Uninterruptible Power Supplies MINIpower PLUS User Manual

Pioneering solutions for total power protection
MINIpower PLUS
User Manual
Document Control
ISSUE DATE REVISION SUMMARY
Draft A 7-11-11 First draft issued for comments
Draft A1 9-2-12 Second draft incorporating rack-mounted model
Issue 1.0 08-03-12 Initial release
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Uninterruptible Power Supplies Ltd has taken every precaution to produce an accurate, complete and easy to understand manual and
will therefore assume no responsibility nor liability for direct,
indirect or accidental personal or material damage due to any
misinterpretation of or accidental mistakes in this manual.
© 2005 Uninterruptible Power Supplies Ltd
This manual may not be copied nor reproduced without written
permission of Uninterruptible Power Supplies Ltd.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 -I
:
1 Safety
1.1 Description of symbols used in this manual 3-1
1.2 User precautions 3-1
2 General Description
2.1 Reliability and Quality Standards 4-1
2.2 MINIpowerPLUS Model Range 4-1
2.3 Operating Principles 4-2
2.4 Warranty 4-4
2.5 Extended Warranty 4-5
2.6 Additional Service/Maintenance Support 4-5
3 Installation
3.1 Introduction 5-1
3.1.1 Receipt of the UPS 5-1
3.1.2 Site transportation 5-2
3.1.3 Unpacking the UPS 5-2
3.1.4 Batteries 5-2
3.1.5 Storage 5-2
3.2 Planning the Installation 5-3
3.2.1 MINIpowerPLUS Tower versions 5-3
3.2.2 MINIpowerPLUS Rack-mounted versions 5-4
3.2.3 Environmental considerations 5-4
3.3 UPS Installation Procedure 5-5
3.3.1 Connect the UPS cabinet to the battery cabinet 5-5
3.3.2 Connecting the UPS communication options 5-7
3.3.3 Connect the UPS input/output power cables 5-8
3.3.4 Powering ON the UPS 5-11
4 Operation
4.1 Operating Instructions 6-1
4.1.1 Standard installation without the maintenance bypass option fitted 6-1
4.1.2 Installation with Maintenance Bypass option fitted 6-2
4.2 Control Panel 6-3
4.2.1 Alpha-numeric LCD Display 6-3
4.2.2 Operator Keypad 6-4
4.3 Alarms and Indications 6-4
4.4 UPS Customisation and Event Monitoring Menus 6-5
4.4.1 Main Menu 6-5
4.4.2 UPS Status Menu 6-6
4.4.3 UPS Setup Menu 6-7
4.4.4 Events Menu 6-10
4.4.5 Scheduling Menu 6-11
4.4.6 Tools Menu 6-12
4.5 Diagnostic Software 6-12
5 Maintenance
5.1 Introduction 7-1
5.2 Routine maintenance 7-1
5.3 Battery Testing 7-1
6 Troubleshooting
6.1 Potential Problems and Solutions 8-1
:
-II UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
7 Options
7.1 Maintenance Bypass 9-1
7.1.1 Introduction 9-1
7.1.2 Installation 9-2
7.1.3 Functional testing 9-3
7.1.4 Maintenance bypass specification 9-4
7.2 Shutdown and Monitoring Software 9-4
7.2.1 Introduction 9-4
7.2.2 WAVEMON UPS monitoring software 9-4
7.2.3 SNMP ADAPTER for network management/remote monitoring 9-6
7.3 PowerREPORTER™ management software 9-7
7.3.1 Relay Interface Board 9-8
8 Specifications
8.1 Construction Features 10-1
8.2 Environmental 10-1
8.3 Electrical Input 10-2
8.4 Output Waveform 10-2
8.5 Output When Running on Mains Power 10-2
8.6 Output When Running on Battery Power 10-3
8.7 Battery Operation (MINIpowerPLUS 5000) 10-3
8.8 Battery Operation (MINIpowerPLUS 10000) 10-4
8.9 Bypass 10-4
8.10 Reference Standards 10-4
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 1-1
1
Safety
1.1 Description of symbols used in this manual
1.2 User precautions
WARNING: The warning symbol is used where there is danger of an electrical shock,
equipment damage or personal-injury.
CAUTION: The caution symbol is used to highlight important information to avoid possible equipment malfunction or damage.
WARNING: Keep this manual with the UPS for future reference.
WARNING: The UPS and peripheral equipment must be installed and commissioned by
suitably qualified and trained personnel who are aware of the potential shock hazards.
WARNING: Do not attempt to install this UPS system until you are satisfied that ALL the safety instructions and hazard warnings contained in this manual are read and fully understood.
WARNING: High leakage current! Ensure that the UPS has been correctly earthed before you connect the mains power supply!
WARNING: If the UPS is delivered wi th out the b atte rie s already fitted, i t must n ot be powere d up without having first been commissioned by an engineer authorised by the manufacturer.
WARNING: All servicing must be performed by an authorised engineer or other suitably qualified personnel. Do not attempt to service the UPS yourself. You run risk of exposure to dangerous voltages by opening or removing the UPS covers! Uninterruptible Power Supplies Ltd will assume no responsibility or liability due to incorrect operation or manipulation of the UPS.
WARNING: The MINIpowerPLUS is a Class A UPS product (according to BS EN 62040­2:2006). In a domestic environment the UPS may cause radio interference. In such an environment the user may be required to undertake additional measures.
WARNING: The information conta ined in this manua l is provided as a guide and is subj ect to change without notice for product upgrading.
1: Safety
1-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 2-1
2
General Description
2.1 Reliability and Quality Standards
Congratulations on your purchase of the MINIpowerPLUS UPS. The MINIpowerPLUS UPS incorporates the latest technological advances in power engineering to offer a
highly reliable, upgradeable UPS system with excellent electrical performance and low running costs. Uninterruptible Power Supplies Ltd. are leading specialists in the provision, installation and maintenance of
UPS systems; and this compact and powerful UPS is just one example of our wide range of state-of-the-art power protection devices able to provide your critical equipment with a reliable power supply for many years.
The criteria and methods used in the design, manufacture and maintenance of this UPS system are certified to International Standard ISO 9001/EN 29001 and ISO 14001.
A full equipment specification is provided in Chapter 8 of this manual.
2.2 MINIpowerPLUS Model Range
The MINIpowerPLUS system is available in two model ranges.
MINIpowerPLUS 5000
The MINIpowerPLUS 5000 is available in both Rack­mounted and Tower versions and uses up to four 1250VA power modules to offer a system output rating of 1250VA, 2500VA, 3750VA or 5000VA.
Each power module requires three batteries which are housed within the UPS cabinet to provide a completely self-contained UPS system.
An optional external battery cabinet can be connected to the UPS to extend the system’s autonomy time if required.
MINIpowerPLUS 10000
MINIpowerPLUS 10000 uses between four and eight 1250VA power modules to offer a system output of 5000VA, 6250VA, 7500VA, 8750VA or 10000VA.
In this model range the batteries are contained in a separate battery cabinet which is similar in design and appearance to the UPS cabinet and is usually positioned adjacent to the UPS cabinet to form a matching suite.
If required, additional battery cabinets can be connected to the existing battery cabinet to extend the system’s autonomy time.
Figure 2.1 MINIpowerPLUS 5000
Figure 2.2 MINIpowerPLUS 10000
2: General Description
2-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Figure 2.3 MINIpowerPLUS Power module usage
If a system is purchased without the maximum number of power modules fitted, additional modules may be fitted in the field (up to the limit of 4/8 modules) to expand the system up to full capacity; however this requires the UPS to be shut down while the additional module(s) and batteries are fitted.
2.3 Operating Principles
The UPS has three main operating modes:
• Mains operation
• Battery operation
• Bypass operation
Mains operation
When the mains supply is present, the input voltage is filtered then rectified by the power factor correction stage. This optimises the use of the mains supply by making the power factor practically unity, and compensates for any input voltage fluctuations. The rectified output from the power factor correction stage i s connected to the inverter where it is converted to a clean, sinusoidal output voltage with very low distortion.
The operation of the power factor correction stage is particularly important when operating with very low loads. For example, with a nominal load of around 50% it is possible to sustain the inverter operation with the input mains voltage as low as about 100V without reverting to battery power. This feature enables a more intelligent management of the switchover to battery power and minimises battery use. During mains operation the battery is continuously charged by a dedicated battery charger circuit.
MINIpowerPLUS 10000 Fully populated with 8 Power Modules to offer a 10kVA system.
MINIpowerPLUS 5000 (Rack and Tower) cabinets
Fully populated with 4 Power Modules to offer a
Batteries are housed
Batteries are housed in a matching battery cabinet.
5.0kVA system.
within the UPS
cabinets.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 2-3
2: General Description
Figure 2.4 MINIpowerPLUS block diagram
A rapid, synchronised by-pass circuit is used to assist during overloads that exceed the inverter’ s capacity – for example when certain peripherals that require a high start current are initially switched on.
The UPS power circuitry is a ‘passing neutral’ type: i.e. the mains supply neutral is common through to the inverter output. During normal operation, a sensor monitors the potential between the neutral wire and the earth wire and if it becomes excessive it:
• activates the input protection circuitry, which turns off the power factor correction stage
• switches the UPS to battery operation
• signals an error on the UPS control panel
Note: If preferred, the control software can be configured so that only an error signal is produced, without a
switchover to battery operation.
All the UPS operating functions are supervised in real-time by a microprocessor which co ntrols and stores certain operating parameters in addition to managing an RS232 computer interface.
Battery operation
If the mains voltage fails, or is subject to excessive sag, the voltage booste r stage activates automati cally to provide an additional (or alternative) d.c. supply to the inverter. When this occurs the inverter input power source transfers seamlessly between the power factor correction stage and the voltage booster, and the inverter maintains the load supply without any power interruption.
~
=
~
=
=
=
OUTPUT
FILTER
OUTPUT
STATIC
SWITCH
INVERTER
POWER FACTOR
CORRECTION
POWER
MODULE
BATTERY
CHARGER
VOLTAGE BOOSTER
INPUT
FILTER
BATTERIES
Bypass Line
BATTERIES
INPUT
POWER MODULE
POWER MODULE
BATTERIES
MICROPROCESSOR LOGIC
REMOTE
CONTROL
RS232
INTERFACE
2: General Description
2-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
The voltage booster stage obtains its power from the batteries, and when the UPS operates in this mode the operator is informed that the battery is ‘on load’ and th erefor e discha rging, and a number of alarms activate at preset voltage levels as the battery discharges. The operating threshold and function of these battery alarms can be set by the operator through the UPS Setup menu to suit local application requirements.
Bypass operation
When operating in the bypass mode the bypass circuit totally excludes the UPS and connects the UPS input supply directly to the UPS output.
The UPS automatically switches to bypass operation if:
• the UPS develops a fault which renders it unable to sustain the UPS output supply
• the UPS is shutdown for maintenance or repair purposes
• (momentarily) to assist the UPS handle an overload condition that exceeds the inverter rating
During normal operation the inverter is synchronised to the incoming mains supply so that when a transfer to the bypass mode is required it takes place in a synchronised manner to prevent the risk of a power break or excessive voltage.
A dedicated bypass configuration menu provides a mean s of customising the by-pass circuit operatio n to meet specific application demands. T his feature pr ovides many opti ons such as: ‘aut omatic’, ‘dis abled’, ‘by ­pass in load waiting’ mode, etc.
2.4 Warranty
The MINIpowerPLUS is supplied with a limited warranty that the UPS and its component parts are free from material and manufacturing defects for a period of one year from the date of original commissioning or fifteen months from the date of original delivery, whichever is the sooner. This warranty is the only warranty given and no other warranty, express or implied, is provided.
This warranty will be invalidated if the UPS is p ut into use with out having fi rst been commissioned by a fully trained and authorised engineer, unless the UPS is supplied with the batteries already fitted and connected. This warranty does not apply to any losses or damages caused by misu se, abuse, negligence, neglect, unauthorised repair or modification, incorrect installati on, inappropriate enviro nment, accident, act of God or inappropriate application.
If the UPS fails to conform to the above within the warranty perio d then Uninterruptible Power Sup plies Ltd.. will, at its sole option, repair or replace the UPS. All repaired or replaced parts will remain the property of Uninterruptible Power Supplies Ltd..
As a general policy, Uninterruptible Power Supplies Ltd. d oes not recommend the use of any of its produ cts in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect it’s safety or effectiveness. Uninterruptible Power Supplies Ltd. does not recommend the use of any of its products in direct patient care. Uninterruptible Power Supplies Ltd. will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Uninterruptible Power Supplies Ltd. that the risks of injury or damage have been minimized, the customer assumes all such risks and the liability of Uninterruptible Power Supplies Ltd. is adequately protected under the circumstances.
Key Point: When the UPS is operating on battery, if the UPS mains supply cannot be restored the operator should arrange an orderly shutdown of the load before the UPS batteries reach a fully discharged state, whereupon the UPS is forced to shut down.
CAUTION: The UPS contains batteries which must be re-cha rged for a minimum of 24 hours every six months to prevent deep-discharging. Batteries that have been , for whatever reason, deep-discharged are not covered by the warranty.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 2-5
2: General Description
2.5 Extended Warranty
The Standard Warranty may be enhanced by protecting the UPS with an Extended Warranty Agreement (maintenance contract).
An Extended Warranty Agreement enhances the standard warranty by providing the following:
• Regular preventative maintenance inspections
• Guaranteed speed of response to operational problems
• 24 hour telephone support
• Fully comprehensive (excluding batteries) cover
Contact the Service Support Hotline on 0800 731 3269 for further details.
2.6 Additional Service/Maintenance Support
In addition to providing support for the MINIpowerPLUS, Uninterruptible Power Supplies Ltd. are able to provide maintenance and support on a wide range of different UPS products.
If you are interested in an extended warranty for your MINIpowerPLUS UPS, or any other UPS you may have, please complete the enquiry form shown below and return or FAX to:
Uninterruptible Power Supplies Ltd.. Bacchus House Calleva Park Aldermaston Berkshire RG7 8EN
Tel: 0118 981 5151
0800 731 3269 Fax: 0118 981 5152 Email: service@upspower.co.uk
2: General Description
2-6 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Thank you for your enquiry, which will receive our prompt attention.
If you need to contact us immediately call free on,
Freefone 0800 731 3269
or E-mail us on service@upspower.co.uk
www.upspower.co.uk
Uninterruptible Power Supplies Ltd. Bacchus House Calleva Park Aldermaston Berkshire RG7 8EN
Tel: 0118 981 5151
Name: ............................................................................................
Job Title: ................................. ... .................................... ....................
Company: ............................................................................................
Address: ............................................................................................
............................................................................................
............................................................................................
............................................................................................
Post Code ............................................................................................
Tel. ............................................................................................
Fax. ............................................................................................
E-mail ............................................................................................
Please contact me to discuss:
Extended Warranty options for my MINIpowerPLUS UPS
Extended warranty options for my UPS System as below:
Manufacturer:...................................................................
Model Nº:..........................................................................
Rating kVA:.......................................................................
Replacement Batteries......................................................................
Other .................................... ..............................(please specify)
Fax to: 0118 981 5152
www.upspower.co.uk
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-1
3
Installation
3.1 Introduction
This chapter contains all the information necessary to enable you to correctly install the MINIpowerPLUS UPS, including unpacking, storage, positioning and cabling instructions.
Commissioning options
If the UPS is delivered with the batteries already fitted and connected, the system can be considered as being ‘plug and play’ and can be installed and powered ON by the user. However, if it is delivered without the batteries fitted, the cabinet(s) can be installed by the user but the batteries must be fitted and commissioned by an Uninterruptible Power Supplies Ltd. approved engineer.
Note: The MINIpowerPLUS 5000 rack-mounted UPS is always shipped with the batteries fitted and
connected.
3.1.1 Receipt of the UPS
The UPS equipment, which includes the UPS Cabinet, batteries and accessories, are delivered on pallets that can be moved easily with the aid of a pallet jack. Before you accept receipt of the equipment ensure that the shipment is complete and the package(s) match the description shown on the delivery note.
The UPS Cabinet is packed in a container designed to protect it from mechanical and environmental damage during transit. This protection is enhanced by wrapping and sealing the container in a polythene sheet.
Upon delivery you should carefully examine the packing containers for signs of physical damage. If there are signs of transportation damage you must inform both the carrier and Uninterruptible Power Supplies Ltd. immediately.
WARNING: The electrical installation of this UPS system and its peripheral equipment must be carried out by an authorised electrician or other suitably qualified personnel. Uninterruptible Power Supplies Ltd. will take no responsibility for any personal injury or material damage caused by incorrect handling, cabling, operation, or other activities that are not carried out fully in accordance with the instructions contained in this manual.
WARNING: If the UPS is purchased and supplied without batteries, Uninterruptible Power Supplies Ltd. will not accept responsibility for any UPS damage or malfunction caused by the incorrect supply, storage, installation or connection of batteries by third parties.
CAUTION: When off loading the UPS equipment always keep it in an upright position. Do not drop the equipment or stack the pallets.
Key Point: Claims for shipping damage that is discovered later when unpacking the equipment must be filed immediately when found. All damage claims must be reported to the carrier within seven days of receipt of the equipment. If any shipping damage is discovered you should store all affected packaging materials for further investigation.
WARNING: Do not attempt to install or power-up damaged equipment.
3: Installation
3-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
3.1.2 Site transportation
When locally transporting the UPS equipment after it has been off loaded please observe the following cautions:
3.1.3 Unpacking the UPS
Note: Do not unpack the equipment if you intend to put it into storage prior to use (See paragraph 3.1.5).
Castors are fitted to the UPS Tower cabinet to enable it to be wheeled into position once it is unpacked. Before you remove a UPS Tower cabinet from its shipping pallet you should ensure that the floor surface is level and suitable for wheeling the cabinet into its final position. You should also ensure that the floor material can safely support the weight of the UPS equipment and batteries.
1. Remove any external polythene sheeting.
2. Remove the cardboard packing container: Carefully cut through the securing bands then pull the container upwards.
3. Remove the protective polythene covering and any other packing from around the UPS cabinet.
4. Remove the fixings screws that secure the UPS feet to the pallet base, then carefully remove the UPS from the pallet.
5. Retain the packaging materials for future shipment of the UPS.
6. Examine the UPS for signs of damage and notify your carrier or supplier immediately if any damage is apparent.
3.1.4 Batteries
The UPS uses sealed, maintenance-free batteries mounted on shelves within the UPS cabinet or housed in an external battery cabinet. Normally, the system is shipped with the batteries already installed and connected. If the batteries are ordered and sh ipped separately they must b e fitted by a manufacturer­approved engineer as part of the system commissioning procedure.
3.1.5 Storage
UPS Cabinet storage
If you plan to store the UPS cabinet prior to installation it should be kept in a clean, dry environment with an ambient temperature between +5°C to +40°C and relative humidity of less than 90%.
Ideally the UPS cabinet should be stored in its original shipping packaging, but if it is removed from its packing container you must take measures to ensure it is protected from dust and humidity.
Battery storage
If shipped separately, the batteries should be stored in a dry, clean, cool environment and preferably in thei r original packaging. If the packaging is removed, the batteries must be protected from dust and humidity.
When stored, all batteries will self-discharge at a rate that is greatly affected by the ambient temperature. Batteries should therefore be fully charged before being put into storage and if they are to be stored for a long
CAUTION: If dropped, the weight of the UPS cabinet could cause serious injury to personnel or damage equipment in the surrounding area. Always handle with care. If the equipment is accidentally dropped do not connect it to the mains electricity suppl y.
Key Point: Before proceeding further with the installation process, check that the technical specifications on the nameplate located on the UPS back panel matches the purchased material detailed in the goods delivery note.
Key Point: If the batteries are shipped separately, where possible it is preferable to leave them in their packaging until they are required for commissioning (see below for storage information).
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-3
3: Installation
period they should be recharged periodically to prevent them from losing their original capacity. As a guide, the batteries should not be stored for longer than the periods shown below without being recharged:
• 6 months at 20°C
• 3 months at 30°C
• 2 months at 35°C
3.2 Planning the Installation
A certain amount of pre-planning will help ensure smooth, trouble-free installation. The following guidelines should be considered when planning a suitable UPS location and environment.
3.2.1 MINIpowerPLUS Tower versions
Cabinet positioning and accessibility
The MINIpowerPLUS 5000/10000 UPS Tower cabinet is compact and mounted on wheeled castors so that it can be easily moved to its intended operating location.
As shown in Figure 3.1 the UPS and battery cabinets require a minimum of 200 mm clearance at the rear and either side to permit adequate cooling airflow. However, in each case full rear access is required for cabling, and side access is necessary for maintenance and repair. For this reason it is recommended that the cabinets are located so that they can be wheeled forward to provide the necessary side and rear access when required.
This recommendation must be taken into consideration when cabling the equipment so that a sufficient cable length is provided to allow for the prescribed cabinet movement.
Figure 3.1 shows a space of 900 mm provided at the front of the cabinets. This allows adequate room for the safe passage of personnel during normal operation and also sufficient space for the cabinets to be pulled forward for access, as described above.
Note: Ensure that the cabinet is located in an
area where the ventilation grills are unlikely to be accidentally covered.
Moving the UPS to is final location
• The flooring material where the UPS is to be located should be non-flammable and capable of safely
supporting the weight of the UPS cabinet and battery cabinet (where used).
• The transit route must allow the equipment to be transported in an upright position.
CAUTION: Sealed batteries must never be stored in a discharged or partially discharged state. The batteries can be destroyed by extreme temperature, under-charge, overcharge or over-discharge!
UPS
Z
Front
VX200 mm
200 mm
Access Space
BATT.
CAB.
Front
Y*
VX
Y*Z200 mm
900 mm
Y*
X
Figure 3.1 UPS Tower clearances
3: Installation
3-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
3.2.2 MINIpowerPLUS Rack-mounted versions
Rack positioning and accessibility
The MINIpowerPLUS Rack-mounted UPS cabinet is designed to fit into a standard 19 inch rack and is 6U high. The cabinet is fitted through the front of the rack, supported on suitable rails and secured in position by means of two screws on each side of the front of the assembly.
All MINIpowerPLUS 5000 Rack-mounted UPS cabinets also contain the UPS batteries; however a matching rack-mounted battery cabinet is available if an extended battery facility is required. Where used, the separate battery cabinet (also 6U) and UPS cabinet should preferably be fitted in the same rack and positioned immediately adjacent to each other.
Due to the weight of the assembly it is usual to mount the UPS cabinet and optional battery cabinet (where used) near the bottom of the rack.
There is no minimum space requirement above or below the UPS cabinet when it is in-situ, but a minimum of 200mm should be provided at the rear of the unit to allow for adequate cooling air flow and facilitate cabling. As the UPS cabinet is 600mm deep this implies a minimum rack depth of 800mm.
As mentioned above, rear access is required for cabling therefore sufficient room should be provided behind the rack to permit easy passage – recommended 900mm. A similar space is required at the front of the rack to enable the UPS cabinet to be handled while it is being installed.
3.2.3 Environmental considerations
The following conditions apply to both Tower and Rack-mounted installations.
• The UPS location should be subject to a humidity of less than 90% (non-condensing) and temperature
between +15°C to +25°C. An ambient temperature of 20°C is recommended for optimum battery life.
• The location should be free from dust or corrosive/explosive gases.
• The location should not be subject to vibration.
• The air conditioning system must be able to provide a sufficient amount of cooling air to keep the room
at, or below, the maximum permissible operating temperature.
CAUTION: The UPS cabinet is heavy. Ensure that sufficient personnel and appropriate handling equipment are available to install the unit safely.
UPS
Z
Front
X
Y
19" Rack
XY900 mm
200 mm
Access Space
Z 900 mm
Figure 3.2 Rack-mounted clearances
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-5
3: Installation
3.3 UPS Installation Procedure
Figure 3.3 MINIpowerPLUS 5000 Electrical connections
The UPS is installed in three stages:
1. Connect the UPS cabinet to the battery cabinet – not appli cable in a standard MINIpowerPLUS 5000 installation unless an external battery option is used.(See paragraph 3.3.1).
2. Connect the UPS communication options. (See paragraph 3.3.2).
3. Connect the UPS input/output power cables. (See paragraph 3.3.3).
4. Power ON the UPS if commissioning is not required. (See paragraph 3.3.4)
3.3.1 Connect the UPS cabinet to the battery cabinet
In a MINIpowerPLUS 10000 system the UPS batteries are housed in a separate battery cabinet that is connected to the UPS cabinet by three cables. In a MINIpowerPLUS 5000 system a separate battery cabinet is an optional facility that is sometimes added to provide an extended autonomy time over and above that available from the standard internal batteries.
All interconnecting cables are provided in the accessories pack that is shipped with the battery cabinet.
WARNING: Ensure the UPS is isolated from the mains supply while making electrical connections.
1
2
3
123
Note that the Rack-mounted rear panel is identical to the Tower version but turned on its side.
1. External battery connections
2. Communications interface connections
3. UPS Input/Output power receptacle
3: Installation
3-6 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
MINIpowerPLUS 10000 installation
Note: Applies to models 5000/2, 6250/2, 7500/2, 8750/2 & 10000/2.
Figure 3.4 MINIpowerPLUS 10000 battery connections
1. Connect the flexible braided earth strap (provided) between the chassis earth studs of both cabinets – the studs are located adjacent to the battery connectors.
2. Connect all three battery cables between the battery connectors on both cabinets. The cable plugs are keyed to prevent incorrect polarity when making these connections.
Note: It does not matter which sockets are connected to which cable, provided all three cables are
connected.
MINIpowerPLUS 5000 installation (Tower and Rack-mounted)
Note: Applies to models 1250, 2500, 3750 & 5000.
Figure 3.5 MINIpowerPLUS 5000 battery connections
1. On the back of the UPS cabinet, loosen the two screws securing the battery connector cover plate. Slide the cover plate open to expose the battery connectors then retighten the securing screws to ho ld the cover plate open.
2. Connect the flexible braided earth strap (provided) between the chassis earth studs on both cabin ets – the studs are located adjacent to the battery connectors.
3. Connect two of the three provided battery cables between the battery connectors on both cabinets. The cable plugs are keyed to prevent incorrect polarity when making these connections.
Note: On the battery cabinet the top connector will be covered by a blanking plate. It does not matter
which of the remaining two sockets are connected to which cable, provided both are connected.
Braided Earth Strap
Chassis
Earth Stud
Battery Connectors
UPS Cabinet
Battery Cabinet
Braided Earth Strap
Chassis
Earth Stud
Battery Connectors
UPS Cabinet
Battery Cabinet
Cover plate
Blanking plate
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-7
3: Installation
Extended battery cabinet connections
Additional battery cabinets can be connected to either of the above systems to further extend the available autonomy time.
Where an extended cabinet is used, the standard cabinet inter-connect cables are replaced by ‘splitter’ cables that can be effectively daisy chained to connect any number of cabinets together – as illustrated in Figure 3.6.
When several cabinets are connected as shown, the battery charger within the UPS cabinet may not be able to adequately charge all the additional batteries. In this case an independent battery charger is fitted to each extended battery cabinet which must be connected to a mains supply using a standard IEC power cord.
3.3.2 Connecting the UPS communication options
On the UPS cabinet back panel there are three D-type connectors that provide various optional communication facilities.
The 9-pin female connector provides an RS232 communications port that can interface with a range of monitoring and control software – such as the CS121L Adapter Box for WaveMon, or other monitoring software using SNMP and MODBUS.
The remaining connectors (9-pin male) provide logic output signals that can be used to drive remote alarms and indication facilities – this is normally carried out via a relay interface board (See paragraph 7.3.1).
The following output signals are provided:
These outputs can be used individually or connected to an optional Remote Signalling Panel (RSP).
9-pin 15-pin
1 5 Input ON/OFF (Max. voltage +15V, equivalent to the ON/OFF button on the front control panel) 2 4 +15V (max 30mA) 3 3 AUTONOMY RESERVE (active high 15V, max 5mA) 4 2 UPS RUN ON BATTERY (active high 15V, max 5mA) 5 1 GND (common) 6 15 GENERAL ALARM (Open collector active low, max 50mA) 7 14 AUTONOMY RESERVE (Open collector active-low, max 50mA) 8 GND (common) 9 12 UPS RUN ON BATTERY (Open collector active-low, max 50mA)
7 OVERLOAD (Open collector active-low, max 50mA)
UPS Cabinet Batt. Cab. 1 Batt. Cab. 2 Batt. Cab. 3
Standard cable
BA
Splitter cable
B
CA
Figure 3.6 Extended battery cabinet connections
UPS Cabinet
RS232
2x Logic signal (9-pin male &
(9-pin female)
outputs
Figure 3.7 Communication connections
15-pin male)
3: Installation
3-8 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
3.3.3 Connect the UPS input/output power cables
The UPS input and output cables are fitted to a single power connector that plugs into a receptacle located on the rear UPS cabinet wall. A ready-made connector complete with cable is provided with the equipment. The supplied cable is approximately 600mm in length and terminated with an input plug and outlet socket suitable for the UPS capacity rating. Where the supplied cable length is inadequate for a particular installation it can be replaced by a longer cable following the instructions contained at the end of this section.
Note: If the UPS connector is fitted with a maintenance bypass switch refer to the Options chapter in this
manual for details (See paragraph 7.1).
MINIpowerPLUS 5000 power cables
A cable with a maximum capacity of 16A is supplied with the MINIpowerPLUS 5 000. For ap plications where the anticipated UPS input current exceeds 13A (e.g. 5000 VA with Vin=184V) we recommend that the UPS input power cable is connected directly to the electrical distribution control panel . If this requires a longer power cable the connector can be rewired as shown below in Figure 3.9.
MINIpowerPLUS 10000 power cables
A ready-made cable of approximately 600mm in length, fitted with stan dard IEC connecto rs, is supplied with the UPS. If it is necessary to rewire the connector the cable must be a minimum of 4mm² and have insulated wires – see Figure 3.10.
Figure 3.8 UPS input/output power receptacles
Connecting the UPS power connector
1. Connect the UPS input/output power connector assembly to the power receptacle on the rear of the UPS and secure in place using two screws, as shown in Figure 3.8.
2. Check that all the UPS loads are turned OFF then connect the UPS output cable to the load d istribution point.
3. Connect the UPS input mains supply cable to a power outlet adequate for the voltage and current required.
Key Point: A link is fitted in the power connector which ensures that the UPS cannot be started unless the connector is plugged-in to the UPS power receptacle.
CAUTION: Before proceeding, either ensure tha t the UPS input power cable is disconnected from the mains supply or, if the cable is connected directly to the main s, ensure that the mai ns supply is isolated at the distribution point.
Power Receptacle
& Input Fuse
Power Receptacle
& Input Fuse
MINIpowerPLUS 10000
5000/2, 6250/2, 7500/2, 8750/2 & 10000/2
MINIpowerPLUS 5000
1250, 2500, 3750 & 5000
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-9
3: Installation
MINIpowerPLUS 5000 power connector wiring
Figure 3.9 Input/Output power connector wiring
CAUTION: Ensure the UPS input mains supply is isolated before proceeding. Never remove the 230 V power plug whilst the UPS is in operation as this would disconnect the
earth protection of both the UPS and of the connected loads.
3: Installation
3-10 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
MINIpowerPLUS 10000 power connector wiring
Figure 3.10 Input/Output power connector wiring
CAUTION: Ensure the UPS input mains supply is isolated before proceeding. Never remove the 230 V power plug whilst the UPS is in operation as this would disconnect the
earth protection of both the UPS and of the connected loads.
Input Cable (from mains)
Output Cable (to load)
Yellow/Green (Earth)
(1) Blue (N)
(2) Brown (L)
(3) Brown (L)
(4) Blue (N)
Earth Connection
Yellow/Green (Earth)
(I1-I2) Link
Input/Output Power Connector
Cable Glands
Plastic Housing
4x Securing Screws
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 3-11
3: Installation
3.3.4 Powering ON the UPS
If the UPS batteries are already fitted and connected you can apply power to the UPS at this stage and, provided the power-on indications described below are satisfactory, you can put the UPS into operation.
1. Ensure the load equipment is turned OFF or otherwise isolated from the UPS output supply.
2. Turn ON the UPS input mains supply.
3. The UPS is fitted with protection against incorrect power connections. If the red warning light on the UPS control panel is permanently illuminated (not flas hing) and the internal warning buzzer is continuously sounding you should immediately turn off the input mains power supply, disconnect the UPS power connector and seek the manufacturer’s advice.
4. If the initial power-on indications (above) do not indicate a fa ult, you can connect the load equ ipment to the UPS output and switch ON the UPS following the Operating Instructions contained in Chapter 4 of this manual.
Important final checks
As current dispersion towards earth of all the loads merges in the UPS protection wire (earth wire), for safety reasons, it is essential to check that the sum of these currents does not exceed 2.7 mA, according to BS EN 62040-1-1:2003.
WARNING: If the batteries are not already fitted and connected:
Do not continue beyond this point in the installation procedure. The equipment must be commissioned by a manufacturer-approved engineer.
Do not turn on the input mains power until the equipment has been commissioned.
3: Installation
3-12 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-1
4
Operation
4.1 Operating Instructions
Two sets of Operating Instructions are provided below; the first applies to a standard installation and the second applies if the Maintenance Bypass option is fitted.
Note: If the Maintenance Bypass option is fitted there will be a BYPASS switch on the mains power
connector plugged into the back of the UPS.
Once the UPS has been commissioned it is very straightforward to operate.
4.1.1 Standard installation without the maintenance bypass option fitted
To switch ON the UPS
1. Ensure that it is safe to apply power to the load equipment.
2. Switch ON the UPS input mains supply.
3. On the UPS Control Panel press the ON/OFF button once. a) The Control Panel LCD display will initially show UPS Switching on...
b) As the UPS runs through its start-up checks the Control Panel status indicator will change from red
to yellow and then finally remain green.
c) The UPS Control Panel LCD display wil l show the UPS input and output parameters and appear
similar to the example shown in Figure 4.2.
4. The UPS is now fully operational and providing your load equipment with a protected, backed-up supply.
5. You can now further monitor the UPS operating parameters using the Status Menu, as described in paragraph 4.4.2.
To switch OFF the UPS
1. On the UPS Control Panel press and hold the ON/OFF button for a few seconds. The UPS audible alarm will sound repeatedly and the UPS will switch OFF after 5 seconds.
2. To completely isolate the UPS disconnect the UPS input mains supply.
WARNING: If the UPS was supplied without the batteries already fitted and connected, the system must be commissioned by a manufacturer-approved service engineer before it is powered up for the first time.
Key Point: Before operating the UPS for the first time, you should familiarise yourself with the Control Panel functions described in Paragraph 4.2.
4: Operation
4-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
4.1.2 Installation with Maintenance Bypass option fitted
To switch ON the UPS (assuming the maintenance bypass switch is closed)
1. On the UPS Control Panel press the ON/OFF button once. a) The Control Panel LCD display will initially show UPS Switching on...
b) As the UPS runs through its start-up checks the Control Panel status indicator will change from red
to yellow and then finally remain green.
c) The UPS Control Panel LCD display will indicate the UPS inpu t and output parameters and appea r
similar to the example shown in Figure 4.2 except that there will be n o output power shown as the load is currently being powered via the maintenance bypass switch.
2. Transfer the UPS output to its internal static bypass as follows (Note: the UPS SETUP menu may be password protected):
a) Access the MAIN MENU>UPS SETUP>BYPASS menu, as shown on page 4-8. b) From the BYPASS menu, select and enable Forced Mode. This will turn on the UPS static bypass
which is now effectively connected in parallel with th e Maintenance Bypass supply.
3. OPEN the maintenance bypass switch (0) on the UPS mains power connector. a) The light in the switch will extinguish.
b) The load will transfer to the UPS static bypass line.
4. Transfer the UPS output to the Inverter as follows: a) Access the MAIN MENU>UPS SETUP>BYPASS menu, as shown on page 4-8.
b) From the BYPASS menu, select and disable Forced Mode.
5. The UPS is now fully operational and providing your load equipment with a protected, backed-up supply.
6. You can now further monitor the UPS operating parameters using the STATUS Menu, as described in paragraph 4.4.2.
To transfer the load from the UPS to the maintenance bypass line
1. Transfer the UPS output to its internal static bypass as follows (Note: the UPS SETUP menu may be password protected):
a) Access the MAIN MENU>UPS SETUP>BYPASS menu, as shown on page 4-8. b) From the BYPASS menu, select and enable Forced Mode. This will operate the UPS static bypass.
2. CLOSE the maintenance bypass switch (1) on the UPS mains power connector. a) The light in the switch will illuminate.
b) The load will transfer to the UPS maintenance bypass line.
1. To completely shutdown the UPS, press the ON/OFF button for a few seconds. The UPS audible alarm will sound repeatedly and the UPS will switch OFF after 5 seconds.
2. Once the UPS is shut down the mains power connector can be disconnected from the UPS power receptacle, leaving the UPS free to be removed if required whilst maintaining the load power through the maintenance bypass switch.
To power down the load when on the maintenance bypass line
1. If the load is supplied through the maintenance bypass line it can be powered off and on by means of the maintenance bypass switch.
CAUTION: When the load is connected via the maint enance b ypass supply it is not protecte d against mains failure or other power aberrations.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-3
4: Operation
4.2 Control Panel
The UPS is fully controlled from the operator control panel located on the fro nt of the UPS.
Figure 4.1 Operator control panel
4.2.1 Alpha-numeric LCD Display
Figure 4.2 LCD Display panel during normal operation
The user-friendly control panel comprises three areas:
Alpha-numeric LCD Display
Normally provides indication of the UPS operating mode together with the input/ output supply parameters and the battery ‘state of charge’ (SOC). It also displays error messages and UPS set-up data via the control menuing system
Operator Keypad
Provides keys to navigate through the UPS control menu system together with an ON/ OFF button.
Operating status indicator
The area behind the mimic diagram is illuminated by a multi-coloured led to indicate the UPS operating status.
UPS On Mains
Normal operating status when the input mains voltage is present.
On Battery
There is no mains power and the UPS is running on its batteries.
On By-pass
The UPS internal bypass circuit has been turned on and the UPS output is connected directly to the UPS input mains supply.
IN xxxV
Indicates the UPS input voltage and the RMS power absorbed from the mains. This indication is not displayed during battery operation.
OUT xxxV/x,xKW (xx%)
Indicates the output voltage and power. The power is shown in kW and also as the percentage of the total power that the UPS is able to supply.
Batt. xx,x
Indicates the battery state of charge in a bar graph format together with a numerical indication of the available autonomy time (in minutes).
4: Operation
4-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
4.2.2 Operator Keypad
Figure 4.3 Operator keypad functions
4.3 Alarms and Indications
Note: Press the ESC key to silence the audible warning.
Operating Status
Indicator
Audible Alarm Display
Message
Description
Solid Green None UPS on Mains
IN xxxV
Normal operation. Mains OK and load within limits.
Fast flashing Green None UPS on Mains
No sync mains xx.xHz
Output and input voltages are unsynchronised. Possible causes:
• PLL disabled
• Input frequency outside limits
Solid Yellow Short intermittent
every 20sec
UPS on Batteries MAINS ABSENT
UPS input supply has failed (or out of spec) and the UPS is operating
from its battery supply (batteries are discharging). Fast flashing Yellow None UPS on Bypass Load is connected directly to the mains supply via the bypass. Fast flashing Red Short, fast
intermittent
Module failure: Switch off the UPS and contact your service centre
Overload: Reduce the load until it is within the UPS capacity. Solid Red Continuous UPS error or failure.
ATTENTION! We recommend you switch off the ups and contact your
service centre Flashing Red
(every 10s)
Above 90% of MAX load
Flashing Red Alternating short/long
Alternating short,
long intermittent
RESERVE AUTONOMY!
Autonomy reserve. During battery operation
• Incorrect battery connection
• Incorrect Neutral
Flashing Red Short with pause
OUT OF REDUNDANCY!
The load consumption exceeds the set redundancy.
Power module redundancy is not guaranteed in case of failure.
ESCape Key
• Exit a function without modifying it
• Go up one menu level
• Exit the main menu and return to the status display
• Silence the buzzer
SCROLL UP Key
• Select previous function
• Increase a value
• Select a new item within the function (e.g. go from DISABLED to ENABLED)
SCROLL DOWN Key
• Select next function
• Reduce a value
• Select a new item within the function (e.g. go from ENABLED to DISABLED)
ENTER (SELECT) Key
• Confirm a value
• Access an item in the menu
• Go down a menu level
ON/OFF
• UPS ON/OFF pushbutton
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-5
4: Operation
4.4 UPS Customisation and Event Monitoring Menus
The UPS control system can be monitored and customised through a series of menus that can be displayed on the LCD panel and accessed using the operator keypad buttons. This facility is used by the service engineer to set-up the UPS during commissioning and to monitor the UPS performance and alarms history when undertaking maintenance or troubleshooting.
Accessing the Menus
The menu system can be accessed by pressing the ENTER key, which will initially display the Main Menu. From the Main Menu you can navigate to any of the lower-level menus shown below by using the SCROLL UP / SCROLL DOWN keys to highlight the required menu option and then press the ENTER key to select it. Note that the menus can be accessed even if the UPS is switched off.
To exit the menus and return to the normal display screen you must press the ON/OFF key.
4.4.1 Main Menu
The Main Menu provides access to five menus at the next level as shown in Figure 4.4.
Figure 4.4 Main Menu
WARNING: Some of the configuration functions accessible via the customisation menus can
adversely affect the UPS operating performance if programmed incorrectly. These adjustments and configuration settings must be carried out by a trained engineer.
UPS Status UPS Setup Events Scheduling Tools
MAIN MENU
UPS STATUS
UPS Info Output Input Batteries History Data Misc.
UPS SETUP
Output Input Bypass Neutral Sensor Batteries Clock Setup Operator Panel
EVENTS
Log View Log Reset
SCHEDULING
Schedule Planning Restart Shutdown Planning
Signalling test LCD DisplayTest Battery Test Battery Calibration
TOOLS
Details of the UPS STATUS menu are given in paragraph 4.4.2.
Details of the UPS SETUP menu are given in paragraph 4.4.3.
Details of the EVENTS menu are given in paragraph 4.4.4.
Details of the SCHEDULING menu are given in paragraph 4.4.5.
Details of the TOOLS menu are given in paragraph 4.4.6.
4: Operation
4-6 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
4.4.2 UPS Status Menu
The UPS Status menus are provide the user with information concerning the UPS set-up configuration and operational data – both live and historical. Most of the sub-menus are self-explanatory, as shown below.
UPS Info sub-menu
Output sub-menu
Input sub-menu
Batteries sub-menu
History Data sub-menu
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info
Output Input Batteries History Data Misc.
UPS INFO
Mod xxxx POut xxxx SWVer xxxx S/N xxxxxxxxxxxx Installed Modules x Faulty Modules x
Name of UPS Maximum output power (W) Software Version Serial Number Number of power modules fitted Number of faulty power modules
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info
Output
Input Batteries History Data Misc.
OUTPUT
Power xxx x Appar.Pow. xxxx V RMS xxxx I RMS xxxx Peak current xx Frequency xx I Crest Factor xx Power fact. xx
Supplied active power (W) Supplied apparent power (W) UPS RMS output voltage UPS RMS output current Peak current supplied at UPS output UPS Output frequency (Hz) Output crest factor (Ipeak / Irms) Output (load) power factor
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info Output
Input
Batteries History Data Misc.
INPUT
Power xxx x Appar.Pow. xxxx V RMS xxxx I RMS xxxx Peak current xx Frequency xx I Crest Factor xx Power fact. xx
Power from input mains (W) Apparent power from input mains (W) Input mains RMSvoltage (V ) Input mains RMS current (A) Input mains peak supplied current (A) Input mains frequency (Hz) Input mains crest factor (Ipeak / Irms) UPS Input power factor
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info Output Input
Batteries
History Data Misc.
BATTERIES
Voltage xx Residual Cap. xxxx Discharge Count.xxxx Usage xxxx Cal.dd/mm/yyhh:mm Ext. KB units xx Ext. Chargers xx
Voltage at the battery terminals (V) Indicates the percentage battery charge Indicates the number of discharge cycles Hours of operation on battery power Battery last calibration date/timestamp Number of external batt. cab.s fitted Number of external batt. chargers fitted
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info Output Input Batteries
History Data
Misc.
HISTORY DATA
UPS Ontime xxxx Booster Ontime xxx Draind Out N. xxxx Booster Int. xxxx Bypass Interv. xxxx Overheat Count xx
Total number of hours of UPS operation Hours spent in booster mode (on battery) Number of complete battery discharges Number of booster interventions (on battery) Number of bypass interventions Number of times thermal protection triggered
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-7
4: Operation
Misc. sub-menu
4.4.3 UPS Setup Menu
The UPS Setup menu is used to set-up various UPS operating parameters and functions. This menu can be password protected to prevent unauthorised access – see ’Operator Panel sub-menu’ on page 4-10.
Output sub-menu
Frequency: This can be set to a nominal value (i.e. 50Hz or 60Hz) or it can be configured as AUTO whereby the UPS output frequency synchronises to the input mains frequency and changes to the nominal value (50/ 60Hz) if the input mains supply fails.
N+x Redundancy: Where a system is designed to incorporate a number of redundant power modules, the UPS contains more power modules than is required to power the full connected load. Therefore the system could lose one (or more) power module before its ability to provide full load power is affected.
The N+x Redundancy setting determines the number of modules that can be inoperative before the system sounds the OUT OF REDUNDANCY alarm. A practical example is shown in the table below:
Input sub-menu
PLL Enable: If enabled, the UPS synchronises the output frequency to the input frequency. If disabled, the UPS output frequency is not synchronised, the Green status led flashes and th e ‘auto matic by pass’ facility i s inhibited which means that the load is not fully protected in the event of a UPS fault or overload condition.
Extended PLL Range: When enabled, the UPS output frequency synchronisation range is ±14% of the nominal input frequency. When disabled this is reduced to ±2%.
Load (kW) Fitted Power
Modules
Total Available
Power
Redundant
Modules
Redundant Alarm
Level (W)
System Overload
Level (W)
3700 3 3750 0 no 3750 3700 4 5000 1 3750 5000 1500 4 5000 2 2500 5000 1000 4 5000 3 1250 5000
UPS Status
UPS Setup Event s Scheduling Tools
MAIN MENU UPS STATUS
UPS Info Output Input Batteries History Data
Misc.
MISC.
Int. Temp xx Ext. Temp xx Fan Speed xx
UPS Internal termperature (deg C.) UPS External termperature (deg C.) Percentage fan speed (max 100)
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU OUTPUT
Voltage Frequency N+x Redundancy
Set the UPS outputvoltage Set the UPS output frequency (nom/auto) Set the number of redundant power boards
UPS SETUP
Output
Input Bypass Neutral Sensor Batteries Clock Setup Operator Panel
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU INPUT
PLL Enable Extend PLL Range
Enables UPS outputto sync with mains Sets the UPS output synch window
UPS SETUP
Output
Input
Bypass Neutral Sensor Batteries Clock Setup Operator Panel
4: Operation
4-8 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Bypass sub-menu
Bypass Enable: If enabled, the UPS manages bypass operation automatically. If disabled, the UPS will never switch to bypass and will switch off in the event of sustained overload or fault.
Forced Mode: If enabled, the UPS is set to operate permanently on bypass. This is the method used to connect the load to bypass when operating in the ‘ECO’ mode.
DIP Speed: When ‘Forced Mode’ is disabled, this setting alters the speed of bypass intervention. SLOW: for loads which are may cause high peak demands and are insensitive to input voltage disturbance.
STANDARD: normal condition. FAST: For loads which are extremely sensitive to input voltage disturbance.
Off-line Mode: If enabled, the UPS operates in permanent bypass mode while mains supply is available and reverts to battery power if the mains supply fails.
Load Wait Mode: If enabled, the bypass operates normally for loads below the ‘Minimum Load Threshold’ but is not available for higher loads – i.e. for higher loads, during a mains failure the UPS switches OFF and is only restarts when mains is restored. The threshold value is entered in ‘Watts’.
Programming priority:
Neutral Sensor sub-menu
Enable: If enabled, the UPS uses the neutral sensor to verify that the voltage between neutral and earth is within safe limits and switches the UPS to battery mode when this is not the case.
Ignore While Run: If enabled, the UPS only checks the neutral sensor during startup.
Function Enable Bypass Forced Mode Off-line Mode Load Waiting
Forced Enabled Enabled X X Off-Line Enabled Disabled Enabled Enabled Off-Line Enabled Disabled Enabled Disabled Load Waiting Enabled Disabled Disabled Enabled Automatic Enabled Disabled Disabled Disabled Bypass Disabled Disabled X X X
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU BYPASS
Bypass Enable Forced mode DIP Speed Off-line mode Load Wait mode
Enable/Disable bypass intervention Enables permanent bypass operation Sets bypass intervention sensitivity Selects Off-line mode of operation Selects operate on bypass on low load
UPS SETUP
Output Input
Bypass
Neutral Sensor Batteries Clock Setup Operator Panel
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU NEUTRAL SENSOR
Enable Ignore While Run
Enable/disable neutral sensor detection Disable neutral sensor when not running
UPS SETUP
Output Input Bypass
Neutral Sensor
Batteries Clock Setup Operator Panel
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-9
4: Operation
Batteries sub-menu
Capacity Manage: The Capacity Manage setting determines the method used to compute the remaining battery autonomy time that is available. This is used to activate the ‘Autonomy Reserve’ and ‘End Of Autonomy’ warnings shown on the LCD Display Panel when operating on battery power. When selected, the Capacity Manage menu presents further menu selections as shown and described below:
• Advanced Mode
In Advanced Mode the ‘Autonomy Reserve’ and ‘End Of Autonomy’ warning levels calculations are based on the power being drawn by the existing load.
•Simple Mode
In Simple Mode the end of autonomy warning calculation is based on the existing battery voltage.
Reserve Threshold: Sets the battery voltage at which the ‘Autonomy Reserve’ warning is displayed. Exhaust Threshold: Sets the battery voltage at which the ‘End Of Autonomy’ warning is displayed.
Reserve Time: If enabled, sets the maximum time (in seconds) for operation in battery mode after the ‘Autonomy Reserve’ limit is reached. Set to ‘0’ to disable.
Max Time on Batt: If enabled, sets the maximum time (in seconds) for operation in battery mode. Set to ‘0’ to disable.
Max Reserve Time: If enabled, this will turn off the load when the remaining autonomy time falls to the set value. The time is set in minutes – set to ‘0’ to disable.
Turn On Test Enable: If enabled, it initiates a battery test every time the UPS is switched ON. Restart Enable: If enabled, it forces the UPS to restart automatically when the mains supply is restored after
the UPS has shut down due to the end of battery autonomy. If not enabled, the UPS will require starting manually
External Options: This provides access to two further menu options.
• Battery Chargers No.
Enter the number of battery chargers fitted to the external battery cabinets connected to the UPS system.
• KB Kits
Enter the number of battery strings connected to the system. Note that each string comprises three batteries.
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU BATTERIES
Capacity Manage Reserve Time Max Time on Batt Max Time Reserve Turn OnTest Enable Restart Enable External Options
Determines autonomy calculation method Set reserve operating time Set max operating time on battery Set operating time after reserve is reached Enable battery test when UPS is turned on Auto restart when mains returns Set up Batt Charger and strings details
UPS SETUP
Output Input Bypass Neutral Sensor
Batteries
Clock Setup Operator Panel
Capacity Manage
Reserve Time Max Time on Batt Max Time Reserve Turn OnTest Enable Restart Enable External Options
BATTERIES SIMPLE MODE
Automatic Thresholds
Fixed Thresholds
FIXED THRESHOLDS
Reserve Thresholds Exhaust Thresholds
CAPACITY MANAGE
Advanced Mode
Simple Mode
4: Operation
4-10 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Clock Setup sub-menu
Operator Panel sub-menu
Display Backlight: This menu presents three options.
OFF – Permanently OFF TIMED – Switches OFF after a period of inactivity ON – Permanently ON
Password Change: The password ta kes the form of an 8 -digit number and is used to restrict access to the UPS Setup menu (paragraph 4.4.3). You will need to know the existing password in order to gain access to the password change menu. To change the password, allocate each new digit in turn using the UP/DOWN/ ENTER keys. (Note that validation requires that all 8 digits are assigned a value.)
4.4.4 Events Menu
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU BATTERIES
Capacity Manage Determines autonomy calculation method
UPS SETUP
Output Input Bypass Neutral Sensor
Batteries
Clock Setup Operator Panel
UPS Status
UPS Setup
Event s Scheduling Tools
MAIN MENU OPERATOR PANEL
Language Keyboard Beep Display Backlight Display Contrast Password Change
Selects the operator language Enables/disables beeps on keypress Select illumination Fixed/Timed/Disabled Set the display contrast Set the password to access UPS Settings
UPS SETUP
Output Input Bypass Neutral Sensor Batteries Clock Setup
Operator Panel
UPS Status UPS Setup
Events
Scheduling Tools
MAIN MENU
Displays the events stored in the UPS memory Deletes the events stored in the memory
EVENTS
Log View Log Reset
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 4-11
4: Operation
4.4.5 Scheduling Menu
Schedule Planning sub-menu
The Schedule Planning sub-menu allows various operating function s to be set to be programmed to operate at predetermined times.
Enable: This selection either enables or disables ALL the scheduled operations. View/Edit: This allows details of the following programmed operations to be viewed or edited. Note that each
one can be set to operate Daily (hh:mm), Singly (dd-mm hh:mm) or Weekly (name-of-day hh:mm).
Battery Test – Verifies the battery status Batt. Calibration – Calibrates the batteries Turn ON – Switch ON the UPS Turn Off – Switch OFF the UPS Absent – Absent will be displayed if a selected View/Edit page is disabled.
Sched Sequence: Displays up to 16 programmes in day/date order. Reset: Deletes all programmes.
Restart sub-menu
If the UPS is configured to automatically restart following the return of the mains supply, an audible warning is given to alert the operator that this is about to occur. The Restart sub-menu allows two parameters to be set which affect this operation.
Delay: This sets the time delay (in seconds) between the return of the mains supply and the automatic UPS start-up (i.e. the length of time that the restart warning alert signal is active).
Min Autonomy: This sets the percentage of battery discharge (autonomy) below which the UPS will not be permitted to automatically restart.
Shutdown Planning sub-menu
Delay: Sets the duration (seconds) of the signal warning that the UPS is about to be shut down.
UPS Status UPS Setup Event s
Scheduling
Tools
MAIN MENU SCHED. PLANNING
Enable View/Edit Sched. Sequence Reset
Enable/Disable set programmes Set and modify program schedule Displays set programmes in daily order Delete all settings
SCHEDULING
Schedule Planning
Restart Shutdown Planning
UPS Status UPS Setup Event s
Scheduling
Tools
MAIN MENU RESTART
Delay Min. Autonomy
Set UPS switch-on warning signal duration Set min. battery level for UPS to turn back on
SCHEDULING
Schedule Planning
Restart
Shutdown Planning
UPS Status UPS Setup Event s
Scheduling
Tools
MAIN MENU SHUTDOWN PLAN.
Delay Set UPS shutdown warning signal duration
SCHEDULING
Schedule Planning Restart
Shutdown Plan.
4: Operation
4-12 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
4.4.6 Tools Menu
Signalling Test: This provides a facility to test the Green, Yellow and Red led warnin g indicators together with the audible warning device.
LCD Display Test: Tests the alpha-numeric LCD display. All LCD display characters should illuminate when the ENTER key is pressed.
Battery Test: Provides a battery test. Contact your service centre if the test fails. Battery Calibration: Calibrates the batteries by calculating the discharge curve. This test should be carried
out after the batteries have been charged so that the UPS is able to provide precise information on the charge status.
4.5 Diagnostic Software
The UPS is fitted with a standard RS232 interface that can be used to provide computer access to data relating to the operation of the UPS and its log. A suitable inte rface programme for Windo ws® computers is available from our web-site (www.upspower.co.uk). An RS232 cable is require d to connect a serial port on your PC to the interface outlet on the rear of the UPS.
UPS Status UPS Setup Event s Scheduling
Tools
MAIN MENU
ENTER to activate test of Red/Yellow/Green lights and audible sounder. ENTER to activate test. All alpha/numeric characters should display on LCD ENTER performs a functional check of the batteries. ENTER calculates battery discharge curve to enable SOC calculation
Signalling Test LCD Display Test Battery Test Battery Calibration
TOOLS
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 5-1
5
Maintenance
5.1 Introduction
As the UPS contains no user-serviceable parts, the maintenance requirements to be ca rried out by the user are minimal beyond ensuring that the UPS operating environment remains suitably cool and dust-free.
5.2 Routine maintenance
We recommend that the UPS operating parameters are checked and recalibrated annually as part of a regular maintenance schedule to ensure optimum UPS operation efficient load protection. The batteries should also be checked annually, depending on the ambient temperature.
When the UPS is commissioned, the commissioning engineer will attach a service record book to the front of the UPS which will be used to log the full service history of the UPS.
During a preventative maintenance inspection the service engineer will check the following:
• Site environmental conditions
• Integ rity of the electrical installation
• Availability and quality of the cooling airflow
• UPS Rectifier operation and calibration
• UPS Inverter operation and calibration
• UPS Static switch operation
• Battery cond ition and status
• Load characteristics
• Integ rity of the alarm and monitoring systems
• Operation of all installed options
Preventative maintenance inspections form an integral part of all Extended Warranty Agreements (maintenance contracts) offered by Uninterruptible Power Supplies Ltd. For further details on Extended Warranty Agreements see Section 2 of this manual.
5.3 Battery Testing
The battery test procedure can be activated from the UPS operator panel an d can performed independ ently of the UPS operating mode (Off-line or On-line) and whether or not the load is connected.
WARNING: All the maintenance operations described in this chapter must be performed by an authorised electrician or other suitably qualified personnel.
WARNING: Preventative maintenance inspections entail workin g inside the UPS with safety covers removed. This presents a risk of electric shock due to the unavoidable exposure to hazardous AC and DC voltages, and should be undertaken only by trained engineers authorised by Uninterruptible Power Supplies Ltd. who are fully aware of the hazardous areas.
5: Maintenance
5-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 6-1
6
Troubleshooting
6.1 Potential Problems and Solutions
Problem Possible Solution
When the UPS is switched on, the buzzer sounds and the red warning light makes alternating short-long flashes, then the UPS switches off after 15 seconds.
The connection of the neutral conductor is incorrect:
• Swap the connections of the neutral and phase input leads, or exclude the neutral sensor.
The UPS works but a short beep is heard every 12 seconds and the yellow warning light is lit without flashing.
Check power is present at the mains outlet.
• Check that the UPS power supply cable is correctly inserted in both the mains outlet and in the connector on the UPS itself.
• Check the fuse located at the side of the input/output connector under the plastic housing (see Figure 3.8).
The UPS works but it beeps intermittently and the red warning light and the yellow warning light are flashing.
There is an overload on the UPS output.
• Reduce the load so that it does not exceed the maximum power that the UPS can supply.
• Alternatively, if the UPS is not in its maximum configuration, you can ask your Service Centre to increase the power of your UPS by fitting extra power modules and batteries inside the UPS cabinet.
The UPS beeps continuously and the yellow warning light flashes for about 15 seconds, after which the UPS switches off.
The UPS has completely flattened its batteries; it can only start up again when the mains input line is present.
• Check the magneto-thermal or differential switches that precede the UPS and the input fuse.
The UPS works but the green warning light is flashing quickly. The mains supply is out of the limits permitted for the voltage
and/or frequency, but it can still be used by the UPS. However, the by-pass function is not operational.
The UPS beeps intermittently and the red warning light is flashing quickly.
The thermal protection has been tripped.
• Switch the UPS off and wait for a few minutes so that the internal temperature of the UPS can get back to normal.
• Check that the fans operate correctly and that the airflow is not obstructed (e.g. if the UPS is too close to a wall).
• If the above step are satisfactory, there is likely to be a fault on one of the internal circuits. Contact your service centre.
6: Troubleshooting
6-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 7-1
7
Options
7.1 Maintenance Bypass
7.1.1 Introduction
Figure 7.1 Maintenance bypass circuit
The Maintenance Bypass option allows the load to be transferred to the raw input mains supply if it is necessary to completely shut down or remove the UPS for maintenance or repair purposes.
The maintenance bypass switch controls two relays, one of whi ch is connecte d in the bypass circuit and the other in the UPS output line (see Figure 7.1). When the maintenance bypass switch is OPEN (0) the UPS output relay is closed, energised from the UPS output supply via a normally-closed switch contact, and the bypass relay is open. Conversely, when the maintenance bypass switch is CLOSED (1) the bypass relay is closed, and the UPS output relay is opened. This interlocking action prevents the UPS output from being back-fed from the raw mains supply.
Key Point: When the load is connected via the maintenance bypass supply it is not protected against mains failure or other power aberrations.
UPS
N/O
Fuse
Bypass Relay
UPS Output Relay
PE N L
PE
N
L
Maintenance
Bypass Switch
INPUT MAINS
LOAD
SUPPLY
N/C
7: Options
7-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
Both relays and the maintenance bypass switch are built in to the UPS power connector (which replaces the standard power connector). The switch contains a yellow lamp which illuminates when the switch is closed to indicate that the load is connected to the maintenance bypass, as shown below in Figure 7.2.
Figure 7.2 Maintenance bypass switch location
7.1.2 Installation
This procedure provided details of how to replace the standard UPS power connector with the optional maintenance bypass power connector.
1. Isolate the load and turn off the UPS.
2. Isolate/disconnect the UPS input mains supply cable and the UPS output supply cable to the load distribution point.
3. Disconnect and remove the power connector from the UPS power receptacle after first removing the two securing screws that hold it in place.
4. Dismantle the standard power connector and disconnect the input and output power cables – for details see Figure 3.9 and Figure 3.10.
5. Feed the input/output power cables removed from the standard connector (above) through the cable glands in the new connector’s cover – observe the connection details in Figure 7.3 or Figure 7.4 to determine the correct orientation.
6. Connect the input and output cables to the replacement Maintenance Bypass Connector as shown in Figure 7.3 or Figure 7.4. – take care to ensure the cables are connected to the correct terminal blocks.
7. Tighten the cable gland ring nuts to hold the cables securely in place then attach and secure the connector’s cover using the four M3 screws provided.
8. Connect the reassembled power connector to the UPS power receptacle and secure it in place using the two screws removed in step 3.
9. Install the two self threading screws provided with the bypass if the UPS chassis is complete with the corresponding holes.
10. Do not turn ON the UPS until the installation has been functionally tested, as described below.
WARNING: The maintenance bypass switch option must be installed by qualified personnel.
Key Point: Ensure it is safe to disconnect load power before proceeding.
This procedure requires the UPS to be completely shut down and isolated from the ma ins supply.
MINIpowerPLUS 10000MINIpowerPLUS 5000
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 7-3
7: Options
Figure 7.3 Maintenance bypass connector (MINIpowerPLUS 5000)
Figure 7.4 Maintenance bypass connector (MINIpowerPLUS 10000)
7.1.3 Functional testing
1. Connect the input cable to the mains power supply and connect a load to the UPS output (e.g. a lamp).
2. Turn ON the UPS input mains power.
3. With the UPS switched off, verify the following: a) With the maintenance bypass switch in position I (MAINS), the yellow lamp illuminates in the switch
and the load receives power.
b) With the maintenance bypass switch in position 0 (UPS), the yellow lamp in the switch extinguishes
and the load receives no power.
4. Switch ON the UPS and check that the load receives power when the bypass switch is in both positions. If this does not occur:
a) Check the connection of the cables and the supply voltage rating. b) Check that the UPS power connector is fully inserted into the UPS power receptacle.
5. If the above checks prove satisfactory: a) Shutdown the UPS and turn OFF the input mains supply.
b) Disconnect the test load (lamp) and reconnect the normal load equipment.
6. Start the UPS following the procedure given in Chapter 4.
Live
Neutral
PE
Live Neutral
PE
Mains input cable UPS output cable
Live
Neutral
PE
PE
Neutral
Live
UPS output cable Mains input cable
7: Options
7-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
7.1.4 Maintenance bypass specification
7.2 Shutdown and Monitoring Software
7.2.1 Introduction
Power disruptions and depleted battery conditions pose the greatest threat to valuable computer data integrity. However, the risks inherent in these conditions can be alleviated by using a network management tool to monitor the UPS power supplies and alarm status.
By installing UPS/Mains monitoring software an administrator can monitor the utility power from a central location and obtain an early warning of impending power problems, even across more complex systems such as the Wide Area Networks (WAN) and Enterprise Wide Networks of multi-national companies.
To avoid a power loss due to depleted batteries, caused by a mains failure that exceeds the battery autonomy time, the UPS management software can initiate an automatic and con trolled computer shutd own when the battery reaches a predetermined point in its discharge cycle. The allows valuable data to be saved and the operating system to be shut down gracefully before the power is lost.
Four monitoring systems are available for use with the MINIpowerPLUS UPS system:
• WAVEMON – can be used for monitoring and automatic shutdown
• SNMP – can be used for monitoring only
• PowerREPORTER – can be used to automatically email UPS monitored parameters and alarm
events to Uninterruptible Power Supplies Ltd. for appropriate response
• RELAY INTERFACE BOARD – provides volt free contacts for connecting to a remote alarm monitor
7.2.2 WAVEMON UPS monitoring software
WAVEMON is designed to operate with many of the Uninterruptible Power Supplies Ltd. UPS systems and features both monitoring and automatic server/UPS shutdown facilities. The system comprises a bespoke software package which is installed on a local PC and communicates with the UPS over a standard RS232 cable connected to the RS232 port on the UPS back panel. The interconnecting RS232 cable can be up to 15m in length and may be connected/disconnected whilst the UPS is running.
The main characteristics of WAVEMON are:
• On-screen autonomy time/battery time countdown
• On-screen server log off and shutdown procedure
• Time an d date stamp event log
• Extensive logging of all UPS activity and power quality data
• Al l ow alarm warnings to be monitored remotely via email
• Scheduled UPS service mode and other systems status
• Graphical user interface for Windows-compatible platforms
• Automatic unattended local shutdown
• Special modules for MS-Office software to close and save open documents
• Compatible with all optional modules like UPSDIALER, SNMP adaptors, temperature sensors, etc.
MINIpowerPLUS 5000 MINIpowerPLUS 10000
Input voltage 184V - 265V 184V - 265V Output voltage 184V - 265V 184V - 265V Input/Output Current 23A max 46A max Maximum UPS power 5kVA 10kVA Input line fuse 25A FF 2x32A FF Protection IP20 IP20 Dimensions (w x h x d) 240 x 145 x 59 224 x 250 x 55
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 7-5
7: Options
Figure 7.5 WAVEMON Monitoring screen image
WAVEMON Operation
The UPS-Management software is a client/server-application for networks and local workstations and consists of two parts: the server-module of the UPS-Management Software is called UPSServ and the client­module UPSCli.
The server-module (UPSServ) communicates with the UPS via the RS-232 cable and works as a background process which collects messages from the UPS, interprets them and then makes them available to the client­module (UPSCli) and to any operating SNMP-based management station.
When UPSServ detects a voltage variation or a power failure it can be programmed to execute various ‘system event’ routines, which for example may shutdown the server or send a warning message to connected users. These routines are a part of the UPS-Management Software a nd their functionality can be adjusted to suit the user’s demands.
RCCMD - Remote Console Command module for a multi-server shutdown
In some situations it is preferab le to interface the MINIpowerPLUS to the network via an SNMP adapter, which allows up to 50 computers to be shut down in a RCCMD environment.
RCCMD (Remote Console Command) is an additional software module, which can be triggered by the SNMP device to execute a command (typically a shutdown command) on a remote system.
The MINIpowerPLUS can be integrated into a network by means of the server which is being powered by the UPS if it is already integrated into the network. In most cases the server is used as a sub-agent and you only need the PMC-Software without any SNMP Adapter. You need a standard serial connection between the RS232 port of the UPS and the RS232 port of the computer/server.
Licence conditions
The UPS management software includes the licence for using the UPS service on one server with one UPS and an unlimited number of connected Windows workstations. When operating with two or more servers, a further licence is required for each additional server, irrespective of whether the UPS service runs at that location or if the server is halted by a UPS service via remote command (RCCMD).
The same licence conditions apply to the use of remote send/receive modules (RCCMD) and multi-server shutdown under NT, UNIX and other operating systems. The service programs are generally delivered as a single-licence. To use a single CD ROM to shutdown multiple servers you must purchase additional CD license keys.
7: Options
7-6 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
7.2.3 SNMP ADAPTER for network management/remote monitoring
Simple Network Management Protocol (SNMP) is a world-wide standardised communication protocol that can be used to monitor any network-connected device vi a a simple control lang uage. The monitore d results are displayed in a web browser.
When this facility is used in conjunction with the MINIpowerPLUS, an external SNMP adapter is used which is connected to the RS232 connector on the UPS back panel. The SNMP adapter is then connected to the network by means of a standard RJ-45 terminated Ethernet connector.
The adapter is enclosed in a small box which must be powered from a backed-up supply supported by the UPS output so that its power is maintained in the event of a mains failure. A suitable plug-top power supply is included with the option kit.
Note: It is the customer’s responsibility to provide a suitable, backed-up mains supply for the adapter.
The UPS-Management software agent installed in the SNMP adapter monitors the UPS operating parameters and outputs its data in SNMP format to the connected network.
In order to use this adapter the operating system you are using must be SNMP-compatible. We offer our software with SNMP functionality together with NetWare, OS/2, all Windows NT systems on INTEL and ALPHA. The SNMP adapter requires a PC with terminal connections, and for normal operation at least one Ethernet network connection is also required.
Figure 7.6 SNMP Adapter
RCCMD - Remote Console Command module for a multi-server shutdown.
The RCCMD modules are independent programs that may be activated on the computer that is running UPSMAN. This makes a shutdown call possible in any LAN and WAN environment, regardless of the network type or operating system.
Ethernet
External SNMP Adapter
UPS
External SNMP Adapter
The small (125x70 mm) External SNMP adapter comes with following interfaces:
1. RJ-45 connector for 10/100 Base-T (auto switchable).
2. Serial Port for configuration (COM2) or optional ModBus interface.
3. Error/Link LED for UPS status.
4. Aux. Port.
5. DIP Switch.
6. Serial Port to the UPS (COM1)
7. DC Supply (9 VDC or 9-36 VDC supply, depending on model), from a UPS-backed socket.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 7-7
7: Options
7.3 PowerREPORTER™ management software
PowerREPORTER™ is a remote monitoring and management service which is a part of the premiu m power protection concept.
ThePowerREPORTER™ application:
• Provides affordab le, continuous monitoring o ver mission-critical facilities and offers pe ace-of-mind by detecting and warning of any potential system problems before they become a crisis. I
• Acquires key performance parameters and productivity information in real-time to enable you to better understand machine performance and faster troubleshoot downtime events
• Gives total transparent information concerning all actions performed on the system, such as all critical status changes, coordination of equipment service, reporting of all alarms with priorities
Key features
• Redundant and secure communication
• Alarm acknowledgment
• Priority driv en Management (with escalation)
Comprehensive management system
• Reception and management of alarm calls from UPS
• Storage of UPS Data in a database exportable in a CSV-format for easy handling in Excel
• Unlimited number of UPS that can be managed
• User administration with passwords and permission-level
• Administration of Log file
• Data logging with statistical analysis and diagnostics, report
• Visualization of the UPS data – Current status (“single” and “parallel” operation) – Measured values for single or three phase – Recording function including graphs with zooming capabilities for selected measured values – Display of event log file – Display of UPS Parameters – Web Server functionality, for data access from any Web Browser
7: Options
7-8 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
7.3.1 Relay Interface Board
The Relay Interface Board provides volt-free alarm and status outputs that can be connected to a remote panel.
The board is contained in an ABS box which is fitted to the UPS back panel and connected to the 9-pin D-type connector on the back of the UPS by means of the supplied 0.6m ribbon cable.
The box cover is held in place by moulded clips and can be easily removed to provide access to the output terminal connectors.
Three relays are contained on the Interface Board which operate under the following conditions (see also paragraph 3.3.2).
1. UPS on Mains / Battery
2. General UPS fault detected
3. Low battery. UPS has been operating on battery power and remaining autonomy time is low.
All relay contacts are rated at 150Vdc / 125Vac and 1A.
Figure 7.8 Relay Interface Board
Figure 7.7 Relay Board Assembly
EC2 On Mains / On Battery
EC3 General Alarm
EC4 Low Battery (Autonomy Reserve)
UPS D-type connector
Relays are rated at 150Vdc/ 125Vac/ 1Amp
C = Common contact NO = Normally Open NC = Normally Closed
When jumpers J1,J2,J3 are inserted the Alarm and Low Battery warnings are joined.
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 8-1
8
Specifications
8.1 Construction Features
8.2 Environmental
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Weight UPS Cabinet (Kg.) 23.5 34 43 53 24+50 26.5 29 31.5 34 Weight Battery Cabinet (Kg.) 50 57.5 65 72.5 380 Size (mm) (WxDxH) Tower: 270 x 475 x 570
19" Rack: 483.5 x 266 x 600 (6U)
270 x 475 x 570 x 2 cabinets
Technology PWM high frequency both for input stage and output stage. Microprocessor control logic. Expandability Optional upgrading to configurations with
higher power by fitting one or more extra power modules inside the same cabinet, up to a maximum of 4. Optional upgrading of autonomy by fitting extra batteries inside, up to a maximum of 4 sets of 3, 12V, 9Ah batteries.
Optional upgrading to configurations with higher power by fitting one or more extra power modules inside the same cabinet, up to a maximum of 8. Optional upgrading of autonomy by fitting extra batteries inside, up to a maximum of 10 sets of 3, 12V, 9Ah batteries.
Expandability Optional battery cabinets can be connected, with a capacity of max 10 sets of 3, 12V , 9Ah batteries. Computer Interface Output with 9-pin male, SELV insulated connector.
Standard serial RS232 for interfacing with personal computer using diagnostics software. Output with 9pin, female, SELV insulated, connector.
Remote Control Output with 9-pin male, SELV insulated connector for connection to optional remote control.
Optional scheduling of UPS switch ON/OFF and display of main UPS signals.
Protection Electronic protection against overloads, short circuits and excessive battery discharge. Operation
blocked at end of autonomy. Inrush limitation when switching on. Sensor for correct neutral connection. Back-feed protection (electrical insulation for the safety of the input plug when running in battery mode). EPO contact (emergency power off)
Synchronised Bypass Automatic static and manual (optional). Intervenes in case of overload and operating anomaly.
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Storage Altitude 10.000 metres Storage Temperature -20°C to +50°C Operating Temperature 0°C to +40°C Relative Humidity 20-80% non-condensing Protection IP 21 (IEC529) Audible Noise < 40dBA at 1 metre
8: Specifications
8-2 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
8.3 Electrical Input
8.4 Output Waveform
8.5 Output When Running on Mains Power
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Nominal Input Voltage 230V Input Voltage Range 184V to 264V with nominal load
100V to 264V with 50% nominal load Frequency 50 or 60Hz ± 2% auto-sensing and/or selected by operator Current (Nom.) 4.6A 8.9A 13.2A 17.7A 17.7A 22.4A 26.9A 31.25A 36.6A Current (Max.) 5.75A 11.2A 16.6A 22.2A 22.2A 27.8A 33.25A 38.9A 44.5A Current Distortion <3% THD Power Factor > 0.99 at 20% nominal load Inrush Current 100% of nominal current Phases Single Line Fuse 25AF 32 + 32 AFF Battery Charger 0.8A rms (direct from mains)
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Mains Operation Sine wave Battery Operation Sine wave Topology No break, on line UPS with passing neutral and double conversion
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (auto-sensing and/or as selected by operator) Output Current with linear load
and 0.7 pf (A rms)
5.37 10.75 16.25 21.6 21.6 27.2 32.6 38 43.5
Crest Factor 3.5 Output VA 1250 2500 3750 5000 5000 6250 7500 8750 10000 Output W
with 0.7 pf linear/non-linear load
875 1750 2625 3500 3500 4375 5250 6125 7000
THD < 0.5% with nominal load and < 1% with 0.7 pf nominal non-linear load Overload Capacity 300% for 1s, 200% for 5s and 150% for 30s without By-pass intervention Phases Single AC-AC conversion efficiency with
linear load pf=1 and charged batteries
80% with 50% load 85% with 75% load
92% with 100% load
UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12 8-3
8: Specifications
8.6 Output When Running on Battery Power
8.7 Battery Operation (MINIpowerPLUS 5000)
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (auto-sensing and/or as selected by operator) Output VA 1250 2500 3750 5000 5000 6250 7500 8750 10000 Output W
with 0.7 pf linear/non-linear load
875 1750 2625 3500 3500 4375 5250 6125 7000
THD < 1% Overload Capacity 160% for 15s Allowable load pf 0.7-1.0
WARNING: There is a danger of explosion should the batteries be replaced with the wrong type. Dispose of used batteries as per the instructions and precautions for their disposal on the battery label.
UPS Model Range MINIpowerPLUS 5000
1250 2500 3750 5000
Percentage load 50 80 100 50 80 100 50 80 100 50 80 100 *Standard autonomy 20 11 8 20 11 8 20 11 8 20 11 8 Recharge time to 90% charge 5 - 6 hours according to level of discharge Specifications and quantity of
batteries
3 off 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each power
module Reserve signals 32.2 V to 36V, programmable Minimum voltage for battery
operation during discharge
27V to 31.5V with automatic selection depending on applied load, or as programmed by operator.
*Approximate autonomy in minutes with fully charged batteries
8: Specifications
8-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
8.8 Battery Operation (MINIpowerPLUS 10000)
8.9 Bypass
8.10 Reference Standards
UPS Model Range MINIpowerPLUS 10000
5000/2 6250/2 7500/2 8750/2 10000/2
Percentage load 50 80 100 50 80 100 50 80 100 50 80 100 50 80 100 *Standard Autonomy 20 11 8 20 11 8 20 11 8 20 11 8 20 11 8 Recharge time to
90% charge
5 - 6 hours according to level of discharge
Specifications and quantity of batteries
3 pcs 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each power module
Reserve signals 32.2 V to 36V, programmable Minimum voltage for
battery operation during discharge
27V to 31.5V with automatic selection depending on applied load, or as programmed by operator.
*Approximate autonomy in minutes with fully charged batteries
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Type Static and electromechanical Switchover time Zero
UPS Model Range MINIpowerPLUS 5000 MINIpowerPLUS 10000
1250 2500 3750 5000 5000/2 6250/2 7500/2 8750/2 10000/2
Safety Conforms to standard EN 62040-1-1 Electromagnetic
compatibility
Immunity: Conforms to standard EN 50091-2 (class A)
Emissions: Conforms to standard EN 50091-2 (class B)
Typical Performance Conforms to standard EN 62040-3
Loading...