3 UPS Setup

and to select the chosen section:
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-9
xx xx xx
Output Input Bypass Neutral Sensor Batteries Clock Setup Operator Panel
Internal temperature (C) External temperature (C) Percentage cooling fan speed
Output
Voltage Frequency
N+x Redundancy
Set UPS Output Voltage (V) Set UPS Output Frequency<Hz)
Nominal Value
Set to either 50 or 60 Hz
Auto Selection
UPS reads Input Frequency and synchronises Output to it. If disabled UPS uses Nominal Value Set number of redundant Power Modules
NOTE: Redundancy Settings
Function is used to manage the redundancy of power modules. For example: A load requires N power modules; X power modules must be added to achieve N+X redundancy. If the load then exceeds the power available from N module s, the UPS will signal a lack of redundancy alarm.
NOTE: Practical Examples
Load
(W)
3700 3 3750 0 no 3750 3700 4 5000 1 3750 5000 1500 4 5000 2 2500 5000
Power
Modules
Total
Power
(W)
Redundant
Modules
Alarm
Level
(W)
Overload
Level
(W)
1000 4 5000 3 1250 5000
Input
PLL Enable
Extended PLL Range
If the PLL function is disabled, the automatic bypass facility is NOT A VAILABLE. In the event of a UPS fault or overload condition, the load is NOT FULLY PROTECTED.
If enabled, UPS sychronises Output frequency with Input frequency. If disabled, the Output frequecy is not synchronised with the Input and the Status indictor flashes Green If enabled, the Output frequency is synchronised with the Input up to 50 or 60Hz ± 14%. If disabled, the Output frequency is synchronised with the Input up to 50 or 60Hz ± 2%.
4-10 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Bypass
Bypass Enable
Forced Mode
DIP Speed
Off-Line Mode
Load Wait Mode
If enabled, the UPS manages bypass operation automatically. If disabled, the UPS will never switch to bypass and will switch off in the event of sustained overload or fault. If enabled, the UPS is set to premanent bypass condition. When Forced Mode is disabled, this alters the speed of bypass intervention. SLOW: for loads which aremay cause high peak demands and are insensitive to input voltage disturbance.
STANDARD: normal condition. FAST: For loads which are extremely sensitive to
input voltage disturbance. If enabled:
UPS is in permanent bypass mode while mains supply is available
UPS reverts to battery power if the mains supply fails
If enabled, the bypass operates normally for loads below the “Minimum Load Threshold” but is not available for higher loads. During a mains failure the UPS switches OFF and is only restarted when mains is restored.
Programming Priority
Function
Forced Enabled Enabled X X Off-Line Enabled Disabled Enabled Enabled Off-Line Enabled Disabled Enabled Disabled
Load Waiting Enabled Disabled Disabled Enabled
Automatic Enabled Disabled Disabled Disabled
Bypass Disabled Disabled X X X
Enable
Bypass
Forced
Mode
Off-line
Mode
Neutral Sensor
Enable
Ignore While Run
If enabled, the UPS uses the neutral sensor to verify the voltage between neutral and earth is within safe limits. Otherwise the UPS will switch to battery mode. If disabled, the sensor is ignored If enabled, the UPS only checks the neutral sensor during startup.
Load
Waiting
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-11
Batteries
Capacity Manag. ADVANCED MODE: The end of autonomy warning
is based on the power being drawn by the load and is displayed as remaining autonomy time. SIMPLE MODE: The end of autonomy warning is calculated from the battery terminal voltage.
and to select the chosen section:
ADVANCED MODE
Set capacity Reserve Time
SIMPLE MODE
Set capacity Battery Thresholds
Max Time On Batt.
Max. time reserve
TurnOn Test Enable
Restart Enable
External Options
Advanced Mode
Sets the end of battery autonomy warning signal using the remaining run time (mins)
Simple Mode
Sets the end of battery autonomy warning signal using the battery voltage. There are two possible settings in the Mode menu:
Mode - Automatic Thresholds
UPS automatically calculates the voltage threshold based on the load. UPS will signal AUTONOMY RESERVE and END OF AUTONOMY
Mode - Fixed Thresholds
Reserve Thresholds: Sets the battery voltage threshold, UPS signals AUTONOMY RESRVE below this level. Exhaust Threshold: Sets the battery voltage threshold, UPS signals END OF AUTONOMY below this level.
Sets the max. time (in seconds) for continuous operation in battery mode. Set to “0” to disable. Sets max. time (in seconds) for operation in battery mode after the reserve limit is reached. Set to “0” to disable. If enabled, batteries are tested each time the UPS is started. If enabled, the UPS restarts automatically when mains supply is restored after the UPS has switched off due to the end of autonomy.
Battery Chargers No.
Sets the number of external battery chargers.
KB Kits
Sets the number of sets of three cells fitted internally.
4-12 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Clock Setup
26/07/06 - 10:01:05
Use , and to select and modify the chosen setting.
Operator Panel
Language Keyboard Beep Display Backlight
Display Contrast Password Change

4.8.4 Events

and to select the chosen section:
Log View
Log Reset
Sets the display language Enables/disables keyboard beep
Fixed: Always ON Timed: Switches OFF after period of inactivity Disabled: Always OFF
Sets display contrast Sets password to enable access to UPS settings
Log View Log Reset
Displays events stored in UPS memory, for example END OF AUTONOMY, OVERHEATING ALARMS etc with TIME and DATE Deletes events stored in UPS memory

4.8.5 Programming

Schedule Planning Restart Shutdown Planning
and to select the chosen section:
Schedule Planning
Enable View/Edit
Sched. sequence Reset
Enables/Disables set programmes View, Set or Modify programmes:
Batteries Test - Verifies battery status Batt. Calibration - Calibrate batteries Turn On - Switch on UPS Turn Off - Switch off UPS Absent - Disable programming
Each item can be set to operate:
Daily “hours-minutes” Single “day-month-hour-minutes Weekly “day name-hour-minutes”
Displays up to 16 programmes in date order Deletes all programmes
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 4-13
Restart
Delay
Min Autonomy
Shutdown
Delay Duration (seconds) of the signal warning that the
Duration (seconds) of the signal warning that the UPS is about to restart. Percentage of battery charge below which the UPS will NOT automatically restart.
UPS is about to shutdown.

4.8.6 Tools

Signalling Test LCD Display Test Battery Test Battery Calibration
and to select the chosen section:
Signalling Test
LCD Display Test
Battery Test
Battery Calibration
Tests the warning lights. Press the Enter button to execute the test of the Green, Yellow and Red warning lights and the Acoustic warning signal. Tests the alphanumeric display. Press the ENTER button and all the available digits are shown on the alphanumeric display. Tests the batteries. Contact your Service Centre in case of problems. Calibrates batteries by calculating the discharge curve. This should be carried out when the batteries have been changed so that the UPS is able to provide precise information on charge status.

4.9 Diagnostic Software

The UPS is fitted with a standard RS232 interface, which can be used, with a computer, to access data relating to the operation of the UPS and its log.
A suitable interface programme for Windows® computers is available, free of charge, from our website www.upspower .co.uk.
An RS232 cable is required to connect a serial port on your PC to the interface outlet on the rear of the UPS.
4-14 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
5

5.1 Introduction

5.2 User Responsibilities

Maintenance

ALL THE OPERA TIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.
TO ENSURE OPTIMUM OPERA TION OF THE MINIpower PLUS SERIES UPS AND CONTINUOUS AND EFFICIENT PROTECTION OF THE CONNECTED LOAD IT IS RECOMMENDED THAT THE OPERATIONAL PARAMETERS AND CALIBRATIONS OF THE UPS AND THE BATTERIES ARE CHECKED EVERY 6 MONTHS.
There are no user serviceable parts contained within the UPS so the maintenance responsibilities of the user are minimal. To maximise the useful working life and reliability of the UPS and its batteries, the environment in which the UPS operates should be kept cool, dry, dust and vibration free.

5.3 Routine Maintenance

The UPS is designed to receive regular preventative maintenance inspections. These preventative maintenance inspections are essential to ensure that both the useful working life and the reliability of the UPS are maximised. When the UPS is commissioned, the commissioning field service engineer will attach a service record book to the front of the UPS and this will be used to record the full service history of the UPS.
Preventative maintenance inspections involve working inside the UPS which contains hazardous AC and DC voltages. Only Uninterruptible Power Supplies Ltd. trained and authorised field service engineers are fully aware of all of the hazardous areas within the UPS.
During a preventative maintenance inspection the field service engineer will carry out the following checks:
Site/environment conditions.
Integrity of electrical installation.
Cooling airflow.
Rectifier operation and calibration.
Inverter operation and calibration.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 5-1
Static switch operation.
Battery status.
Load characteristics.
Integrity of alarm and monitoring systems.
Operation of all installed options.
Preventative maintenance inspections form an integral part of all Extended Warranty Agreements (maintenance contracts) offered by Uninterruptible Power Supplies Ltd.
For further details on Extended Warranty Agreements please refer to section 2.3.
5-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
6

Troubleshooting

6.1 Potential Problems and Solutions

Problem Possible Solution
When the UPS is switched on, the buzzer sounds and the red warning light makes alternating short-long flashes, then the UPS switches off after 15 seconds
The UPS works but a short beep is heard every 12 seconds and the yellow warning light is lit without flashing.
The UPS works but it beeps intermittently and the red warning light and the yellow warning light are flashing.
The UPS beeps continuously and the yellow warning light flashes for about 15 seconds, after which the UPS switches off
The UPS works but the green warning light is flashing quickly
The connection of the neutral conductor is incorrect: swap the connections of the neutral and phase input leads, or exclude the neutral sensor.
Check power is present at the mains outlet. Check that the UPS power supply cable is correctly inserted in both the mains outlet and in the connector on the UPS itself. Check the fuse located at the side of the input/output connector under the plastic housing (refer to fig.1 or 4)
There is an overload on the UPS output. Reduce the load so that it does not exceed the maximum power that the UPS can supply. Alternatively, if th e UPS is not in its maximum configuration, you can ask your Service Centre to increase the power of your UPS by fitting extra power boards and batteries inside the UPS cabinet.
The UPS has completely flattened its batteries; it can only start up again when the mains input line is present. Check the magneto-thermal or differential switches that precede the UPS and the input fuse
The mains supply is out of the limits permitted for the voltage and/or frequency, but it can still be used by the UPS. However, the by-pass function is not operational
The UPS beeps intermittently and the red warning light is flashing quickly.
The thermal protection has been tripped. Switch the UPS off and wait for a few minutes so that the internal temperature of the UPS can get back to normal. Check that the fans operate correctly and that the airflow is not obstructed (e.g. if the UPS is too close to a wall). There is a fault on one of the internal circuits. Contact your service centre.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 6-1

6.2 Contacting Service

Uninterruptible Power Supplies Limited has a service department dedicated to providing routine maintenance and emergency service cover for your UPS.
If you have any queries regarding your UPS please contact us .
Uninterruptible Power Supplies Ltd.. Bacchus House Calleva Park Aldermaston Berkshire RG7 8EN
Tel: 0118 981 5151
Fax: 0118 981 5152 Email: service@upspower.co.uk
0800 7313269
We recommend that your UPS is protected by an Extended Warranty Agreement (see section 2.3 for details). These agreements assist us in caring for your UPS correctly, ensuring that it is well maintained and attended to promptly should any problems occur.
6-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
7

Options

Non available.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 7-1
7-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
8
Construction
Model 1250 2500 3750 5000 Weight (Kg.) 23.5 34 43 53 Size (mm) (WxHxD) 19” Rack 6U 483.5 x 266 x 600 Technology PWM high frequency both for input stage and output stage. Microprocessor control logic

Specifications

Expandability Optional upgrading to configurations with higher power by fitting one or more extra power
Expandability For greater autonomies, optional battery cabinets can be connected, each with a capacity
Computer Interface With logic levels, to interface with optional kits. Output with 9-pin male, SELV insulated
Remote control Output with 9-pin male, SELV insulat ed connector for connection to optional remote control.
Protection Electronic protection against overloads, short circuits and excessive battery discharge.
Synchronised By-pass Automatic static and manual (optional). Intervenes in case of overload and operating
Environmental
Model 1250 2500 3750 5000 Storage Altitude 10.000 metres Storage Temperature -20° C to +50° C
modules inside the same cabinet, up to a maximum of 4. Optional upgrading of autonomy
by fitting extra batteries inside, up to a maximum of 4 sets of 3, 12V, 9Ah batteries.
of max 10 sets of 3, 12V, 9Ah batteries.
connector. S tandard serial RS232 for interfacing with personal computer using diagnostics
software. Output with 9pin, female, SELV insulated, connector.
Optional scheduling of UPS switch on/off and display of main UPS signals.
Operation blocked at end of autonomy. Inrush limitation when switching on. Sensor for
correct neutral connection. Back-feed protection (electrical insulation for the safety of the
input plug when running in battery mode). EPO contact (emergency power off)
anomaly.
Operating Temperature 0° C to +40° C Relative Humidity 20-80% non-condensing Protection IP 21 (IEC529) Audible Noise < 40dBA at 1 metre
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 8-1
Electrical Input
Model 1250 2500 3750 5000 Voltage 184V to 264V with nominal load
Frequency 50 or 60Hz ± 2% autosensing and/or selected by operator Current (Nom.) 4.6A
Current (Max.) 5.75A Current Distortion <3% THD
Power Factor > 0.99 at 20% nominal load Inrush Current 100% of nominal current Phases Single Line Fuse 25AF Battery Charger 0.8A rms (direct from mains)
100V to 264V with 50% nominal load
8.9A 13.2A 17.7A
11.2A 16.6A 22.2A
Output Waveform
Model 1250 2500 3750 5000 Mains Operation Sine wave Battery Operation Sine wave Topology No break, on line UPS with passing neutral and double conversion
Output When Running on Mains Power
Model 1250 2500 3750 5000 Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (autosensing and/or as selected by operator) Output Current with linear load
and 0.7 pf (A rms) Crest Factor 3.5 Output VA 1250 2500 3750 5000 Output W
with 0.7 pf linear/non-linear load THD < 0.5% with nominal load and < 1% with 0.7 pf nominal non-linear load Overload Capacity 300% for 1s, 200% for 5s and 150% for 30s without By-pass intervention Phases Single AC-AC conversion efficiency with
Linear load pf=1 and charged batteries
5.37 10.75 16.25 21.6
875 1750 2625 3500
80% with 50% load 85% with 75% load
92% with 100% load
8-2 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Output When Running on Battery Power
Model 1250 2500 3750 5000 Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (autosensing and/or as selected by operator) Output VA 1250 2500 3750 5000 Output W
with 0.7 pf linear/non-linear load THD < 1% Overload Capacity 160% for 15s Allowable load pf 0.7-1.0 DC-AC conversion efficiency 80% with 50% linear load pf = 1 and charged batteries:
875 1750 2625 3500
80% with 75% load
80% with 100% load
There is a danger of explosion should the batteries be replaced with the wrong type. Dispose of used batteries as per the instructio ns and precautions for their disposal on the battery label.
Battery Operation
Model 1250 2500 3750 5000 Approximate autonomy in minutes with charged batteries Percentage of applied load 50 80 100 50 80 100 50 80 100 50 80 100 Standard UPS 20 11 8 20 11 8 20 11 8 20 11 8 Recharge time to 90% charge 5 - 6 hours according to level of discharge Specifications and quantity of
batteries Reserve signals 32.2 V to 36V, programmable Minimum voltage for battery
operation during discharge Average battery life 3-6 years according to use and working temperature
3 pcs 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each
power module
27V to 31.5V with automatic selection depending on applied load, or as programmed by
operator.
The UPS batteries are subject to a reduction in capacity depending on their age (a
feature declared by their manufacturer in the technical manual). For example, the
reduction of capacity of a 4-year-old battery can be as much as 40%, resulting in a
proportional reduction of UPS autonomy time when running on battery power.
UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 8-3
Bypass
Model 1250 2500 3750 5000 Type Static and electromechanical Switchover time Zero
Reference Standards
Model 1250 2500 3750 5000 Safety Conforms to standard EN 62040-1-1 Electromagnetic
compatibility Typical Performance Conforms to standard EN 62040-3
Immunity: Conforms to standard EN 50091-2 (class A)
Emmisions: Conforms to standard EN 50091-2 (class B)
8-4 UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06
Loading...