Unigas Idea, LO280, LO400 Series Manual

®
IDEA RANGE
LIGHT OIL BURNERS
LO280 LO400
EMC 79/336/CEE
LV 73/23/CEE
Documentazione Tecnica CIB UNIGAS spa - Campodarsego (Padova - Italy)
M039134CB Rev. 1 12-06
TABLE OF CONTENTS
WARNINGS ...................................................................................................................................................... 3
PART I: INSTALLATION................................................................................................................................. 5
BURNERS CHARACTERISTICS .........................................................................................................................................5
Burner model identification................................................................................................................................................... 5
Technical Specifications .......................................................................................................................................................5
Overall dimensions (mm) .....................................................................................................................................................6
Performance curves ............................................................................................................................................................7
How to modify blast tube length (mod. LO400) ....................................................................................................................8
MOUNTING AND CONNECTIONS ....................................................................................................................................10
Fitting the burner to the boiler ............................................................................................................................................10
LIGHT OIL PIPING INSTALLATION DIAGRAM ................................................................................................................ 12
Pump operating principle ....................................................................................................................................................13
about the use of fuel pumps ...............................................................................................................................................14
Mounting of flexible light oil hoses...................................................................................................................................... 14
SETTING LO280 ................................................................................................................................................................15
Oil rate adjustment - Single stage burners .........................................................................................................................15
Priming the pump ...............................................................................................................................................................15
Choosing oil nozzles ..........................................................................................................................................................15
Oil rate adjustment - High-low flame burners .....................................................................................................................16
Priming the pump ...............................................................................................................................................................16
mod. LO280 Air rate setting ...............................................................................................................................................17
MOD. LO400 SETTINGS ...................................................................................................................................................18
Priming the pump ...............................................................................................................................................................18
Fuel rate adjustment ...........................................................................................................................................................18
Choosing the light oil nozzles .............................................................................................................................................18
First start and air rate setting (MOD. LO400) ..................................................................................................................... 20
SERVOCONTROL CAMS SETTING - Adjustment of cams microswitches .......................................................................21
LIGHT OIL PUMPS ............................................................................................................................................................ 22
mod. LO280 Pumps ...........................................................................................................................................................22
Pumps for mod. LO400 ......................................................................................................................................................23
ADJUSTING THE COMBUSTION HEAD .......................................................................................................................... 23
PART II: OPERATION................................................................................................................................... 24
OPERATION ...................................................................................................................................................................... 25
Single-stage burners ..........................................................................................................................................................25
Double-stage burners......................................................................................................................................................... 25
Burner’s control panel .......................................................................................................................................................25
PART III: MAINTENANCE............................................................................................................................. 26
ROUTINE OPERATIONS................................................................................................................................................... 26
Removing the combustion head .........................................................................................................................................26
Removing burner components plate .................................................................................................................................. 28
Assembling burner components plate ................................................................................................................................28
Removing the electrodes ....................................................................................................................................................29
DISASSEMBLY OF THE NOZZLE mod. LO280 ............................................................................................................... 29
Removing the nozzles LO400 ............................................................................................................................................30
Correct position of electrodes and combustion head .........................................................................................................31
Check the detection current ...............................................................................................................................................31
TROUBLESHOOTING ....................................................................................................................................................... 32
WIRING DIAGRAMS.......................................................................................................................................................... 33
SPARE PARTS ..................................................................................................................................................................41
APPENDIX..................................................................................................................................................... 43
2
WARNINGS
THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER.
INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOW ING PRODUCT INSTALLATION AND MAINTENANCE.
THE USER WILL FIND FURTHER INFORMATION ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SEC­TION OF THIS MANUAL. WE HIGHLY RECOMMEND TO READ IT.
CAREFULLY KEEP THIS MANUAL FOR FUTURE REFERENCE.
1) GENERAL INTRODUCTION
z The equipment must be installed in compliance with the
regulations in force, following the manufacturer’s instruc­tions, by qualified personnel.
z Qualified personnel means those having technical knowle-
dge in the field of components for civil or industrial heating systems, sanitary hot water generation and particularly ser­vice centres authorised by the manufacturer.
z Improper installation may cause injury to peopl e and ani-
mals, or damage to property, for which the manufacturer cannot be held liable.
z Remove all packaging material and inspect the equipment
for integrity. In case of any doubt, do not use the unit - contact the supplier. The packaging materials (wooden crate, nails, fastening devi­ces, plastic bags, foamed polystyrene, etc), should not be left within the reach of children, as they may prove harmful.
z Before any cleaning or servicing operation, disconnect the
unit from the mains by turning the master switch OFF, and/
or through the cut-out devices that are provided.
z Make sure that inlet or exhaust grilles are unobstructed. z In case of breakdown and/or defective unit operation,
disconnect the unit. Make no attempt to repair the unit or
take any direct action. Contact qualified personnel only. Units shall be repaired exclusively by a servicing centre, duly authorised by the manufacturer, with original spare parts. Failure to comply with the above instructions is likely to impair the unit’s safety. To ensure equipment efficiency and proper operation, it is essential that maintenance operations are performed by quali­fied personnel at regular intervals, following the manufactu­rer’s instructions.
z When a decision is made to discontinue the use of the
equipment, those parts likely to constitute sources of dan-
ger shall be made harmless.
z In case the equipment is to be sold or transferred to
another user, or in case the original user should move and
leave the unit behind, make sure that these instructions
accompany the equipment at all times so that they can be
consulted by the new owner and/or the installer.
z For all the units that have been modified or have options fit-
ted then original accessory equipment only shall be used.
z This unit shall be employed exclusively for the use for
which it is meant. Any other use shall be considered as
improper and, therefore, dangerous. The manufacturer shall not be held liable, by agreement or otherwise, for damages resulting from improper installation, use and failure to comply with the instructions supplied by the manufacturer.
2) SPECIAL INSTRUCTIONS FOR BURNERS
z The burner should be installed in a suitable room, with ven-
tilation openings complying with the requirements of the regulations in force, and sufficient for good combustion.
z Only burners designed according to the regulations in force
should be used.
z This burner should be employed exclusively for the use for
which it was designed.
z Before connecting the burner, make sure that the unit
rating is the same as delivery mains (electricity, gas oil, o r other fuel).
z Observe caution with hot burner components. Thes e are,
usually, near to the flame and the fuel pre-heating system, they become hot during the unit operation and will remain
hot for some time after the burner has stopped. When the decision is made to discontinue the use of the bur­ner, the user shall have qualified personnel carry out th e fol­lowing operations:
a) Remove the power supply by disconnecting the power cord
from the mains. b) Disconnect the fuel supply by means of the hand-operated
shut-off valve and remove the control handwheels from
their spindles.
Special warnings
z Make sure that the burner has, on installation, been firmly
secured to the appliance, so that the flame is generated
inside the appliance firebox.
z Before the burner is started and, thereafter, at least once a
year, have qualified personnel perform the following opera-
tions: a) set the burner fuel flow rate depending on the heat input of
the appliance; b) set the flow rate of the combustion-supporting air to obtain
a combustion efficiency level at least equal to the lower
level required by the regulations in force; c) check the unit operation for proper combustion, to avoid
any harmful or polluting unburnt gases in excess of the
limits permitted by the regulations in for ce; d) make sure that control and safety devices are operating
properly; e) make sure that exhaust ducts intended to discharge the
products of combustion are operating properly; f) on completion of setting and adjustment operations, make
sure that all mechanical locking devices of controls have
been duly tightened; g) make sure that a copy of the burner use and maintenance
instructions is available in the boiler room.
z In case of repeated burner shut-downs, do not continue re-
setting the unit manually. Contact qualified personnel to
take care of such defects.
z The unit shall be operated and serviced by qualified per-
sonnel only, in compliance with the regulations in force.
WARNINGS3
3) GENERAL INSTRUCTIONS DEPENDING ON FUEL USED
3a) ELECTRICAL CONNECTION
z For safety reasons the unit must be efficiently earthed and
installed as required by current safety regulations.
z It is vital that all saftey requirements are met. In case of any
doubt, ask for an accurate inspection of electrics by quali­fied personnel, since the manufacturer cannot be held lia­ble for damages that may be caused by failure to correctly earth the equipment.
z Qualified personnel must inspect the system to make sure
that it is adequate to take the maximum power used by the equipment shown on the equipment rating plate. In particu­lar, make sure that the system cable cross section is ade­quate for the power absorbed by the unit.
z No adaptors, multiple outlet sockets and/or extension
cables are permitted to connect the unit to the electric mains.
z An omnipolar switch shall be provided for connection to
mains, as required by the current safety regulations.
z The use of any power-operated component implies obser-
vance of a few basic rules, for example:
do not touch the unit with wet or damp parts of the body
and/or with bare feet;
do not pull electric cables;
do not leave the equipment exposed to weather (rain,
sun, etc.) unless expressly required to do so;
do not allow children or inexperienced persons to use
equipment;
z The unit input cable shall not be replaced by the user.
In case of damage to the cable, switch off the unit and contact qualified personnel to replace. When the unit is out of use for some time the electric swi tch supplying all the power-driven components in the system (i.e. pumps, burner, etc.) should be switched off.
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS GENERAL
z The burner shall be installed by qualified personnel and in
compliance with regulations and provisions in force; wrong
installation can cause injuries to people and animals, or
damage to property, for which the manufacturer cannot be
held liable.
z Before installation, it is recommended that all the fuel sup-
ply system pipes be carefully cleaned inside, to remove
foreign matter that might impair the burner operation.
z Before the burner is commissioned, qualified personnel
should inspect the following: a) the fuel supply system, for proper sealing;
b) the fuel flow rate, to make sure that it has been set based
on the firing rate required of the burner; c) the burner firing system, to make sure that it is supplied for
the designed fuel type; d) the fuel supply pressure, to make sure that it is included in
the range shown on the rating plate; e) the fuel supply system, to make sure that the system
dimensions are adequate to the burner firing rate, and that
the system is equipped with all the safety and control devi-
ces required by the regulations in force.
z When the burner is to remain idle for some time, the fuel
supply tap or taps should be closed.
SPECIAL INSTRUCTIONS FOR USING GAS
Have qualified personnel inspect the installation to ensure that:
a) the gas delivery line and train are in compliance with the
regulations and provisions in force; b) all gas connections are tight; c) the boiler room ventilation openings are such that they
ensure the air supply flow required by the current regula-
tions, and in any case are sufficient for proper combustion.
z Do not use gas pipes to earth electrical equipment. z Never leave the burner connected when not in use. Always
shut the gas valve off.
z In case of prolonged absence of the user, the main gas
delivery valve to the burner should be shut off.
Precautions if you can smell gas
a) do not operate electric switches, the telephone, or any
other item likely to generate sparks; b) immediately open doors and windows to create an air flow
to purge the room; c) close the gas valves; d) contact qualified personnel.
z Do not obstruct the ventilation openings of the room where
gas appliances are installed, to avoid dangerous conditions
such as the development of toxic or explosive mixtures.
WARNINGS 4
PART I: INSTALLATION
BURNERS CHARACTERISTICS
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follow. Type LO400 Model G-. TN. S. *. A. (1) (2) (3) (4) (5) (6)
(1) BURNER TYPE LO280 - LO400 (2) FUEL G - Light oil
A - Biodiesell
(3) OPERATION Available versions TN - Single stage
AB - Double stage
(4) BLAST TUBE M - Modular
S - Standard
L - Long (5) DESTINATION COUNTRY * - destination country (see data plate) (6) BURNER VERSION A - Standard
Y - Special
M -Hydraulic jack
Technical Specifications
BURNERS
Output
Light oil rate
Fuel
Power supply
Electric motor
Total power consumption W
Weight
Operation
Operating temperature °C
Storage Temperature °C
Working service*
BURNERS
Output
Light oil rate
Fuel
Power supply
Electric motor
Total power consumption W
Weight
Operation
Operating temperature °C
Storage Temperature °C
Working service*
min. - max. kW
max. kg/h - 9.6 - 26 5.8 - 26
min.-
kW
kg
min.-max.kW
min. - max. kg/h
kW
Kg
LO280
G-.TN.x.xx.A
115 - 310 70 - 310
Light oil Light oil
230V 50Hz
0.25 0.25
0.55 0.55
42 42
Single stage éDouble stage
-10 ÷ +50
-20 ÷ +60
Intermittent
LO400
G-.TN.x.xx.A
195 - 420 115 - 420
16 - 35 10 - 35
Light oil Light oil
230V 50Hz
0.37 0.37
0.67 0.67
42 42
Single stage éDouble stage
-10 ÷ +50
-20 ÷ +60
Intermittent
LO280
G-.AB.x.xx.A
LO400
G-.AB.x.xx.A
*NOTE ON THE BURNER WORKING SERVICE: for safety reasons, one controlled shutdown must take place every 24
hours.
WARNING: if fuel used is BIODIESEL, some components must be replaced. Please contact our Technical Depart-
ment for further details.
PART I: INSTALLATION 5
O
K
2
O min.
O max.
P
K1
m
O
i
n
.
m
O
a
x
.
P
H
N
M
Fig. 5: Boiler’s drilling plate and burner’s flange
F
X
G
Y
L
B
Fig. 4
T
748 877.5 178 307.5 570 396 125 164 215 223 348 M10 219 131 179 155 491 144
AS* AL* BS* BL* C F G H K1 K2 L M N Omin Omax P X Y
732.5 877.5 162.5 307.5 570 396 108 128 215 223 348 M10 219 131 179 155 492 108
A
C
LO280
LO400
OVERALL DIMENSIONS (mm)
*S = standard blast tube
*L = long blast tube
.As far as modifying the blast tube for mod. LO400, see page 8.
PART I: INSTALLATION6
Performance curves
LO280 Single stage
6
5
4
3
2
1
0
BACK PRESSURE IN
100 150 200 250 300 350
CCOMBUSTION CHAMBER mbar
LO400 Single stage
8 7 6 5 4 3 2 1 0
BACK PRESSURE IN
-1 150 200 250 300 350 400 450
CCOMBUSTION CHAMBER mbar
LO280 High-Low flame
6
5
4
3
2
1
0
50 100 150 200 250 300 350
kW
Fig. 6 Fig. 7
LO400 High-Low flame
9 8 7 6 5 4 3 2 1 0
-1 100 150 200 250 300 350 400 450
kW
Fig. 8 Fig. 9
kW
kW
PART I: INSTALLATION 7
How to modify blast tube length (mod. LO400)
To modify blast tube length please read the following instructions. 1 Remove combustion head (See “Removing the combustion head” - Part III of this user’s manual). 2 Remove the flanged piece T by removing the 4 socket head screws VTF (Fig. 10). 3 Remove the 4 screws which hold the blast tube to the flanged piece (Fig. 2). 4 Extract the blast tube from the flanged piece and assemble it in the other way round as shown in pictures Fig. 12 and Fig.
13. Now fasten the two pieces using the same screws (Fig. 14).
5 Assemble the whole piece to the burner by caring attention to the indication in picture Fig. 15.
VTF
Fig. 10 Fig. 11
Fig. 12 - Short blast tube
T
Fig. 13 - Long blast tube
Fig. 14 Fig. 15
PART I: INSTALLATION8
If you modify the blast tube length you have to modify also the combustion head length by reading the following instructions: 1 Loosen the light oil feeding pipes connected to the nozzle-holder by using two spanners size 22 and 10 (Fig. 16). 2 Adjust cables length by pulling them very slightly as shown in Fig. 17. 3 Loosen the screw VA which tights the rod A (Fig. 18) and shift backward the flange as shown. 4 Tight the screw in the backward hole on the rod, see picture Fig. 19. 5 Fix the two extensions (supplied along with the burner inside the accessories carton box) on the light oil feeding pipes (Fig.
20) and tight them by using two spanners size 13 and 10 (Fig. 21). Fix the extensions to the nozzle holder by using two spanners size 22 and 10 (Fig. 16).
6 Assemble again the combustion head (See “Removing the combustion head” - Part III of this user’s manual).
22
10
Fig. 16
Fig. 17
VA
A
Fig. 18
Fig. 19 Fig. 20
13
Fig. 21
10
PART I: INSTALLATION 9
MOUNTING AND CONNECTIONS
Packing
The burners are despatched in packages of dimensions 795 x 550 x 490 mm (W x H x D). Packing cases of this kind are affected by humidity; the maximum number of cases to be stacked is indicated outside the
packing . The following are placed in each packing case: 1 burner; 2 light oil flexible hoses; 1 light oil filter; 1 gasket to be inserted between the burner and the boiler; 1 envelope containing this manual. To get rid of the burner’s packing and in the event of scrapping of the latter, follow the procedures laid down by current laws on
disposal of materials.
ATTENZIONE: LEGGERE SCRUPOLOSAMENTE LE AVVERTENZE RIPORTATE ALL’INIZIO DEL MANUALE.
Fitting the burner to the boiler
To perform the installation, proceed as follows: 1 fix 4 holes on the boiler’s door, according to the burner’s drilling plate described on
paragraph “Overall dimensions”; 2 place the gasket on the burner’s flange; 3 install the burner into the boiler; 4 fix the burner to the stud bolt, by means of the fixing nuts, according to Fig. 22. 5 After fitting the burner to the boiler, ensure that the gap between the blast tube and
the refractory lining is sealed with appropriate insulating material (ceramic fibre
cord or refractory cement).
Key
1Burner 2 Fixing nut 3 Washer 4 Sealing gasket 5 Stud bolt 7Blast tube
Fig. 22
PART I: INSTALLATION10
ELECTRICAL WIRING
ATTENTION: PLEASE READ CAREFULLY THE “WARNINGS” CHAPTER, AT THE BEGINNIG OF THIS MANUAL.
Identification of linking connectors
HIGH/LOW flame connector
(CONN-TAB, ) - mod. LO400
Fig. 23
Burner power supply connector
(CONN-LINEA, Fig. 24, )
Fig. 24
IMPORTANT: before operating the burner, be sure all connectors are linked as indicated in the diagrams.
Make the electric connections following the diagrams below.
WARNING: the burner is fitted with a bridge between terminals T6 and T8 on CN2-TAB connector
(external side link, male connector); remove this bridge before thermostat connection.
Fig. 25: Single stage burners
Key
C1-C2 Time counter CONN-LINEAConnectors on electrical board CONN-TABConnectors on electrical board F1-F3 Fuses IL Line switch for burner’s auxiliaries IM Fan motor line switch L Phase
Fig. 26: High - Low flame burners
LAF Burner in high flame signalling lamp (high-low flame and progressive versions only) LB Burner lockout signalling lamp LBF Burner in low flame signalling lamp (high-low flame and progressive versions only) N Neutral ST Thermostats or pressure switches group TAB High-Low flame thermostat TS Boiler safety thermostat
PART I: INSTALLATION 11
LIGHT OIL PIPING INSTALLATION DIAGRAM
PLEASE READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNIGN OF THIS MANUAL
From tank
To tank
Fig. 27
Key
1Burner 2 Flexible hoses (fitted) 3 Light oil filter (fitted) 4 Automatic interceptor (*) 5 One-way valve (*) 6 Gate valve 7 Quick-closing gate-valve (not in vicinity of tank or boiler)
(*) Only for installations with gravity, siphon or for­ced circulation feed systems. If the device installed is a solenoid valve, a timer must be installed to delay the valve closing. The direct connection of the device without a timer may cause pump breaks.
PART I: INSTALLATION12
Pump operating principle
In the burners, the mixture bertween oil and air, to perform a clean and efficient combustion, is activated by atomization of oil into very small particles. This process is achieved making oil passing through the nozzle at a determined pressure
The pump’s main function is to transfer oil from the tank to the nozzle in the desired quantity and pressure. To adjust this pres­sure, pumps are provided with a pressure regulator (except for some models for which a separate regulating valve si provided).
Other pumps are provided with two pressure regulators: one for the high and one for low pressure (in tow-stage systems with one nozzle).
These pumps can be installed both into single-pipe and double-pipe systems. Single-pipe system: a single pipe drives the oil from the tank to the pump’s inlet. Then, from the pump, the pressurised oil is
driven to the nozzle: a part comes out from the nozzle while the othe part goes back to the pump. In this system, the by-pass pulg, if provided, must be removed and the optional return port, on the pump’s body, must be sealed by steel plug and washer.
Double-pipe system: as for the single pipe system, a pipe that connects the tank to the pump’s inlet is used besides another pipe that connects the pum’s return port to the tank, as well. The excess of oil goes back to the tank: this installation can be con­sidered self-bleeding. If provided, the inside by-pass plug must be installed to avoid air and fuel passing through the pump.
Burners come out from the factory provided for double-stage systems. They can be suited for single-pipe system (recommen­ded in the case of gravity feed) as decribed before.
Bleed
Bleeding in two-pipe operation is automatic : it is assured by a bleed flat on the piston. In one-pipe operation, the plug of a pres­sure gauge port must be loosened until the air is evacuated from the system.
As far as the pipes installation, refer to the following values, considering as well, the plant’s needs.
Syphon twin pipe feed Twin pipe suction feed
Fig. 28
SUNTEC AL65 - AS47 - AT2 45 SUNTEC AL65 - AS47 - AT2 45
H (m) L (m) H (m) L (m)
Fig. 29
ø6 ø8 ø10 ø12 ø6 ø8 ø10 ø12
0 14 49 123 150 0 14 49 123 150
0,5 16 55 136 150 0,5 12 44 110 150
1 18 61 150 150 1 10 38 96 150 2 22 73 150 150 2 7 26 66 140 3 2585150150 3 3 131375 4 29 96 150 150 4 0 1 1 15
PART I: INSTALLATION 13
about the use of fuel pumps
z Make sure that the by-pass plug is not used in a single pipe installation, because the fuel unit will not function properly and
damage to the pump and burner motor could result.
z Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear
teeth, thus obstructing them.
z After filling the tank, wait before starting the burner. This will give any suspended impurities time to deposit on the bottom of
the tank, thus avoiding the possibility that they might be sucked into the pump.
z On initial commissioning a "dry" operation is foreseen for a considerable length of time (for example, when there is a long
suction line to bleed). To avoid damages inject some lubrication oil into the vacuum inlet.
z Care must be taken when installing the pump not to force the pump shaft along its axis or laterally to avoid excessive wear
on the joint, noise and overloading the gears.
z Pipes should not contain air pockets. Rapid attachment joint should therefore be avoided and threaded or mechanical seal
junctions preferred. Junction threads, elbow joints and couplings should be sealed with removable sg component. The num-
ber of junctions should be kept to a minimum as they are a possible source of leakage.
z Do not use PTFE tape on the suction and return line pipes to avoid the possibility that particles enter circulation. These
could deposit on the pump filter or the nozzle, reducing efficiency. Always use O-Rings or mechanical seal (copper or alumi-
nium gaskets) junctions if possible.
z Filter must be thoroughly cleaned at least once in a season to ensure correct working of the fuel unit. To remove the filter,
unscrew the four screws on the cover. When reassemble, make sure that the filter is mounted with the feet toward the pump
body. If the gasket between cover and pump housing should be damaged, it must be replaced. An external filter should
always be installed in the suction line upstream of the fuel unit.
Mounting of flexible light oil hoses
To connect the flexible hoses to the pump, proceed as follows. 1 Remove burner’s cover.
mod. LO280
mod. LO400
A
B
F
Fig. 30
Fig. 31
Fig. 32
DD
F
2 Remove the light oil pump delivery and return line plugs. 3 Screw the rotating nut D of the two flexible hoses F on the pump being careful to avoid inverting the delivery and return lines. 4 Fix the flexible hoses as shoewed on Fig. 33
Fig. 33
5 Replace burner’s cover.
WARNING: if fuel used is BIODIESEL, some components must be replaced. Please contact our Technical Depart-
ment for further details.
PART I: INSTALLATION14
SETTINGS LO280
Oil rate adjustment - Single stage burners
Priming the pump
Before carrying out the adjustment it is necessary to start up the fuel pump, proceeding as follows:
Prior to start up the burner, make sure that the return pipe to the tank is not obstructed. Any obstruction would
cause the pump seal to break.
Start the burner, light up the photoresistor after the opening of the solenoid valve and escape the air from the pressure port. The fuel flow rate is set choosing a properly dimensioned nozzle and setting the inlet pressure on the pump (see the hydraulic
diagram in Fig. 34 To choose the correct nozzle refer to table Tab. 1; for setting of the pump pressure, see pag. 23.
Note: all pumps are set to 12 bar. The nozzle rate must be higher than the rate referred to the minimum burner
Choosing oil nozzles
Key
EVG Light oil solenoid valve M Manometer P Pump (see chapter “LIGHT OIL PUMPS”)
Tab. 1 - Choice of the oil nozzle - Single stage burners
NOZZLE PUMP PRESSURE (bar)
67891011121314
G.P.H. kg/h
1,35 3,97 4,29 4,59 4,86 5,13 5,38 5,62 5,85 6,07
1,50 4,41 4,77 5,10 5,41 5,70 5,98 6,24 6,50 6,74
1,65 4,85 5,24 5,61 5,95 6,27 6,57 6,87 7,15 7,42
1,75 5,15 5,56 5,95 6,31 6,65 6,97 7,28 7,58 7,87
2,00 5,88 6,36 6,80 7,21 7,60 7,97 8,32 8,66 8,99
2,25 6,62 7,15 7,64 8,11 8,55 8,96 9,36 9,74 10,11
2,50 7,36 7,95 8,49 9,01 9,50 9,96 10,40 10,83 11,24
3,00 8,83 9,53 10,19 10,81 11,40 11,95 12,48 12,99 13,48
3,50 10,30 11,12 11,89 12,61 13,29 13,94 14,56 15,16 15,73
4,00 11,77 12,71 13,59 14,41 15,19 15,94 16,64 17,32 17,98
4,50 13,24 14,30 15,29 16,22 17,09 17,93 18,72 19,49 20,23
5,00 14,71 15,89 16,99 18,02 18,99 19,92 20,81 21,65 22,47
5,50 16,18 17,48 18,69 19,82 20,89 21,91 22,89 23,82 24,72
6,00 17,65 19,07 20,39 21,62 22,79 23,90 24,97 25,99 26,97
6,50 19,13 20,66 22,08 23,42 24,69 25,90 27,05 28,15 29,21
output.
Fig. 34
P
M
EVG
PART I: INSTALLATION 15
Oil rate adjustment - High-low flame burners Priming the pump
Before carrying out the adjustment it is necessary to start up the fuel pump, proceeding as follows:
Prior to start up the burner, make sure that the return pipe to the tank is not obstructed. Any obstruction would
cause the pump seal to break.
Start the burner, light up the photoresistor after the opening of the solenoid valve and escape the air from the pressure port. The light oil flow rate is adjusted choosing a nozzle of proper dimensions and setting the inlet pump pressure. To choose the nozzle refer to the table below.
Setting the light oil pump
Adjust the ignition stage of the pump, to a pressure value of 8 - 10 bar. After 10”, the safety device switch to the second stage. The pump setting must be fixed to 24 bar, by means of the adjusting screw (see chapter “LIGHT OIL PUMPS”).
NOTE: The nozzle oil rate at a pressure of 8 bar, must be greather than the oil rate at the minimum output.
Regulator high flame
Regulator low flame
low flame: 8÷10 bar high flame: 24 bar
Tab. 2 - Choice of the oil nozzle - High-low flame burners
NOZZLE
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
G.P.H. kg/h
0,40 1,36 1,44 1,52 1,59 1,66 1,73 1,80 1,86 1,92 1,98 2,04 2,09 2,15 2,20 2,25 2,30 2,35 2,40 0,50 1,70 1,80 1,90 1,99 2,08 2,17 2,25 2,33 2,40 2,48 2,55 2,62 2,69 2,75 2,82 2,88 2,94 3,00 0,60 2,04 2,16 2,28 2,39 2,50 2,60 2,70 2,79 2,88 2,97 3,06 3,14 3,22 3,30 3,38 3,46 3,53 3,60 0,65 2,21 2,34 2,47 2,59 2,70 2,82 2,92 3,02 3,12 3,22 3,31 3,40 3,49 3,58 3,66 3,74 3,83 3,90 0,75 2,55 2,70 2,85 2,99 3,12 3,25 3,37 3,49 3,60 3,71 3,82 3,93 4,03 4,13 4,23 4,32 4,41 4,50 0,85 2,89 3,06 3,23 3,39 3,54 3,68 3,82 3,95 4,08 4,21 4,33 4,45 4,57 4,68 4,79 4,90 5,00 5,11 1,00 3,40 3,60 3,80 3,98 4,16 4,33 4,49 4,65 4,80 4,95 5,10 5,24 5,37 5,50 5,63 5,76 5,88 6,01 1,10 3,74 3,96 4,18 4,38 4,58 4,76 4,94 5,12 5,29 5,45 5,61 5,76 5,91 6,06 6,20 6,34 6,47 6,61 1,20 4,08 4,32 4,56 4,78 4,99 5,20 5,39 5,58 5,77 5,94 6,12 6,28 6,45 6,61 6,76 6,91 7,06 7,21 1,25 4,25 4,50 4,75 4,98 5,20 5,41 5,62 5,82 6,01 6,19 6,37 6,54 6,71 6,88 7,04 7,20 7,36 7,51 1,35 4,59 4,86 5,13 5,38 5,62 5,85 6,07 6,28 6,49 6,69 6,88 7,07 7,25 7,43 7,61 7,78 7,94 8,11 1,50 5,10 5,41 5,70 5,98 6,24 6,50 6,74 6,98 7,21 7,43 7,64 7,85 8,06 8,26 8,45 8,64 8,83 9,01 1,65 5,61 5,95 6,27 6,57 6,87 7,15 7,42 7,68 7,93 8,17 8,41 8,64 8,86 9,08 9,30 9,51 9,71 9,91 1,75 5,95 6,31 6,65 6,97 7,28 7,58 7,87 8,14 8,41 8,67 8,92 9,16 9,40 9,63 9,86 10,08 10,30 10,51 2,00 6,80 7,21 7,60 7,97 8,32 8,66 8,99 9,30 9,61 9,91 10,19 10,47 10,74 11,01 11,27 11,52 11,77 12,01 2,25 7,64 8,11 8,55 8,96 9,36 9,74 10,11 10,47 10,81 11,14 11,47 11,78 12,09 12,39 12,68 12,96 13,24 13,51 2,50 8,49 9,01 9,50 9,96 10,40 10,83 11,24 11,63 12,01 12,38 12,74 13,09 13,43 13,76 14,09 14,40 14,71 15,02 3,00 10,19 10,81 11,40 11,95 12,48 12,99 13,48 13,96 14,41 14,86 15,29 15,71 16,12 16,51 16,90 17,28 17,65 18,02 3,50 11,89 12,61 13,29 13,94 14,56 15,16 15,73 16,28 16,82 17,33 17,84 18,33 18,80 19,27 19,72 20,16 20,60 21,02 4,00 13,59 14,41 15,19 15,94 16,64 17,32 17,98 18,61 19,22 19,81 20,39 20,94 21,49 22,02 22,54 23,04 23,54 24,02 4,50 15,29 16,22 17,09 17,93 18,72 19,49 20,23 20,94 21,62 22,29 22,93 23,56 24,17 24,77 25,35 25,92 26,48 27,03
PUMP PRESSURE
(bar)
PART I: INSTALLATION16
mod. LO280 Air rate setting
z Single stage burners
z loosen VR screw. z move the ID index along the graduated
slot towards + or -, in order to increase
or decrease the air flow-rate, according
ID
to the required combustion values.
z asten the VR screw again.
VR
Fig. 35
z Double stage burners
Servocontrol cams adjustement
. .Air damper position is set by means of the servocontrol cams. As for the setting, refer to the next table
The STA4.5B0.37 is not provided with the manual contrl for the air damper. The cams adjustement must be performed by
means of a screwdriver acting on the VS screw placed inside the cam. During the first setting, set the cam III between the cams I and II. Then, passing from the low to high flame stage, or viceversa, change the setting according to the flame composi-
tion: if cam III is too near to the low flame position (cam II), flue gas can take place, because there is more fuel than air; if cam III
is too near to high flame (cam I), the flame could fade because of too much air.
Fig. 36 - Berger STA4.5B0.37/63N30L
I
II
III
BERGER
STA4.5B0.37/6..
I High flame
II Low flame - stand by - ignition
III EVG2 opening (2nd nozzle)
VS
PART I: INSTALLATION 17
MOD. LO400 SETTINGS
Priming the pump
Before carrying out the adjustment it is necessary to start up the fuel pump, proceeding as follows:
Prior to start up the burner, make sure that the return pipe to the tank is not obstructed. Any obstruction would
cause the pump seal to break.
Start the burner, light up the photoresistor after the opening of the solenoid valve and escape the air from the pressure port.
Fuel rate adjustment
The fuel rate is setting choosing properly sized nozzles and adjusting the fuel pressure at the pump inlet (see the diagram Fig. 37 and Fig. 38). To choose the nozzles refer to Tab. 3b and Tab. 1b; for pump pressure regulation see on pag. 23. For further information on fuel pump see also the appendix.
Note: all pumps are set to 12 bar. The nozzle rate must be higher than the rate referred to the minimum burner
Key
EV Fuel solenoid valve EVG1 Fuel solenoid valve - low flame EVG2 Fuel solenoid valve - high flame (only hi-lo
flame burners) M Manometer PPump
output.
Fig. 37 - Single stage burners
EVG
Fig. 38 - Double stage burners
EVG2
P
M
EVG1
Choosing the light oil nozzles
Tab. 3a - Single-stage LO400
NOZZLE (G.P.H.) FUEL RATE kg/h
PUMP PRESSURE (bar)
10 12 14
4,00 15,19 16,64 17,98 4,50 17,09 18,72 20,23 5,00 18,99 20,81 22,47 5,50 20,89 22,89 24,72 6,00 22,79 24,97 26,97 6,50 24,69 27,05 29,21 7,00 26,59 29,13 31,46 7,50 28,49 31,21 33,71 8,30 31,53 34,54 37,30 9,50 36,09 39,53 42,70
PART I: INSTALLATION18
Tab. 3b - Double-stage LO400
RATE OUTPUT PUMP PRESSURE
kg kcal/h kW 10bar 12bar 14bar
30 306.300 356 3.50+4.50 3.00+4.00 3.00+3.50
35 357.350 416 4.00+5.00 3.50+5.00 3.50+4.00
40 408.400 475 4.50+6.00 4.00+5.50 4.00+5.00
45 459.450 534 5.00+6.50 4.50+6.00 4.00+6.00
50 510.500 594 5.50+7.50 5.00+7.00 4.50+6.50
PART I: INSTALLATION 19
First start and air rate setting (MOD. LO400)
Single stage burners
Set the air rate working on the screw VBS (Fig. 39); screw to decrease the air rate or unscrew to increase it.
Two-stage burners
z The air flow can be adjusted using the air damper servo-con-
trol cams as follows.
z Remove the burner's cover cover. z Remove the servo-control's cover. z Start the burner and let it burn at low flame (remove the bri-
dge between Terminals T6 and T8).
z Adjust the air flow in low flame by working on the appropriate
cam (Fig. 42).
z Prime the second nozzle using the following procedure:
Start the burnerWhen the flame appears press the P1 button (Fig. 40) for a
few seconds to fill the second nozzle pipe;
z The cycle continues, and if the TAB thermostat is con-
nected, the flame control apparatus brings the burner to high flame. If the TAB thermostat is not connected, bridge Termi­nals T6 and T8 on the connector (see “Identification of linking connectors” on page 11 and “Connectors layout on printed board” on page 41). Adjust the air flow at high flame by working on the appropriate cam.
z The cam that triggers the opening of the 2nd stage fuel valve
(valve EVG2) must be set in an intermediate position between the other two cams.
z Replace the cover on the servo-control. z Replace the burner's cover.
VBS
Fig. 39
P1
Connections for pressure measurement
Fig. 40 - Second nozzle’s ignition pushbutton on double stage
burners
Combustion chamber pressure port
Fan air pressure port
Fig. 41
PART I: INSTALLATION20
SERVOCONTROL CAMS SETTING - Adjustment of cams microswitches
Refer to Tab. 4 for cams functions.
I
II
III
VS
Fig. 42 - Berger STA4.5B037/4
Air damper position is set by means of the servocontrol cams. As for the setting, refer to the next table. The STA4.5B0.37 is not provided with the manual control for the air damper. The cams adjustement must be performed by
means of a screwdriver acting on the VS screw placed inside the cam. During the first setting, set the cam III inbetweens the cam I and II. Then, passing from the low to high flame stage, or viceversa, change the setting according to the flame composi­tion: if cam III is too near to the low flame position (cam II), flue gas can take place, because there is more fuel than air; if cam III is too near to low flame (cam I), the flame could be turned off because of too much air.
Tab. 4
BERGER
STA4.5BO.37
Air adjustment in high flame cam I
Air adjustment in low flame - Stand-by - Ignition cam II
Auxiliary cam for the opening consent to the second fuel valve III
PART I: INSTALLATION 21
LIGHT OIL PUMPS
mod. LO280 Pumps
Pump Suntec AS47 A
Viscosity 2 - 12 mm²/s (cSt) Fuel temperature 0 - 60 °C into the pump Maximum inlet pressure 14 bar max.
- 0,45 barto avoid the separation
between air and oil Return pressure 2 bar max. Rated speed 3600 rpm max.
Pump Suntec AT2 45A
2
Viscosity range 2 ÷ 12 (cSt) mm Oil temperature 60 °C max Inlet pressure 2 bar max.
- 0,35 barto avoid the separation
between air and oil Return pressure 2 bar max. Rated speed 3600 rpm
/s
Fig. 43
Fig. 44
Keys for Suntec AS47 A pump
1 Pressure governor 2 Manometer 3 Vacuum gauge 4 Solenoid valve 5 Nozzle 7 Suction 8 Return
Keys for Suntec A T2 45A pump 1 Low pressure regulation (first stage) 2 Manometer 3 Vacuum gauge 4 Light oil solenoid valve 4a High-low pressure solenoid valve 5 To nozzle 6 High pressure regulation (second stage) 7 Suction 8 Return (with internal by-pass plug)
PART I: INSTALLATION22
Pumps for mod. LO400
Pump Suntec AL65
2
Viscosity range 2 ÷ 12 (cSt) mm
/s Oil temperature 0 - 60 °C in the pump Inlet pressure 2 bar max.
Minimum inlet pressure
- 0,45 barto avoid the separation
between air and oil Return pressure 2 bar max. Rated speed 3600 rpm
1 suction 2 return and internal by-pass plug 3 nozzle outlet 4 pressure gauge port 5 vacuum gauge port 6 pressure adjustement
Fig. 45
ADJUSTING THE COMBUSTION HEAD
The burner is set in the factory with the combustion head in the "MAX" position, corresponding to the maximum power (combu­stion head all-forward). To operate the burner at a lowest strenght, progressively shift back the combustion head, toward the "MIN" position, rotating the VRT screw clockwise (Fig. 47).
MAX
MIN
MIN
VRT
MAX
Fig. 46 LO280 Fig. 47 LO400
VRT
PART I: INSTALLATION 23
PART II: OPERATION MANUAL
LIMITATIONS OF USE
THE BURNER IS AN APPLIANCE DESIGNED AND CONSTRUCTED TO OPERATE ONLY AFTER BEING CORRECTLY CONNECTED TO A HEAT GENERATOR (E.G. BOILER, HOT AIR GENERATOR, FURNACE, ETC.), ANY OTHER USE IS TO BE CONSIDERED IMPROPER AND THEREFORE DANGEROUS.
THE USER MUST GUARANTEE THE CORRECT FITTING OF THE APPLIANCE, ENTRUSTING THE INSTALLATION OF IT TO QUALIFIED PERSONNEL AND HAVING THE FIRST COMMISSIONING OF IT CARRIED OUT BY A SERVICE CENTRE AUTHORISED BY THE COMPANY MANUFACTURING THE BURNER.
A FUNDAMENTAL FACTOR IN THIS RESPECT IS THE ELECTRICAL CONNECTION TO THE GENERATOR’S CONTROL AND SAFETY UNITS (CONTROL THERMOSTAT, SAFETY, ETC.) WHICH GUARANTEES CORRECT AND SAFE FUNCTIO­NING OF THE BURNER.
THEREFORE, ANY OPERATION OF THE APPLIANCE MUST BE PREVENTED WHICH DEPARTS FROM THE INSTALLA­TION OPERATIONS OR WHICH HAPPENS AFTER TOTAL OR PARTIAL TAMPERING WITH THESE (E.G. DISCONNEC­TION, EVEN PARTIAL, OF THE ELECTRICAL LEADS, OPENING THE GENERATOR DOOR, DISMANTLING OF PART OF THE BURNER).
NEVER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE.
OPERATE ONLY THE MAIN SWITCH, WHICH THROUGH ITS EASY ACCESSIBILITY AND RAPIDITY OF OPERATION ALSO FUNCTIONS AS AN EMERGENCY SWITCH, AND ON THE RESET BUTTON.
IN THE EVENT OF REPEATED LOCKOUTS, DO NOT PERSIST WITH THE RESET BUTTON AND CONTACT QUALIFIED PERSONNEL WHO WILL PROCEED TO ELIMINATE THE MALFUNCTION.
WARNING: DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR (COUPLING FLANGE) CAN BECOME VERY HOT, AVOID TOUCHING THEM SO AS NOT TO GET BURNT.
PART II: OPERATION MANUAL24
FUNCIONAMIENTOOPERATION
Single-stage burners
z Turn on the burner using the switch A on the control panel (Fig. 48: the control panel of the single stage burner is only pro-
vided with the power switch and the fuse).
z Make sure that the apparatus is not in shutdown condition and if so, release by using the release button S on the burner
cover (see Fig. 49).
z Make sure that the set of thermostats (or pressure-switches) triggers burner operation. z The burner starting cycle begins and the apparatus starts the burner fan while the ignition transformer switches on at the
same time.
z At the end of pre-ventilation, the fuel solenoid valve receives input and the burner switches on. z The ignition transformer remains switched on for a few seconds after the ignition of the flame (post-ignition time) after which
it is disconnected from the circuit.
Double-stage burners
z Turn on the burner using the switch A on the control panel (Fig. 48). z Make sure that the apparatus is not in shutdown condition and if so, release by using the release button S on the burner
cover (see Fig. 49).
z Make sure that the set of thermostats (or pressure-switches) triggers burner operation. z The burner starting cycle begins and the apparatus starts the burner fan while the ignition transformer switches on at the
same time; pre-ventilation lasts for 13 or 25 seconds depending on the apparatus provided with the burner.
z At the end of pre-ventilation, the fuel solenoid valve (1st stage, EVG1) receives input as signalled by the illumination of the
signal light H on the control panel and the burner starts.
z The ignition transformer remains switched on for a few seconds after the ignition of the flame (post-ignition time), after
which it is disconnected from the circuit and the corresponding signal light switches off.
z In this way, the burner is lit at low flame; after 5 or 15 seconds (depending on the apparatus installed) two-stage operation
begins and the burner is either automatically brought to high flame (light G on) or remains burning at low flame (light H on) depending on the requests received from the system.
Burner’s control panel
A
F
E
DCB
GH
Fig. 48
Keys
AMain switch B High flame lamp C Low flame lamp D Ignition transformer ligh E Lockout signalling lamp FFuse G High flame solenoid valve operation light H Low flame solenoid valve operation light S Reset pushbutton (Fig. 49)
S
Fig. 49
PART II: OPERATION MANUAL 25
PART III: MAINTENANCE MANUAL
At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6 months.
WARNING: All operations on the burner must be carried out with the mains disconnected!
PLEASE, READ CAREFULLY “WARNINGS” CHAPTER, AT THE BEGINNING OF THIS MANUAL.
ROUTINE OPERATIONS
z Inspection and cleaning of the light oil filter cartdrige; replace it if necessary. z Check the overall condition of the flexible light oil hoses and make sure there are no signs of leakage; z Inspection and cleaning of the filter inside the light oil pump: filter must be thoroughly cleaned at least once in a season to
ensure correct working of the fuel unit. To remove the filter, unscrew the four screws on the cover. When reassemble, make sure that the filter is mounted with the feet toward the pump body. If the gasket between cover and pump housing should be damaged, it must be replaced.
z Disassembly, inspection and cleaning of the combustion head. Respect the measurements listed on pag. 31 carefully
during re-assembly.
z Inspection and cleaning of ignition electrodes (pag. 29) and respective ceramic insulators: clean, adjust, and replace if
necessary.
z Disassemble and clean the light oil nozzles (pag. 29).
IMPORTANT: cleaning must be performed using solvent, not metal tools!
At the end of maintenance operations after first reassembling the burner, light the flame and check its shape, replacing the noz­zle whenever a questionable flame shape appears. Whenever the burner is used intensely, we recommend preventively repla­cing the nozzle at the start of each heating season;
z Inspect and thoroughly clean the flame detection photoresistor and replace if necessary. In case of doubt, check the detec-
tion current after first starting the burner by following the procedure illustrated in Fig. 69.
z Clean and grease levers and rotating parts.
Removing the combustion head
z Remove the burner’s cover by unscrewing the fixing
screws.
z Slacken the light oil pipes T1 and T2 from the pump (Fig.
50).
z Disconnect the ignition cables CA1 and CA2 from the
transformer TA (Fig. 51).
z Remove the 4 screws V1 - V4 shown in Fig. 53. z Disconnect the connector CE fron the solenoid valve EV2
ATTENTION: the screw V1 is longer than the other
and must be replaced in the same position!
z Withdraw the photoelectric cell FR from its housing (Fig.
54).
ATTENTION: avoid to withdraw the photoelectric cell
drawing its cable!
z Remove the combustion head from its housing as shown
in Fig. 55.
z Clean the combustion head by a compressed air blow or,
in case of scale, scrape it off by a scratchbrush.
z Replace the combustion head. z Replace the burner’s cover.
T1
T
T2
Fig. 50
PART III: MAINTENANCE MANUAL26
Fig. 51
CA1
CA2
TA
Fig. 52
V4
CE
V1 V2
V3
Fig. 53 Fig. 54
FR
Fig. 55
PART III: MAINTENANCE MANUAL 27
Removing burner components plate
z Remove the combustion head (see “Removing the combustion head” a pagina 26). z Remove the 7 screws V5 - V11 which fasten the components plate (Fig. 56). z Remove the rod T from its housing as shown in Fig. 57. z Hook the burner components plate as shown in Fig. 58.
V10
V8
V9
V11
Fig. 56
V5
T
V6
Fig. 57
V7
Fig. 58
Assembling burner components plate
z Reassemble burner components plate and tighten the 6 screws V5 - V11 (Fig. 56). z Refit the rod T (Fig. 57). z Reassemble the combustion head and tighten the 4 screws V1 - V4 (Fig. 53).
PART III: MAINTENANCE MANUAL28
Removing the electrodes
z Remove the combustion head (see “Removing the combustion head” on page 26). z Withdraw the screw VE and remove the electrodes from the support (Fig. 59 - Fig. 60).
VE VE
Fig. 59 Fig. 60
DISASSEMBLY OF THE NOZZLE
mod. LO280
Before disassembly the nozzle, measure the real position “A” (see Fig. 61) and make a note in the panel below.
Fig. 61
NOZZLE A
60° 8
Position “A” set in the factory mm:
45° 10
60°
......................
Measurement of real “A” position, mm:
45°
Unscrew the V screw that fastens the combustion head and remove the head from the nozzle-holder (Fig. 62 - Fig. 63).
z
......................
In order to remove the nozzle, it is important to use two wrenches as shown in Fig. 63, to avoid damaging the bur-
ner component plate!
z Reassemble the combustion head by respecting the position "A" measured previously, making sure to fasten the V screw
(Fig. 62).
PART III: MAINTENANCE MANUAL 29
V
Fig. 62 Fig. 63
Removing the nozzles LO400
z Unscrew the Allen screw VT and remove the combustion head TC. z Unscrew the nozzles using two wrenches (16 and 24 mm), as shown in Fig. 66.
Double stage burners
VT
TC
Fig. 64
Single stage burners
VT
TC
Fig. 65
Fig. 66
PART III: MAINTENANCE MANUAL30
Correct position of electrodes and combustion head
To ensure a good ignition, respect the measures in Fig. 67 - Fig. 68.
Single stage burners (mod. LO280-LO400) and Double stage burners (mod. LO280)
A 8 ÷ 10 mm B 4,5 ÷ 6 mm C 10 mm D 6.5 mm
D
Double-stage burners (mod. LO400)
A 8 ÷ 10 mm B 4,5 ÷ 6 mm C8 mm D5 mm
C
C
B
A
Fig. 67
A
D
Check the detection current
See the diagram in Fig. 69 to measure the detection current. If the signa l doesn’t suit the suggested value, verify the electric terminal, the cleaning of the combustion head and the position of the photoelectric cell; replace it if necessary..
Minimum current intensity with flame 45 µA Maximum current intensity without flame 5 µA Maximum possible current intensity with flame
45 µA (LOA..)
100 µA (LMO..)
B
Fig. 68
CN7 CONNECTOR
12
µA DC SCALE
Fig. 69
PART III: MAINTENANCE 31
TROUBLESHOOTING
MAINS SWITCH OPEN
FUSES INTERVENTION
MAXIMUM PRESSURE SWITCH FAULT
INTERVENTION OF THE FAN MOTOR THERMAL CUTOUT
AUXILIARIES RELAY FUSES INTERVEN­TION
FLAME CONTROL DEVICE FAULT
SERVOCONTROL FAULT
SMOKY FLAME
IGNITION TRANSFORMER FAULT
IGNITION ELECTRODE DIRTY OR BAD POSITION
DIRTY NOZZLE
FUEL SOLENOID VALVE DEFECTIVE
PHORESISTANCE DIRTY OR DEFEC­TIVE
HIGH - LOW FLAME THERMOSTAT DEFECTIVE
BAD POSITION OF SERVOCONTROL CAMS
FUEL LOW PRESSURE
START
BURNER DOESN’T
REPETITION OF PRE-
PURGE
NOISY FUEL PUMP
BURNER DOESN’T
START AND LOCKS
LOCKS
BURNER STARTS AND
FLAME
SWITCH TO HIGH
BURNER DOESN’T
BURNER LOCK
DURING OPERATION
REPEATS CYCLE
DURING OPERATION
BURNER LOCKS AND
●●
●● ●●
●●
●●
●●
FUEL FILTERS DIRTY
●●
PART III: MAINTENANCE MANUAL32
WIRING DIAGRAMS
Wiring diagram 04-743 - LO280 Single stage burners
PART III: MAINTENANCE MANUAL 33
PART III: MAINTENANCE MANUAL34
Wiring diagram 18-116 - LO280 Double stage burners
PART III: MAINTENANCE MANUAL 35
PART III: MAINTENANCE MANUAL36
WIRING DIAGRAMS - Complete key - mod. LO400
C1 LOW FLAME TIME METER C2 HIGH FLAME TIME METER EVG LIGHT OIL ELECTRO-VALVE FR PHOTORESISTOR FLAME DETECTOR FU1 FAN MOTOR LINE FUSE FU2 LINE FUSE FU3 BURNER LINE FUSE IL BURNER LINE SWITCH IM FAN MOTOR LINE SWITCH KA2.3 AUXILIARY RELAY KA2.4 AUXILIARY RELAY KM1.1 FAN MOTOR CONTACTOR KT2.4 DELAYED RELAY LAF BURNER IN HIGH FLAME INDICATOR LIGHT LANDIS LOA24/44 - LMO 24/44FLAME MONITOR DEVICE LB INDICATOR LIGHT FOR BURNER LOCK-OUT LBF BURNER IN LOW FLAME INDICATOR LIGHT LEVG1 INDICATOR LIGHT FOR OPENING OF ELECTRO-VALVE [EVG1] LTA IGNITION TRANSFORMER INDICATOR LIGHT MV FAN MOTOR PS LOCK-OUT RESET BUTTON (WITH LOA44 AND LMO.. ONLY) SATRONIC DKO976 - DKW976FLAME MONITOR DEVICE SATRONIC DKW972 FLAME MONITOR DEVICE SATRONIC TF976 FLAME MONITOR DEVICE ST SERIES OF THERMOSTATS OR PRESSURE SWITCHES SW1 II° STAGE BURNER START BUTTON TA IGNITION TRANSFORMER TAB HIGH-LOW THERMOSTAT/PRESSURE SWITCHES TS SAFETY THERMOSTAT OR PRESSURE SWITCH
($) IF "TAB" USED REMOVE THE BRIDGE BETWEEN TERMINALS T6-T8
SERVOCONTROL CAMS
IHIGH FLAME II STAND-BY, IGNITION, LOW FLAME III EVG2 OPENING
WARNING
1 - Electrical supply 230V 50/60Hz 2N a.c. 2 - Do not reverse phase with neutral 3 - Ensure burner is properly earthed
PART III: MAINTENANCE MANUAL 37
Wiring diagram 18-049 - LO400 Single stage burners
PART III: MAINTENANCE MANUAL38
Single stage burners 18-049 - LO400 Double-stage burners
PART III: MAINTENANCE MANUAL 39
Connectors layout on printed board
PART III: MAINTENANCE MANUAL40
SPARE PARTS
DESCRIPTION CODE
LO280 Single stage LO280 Doulbe stage LO400 Single stage LO400 Doulbe stage
LOA24 CONTROL BOX 2020445 2020445 2020445 2020445
ELECTRIC MOTOR 2180717 2180717 2180714 2180714
IGNITION TRANSFORMER 2170231 2170231 2170231 2170231
PUMP 2590130 2590152 2590170 2590170
IGNITION CABLES 6050153 6050153 6050153 6050153
IGNITION ELECTRODES 2080283 2080283 2080259 2080259+2080260
COMBUSTION HEAD 30601C5 30601C5 30601A1 30601A0
FUEL FILTER 2090027 2090027 2090025 2090025
SERVOCONTROL - 2480057 - 2480057
FAN 2150071 2150071 2150060 2150060
BLAST TUBE
NOZZLE HOLDER
Standard: 30900L3
Long: 30900L4
Standard: 30200F1
Long: 30200F2
PHOTORESISTOR 2510034 2510033 2510033 2510033
NOZZLES 261... 261... 261... 261...
Flexible hoses 234Fx22 234Fx22 2340001 2340001
GASKET 2110059 2110059 2110059 2110059
BOARDPRINTED CIRCUIT - 6100547 6100542 6100542
EVG2 ELECTRO-VALVE - - - 2190638
MOTOR-PUMP COUPLING 2540055 2540055 2540055 2540055
EVG1 COIL 2580402 2580402 2580402 2580402
EVG2 COIL - 2580402 - -
Standard: 30900L3
Long: 30900L4
Standard30200F1
Long: 30200F2
30900G2 30900G2
2850090 2850089
PART III: MAINTENANCE MANUAL 41
PART III: MAINTENANCE MANUAL42
APPENDIX - COMPONENTS SPECIFICATIONS
LANDIS OIL BURNERS AUTOMATIC CONTROLLER LOA24
Use
LOA... safety devices are intended for use solely with QRB... photore­sistors, for lighting and controlling low capacity forced air light oil bur­ners with max. capacity 30 kg/h in accordance with standard DIN
4787. The One or two flamess are lit through electrical connections with or
without post-ignition.
To replace LAl... AND LAB.. WITH LOA...
LOA... models can be used as replacement for LAl... and LAB.. con­trollers by means of the adapter KF8819 and without the need to change the electrical wiring. Because the LOA is smaller in dimen­sions, when it is used with the adapter the external dimensions are almost identical, which means that there is no need to move the reset button.
Performance
The controllers just need plugging in, so they can be mounted in almost any position: on the burner, on the electrical panel or on the control panel. The casing is made of robust heat-resistant plastic and contains:
z the thermic programmer operating a multiple switch control system
with ambient temperature compensator
z flame signal amplifier with flame relay z warning light indicating lockout and associated sealed reset but-
ton.
The plug-in socket, also made of robust heat-resistant plastic, con­tains the 12 terminals and also:
z 3 neutral terminals, ready wired up to terminal 2 z 4 earth terminals for earthing the burner z 2 supplementary terminals numbered “31” and “32”.
The socket has two openings at the bottom for the leads; 5 others with threaded connection for cable holders PG11 or 3/4UNP for non­metallic sleeves are located on a mobile stuffing box, one on either side and 3 on the front.
There are two flexible metal tongues on the sides of the socket for mounting.
To dismantle it only requires gentle pressure with a screw driver in the slot of the mounting guide. The base dimensions of the socket are exaclty the same as for types LAB/LAI and there is no difference in the diameter of the reset button, the two mounting screws and the flange of the burner earth.
Safety at low voltage levels
Safety devices against any reduction in the mains voltage operate on a special electronic circuit which, in the event of the power supply fal­ling below 165V~, stops the burner switching on without releasing the fuel and locks out the apparatus.
Wiring diagram of the programme
To ensure correct wiring it is essential to observe local standards and follow the instructions of the burner manufacturer with regard to assembly and start-up.
Program's legend:
Controller output signals Required input signals
A’ Burner start up with light oil pre-heater OH A Burner start-up without light oil pre-heater BFlame lit C Normal operation D Normal stop through R tw Oil pre-heating time until operational all clear given through
contact OW tl Pre-purge time t3 Pre-ignition time t2 Safety time t3n Post-ignition time t4 Interval between the flame lighting and energising of solenoid
2a at terminal 5
Internal layout
AL Optical alarm BV. Fuel valve EK Reset button FR Flame relay fr Flame relay contacts FS Flame alight signal G Burner motor K Flame relay anchor to delay the tzl command in the event of a
premature flame signal or endorse it where the signal is
correct. OH light oil pre-heater OW Operational all-clear contact QRB Photo-resistant cell (flame detector) R Thermostat or pressure switch TZ Thermo-electric programmer (bimetal system) tz.. TZ contacts V Flame signal amplifier W Safety thermostat or pressure switch Z Ignition transformer
The above are safety devices!
To tamper with them in any way may have unforeseeable conse­quences!
Do not open them!
APPENDIX - COMPONENTS SPECIFICATIONS 43
Technical characteristics
Voltage 220V -15%..240V+10% or
100V -15%...110V+10% Frequency 50...60Hz +/- 6% External fuse max.10A slow action Contact flow:
- terminal 1 5A
- terminal 3 5A (incl.capacity absorbed by motor
and pre-heater) Terminal flow: terminals 4, 5 &10 1A terminals 6&7 2A terminal 8 5A Absorbed cap 3VA Protection IP40 Premitted temp: operational -20...+60°C transport & storage -50...+60°C Emplacement any Mass (weight) controller 180g, socket 50g,
AGK accessories 12 g.
Commands in the event of operational interference
Stray light/premature ignition
During pre-purge and/or pre-ignition there should be no flamesignal. If there is a flame signal, eg from premature ignition due to a faulty sole­noid, external light, short circuit in the photoresisto or wiring, malfunc­tion in the flame signal amplifier, etc., at the end of pre-purge and safety time the controller locks out the burner and stops the fuel flow even during safety time.
Absence of flame
If there is no flame at the end of safety time the controller locks out immediately.
Absence of flame during operation
If there is no flame during operation the controller cuts off the supply of fuel and automatically initiates a fresh start-up programme: at the end of t4 the start-up programme ends.
Whenever there is a safety stop, terminals 3-8 and 11 are de-energi­sed in less than 1 second; at the same time a remote lockout signal is transmitted through terminal 10. The controller can be reset after c. 50 seconds.
APPENDIX - COMPONENTS SPECIFICATIONS44
LANDIS OIL BURNERS AUTOMATIC CONTROLLER LOA44 OPERATION
Burners without fuel pre-heater
Start-up, thermostat and pressure switches R, burner motor G and ignition transformer Z are all controlled at the same time.
After about 25 seconds the solenoid is energised (in this period the flame amplifier is at maximum sensitivity). The command to the first solenoid BV1 marks the start of the safety time during which, either there is no flame in the burner and the controller locks it out, or after 5 seconds the stage 2 solenoid BV2 is energised and this ends the bur­ner start-up programme.
Burners with fuel pre-heater
(Operational all-clear from contact OW which short circuits terminals 3 and 8). The burner start-up programme is exactly the same as above except that it is initiated by the closing of the OW contact of the preheater OH.
When the flame lights the flame relay contact (fr2) is short circuited and should the contact OW open that does not cause a lockout but a repetition of the cycle.
Commands in the event of operational interference Premature ignition / Flame present during pre-purge: Lockout and
termination of pre-purge
Defective components in controller or electronic programmer:
Lockout
No flame signal at the end of safety time: Lockout No flame during post-ignition: Lockout No flame during normal operation: Repetition of start-up pro-
gramme Power cut during start-up programme or operation: Automatic
repetition of programme when power restored. Lack of sufficient power (~160V): Solenoid BV1 de-energised, sole-
noid BV2 de-energised when flame goes out Lockout which occurs within less than 1 second, cuts off power to ter-
minals 3-8 and 12; terminal 10 still remains live in order to activate the optical lockout indicator. The controller can be reset 2 seconds after a lockout.
Important: when external wiring is replaced ensure that it is switched on at the same phase of terminal 2 (so that terminal 9 is connected up to neutral).
Electrical connections and programmer's layout
A’ burner start-up B Flame signal with oil pre-heater present C End of programme-start of normal operation A burner start-up C-D normal operation without oil pre- heater D normal stop
Programme or command cycle
tw fuel pre-heating time acc. to system tl pre-purge time, ~25secs. t3 pre-ignition time, ~25secs. t2 safety time max.5 secs. t3n post-ignition time, ~2 secs. t4 interval between BV1 and BV2 commands, ~5 secs* - lockout
from absence of flame, <1 sec. * In relation to the moment when the flame occurs.
Key - Internal diagram
AL alarm device AR main relay with contacts BV.. fuel valve BR lockout relay EK.. lockout reset button FS flame signal M burner motor HR auxiliary relay with contacts hr OH oil pre-heater OW release contact of oil pre-heater QRB photoresistive detector R control pressostat or pressure switch V flame signal amplifer W limit thermostat or pressure switch Z ignition transformer
APPENDIX - COMPONENTS SPECIFICATIONS 45
Technical characteristics
Voltage 220V-15%..240V+10% or
Frequency 50...60Hz _6% External fuse max.10 A, slow action Contact flow: terminal 1 max. 5A terminal 3 5A (incl. consumed cap. of motor and
terminals 4,5& 6 max.2A terminal 8 max. 5A terminal 10 max.1A Permitted temperature operation -20...+60°C storage and transport -50...+40°C Protection IP40 Mass (weight) controller/socket 140g/80g, AGK accessories ~12g
Key to internal diagram
AL Remote optical lockout indicator AR Main relay with contacts ar... BV.. Fuel solenoid BR Lockout relay with contacts br.. EK Reset button FR Flame relay with contacts fr... FS Flame present signal G Burner motor HR Auxiliary relay with contacts hr.. L Lockout LED incorporated in the reset button OH Fuel pre-heater OW All-clear contact for pre-heater QRB Photo resistor (flame detector) R Normal thermostat or pressure switch V Flame signal amplifier W Safety thermostat or pressure switch Z Safety transformer
100V-15%..110V+10%
pre-heater)
Internal diagram
APPENDIX - COMPONENTS SPECIFICATIONS46
APPENDIX - COMPONENTS SPECIFICATIONS 47
Loading...