Unigas P20, P45, P50, P30, P65 Installation, Operation And Maintanance Manual

Technical Documentation CIB Unigas - Campodarsego (PD) - Italy
MANUAL OF
- INSTALLATION
- OPERATION
- MAINTENANCE
GAS BURNERS
TOWN GAS VERSION
M03980CA Rev. 00 01/02
NOTICES2
NOTICES
THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER.
INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
THE USER WILL FIND FURTHER INFORMATION ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SEC­TION OF THIS MANUAL. WE HIGHLY RECOMMEND TO READ IT.
CAREFULLY KEEP THIS MANUAL FOR FUTURE REFERENCE.
1) GENERAL INTRODUCTION
! The equipment must be installed in compliance with the
regulations in force, following the manufacturer’s instruc­tions, by qualified personnel.
! Qualified personnel means those having technical knowle-
dge in the field of components for civil or industrial heating systems, sanitary hot water generation and particularly ser­vice centres authorised by the manufacturer.
! Improper installation may cause injury to people and ani-
mals, or damage to property, for which the manufacturer cannot be held liable.
! Remove all packaging material and inspect the equipment
for integrity. In case of any doubt, do not use the unit - contact the supplier. The packaging materials (wooden crate, nails, fastening devi­ces, plastic bags, foamed polystyrene, etc), should not be left within the reach of children, as they may prove harmful.
! Before any cleaning or servicing operation, disconnect the
unit from the mains by turning the master switch OFF, and/
or through the cut-out devices that are provided.
! Make sure that inlet or exhaust grilles are unobstructed. ! In case of breakdown and/or defective unit operation,
disconnect the unit. Make no attempt to repair the unit or
take any direct action. Contact qualified personnel only. Units shall be repaired exclusively by a servicing centre, duly authorised by the manufacturer, with original spare parts. Failure to comply with the above instructions is likely to impair the unit’s safety. To ensure equipment efficiency and proper operation, it is essential that maintenance operations are performed by quali­fied personnel at regular intervals, following the manufactu­rer’s instructions.
! When a decision is made to discontinue the use of the
equipment, those parts likely to constitute sources of dan-
ger shall be made harmless.
! In case the equipment is to be sold or transferred to
another user, or in case the original user should move and
leave the unit behind, make sure that these instructions
accompany the equipment at all times so that they can be
consulted by the new owner and/or the installer.
! For all the units that have been modified or have options fit-
ted then original accessory equipment only shall be used.
! This unit shall be employed exclusively for the use for
which it is meant. Any other use shall be considered as
improper and, therefore, dangerous. The manufacturer shall not be held liable, by agreement or otherwise, for damages resulting from improper installation, use and failure to comply with the instructions supplied by the manufacturer.
2) SPECIAL INSTRUCTIONS FOR BURNERS
! The burner should be installed in a suitable room, with ven-
tilation openings complying with the requirements of the regulations in force, and sufficient for good combustion.
! Only burners designed according to the regulations in force
should be used.
! This burner should be employed exclusively for the use for
which it was designed.
! Before connecting the burner, make sure that the unit
rating is the same as delivery mains (electricity, gas oil, or other fuel).
! Observe caution with hot burner components. These are,
usually, near to the flame and the fuel pre-heating system, they become hot during the unit operation and will remain
hot for some time after the burner has stopped. When the decision is made to discontinue the use of the bur­ner, the user shall have qualified personnel carry out the fol­lowing operations:
a) Remove the power supply by disconnecting the power cord
from the mains. b) Disconnect the fuel supply by means of the hand-operated
shut-off valve and remove the control handwheels from
their spindles.
Special warnings
! Make sure that the burner has, on installation, been firmly
secured to the appliance, so that the flame is generated
inside the appliance firebox.
! Before the burner is started and, thereafter, at least once a
year, have qualified personnel perform the following opera-
tions: a) set the burner fuel flow rate depending on the heat input of
the appliance; b) set the flow rate of the combustion-supporting air to obtain
a combustion efficiency level at least equal to the lower
level required by the regulations in force; c) check the unit operation for proper combustion, to avoid
any harmful or polluting unburnt gases in excess of the
limits permitted by the regulations in force; d) make sure that control and safety devices are operating
properly; e) make sure that exhaust ducts intended to discharge the
products of combustion are operating properly; f) on completion of setting and adjustment operations, make
sure that all mechanical locking devices of controls have
been duly tightened; g) make sure that a copy of the burner use and maintenance
instructions is available in the boiler room.
! In case of repeated burner shut-downs, do not continue re-
setting the unit manually. Contact qualified personnel to
take care of such defects.
! The unit shall be operated and serviced by qualified per-
sonnel only, in compliance with the regulations in force.
NOTICES 3
3) GENERAL INSTRUCTIONS DEPENDING ON FUEL USED
3a) ELECTRICAL CONNECTION
! For safety reasons the unit must be efficiently earthed and
installed as required by current safety regulations.
! It is vital that all saftey requirements are met. In case of any
doubt, ask for an accurate inspection of electrics by quali­fied personnel, since the manufacturer cannot be held lia­ble for damages that may be caused by failure to correctly earth the equipment.
! Qualified personnel must inspect the system to make sure
that it is adequate to take the maximum power used by the equipment shown on the equipment rating plate. In particu­lar, make sure that the system cable cross section is ade­quate for the power absorbed by the unit.
! No adaptors, multiple outlet sockets and/or extension
cables are permitted to connect the unit to the electric mains.
! An omnipolar switch shall be provided for connection to
mains, as required by the current safety regulations.
! The use of any power-operated component implies obser-
vance of a few basic rules, for example:
do not touch the unit with wet or damp parts of the body
and/or with bare feet;
do not pull electric cables;
do not leave the equipment exposed to weather (rain,
sun, etc.) unless expressly required to do so;
do not allow children or inexperienced persons to use
equipment;
! The unit input cable shall not be replaced by the user.
In case of damage to the cable, switch off the unit and contact qualified personnel to replace. When the unit is out of use for some time the electric switch supplying all the power-driven components in the system (i.e. pumps, burner, etc.) should be switched off.
3b) FIRING WITH GAS, GASOIL OR OTHER FUELS
GENERAL
! The burner shall be installed by qualified personnel and in
compliance with regulations and provisions in force; wrong
installation can cause injuries to people and animals, or
damage to property, for which the manufacturer cannot be
held liable.
! Before installation, it is recommended that all the fuel sup-
ply system pipes be carefully cleaned inside, to remove
foreign matter that might impair the burner operation.
! Before the burner is commissioned, qualified personnel
should inspect the following: a) the fuel supply system, for proper sealing;
b) the fuel flow rate, to make sure that it has been set based
on the firing rate required of the burner; c) the burner firing system, to make sure that it is supplied for
the designed fuel type; d) the fuel supply pressure, to make sure that it is included in
the range shown on the rating plate; e) the fuel supply system, to make sure that the system
dimensions are adequate to the burner firing rate, and that
the system is equipped with all the safety and control devi-
ces required by the regulations in force.
! When the burner is to remain idle for some time, the fuel
supply tap or taps should be closed.
SPECIAL INSTRUCTIONS FOR USING GAS
Have qualified personnel inspect the installation to ensure that:
a) the gas delivery line and train are in compliance with the
regulations and provisions in force; b) all gas connections are tight; c) the boiler room ventilation openings are such that they
ensure the air supply flow required by the current regula-
tions, and in any case are sufficient for proper combustion.
! Do not use gas pipes to earth electrical equipment. ! Never leave the burner connected when not in use. Always
shut the gas valve off.
! In case of prolonged absence of the user, the main gas
delivery valve to the burner should be shut off.
Precautions if you can smell gas
a) do not operate electric switches, the telephone, or any
other item likely to generate sparks; b) immediately open doors and windows to create an air flow
to purge the room; c) close the gas valves; d) contact qualified personnel.
! Do not obstruct the ventilation openings of the room where
gas appliances are installed, to avoid dangerous conditions
such as the development of toxic or explosive mixtures.
PART I : INSTALLATION4
TECHNICAL DATA SINGLE STAGE BURNERS
BURNERS TYPE/MODEL P20 C-....25 P20 C-....40 P30 C-....40/50 P45 C-....40
Input min. kW 80 80 150 240
max. kW 230 280 350 520 min. kcal/h 68.800 68.800 129.000 206.400
max. kcal/h 197.800 240.800 301.000 447.200 Fuel Town gas Town gas Town gas Town gas Category I
2h
I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
20 - 58 20 - 70 37 - 87 25.4 - 55 Gas pressure min.* - max. mbar 50 - 200 60 - 200 60 - 200 80 - 200 Power supply 230V - 50Hz 230V - 50Hz 230V - 50Hz 230V - 50Hz Power consumption W 650 650 650 900 Electric motor (2800 rpm) W 370 370 370 620 Protection IP40 IP40 IP40 IP40 Weight Kg 30 30 30 58 Gas train size 1” 1”
1/2
1”
1/2
/ 2” 1”
1/2
Gas connections Rp 1 Rp 1
1/4
Rp 1
1/4
/ Rp2 Rp 1
1/2
Operation single stage single stage single stage single stage Destination country * * * *
BURNERS TYPE/MODEL P45 C-....50 P50 C-....40 P50 C-....50 P50 C-....65
Input min. kW 240 350 350 350
max. kW 520 523 860 860 min. kcal/h 206.400 301.000 301.000 301.000
max. kcal/h 447.200 449.700 739.600 739.600 Fuel Town gas Town gas Town gas Town gas Category I
2h
I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
25.4 - 55 37 - 55 37 - 91 37 - 91 Gas pressure min.* - max. mbar 60 - 200 80 - 200 90 - 200 50 - 200 Power supply 230V - 50Hz 230-400V - 50Hz 230-400V - 50Hz 230-400V - 50Hz Power consumption W 900 1.600 1.600 1.600 Electric motor (2800 rpm) W 620 1.100 1.100 1.100 Protection IP40 IP40 IP40 IP40 Weight Kg 58 58 58 65
Gas train size 2” 1”
1/2
2” 2”
1/2
Gas connections Rp 2 Rp 1
1/2
Rp 2 DN 65 Operation single stage single stage single stage single stage Destination country * * * *
PART I: INSTALLATION
PART I : INSTALLATION 5
DOUBLE STAGE, PROGRESSIVE AND FULLY MODULATING BURNERS
Note: all the gas flow rates (m
3
/h) are referred to standard gas conditions: 1013 mbar pressure, 15° C temperature.
* Minimum pressure required to get the maximum rate with any back-pressure in combustion chamber (referring to the perfor­mance curves). The burner operates correctly also with lowest pressure only if these are enough to guarantee the necessary gas rate.
BURNERS TYPE/MODEL P20 C-....25 P20 C-....40 P30 C-....40/50 P45 C-....40
Input min. low flame kW 85 85 65 145
min. high flame kW 120 120 100 220 max. kW 230 280 350 520 min. low flame kcal/h 73.100 73.100 55.900 124.700 min. high flame kcal/h 103.200 103.200 86.000 189.200
max. kcal/h 197.800 240.800 301.000 447.200 Fuel Town gas Town gas Town gas Town gas Category I
2h
I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
21 - 58 21 - 70 16 - 87 36 - 130 Gas pressure min.* - max. mbar 50 - 200 60 - 200 50 - 200 80 - 200 Power supply 230V - 50Hz 230V - 50Hz 230V - 50Hz 230V - 50Hz
Power consumption W 650 650 650 900 Electric motor (2800 rpm) W 370 370 370 620 Protection IP40 IP40 IP40 IP40 Weight Kg 30 30 30 58 Gas train size 1” 1”
1/2
1”
1/2
/ 2” 1”
1/2
Gas connections Rp 1 Rp 1
1/4
Rp 1
1/4
/ Rp1 Rp 1
1/2
Operation
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
Destination country * * * *
BURNERS TYPE/MODEL P45 C-....50 P65 C-....50 P65 C-....65
Input min. low flame kW 145 270 270
min. high flame kW 220 480 480 max. kW 520 970 970 min. low flame kcal/h 124.700 232.200 232.200 min. high flame kcal/h 189.200 412.800 412.800 max. kcal/h 447.200 834.200 834.200
Fuel Town gas Town gas Town gas Category I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
36 - 130 67 - 242 67 - 242 Gas pressure min.* - max. mbar 60 - 200 120- 200 70 - 200 Power supply 230/400V - 50Hz 230V - 50Hz 230V - 50Hz Power consumption W 900 2000 2000 Electric motor (2800 rpm) W 620 1500 1500 Protection IP40 IP40 IP40 Weight Kg 58 150 155 Gas train size 2” 2” 2”
1/2
Gas connections Rp 2 Rp 2 DN 65
Operation
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
Destination country * * *
PART I : INSTALLATION6
BURNER MODEL IDENTIFICATION
Burners are identified by burner type and model. Burner model identification is described as follow. Type: P20 Model: C-. AB. S. *. A. 0. 40
(1) (2) (3) (4) (5) (6) (7) (8) (1) BURNER TYPE (2) FUEL C - Town gas (3) OPERATION Available versions TN - Single stage
AB - Double stage PR - Progressive MD - Fully modulating
(4) BLAST TUBE LENGHT (see overall dimensions)
Available versions S - Standard
L - Long (5) DESTINATION COUNTRY * - see data plate (6) SPECIAL VERSION A - Standard (7) BURNER EQUIPMENT Available versions 0 - 2 Valves
1 - 2 Valves + leakage control (optional if burner input < 1200 kW) (8) GAS TRAIN SIZE (See Technical data)
25= Rp1 40 = Rp1
1/2
50 = Rp2 65 = DN65
BL - Long blast tube
OVERALL DIMENSIONS IN mm
Fig. 4a
Fig. 4b - Boiler plate drilling template - Make 4 M10 threaded holes
ABBLCCLDE FGKJLN
P20 555 210 295 765 850 510 200 710 126 290 178 360 370 P30 555 230 330 785 885 510 200 710 148 290 178 360 370 P45 660 255 355 915 1015 640 250 890 144 350 210 460 450 P50 660 345 435 1005 1095 640 250 890 184 350 210 460 450 P65 825 325 415 1150 1240 750 350 1060 184 375 230 460 450
UVWZ
P20 155 155 220 160 P30 155 155 220 160 P45 215 190 287 200
P50 215 190 287 200 P65 233 233 330 250
PART I : INSTALLATION 7
PERFORMANCE CURVES
------ Minimum high flame
To get the input in kcal/h, multiply value in kW by 860.
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P20 C-.TN...25
kW
P30 C-.TN..40
kW
Fig. 5
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P20 C-.AB...25 - C-.PR...25 - C-.MD...25
kW
P30 C-.AB...40 - C-.MD...40 - C-.PR...40
kW
Fig. 6
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P20 C-.TN...40
kW
P45 C-.TN...xx
kW
Fig. 7
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P20 C-.AB...40 - C-.PR...40 - C-.MD...40
kW
P45 C-.AB...xx - C-.PR...xx - C-.MD...xx
kW
Fig. 8
0
1
2
3
4
5
6
7
8
40 60 80 100 120 140 160 180 200 220 240 260 280
0
1
2
3
4
5
6
7
100 140 1 80 220 260 300 340 380 420
0
1
2
3
4
5
6
7
8
40 60 80 100 120 140 160 180 200 220 240 260 280
0
1
2
3
4
5
6
7
0 40 80 120 160 200 240 280 320 360 400
80 120 160 200 240 280 320 360
0
1
2
3
4
5
6
7
8
0 40 80 120 160 2 00 240 280 320 360
0
1
2
3
4
5
6
7
8
200 240 2 80 320 360 4 00 440 480 520 56
0
0
1
2
3
4
5
6
7
8
40 80 120 160 200 240 280 320 360
0
1
2
3
4
5
6
7
8
120 160 200 240 280 320 360 400 440 480 520 560
PART I : INSTALLATION8
------ Minimum high flame
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P50 C-.TN...40
kW
P65 C-.AB...xx - C-.PR...xx - C-.MD...xx
kW
Fig. 9
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
P50 C-.TN...50 - C-.TN...65
kW
Fig. 10
0
1
2
3
4
5
6
7
8
300 340 380 420 460 500 540 580
0
1
2
3
4
5
6
7
8
9
200 300 400 500 600 700 800 900 1000
0
1
2
3
4
5
6
7
8
300 400 500 600 700 800 900
PART I : INSTALLATION 9
PRESSURE - RATE IN COMBUSTION HEAD CURVES
The pressure - gas rate curves are referred to the burner in operation with 3% of O
2
, with the combustion head at the maximum opening, servocontrol at the maximum opening and gas butterfly valve fully opened.. Refer to Fig. 11, showing the correct way to take the gas pressure, considering values of back pressure in combustion chamber.
Fig. 11
Key
1 Boiler 2 Gas pressure port on butterfly valve 3 Sightglass cooling port 4 Water column pressure gauge
Curves are referred to a null pressure in combustion head!
NOTE: THE PRESSURE-RATE CURVES ARE INDICATIVE; FOR A PROPER SETTING OF THE GAS RATE, PLEASE
REFER TO THE GAS METER READING.
INLET PRESSURE
IN COMBUSTION HEAD mbar
P20
NATURAL GAS FLOW RATE Stm
3
/h
Fig. 12
INLET PRESSURE
IN COMBUSTION HEAD mbar
P30
NATURAL GAS FLOW RATE Stm
3
/h
Fig. 13
1
3
4
2
0
1
2
3
4
5
6
7
8
9
8 101214161820222426283032
0
1
2
3
4
5
6
7
8
14 16 18 20 22 24 26 2 8 30 32 34 36 38
WARNING: THESE DIAGRAMS ARE VALID ONLY FOR NATURAL GAS BURNER!
PART I : INSTALLATION10
INLET PRESSURE
IN COMBUSTION HEAD mbar
P45
NATURAL GAS FLOW RATE Stm
3
/h
Fig. 14
INLET PRESSURE
IN COMBUSTION HEAD mbar
P50
NATURAL GAS FLOW RATE Stm
3
/h
Fig. 15
INLET PRESSURE
IN COMBUSTION HEAD mbar
P65
NATURAL GAS FLOW RATE Stm
3
/h
Fig. 16
0
5
10
15
20 25 30 35 40 45 50 55 60
2
3
4
5
6
7
8
20 30 40 50 60 70 80 90
2
3
4
5
6
7
8
9
10
20 30 40 50 60 70 80 90 100 110
WARNING: THESE DIAGRAMS ARE VALID ONLY FOR NATURAL GAS BURNER!
PART I : INSTALLATION 11
MOUNTINGS AND CONNECTIONS Packing
The burners are dispatched in cardboard pakages with dimensions: P20 - P30 98 x 55 x 46 (W x H x D) P45 - P50 118 x 67 x 57 (W x H x D) P65 127 x 84 x 76 (W x H x D) Packing cases of this kind are affected by humidity and are not suitable for stacking. The following are placed in each packing case.
1 burner with detached gas train (but electrically connected to the burner in DN65 models); 1 gasket to be inserted between the burner and the boiler; 1 envelope containing this manual .
To get rid of the burner’s packing and in the event of scrapping of the latter, follow the procedures laid down by current laws on disposal of materials.
Unpacking the burner take care of not to damage the electrical connection between the burner and the gas train
(only on DN65 models).
Fitting the burner to the boiler
After fitting the burner to the boiler ensure that the space between the blast tube and the refractory lining is sealed with appropriate insulating material (ceramic fibre cord or refractory cement).
Key
1 Burner 2 Fixing nut 3 Washer 4 Seal 5 Stud bolt 6 Sightglass cleaning tube 7 Blast tube
Fig. 17
Matching the burner to the boiler
The burners described in this manual have been tested with combustion chambers that comply with EN676 regulation and whose dimensions are described in the diagram in Fig. 18. In case the burner must be coupled with boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram, please contact the supplier, to verify that a correct matching is possible, with respect of the application involved.
To correctly match the burner to the boiler verify the necessary input and the pressure in combustion chamber are included in the burner performance curve; otherwise the choice of the burner must be revised consulting the burner manufacturer.
To choose the blast tube lenght follow the instructions of the boiler manufacturer. In absence of these consider the following:
! Cast-iron boilers, three pass flue boilers (with the first pass in the rear part): the blast tube must protrude no more than 100
mm into the combustion chamber.
The length of the blast tubes does not always allow this requirement to be met, and thus it may be necessary to use a suitably­sized spacer to move the burner backwards.
! Pressurised boilers with flame reversal: in this case the blast tube must penetrate at least 50 - 100 mm into combustion
chamber in respect to the tube bundle plate.
Fig. 18 Firing intensity, diameter and lenght of the test flame
tube as a function of the heat input Q.
Key
a) Heat input Q in kW b) Lenght of the flame tube in metres c) Flame tube firing intensity in kW/m
3
d) Diameter of combustion chamber (m)
PART I : INSTALLATION12
ELECTRICAL CONNECTIONS
! Remove the front panel of the electrical board on the burner. ! Carry out the connections in the power supply electrical board as shown in the following diagrams, verify the fan motor direc-
tion (only in three-phase burners) and refit the electrical board front panel.
For a complete key, see on page 28 and page 31.
Diagrams for burners WITH printed circuit
WARNING: The burners with high-low flame operation are fitted with an electrical bridge between terminals 6 and 7; in the event of connecting the high/low flame thermostat remove this bridge before connecting the thermostat.
IMPORTANT: In connecting electric supply wires to burner teminal block be sure that ground wire should be longer than phase and neutral ones.
Burners type P20 - P30 - P50 - P65 single stage, double stage and progressive
Fig. 19a
Burners type P45 single stage, double stage and progressive
Fig. 19b
PART I : INSTALLATION 13
Diagrams for burners WITHOUT printed circuit
Power supply terminal board
(three-phase burners)
Terminal block for connections on printed circuit
Fig. 20a
Power supply terminal board for mono-phase
burners type P45
Fig. 20b
Fig. 21
Fig. 22a
Type P20 - P30 C-.TN...
Fig. 23a
Type P50 C-.TN...
Fig. 22b
Type P20 - P30 C-.AB...
Fig. 23b
Type P65 C-.AB...
PART I : INSTALLATION14
(**) Probe connection, see Fig. 25
Fan motor direction
After completing the electrical connection of the burner, remember to check the rotation of the fan motor. The motor should rotate in an anti-clockwise direction looking at cooling fan. In the event of incorrect rotation reverse the three-phase supply and check again the rotation of the motor.
NOTE: the burners are supplied for three-phase 400 V supply, and in the case of three-phase 230 V supply it is necessary to modify the electrical connections inside the terminal box of the electric motor and replace the thermal cutout relay.
Fig. 24a
Type P20 - P30 C-.MD... PROBE CONNECTION ON FULLY MODULATING BURNERS
Fig. 25
Fig. 24b
Type P45 C-.MD
Fig. 24c
Type P65 C-.MD
RESPECT THE BASIC SAFETY RULES. MAKE SURE OF THE CONNECTION TO THE EARTHING SYSTEM. DO NOT
REVERSE THE PHASE AND NEUTRAL CONNECTIONS. FIT A DIFFERENTIAL THERMAL MAGNET SWITCH
ADEQUATE FOR CONNECTION TO THE MAINS.
PART I : INSTALLATION 15
GAS TRAIN INSTALLATION DIAGRAMS
In Fig. 26a, Fig. 26b and Fig. 26c are shown the diagrams with the gas train components wich are included in the delivery and those wich must be fitted by the customer. The diagrams complies with regulations in force.
Burner equipped with 2 gas val­ves, governor with filter and pres­sure switch.
Fig. 26a
Burner equipped with DUNGS MBDLE valves group (2 valves + filter + governor + pressure switch).
Fig. 26b
Burner equipped with 2 gas val­ves, one of which is equipped with pressure governor, gas filter and pressure switch.
Fig. 26c
Key
1 Burner 2 Gas valve EV2 3 Gas valve EV1 4 Minimum gas pressure switch 5 Governor with filter 6 Manually operated shut-off valve 7 Bellow joint 8 Leakage control (optional if output is greater than 1200 kW) 9 Multibloc gas valves group 10 Gas valve EV2 with governor 11 Gas filter
12835 764
MANUFACTURER
CUSTOMER
76
198
7611083411
PART I : INSTALLATION16
SETTINGS
WARNING!
THE SEALED SCREWS MUST NOT BE UNLOOSED!
IN A SUCH CASE THE DEVICE WARRANTY IS IMMEDIATELY INVALIDATE!
Fig. 27 - Multibloc MB-DLE - VPS504
The multibloc unit is a compact unit consisting of two valves, gas pressure switch, pressure stabilizer and gas filter.
It can be paired jointly to the Dungs VPS504 sealing controls. The gas flow rate is adjusted by means of the RP regulator after
slackening the locking screw VB by a number of turns. By unscrewing the regulator RP the flow increases and screwing it is reduced.
Tight the screw VB after settings. To set the fast opening remove cover T, reverse it upside down
and use it as a tool to rotate screw VR. Screw to reduce the star­tup flow rate, unscrew to increase it.
Do not use a screwdriver on the screw VR!
The pressure governor is adjusted by operating the screw VS located under the cover C. By screwing down the pressure is increased and by unscrewing it is reduced.
Note: the screw VSB must be removed only in case of repla­cemente of the coil.
Leakage control device VPS504 (Optional)
The VPS504 check the operation of the seal of the gas shut off valves costituting the MB-DLE. This check, carried out as soon as the boiler thermostat gives a start signal to the burner, crea­tes, by means of the diaphragm pump inside it, a pressure in the test space of 20 mbar higher than the supply pressure. When wishing to monitor the test, install a pressure gauge ranged to that of the pressure supply point PA. If the test cycle is sati­sfactory, after a few seconds the consent light LC (yellow) comes on. In the opposite case the lockout light LB (red) comes on.
To restart it is necessary to reset the appliance by pressing the illuminated pushbutton LB.
.
Fig. 27
Gas valve Dungs MV- DLE
! To adjust the gas flow rate loosen the screw VB and rotate the
regulator RP as necessary. Flow decreases sccrewing and increases unscrewing.
! Tighten the screw VB. ! To set the fast opening remove the cover T, reverse it upside
down and use it as a tool to rotate the screw VR. Clockwise rotation reduces the ignition flow rate, anticlockwise rotation increase it.
Note: the screw VSB must be removed only in case of repla­cemente of the coil.
Do not use a screwdriver on the screw VR!
Fig. 28
C
VS T(VR)
R
P
LC LB
PA
VB
VSB
T
VR
RP
VSB
VB