Uniflair CAL0231, CAL0251, CAL0331, CAL0361, CAL0511 Instruction Manual

...
Versione: 1.0 - Data: 17.04.96
Pag. 23 - Cod.: 05MU050X1A
CAL
CONDENSATORE AD ARIA
AIRCOOLED CONDENSER
LUFTGEKÜHLTE KONDENSATOREN
CONDENSEUR REFROIDI PAR AIR
MANUALE DI ISTRUZIONI
ATTENZIONE: prima di installare o intervenire sul condensatore leggere attentamente le istruzioni e le norme di sicurezza
INSTRUCTION MANUAL
WARNING: before installing or servicing the unit read the instructions and the safety notes carefully
BEDIENUNGSANLEITUNGEN
ACHTUNG: Bitte vor Installation oder jeglichem Eingriff an diesem Gerät die Bedienungs-anleitung und Sicherheitsnormen sorgfältig durchlesen
MANUEL D’INSTRUCTIONS
ATTENTION: avant d’installer ou intervenir sur l’unité, lire attentivement les instructions et les normes de sécurité
MANUAL DE ISTRUCCIONES
ATENCION: antes de proceder a la instalación o intervenir en la unidad, leer atentamente las instrucciones y las normas de seguridad
UNIFLAIR
3
Fig. 1.
DISPOSIZIONE CON FLUSSO D’ARIA ORIZZONTALE HORIZONTAL AIR DISCHARGE ARRANGEMENT HORIZONTALER LUFTSTROM ARRANGEMENT AVEC PULSION D’AIR HORIZONTAL DISPOSICIÓN CON FLUJO DE AIRE HORIZONTAL
Fig. 1.
DISPOSIZIONE CON FLUSSO D’ARIA VERTICALE VERTICAL AIR DISCHARGE ARRANGEMENT SENKRECHTER LUFTSTROM ARRANGEMENT AVEC PULSION D’AIR VERTICAL DISPOSICIÓN CON FLUJO DE AIRE VERTICAL
1 Ventilatore Propeller Fan Axialventilator Ventilateur helicoïde Ventilador helicoidal 2 Staffe di supporto Holding Brackets Aufstellkonsolen Brides de support Bridas de soporte 3 Gambe di supporto Holding Legs Stützbeine Pieds de support Patas 4 Connessioni frigorifere Connections Anschlüsse Raccordements Conexiones 5 Sezionatore Mains Isolator Hauptschalter Sectionneur Interruptor 6 Regolatore di pressione Pressure Regulator Druckregler Régulateur de pression Regulador de presión 7 Targa di identificazione Identification Plate Typenschild Plaque d’identification Placa de identificación
N.B.: Il numero e la disposizione dei ventilatori varia con il modello di condensatore
Fan number and layout depend on condenser model Anordnung und Anzahl der Ventilatoren ist abhängig vom Kondensatormodell Le nombre et la disposition des ventilateurs varient selon le modèle de condenseur El número y la disposición de los ventiladores varia según el modelo del condensador
8
SAFETY INSTRUCTIONS
READ THE INSTRUCTION MANUAL CAREFULLY BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT.
The condenser is factory precharged with dry nitrogen to prevent the ingress of any water vapour. Before removing the plugs from the inlet and outlet connections for installation, discharge the nitrogen by means of the needle valve on the inlet manifold
Work on the condenser should only be carried out by authorised and suitably qualified personnel
The condenser contains live electrical parts and rotating devices: before carrying out any work on the electrics or on the fan, isolate
the unit (turn optional isolator to position ‘O’)
The condenser contains gas above atmospheric pressure: tampering with connections or pipework can cause leakage of compressed gas
The temperature of the inlet pipe to the condenser can rise above 70°C and therefore presents the risk of burns
INSTALL THE CONDENSER IN A POSITION WHICH IS INACCESSIBLE TO UNAUTHORISED PERSONNEL: the fins of the heat
exchanger are made from thin aluminium sheet and can cause cuts in the event of accidental contact.
NAMEPLATE
The nameplate of the condenser is located on one side (see Fig. 1) and contains the following data:
Unit model;
Serial number;
Year of manufacture;
Current and power absorbed;
Standard settings.
TRANSPORT - POSITIONING ON SITE
The condenser leaves the factory in perfect condition; At the moment of delivery its condition should be carefully checked and any damage which might have been caused in transit should be notified in writing to the haulier. During transit and positioning on site:
Do not overturn or lean the condenser on its side.
Before removing the packaging carry the condenser to the
nearest possible point to the actual installation location by using a pallet truck or a forklift securing the unit to ensure that it does not fall off.
Carefully cut or remove the strapping and then remove the packaging.
DIMENSIONS AND WEIGHT
See drawing DIUI ........... attached.
INSTALLATION
Position the condenser in the open air out of direct sunlight. It can be installed:
with horizontal air discharge (standard version) for best protection (from snow or from objects falling from above) and easier maintenance; in this configuration the condenser must be protected from the wind which could interfere with the operation of the fan;
with vertical air discharge ; the optional leg kit is available for this configuration (four legs up to model CAL 0661; six legs for the larger models) and it is recommended for installation in windy locations or wherever a horizontal air flow would be obstructed. Assembly instructions are included with the leg kit.
The limited weight of the CAL condensers means that they can be installed on relatively lightweight bases. Position the condenser on a solid, level surface. Fix the condenser down using the appropriate bolt holes in the base (horizontal air discharge) or in the
bottoms of the legs
(vertical air discharge): See drawing No. DIUI........ attached for
dimensions. Ensure that the necessary clearances for free circulation of the air are left around the unit as shown in Fig.2.
Fig. 2a Horizontal Air Flow
Fig. 2b Vertical Air Flow
Use shims if necessary to ensure a level installation to within one degree.
INSTALL THE CONDENSER IN A POSITION WHICH IS INACCESSIBLE TO UNAUTHORISED
PERSONNEL: The heat exchanger fins are made from aluminium sheet which is only 0.1 mm thick and could cause cuts in the event of forceful accidental contact.
N.B. the fan characteristic does not allow any ducting of the air flow.
> 0,7 m > 4 m
> 4 m
> 1 m
> 1 m