Uniflair UST500 Instruction Manual

UNIFLAIR Instruction manual
UST500 CONTROL BOARD
EN
UST500 CONTROL BOARD
2 06MC0074@00B0100
14/04/2010
UNIFLAIR SpA policy is one of continuous technological innovation. The Company therefore reserves the right to amend any data herein without prior notice.
D
isposal: the product is made up of metal parts and plastic parts.
In reference to European Union directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that:
•••• W EEE cannot b e dispos ed of as munic ipal waste and suc h waste must be collected and disposed of separately;
•••• The public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment.
•••• The equipm ent may contai n hazardous substa nces: the im proper use or incorrect disposal of such may have negative effects on human health and on the environm ent;
•••• The s ymbol (crossed-out wheeled bin) shown on the product or on the packaging and o n the instruction sheet indica tes that the equipment has been introduced onto the m arket after 13 Augus t 2005 and that it must be disposed of separately;
•••• In the event of illegal disposal of electrical waste, the penalties are specified by local disposal legislation.
D
rafted by:
C
hecked by:
A
pproved by:
Munari Andrea 14/04/2010
R
EAD AND SAVE
THESE INSTRUCTIONS
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
3
CONTENTS
HOW TO USE THIS MANUAL ....................................................................................................................................................... 6
INTRODUCTION ............................................................................................................................................................................ 7
General Description ......................................................................................................................................................................................... 7
Typical applications: ........................................................................................................................................................................................ 7
Technical data: ................................................................................................................................................................................................ 7
Main functions: ................................................................................................................................................................................................ 7
Models and Features ....................................................................................................................................................................................... 7
USER INTERFACE (FOLDER PAR/UI) ......................................................................................................................................... 8
Keys ................................................................................................................................................................................................................ 8
Keys and associated functions ......................................................................................................................................................................... 8
Local On/OFF .................................................................................................................................................................................................. 9
Keys – combined action ................................................................................................................................................................................. 10
Manual alarm acknowledgment and reset ...................................................................................................................................................... 10
LEDs and Display .......................................................................................................................................................................................... 11
Display........................................................................................................................................................................................................... 11
LED: decimal point ......................................................................................................................................................................................... 11
LED: States and Operating Modes ................................................................................................................................................................. 12
LED: Values and Units of Measure ................................................................................................................................................................ 12
LED: utilities ................................................................................................................................................................................................... 12
First switch on ................................................................................................................................................................................................ 13
Access to folders - menu structure ................................................................................................................................................................. 13
“Main Display” Menu ...................................................................................................................................................................................... 15
“Operating Mode” menu ................................................................................................................................................................................. 16
‘States’ menu ................................................................................................................................................................................................. 17
View Inputs/Outputs (Ai, di, AO, dO) .............................................................................................................................................................. 17
Setting the clock (CL)..................................................................................................................................................................................... 18
Alarm Display (AL) ......................................................................................................................................................................................... 20
Example of how to set the setpoint (SP) ........................................................................................................................................................ 20
View and Reset compressor/pump time ......................................................................................................................................................... 22
Programming menu ....................................................................................................................................................................................... 23
Parameters (folder PAr) ................................................................................................................................................................................. 23
Functions (FnC folder) ................................................................................................................................................................................... 24
Entering a password (Par/PASS folder) ......................................................................................................................................................... 2 4
Alarm events (EU folder) ................................................................................................................................................................................ 25
SYSTEM CONFIGURATION (FOLDER PAR/CF) ....................................................................................................................... 28
Configuration of analogue inputs.................................................................................................................................................................... 28
Configuration of digital inputs ......................................................................................................................................................................... 29
Configuration of digital outputs ....................................................................................................................................................................... 30
Configuration of analogue outputs ................................................................................................................................................................. 31
Serial configurations – Protocol parameters ................................................................................................................................................... 33
REMOTE TERMINAL ................................................................................................................................................................... 34
OPERATING MODES – TEMPERATURE CONTROL (FOLDER PAR/TR) ................................................................................ 35
Proportional temperature control .................................................................................................................................................................... 35
Temperature con tr o l differential ..................................................................................................................................................................... 37
Digital temperatu r e co n trol ............................................................................................................................................................................. 37
Block heat pump ............................................................................................................................................................................................ 37
Block heat pump based on external temperature and/or parameter ............................................................................................................... 38
Block heat pump from digital input ................................................................................................................................................................. 38
Economy function .......................................................................................................................................................................................... 38
OPERATING STATES (FOLDER PAR/ST) ................................................................................................................................. 39
Operating mode s ........................................................................................................................................................................................... 3 9
Operating mode s ........................................................................................................................................................................................... 3 9
Automatic changeover ................................................................................................................................................................................... 40
COMPRESSORS (FOLDER PAR/CP) ......................................................................................................................................... 41
Type of compressors ..................................................................................................................................................................................... 41
Compressor ti min g s ....................................................................................................................................................................................... 41
Minimum time between the switching on of more than one compressor (CP05) ............................................................................................. 41
For partialized compressors only - Minimum ON step during increase in output (CP08) ................................................................................. 42
Minimum time between the switching off of more than one compressor (CP06) ..................................................... ........................................ 42
For partialized compressors only - Minimum ON step during decrease in output (CP09) ............................................................................... 43
Minimum time between switching off and on of the same compressor (CP03) ............................................................................................... 43
Minimum time between the switching on of the same compressor (CP04) ..................................................................................................... 43
Minimum compressor ON time ....................................................................................................................................................................... 43
Compressor switch on/off sequence .............................................................................................................................................................. 44
UST500 CONTROL BOARD
4 06MC0074@00B0100
14/04/2010
INTERNAL CIRCUIT PUMP (FOLDER PAR/PI) .......................................................................................................................... 45
Operating mode s ........................................................................................................................................................................................... 4 6
Antifreeze operation with pump ...................................................................................................................................................................... 47
EXTERNAL EXCHANGER FAN (FOLDER PAR/FE) .................................................................................................................. 48
Configuration of fan ....................................................................................................................................................................................... 48
Fan control in defrost ..................................................................................................................................................................................... 50
INTERNAL EXCHANGER ELECTRIC HEATERS (FOLDER PAR/HI) ........................................................................................ 52
Internal exchanger heaters for antifreeze ....................................................................................................................................................... 53
Internal exchanger heaters in integrated use ................................................................................................................................................. 53
EXTERNAL EXCHANGER ELECTRIC HEATER PARAMETERS (FOLDER PAR/HE) ............................................................. 55
AUXILIARY ELECTRIC HEATERS (FOLDER PAR/HA) ............................................................................................................. 56
DEFROST (FOLDER PAR/DF) .................................................................................................................................................... 57
Start defrost ................................................................................................................................................................................................... 58
End defrost .................................................................................................................................................................................................... 59
Defrost when compressor stops ..................................................................................................................................................................... 59
Manual defrost ............................................................................................................................................................................................... 59
Power failure during defrost. .......................................................................................................................................................................... 59
ADAPTIVE (FOLDER PAR/AD) ................................................................................................................................................... 60
Operating mode s ........................................................................................................................................................................................... 6 0
Adaptive function with setpoint modification ................................................................................................................................................... 60
Adaptive function with hysteresis modification ............................................................................................................................................... 61
Adaptive function with setpoint and hysteresis modification ........................................................................................................................... 61
Setpoint regression ........................................................................................................................................................................................ 62
Protection ...................................................................................................................................................................................................... 6 2
ANTIFREEZE PARAMETERS WITH HEAT PUMP (FOLDER PAR/AF) ..................................................................................... 63
POWER LIMITATION (FOLDER PAR/PL)................................................................................................................................... 64
Operating mode s ........................................................................................................................................................................................... 6 4
Power limitation – by high pressure probe (Cool and Heat) ............................................................................................................................ 64
Power limitation – by low pressure probe (Cool and Heat) ............................................................................................................................. 65
Power limitation – by temperature control probe (Cool and Heat) ................................................................................................................... 65
Power limitation – by external temperature (Cool and Heat) ........................................................................................................................... 65
ALARMS AND DIAGNOSTICS (FOLDER PAR/AL) ................................................................................................................... 66
Digital alarms ................................................................................................................................................................................................. 67
Analogue alarms ............................................................................................................................................................................................ 68
Table of Alarms ............................................................................................................................................................................................. 68
PARAMETERS (PAR) .................................................................................................................................................................. 73
Visibility and value of Parameters .................................................................................................................................................................. 73
CONFIGURATION PARAMETERS (CF) ..................................................................................................................................... 74
User interface parameters (UI) ....................................................................................................................................................................... 77
Temperature control parameters (tr) – temperature controller ........................................................................................................................ 78
Function mode selection parameters (St) ....................................................................................................................................................... 79
Compressor Par ameters (CP) ........................................................................................................................................................................ 79
Internal circuit pump parameters (PI) ............................................................................................................................................................. 80
Recirculation fan parameters (FI) ................................................................................................................................................................... 81
Secondary (external) exchanger fan parameters (FE) .................................................................................................................................... 81
Electric heater parameters (HI) ...................................................................................................................................................................... 83
External exchanger electric heater parameters (HE) ...................................................................................................................................... 83
Auxiliary electric heater parameters (HA) ....................................................................................................................................................... 84
External circuit pump parameters (PE) ........................................................................................................................................................... 84
Boiler parameters (br) -boiler ......................................................................................................................................................................... 84
Defrost parameters (dF) ................................................................................................................................................................................. 84
Dynamic setpoint parameters (dS) ................................................................................................................................................................. 85
Adaptive parameters (Ad) .............................................................................................................................................................................. 85
Antifreeze parameters with heat pump (AF) ................................................................................................................................................... 86
Power limitation parameters (PL) ................................................................................................................................................................... 86
Alarm parameters (AL) ................................................................................................................................................................................... 86
FUNCTIONS (FOLDER FNC) ...................................................................................................................................................... 88
Manual defrost activation (folder FnC/dEF) .................................................................................................................................................... 89
Alarm acknowledgment (folder FnC/tA) .......................................................................................................................................................... 89
Change On/OFF state (folder FnC/St)............................................................................................................................................................ 89
Multi Function Key ............................................................................................................ ............................................................................. 90
Using the Multi Function Key (folder FnC/CC) ................................................................................................................................................ 90
Download from reset ...................................................................................................................................................................................... 91
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
5
Reset alarm log (folder EUr) .......................................................................................................................................................................... 92
MECHANICAL ASSEMBLY ......................................................................................................................................................... 93
TECHNICAL DATA ...................................................................................................................................................................... 94
I/O features .................................................................................................................................................................................................... 94
Mechanical specifications .............................................................................................................................................................................. 95
Display and LEDS .......................................................................................................................................................................................... 95
Serials ........................................................................................................................................................................................................... 95
Transformer ................................................................................................................................................................................................... 95
Mechanical dimensions .................................................................................................................................................................................. 95
DEVICE OPERATION .................................................................................................................................................................. 96
Permitted use ................................................................................................................................................................................................ 96
Unintended Use ............................................................................................................................................................................................. 96
REGULATIONS ............................................................................................................................................................................ 96
RESPONSIBILITY AND RESIDUAL RISKS ................................................................................................................................ 96
NON-LIABILITY CLAUSE ............................................................................................................................................................ 96
UST500 CONTROL BOARD
6 06MC0074@00B0100
14/04/2010
How to use this manual
This manual is designed to permit quick, easy reference with the following features:
References column: A column to the left of the text contains references to subjects discussed in the text to help you locate the information you need quickly and easily.
Cross references: All words written in italics are referenced in the subject index to help you find the page containing details on this subject; supposing you read the following text: ” If there are 2 compressors in the installation, the min imum ti me between the switching on and t he switching off) of the two compressors is observed. ” The italics mean that you will find a reference to the page on the topic of compressors listed under the item compressors in the index. If you are consulting the manual “on-line” (using a computer), words which appear in italics are hyperlinks: just click on a word in italics with the mouse to go directly to the part of the manual that discusses this topic.
Some segments of text are marked by icons appearing in the references column with the meanings specified below:
Warning! : information which is essential for preventing negative consequenc es for the system or a hazard to personnel, instruments, data, etc., and which users MUST read with care.
Take note: information on the topic under discussion which the user ought to keep in mind
Tip: a recommendation which may help the user to understand and make use of the information supplied on the topic under
discussion.
References
Cross references
I
cons for
emphasis
UST500 CONTROL BOARD
7 06MC0074@00B0100
14/04/2010
Introduction
General Description
Uniflair SpA, a leading manufacturer for over a decade of control equipment for sm all and medium-size air c onditioni ng units is proud t o present UST500, the new range of compact devices with advance functions and groundbreaking appl i cations.
Single-circuit control of centralized air-conditioning systems with 1 or 2 compressors (steps) such as:
Chillers, Heat Pumps, Close Control:
o water-air; o air-water; o water-water; o air-air;
Motorized condensers
o air-cooled; o water-cooled.
Typical applications:
Minimarkets,
Industrial plants,
Offices,
Hotels,
Residential buildings.
Technical data:
There are 6 models in the UST 500 range providing up to 5 relay outputs, one TRIAC output, 2 PWM analogue outputs, a 0…10V/4…20mA configurable analogue output and an Open Collector digital output for an external relay. All inputs and outputs are independent and configurable, meaning they can be adapted to fit any system. Uniflair SpA's standard 32x74mm format also ensures the utmost flexibility and ease of installation.
Main functions:
Temperature control via the input or output probe;
Integrated boiler or heating control;
Integrated control of two electric heaters or heating system;
Dynamic set point;
Automatic changeover;
Indoor ventilation control;
Dynamic defrosting;
Full diagnostics;
Modulating water pump control;
Adaptive” function for units with no accumulation;
Antifreeze function with water pump on external probe;
Control of non-uniform tandem compressors;
Power limitation;
Resources optimized in accordance with the external temperature.
Models and Features
-->See Annexe A - Models and Accessories and the Specifications chapter
UST500 CONTROL BOARD
8 06MC0074@00B0100
14/04/2010
User Interface (folder PAr/UI)
The front panel of the device functions as the user interface and is used to perform all operations relating to the device.
Keys
There are 4 keys on the front panel. Each key has (see the two tables below):
o A “direct” action (indicated on the key) o An “associated” function (indicated on the front panel of the device beside the key). In the manual, this is shown in square brackets
(e.g. [UP])
o A “combined” action involving two keys. In the manual, this is shown in square brackets (e.g.[UP+DOWN])
Keys and associated functions
Key
Description
Key
Press once
(press and release)
Key
[associated
f
unction]
P
ress and hold
[press for about 3
s
econds]
Menu / Comments
UP
(UP)
Increases a value
Goes to the next
label
[Manual defrost
activation]
Functions menu see
Functions chapter
(folder FnC)
DOWN
(DOWN)
Decreases a value
Goes to the previous
label
[Local ON/OFF]
See
L
ocal On/OFF
section
----
See also Functions
menu
Functions chapter
(folder FnC)
Esc(ape)
Output
(Without saving new
settings)
Exit without saving new settings
Go back to previous level
mode
[Change mode]
---
See section on
Changing operating
mode
Operating mode
menu
Set
Confirm
(save new settings)
Confirms value / exit and save new settings
Move to next level (open folder, subfolder, parameter, value)
Open State Menu
disp
[Main display]
---
See Main Display
section
[Main Display Menu]
ALL Alarm acknowledgment
See
M
anual alarm acknowledgment and reset section
By parameter (see parameters chapter, parameters
U
I10-11-12-13-
14) the function [associated] can be enabled or disabled:
0 = Key not enabled for the function
1 = Key enabled for the function
<IMG INFO> 226,75 117,6 0 2 99,25 0
-1
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
9
Local On/OFF
Device ‘On’ --> ‘OFF’
Press the [DOWN] key for about 3 seconds from
the main display
The word OFF will appear on the display.
All other LEDs will be off
Device ‘OFF’ --> ‘On’
The word OFF will appear on the display.
Press the [DOWN] key for about 3 seconds
UST500 will return to the “normal” screen
NOTE: The local ON/OFF function is deactivated if the device has been turned OFF remotely or if a digital input is configured as a remote ON/OFF.
<IMG INFO> 226,65
<IMG INFO> 226,65
UST500 CONTROL BOARD
10 06MC0074@00B0100
14/04/2010
Keys – combined action
S
ymbol
[function associated to the combined
pressing of
the
keys
]
Combination
Keys
C
ombined
pressing
of keys Press
once
(press and
r
elease
[associated function] [Menu] / Comments
[UP
(UP)
+
DOWN
(DOWN)]
[Manual reset]
See Manual alarm
acknowledgment and
reset section
[Esc
+
SETPOINT]
[Open programming
menu]
[Programming menu]
Manual alarm acknowledgment and reset
Alarm messages blink. How to acknowledge an alarm is explained below. All error messages are shown in the AL folder (see state Menu)
set
esc
set
esc
An error message will be shown, alternating
with the error alert and the main display.
The ALARM LED will be permanently on.
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
11
A
LARM/ERROR ACKNOWLEDGMENT
set
esc
An error can be acknowledged by pressing any
key once.
After pressing any key, the alarm LED will start
to blink.
M
ANUAL RESET
set
esc
To manually reset an alarm, press the “up” and
“down” keys together [UP+DOWN]
- - - - - - - - -
N.B: resetting an active alarm* will save the
alarm in the AL folder (see state Menu).
* i.e. manual reset (alarm)
set
esc
The device will return to the main display.
LEDs and Display
The display has 18 icons (LEDs) split into 3 categories (+ decimal point):
Decimal point
States and Operating Modes
Values and Units of Measure
Loads
Display
Values of up to 4 figures or 3 figures plus a sign can be displayed.
LED: decimal point
Values are always shown in tenths of a degree/bar.
UST500 CONTROL BOARD
12 06MC0074@00B0100
14/04/2010
<IMG INFO>
LED: States and Operating Modes
L
ED states and Operating
Modes
I
con
C
olour
C
olour Permanently
o
n
B
linking
The display shows the value/resource set for the “main display”. In the event of an alarm, it will alternate with the alarm code Exx. (when more than one alarm occurs at the same time, the one with the lowest number will be shown first - see Alarms and Diagnostics chapter)
Alarm Red Active alarm Al arm acknowledged
Heating
Green
Heating mode
Antifreeze with heat pump
active
Remote heating mode
(Missing
Icon)
Cooling Cooling mode Remote cooling mode
Standby
Local standby
mode
(from
keyboard)
Remote standby
Defrost Defrost active Manual defrost activated
Economy
Configurable
----
See
Parameters
chapter
----
Ui /dS folder
Parameters
UI07 /dS00
Configurable
----
See Parameters chapter
----
Ui /dS folder
Parameters UI07 /dS00
LED: Values and Units of Measure
L
ED Unit of measure
I
con
C
olour
P
ermanently on
B
linking
Values can be displayed with a decimal point by setting parameter Ui08 see parameters chapter, Ui folder)
Clock (RTC) Red Shows current time
(24hr format)
Set time
Degrees
centigrade
/ /
Pressure (Bar) / /
Relative
humidity
(% RH)
Not used Not used
Menu (ABC) Menu navigation /
LED: utilities
L
ED utilities
C
olour
P
ermanently on
B
linking
Amber
Configurable (°)
----
See Parameters
chapter
----
Ui folder
Parameters
UI00..UI07
Configurable (°°)
----
See Parameters
chapter
----
Ui folder
Parameters
UI00..UI07
(°) permanently on: utility active (°°) blinking:
example UI00..UI07= 1 (Compressor 1) indicates:
o safety timing o power limited to 50% o block compressor
example UI00..UI07= 2 (step 2) indicates: safety timing
<IMG INFO> 122,45 67,9 0 2 0,35 6,3
-1
<IMG INFO> 122,45 72,95 0 2
-2 5,75
-1
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
13
default configuration
LEDs for utilities are all configurable (see parameters chapter, folder Ui). The fact ory settings are listed in the table below:
L
ED symbol
on display
LED Default
Default icon
on front panel
LED 1
(first from left)
Compressor 1 LED 2 Output step 2 LED 3 Internal exchanger electric heater 1 LED 4 Internal exchanger electric heater 2 LED 5 Boiler
LED 6 External exchanger fan LED 7 Internal circ uit water pum p
First switch on
set
esc
When UST500 is switched on for the first time, a lamp test is carried out to check the state and proper function of lamps.
---------­The Lamp Test lasts for a few seconds. During this short time, all LEDs and digits flash at the same time.
set
esc
After the lamp test, based on preselected settings, the following are displayed:
time,
real setpoint
parameter setpoint
the value of the analogue input selected
(AI1…AI4)
---------­In the example, the current time is the main display (RTC)
Access to folders - menu structure
Access to folders is organised into menus. Access is determined by the keys on the front panel (see relative sections). Access to each individual menu is explained below (or in the sections indicated). There are 4 menus:
• ‘Main Display’ menu
see ‘Main Display Menu’ section;
‘Operating Mode’ menu
see ‘Operating Mode Menu’;
‘States menu’
see "States Menu’ section;
Programming Menu’
see ‘Programming Menu’ section.
There are 4 folders/submenus in the Programming Menu:
Parameters Menu (Par folder)
see Parameters chapter
Functions Menu (Fnc folder)
see Functions chapter;
Password PASS
Alarm codes EU
UST500 CONTROL BOARD
14 06MC0074@00B0100
14/04/2010
All menus and labels are listed in the table below:
M
ENU
Main Display
Ai AI1 Ai2 AI3 AI4 di Di01 Di02 … Di05
rtC HOUr dAtE YEAr
Setr
Operating mode
HEAt
COOL
StdBY
States
Ai di
CL HOUr dAtE YEAr
Hr
C
P01 CO02 PU01 PU02
Programming
M
ENU
Parameters
CF
C
F00…CF78
UI … … … … AL AL00Al48
Functions
dEF
tA St OFF / On
CC UL dL Fr
EUr
P
assword
EU
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
15
“Main Display” Menu
‘Main Display’ refers to the contents of the default display, i.e. when keys are not used. In UST500, the main display can be customized to suit personal requirements. The various c ontents can be selected from the “disp” menu
which is opened by pressing and holding the [set] key for more than 3 seconds. The main display can be selected from:
analogue inputs Ai1, Ai2, Ai3, Ai4 (when configured as digital inputs, the display will be defined on the basis of the state and logical parameter - digital input associations)
rtC,
Setpoint
o SetP= set from parameter, o Setr= real with any decalibration;
Step by step instructions are provided below.
set
esc
To open the [disp] menu to modify the main
display setup, press and hold the set key for at
least 3 seconds.
[set]
set
esc
Opens the blinking menu for the previous
display (rtC, i.e. current ti me, in this case).
set
esc
To modify the display, use the “up” and “down”
keys to scroll the menu and press the set key to
confirm.
set
esc
On selection of your preferred display, press the
set key to confirm. You will be automatically
returned to the main display set.
UST500 CONTROL BOARD
16 06MC0074@00B0100
14/04/2010
“Operating Mode” menu
Instructions are provided below on how to change the operating mode. There are three different operating modes:
Standby mode (StbY)
Heat mode (HEAT)
Cool only mode (COOL)
set
esc
For example, let's say you want to change
from StbY to COOL mode
To change operating mode, press and hold
the mode key for at least 2 seconds
PS The main display is set as rtc (current
time)
set
esc
A blinking menu will open containing the
values StbY (standby), HEAt (heat) and
COOL (cool).
set
esc
set
esc
Select your required operating mode and
press the set key.
set
esc
You will be automatically returned to the main display and you will see that the Stby LED that was previously on has gone off and the COOL
LED has come on.
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
17
‘States’ menu
From the states menu you can view values for each resource. For some resources, a "dynamic" view is possible.
For example, when declared as not present / probe not configured (see System Configuration chapter (
folder Par/CF), parameter
CF01=0), analogue input AI2 will not be displayed.
For example the hours of functioning of compressor 2 - CP02 – not available on single compressor machines.
L
abel
V
isibility
D
escription
C
hange
Ai Ai1 Ai2 Ai3 Ai4 // // Dynamic Analogue inputs // di di1 di2 di3 di4 di5 // Dynamic
D
igital inputs //
AO AO1 AO2 AO3 // // // Dynamic Analogue outputs // dO dO1 dO2 dO3 dO4 dO5 dO6 Dynamic
D
igital outputs //
CL HOUr dAtE YEAr Clock YES AL Er00 …. … … … Er99 Dynamic Alarms // SP Value // // // // // Setpoint (set) YES
Sr Value // // // // // Real setpoint // Hr
C
P01 CP02 PU01 PU02 // // Dynamic Running time
(hoursx10)
compressor/pumps
YES
As you will be able to see from the table, the setpoint SP and time can be modified and viewed:
View Inputs/Outputs (Ai, di, AO, dO)
Press the set key from the main display
Example of view for Analogue Inputs The same
procedure applies for all other I/Os. ***
The label Ai will appear on the display.
(Use the UP and DOWN keys to scroll the other
labels until you find the label required)
Press the set key to view the label for the first
analogue input (Ai01in this case)
Press the set key again to view the value in Ai01. Note that the °C icon lights up to indicate that the
value shown is in degrees centigrade.
***For digital inputs / analogue outputs configured
as digital (DI), the value will be 0/1 (0 indicates Off,
1 indicates On)
-------------------------------------
Press the esc key to go back to the main display.
UST500 CONTROL BOARD
18 06MC0074@00B0100
14/04/2010
Setting the clock (CL)
UST500 has a clock (RTC) to run the alarm log and time bands, just like a programmable chronothermostat. Instructions are provided below on how to set the time: the same procedure applies to change the date and year.
set
esc
To change the clock on your machine, press the set key
from the main display.
set
esc
Pressing the set key once will open a list of the various
folders.
Use the “UP” and “DOWN” keys to find the CL folder.
Press the set key to open the CL menu.
set
esc
set
esc
On entering this menu, you will see HOUr. Use the “UP” and
“DOWN” keys to select the time, date or year.
Once you have decided what you want to set, press the
[set]** key to open the modification menu for the variable
selected.
**press and hold for about 3 seconds
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
19
set
esc
set
esc
To set the time, date and year, use the “UP” and “DOWN”
keys to enter the required value.
set
esc
Press the Esc key to exit the set clock menu and go back to
the main display.
UST500 CONTROL BOARD
20 06MC0074@00B0100
14/04/2010
Alarm Display (AL)
Press the set key from the main display
The label Ai will appear on the display. Use the UP and DOWN keys to scroll the other labels until you
find the AL label
Press the set key to view the label of the first active
alarm (if it exists)
In this case, the first alarm is Er01. Use the UP and
DOWN keys to scroll any other alarms.
-------------------------------------
N.B: the menu is not cyclical.
For example, if the active alarms are ER01, Er02
and Er03, the display will show:
Er01 ->Er02->Er03 <-Er02<-Er01
N.B: -> UP, <-DOWN
Press the esc key to go back to the main display.
Example of how to set the setpoint (SP)
By way of example, we will change the setpoint value in COOL mode by 12.0 degrees centigrade to12.5 degrees centigrade.
set
esc
To change the setpoint on your machine, press the set key
from the main display.
set
esc
Pressing the set key once will open a list of the various
folders. Use the “UP” and “DOWN” keys to scroll the menu
and find the SP folder.
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
21
set
esc
Press the set key to open the SP folder.
set
esc
set
esc
The first screen you see will be the COOL mode then the
HEAT mode, using the “up” and “down” keys to scroll
(shown beside each view).
set
esc
Let's say you want to change the COOL mode setpoint.
Select COOL from the menu, then press the set key.
set
esc
The device will show the current machine setpoint, which in
this case is 12.0 degrees centigrade). Use the “up” and “down” keys to increase or decrease it. For example, if you want to change the setpoint to 12.5 degrees, press the "up
arrow" key until you reach the required value.
set
esc
Once you have reached the required setpoint, press the set
key. The device will save the value 12.5.
UST500 CONTROL BOARD
22 06MC0074@00B0100
14/04/2010
set
esc
To get back to the main display, press the esc key or allow a
15 second timeout to elapse for each menu.
View and Reset compressor/pump time
Example display and reset time (hours x10) for
Pump 2
Press the set key from the main display
The label Ai will appear on the display. Use the UP and DOWN keys to scroll the other labels until you
find the Hr label.
Press the set key to view the first label - which in
this case is the running time for compressor 1
(CP01)
Scroll with the UP and DOWN keys to view (if the
relative resources are present) the running time for
compressor 2 (CP02) the pump running time
(PU01, PU02)/
Press the set key to view the pump running time
PU02.
The tens of hours of functioning are 2.
(Hours expressed in tens:
2 means 20 hours of operation).
To clear pump running time PU02, press and hold
the [set] key.
Note: Repeat the procedure described to reset the
hours of functioning of the other resources.
-------------------------------------
Press the esc key to go back to the main display.
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
23
Programming menu
L
abel
D
escription
C
hange
C
omments
PAr CF Ui St … Al Parameters
FnC dEF tA St CC EUr Functions See Functions
chapter (folder
FnC)
PASS Password
EU Eu00 … … … …
Parameters (folder PAr)
Modifying a parameter
Instructions are provided below on how to change a machine param eter. By way of example, let's look at the CF configuration parameters folder, parameter CF00 (folder PAr/CF/CF00).
set
esc
Press the esc and set keys together to
open the parameters menu. This will open
the PAr menu.
set
esc
The PAr parameters menu contains all
device parameters. Press the set key to
view all folders.
set
esc
The first folder shown for the device is the
CF configuration folder. Simply press the
set key again to modify individual CF
parameters.
UST500 CONTROL BOARD
24 06MC0074@00B0100
14/04/2010
set
esc
The CF00 parameter will be shown on the
device (factory default settings).
Press the "up" key to scroll the various
parameters or move to the next parameter
(CF01 in this case) or the “down” key to go
back to the previous parameter (CF47 in this
case).
CF00->CF01->CF02->…->CF47->CF00 CF47<-CF00<-CF01->…<-CF46<-CF47
N.B: -> UP, <-DOWN
set
esc
Press the set key to view the value of the
parameter (CF00 in this case).
set
esc
For parameter CF00, the value shown will be 2.
Press the “up” and “down” keys to modify this
value.
set
esc
Press the set key once you have entered the required value. **
Press the esc key to exit this display and go back to the previous level.
**N.B. pressing the set key will confirm the value entered. Pressing the esc key will take you back to the previous level without saving the value entered.
Functions (FnC folder)
See Functions chapter (folder FnC)
Entering a password (Par/PASS folder)
Levels of visibility
Four levels of visibility can be set by assigning suitable values to each parameter and folder, by serial, software
(Param Manager or other communicatio n so ftwares) or by programming key. The visibility levels are:
Value 3 = parameter or folder always visible
Value 2 = manufacturer level; these parameters can only be seen by entering the manufacturer's password (see parameter UI18)
(all parameters specified as always visible, parameters that are visible at the installation level, and manufact urer level parameters will be visible).
Value 1 = installation level; these parameters can only be viewed by entering the installat ion password (see parameter UI17) (all parameters specified as always visible and parameters that are visible at the installation level will be visible)
Value 0 = parameter or folder NOT visible
1. Parameters and/or folders with visibility level <>3 (i.e. password protected) will only be visible if the correct password is entered (installation or manufacturer) following the procedure outlined below:
2. Parameters and/or folders with visibility level =3 are always visible and no password is required; in this case, the procedure below is not required.
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
25
To view parameters visible for the given password, open the PASS folder (press esc and set t ogether [esc+set] from the main display and search the folder using the up/down keys) and set the PASS value.
set
esc
Press the esc and set keys together from the main display to
enter the PASS folder. [esc+set]
set
esc
Pressing the two keys will open the menu containing the list of
folders. Use the “up” and “down” keys to scroll the list until you
find the PASS folder.
set
esc
Press the set key to open the PASS folder.
Enter the password (installation or manufacturer) from here, press
the set key and exit.
Now open and view parameters to change a value (see
parameters chapter).
Alarm events (EU folder)
set
esc
Press the esc and set keys together from the
main display to enter the PASS folder.
[esc+set]
set
esc
Pressing the two keys will open the menu
containing the list of folders. Use the “up” and
“down” keys to find the EU folder.
UST500 CONTROL BOARD
26 06MC0074@00B0100
14/04/2010
Press set to view the last alarm event - if it
exists – EU00.
N.B: EU00 indicates the last alarm recorded,
EU01 the second last, and so on.
Scroll with the UP and DOWN keys to view (if
present) any other alarm events.
Press the set key again to view details of the
selected event (EU00 in this case).
The first label will be shown (alarm code).
With the UP and DOWN keys you can scroll:
Alarm code (as previously indicated)
Alarm start time
Alarm start date
Alarm stop time
(in this case, the alarm is still active)
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
27
Alarm stop date
(in this case, the alarm is still active)
Type of alarm
(Automatic)
or alternatively
(manual)
UST500 CONTROL BOARD
28 06MC0074@00B0100
14/04/2010
<IMG INFO> 57,1 43,9 1 2 51
-28,35
-1
System configuration (folder PAr/CF)
Before doing anything, make sure the device is connected to a suitable external transformer. The following rules must be followed when connecting cards to each other and to the application:
Loads that exceed the maximum limits set forth herein must not be applied to outputs;
When connecting loads, follow connection diagrams carefully;
To avoid electric pairings, wire all low SELV utilities separately from high voltage ones.
(°) SELV: SAFETY EXTRA LOW VOLTAGE Instrument configuration is determined by the values of the parameters associat ed with inputs and outputs.
Configuration of analogue inputs
The analogue inputs referred to below as AI1…AI4 are 4 in total. A further analogue input Ai5 is available on the remote keyboard.
Using the parameters, a physical resource (probe, digital input, voltage/c urrent signal) can be “physically” configured for each type of input:
4 inputs can be configured as temperature probes, an NTC type probe, or as digital inputs.
2 inputs (AI3., AI4) can be configured as temperature probes, an NTC type probe, as digit al inputs or current/volt age input (signal 4-
20mA / 0-10V, 0-5V, 0-1V).
A “logical” meaning can also be associated to each analogue input using the relevant parameter. Inputs can be “physically” configured as specified in the table below.
Analogue inputs: Configuration table
Parameter Description
V
alue
0 1 2 3 4 5 6
CF00
Type of input
analogue AI1
Probe not
configured
Probe configured as no
voltage digital input
NTC
sensor
// // // //
CF01
Type of input
analogue AI2
Probe not
configured
Probe configured as no
voltage digital input
NTC
sensor
// // // //
CF02
Type of input
analogue AI3
Probe not
configured
Probe configured as no
voltage digital input
NTC
sensor
4-20 mA 0-10 V 0-5 V 0-1 V
CF03
Type of input
analogue AI4
Probe not
configured
Probe configured as no
voltage digital input
NTC
sensor
4-20 mA 0-10 V 0-5 V 0-1 V
CF73
Type of input
analogue AI5
Probe not
configured
Not used
NTC
sensor
// // // //
S
ee
Configuration of digital inputs
N.B: // indicates that value is not present
A
nalogue input AI
P
arameter
R
ange
D
escription
AI3
C
F04
C
F05…99.9 Analogue input AI3 full scale value
AI3
C
F05
-50.0…CF04 Analogue input AI3 start of scale value
AI4
C
F06
C
F07…99.9 Analogue input AI4 full scale value
AI4
C
F07
-50.0…CF06 Analogue input AI4 start of scale value
The values read by analogue inputs can be configured in parameters CF08…CF11
P
arameter
D
escription
U
nit of measure
R
ange
C
F08
Analogue input AI1 differential °C -12.0..12.0
C
F09
Analogue input AI2 differential °C -12.0..12.0
C
F10
Analogue input AI3 differential °C / Bar -12.0..12.0
C
F11
Analogue input AI4 differential °C / Bar -12.0..12.0
C
F76
Analogue input AI5 differential °C -12.0..12.0
Study the following tables:
Table A – parameter association - configuration of analogue inputs
Parameter Description Value Description Notes
CF12
Configuration of analogue input AI1 0…6 See table B
If
C
F00=1 (AI1 configured as DI),
set CF12=0
CF13
Configuration of analogue input AI2 0…6 See table B
If
C
F01=1 (A2 configured as DI)
set CF13=0
CF14
Configuration of analogue input AI3 0…11 See table B
If
C
F02=1 (AI3 configured as DI)
set CF14=0
CF15
Configuration of analogue input AI4 0…11 See table B
If
C
F03=1 (AI4 configured as DI)
set CF15=0
C
F77
Configuration of analogue input AI5 0…2 See table B
Analogue inputs
UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
29
Table B – analogue input logical meaning & parameter values CF12…CF15
A
nalogue input AI
A
nalogue input AI5 on
r
emote keyboard
V
alue
D
escription
AI1 AI2 AI3 AI4 AI5 0 Probe disabled AI1 AI2 AI3 AI4 AI5 1 Internal exchanger water/air inlet temperature AI1 AI2 AI3 AI4 AI5 2 Internal exchanger water/air outl et t em perature AI1 AI2 AI3 AI4 AI5 3 External exchanger temperature AI1 AI2 AI3 AI4 AI5 4 External exchanger inlet water temperature AI1 AI2 AI3 AI4 AI5 5 External exchanger outlet water temperature AI1 AI2 AI3 AI4 AI5 6 External temperature
AI3 AI4 // 7 High pressure input AI3 AI4 // 8 Low pressure input AI3 AI4 // 9 Dynamic setpoint input AI3 AI4 // 10 External exchanger pressure AI3 AI4 // 11 Internal exchanger pressure
N.B: // indicates that value is not present
Configuration of digital inputs
The no voltage digital inputs referred to below as DI1…DI5 are 5 in total.
These can be added to by AI1…AI4 if the latter are configured as digital inputs (via parameters CF23…26 respectively). A total of 8 digital inputs is thus available. Study the following tables:
Table A – parameter association - configuration of digital inputs
Parameter Description Value Description Notes
C
F16
Configuration of digital input DI1 -32…+32 See table B
C
F17
Configuration of digital input DI2 -32…+32 See table B
C
F18
Configuration of digital input DI3 -32…+32 See table B
C
F19
Configuration of digital input DI4 -32…+32 See table B
C
F20
Configuration of digital input DI5 -32…+32 See table B
CF23
Configuration of analogue input AI1
if configured as a digital input
-32…+32 See table B
Set to 0 if AI1
is NOT
configured as
a DI
CF24
Configuration of analogue input AI2
if configured as a digital input
-32…+32 See table B
Set to 0 if AI2
is NOT
configured as
a DI
CF25
Configuration of analogue input AI3
if configured as a digital input
-32…+32 See table B
Set to 0 if AI3
is NOT
configured as
a DI
CF26
Configuration of analogue input AI4
if configured as a digital input
-32…+32 See table B
Set to 0 if AI4
is NOT
configured as
a DI
Digital inputs
UST500 CONTROL BOARD
30 06MC0074@00B0100
14/04/2010
Table B – Digital inputs: Configuration table
The polarity of is defined as listed below:
V
alue
D
escription
+ Positive Active when contact closed
- Negative Active when contact open
V
alue
D
escription
N
otes
0 Input disabled ±1 High pressure pressure switch ±2 Low pressure pressure switch ±3 External exchanger fan thermoswitch ±4 Internal exchanger fan thermoswitch ±5 Internal circuit flow switch ±6 External circuit flow switch ±7 Compressor 1 thermoswitch ±8 Compressor 2 thermoswitch ±9 Internal circuit pump thermoswitch ±10 External circuit pump thermoswitch ±11 Compressor 1 oil pressure switch ±12 Compressor 2 oil pressure switch ±13 Remote ON/OFF
L
ocal ON/OFF has no impact
±14 Remote Summer/Winter See also
d
igital temperature control
±15 Power step 1 request See also digital temperature control ±16 Power step 2 request See also digital temperature control ±17 Auxiliary electric heater thermoswitch ±18 Digital input heat step 1 request See also digital temperature control ±19 Digital input heat step 2 request See also digital temperature control ±20 Digital input cool step 1 request See also digital temperature control ±21 Digital input cool step 2 request See also digital temperature control ±22 End of defrost ±23 Internal exchanger electric heater 1 thermoswitch ±24 Internal exchanger electric heater 2 thermoswitch ±25 External exchanger electric heater thermoswitch ±26 Economy input ±27 Remote STD-BY ±28 General alarm ±29 Block compressor 1 ±30 Block compressor 2 ±31 Power limited to 50% ±32
B
lock heat pump
If more than one parameter in the table is configured with the same value, the function is activated when at least one of the inputs is piloted (OR LOGICAL).
Configuration of digital outputs
See the chapter on electrical Connections for t he number and capacity of relays/open collectors and for inform ation on the
symbols used on labels supplied with the device.
High voltage outputs (relays) are identified as DO1, DO2, DO3, DO4 and D06.
The low voltage (SELV), open collector output is called DO5.
All digital outputs can be configured as outlined in the table below:
Table A – parameter association - configuration of outputs
Parameter Description Value Description Notes
C
F45
Configuration of digital output DO1 -13…+13 See table B Present in all models
C
F46
Configuration of digital output DO2 -13…+13 See table B Present in all models
C
F47
Configuration of digital output DO3 -13…+13 See table B Present in all models
C
F48
Configuration of digital output DO4 -13…+13 See table B Present in all models
CF49 Configuration of digital output DO5 -13…+13 See table B
Present in all models
(
Open collector ouput)
C
F50
Configuration of digital output DO6 -13…+13 See table B Present in models with 5 relays
CF51 Configuration of digital output AO1 -13…+13 See table B
See table A –
Analogue outputs and Models
CF34
=
0
-
CF43
CF52 Configuration of digital output AO2 -13…+13 See table B
See table A –
Analogue outputs and Models
CF35
=
0
-
CF44
D
igital inputs:
Configuration
table
Digital outputs
Loading...
+ 70 hidden pages