THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE
USER.
INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
THE USER WILL FIND FURTHER INFORMATION ABOUT OPERATING AND USE RESTRICTIONS, IN THE SECOND SECTION
OF THIS MANUAL. WE HIGHLY RECOMMEND TO READ IT.
CAREFULLY KEEP THIS MANUAL FOR FUTURE REFERENCE.
1)GENERAL INTRODUCTION
zThe equipment must be installed in compliance with the regulations
in force, following the manufacturer’s instructions, by qualified personnel.
zQualified personnel means those having technical knowledge in the
field of components for civil or industrial heating systems, sanitary
hot water generation and particularly service centres authorised by
the manufacturer.
zImproper installation may cause injury to people and animals, or
damage to property, for which the manufacturer cannot be held liable.
zRemove all packaging material and inspect the equipment for inte-
grity.
In case of any doubt, do not use the unit - contact the supplier.
The packaging materials (wooden crate, nails, fastening devices, plastic
bags, foamed polystyrene, etc), should not be left within the reach of children, as they may prove harmful.
zBefore any cleaning or servicing operation, disconnect the unit from
the mains by turning the master switch OFF, and/or through the cut-
out devices that are provided.
zMake sure that inlet or exhaust grilles are unobstructed.
zIn case of breakdown and/or defective unit operation, disconnect the
unit. Make no attempt to repair the unit or take any direct action.
Contact qualified personnel only.
Units shall be repaired exclusively by a servicing centre, duly authorised
by the manufacturer, with original spare parts.
Failure to comply with the above instructions is likely to impair the unit’s
safety.
To ensure equipment efficiency and proper operation, it is essential that
maintenance operations are performed by qualified personnel at regular
intervals, following the manufacturer’s instructions.
zWhen a decision is made to discontinue the use of the equipment,
those parts likely to constitute sources of danger shall be made har-
mless.
zIn case the equipment is to be sold or transferred to another user, or
in case the original user should move and leave the unit behind,
make sure that these instructions accompany the equipment at all
times so that they can be consulted by the new owner and/or the
installer.
zFor all the units that have been modified or have options fitted then
original accessory equipment only shall be used.
zThis unit shall be employed exclusively for the use for which it is
meant. Any other use shall be considered as improper and, there-
fore, dangerous.
The manufacturer shall not be held liable, by agreement or otherwise, for
damages resulting from improper installation, use and failure to comply
with the instructions supplied by the manufacturer.
2)SPECIAL INSTRUCTIONS FOR BURNERS
zThe burner should be installed in a suitable room, with ventilation
openings complying with the requirements of the regulations in force,
and sufficient for good combustion.
zOnly burners designed according to the regulations in force should
be used.
zThis burner should be employed exclusively for the use for which it
was designed.
zBefore connecting the burner, make sure that the unit rating is the
same as delivery mains (electricity, gas oil,
zObserve caution w
near to the flame and the fuel pre-heating system, they become hot
during the unit operation and will remain hot for some time after the
burner has stopped.
When the decision is made to discontinue the use of the burner, the user
ith hot burner components. These are, usually,
or other fuel).
shall have qualified personnel carry out the following operations:
aRemove the power supply by disconnecting the power cord from the
mains.
b) Disconnect the fuel supply by means of the hand-operated shut-off
valve and remove the control handwheels from their spindles.
Special warnings
zMake sure that the burner has, on installation, been firmly secured to
the appliance, so that the flame is generated inside the appliance
firebox.
zBefore the burner is started and, thereafter, at least once a year,
have qualified personnel perform the following operations:
aset the burner fuel flow rate depending on the heat input of the
appliance;
bset the flow rate of the combustion-supporting air to obtain a combu-
stion efficiency level at least equal to the lower level required by the
regulations in force;
ccheck the unit operation for proper combustion, to avoid any harmful
or polluting unburnt gases in excess of the limits permitted by the
regulations in force;
dmake sure that control and safety devices are operating properly;
emake sure that exhaust ducts intended to discharge the products of
combustion are operating properly;
fon completion of setting and adjustment operations, make sure that
all mechanical locking devices of controls have been duly tightened;
gmake sure that a copy of the burner use and maintenance instruc-
tions is available in the boiler room.
zIn case of a burner shut-down, reser the control box by means of the
RESET pushbutton. If a second shut-down takes place, call the
Technical Service, without trying to RESET further.
zThe unit shall be operated and serviced by qualified personnel only,
in compliance with the regulations in force.
3)GENERAL INSTRUCTIONS DEPENDING ON FUEL USED
3a) ELECTRICAL CONNECTION
zFor safety reasons the unit must be efficiently earthed and installed
as required by current safety regulations.
zIt is vital that all saftey requirements are met. In case of any doubt,
ask for an accurate inspection of electrics by qualified personnel,
since the manufacturer cannot be held liable for damages that may
be caused by failure to correctly earth the equipment.
zQualified personnel must inspect the system to make sure that it is
adequate to take the maximum power used by the equipment shown
on the equipment rating plate. In particular, make sure that the
system cable cross section is adequate for the power absorbed by
the unit.
zNo adaptors, multiple outlet sockets and/or extension cables are per-
mitted to connect the unit to the electric mains.
zAn omnipolar switch shall be provided for connection to mains, as
required by the current safety regulations.
zThe use of any power-operated component implies observance of a
few basic rules, for example:
- do not touch the unit with wet or damp parts of the body and/or with
bare feet;
- do not pull electric cables;
- do not leave the equipment exposed to weather (rain, sun, etc.)
unless expressly required to do so;
- do not allow children or inexperienced persons to use equipment;
zThe unit input cable shall not be replaced by the user.
In case of damage to the cable, switch off the unit and contact qualified
personnel to replace.
When the unit is out of use for some time the electric switch supplying all
the power-driven components in the system (i.e. pumps, burner, etc.)
should be switched off.
2
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS
GENERAL
zThe burner shall be installed by qualified personnel and in com-
pliance with regulations and provisions in force; wrong installation
can cause injuries to people and animals, or damage to property, for
which the manufacturer cannot be held liable.
zBefore installation, it is recommended that all the fuel supply system
pipes be carefully cleaned inside, to remove foreign matter that might
impair the burner operation.
zBefore the burner is commissioned, qualified personnel should ins-
pect the following:
athe fuel supply system, for proper sealing;
bthe fuel flow rate, to make sure that it has been set based on the
firing rate required of the burner;
cthe burner firing system, to make sure that it is supplied for the desi-
gned fuel type;
dthe fuel supply pressure, to make sure that it is included in the range
shown on the rating plate;
ethe fuel supply system, to make sure that the system dimensions are
adequate to the burner firing rate, and that the system is equipped
with all the safety and control devices required by the regulations in
force.
zWhen the burner is to remain idle for some time, the fuel supply tap
or taps should be closed.
SPECIAL INSTRUCTIONS FOR USING GAS
Have qualified personnel inspect the installation to ensure that:
athe gas delivery line and train are in compliance with the regulations
and provisions in force;
ball gas connections are tight;
cthe boiler room ventilation openings are such that they ensure the air
supply flow required by the current regulations, and in any case are
sufficient for proper combustion.
zDo not use gas pipes to earth electrical equipment.
zNever leave the burner connected when not in use. Always shut the
gas valve off.
zIn case of prolonged absence of the user, the main gas delivery
valve to the burner should be shut off.
Precautions if you can smell gas
ado not operate electric switches, the telephone, or any other item
likely to generate sparks;
bimmediately open doors and windows to create an air flow to purge
the room;
cclose the gas valves;
dcontact qualified personnel.
zDo not obstruct the ventilation openings of the room where gas
appliances are installed, to avoid dangerous conditions such as the
development of toxic or explosive mixtures.
DIRECTIVES AND STANDARDS
Gas burners
European directives:
- Directive 90/396/CEE - Gas Appliances;
- Directive 2006/95/EC on low voltage;
- Directive 2004/108/CEE on electromagnetic compatibility
Harmonised standards :
-UNI EN 676 (Gas Burners;
-CEI EN 60335-1(Household and similar electrical appliances - Safety.
Part 1: General requirements;
- EN 50165 (Electrical equipment of non-electric appliances for household and similar purposes. Safety requirements.
Light oil burners
European directives:
- Directive 2006/95/EC on low voltage;
-
Directive 2004/108/
Harmonised standards :
-CEI EN 60335-1(Household and similar electrical appliances - Safety.
Part 1: General requirements;
- EN 50165 (Electrical equipment of non-electric appliances for household and similar purposes. Safety requirements.
National standards :
-UNI 7824: Monobloc nebulizer burners for liquid fuels. Characteristics
and test methods
European directives:
- Directive 2006/95/EC on low voltage;
- Directive 2004/108/CEE on electromagnetic compatibility
Harmonised standards :
-CEI EN 60335-1 Household and similar electrical appliances - SafetyPart
1: General requirements;
- EN 50165 Electrical equipment of non-electric appliances for household
and similar purposes. Safety requirements.
National standards :
-UNI 7824: Monobloc nebulizer burners for liquid fuels. Characteristics
and test methods
European directives:
- Directive 90/396/CEE Gas Appliances;
- Directive 2006/95/EC on low voltage;
- Directive 2004/108/CEE on electromagnetic compatibility
Harmonised standards :
-UNI EN 676 Gas Burners
-CEI EN 60335-1(Household and similar electrical appliances - Safety.
Part 1: General requirements;
- EN 50165 Electrical equipment of non-electric appliances for household
and similar purposes. Safety requirements.
National standards :
-UNI 7824: Monobloc nebulizer burners for liquid fuels. Characteristics
and test methods
European directives:
- Directive 90/396/CEE - Gas Appliances;
- Directive 2006/95/EC on low voltage;
- Directive 2004/108/CEE on electromagnetic compatibility
Harmonised standards :
-UNI EN 676 (Gas Burners;
-CEI EN 60335-1(Household and similar electrical appliances - Safety.
Part 1: General requirements;
- EN 50165 Electrical equipment of non-electric appliances for household
and similar purposes. Safety requirements.
National standards :
-UNI 7824: Monobloc nebulizer burners for liquid fuels. Characteristics
and test methods
CEE on elec
Gas - Light oil burners
Gas - Heavy oil burners
tromagnetic compatibility
Heavy oil burners
3
C.I.B. UNIGAS - M03957CI
PART I: INSTALLATION
9
5
7
6
4
3
2
1
8
10
GENERAL FEATURES
This series represents monobloc gas burners made in die-cast aluminium housing, that can burn either gas or light oil, thanks to the
adjustable combustion head which allows a good performance with both fuels. They can be provided in progressive or fully-modulating
version.
Fig. 1
1Mimic panel with startup switch
2Gas proving system
3Gas valve group
4Burner flange
5Blast tube-Combustion head ass.y
6Cover
7Light oil pump
8Pump motor
9Gas adjusting cam
10 Actuator
Gas operation: the gas coming from the supply line, passes through the valves group provided with filter and stabiliser. This one forces the pressure in the utilisation limits. The actuator (10) moves proportionally the air damper and the gas butterfly valve It drives an
adjusting cam (13) with variable shape. This one allows the optimisation of the gas flue values, as to get an efficient combustion.
Light oil operation:the fuel coming from the supply line, is pushed by the pump (8) to the nozzle and then into the combustion chamber, where the mixture between fuel and air takes place and consequently the flame.
In the burners, the mixture bertween fuel and air, to perform clean and efficient combustion, is activated by atomisation of oil into very
small particles. This process is achieved making pressurised oil passing through the nozzle.
The pump (8) main function is to transfer oil from the tank to the nozzle in the desired quantity and pressure. To adjust this pressure,
pumps are provided with a pressure regulator (except for some models for which a separate regulating valve is provided). Other pumps
are provided with two pressure regulators: one for the high and one for low pressure (in double-stage systems with one nozzle).
The adjustable combustion head can improve the burner performance. The combustion head (5) determines the energetic quality and
the geometry of the flame. Fuel and comburent are routed into separated ways as far as the zone of flame generation (combustion
chamber). The control panel (1), placed on the burner front side, shows each operating stage.
How to interpret the burner “Performance curve”
To check if the burner is suitable for the boiler to which it must be installled, the following parameters are needed:
zfurnace input, in kW or kcal/h (kW = kcal/h / 860);
zbackpressure (data are available on the boiler’s ID plate or in the user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4mbar
In the “Performance curve” diagram (Fig. 2), draw a vertical line matching the furnace input value and an horizontal line matching the
backpressure value. The burner is suitable if the intersection point A is inside the performance curve.
4
C.I.B. UNIGAS - M03957CI
()
0
5
10
15
20
25
100200300400500600700800900
Potenza / Output (kW)
Minima pressione gas in
rete / Minimum inlet gas
pressure (mbar)
Rp 2" (50)
DN65
Camp o di lav o ro bruciat o ri
TipoP60 Mod. M-xx.x.IT.A.0.50 -M-.xx.x.IT.A.0.65
8
7
6
5
4
3
2
1
combustione mbar
0
Contropressione in camera di
-1
100200300400500600700800900
A
Pote nza kW
Fig. 2
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15°C
Checking the proper gas train size
To check the proper gas train size, it is necessary to know the available gas pressure value upstream the burner’s gas valve. Then
subtract the backpressure. The result is called p
quoted on the x-axis, as far as intercepitng the network pressure curve, according to the installed gas train (DN65, in the example).
From the interception point, draw an horizontal line as far as matching, on the y-axis, the value of pressure necessary to get the requested furnace input. This value must be lower or equal to the p
gas. Draw a vertical line matching the furnace input value (600kW, in the example),
gas value, calculated before.
Fig. 3
Matching the burner to the boiler
The burners described in this manual have been tested with combustion chambers that comply with EN676 regulation and whose
dimensions are described in the diagram . In case the burner must be coupled with boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram, please contact the supplier, to verify that a correct matching is possible, with respect of the application involved. To correctly match the burner to the boiler verify the necessary input and the pressure in combustion
chamber are included in the burner performance curve; otherwise the choice of the burner must be revised consulting the burner manufacturer. To choose the blast tube lenght follow the instructions of the boiler manufacturer. In absence of these consider the following:
z Cast-iron boilers, three pass flue boilers (with the first pass in the rear part): the blast tube must protrude no more than 100 mm into
the combustion chamber.
z Pressurised boilers with flame reversal: in this case the blast tube must penetrate at least 50 - 100 mm into combustion chamber in
respect to the tube bundle plate.
z The length of the blast tubes does not always allow this requirement to be met, and thus it may be necessary to use a suitably-
spacer to move the burner backwards or to design a blast tube tha suites the utilisation (please, contact the manifacturer).
Key
a) Heat output in kW
b) Lenght of the flame tube in meters
c) Flame tube firing intensity in MW/m
3
d) Combustion chamber diameter (m)
Fig. 4 - Firing intensity, diameter and lenght of the test flame tube as a function of the heat
input in kW.
Fig. 4
sized
5
C.I.B. UNIGAS - M03957CI
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Type HP60 Model MG. PR. S. *. A. 1. 50
(1) (2) (3) (4) (5) (6) (7) (8)
(1) BURNER TYPEHP60
(2) FUELM - Natural gas G - Light oil
(4) BLAST TUBES - Standard L - Extended
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSIONA - Standard
Y - Speciale
(7) EQUIPMENT 0 = 2 gas valves
1 = 2 gas valves + gas proving system
7 = 2 gas valves + maximum gas pressure switch
8 = 2 gas valves + gas proving system + maximum gas pressure switch
(8) GAS CONNECTION
see Specifications
40 = Rp1
50 = Rp2
1/2
65 = DN65 80 = DN80
Specifications
BURNER TYPEHP60...0.40HP60...0.50HP60...0.65
Outputmin. - max. kW
Fuel
Gas category(see next paragraph)
Gas rate
Gas pressure
Oil train inlet pressure
Light oil rate
min. - max. (Stm
min. - max. mbar
max. bar
min. - max.kg/h14 - 4414 - 7414 - 74
3
/h)
Oil viscosity 2 - 7.4 cSt @ 40°C
Oil density 840 kg/m3
Power supply230V 3~ / 400V 3N ~ 50Hz
Total power consumption
Fan motor
Pump motor
kW2.15
kW1.1
kW0.55
Protection
Approx. weight
kg657080
Operation
Gas Train
Valves size / Gas connection
Operating temperature°C
Storage Temperature°C
Working service*
170 - 523170 - 880170 - 880
Natural gas - Light oil
18 - 5518 - 9318 - 93
(see Note 2)
1
IP40
Progressive - Fully modulating
405065
/ Rp1
1”
1/2
1/2
2” / Rp2
-10 ÷ +50
-20 ÷ +60
Intermittent
2”
/ DN65
1/2
* NOTE ON THE BURNER WORKING SERVICE: for safety reasons, one controlled shutdown must be performed every 24 hours of
continuous operation.
Country and usefulness gas categories
GAS
CATEGORY
I
2H
I
2E
I
2E( R ) B
I
2L
I
2ELL
I
2Er
AT ES GR SE FIIE HU IS NO CZ DK GB ITPT CY EE LVSI MT SK BG LT RO TR CH
LUPL-----------------------
BE------------------------
NL------------------------
DE------------------------
FR------------------------
COUNTRY
6
C.I.B. UNIGAS - M03957CI
BURNER TYPEHP65...0.50HP65...0.65
Outputmin. - max. kW
Fuel
270 - 970
Nat. gas - Light oil
Gas category(see next paragraph)
Gas rate
Gas pressure
Oil train inlet pressure
Light oil rate
min. - max. kW (Stm3/h)
min. - max. mbar
max. bar
min.- max.kg/h23 - 82
29 - 103
(see Note 2)
1
Oil viscosity 2 - 7.4 cSt @40°C
Oil density 840 kg/m3
Power supply230V 3~ / 400V 3N ~ 50Hz
Total power consumption
Fa motor
Pump motor
Protection
Approx. weight
Operation
Gas Train
Valves size / Gas connection
Operating temperature°C
Storage Temperature°C
Working service*
kW2.6
kW1.5
kW0.55
IP40
kg105115
Progressive - Fully modulating
5065
2” / Rp2
2”
1/2
-10 ÷ +50
-20 ÷ +60
Intermittent
/ DN65
BURNER TYPEHP72...0.50HP72...0.65HP72...0.80
Outputmin. - max. kW
Fuel
330 - 1200
Nat. gas - Light oil
Gas category(see next paragraph)
Gas rate
Gas pressure
Oil train inlet pressure
Light oil rate
3
min.- max. (Stm
/h)
min. - max. mbar(see Note 2)
max. bar
min.- max. kg/h28 - 101
35 - 127
1
Oil viscosity 2 - 7.4 cSt @40°C
Oil density 0.84 kg/m3
Power supply230V 3~ / 400V 3N ~ 50Hz
Total power consumption
Fan motor
Pump motor
Protection
Approx. weight
Operation
Gas Train
Valves size / Gas connection
Operating temperature°C
Storage Temperature°C
Working service*
kW3.25
kW2.2
kW0.55
IP40
kg110120130
Progressive - Fully modulating
506580
/ DN65
2” / Rp2
2”
1/2
-10 ÷ +50
-20 ÷ +60
Intermittent
3” / DN80
* NOTE ON THE BURNER WORKING SERVICE: for safety reasons, one controlled shutdown must be performed every 24 hours of
continuous operation.
7
C.I.B. UNIGAS - M03957CI
BURNER TYPEHP72...1.50HP72...1.65HP72...1.80
Outputmin. - max. kW
Fuel
330 - 1550
Nat. gas - Light oil
Gas category(see next paragraph)
Gas rate
Gas pressure
Oil train inlet pressure
Light oil rate
min. - max. (Stm
3
/h)
min.- max. mbar(see Note 2)
max. bar
min.- max. kg/h28 - 131
35 - 164
1
Oil viscosity 2 - 7.4 cSt @40°C
Oil density 840 kg/m3
Power supply230V 3~ / 400V 3N ~ 50Hz
Total power consumption
Fan motor
Pump motor
Protection
Approx. weight
Operation
Gas Train
Valves size / Gas connection
Operating temperature°C
Storage Temperature°C
Working service*
it is recommended to fit a counterflange between burner and boiler. As an alternative, make a smaller hole H, but greather than Y and fit the blast tube from the internal side of boiler.
Performance Curves
-2
-1
0
1
2
3
4
5
6
7
8
100200300400500600
-2
-1
0
1
2
3
4
5
6
7
8
10020030040050060 0700800900
0
1
2
3
4
5
6
7
8
9
2003004005006007008009001000
-2
0
2
4
6
8
10
12
14
0200400600800100012001400
-2
0
2
4
6
8
10
12
200 400 600 800 1000 1200 1400 1600 1800
0
2
4
6
8
10
12
05001000150020002500
HP60 MG.xx.x.xx.A.0.40
BACK PRESSURE IN
C.I.B. UNIGAS - M03957CI
HP60 MG....50/65
COMBUSTION CHAMBER mbar
HP65 MG....50/65
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
HP72 MG.....1...
kW
HP72 MG.....0...
kW
HP73A ..1...
kW
kW
BACK PRESSURE IN
COMBUSTION CHAMBER mbar
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15°C
NOTE: The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory
tests, but does not represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adjsuting the combustion head to its “MAX” position (see paragraph “Adjusting the combustion head”); the minimum output point is reached setting the combustion head to its “MIN” position. During the first ignition, the combustion head is set in order to find a
compromise between the burner output and the generator specifications, that is why the minimum output may be different from the Performance curve minimum.
kW
kW
11
Pressure in the network - gas rate curves
0
5
10
15
20
25
102030405060708090
DN50
DN65
DN40
0
5
10
15
20
25
30
20 304050 607080 90 100 110 120
DN50
DN65
Rp2(50)
0
10
20
30
40
20406080100120140
DN50
DN65
DN80
0
10
20
30
40
50
60
70
20406080100120140160180
Rp 2" (50)
DN65
DN80
0
25
50
75
100
125
050100150200250
Rp 2" (50)
HP60
GAS PRESSURE IN
THE NETWORK mbar
Gas rate Stm
HP72...0.xx
C.I.B. UNIGAS - M03957CI
HP65
3
/h
HP72...1.xx
Gas rate Stm3/h
GAS PRESSURE IN
THE NETWORK mbar
HP73A
GAS PRESSURE IN
THE NETWORK mbar
Caution: the gas rate value is quoted on the x-axis, the related network pressure is quoted on the y-axis (pressure value in
the combustion chamber is not included). To know the minimum pressure at the gas train inlet, necessary to get the requested gas rate, add the pressure value in the combustion chamber to the value read on the y-axis.
Burners are despatched in cardboard packages and whose dimensions: 1280mm x 850mm x 760mm (L x P x H)
Packing cases of this kind are affected by humidity and are not suitable for stacking. The following are placed in
each packing case:
zburner with gas train detached;
zgasket to be inserted between the burner and the boiler;
zflexible oil pipes;
zoil filter;
zenvelope containing this manual
To get rid of the burner’s packing, follow the procedures laid down by current laws on disposal of materials
Handling the burner
ATTENTION! The lhandling operations must be carried out by specialised and trained personnel. If these operations are not carried out correctly, the residual risk for the burner to overturn and fall down still persists.
To move the burner, use means suitable to support its weight (see paragraph “Technical specifications”).
The unpacked burner must be lifted and moved only by means of a fork lift truck.
The burner is mounted on a stirrup provided for handling the burner by means of a fork lift truck: the forks must be inserted into the A
anb B ways. Remove the stirrup only once the burner is installed to the boiler.
Fitting the burner to the boiler
To install the burner into the boiler, proceed as follows:
1make a hole on the closing door of the combustion chamber as described on paragraph “Overall dimensions”)
2place the burner to the boiler: lift it up and handle it according to the procedure described on paragraph “Handling the burner”;
3place the 4 stud bolts (5) on boiler’s door, according to the burner’s drilling template described on paragraph “Overall dimensions”;
4fasten the 4 stud bolts;
5place the gasket on the burner flange;
6install the burner into the boiler;
7fix the burner to the stud bolts, by means of the fixing nuts, according to the next picture.
8After fitting the burner to the boiler, ensure that the gap between the blast tube and the refractory lining is sealed with appropriate
insulating material (ceramic fibre cord or refractory cement).
The burner is designed to work positioned according to the picture below. For different installations, please contact the Technical
Department.
13
C.I.B. UNIGAS - M03957CI
1
2
3
4
5
78
9
4
MANUFACTURER
INSTALLER
1
2
54
6
78
10
4
MANUFACTURER
INSTALLER
1
2
3
4
5
78
18
4
MANUFACTURER
INSTALLER
1
2
3
4
78
5
6
19
4
MANUFACTURER
INSTALLER
Gas train connections
The next diagrams show the components of the gas train included in the delivery and which must be fitted by the installer.The diagrams
are in compliance with the current laws.
ATTENTION: BEFORE EXECUTING THE CONNECTIONS TO THE GAS PIPE NETWORK, BE SURE THAT THE
MANUAL CUTOFF VALVES ARE CLOSED. READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNING
OF THIS MANUAL.
Gas train - 1 Gas train with valves group MB-DLE with built-in gas pressure governor + VPS504 gas proving system
Gas train - 2
Gas train - 3
Gas train - 4 Gas train with valves group MBC 1900/3100/5000SE (2 valves + gas filter + pressure governor) + VPS504 gas proving
Gas train with valves group VGD 20/40.. with built-in gas pressure governor + VPS504 gas proving system
Gas train with valves group MBC 1200SE (2 valves + gas filter + pressure governor) + VPS504 gas proving system
system
Key
1Burner
2Butterfly valve
3Gas proving system (option)
4Maximum gas pressure switch (option*)
5Minimum gas pressure switch
8Manual cutoff valve
9MB-DLE Valves group
10VGD Valves group
18MBC Valves group (2” with filter provided)
19MBC Valves group (DN65/80/100)
6Gas filter
7Bellow joint
*Note: the high gas pressure switch can be mounted either upstream the gas valve or downstream the gas valves but upstream the butterfly gas valve.
14
C.I.B. UNIGAS - M03957CI
1A
5
1B
4
1C
21D
1E
3
”direction” arrows for installation
gas supply network
Keys
1A..1EGasket
2Gas filter
3Gas valves group
4Bellow joint
5Manual cock
A
B
C
D
C
B
D
A
MOUNTING POSITIONS
Assembling the gas grain
Fig. 5 - Example of gas train
To mount the gas train, proceed as follows:
1-a) in case of threaded joints: use proper seals according to the gas used;
1-b) in case of flanged joints: place a gasket (no. 1A..1E - Fig. 5) between the elements
NOTE: the bellow joint, the manual valve and the gaskets are not part of the standard supply.
ATTENTION: once the gas train is mounted according to the diagram on Fig. 5, the gas proving test mus be performed,
according to the procedure set by the laws in force.
ATTENTION: it is recommended to mount filter and gas valves to avoid that extraneous material drops inside the valves,
during maintenance and cleaning operation of the filters (both the filters outside the valves group and the ones built-in the
gas valves).
The procedures of installation fo the gas valves are showed in the next paragraphs, according to the gas train used:
zthreaded gas trains with Multibloc Dungs MB-DLE, MBC..SE 700 or Siemens VGD20..
zflanged gas trains with Multibloc Dungs MBC..SE 1900-3100-5000 or Siemens VGD40..
MULTIBLOC DUNGS MB-DLE 415..420
Mounting
1. Loosen screws A and B do not unscrew (Fig. 6 - Fig. 7).
2. unscrew screws C and D (Fig. 6 - Fig. 7).
3. Remove MultiBloc between the threaded flanges (Fig. 7).
4. After mounting, perform leakage and functional tests.
4. Tighten setscrews A + B.
Ensure correct seating of the seal!
6. After installation, perform leakage and functional test.
7. Disassembly in reverse order.
Fig. 11
Fig. 12
Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor)
Mounting
zWhen mounting the VGD.. double gas valve, two flanges are required (as for VGD20.. model, the flanges are threaded);
zto prevent cuttings from falling inside the valve, first fit the flanges to the piping and then clean the associated parts;
zinstall the valve;
zthe direction of gas flow must be in accordance with the direction of the arrow on the valve body;
zensure that the bolts on the flanges are properly tightened;
zensure that the connections with all components are tight;
zmake certain that the O-rings and gaskets between the flanges and the double gas valve are fitted.
z
Connect the reference gas pipe (TP in figure), to the gas pressure nipples placed on the gas pipe, downstream the gas valves: gas pressure must be measured at a distance that must be at least 5 times the pipe size .
Leave the blowhole free (SA in figure). Should the spring fitted not permit satisfactory regulation, ask one of our service centres for a
suitable replacement.
Caution: the SKP2 diaphragm D must be vertical (see Fig. 15).
16
C.I.B. UNIGAS - M03957CI
BS
BS
SKP1.SKP2.
BS
BS
SA
TP
D
7631z05/0101
1
2
2
1
WARNING: removing the four screws BS causes the device to be unserviceable!
SIEMENS VGD..MOUNTING
POSITIONS
Fig. 16
Fig. 13
Fig. 14Fig. 15
Pressure adjusting range
The pressure adjusting range, downstream the gas valves group, changes according to the spring provided with the valve group.
DUNGS MBC..SE Siemens SKP actuator
Keys
1 spring
2 cap
DUNGS MBC valves:
Performance range
Spring colour-redblackgreen
Siemens VGD valves with SKP actuator
Performance range (mbar)0 - 2215 - 120100 - 250
Spring colourneutralyellowred
Once the train is installed, connect electrically all its elements: gas valves group, pressure switches, gas proving system.
ATTENTION: once the gas train is mounted according to the diagram on Fig. 5, the gas proving test mus be performed,
according to the procedure set by the laws in force.
(mbar)4 - 2020 - 4040 - 8080 - 150
:
17
C.I.B. UNIGAS - M03957CI
Hydraulic diagrams for light oil supplying circuits