Uniflair Aquaflair 00182, Aquaflair 00302, Aquaflair 00403, Aquaflair 00504, Aquaflair 00152 Instruction Manual

...
Versione: 1.4 - Data: 01.12.2000
Pag.: 48 - File: A-B-C-Ara14en
ARA
AIR-COOLED WATER CHILLERS
00182 - 00202 - 00232 - 00252 - 00302 - 00403 - 00504
AIR-COOLED HEAT PUMPS
00182 - 00202 - 00232 - 00252 - 00302 - 00403 - 00504
00182 - 00202 - 00232 - 00252 - 00302
ULTRA-LOW NOISE LEVEL FREE COOLING CHILLERS
00152 - 00182 - 00202 - 00232 - 00252 - 00302
INSTRUCTION MANUAL
© UNIFLAIR 2000.
GB
A - D - L
H - P - Q
E
M
2
UNIFLAIR ITALIA S.r.l.
Via dell’Industria, 10
35020 BRUGINE (Padova) Italy
Tel. +39 (0)49 9713211
Fax. +39 (0)49 5806906
Internet: www.UNIFLAIR.com
E-Mail: info@UNIFLAIR.com
Release:
1.4
Date:
01 - 12 – 2000
Checked by:
3
CONTENTS
WARNINGS Page. 4 SYMBOLS USED 5 SAFETY 5
GENERAL DESCRIPTION 6
Documentation included with the unit 6 Available versions and accessories 7 Data plate 8 General description and intended use of the unit 8 Access to main components 10 Description of the main components of the unit 12 Free cooling System - Free cooling 14 Recovery of condensation heat 15
INSTALLATION 16
Transport and handling 16
Receiving and storing the unit 17
Positioning the unit – working space 18 Water connections 19 Low-temperature operation with anti-freeze mixture 20 Guide to sizing of the expansion tank 21 Electrical connections 22 Remote control, local networks and supervision systems 24 Check list for start-up and testing 27
PROGRAMMING AND REGULATION 29
Microprocessor control 29
Introduction 29
Basic control 29
Advanced mP20 control 29 Regulation of cooling capacity 31 Setting the safety devices 32
TECHNICAL DATA 33
Current absorption – Cooling only versions and Heat Pumps 33 Current absorption – Free cooling version 34 Current absorption – Ultra-Quiet free cooling version 35 Dimensions and weights 36 ARA Basic version (cooling only) - Models 00182 - 00232 37 ARA Heat pump - Models 00182 - 00232 37 ARA Ultra low-noise version - Models 00182 - 00232 37 ARA Basic version (cooling only) - Models 00252 - 00504 38 ARA Heat pump - Models 00252 - 00504 38 ARA Ultra low-noise version - Models 00252 - 00504 38 ARA Free cooling version - Models 00182 - 00232 39 ARA Free cooling Low Noise Level - Models 00152 - 00232 39 ARA Free cooling version - Models 00252 - 00302 40 ARA Free cooling Low Noise level - Models 00252 - 00302 40
PROBLEM SOLVING 41
Guide to problem solving 41 Bleeding the water circuit 44 Refrigerant charge 44 Maintenance and cleaning 46 Changing the air filter 46
APPENDIX
Instruction manual for ARA microprocessor controls
4
This unit has been subjected to risk analysis under EC Directive 98/37/CEE (89/392/CEE). The technical solutions implemented during the design phase are described in the unit’s technical file.
This equipment is manufactured to function safely for the purposes for which it was designed as long as the
installation, operation and maintenance are carried out according to the instructions in this manual and on the labels attached to the unit.
Warnings in this manual which are particularly important for user safety are shown by this danger symbol.
IMPORTANT WARNINGS
This unit contains refrigerant gas circuits, chilled water under pressure, live electrical components, hot surfaces, sharp edges (the fins on the coils) and rotating devices such as the fans.
All service and maintenance operations which require access to the inside of the unit while it is in operation must be performed by qualified and experienced personnel who are aware of the necessary precautions.
Before accessing the inside of the unit, disconnect it from the electrical power supply.
In any case, all safety legislation of the installation location must be followed.
In the event of fire water and other conductive substances must not be used to put out the fire near live electrical components. This warning must be displayed on notices in the unit installation location.
If the refrigerants used come into contact with fire they decompose, forming acids and other irritants. The smell of these substances, even at concentrations below danger levels, gives enough warning to allow evacuation of the area at risk.
Make sure that the mains supply to the unit is the same as that shown on the rating plate.
Drain all water from the system before the winter season to avoid freezing.
In periods in which the temperature may fall below 0°C, empty the unit in order to prevent the serious damage caused by the formation of ice. This precaution is not necessary if the unit is charged with an appropriate anti-freeze mixture.
Free cooling chillers must be loaded with anti-freeze.
If the unit is fitted with the optional heating cable, it must be turned off without cutting the electrical power supply.
Install a mechanical filter in the section of tubing near the intake of the unit to prevent the fouling of the heat exchanger with pieces of welding or flakes of oxidised metal from the water mains.
5
SYMBOLS USED
SYMBOL MEANING SYMBOL MEANING
DANGER MOVING COMPONENTS
IMPORTANT WARNING HOT SURFACES – DANGER OF
BURNING
HIGH VOLTAGE – ELECTRICAL
RISK
SHARP EDGES
SAFETY
The new range of UNIFLAIR ARA water chillers and heat pumps features state-of-the-art technology to give maximum reliability, safety, quietness of operation and respect for the environment.
1) RELIABILITY: Trouble-free operation of Uniflair precision chillers is ensured by rigorous production process controls under ISO 9001-certified quality procedures:
quality control of components;
pressure testing of refrigerant and water circuits;
testing of current absorption and IEC safety testing;
calibration and testing of instruments and safety devices;
final testing of unit under operating conditions
2) ACTIVE SAFETY: UNIFLAIR safety and control systems have a supervision and prevention function with:
automatic blocking of components in dangerous conditions;
indication of function status; reading and continuous display of circulating fluid temperature;
management of compressor start-ups to reduce excessive switching on and off
compressor start timing to reduce total unit start-up current
indication of anomalous function conditions and/or alarms.
3) PASSIVE SAFETY: The essential functions of UNIFLAIR chillers are protected against anomalous function conditions and potential damage with:
high and low pressostats on the refrigerant circuit (HP with manual re-set)
safety valve on the high pressure refrigerant line
anti-freeze protection to prevent freezing of the evaporator, pump and tank
compressor motor electrical protection
standard differential flow gauge
water circuit safety (with optional pump group)
compressor crankcase heater (standard on free-cooling and heat pump versions).
4) PERSONAL SAFETY. The design and cabling of all UNIFLAIR chillers conforms to IEC electro­technical norms. Electrical panels have auxiliary 24V circuits and are equipped with:
general switch and door lock switch;
automatic circuit-breaker switches;
double protection panel on fan compartment.
The fans are protected by an external metal grille which conforms to applicable safety norms.
6
GENERAL DESCRIPTION
DOCUMENTATION INCLUDED WITH THE UNIT
Every ARA chiller is delivered complete with the following documentation:
ARA and microprocessor control instruction manuals
Unit installation diagrams
Diagrams of the refrigerant and hydraulic circuits of the unit
Electrical diagrams
List of spare parts
CE declaration with list of European directives and norms to which the unit conforms
Guarantee Conditions.
7
AVAILABLE VERSIONS AND ACCESSORIES
Models
ARA00152 (only M versions), ARA00182, ARA00202, ARA00232, ARA00252, ARA00302, ARA00403 (not supplied for E and M versions), ARA00504 (not
supplied for E and M versions)
Configurations A : Basic version: mechanical cooling with on-off condensation control
D : Basic version with modulating condensation control L : Ultra low-noise version with modulating condensation control H : Heat pump with on-off condensation control P : Heat pump with modulating condensation control Q : Ultra low-noise heat pump with modulating condensation control E : Free cooling version with modulating condensation control M: Ultra low-noise free cooling version with modulating condensation control
Pump group
Group with 1 type A pump (0.9 kW) Group with 2 type A pumps (0.9 kW) Group with 1 type B pump (1.1 kW) Group with 2 type B pumps (1.1 kW) Group with 1 type C pump (1.85 kW) Group with 2 type C pumps (1.85 kW)
Reservoir tank
(only with pump group)
Tank type “A” (210 litres) Tank type “B” (300 litres) Tank type “C” (500 litres)
Heat recovery
Partial heat recovery (with modulating condensation control as standard - not supplied for heat pump versions)
Power supply
400V/3ph+N/50Hz
Electrical accessories
Power phase correction capacitors
Control
Basic control (not available on free-cooling versions) Basic control with remote terminal (not available on free-cooling versions) mP20 control without user terminal (not available on heat pumps) mP20 control with local user terminal (not available on heat pumps) mP20 control with remote user terminal (not available on heat pumps)
Serial connections
LAN (with mP20 control) RS485 serial output (with basic control) RS485 serial output (with mP20 control) RS422 serial output + LAN (with mP20 control) RS485 serial output + LAN (with mP20 control)
Refrigerant
R22 R407C R134a
Norms
ISPESL (Italian) TÜV (German)
Refrigerant Accessories
Anti-freeze heater on evaporator (not supplied for Free cooling versions) Anti-freeze heater on pumps (not supplied for Free cooling versions) Anti-freeze heater on tank (not supplied for Free cooling versions) High/Low pressure manometers
Pressure sensors
Low pressure sensor (with mP20 control only) High pressure sensor
Options
Rubber anti-vibration feet Coil protection grilles Metal filters for free cooling coil.
8
DATA PLATE
The chiller data plate is in the electrical panel and gives the following information:
Model of the unit
Serial number
Voltage, number of phases and power supply frequency for primary and auxiliary circuits
Current and power absorbed
OA (Operating current), FLA (Full load current) and LRA (Locked rotor current)
Safety device settings
Refrigerant type and charge in kg for each circuit.
MODEL SERIAL No.
POWER SUPPLY VOLTAGE
CURRENT
OA FLA LRA KW TOTALI
SAFETY DEVICE SETTINGS
REFRIGERANT
GENERAL DESCRIPTION AND INTENDED USE
Air-cooled and water-cooled ARA air-cooled liquid chillers and heat pumps are designed for outdoor installation in comfort and industrial applications. The chilled water produced can be sent to fan coils or room air conditioning units or can be used for industrial process cooling.
Units fitted with the mP20 microprocessor control can be connected in parallel on a single water circuit thanks to the possibility to connect the microprocessor control boards in a local network. The cooling capacity of the system can therefore be altered at any time.
FUNCTION LIMITS
In free cooling and heat pump versions or in applications which require the production of chilled water in winter as well as summer, an anti-freeze mixture (water and ethylene glycol) must be used (see “Low­temperature operation with anti-freeze mixture”). The standard cooling-only unit can operate at air
temperatures up to +46°C.
EASE OF INSTALLATION AND MAINTENANCE
The compact dimensions and reduced weight of these chillers facilitates installation even where space is limited. All models are fitted with a main switch to enable direct connection to the mains power supply without the need for an external switch; short-circuit protection fuses should be fitted however. All units are assembled and fully tested in the factory, making installation simply a question of connection to the electrical power supply and water circuits. An important feature of the design is the positioning of components to allow easy access for service and maintenance.
9
RESISTANCE TO THE ELEMENTS
Uniflair chillers boast excellent corrosion resistance and are built to withstand the harshest of conditions. The structure is in galvanised steel sheet painter with polyester powder; all external fastenings are in stainless steel.
LOW NOISE LEVELS
Even the basic units have very low noise levels thanks to large exchange surfaces and low fan running speeds. For special applications where near-silent operation is required there are ultra-low noise versions available; these units have vibration dampers on the compressor output, sound insulation on the compressor housing and modulating fan speed control.
10
ACCESS TO MAIN COMPONENTS
COMPRESSOR HOUSING
To access the compressor housing, remove the 8 fixing screws
1
and lift panel
A
using the two front
handles
B
. Removing panel A gives access to the compressor housing, the microprocessor control user
terminal and to the optional high and low pressure manometers..
A
C
1
3
4
B
2
5
IG
DANGER – HOT SURFACES! RISK OF BURNING. When panel
A
has been removed the compressor and refrigerant tubes are exposed – during normal unit operation these components are very hot and can cause burns.
IMPORTANT: Removing panel
A
does not stop the unit and the power supply to the compressors is not
interrupted. For service and maintenance, the main switch IG must be turned off (position ‘O’).
ELECTRICAL PANEL
To access the electrical panel move the main switch
IG
to position “O” and turn the two screws
4
1/4 turn.
This enables panel
C
, hinged at the base of the electrical panel to be opened.
11
PUMP GROUP
To access the optional pump group and the free cooling pump remove the six fixing screws
6
and remove
panel
D
using front handle E. To avoid contact with the fan blades there is a further steel protection panel
F
, fixed with screws.
D
6
7
E
IMPORTANT: Before removing panel
D
switch off the unit by moving main switch IG to position ‘O’ to make
sure that there is no power supply to the compressors and circulation pumps.
ATTENZIONE
PRIMA DI QUALSIASI INTERVENTO LEGGERE ATTENTAMENTE IL LIBRETTO DI ISTRUZIONI. APPARECCHIO IN TENSIONE E CON ORGANI ROTA NTI: PRIMA DI INTERVENIRE SU QUALSIASI PARTE ELETTRICA OPPURE SUL VENTILATORE/I TO GLIERE TENSIONE ALL’APPARECCHIO.
WARNING
BEFORE ANY OPERATI ONS ON THIS UNIT READ T HE INSTRUCTION MANUAL CAREF ULLY. THIS EQUIPMENT CONTAINS COMPONENTS AT MAINS VOLTAGE AS WELL AS ROTATING FANS: DISCONNECT POWER BEFORE ANY OPERATION ON ELECTRICAL COMPONENTS OR FANS.
ACTHUNG
VOR ALLEN ARBEITEN AN DIESEM GERÄT IST DIE BEDIE NUNGSANLEITUNG GENAU STUDIEREN. DIESES GERÄT ENTHÄLT BUTEILE, DIE UNTER SPANNUNG ST EHEN SOWIE SICH DREHENDE VENTILATOREN: VOR ARBEITEN IM GERÄT IST DIE NETZZULEITUNG ABZUSCHALTEN.
ATTENTION
LIRE ATTENTIVEMENT LE MANUEL D’INSTRUCTIONS AVANT TUOTE INTERVENTION. CET EQUIPEMENT UTILISE DES COMPOSANTS ÉLECTRIQUE SOUS TENSION ET DES PIECES EN MOUVEMENT. COUPER L'ALIMENTATION AU DISJONCTEUR AVANT TOOTE INTERVENTION SUR LES COMPOSANTS ELECTRIQUES.
ATENCION
ANTES DE CUALQUIER INTERV ENCIÓN LEER ATENTAMENT E EL MANUAL DE INSTRUCCIONES. APARATO BAJO TENSIÓN Y CON COMPONENTES ROTANTES. ANTES DE INTERVENIR SOBRE CUALQUIER PARTE ELÈTRICA O SOBRE EL VENTILADOR/ES QUITAR TENSION AL APPARATO.
12
DESCRIPTION OF MAIN COMPONENTS
STRUCTURE
These units are normally installed outdoors, often on the roof of a building. For this reason the structure of the unit is made entirely in galvanised steel, painted with corrosion-resistant polyester powder. All external fastenings are in stainless steel. The panels can be easily removed to facilitate maintenance and all internal components can be accessed via two sides of the unit.
COMPRESSORS
Ultra-reliable rotating SCROLL compressors from a leading manufacturer are used (in tandem on models 00403 and
00504). All ARA units have two independent refrigerant circuits, ensuring at least 50% capacity in the unlikely event of a fault in one of the circuits. The microprocessor control manages the switching on and off of the compressors in order to ensure effective control of unit capacity; capacity steps depend on the type of control fitted; in the case of the mP20 control the steps are:
0 - 45 - 100% on models 00182 and 00232 0 - 50 - 100% on models 00202, 00252 and 00302 0 - 45 - 70 - 100% on model 00403 0 - 25 - 50 - 75 - 100% on model 00504
These units are available in versions for use with HCFC­R22 and HFC-R407C (environment-friendly) refrigerants. Units for operation with R134a are available on special order from UNIFLAIR ITALIA Srl. In order to prevent the refrigerant fluid diluting the oil and creating foam when the unit is started all free cooling or heat pump ARA models are fitted with oil heaters which switch on automatically when the compressor stops. Each compressor is fitted on rubber mountings to reduce vibration transmission.
FANS
The sickle-blade axial fans are directly connected to external rotor motors which can be fitted with voltage modulation speed control. The metal support grille conforms to all the main safety standards. The motors have class F insulation and IP44 protection under DIN VDE 0470 section 1/11.92 and EN 60529. Modulating condensation temperature control is available with fan speed regulation. This control is standard with certain unit configurations (ultra low-noise versions, free cooling versions, partial heat recovery).
EVAPORATOR
The brazed plate heat exchangers are in AISI 316 stainless steel. The exchanger is fully lined with closed-cell expanded polyurethane to prevent the formation of condensation and to limit heat loss. Given the internal volume and operating pressure, the evaporator does not need ISPESL or TÜV homologation under the standards for pressurised containers.
13
CHILLED WATER PUMP GROUP (optional)
The pump group for the circulation of chilled water is available in different configurations:
- one pump (type “A”, “B” or “C”);
- two pumps (one in stand-by);
- one pump plus reservoir tank;
- two pumps (one in stand-by) plus reservoir tank. The pumps, with 2-pole motors (2900 rpm), are fitted with the related connections, collectors and electrical panel (located in the main electrical panel housing). The pump panel controls rotation of operation between the two pumps on the basis of run time or alarms. The electrical panel contains the run hour counter for each pump and red LED alarm indicators. Pump body, flange and impeller are AISI 304 stainless steel, insulation is class F and protection is to IP55. The materials used ensure correct pump operation with liquid temperatures from -10°C to +85°C.
CIRCULATING PUMPS
ARA 00152 00182 00202 00232 00252 00302 00403 00504
Solo freddo n.a.
A - B - C B – C C
Cooling onl
y
Pompa di calore n.a.
A - B - C B – C C
Heat pump
Free cooling
A - B – C B – C
n.a. n.a.
Free cooling
Free cooling silenziato
A - B – C B – C
n.a. n.a.
Low noise - Free cooling
n.a. = Non disponibile
n.a. = Not available
RESERVOIR TANK
ARA 00152 00182 00202 00232 00252 00302 00403 00504
Solo freddo n.a.
A A – B A - B - C
Cooling onl
y
Pompa di calore n.a.
A A – B A - B - C
Heat pump
Free cooling
A A – B
n.a. n.a.
Free cooling
Free cooling silenziato
A A – B A - B - C
n.a. n.a.
Low noise - Free cooling
n.a. = Non disponibile
n.a. = Not available
FINNED COILS
In air-cooled versions the condenser consists of coils with aluminium fins and copper tubes mechanically expanded to obtain an optimum metallic contact and maximum exchange efficiency. The coil has a very large surface area for operation with high ambient temperatures and has an integrated super-cooling circuit. If there are harsh conditions in the installation environment, various treatments are available for the exchanger: pre-painted aluminium, copper-copper protection and cataforesis aluminium treatment; cataforesis provides the best compromise between cost and performance.
14
FREE COOLING
During normal chiller functioning, the water consumed is treated in the brazed plate heat exchanger. When the external air temperature drops to such a level as to allow water pre-cooling, the control activates a recirculation pump which sends the water to a finned pipe coil, mounted in front of the condenser. For the correct power supply of the thermostatic valve it is necessary to maintain the condensation pressure sufficiently high. For this reason, in the event of combined functioning of free cooling and mechanical cooling with the compressors, the speed of the fans is reduced (regulation of the standard speed of all ARA models with free cooling).
CONDENSATOR
COIL
FREE COOLING
COIL
FANS
AIR FLOW
Positioning of the Free Cooling Coil.
Since water passes through the free cooling coils, chillers must be loaded with antifreeze, or
guarantee conditions may be effected.
15
RECOVERY OF CONDENSATION HEAT
Recovery of heat from de-superheating and condensation of the refrigerant leaving the compressor enables the production of hot water. Without heat recovery this heat is dissipated in the environment via the finned condenser coils. The diagram below shows the partial heat recovery circuit. The cooling and hydraulic circuit diagrams are included with all ARA units with heat recovery.
Heat Recovery Diagram
SAC
PE
VE
D
C
CA
MV
Refrigerant Circuit
(Inside unit)
M
VS
Water Circuit
(Not supplied by Uniflair)
VS
A
VM
In order to ensure the correct functioning of the chillers avoid that the heat recovery plate exchanger D is powered by water which is too cold. For this reason use of a three way valve VM is strongly advised yet remains the responsibility of the installer (see diagram). Heat recovery uses plate heat exchangers located on the output line before the air-cooled condensers and supplied with water from the user system. Condensation control, as described above, is included in units with heat recovery.
INSTALL a metal filter on the piping at the unit intake to stop the heat exchanger getting blocked by flakes of welding or rust.
VM
motoriste 3-way valve
VS
water safety valve
VE
expansion tank
PE
circulation pump
SAC
reservoir tank
MV
fan
CA
finned condenser coil
C
compressor
D
heat recovery plate
exchanger
VSA
safety valve