After decommissioning, this appliance must not be disposed of as mixed urban waste.
Separate waste collection is mandatory for this type of waste, in order to allow the recovery and reuse of the
materials making up the appliance.
Please contact operators authorised for the disposal of this type of appliances
Incorrect management of waste and of its disposal has potential negative eects on the environment and human health
The symbol on the appliance, represents the prohibition to dispose of the product as mixed urban waste.
2
Attention: this manual contains instructions for the exclusive use of the professionally qualied installer and/or maintenance
technician in compliance with current legislation.
The user is NOT qualied to intervene on the boiler.
The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from failure to comply with
the instructions contained in the manuals supplied with the boiler
1 GENERAL INFORMATION.................................................................................................................................................4
1.1 General warnings .......................................................................................................................................................4
1.2 Symbols used in the manual ......................................................................................................................................5
1.3 Appropriate use of appliance .....................................................................................................................................5
1.4 Information for system manager ................................................................................................................................5
1.6 Technical data plate ...................................................................................................................................................7
1.7 Water treatment .........................................................................................................................................................8
2.1 Technical features ....................................................................................................................................................10
2.2 Main components view and dimensions ..................................................................................................................10
2.4 Operating data .........................................................................................................................................................13
2.4.1 Technical data according to ErP Directive ......................................................................................................14
2.4.2 Determination of the primary circuit pump or boiler pump ..............................................................................15
ENGLISH
General information
3 INSTRUCTIONS FOR THE INSTALLER .........................................................................................................................16
3.1 General warnings ......................................................................................................................................................16
3.3 Preventive system verication and adjustment operations .......................................................................................16
3.4 Package and Weights ..............................................................................................................................................17
3.9 Filling and emptying the system ................................................................................................................................24
3.12 Measurement of combustion eciency during installation ........................................................................................37
3.12.1 Activation of the calibration function ...............................................................................................................37
3.12.2 Positioning the sensors ..................................................................................................................................37
3.14 Control panel, emergency operation and safety devices ..........................................................................................39
The instruction manual is an integral and essential part of the
product and must be kept by the user.
Read the warnings contained in this instruction manual carefully
as they provide important guidelines regarding installation, use
and maintenance safety.
Keep the manual with care for further consultation.
Your appliance must be installed and serviced in compliance with
the standards in force according to the manufacturer instructions,
up to standard and by legally qualied and certied personnel.
Systems for the production of domestic hot water MUST be
constructed entirely with compliant materials.
By professionally qualied personnel we mean: personnel with
specic technical skill in the eld of heating system components
for civil use, domestic hot water production and maintenance.
Personnel must have the qualications provided for by current
legislation.
Incorrect installation or improper maintenance can cause dam-
age to persons, animals or objects for which the manufacturer
is not responsible.
Before performing any cleaning or maintenance, disconnect the
appliance from the energy mains by acting on the switch of the
system and/or through the specic cut-o devices.
Do not obstruct the terminals of the intake/exhaust ducts.
Any product repairs must be performed solely by personnel
authorised by Unical, using original spare parts only. Failure to
comply with the above can compromise the safety of the appliance and void the warranty.
To guarantee appliance eciency and its correct operation,
yearly maintenance must be performed by qualied personnel.
Should you decide not to use the appliance, parts entailing
potential sources of hazard must be made safe.
Before commissioning an appliance that has not been used,
wash the domestic hot water production system, making the
water ow until it has been fully replaced.
Should the appliance be sold or transferred to a new owner or
if you move and leave the appliance, always make sure that the
instruction manual accompanies it so that the new owner and/
or installer can refer to it.
Only original accessories must be used for all appliances with
optional features or kits (including electric ones).
This appliance is intended solely for the use for which it was
expressly designed.
Any other use is to be considered improper and therefore dangerous (*)
(see 1.7 Water Treatment).
In the event of failure and/or malfunctioning of the appliance,
switch it o and do not try to repair it or intervene on it directly.
Contact only personnel qualied in compliance with law.
ATTENTION
THE THERMAL UNIT MUST BE INSTALLED IN SUCH A WAY AS TO AVOID, IN
THE ENVISAGED OPERATING CONDITIONS, THE LIQUID IT CONTAINS
FROM FREEZING AND PREVENT COMMAND AND CONTROL PARTS
FROM BEING EXPOSED TO TEMPERATURES BELOW -15°C AND ABOVE
THE THERMAL UNIT MUST BE PROTECTED FROM CLIMATIC/ENVIRONMEN-
TAL VARIATIONS WITH:
+40°C.
- The insulation of hydraulic pipes and condensation drain
- The use of specic antifreeze products in the hydraulic system.
4
1.2 - SYMBOLS USED IN THE MANUAL
When reading this manual, pay special attention to the parts marked by the symbols shown:
DANGER!
Serious danger
to safety
and health
DANGER!
Danger of burns!
ATTENTION!
Possible dangerous
situation for the product
and the environment
OBLIGATION!
wear protective
gloves
1.3 - APPROPRIATE USE OF APPLIANCE
The boiler has been constructed according to the current level of engineering and acknowledged technical
safety rules.
Nonetheless, improper use could result in hazards for the safety and life of the user or other persons, i.e.
damage to the appliance or other property.
The appliance is designed to work in heating systems, with hot water circulation, for the production of
domestic hot water.
Any other use shall be considered as misuse.
UNICAL will not be held liable for any damage resulting from improper use.
Use according to the intended purposes also includes strict compliance with the instructions in this manual.
NOTE!
Tips
for the user
NOTE!
For further details
refer to the Technical Informa-
tion:
at the address indicated
on page 2.
1.4 - INFORMATION FOR THE SYSTEM MANAGER
The user must be instructed on use and operation of the heating system, in particular:
• Deliver these instructions to the user, as well as other documents concerning the appliance inserted in the envelope
inside the packaging. The user must keep this documentation safe for future reference.
• Inform the user about the importance of the air vents and the ue gas exhaust system, highlighting their essential
features and the absolute prohibition of modifying them.
• Inform the user on how to control the system's water pressure as well as operations to restore it.
• Inform the user on correct temperature control, control units/thermostats and radiators for saving energy.
• Please note that, in compliance with the standards in force, the inspection and maintenance of the appliance must
be carried out in compliance with the regulations and frequency indicated by the manufacturer.
• Should the appliance be sold or transferred to a new owner or if you move and leave the appliance, always make
sure that the instruction manual accompanies it so that the new owner and/or installer can refer to it.
The manufacturer will not be held liable in the event of damage to persons, animals or objects resulting from
failure to comply with the instructions contained in this manual.
5
1.5 - SAFETY WARNINGS
ATTENTION!
The appliance must not be used by children.
The appliance may be used by adults and only after carefully reading the operating
instructions manual for the user / person in charge.
Children must be supervised so they do not play or tamper with the appliance.
ATTENTION! The appliance must be installed, adjusted and maintained by profes-
sionally qualied personnel, in compliance with the standards and provisions in force.
Incorrect installation can cause damage to persons, animals and property for which
the manufacturer cannot be held liable.
DANGER! NEVER attempt performing maintenance or repairs on the boiler on your
own initiative.
Any work must be done by professionally qualied personnel. We recommend stipulating a maintenance contract.
Insufcient or irregular maintenance can jeopardise the operating safety of the appliance and cause damage to persons, animals and property for which the manufacturer
will not be held liable.
ATTENTION! Modifying parts connected to the appliance (upon
completing appliance installation)
Do not modify the following parts:
- the boiler
- the gas, air, water and electricity supply lines
- the ue gas pipe, the safety valve and the exhaust pipe
- the construction parts which affect the operating safety of the appliance
ATTENTION!
To tighten or loosen the screwed ttings, use only appropriate xed spanners.
Incompliant use and/or inappropriate tools can cause damage (e.g. water or gas
leakage).
ATTENTION!
Indications for propane gas-red appliances
Make sure that the gas tank has been deaerated before installing the appliance.
For state-of-the-art tank venting, contact the LPG supplier or person qualied in
compliance with the legal requirement.
If the tank has not been professionally deaerated, ignition problems could arise. In
that case, contact the supplier of the LPG tank.
DANGER Gas smell Should a smell of gas be perceived, follow these safety guidelines:
- do not turn electrical switches on or off
- do not smoke
- do not use the telephone
- close the gas shut-off valve
- ventilate the area where the gas leakage has occurred
- inform the gas supplier or a company specialised in the installation and maintenance of heating systems.
DANGER! Explosive and easily ammable substances
Do not use or store explosive or easily ammable materials (e.g. petrol, paints, paper)
in the room where the appliance is installed.
6
/
DANGER! Do not use the appliance to support any object.
Specically, do not place any liquid containers (Bottles, Glasses, Containers or
Detergents) on top of the boiler.
If the appliance is installed inside a box, do not insert or place other objects inside it.
1.6 - TECHNICAL DATA PLATE
ENGLISH
The CE Marking
certies the appliance compliance with the essential safety requirements dened in the applicable European Directives and
Regulations and that its operation meets the technical standards
of reference.
The CE marking is axed on each individual appliance by a
special label.
The EC declaration of conformity, issued by the Manufacturer
pursuant to international regulations, can be found in the documentation accompanying the product.
The technical data plate can be found under
the casing, on the front xing crosspiece. ITS
DUPLICATE is placed next to the temperature
control unit.
KEY:
1 = CE monitoring body
2 = Type of boiler
3 = Boiler model
5 = (S.N°) Serial Number
6 = P.I.N. Product Identication Number
7 = Types of approved ue gas exhaust congurations
8 = (NOx) NOx Class
A = Heating circuit characteristics
9 = (Pn) Effective nominal output
10 = (Pcond) Effective output in condensation
B = Domestic hot water circuit characteristics
15 = (Qnw) Rated heat output in domestic hot water function
(if different than Qn)
16 = (D) Specific D.H.W. flow rate according to EN625-
EN13203-1
19 = (PMW) Max. domestic hot water operating pressure
20 = (T max) Max. domestic hot water temperature
General information
C = Electrical characteristics
21 = Electrical power supply
22 = Consumption
23 = Protection rating
D = Countries of destination
24 = Direct and indirect countries of destination
25 = Gas category
26 = Supply pressure
E = Factory settings
27 = Adjusted for gas type X
28 = Space for national brands
G = ErP
29 = Seasonal energy efciency to heat the room
30 = Seasonal water heating energy efciency.
7
1.7 - WATER TREATMENT
Feed water treatment prevents problems and
maintains the functionality and eciency of the
generator over time.
The ideal water pH in heating systems must be
within:
VALUEMIN MAX
PH6.58
Hardness [°fr]915
To minimise corrosion, it is crucial to use a corrosion inhibitor; in order for it to work properly,
the metal surfaces must be clean.
(see system protection ACCESSORIES sect. in
domestic price list)
ATTENTION!
ANY DAMAGE TO THE BOILER CAUSED BY
THE FORMATION OF SCALING OR BY CORROSIVE WATER WILL NOT BE COVERED BY
THE WARRANTY.
ATTENTION (*) see general warnings 1.1:
The heating only models are NOT suitable
for the production of water for human consumption according to Ministerial Decree
D.M. 174/2004.
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
8
1.8 - BOILER ANTIFREEZE
PROTECTION
It is activated by default
This protection can trigger only if the electricity
and gas supplies are connected.
If one of the two is not available and upon reset
11 (SM) a temperature level between 2 and
5°C is detected, the appliance will behave as
described in the table below, pos 2.
The heating system can be protected eectively
from frost by using antifreeze products with
inhibitor for heating systems (specic for multi-
metal)
Do not use car engine antifreeze products as
they could damage the water gaskets.
ENGLISH
P
O
S
1ONON< 7 °CON- Burner and Pump ON until T > 15°C
2
(*) SR Sensor par. 2.2
Supplies11 - SR (*)Status
ElectricGas
ONOFF
< 5 ÷ 5 °COFF
OFFONOFFIgnition inhibited.
OFFOFFOFFIgnition inhibited.
ANTIFREEZE FUNCTION
Actions
antifreeze func-
tion
FAULT SIGNAL CODE 16
(see par. 4.4 ERROR CODES).
Ignition inhibited.
Technical Features
9
TECHNICAL FEATURES AND DIMENSIONS
2
NOTE!
2.1 - TECHNICAL FEATURES
2.2 - INTERNAL VIEW WITH THE INDICATION OF THE MAIN COMPONENTS
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
10
ENGLISH
Technical Features
KEY
No.C.E. S.E.Description
1UyControl panel
2VGGas valve
3Burner cover
4E. ACC.Ignition electrode
5E. RIL.Detection electrode
7 TLLimit Thermostat
8Burner
9Silicon Aluminium Heat Exchanger
10SLCondensate level sensor
11
12Frame
Flue gas outlet LEFT, RIGHT, REAR side
Flow LEFT side
Return LEFT side
Gas inlet LEFT side
Combustion eciency at nominal load%97.8
Combustion eciency with reduced load%98.5
Casing heat loss with burner on (Qmin)% 5.04
Casing heat loss with burner on (Qn)%0.1
Net ue gas temperature tf-ta (min)(*) °C31
Net ue gas temperature tf-ta (max)(*)°C 46.046.746.746.746.745.8
Maximum permitted temperature°C100
Maximum operating temperature°C85
Flue gas mass ow rate (min)kg/h25
Flue gas mass ow rate (max)kg/h558693866104012131386
Excess air%24.25
Heat loss at chimney with burner on (min)%1.5
Heat loss at chimney with burner on (max)%2.402.582.532.512.582.58
Minimum heating circuit pressurebar0.5
Maximum heating circuit pressurebar6
Water contentL67 67 80 94 108 122
3
Methane gas consumption G20 (sup.p. 20 mbar) at Qn m
Methane gas consumption G20 (sup.p. 20 mbar) at Qmin
Gas consumption G25 (sup.p. 20/25 mbar) at Qnm
Gas consumption G25 (sup.p. 20/25 mbar) at Qminm
/h36.8045.6857.1068.5279.9491.36
m3/h2.33
3
/h42.8053.1366.4179.6992.97106.25
3
/h2.71
Propane gas consumption (sup.p. 37/50 mbar) at Qnkg/h27.0133.5341.9250.3058.6867.01
Propane gas consumption (sup.p. 37/50 mbar) at Qmin kg/h1.71
Chimney base maximum pressure availablePa100
Max condensate productionkg/h59.173.491.711 0128.4146.7
Emissions
CO at maximum heat output with 0% of O2 (PCI)mg/kWh557276877276
NOx at maximum heat output with 0% of O2 (PCI)mg/kWh565252585557
(***) Sound pressure level dB (A)545454545456
ENGLISH
Technical Features
Electrical data
Power supply voltage/frequencyV/Hz230 / 50
(**) Protection ratingIPX5D
Room Temperature = 20°C
(*) Temperature detected with appliance operation ow 80°C / ret. 60°C
(min/max) See ‘’NOZZLES - PRESSURE’’ table
CO
2
Seasonal Energy Eciency
Leaks upon stop at ∆T 30°C - Pstb - see
Electricity consumption on standby - Psb - see
according to 2009/125 EEC (<=400Kw)
ErP table
ErP table
ηs - see ErP table
(***) at 1 m away in free eld.
(**) The IP protection rating is obtained with the cover down
13
2.4.1 - TECHNICAL DATA ACCORDING TO ErP DIRECTIVE
MODULEX
EXT 348 EXT 440 EXT 550 EXT 660 EXT770 EXT 900
ElementSymbolUnit
Eective nominal output PratedkW342424530636743849
Seasonal energy eciency of
central heating
Season eciency class for
heating
ƞ
s%93
A*****
For boilers for central heating
and mixed boilers:
eective heat output
Eective heat output with
high temperature capacity
P
4kW341.7-----
(Tr 60 °C / Tm 80 °C)
Rated heat output eciency
with high temperature capacity
4%88.5-----
ƞ
(Tr 60 °C / Tm 80 °C)
Eective output at 30% of the rated heat
output with low temperature
1kW11.5-----
P
capacity (Tr 30 °C)
Performance at 30% of the rated heat
output with low temperature
ƞ
1%96.2-----
capacity (Tr 30 °C)
Boiler with output range adjustment: YES / NO NONONONONONO
Auxiliary electricity consumption
With a full loadelmaxkW0.3930.6260.7830.9401.0961.252
With a partial load elminkW0.054
Standby modeP
SBkW0.020
Other elements
Heat dispersion on standbyP
Nitrogen oxides emissions ref. PCSNOx
stbkW0.21140.21140.21140.2114 0.2114 0.2114
Mg/kWh
49
NOx class 6
Annual electricity consumptionQ
HEGJ105013031633195922862612
For mixed heating appliances
Declared load prole-------
Water heating
energy eciency
wh%-------
ƞ
Daily consumption of electricityQeleckWh------Daily consumption of fuelQfuelkWh------Internal sound power levelLwadB (A)------Annual electricity consumptionAECkWh------Annual fuel consumptionAFCGJ-------
Seasonal DHW eciency class
14
-------
2.4.2 - DETERMINATION OF THE PRIMARY CIRCUIT PUMP OR BOILER PUMP
The boiler pump must have head that is able to ensure the
pump's ow rates according to the circuit's ∆t.
The pumps must be determined by the installer
or designer according to the boiler and system data.
MODULEX EXT 440
Maximum ow rate in l/h (∆t=15K)24,326
Requested rated ow rate in l/h (∆t=20K)18,243
MODULEX EXT 550
Maximum ow rate in l/h (∆t=15K)30,404
Requested rated ow rate in l/h (∆t=20K)22,804
MODULEX EXT 660
Maximum ow rate in l/h (∆t=15K)36,487
Requested rated ow rate in l/h (∆t=20K)27,365
The pump is not an integral part of the boiler.
It is recommended to select a pump with a ow rate
and head of approximately 2/3 of its characteristic
curve.
ENGLISH
MODULEX EXT 770
Maximum ow rate in l/h (∆t=15K)42,570
Requested rated ow rate in l/h (∆t=20K)31,926
MODULEX EXT 900
Maximum ow rate in l/h (∆t=15K)48,647
Requested rated ow rate in l/h (∆t=20K)36,487
O)
2
Pressure drop (mH
FLOW RATE l/h
EXAMPLE:
For a ∆T 20K, of a MODULEX 900, the maximum
water ow rate required is 36,289 l/h.
The graph of the boiler pressure drops shows that
the pump must ensure a head of at least 1.6 m/H2O
Technical Features
NOTE:
It is always advisable to use a hydraulic separator (*) between
the boiler circuit and the system.
(*) For the features, refer to the SPINOX
installation manual, available on the website.
15
3
INSTRUCTIONS FOR
INSTALLATION
3.1 - GENERAL WARNINGS
ATTENTION!
This boiler is intended solely for the use it
was expressly designed for. Any other use
is considered improper and therefore dangerous.
This boiler heats water at a temperature
lower than the atmospheric pressure boiling
temperature.
Before connecting the boiler, have professionally
qualied personnel:
a) Thoroughly wash all of the system piping
to remove any residues or impurities
which could jeopardise proper operation
of the boiler, even from a hygiene point of
view.
b) Check that the boiler is set up to operate with
the type of fuel available.
The type of fuel can be seen written on the
package and on the technical feature plate.
c) Check that the chimney/ue has an appro-
priate draught, without any bottlenecks, and
that no exhausts from other appliances are
inserted, unless the ue has been implemented to accommodate several utilities according
to specic standards and requirements in
force. Only after this check can the tting be
mounted between the boiler and chimney/ue.
ATTENTION!
In rooms with the presence of aggressive
vapours or dust, the appliance must operate
independently from the air inside the installation room!
ATTENTION!
The appliance must be installed by a qualied
technician with the technical-professional
requirements according to law 46/90 which,
under his own responsibility, guarantees
compliance with standards according to
good practice rules.
ATTENTION!
Mount the appliance respecting the minimum distances required for installation and maintenance.
The boiler must be connected to a heating system
compatible with its performance and output.
3.2 - STANDARDS FOR INSTALLATION
It must be installed by a professionally qualied technician, who
shall take the responsibility of observing all local and/or
national laws published in the Ocial Journal, as well as
applicable technical standards.
3.3 - PREVENTIVE SYSTEM VERIFICATION
AND ADJUSTMENT OPERATIONS
Before installing this appliance on old systems, check that:
- The chimney is suitable for appliances with condensation, at
combustion products temperatures, calculated and built in
compliance with the standards in force in this regard.
Is as straight as possible, airtight, insulated, and has no
obstructions or constrictions.
- The chimney is equipped with a tting to drain
condensate.
- The boiler room is equipped with a duct to drain condensate
produced by the boiler.
- The electrical system has been set up by a qualied technician in compliance with the rules in force.
- The rate, head and direction of the ow of the circulation
pumps are appropriate.
- The fuel adduction line and the tank, if any, are made according to relevant standards in force.
- The expansion vessels can fully absorb dilation of the uid in
the system.
- The system has been cleaned from sludge and scaling.
16
3.4 - PACKAGING
The boiler MODULEX is supplied assembled in a sturdy cardboard box.
After removing the two straps, remove the cardboard from the top and ensure the integrity of the
contents.
Keep the packaging material (cardboard box,
straps, plastic bags, etc.) out of the reach of chil-
dren as they are potential sources of danger.
Unical will not be held liable for damage to per-
sons, animals or objects due to failure to comply
with the above instruction.
OBLIGATION!
wear protective gloves
- Transport the boiler using suitable transportation means.
- Protect all parts against impacts if they must be transported.
- Follow the transport instructions on the packaging.
• The boilers must always be lifted and carried with a carrying
trolley or equipment suitable for transport.
To remove the boiler from the pallet, it is necessary to have a
rocker crane, to avoid damage during gripping.
- Remove the casings and harness with the straps “A”, taking
care to pass the straps on the load-bearing crosspieces of
the frame
- Tie the straps to the rocker arm “B”, operating with caution.
Gasket between pan and terminal.
Collar gasket (Ø 250) Ø 300.
Two elbows + a Tee + a plastic
condensate drain plug
The screws necessary for xing the ue gas terminal
- The sensors: external, heater.
- The ue inspection cap
- Sheet and cable glands for power supply output
- A cardboard box containing:
The anges
Inside the rear side casing:
- The condensate drain trap pipes (1 m)
Above the boiler cover:
A plastic bag containing:
- Instruction manual for the installation and maintenance
technician
- Uy control unit operating manual
- BCM 2.0 manual
- Hydraulic test certicate
- Certicate of conformity
- Warranty certicate (IT only)
- Warranty extension 10 A (IT only)
- INAIL certicate (IT only)
- Spare parts coupon (IT only)
- Dowels to lock the fan set in raised position (use only
for models 100 ÷ 350 kW)
Gross
Weight
ENGLISH
Installation instructions
17
3.4.1 - UNLOADING AND REMOVING THE PACKAGING
1
Max. admitted boilers
stacked
Do not turn upside down Do not expose to rain FragileDo not expose to sunlight Do not store at
temperature:
lower than - 5 ° C / 23 °F
superior than 50 °C / 122 °F
T max
50°C/122°F
T min
-5°C/23°F
2
Max. admitted boilers
stacked
Do not turn upside down Do not expose to rain FragileDo not expose to sunlight Do not store at
temperature:
lower than - 5 ° C / 23 °F
superior than 50 °C / 122 °F
T max
50°C/122°F
T min
-5°C/23°F
3
Max. admitted boilers
stacked
Do not turn upside down Do not expose to rain FragileDo not expose to sunlight Do not store at
temperature:
lower than - 5 ° C / 23 °F
superior than 50 °C / 122 °F
T max
50°C/122°F
T min
-5°C/23°F
4
ATTENTION!
Handling with forklift or strap hoist,
ATTENTION!
Strap passage points for lifting. The straps must
be mounted on the load-bearing crosspieces.
18
3.5 - POSITIONING IN THE BOILER ROOM
A> 400 mm
B > 400 mm
C = 100 mm
D= 500 mm
Szifon
Special attention must be paid to the standards and local laws
with regard to boiler rooms, especially the minimum distances
that must be kept free around the boiler.
Installation must comply with the provisions in the most recent
standards and laws in force with regard to boiler rooms, installation of heating systems and domestic hot water production,
ventilation, suitable chimneys to drain combustion products from
condensate boilers and anything else applicable.
The boiler can be placed on a at and suciently sturdy base,
with a size, in the plan, not inferior to that of the boiler and at
least 100 mm high (see gure) in order to be able to mount the
siphon for condensate draining. As an alternative to this base,
a sump can be obtained on the oor, next to the boiler, with a
100 mm depth for housing the siphon (see gure).
When installation has been performed, the boiler must be perfectly horizontal and stable (to reduce any vibrations and noise).
Comply with the minimum clearance distances in
order to execute normal maintenance and cleaning
operations.
ENGLISH
C
A
B
D
Installation instructions
SIPHON
19
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
To connect the ue gas exhaust pipe, local and national standards must be observed
The boiler is type approved for the exhaust congurations listed
below:
B23P
Connection to a combustion products evacuation pipe outside
the room; the combustion air is taken directly from the room
where the appliance is installed.
HEAD AVAILABLE AT THE BASE OF THE CHIMNEY
The maximum permitted length of the pipes is determined
by the head (∆p) available at the base of the chimney.
ATTENTION
For this type of connection, the room follows the
same installation rules for boilers with natural
draught.
D (Drain)I (Intake)
∆p = 100 Pa
-
C63
Separate combustion air intake and combustion products
evacuation pipes. (Commercial accessories)
HEAD AVAILABLE AT THE BASE OF THE CHIMNEY
The maximum permitted length of the pipes is determined
by head (∆p) available at the base of the chimney.
ATTENTION
For the C63 conguration, you must order
the optional air intake kit, which contains the
installation instructions.
D (Drain) + I (Intake)
∆p = 100 Pa
ATTENTION:
for B23P types of connection, the
room follows the same installation rules
for natural draught
boilers.
3.6.1- MANIFOLD CONNECTION
EXHAUST PIPE
Use the nuts and washers contained in the bag to
x the ue gas exhaust manifold.
The ue gas inlet must be positioned on the rst
straight section within 1 metre from the boiler.
To create the ue gas inspection inlet, make one
Ø 21 mm hole in the ue gas outlet pipe and t the
inspection inlet following the indicated sequence.
ATTENTION:
The chimney must comply
with the standards in force.
20
3.7 - BOILER CONNECTION
F
F
G
F
RM
The MODULEX boiler leaves the factory ready for hydraulic
(ow and return), gas connections on the left side of the boiler.
To x the ue gas exhaust manifold, use the screws and gaskets
contained in the accessory kit box and a 10 mm socket wrench.
The ue gas manifold is set-up on the LEFT SIDE, the outlet can
also be set-up on the RIGHT and REAR SIDE.
ENGLISH
Collector mounted on the rst and last element of the ow
manifold Ø 18 (A), inside Ø 27 (B)
Gaskets mounted on all other elements (C).
Collectors and Gaskets
A
B
A
Installation instructions
C
21
3.8 - CONNECTION
GGAS G 3’’
Danger!
The gas must be connected only by a qual-
ied installer who must respect and apply
the requirements set forth by relevant laws
in force and by the local prescriptions of
the supply company. Incorrect installation
can cause harm to persons and animals and
damage property for which the manufacturer
shall not be held liable.
If you smell gas:
a) Do not operate electrical switches,
the telephone or any other object that
may cause sparks;
b) Immediately open doors and
windows to create air current
to air out the room;
c) Close the gas valves.
d) Request the intervention of professionally
qualied personnel.
MFLOW G 4’’
RRETURNG 4’’
Make sure that the system pipes are not used as
earthing electrodes of the electric or telephone
system. They are absolutely not suitable for this
type of use. Serious damage could result for the
piping, boiler and radiators in a short amount
of time.
ATTENTION!
IT IS STRICTLY FORBIDDEN TO FIT SHUTOFF DEVICES ON THE GENERATOR BEFORE
THE SAFETY DEVICES.
As a precaution against gas leaks, we recommend installing a monitoring and protection
system consisting of a gas leak detector
coupled with a shut-o solenoid valve on the
gas feed line.
22
Condensation drain
H min 100 mm
150
C
B
150**
25*
A
The boiler, during the combustion process, produces conden-
sation that, through pipe “A”, ows into the trap.
The condensation that forms inside the boiler ows
into a suit-
able drain via pipe “B”.
Danger!
Before commissioning the appliance:
- check that the siphon is assembled correctly
- ll the siphon through the ller cap C and
check correct drainage of the condensate
If the appliance is used with an empty conden-
sation drain trap, there is an intoxication hazard
due to the release of exhaust gases.
FRONT SIDE
The outlet of the condensate drainage pipe is towards the con-
nection side of the ue gas box manifold, removing the pre-cut
part on the covering panel.
The upper generator
of the drain pipe
must not be higher than
the bottom of the pan.
ENGLISH
BOILER ROOM
FLOOR
* Minimum safety siphon set by the standard
** Minimum head with boiler running at maximum power.
The connection between the appliance and the
domestic wastewater system must be made in
compliance with the specic reference standards.
AT
BLOW DOWN
DRAINAGE
If you do not want to or cannot create a base,
the boiler can be mounted at ground level and
a sump at least 100 mm deep can be made to
house the siphon
NOTE!
For further details
refer to the Technical Information
from the website
Installation instructions
23
3.9 - FILLING AND EMPTYING
THE SYSTEM
When all system connections have been com-
pleted, the circuit can be lled.
To ll the system, you must provide a lling
valve on the system's return.
EXAMPLE OF THE SYSTEM'S LOADING UNIT
UNIT OF
LOADING
To ll the system, you must provide a lling valve on
the heating circuit, or use the optional accessories.
The boiler is equipped with its own drain valve, 14
This valve can never be used to drain the system
since all the dirt in the system can accumulate
in the boiler and jeopardise its proper operation.
Therefore, before using the drain valve, make sure
the system's check valve, which is situated under
the pump, has been closed.
The system must be equipped with its own
drain valve, which is to be suitably sized according the system's capacity.
24
ENGLISH
PAGE LEFT INTENTIONALLY BLANK
Installation instructions
25
3.10 - ELECTRICAL CONNECTIONS
F1
AE
G
H
F
I
18:28
giov 30 20ott 18
effettiva
richiesta
76°C84
°C
generatore
10/10
modulazione
100
%
INFO MENU
status
sanitaria
25
°C
678910 11 12 FL TA
INAIL
Y2- BCM
12345
1
Y3- BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4- BCM
23
B
1
2
3
4
5
6
7
A2
A1
A4
A3
Y2
Y1
Y3
GND
A5
1
2
1
2
3
M1
M2
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4
56
789101112
123
4
5678
Y1
1
2
34
A2
1
2
34
A3
A1
123
456
ROD1 ROD
F1
A4
51
50
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4
56
789101112
123
4
5678
Y1
1
2
34
A2
1
2
34
A3
A1
123
456
ROD1 ROD
F1
A4
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4
56
789101112
123
4
5678
Y1
1
2
34
A2
1
2
34
A3
A1
123
456
ROD1 ROD
F1
A4
D
NPE
L1
NPE
L1
F1
A8
3214
7658
321
A7
456
A5
2
1
A6
2
1
123
456
789101112
123
4
5678
Y1
1
2
34
A2
1
2
34
A3
A1
123
456
ROD1ROD
F1
A4
52
53
00330914
ATTENZIONE!
ATTENTION!
ACHTUNG!
ATENCIÓN!
ATTENTIE!
UPOZORNÌNÍ!
230 V
!
Danger!
Before performing connections or any type of
operation on electrical parts, always disconnect
the electrical power and make sure that it cannot
be reconnected accidentally.
KEY
No.Description
ABCMBoiler controller
BServices connection return terminal board
DWieland mobile pow. supp. socket 230 V -
50Hz
EUy P heating controller
FLTGLTLG triggering lamp
GF1Power supply fuse 6.3 AT 250V
HBoiler Main switch
ILTGLManual reset main limit thermostat
50BMMBurner management board
51Power supply board
52F1Power supply fuse 6.3AF 250V
53F1BMM Board Fuse 6.3AF 250V
26
Danger!
Only a qualied technician may perform the
electrical installation.
Electrical connection to the main power supply.
This connection must be made up to standard, as
required by regulations in force.
Electric power supply connection
Remember that a bipolar switch must be installed
on the boiler power line with over 3 mm between
contacts, easy to access, making maintenance
quick and safe.
The power supply of the boiler, single-phase 230
V - 50 Hz, must be made with H05VV-F type
three-pole cable
(PHASE - NEUTRAL - EARTH)
with 0.75 mm section up to 1.5 mm.
ATTENTION!
Respect the PHASE and NEUTRAL polarity
since ame detection is Phase Sensitive.
ATTENTION:
The 230 V cables must run far apart from 24V
cables.
ENGLISH
- Make the power supply connection on the “D” plug, sup-
plied with the boiler.
N.B. 24 V - 230 V output - Keep the 2 voltages separate
Installation instructions
27
NOTE:
P.
Coll.
P.
CH
P. Car.
DHW
1
2
3
Y5
0
1
2
3
4
5
6
7
8
9
2
3
4
Y3
1
5
4
3
2
1
Y1
J1P
Modbus
INAIL
SAFE
INPUT 0-10V
1
Y3 -BCM
Y2 -HSCP/UFLY
56
843
Y1 -BMM1
4321
Y4 -BCM
23
INAIL
Modbus
BCM
Ufly
The boiler is set up for direct ow and storage tank
management.
If Stemp. ACC is connected automatically, DHW is
activated, which will have priority management with
regard to direct ow through the pumps shown below.
Should additional services be requested (storage tanks, mixed
areas, solar, etc), you must purchase SHC multifunction kits for
full control through the Uy P heating control.
At the
corresponding
terminal boards
of the boards in
the
boiler
Alarm
signal
12345
(-) GND
(+) 0-10V
678910 11 12 FL TA
Y2 -BCM
28
Alim.
230V
C.P. M.
P.
Mod.
SE
+
Stemp.
ACC
FL
TA
Connections for:
1
2
3
Y5
0
1
2
3
4
5
6
7
8
9
2
3
4
Y3
1
2
3
4
1
5
6
7
Y4
5
4
3
2
1
765
8
4
3
2
Y2
Y1
1
J1P
SHC
Modbus
Ufly
Y2 BCM
Modbus BCM
A
B
1
2
Remote boiler control
A (1) Data connection
B (2) Data connection
P. mod4 - 5 Modulating heating pump
SE6 - 7External sensor
- / +6 - 70 / 10 V signal contact
Stemp ACC
( * )
6 - 8Storage Tank Temperature
Sensor
FLFL - 10 Flow switch (remove jumper)
INAIL11-12Safety devices
(remove jumper)
TATA - 9Room thermostat / Clock
remove jumper
Y4 - BCM
Alarm signal
(**)
3 - 4Alarm / signal contact
(NO potential-free contact)
P. Coll.1 - 2 Manifold pump (primary loop)
Y3 - BCM
P. CH1 - 3Heating circuit pump
P. Car DHW1 - 2Storage Tank loading Pump
UFLY
Y2 -
Modbus Uy
A
B
5
6
Remote Temperature
A (5) Data connection
B (6) Data connection
Control
Y1 BMM1
SHC
(***)
8 - 4 - 3Optional multifunction module
(to be inserted in the box cover)
ENGLISH
( * )
If the storage tank temperature sensor is connected, DHW service is automatically activated on boiler power supply.
Parameter (803) Srv (is automatically updated).
( ** )
Relay contact that closes when in alarm mode
( *** )
SHC optional
The system can power only one SHC module.
If you need to have more than one SHC module, they must be
placed externally in a dedicated electrical panel and
powered with their own power supply unit.
Installation instructions
The BCM and SHC relay contacts support
pumps with max. 4A absorption.
Modbus BCM
can be used for control from building automation,
can also be connected
with Modbus Uy to have a single bus.
29
PAGE LEFT INTENTIONALLY BLANK
30
Connection diagram example:
1
NPEL1
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
FL
1
CCCNCNCNO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
SE
Menu
B
Power supply, INAIL, Modulating pump, External sensor, Flow switch
230 V - 50 Hz
N
PE
L1
ENGLISH
PE
L1
2
D
N
KEY
No.Description
1INAIL - Safety bodies
2Main electrical panel (not supplied)
BServices connection return terminal board
DWieland mobile pow. supp. socket 230 V -
50Hz
FLTerminals for Flow switch
SETerminals for external Sensor
SMGGlobal ow sensor
P on_oManifold Pump Connections (on_o)
P modModulating pump Connections
Installation instructions
31
Connection diagram example: 2 modulex in pack managed by cascade manager
CH
P.
CH
Y4
1
2
3
4
1
2
3
123
4
5
6
Y3
Y2
1211 10 98765
4321
0
1
2
3
4
5
6
7
8
9
981011121314
2134567
Jp2
SE
24 V -DC
CM 140 - cascade manager
24 V -DC
BR
BK
R
S
M
G
FL
D
230 V - 50 Hz
L1
PE
N
2
L1
PE
N
1
CCCNCNCNO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
1
NPEL1
Menu
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
D
230 V - 50 Hz
L1
PE
N
2
L1
PE
N
1
NPEL1
Menu
+ 24 V
(-)
eBUS +
1
2
3
4
1
2
3
4
5
6
7
Menu
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
eBUS -
eBUS +
FL
1
CCCNCNCNO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
eBUS -
eBUS +
B
B
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
primary loop
(*) Note:
For the cascade connection,
position the selector on the BCM
in the indicated position.
(*)
(*)
(*) Note:
For the cascade connection,
position the selector on the BCM
in the indicated position.
32
CH
C
P.
CH
P. Car.
DHW
Stemp.
ACC
Y4
1
2
3
4
1
2
3
123
4
5
6
Y3
Y2
12 11 10 98765
4321
0
1
2
3
4
5
6
7
8
9
981011121314
2134567
Jp2
L
with direct zone and DHW production.
secondary loop
ENGLISH
Note:
To congure cascade boiler management parameters, refer to the specic installation manual.
Note:
Installation instructions
In case of installation with single boiler, the above
connections must be made on the return
terminal board (BCM board) inside the boiler.
Note:
Illustrative diagram, consider the total nominal
ow rate, any check valves (not supplied), and
verify the eciency of the ow switches at each
ow rate in modulation.
qualied personnel. Unical will not be held liable
for damage to persons, animals or objects, due to
failure to comply with the aforesaid instructions.
does the installation meet the specic standards and regulations in force, both relating to the
gas part as well as the electrical part?
do the combustion air intake and ue gas exhaust take place properly according to
what is dened by the specic rules and regulations in force?
is the fuel supply system sized according to the capacity required by the
boiler? Is it equipped with all safety and control devices required by the standards in force?
is the power supply of the boiler 230V - 50Hz?
has the system been lled with water (approximately 0.8/1 bar pressure on the pressure gauge with the pump stopped)?
Has the condensation drain trap been lled with water as indicated in chapter 3.8?
are any system shut-o gate valves open?
does the gas to be used correspond to the boiler calibration gas?: otherwise, perform
the boiler conversion in order to use the gas available;
this operation must be carried out by technical sta qualied in compliance with the standards in force;
is the gas supply valve open?
Before commissioning the boiler, check the following:
ENGLISH
has the system been checked for gas leaks?
is the outside main switch ON?
is the system safety valve ecient and is it connected to the drains?
is the condensation drain trap connected to the drains?
has the system been checked for water leaks?
are the ventilation conditions and minimum distances to perform any maintenance
ensured?
have the GAS, HEATING and DOMESTIC HOT WATER pipes been cleaned thoroughly with products suitable for
each circuit?
has a surveillance and protection system against gas leaks been installed? (Optional)
are the system pipes NOT used as the electrical system earthing?
has the system been sized properly bearing in mind the radiator pressure drops,
thermostatic valves, radiator stop valves?
has the operator been trained and has the documentation been supplied?
Please tick the completed operations
Switching boiler on and o
To switch the boiler on and o, see the Uy regulator manual
Installation instructions
35
3.12 -
3
1
2
4
MEASUREMENT OF THE COMBUSTION EFFICIENCY DURING INSTALLATION Generator Menu
3.12.1 - CALIBRATION FUNCTION (CHIMNEY SWEEP)
ATTENTION!
Function reserved for After Sale
Service Centres only.
3.12.2 - POSITIONING THE SENSORS
To determine the combustion eciency
one must make the following measurements:
- measurement of the combustion air temperature
- measurement of the ue gas temperature and content of
CO2 taken in the relevant hole 2.
Take the measurements with the generator in steady state
conditions (see par. 3.12.1).
ATTENTION!
These functions are explained in
chapter 2.9 (Burner menu) of the
Uy P. TOUCH CONTROL installation and maintenance manual.
All boilers leave the factory already calibrated
and tested. However, if the calibration conditions
should be modied, it is necessary to recalibrate
the gas valve.
ATTENTION!
Remove cap 2, x the red cap 3 to the ue gas
inlet 1. Insert the CO2 analysis sensor 4 in the
cap hole.
Perform the measurement. Remove the cap
and close the ue gas exhaust inlet with the
specic cap 2.
36
3.13 - ADJUSTING THE BURNER
A
B
B
B
A
C
D
All boilers leave the factory already calibrated and
tested, however, if required, recalibrate the gas
valves (MODULE 1, MODULE 2, etc.)
The following instructions are intended exclusively
for authorised service personnel.
ENGLISH
ATTENTION!
To access the gas valves more easily, release the electrical panel
“A” by means of the springs “B” (right and left).
Slightly turn the electrical panel ”A” and lower the tilting panel
“C”.
Fix the tilting panel “C” for the time necessary for the adjustment
operation, using the 2 M4 screws + washers ”D” (contained in
the documentation bag).
Installation instructions
37
- Remove the cap and insert the CO2 analysis sensor in the
ue gas sample point of the intake/exhaust terminal, see
chap. 3.12.2.
1) Maximum output adjustment
- Operate the boiler in “calibration” mode at MAXIMUM OUTPUT (see 3.12.1)
- Once the burner is on, check
that the “MAXIMUM” CO2 output value corresponds to that
indicated in the “NOZZLES - PRESSURE” table.
- If necessary, adjust the value by turning the ‘’S’’ adjustment
screw CLOCKWISE to decrease it and ANTICLOCKWISE
to increase it
(see NOZZLES-CAPACITY-PRESSURE table).
2) Minimum output adjustment
- Operate the boiler in “calibration” mode at MINIMUM OUTPUT
(see 3.12.1)
- Once the burner is on, check that the “MINIMUM” CO2 output
value corresponds to what is indicated in the “NOZZLES PRESSURE” table.
- If necessary, adjust the value by turning (with a 2.5 mm hex
key) screw “R” CLOCKWISE to increase it, ANTICLOCKWISE to decrease it
(see NOZZLES-CAPACITY-PRESSURE table).
(S)
ADJUSTMENT SCREW
MAXIMUM OUTPUT
In case of replacement of the Gas valve or
ignition diculties:
Tighten the maximum adjustment screw ”A”
clockwise up to the stop, then loosen by 7 turns.
Check the boiler ignition, in case of a block,
loosen the screw “A” again by one turn, then try
igniting it again. If the boiler still stops running,
perform the above operations again until the
boiler ignites.
Now adjust the burner as previously illustrated.
(R)
ADJUSTMENT SCREW
MINIMUM OUTPUT
38
Follow this procedure to also adjust the other modules.
1
If the capacity read is too low, make sure the power feed and
drain system (feed and drain pipes) are not clogged.
If they are not clogged, make sure the burner and/or heat exchanger is not dirty.
ENGLISH
ATTENTION
To calibrate the VG (Gas Valves) in the
boiler room, follow the procedures below.
The VG must be calibrated
with chimney pressure = 0 Pa;
for this reason:
- open the smoke duct 1 inspection door,
after calibration, restore the door gasket.
INDICATIVE DIAGRAM, REFERRING TO BOILERS
MODULEX 150 ÷ 350
C) CONCLUSION OF THE BASIC
CALIBRATIONS
- Check the CO2 values at minimum and maximum levels.
- If necessary, make any adjustments.
For proper operation, the CO2 values must be
calibrated with particular attention, observing
the values indicated in the table.
- Close the ue gas inspection inlet (1) with the specic cap
(2 - 3)
NOTE: Do not force the end stroke limits
of the adjustment screw.
NOZZLES - PRESSURE - CAPACITY TABLE
MODULEX EXT: 440 - 550 - 660 - 770 - 900
Type of GasSupply Press.Ø Noz-
[mbar](mm)[Ø/mm]min FLmax FU[%][%]
minmaxIG
Nat. gas (G20) 209NO2996 9.09.050
Nat. gas (G25)259NO2898 9.18.650
Nat. gas (G27)209YES2894 9.19.350
Propane (G31)379NO2890 10.2 10.450
MODULEX EXT: 348
Type of GasSupply Press.Ø Noz-
[mbar](mm)[Ø/mm]minmax[%][%]
minmaxIG
Nat. gas (G20) 209NO2976 9.09.050
Nat. gas (G25)259NO2882 9.18.650
Nat. gas (G27)209YES2894 9.19.350
Propane (G31)379NO2873 10.2 10.450
zles
zles
Fan
deector
Fan
deector
Fan speedCO
Fan speedCO
levels Start.
2
levels Start.
2
power
power
Installation instructions
39
3.14 - EMERGENCY OPERATION AND SAFETY DEVICES
F1
AE
G
H
F
I
18:28
giov 30 20ott 18
effettiva
richiesta
76
°C
84
°C
generatore
10/10
modulazione
100
%
INFOMENU
status
sanitaria
25
°C
The BCM prevents system shutdown if the man-
agement of the Uy system or main boiler system
is out of service
(Refer to the BCM manual)
A
YELLOW LED = ashing
(communication between BMM and BCM) ok
GREEN LED = on (Pump Active)
RED LED = on (Error code detected)
EUy control panel
FTLG triggering lamp Main Limit Thermostat
GFuse
HMain Switch
TLG Main Limit Thermostat, when it triggers it cuts
I
power to the boiler, the F lamp lights up. To rearm,
remove the cap and press.
Condensate level sensor position
NOTE:
The devices are positioned under the casing, next
to the control unit.
NOTE: The emergency function only activates the
boiler burners at 100% on ow. All system loads,
including the manifold pump, must be manually
controlled.
40
3.15 - PROGRAMMING THE OPERATING PARAMETERS
ATTENTION!
ATTENTION!
Function reserved for After Sale
Service Centres only.
BMM parameters
CodeSymbolDescription UnitMin.Max.Imp. Fab.
803SrvEnabled Services01
48
784BCLocal BUS address07
816MIModbus Address1127
817MTModbus Time-outsec.0240
896TU°Fahrenheit01
799ACInput 0/10V02
376DI1Programmable Input #103
322PoPump: Post-circulationmin.130
341PLPump: Minimum Control%0100
313PrPump: Maximum Control%0100
31HLCH#1: Minimum Set-point°C2085
39HHCH#1: Maximum Set-point°C2085
792CHPCH: Max. Modulation%0100
619IGIgnition Modulation%3080
527PUFan: PPR03
486FPFan: Reg. Prop.050
487FIFan: Reg. Int.050
489FplFan: PWM min.%515
337FrModulation Gradient%1.0
526FUFan: Max Max.Hz50120
319FHMaximum Modulation%1.0
346FLMinimum Modulation%1.0
314SbModulation on Standby%0100
620IPPostpurge: Fan%0100
617IGLIgnition: Mod. Min.%0100
618IGHIgnition: Mod. Max.%0100
353HPCH PID: Proportional°K050
354HICH PID: Integrative050
478HdCH PID: Derivative050
34HYBurner Hysteresis°K5.020.0
336HSTemperature Gradient
483rP
380Al1Programmable Sensor #102
777AFCAPS Control02
805LVMains VoltageV100240
2590Burner OutputkW101000
( ) LPG values
ChSet
CH#1: Set-point°C2085
°C/min
Gen: Temp. Max Dierential
°C0.050.0
These functions are explained
in chapter 2.8 (DEVICES menu)
of the Uy P. TOUCH CONTROL
installation and maintenance
manual.
100.0
100.0
100.0
030
ENGLISH
Installation instructions
41
BCM Parameters
CodeSymbolDescription UnitMin.Max.Imp. Fab.
803SrvEnabled Services1627
483rPGen: Temp. Max Dierential°K0.050.0
34HYBurner Hysteresis°K5.020.0
31HLCH#1: Minimum Set-point°C20.040.0
39HHCH#1: Maximum Set-point°C45.085.0
799ACInput 0/10V03
376DI1Programmable Input #102
322PoPump: Post-circulationmin.110
341PLPump: Minimum ControlV010
313PrPump: Maximum ControlV010
792CHPCH: Max. Modulation%0100
611POTGen: Err. Max. Parallel°K030
612POLGen: Mod. Max. Parallel%0100
650dLDHW: Minimum Set-point °C25.045.0
385dHDHW: Maximum Set-point50.065.0
360dtHeater Adjustment0 15
656drTDHW: Temp. Requested Dierential°K -20
20
657drHDHW: Requested Temp. Hysteresis°K 120
310DpTDHW Pump: Postcirc. sec. 5
660dbTDHW: Temp. Maximum Boiler °C 50.0
48ChSetCH#1: Set-point °C20.0
600
85.0
85.0
64ChPO1CH#1: Parallel Supply 0 1
346FLMinimum Modulation %0 100.0
600mBBurners: Min. Inserted1 8
616BStGen: Insertion Timesec. 30 900
613BRtGen: Removal Timesec. 30 900
336HSTemperature Gradient°C/min1 30
353HPCH PID: Proportional °K 0 50
354HICH PID: Integrative °K 0 50
478HdCH PID: Derivative °K 0 50
816MIModbus Address1 127
817MTModbus Time-outsec.0240
896TU°Fahrenheit0 1
309StApplication Code01
368VA1Programmable Relay #101
369VA2Programmable Relay #201
771PSWater Pressure Sensor01
768LGSens. Min. Gas Pressure01
793COCChimney Obstruction Sensor02
622FSMinimum Flow Sensor01
42
3.16 - ERROR CODES
ENGLISH
Fault that causes the boiler to stop:
- The error code is displayed, the boiler has stopped
running. After solving the failure, press Reset to
restart the boiler.
CODEDESCRIPTION
detected on BMM
01
04
05
06
SAFETY THERMOSTAT
Triggering of the safety thermostat (10)
BURNER
No gas or failed burner ignition
FLAME LOSS
DURING
OPERATION.
HIGH TEMPERATURE
Boiler temperature too high
INTERNAL FAULT
SOLUTIONS
Press the release button on the panel and/or check that the thermostat
and its connections are not blocked, and make sure the INTC switches
are closed (position 1)
Check the gas supply or that the ignition/detection electrode is working
properly (4).
Check the detection electrode
Check pump operation and if needed
clean the heat exchanger (24)
Primary circuit water circulation insucient (∆t > 40° C)
HEAT EXCHANGER
FREEZING ( 24 )
Heat exchanger freezing is detected. If
the heating sensor detects a temperature
below 2° C, burner ignition is inhibited
until the sensor detects a temperature
above 5°C.
Check the eciency of the sensor (see Res/Temp table) (Par.4) or its
connections.
Check the wiring, if needed, replace the auxiliary sensor (22)
Check pump operation and its speed - remove any obstructions in the
heating system
Disconnect power, close the gas valve, defrost the heat exchanger
carefully.
Fault that does NOT cause the boiler to stop:
- The error code is displayed, the boiler has a heating request, Reset icon (informing that a failure has
been detected, even if the fault was temporary).
Therefore, you must always carry out reset to cancel the word “Error” displayed.
( Num ) = see key Par. 2.2
Installation instructions
43
22
NO AIR UPON IGNITION
Stop
UNEXPECTED AIR FLOWBlocked min pressure switch (closed)
23
24
26
27
30
32
CODEDESCRIPTION
2
17
19
28
29
37
38
40
56
57
58
SPEED OUT OF CONTROL
Alteration of the fan speed; the speed is
not reached.
SPEED OUT OF CONTROL
Alteration of the fan speed; the speed is
above that requested
NO AIR
Stop
FACTORY PARAMETERS
Alteration of the factory parameters or
possible electromagnetic interferences.
Line voltage at 80% of the nominal value. Wait until the line voltage is > 85%
of the nominal value.
detected on HCM (BCM)
GAS PRESSURE MINIMUM PRESSURE SWITCH TRIGGERED
stop eect
HEAT EXCHANGER
FREEZING ( 24 )
stop eect
FLOW
OVERTEMPERATURE.
It is activated when the ow temperature
is > 95. Resetting is automatically carried
out when the temperature is < 80.
Eect: Stop burner, Pump On
CLOGGED OUTLETS
Stop
WATER IN THE COMBUSTION CHAMBER
Stop
PARAMETERS MEMORY
DEFECTIVE
Flame Block
DAMAGED DEFAULT PARAMETERS
due to electromagnetic interferences
stop
FL INTERVENTION insucient water
circulation Stop
NO REMOTE CONTROL DETECTED
Flame Block
BMM BOARD NOT DETECTED
stop
FLOW SENSOR
Stop
Check that the fan head is at least 60 Pa.
Check fan operation (18) and the connections
Check fan operation (18) and the connections
Check that the fan head is at least 60 Pa.
Press the unblock key; if the anomaly persists, replace the board
Correction: if the line voltage is < 190Vac: the line voltage is really below the minimum limit, otherwise there is a monitor line error: replace
BMM
SOLUTIONS
The ignition procedure is inhibited until gas pressure
reaches the correct values.
Try to Reset since the system automatically activates an antifreeze
function, therefore, it could only be a warning.
Circulation control
Check the Chimneys / Check the trap.
Check the combustion chamber / check the siphon.
Contact Customer Care
Contact Customer Care
Check water circulation
Check electrical connections e-BUS1
check electrical connections BMM and e-BUS
Connect a new sensor if the code disappears, replace the sensor otherwise check the electrical connections
93
The error codes are displayed in the info row of the remote console and remain there even if the fault is temporary.
Therefore, you must always carry out a reset to cancel the word “Alarm” displayed.
44
ISPESL SAFETY DEVICES TRIGGERING
Stop
check the safety devices, manually reset after releasing each individual
safety device
4
INSPECTION AND
MAINTENANCE
Inspections and maintenance performed professionally and according to a regular schedule, as
well as the use of original spare parts, are of the
utmost importance for fault-free operation of the
boiler and to guarantee its long life.
Yearly maintenance of the appliance is mandatory
in compliance with the Laws in force.
4.1 - INSPECTION AND MAINTENANCE
INSTRUCTIONS
To assure long-term functioning of your appliance and to avoid
altering its approved status, only original UNICAL spare parts
must be used.
If a component needs to be replaced:
• Disconnect the appliance from the electrical mains and make
sure that it cannot be reconnected accidentally.
• Close the gas shut-o valve upstream of the boiler.
• If needed, and depending on the intervention to be carried
out, close any shut-o valves on the ow and return line of
the heating system, as well as the cold water inlet valve.
Failure to perform Inspections and Maintenance
can entail material and personal damage
Once all maintenance operations are complete
resume boiler operation
• Open the heating ow and return pipes, as well as the cold
water inlet valve (if closed previously).
• Vent and, if necessary, restore the heating pressure until
reaching a pressure of 0.8/1.0 bar.
• Open the gas shut-o valve.
• Switch the boiler on
• Make sure the appliance is gas tight and watertight.
ENGLISH
OBLIGATION!
wear protective gloves
TABLE OF THE RESISTANCE VALUES ACCORDING TO THE TEMPERATURE, HEATING SENSOR (SR) AND DHW
SENSOR (SS) AND HEATING RETURN SENSOR, IF ANY (SRR)
Relation between the temperature (°C) and the nom. resistance (Ohm) of the heating sensor SR and of the domestic
hot water sensor SS
Example: At 25°C, the nominal resistance is 10067 Ohm At 90°C, the nominal resistance is 920 Ohm
Danger of burns!
Caution during maintenance operations.
Installation instructions
45
We recommend having qualified technical
personnel carry out the provisions of current
regulation concerning periodic maintenance
checks.
Since the dust is vacuumed inside, the ue gas side resistance,
through the boiler, increases which, eventually, will lead to a
reduction of the thermal load (and, consequently, of the power).
Before cleaning, check the thermal load (see 3.13) and the
CO2 percentage (see 3.13). If the read load (with correct CO2)
is around 5% of the indicated value, the boiler does not need
to be cleaned.
Therefore, the operation can be limited to cleaning the siphon
ATTENTION!
A drop in thermal load may be caused by the
obstruction of the exhaust duct or of the air inlet
duct. Firstly check that this is not the cause.
If a load reduction is detected of more than 5%,
check the cleanliness of the condensate collection pan and of the burner. Clean the siphon also.
First phase – Disassembly
• Close the power and gas supply ensuring that the valve is
closed properly.
• Remove:
- all casings
- Act on the two rear closing hinges to remove the cover
- Remove the casing fastening screws, rear, front and lateral.
- Turn the indicated screw to lift the cover
- Remove the 2 cover fastening screws
46
- Remove the red silicon pipes and then the fan chamber
• Element screws
ENGLISH
- Release the fan chamber fastening spring
(right/left side).
Installation instructions
- Remove screws “A” for each element
(with socket wrench and 13 mm at spanner)
47
• Element screws
- Remove screws “A” for each element
(with 13 mm socket wrench)
- Remove the screws “B” (with 13 mm socket wrench / 13
mm hex spanner) and remove the fastening plates
- Remove the gas pipe fastening screws (right and
left sides)
- Remove the four screws with a 10 mm socket wrench, then
the gas ange
48
- Slightly lift the rear burner block and remove the 2 pins
using a 5 mm hex spanner, until you reach the holes “C”
(left and right side).
ENGLISH
- Lift the burner block (front part)
- Remove the gas ttings from the gas manifold using the 36
mm at spanner.
Installation instructions
49
Second phase – Cleaning
• Remove the gaskets and the burners.
• Dry clean the burners by blowing compressed air from the
“ame side”
• Visually inspect the welding on the corner pieces and on the
burner mesh.
The burner gaskets must be replaced at each
cleaning operation.
• Wash the combustion chamber with water, taking care not to
wet the electrical wiring.
During this operation, make sure that the condensate drain
pipe always remains clear so that the washing water does
not leak from the inspection opening.
• Blow the combustion chamber with compressed air, trying to
remove any dirt still attached to the pins.
• When the parts have been washed, make sure that the condensate drain trap is clear: clean it if necessary
• Inspect the ue gas exhaust pipe and the ue
Third phase – Re-assembly
• After cleaning the body and/or burners, put the burners back
in their seats
• Position the new graphite gaskets
When reassembling, proceed in reverse
order, taking care to tighten the fastening
screws of the mixer/fan unit to the body, with
13 Nm tightening torque
ATTENTION
AT EACH MAINTENANCE OPERATION, IT IS
MANDATORY TO REPLACE THE SEALING
GASKETS OF EACH BURNER.
• Before ignition, check that the condensation drain trap is
properly lled with water.
• Before opening the gas supply valve again make sure that
the previously loosened gas tting, is tight. To do this, open
the valve and check its seal with soapy solution.
• As a burner ignites, immediately check the seals between
each individual gas valve and its premixing chamber
• Analyse the combustion and check its parameters.
• Make sure that all opened gas pressure sockets are closed.
50
ENGLISH
PAGE LEFT INTENTIONALLY BLANK
Installation instructions
51
BL- N
BR - L1
R
BK
F-6,3A
A2
3
1
4
2
Modbus A
Modbus B
A1
Ufly
BR
BL
BK GND
BR eBU S+
R +24V
13 2
BR
BL
Y/G
BR
BK
BR
BL
BR
IG
2
1
GND
A4
3
1
4
2
1
23
A3
3
142
2
1
C
4L
1N
5L
2N
GND
+24V
eBUS+
IG1
IG2
YG/
Ufly
(M3)
ALIM.
230 V - 50 Hz
1b1a
BR
BL
Y/G
BCM
R
BR
BK
123
4
5
6
7
A2
A1
A4
A3
Y2
Y1
Y3
GND
1
2
123
BL
BR
Y G/
ST1
1
R
R
FILTER
4
N° MOD.
1
2-3
522-3/4-5
622-3/4-5
73 2-3/4-5/6-7
N
L1BR
BL
YG/
2
1
2
1
BK GN D
BR +e BUS
E.RIL.
1-7/8
TEFLON WH
BL
BR
YG/
ST2
1
BK (-)
BR (PWM)
BL (TA CHO)
OR (+)
OR +24V
BL XWDC
1
2
3
4
1
2
3
4
A2/A3-A2/A3
BMM2-7/8
PHS
1-2: FASEHNOT SENS.
2-3: FASE SENSIBH.
PIN1
123
4
56
789101112
123
4
5678
Y1
1
2
34
A2
1
2
34
A3
A1
123
456
A4
A8
3214
7658
321
A7
456
A5
2
1
A6
2
1
ROD1ROD
F1
A2
BK GN D
BR +e BUS
OR +24V
BL XWDC
1
2
3
4
A3
(*) EXT 100 ÷ 350
C
NO
CNO
123
4
56
789101112
A4
S1R
WH
WH
SR
WH
WH
WH
BR
BL
BL
PF
min
TLT1L
BL
BL
ONLY
AUSTRALIA
MOD. 1
PF
min.
MOD. 2 - 7
BL
SR
2-7
PF
min
TL
2-7
WH
WH
WH
WH
BL
A4
123
4
56
789101112
123
456
A1
VM (R)
1 - 7 / 8
2345
A8
3214
7658
321
A7
456
A5
A6
eBUS +
eBUS
+ 24 V
MOD. 1
KITSHC
(+24 V only
for 1SHC)
VM (A)
23
BR
BL
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
BR
BL
BL
BR
Y G/
ST1
1
VM (A)
23
ST1
1
VM (A)
23
BL
BR
Y G/
BR
BL
1° Mod.
intermediate /
last module
FILTER POSITIONBETWEEN MOD.
ALIM.VENT.
ALIM.VENT.
EXT 100 ÷ 350
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
FILTER
(MV1)
BLBL
BK
BK
BK
BK
FILTER
ALIM.VENT.
EXT 440 ÷ 900
ALIM.VENT.
BMM
ONLY
AUSTRALIA
PF
min.
F1
4.2 - PRACTICAL CONNECTION WIRING DIAGRAM
L1
N
N
L1
N
L1
(MV1)
L1
L1
(M2)
N
(M1)
N
KEY
E. ACC. Ignition electrode
E. RIL.Detection electrode
HSCP / UyTemperature control
SRHeating sensor (only mod.1)
SR 1...7 Local heating sensor
PF Flue gas press. switch (only mod.1)
PF minFlue gas minimum press. switch (only mod.1)
SLCondensate level sensor (mod.2)
T. ACC Ignition transformation
TLLimit thermostat
TL 1....7Local limit thermostat
VGGas valve
VM (A)Modulating Fan Power Supply
VM (R)Modulating Fan Det./Adjustment
SRRGlobal return sensor
PG
IG
Gas pressure switch
Main switch
52
SE
124
A4
ALIM (50)
+24V
GND
eBUS+
2134567
9
81011121314
2
1
C
NC
31
4
11
3
10
8
2
9
1
C
NO
13
6
A1
BR
WH
WH
WH
BR
BR
WH
BR
R
R
OR
OR
PF SL PG SRR
SMG
WH
WH
R
BK
BR
N
L1BR
BL
YG/
A5/A6-A5/A6
BMM2-7
2
1
2
1
E.RIL.
1-7/8
TEFLON WH
N
L
V1
N
L1
BL
BR
YG/
PHS
A8
3214
7658
321
A7
4 5 6
A5
2
1
A6
2
1
ROD1 ROD
F1
(*) EXT 440 ÷ 900
C
NO
CNO
123
4
56
789101112
A4
S1R
WH
BK
SR
WH
BK
WH
BR
BL
BL
PF
min
TLT1L
BL
BL
MOD. 1
MOD. 2 - 8
BL
SR
2-8
PF
min
TL
2-8
WH
BK
WH
BK
BL
A4
123
4
56
789101112
A8
3214
7658
321
A7
4 5 6
V2
VG
1 - 7 / 8
T. ACC.
1 - 7 / 8
1
E.ACC.
1 - 7 / 8
SILICON- R
YG/
BR
BL
A5
A6
N
BL
BR
Y G/
ST1
1
VM (A)
23
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
BK
BK
FILTER
(*)
NO
AUSTRALIA
ONLY
AUSTRALIA
PF
min.
ONLY
AUSTRALIA
PF
min.
VI
VIOLA
M2
+24V
G
V
TA
FL
INAIL
R
WH
Stemp. ACC
12 11 10 98 765
Y2
123
COLOURS
BLUE
BROWN
BLACK
ENGLISH
C.P.M.
P. Coll.
GREEN
P. CH
P. Car. DHW
GREY
SKY BLUE
ORANGE
1
2
3
4
PINK
RED
YELLOW
YELLOW GREEN
WHITE
VIOLET
0-10V -
INGR ANA LOG.
GND 0-10V - INGR.
Modbus B
eBUS-
eBUS+
4321
Jp2
4
5
6
COM AND
USC ALL ARM SIGNAL
Modbus A
3
4
Y4
0
1
9
2
8
3
7
4
6
5
2
1
2134567
981011121314
COM AND
COM AND
COM .
3
1
2
Y3
0
9
8
7
6
5
PF
min
Installation instructions
TLG
LTLG
F
BCM (*) the connections reported below are only meant as
an indication and are to be carried out on the services return
terminal boards ‘‘B’’ indicated in chap. 3.10.