Unical MODULEX EXT 440, MODULEX EXT 348, MODULEX EXT 770, MODULEX EXT 900, MODULEX EXT 550 Installation And Maintenance Instructions Manual

...
ENGLISH
MODULEX EXT
348 - 440 - 550 - 660 - 770 - 900
INSTALLATION AND MAINTENANCE INSTRUCTIONS
https://www.unicalag.it/prodotti/professionale-300/commercial-condensazione-alluminio/347/modulex-ext
Provisions for proper disposal of the product
After decommissioning, this appliance must not be disposed of as mixed urban waste.
Please contact operators authorised for the disposal of this type of appliances
Incorrect management of waste and of its disposal has potential negative e󰀨ects on the environment and human health
The symbol on the appliance, represents the prohibition to dispose of the product as mixed urban waste.
2
Attention: this manual contains instructions for the exclusive use of the professionally qualied installer and/or maintenance
technician in compliance with current legislation.
The user is NOT qualied to intervene on the boiler. The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from failure to comply with
the instructions contained in the manuals supplied with the boiler
1 GENERAL INFORMATION.................................................................................................................................................4
1.1 General warnings .......................................................................................................................................................4
1.2 Symbols used in the manual ......................................................................................................................................5
1.3 Appropriate use of appliance .....................................................................................................................................5
1.4 Information for system manager ................................................................................................................................5
1.5 Safety warnings .........................................................................................................................................................6
1.6 Technical data plate ...................................................................................................................................................7
1.7 Water treatment .........................................................................................................................................................8
1.8 Boiler antifreeze protection ........................................................................................................................................9
2 TECHNICAL SPECIFICATIONS{J}AND DIMENSIONS.................................................................................................10
2.1 Technical features ....................................................................................................................................................10
2.2 Main components view and dimensions ..................................................................................................................10
2.3 Dimensions ..............................................................................................................................................................12
2.4 Operating data .........................................................................................................................................................13
2.4.1 Technical data according to ErP Directive ......................................................................................................14
2.4.2 Determination of the primary circuit pump or boiler pump ..............................................................................15
ENGLISH
General information
3 INSTRUCTIONS FOR THE INSTALLER .........................................................................................................................16
3.1 General warnings ......................................................................................................................................................16
3.2 Installation rules ........................................................................................................................................................16
3.3 Preventive system verication and adjustment operations .......................................................................................16
3.4 Package and Weights ..............................................................................................................................................17
3.4.1 Unloading operations .......................................................................................................................................18
3.5 Positioning in boiler room ..........................................................................................................................................19
3.6 Flue gas exhaust pipe connection.............................................................................................................................20
3.7 Boiler connection.......................................................................................................................................................21
3.8 Connection ................................................................................................................................................................22
3.9 Filling and emptying the system ................................................................................................................................24
3.10 Electrical connections ..............................................................................................................................................26
3.11 Commissioning..........................................................................................................................................................35
3.12 Measurement of combustion e󰀩ciency during installation ........................................................................................37
3.12.1 Activation of the calibration function ...............................................................................................................37
3.12.2 Positioning the sensors ..................................................................................................................................37
3.13 Checking burner pressure adjustment ......................................................................................................................38
3.14 Control panel, emergency operation and safety devices ..........................................................................................39
3.15 Programming operating parameters .........................................................................................................................40
3.16 Release and reset error codes ..................................................................................................................................43
4 INSPECTION AND MAINTENANCE ................................................................................................................................ 43
4.1 Inspection and maintenance instructions .................................................................................................................. 43
4.2 Wiring diagram ..........................................................................................................................................................50
Technical Features
Installation instructions
Maintenance instructions
3
1
GENERAL INFORMATION
1.1 - GENERAL WARNINGS
The instruction manual is an integral and essential part of the product and must be kept by the user.
Read the warnings contained in this instruction manual carefully as they provide important guidelines regarding installation, use and maintenance safety.
Keep the manual with care for further consultation.
Your appliance must be installed and serviced in compliance with the standards in force according to the manufacturer instructions,
up to standard and by legally qualied and certied personnel.
Systems for the production of domestic hot water MUST be constructed entirely with compliant materials.
By professionally qualied personnel we mean: personnel with specic technical skill in the eld of heating system components
for civil use, domestic hot water production and maintenance.
Personnel must have the qualications provided for by current
legislation.
Incorrect installation or improper maintenance can cause dam-
age to persons, animals or objects for which the manufacturer
is not responsible.
Before performing any cleaning or maintenance, disconnect the appliance from the energy mains by acting on the switch of the
system and/or through the specic cut-o󰀨 devices.
Do not obstruct the terminals of the intake/exhaust ducts.
Any product repairs must be performed solely by personnel authorised by Unical, using original spare parts only. Failure to comply with the above can compromise the safety of the appli­ance and void the warranty.
To guarantee appliance e󰀩ciency and its correct operation, yearly maintenance must be performed by qualied personnel.
Should you decide not to use the appliance, parts entailing potential sources of hazard must be made safe. Before commissioning an appliance that has not been used, wash the domestic hot water production system, making the
water ow until it has been fully replaced.
Should the appliance be sold or transferred to a new owner or if you move and leave the appliance, always make sure that the instruction manual accompanies it so that the new owner and/ or installer can refer to it.
Only original accessories must be used for all appliances with optional features or kits (including electric ones).
This appliance is intended solely for the use for which it was expressly designed. Any other use is to be considered improper and therefore dan­gerous (*) (see 1.7 Water Treatment).
In the event of failure and/or malfunctioning of the appliance,
switch it o󰀨 and do not try to repair it or intervene on it directly. Contact only personnel qualied in compliance with law.
ATTENTION
THE THERMAL UNIT MUST BE INSTALLED IN SUCH A WAY AS TO AVOID, IN
THE ENVISAGED OPERATING CONDITIONS, THE LIQUID IT CONTAINS FROM FREEZING AND PREVENT COMMAND AND CONTROL PARTS
FROM BEING EXPOSED TO TEMPERATURES BELOW -15°C AND ABOVE
THE THERMAL UNIT MUST BE PROTECTED FROM CLIMATIC/ENVIRONMEN-
TAL VARIATIONS WITH:
+40°C.
- The insulation of hydraulic pipes and condensation drain
- The use of specic antifreeze products in the hydraulic system.
4
1.2 - SYMBOLS USED IN THE MANUAL
When reading this manual, pay special attention to the parts marked by the symbols shown:
DANGER!
Serious danger
to safety
and health
DANGER!
Danger of burns!
ATTENTION!
Possible dangerous
situation for the product
and the environment
OBLIGATION!
wear protective
gloves
1.3 - APPROPRIATE USE OF APPLIANCE
The boiler has been constructed according to the current level of engineering and acknowledged technical safety rules. Nonetheless, improper use could result in hazards for the safety and life of the user or other persons, i.e. damage to the appliance or other property. The appliance is designed to work in heating systems, with hot water circulation, for the production of domestic hot water. Any other use shall be considered as misuse. UNICAL will not be held liable for any damage resulting from improper use. Use according to the intended purposes also includes strict compliance with the instructions in this manual.
NOTE!
Tips
for the user
NOTE!
For further details
refer to the Technical Informa-
tion:
at the address indicated
on page 2.
1.4 - INFORMATION FOR THE SYSTEM MANAGER
The user must be instructed on use and operation of the heating system, in particular:
• Deliver these instructions to the user, as well as other documents concerning the appliance inserted in the envelope
inside the packaging. The user must keep this documentation safe for future reference.
• Inform the user about the importance of the air vents and the ue gas exhaust system, highlighting their essential
features and the absolute prohibition of modifying them.
• Inform the user on how to control the system's water pressure as well as operations to restore it.
• Inform the user on correct temperature control, control units/thermostats and radiators for saving energy.
• Please note that, in compliance with the standards in force, the inspection and maintenance of the appliance must
be carried out in compliance with the regulations and frequency indicated by the manufacturer.
• Should the appliance be sold or transferred to a new owner or if you move and leave the appliance, always make
sure that the instruction manual accompanies it so that the new owner and/or installer can refer to it.
The manufacturer will not be held liable in the event of damage to persons, animals or objects resulting from
failure to comply with the instructions contained in this manual.
5
1.5 - SAFETY WARNINGS
ATTENTION! The appliance must not be used by children. The appliance may be used by adults and only after carefully reading the operating instructions manual for the user / person in charge. Children must be supervised so they do not play or tamper with the appliance.
ATTENTION! The appliance must be installed, adjusted and maintained by profes-
sionally qualied personnel, in compliance with the standards and provisions in force.
Incorrect installation can cause damage to persons, animals and property for which the manufacturer cannot be held liable.
DANGER! NEVER attempt performing maintenance or repairs on the boiler on your own initiative. Any work must be done by professionally qualied personnel. We recommend stip­ulating a maintenance contract. Insufcient or irregular maintenance can jeopardise the operating safety of the appli­ance and cause damage to persons, animals and property for which the manufacturer will not be held liable.
ATTENTION! Modifying parts connected to the appliance (upon completing appliance installation) Do not modify the following parts:
- the boiler
- the gas, air, water and electricity supply lines
- the ue gas pipe, the safety valve and the exhaust pipe
- the construction parts which affect the operating safety of the appliance
ATTENTION!
To tighten or loosen the screwed ttings, use only appropriate xed spanners.
Incompliant use and/or inappropriate tools can cause damage (e.g. water or gas leakage).
ATTENTION!
Indications for propane gas-red appliances
Make sure that the gas tank has been deaerated before installing the appliance.
For state-of-the-art tank venting, contact the LPG supplier or person qualied in
compliance with the legal requirement. If the tank has not been professionally deaerated, ignition problems could arise. In that case, contact the supplier of the LPG tank.
DANGER Gas smell Should a smell of gas be perceived, follow these safety guide­lines:
- do not turn electrical switches on or off
- do not smoke
- do not use the telephone
- close the gas shut-off valve
- ventilate the area where the gas leakage has occurred
- inform the gas supplier or a company specialised in the installation and mainte­nance of heating systems.
DANGER! Explosive and easily ammable substances Do not use or store explosive or easily ammable materials (e.g. petrol, paints, paper)
in the room where the appliance is installed.
6
/
DANGER! Do not use the appliance to support any object.
Specically, do not place any liquid containers (Bottles, Glasses, Containers or
Detergents) on top of the boiler.
If the appliance is installed inside a box, do not insert or place other objects inside it.
1.6 - TECHNICAL DATA PLATE
ENGLISH
The CE Marking
certies the appliance compliance with the essential safety re­quirements dened in the applicable European Directives and
Regulations and that its operation meets the technical standards of reference.
The CE marking is a󰀩xed on each individual appliance by a
special label.
The EC declaration of conformity, issued by the Manufacturer pursuant to international regulations, can be found in the docu­mentation accompanying the product.
The technical data plate can be found under
the casing, on the front xing crosspiece. ITS DUPLICATE is placed next to the temperature
control unit.
KEY: 1 = CE monitoring body 2 = Type of boiler 3 = Boiler model 5 = (S.N°) Serial Number
6 = P.I.N. Product Identication Number 7 = Types of approved ue gas exhaust congurations 8 = (NOx) NOx Class
A = Heating circuit characteristics 9 = (Pn) Effective nominal output 10 = (Pcond) Effective output in condensation
11 = (Qn) Maximum thermal ow rate
12 = (Adjusted Qn) Adjusted for rated heat output
13 = (PMS) Max. heating operating pressure 14 = (T max) Max. heating temperature
B = Domestic hot water circuit characteristics 15 = (Qnw) Rated heat output in domestic hot water function
(if different than Qn)
16 = (D) Specific D.H.W. flow rate according to EN625-
EN13203-1
19 = (PMW) Max. domestic hot water operating pressure 20 = (T max) Max. domestic hot water temperature
General information
C = Electrical characteristics 21 = Electrical power supply 22 = Consumption 23 = Protection rating
D = Countries of destination 24 = Direct and indirect countries of destination 25 = Gas category 26 = Supply pressure
E = Factory settings 27 = Adjusted for gas type X 28 = Space for national brands
G = ErP
29 = Seasonal energy efciency to heat the room 30 = Seasonal water heating energy efciency.
7
1.7 - WATER TREATMENT
Feed water treatment prevents problems and
maintains the functionality and e󰀩ciency of the
generator over time.
The ideal water pH in heating systems must be within:
VALUE MIN MAX
PH 6.5 8
Hardness [°fr] 9 15
To minimise corrosion, it is crucial to use a cor­rosion inhibitor; in order for it to work properly, the metal surfaces must be clean. (see system protection ACCESSORIES sect. in domestic price list)
ATTENTION! ANY DAMAGE TO THE BOILER CAUSED BY THE FORMATION OF SCALING OR BY COR­ROSIVE WATER WILL NOT BE COVERED BY THE WARRANTY.
ATTENTION (*) see general warnings 1.1: The heating only models are NOT suitable for the production of water for human con­sumption according to Ministerial Decree D.M. 174/2004.
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
8
1.8 - BOILER ANTIFREEZE PROTECTION
It is activated by default
This protection can trigger only if the electricity
and gas supplies are connected. If one of the two is not available and upon reset
11 (SM) a temperature level between 2 and 5°C is detected, the appliance will behave as described in the table below, pos 2.
The heating system can be protected e󰀨ectively
from frost by using antifreeze products with
inhibitor for heating systems (specic for multi-
metal)
Do not use car engine antifreeze products as they could damage the water gaskets.
ENGLISH
P O S
1 ON ON < 7 °C ON - Burner and Pump ON until T > 15°C
2
(*) SR Sensor par. 2.2
Supplies 11 - SR (*) Status
Electric Gas
ON OFF
< 5 ÷ 5 °C OFF
OFF ON OFF Ignition inhibited.
OFF OFF OFF Ignition inhibited.
ANTIFREEZE FUNCTION
Actions
antifreeze func-
tion
FAULT SIGNAL CODE 16 (see par. 4.4 ERROR CODES). Ignition inhibited.
Technical Features
9
TECHNICAL FEATURES AND DIMENSIONS
2
NOTE!
2.1 - TECHNICAL FEATURES
2.2 - INTERNAL VIEW WITH THE INDICATION OF THE MAIN COMPONENTS
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
10
ENGLISH
Technical Features
KEY
No. C.E. S.E. Description
1 Uy Control panel
2 VG Gas valve
3 Burner cover
4 E. ACC. Ignition electrode
5 E. RIL. Detection electrode
7 TL Limit Thermostat
8 Burner
9 Silicon Aluminium Heat Exchanger
10 SL Condensate level sensor
11
12 Frame
Flue gas outlet LEFT, RIGHT, REAR side Flow LEFT side Return LEFT side Gas inlet LEFT side
Condensate collection pan /
Chimney tting
13 Condensation drainage outlet
14 Drain valve
15 SRR Global Return Sensor
16 SMG Global Flow Sensor
17 Automatic air vent
18 Fan
19 PF min
20 PF Smoke pressure switch
Smoke pressure minimum pressure switch
BCM: under the front casing
11
2.3 - DIMENSIONS
395
946
235
S
1267
534
327
R
M
G
122
L1
287
L
62,5
24
S
=
=
1448
FRONT VIEW
LEFT SIDE VIEW
RIGHT SIDE VIEW
TOP VIEW
Flue Gas Outlets: Left side (supply conditions)
Right side Rear side
MODULEX EXT 348 440 550 600 770 900 Dimensions
No. of heating elements 4 4 5 6 7 8 Height mm 1448 1448 1448 1448 1448 1448 Width “L” mm 1087 1087 1355 1355 1623 1623 Width “L1” mm 1039 1039 1307 1307 1575 1575
Depth mm 946 946 946 946 946 946
Connection dimensions
Gas Fitting G mm (inch) 80 (3) 80 (3) 80 (3) 80 (3) 80 (3) 80 (3) System ow M mm (inch) 100 (4) 100 (4) 100 (4) 100 (4) 100 (4) 100 (4) System return R mm (inch) 100 (4) 100 (4) 100 (4) 100 (4) 100 (4) 100 (4) Chimney tting mm 250 250 250 300 300 300 Condensation drain mm 40 40 40 40 40 40
12
2.4 - OPERATING DATA AND GENERAL FEATURES
For the adjustment data: NOZZLES - PRESSURE - COLLECTORS - FLOW RATES refer to the paragraph ADAPTATION TO
OTHER TYPES OF GAS.
MODULEX EXT 348 EXT 440 EXT 550 EXT 660 EXT 770 EXT 900 Boiler category II
2H3P
II
2H3P
II
2H3P
II
2H3P
II
2H3P
Modulation ratio 1:15.8 1:19.6 1:24.5 1:29.4 1:34.3 1:39.2 Rated heat output on P.C.I. Qn kW 348 432 540 648 756 864 Minimum heat output on P.C.I. Qmin kW 22
E󰀨ective nominal output (Tr 60 / Tm 80 °C) Pn kW 341.7 424.3 530.4 636.5 742.6 849.0 Minimum e󰀨ective output (Tr 60 / Tm 80 °C) Pn min kW 20.6 E󰀨ective nominal output (Tr 30 / Tm 50 °C) Pcond kW 359.2 445.0 557.8 670.1 783.2 900.3 Minimum e󰀨ective output (Tr 30 / Tm 50 °C) Pcond min kW 23.9
Nominal output performance (Tr 60 / Tm 80°C) % 98.2 Minimum output performance (Tr 60 / Tm 80°C) % 93.5 Nominal output performance (Tr 30 / Tm 50°C) % 104 Minimum output performance (Tr 30 / Tm 50°C) % 109 Performance at 30% of the load (Tr 30°C) 106.8 107.3 107.5 108.3 107.8 107.6
Combustion e󰀩ciency at nominal load % 97.8 Combustion e󰀩ciency with reduced load % 98.5
Casing heat loss with burner on (Qmin) % 5.04 Casing heat loss with burner on (Qn) % 0.1
Net ue gas temperature tf-ta (min)(*) °C 31 Net ue gas temperature tf-ta (max)(*) °C 46.0 46.7 46.7 46.7 46.7 45.8
Maximum permitted temperature °C 100 Maximum operating temperature °C 85
Flue gas mass ow rate (min) kg/h 25 Flue gas mass ow rate (max) kg/h 558 693 866 1040 1213 1386
Excess air % 24.25 Heat loss at chimney with burner on (min) % 1.5 Heat loss at chimney with burner on (max) % 2.40 2.58 2.53 2.51 2.58 2.58 Minimum heating circuit pressure bar 0.5 Maximum heating circuit pressure bar 6 Water content L 67 67 80 94 108 122
3
Methane gas consumption G20 (sup.p. 20 mbar) at Qn m Methane gas consumption G20 (sup.p. 20 mbar) at Qmin Gas consumption G25 (sup.p. 20/25 mbar) at Qn m Gas consumption G25 (sup.p. 20/25 mbar) at Qmin m
/h 36.80 45.68 57.10 68.52 79.94 91.36
m3/h 2.33
3
/h 42.80 53.13 66.41 79.69 92.97 106.25
3
/h 2.71 Propane gas consumption (sup.p. 37/50 mbar) at Qn kg/h 27.01 33.53 41.92 50.30 58.68 67.01 Propane gas consumption (sup.p. 37/50 mbar) at Qmin kg/h 1.71 Chimney base maximum pressure available Pa 100 Max condensate production kg/h 59.1 73.4 91.7 11 0 128.4 146.7
Emissions
CO at maximum heat output with 0% of O2 (PCI) mg/kWh 55 72 76 87 72 76 NOx at maximum heat output with 0% of O2 (PCI) mg/kWh 56 52 52 58 55 57 (***) Sound pressure level dB (A) 54 54 54 54 54 56
ENGLISH
Technical Features
Electrical data
Power supply voltage/frequency V/Hz 230 / 50 (**) Protection rating IP X5D
Room Temperature = 20°C
(*) Temperature detected with appliance operation ow 80°C / ret. 60°C
(min/max) See ‘’NOZZLES - PRESSURE’’ table
CO
2
Seasonal Energy E󰀩ciency
Leaks upon stop at ∆T 30°C - Pstb - see Electricity consumption on standby - Psb - see
according to 2009/125 EEC (<=400Kw)
ErP table
ErP table
ηs - see ErP table
(***) at 1 m away in free eld.
(**) The IP protection rating is obtained with the cover down
13
2.4.1 - TECHNICAL DATA ACCORDING TO ErP DIRECTIVE
MODULEX
EXT 348 EXT 440 EXT 550 EXT 660 EXT770 EXT 900
Element Symbol Unit
E󰀨ective nominal output Prated kW 342 424 530 636 743 849 Seasonal energy e󰀩ciency of
central heating
Season e󰀩ciency class for
heating
ƞ
s % 93
A * * * * *
For boilers for central heating
and mixed boilers: e󰀨ective heat output
E󰀨ective heat output with
high temperature capacity
P
4 kW 341.7 - - - - -
(Tr 60 °C / Tm 80 °C)
Rated heat output e󰀩ciency
with high temperature capacity
4 % 88.5 - - - - -
ƞ
(Tr 60 °C / Tm 80 °C)
E󰀨ective output at 30% of the rated heat
output with low temperature
1 kW 11.5 - - - - -
P
capacity (Tr 30 °C)
Performance at 30% of the rated heat output with low temperature
ƞ
1 % 96.2 - - - - -
capacity (Tr 30 °C)
Boiler with output range adjustment: YES / NO NO NO NO NO NO NO
Auxiliary electricity consumption
With a full load elmax kW 0.393 0.626 0.783 0.940 1.096 1.252
With a partial load elmin kW 0.054 Standby mode P
SB kW 0.020
Other elements
Heat dispersion on standby P Nitrogen oxides emissions ref. PCS NOx
stb kW 0.2114 0.2114 0.2114 0.2114 0.2114 0.2114
Mg/kWh
49 NOx class 6 Annual electricity consumption Q
HE GJ 1050 1303 1633 1959 2286 2612
For mixed heating appliances
Declared load prole - - - - - - -
Water heating
energy e󰀩ciency
wh % - - - - - - -
ƞ
Daily consumption of electricity Qelec kWh - - - - - - ­Daily consumption of fuel Qfuel kWh - - - - - - ­Internal sound power level Lwa dB (A) - - - - - - ­Annual electricity consumption AEC kWh - - - - - - ­Annual fuel consumption AFC GJ - - - - - - -
Seasonal DHW e󰀩ciency class
14
- - - - - - -
2.4.2 - DETERMINATION OF THE PRIMARY CIRCUIT PUMP OR BOILER PUMP
The boiler pump must have head that is able to ensure the pump's ow rates according to the circuit's ∆t.
The pumps must be determined by the installer or designer according to the boiler and sys­tem data.
MODULEX EXT 440
Maximum ow rate in l/h (t=15K) 24,326
Requested rated ow rate in l/h (t=20K) 18,243
MODULEX EXT 550
Maximum ow rate in l/h (t=15K) 30,404
Requested rated ow rate in l/h (t=20K) 22,804
MODULEX EXT 660
Maximum ow rate in l/h (t=15K) 36,487
Requested rated ow rate in l/h (t=20K) 27,365
The pump is not an integral part of the boiler.
It is recommended to select a pump with a ow rate and head of approximately 2/3 of its characteristic
curve.
ENGLISH
MODULEX EXT 770
Maximum ow rate in l/h (t=15K) 42,570
Requested rated ow rate in l/h (t=20K) 31,926
MODULEX EXT 900
Maximum ow rate in l/h (t=15K) 48,647
Requested rated ow rate in l/h (t=20K) 36,487
O)
2
Pressure drop (mH
FLOW RATE l/h
EXAMPLE:
For a ∆T 20K, of a MODULEX 900, the maximum water ow rate required is 36,289 l/h.
The graph of the boiler pressure drops shows that the pump must ensure a head of at least 1.6 m/H2O
Technical Features
NOTE:
It is always advisable to use a hydraulic separator (*) between the boiler circuit and the system.
(*) For the features, refer to the SPINOX installation manual, available on the website.
15
3
INSTRUCTIONS FOR INSTALLATION
3.1 - GENERAL WARNINGS
ATTENTION! This boiler is intended solely for the use it
was expressly designed for. Any other use
is considered improper and therefore dan­gerous. This boiler heats water at a temperature lower than the atmospheric pressure boiling temperature.
Before connecting the boiler, have professionally
qualied personnel:
a) Thoroughly wash all of the system piping
to remove any residues or impurities which could jeopardise proper operation of the boiler, even from a hygiene point of view.
b) Check that the boiler is set up to operate with
the type of fuel available.
The type of fuel can be seen written on the
package and on the technical feature plate.
c) Check that the chimney/ue has an appro-
priate draught, without any bottlenecks, and that no exhausts from other appliances are inserted, unless the ue has been implement­ed to accommodate several utilities according
to specic standards and requirements in force. Only after this check can the tting be mounted between the boiler and chimney/ue.
ATTENTION! In rooms with the presence of aggressive vapours or dust, the appliance must operate independently from the air inside the instal­lation room!
ATTENTION!
The appliance must be installed by a qualied
technician with the technical-professional requirements according to law 46/90 which, under his own responsibility, guarantees compliance with standards according to good practice rules.
ATTENTION! Mount the appliance respecting the minimum dis­tances required for installation and maintenance.
The boiler must be connected to a heating system compatible with its performance and output.
3.2 - STANDARDS FOR INSTALLATION
It must be installed by a professionally qualied technician, who shall take the responsibility of observing all local and/or
national laws published in the O󰀩cial Journal, as well as
applicable technical standards.
3.3 - PREVENTIVE SYSTEM VERIFICATION
AND ADJUSTMENT OPERATIONS
Before installing this appliance on old systems, check that:
- The chimney is suitable for appliances with condensation, at combustion products temperatures, calculated and built in compliance with the standards in force in this regard.
Is as straight as possible, airtight, insulated, and has no obstructions or constrictions.
- The chimney is equipped with a tting to drain
condensate.
- The boiler room is equipped with a duct to drain condensate produced by the boiler.
- The electrical system has been set up by a qualied techni­cian in compliance with the rules in force.
- The rate, head and direction of the ow of the circulation
pumps are appropriate.
- The fuel adduction line and the tank, if any, are made ac­cording to relevant standards in force.
- The expansion vessels can fully absorb dilation of the uid in
the system.
- The system has been cleaned from sludge and scaling.
16
3.4 - PACKAGING
The boiler MODULEX is supplied assembled in a sturdy card­board box.
After removing the two straps, remove the card­board from the top and ensure the integrity of the contents.
Keep the packaging material (cardboard box, straps, plastic bags, etc.) out of the reach of chil-
dren as they are potential sources of danger. Unical will not be held liable for damage to per-
sons, animals or objects due to failure to comply
with the above instruction.
OBLIGATION! wear protective gloves
- Transport the boiler using suitable transportation means.
- Protect all parts against impacts if they must be transported.
- Follow the transport instructions on the packaging.
• The boilers must always be lifted and carried with a carrying
trolley or equipment suitable for transport.
To remove the boiler from the pallet, it is necessary to have a rocker crane, to avoid damage during gripping.
- Remove the casings and harness with the straps “A”, taking care to pass the straps on the load-bearing crosspieces of the frame
- Tie the straps to the rocker arm “B”, operating with caution.
the box contains:
Modulex EXT A B C
mm mm mm kg 348 1263 1120 1515 585 440 1263 1120 1515 585 550 1531 1120 1515 643 660 1531 1120 1515 707 770 1799 1120 1515 806 900 1799 1120 1515 858
on the left side of the boiler:
- The ue gas exhaust manifold
- A cardboard box containing:
Gasket between pan and terminal. Collar gasket (Ø 250) Ø 300. Two elbows + a Tee + a plastic condensate drain plug
The screws necessary for xing the ue gas terminal
- The sensors: external, heater.
- The ue inspection cap
- Sheet and cable glands for power supply output
- A cardboard box containing:
The anges
Inside the rear side casing:
- The condensate drain trap pipes (1 m)
Above the boiler cover:
A plastic bag containing:
- Instruction manual for the installation and maintenance technician
- Uy control unit operating manual
- BCM 2.0 manual
- Hydraulic test certicate
- Certicate of conformity
- Warranty certicate (IT only)
- Warranty extension 10 A (IT only)
- INAIL certicate (IT only)
- Spare parts coupon (IT only)
- Dowels to lock the fan set in raised position (use only for models 100 ÷ 350 kW)
Gross Weight
ENGLISH
Installation instructions
17
3.4.1 - UNLOADING AND REMOVING THE PACKAGING
1
Max. admitted boilers stacked
Do not turn upside down Do not expose to rain Fragile Do not expose to sunlight Do not store at
temperature: lower than - 5 ° C / 23 °F superior than 50 °C / 122 °F
T max 50°C/122°F
T min
-5°C/23°F
2
Max. admitted boilers stacked
Do not turn upside down Do not expose to rain Fragile Do not expose to sunlight Do not store at
temperature: lower than - 5 ° C / 23 °F superior than 50 °C / 122 °F
T max 50°C/122°F
T min
-5°C/23°F
3
Max. admitted boilers stacked
Do not turn upside down Do not expose to rain Fragile Do not expose to sunlight Do not store at
temperature: lower than - 5 ° C / 23 °F superior than 50 °C / 122 °F
T max 50°C/122°F
T min
-5°C/23°F
4
ATTENTION! Handling with forklift or strap hoist,
ATTENTION! Strap passage points for lifting. The straps must be mounted on the load-bearing crosspieces.
18
3.5 - POSITIONING IN THE BOILER ROOM
A> 400 mm B > 400 mm C = 100 mm D= 500 mm
Szifon
Special attention must be paid to the standards and local laws with regard to boiler rooms, especially the minimum distances that must be kept free around the boiler. Installation must comply with the provisions in the most recent standards and laws in force with regard to boiler rooms, instal­lation of heating systems and domestic hot water production, ventilation, suitable chimneys to drain combustion products from condensate boilers and anything else applicable.
The boiler can be placed on a at and su󰀩ciently sturdy base,
with a size, in the plan, not inferior to that of the boiler and at
least 100 mm high (see gure) in order to be able to mount the
siphon for condensate draining. As an alternative to this base,
a sump can be obtained on the oor, next to the boiler, with a 100 mm depth for housing the siphon (see gure).
When installation has been performed, the boiler must be per­fectly horizontal and stable (to reduce any vibrations and noise).
Comply with the minimum clearance distances in order to execute normal maintenance and cleaning operations.
ENGLISH
C
A
B
D
Installation instructions
SIPHON
19
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
To connect the ue gas exhaust pipe, local and national stand­ards must be observed
The boiler is type approved for the exhaust congurations listed
below:
B23P
Connection to a combustion products evacuation pipe outside the room; the combustion air is taken directly from the room where the appliance is installed.
HEAD AVAILABLE AT THE BASE OF THE CHIMNEY
The maximum permitted length of the pipes is determined by the head (p) available at the base of the chimney.
ATTENTION For this type of connection, the room follows the same installation rules for boilers with natural draught.
D (Drain) I (Intake)
p = 100 Pa
-
C63
Separate combustion air intake and combustion products evacuation pipes. (Commercial accessories)
HEAD AVAILABLE AT THE BASE OF THE CHIMNEY
The maximum permitted length of the pipes is determined by head (p) available at the base of the chimney.
ATTENTION For the C63 conguration, you must order the optional air intake kit, which contains the installation instructions.
D (Drain) + I (Intake)
p = 100 Pa
ATTENTION:
for B23P types of connection, the room follows the same installation rules for natural draught
boilers.
3.6.1- MANIFOLD CONNECTION EXHAUST PIPE
Use the nuts and washers contained in the bag to
x the ue gas exhaust manifold.
The ue gas inlet must be positioned on the rst
straight section within 1 metre from the boiler.
To create the ue gas inspection inlet, make one Ø 21 mm hole in the ue gas outlet pipe and t the
inspection inlet following the indicated sequence.
ATTENTION: The chimney must comply with the standards in force.
20
3.7 - BOILER CONNECTION
F
F
G
F
RM
The MODULEX boiler leaves the factory ready for hydraulic
(ow and return), gas connections on the left side of the boiler. To x the ue gas exhaust manifold, use the screws and gaskets
contained in the accessory kit box and a 10 mm socket wrench.
The ue gas manifold is set-up on the LEFT SIDE, the outlet can
also be set-up on the RIGHT and REAR SIDE.
ENGLISH
Collector mounted on the rst and last element of the ow manifold Ø 18 (A), inside Ø 27 (B) Gaskets mounted on all other elements (C).
Collectors and Gaskets
A
B
A
Installation instructions
C
21
3.8 - CONNECTION
G GAS G 3’’
Danger! The gas must be connected only by a qual-
ied installer who must respect and apply
the requirements set forth by relevant laws in force and by the local prescriptions of the supply company. Incorrect installation can cause harm to persons and animals and damage property for which the manufacturer
shall not be held liable.
If you smell gas:
a) Do not operate electrical switches,
the telephone or any other object that
may cause sparks;
b) Immediately open doors and windows to create air current to air out the room;
c) Close the gas valves.
d) Request the intervention of professionally
qualied personnel.
M FLOW G 4’’
R RETURN G 4’’
Make sure that the system pipes are not used as earthing electrodes of the electric or telephone system. They are absolutely not suitable for this type of use. Serious damage could result for the piping, boiler and radiators in a short amount of time.
ATTENTION!
IT IS STRICTLY FORBIDDEN TO FIT SHUT­OFF DEVICES ON THE GENERATOR BEFORE THE SAFETY DEVICES.
As a precaution against gas leaks, we recom­mend installing a monitoring and protection system consisting of a gas leak detector
coupled with a shut-o󰀨 solenoid valve on the
gas feed line.
22
Condensation drain
H min 100 mm
150
C
B
150**
25*
A
The boiler, during the combustion process, produces conden-
sation that, through pipe “A”, ows into the trap. The condensation that forms inside the boiler ows
into a suit-
able drain via pipe “B”.
Danger! Before commissioning the appliance:
- check that the siphon is assembled correctly
- ll the siphon through the ller cap C and
check correct drainage of the condensate
If the appliance is used with an empty conden-
sation drain trap, there is an intoxication hazard due to the release of exhaust gases.
FRONT SIDE
The outlet of the condensate drainage pipe is towards the con-
nection side of the ue gas box manifold, removing the pre-cut
part on the covering panel.
The upper generator
of the drain pipe
must not be higher than
the bottom of the pan.
ENGLISH
BOILER ROOM FLOOR
* Minimum safety siphon set by the standard
** Minimum head with boiler running at maximum power.
The connection between the appliance and the domestic wastewater system must be made in
compliance with the specic reference standards.
AT BLOW DOWN DRAINAGE
If you do not want to or cannot create a base, the boiler can be mounted at ground level and a sump at least 100 mm deep can be made to
house the siphon
NOTE!
For further details
refer to the Technical Information
from the website
Installation instructions
23
3.9 - FILLING AND EMPTYING
THE SYSTEM
When all system connections have been com-
pleted, the circuit can be lled.
To ll the system, you must provide a lling
valve on the system's return.
EXAMPLE OF THE SYSTEM'S LOADING UNIT
UNIT OF LOADING
To ll the system, you must provide a lling valve on
the heating circuit, or use the optional accessories.
The boiler is equipped with its own drain valve, 14 This valve can never be used to drain the system since all the dirt in the system can accumulate
in the boiler and jeopardise its proper operation.
Therefore, before using the drain valve, make sure
the system's check valve, which is situated under
the pump, has been closed.
The system must be equipped with its own drain valve, which is to be suitably sized ac­cording the system's capacity.
24
ENGLISH
PAGE LEFT INTENTIONALLY BLANK
Installation instructions
25
3.10 - ELECTRICAL CONNECTIONS
F1
AE
G
H
F
I
18:28
giov 30 20ott 18
effettiva
richiesta
76°C84
°C
generatore
10/10
modulazione
100
%
INFO MENU
status
sanitaria
25
°C
678910 11 12 FL TA
INAIL
Y2- BCM
12345
1
Y3- BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4- BCM
23
B
1 2 3 4 5 6 7
A2
A1
A4
A3
Y2
Y1
Y3
GND
A5
1 2
1 2 3
M1
M2
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4 56
789101112
123
4 5678
Y1
1 2
34
A2
1 2
34
A3
A1
123
456
ROD1 ROD
F1
A4
51
50
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4 56
789101112
123
4 5678
Y1
1
2
34
A2
1 2
34
A3
A1
123
456
ROD1 ROD
F1
A4
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4 56
789101112
123
4 5678
Y1
1 2
34
A2
1 2
34
A3
A1
123
456
ROD1 ROD
F1
A4
D
NPE
L1
NPE
L1
F1
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
123
4 56
789101112
123
4 5678
Y1
1 2
34
A2
1 2
34
A3
A1
123
456
ROD1 ROD
F1
A4
52
53
00330914
ATTENZIONE!
ATTENTION!
ACHTUNG! ATENCIÓN!
ATTENTIE!
UPOZORNÌNÍ!
230 V
!
Danger!
Before performing connections or any type of operation on electrical parts, always disconnect the electrical power and make sure that it cannot be reconnected accidentally.
KEY
No. Description
A BCM Boiler controller
B Services connection return terminal board
D Wieland mobile pow. supp. socket 230 V -
50Hz
E Uy P heating controller
F LTGL TLG triggering lamp
G F1 Power supply fuse 6.3 AT 250V
H Boiler Main switch
I LTGL Manual reset main limit thermostat
50 BMM Burner management board
51 Power supply board
52 F1 Power supply fuse 6.3AF 250V
53 F1 BMM Board Fuse 6.3AF 250V
26
Danger!
Only a qualied technician may perform the
electrical installation.
Electrical connection to the main power sup­ply.
This connection must be made up to standard, as required by regulations in force.
Electric power supply connection
Remember that a bipolar switch must be installed on the boiler power line with over 3 mm between contacts, easy to access, making maintenance quick and safe.
The power supply of the boiler, single-phase 230 V - 50 Hz, must be made with H05VV-F type three-pole cable (PHASE - NEUTRAL - EARTH) with 0.75 mm section up to 1.5 mm.
ATTENTION!
Respect the PHASE and NEUTRAL polarity
since ame detection is Phase Sensitive.
ATTENTION:
The 230 V cables must run far apart from 24V cables.
ENGLISH
- Make the power supply connection on the “D” plug, sup-
plied with the boiler.
N.B. 24 V - 230 V output - Keep the 2 voltages separate
Installation instructions
27
NOTE:
P.
Coll.
P.
CH
P. Car.
DHW
1
2
3
Y5
0
1
2
3
4
5
6
7
8
9
2
3
4
Y3
1
5
4
3
2
1
Y1
J1P
Modbus
INAIL
SAFE
INPUT 0-10V
1
Y3 -BCM
Y2 -HSCP/UFLY
56
843
Y1 -BMM1
4321
Y4 -BCM
23
INAIL
Modbus
BCM
Ufly
The boiler is set up for direct ow and storage tank
management. If Stemp. ACC is connected automatically, DHW is activated, which will have priority management with regard to direct ow through the pumps shown be­low.
Should additional services be requested (storage tanks, mixed areas, solar, etc), you must purchase SHC multifunction kits for full control through the Uy P heating control.
At the
corresponding terminal boards of the boards in
the
boiler
Alarm signal
12345
(-) GND
(+) 0-10V
678910 11 12 FL TA
Y2 -BCM
28
Alim. 230V
C.P. M.
P.
Mod.
SE
+
Stemp.
ACC
FL
TA
Connections for:
1
2
3
Y5
0
1
2
3
4
5
6
7
8
9
2
3
4
Y3
1
2
3
4
1
5
6
7
Y4
5
4
3
2
1
765
8
4
3
2
Y2
Y1
1
J1P
SHC
Modbus
Ufly
Y2 BCM
Modbus BCM A B
1 2
Remote boiler control A (1) Data connection B (2) Data connection
P. mod 4 - 5 Modulating heating pump
SE 6 - 7 External sensor
- / + 6 - 7 0 / 10 V signal contact
Stemp ACC ( * )
6 - 8 Storage Tank Temperature
Sensor
FL FL - 10 Flow switch (remove jumper)
INAIL 11-12 Safety devices
(remove jumper)
TA TA - 9 Room thermostat / Clock
remove jumper
Y4 - BCM
Alarm signal
(**)
3 - 4 Alarm / signal contact
(NO potential-free contact)
P. Coll. 1 - 2 Manifold pump (primary loop)
Y3 - BCM
P. CH 1 - 3 Heating circuit pump
P. Car DHW 1 - 2 Storage Tank loading Pump
UFLY
Y2 -
Modbus Uy
A
B
5 6
Remote Temperature A (5) Data connection B (6) Data connection
Control
Y1 BMM1
SHC (***)
8 - 4 - 3 Optional multifunction module
(to be inserted in the box cover)
ENGLISH
( * ) If the storage tank temperature sensor is connected, DHW ser­vice is automatically activated on boiler power supply. Parameter (803) Srv (is automatically updated).
( ** ) Relay contact that closes when in alarm mode
( *** ) SHC optional The system can power only one SHC module. If you need to have more than one SHC module, they must be placed externally in a dedicated electrical panel and powered with their own power supply unit.
Installation instructions
The BCM and SHC relay contacts support pumps with max. 4A absorption.
Modbus BCM can be used for control from building automation, can also be connected
with Modbus Uy to have a single bus.
29
PAGE LEFT INTENTIONALLY BLANK
30
Connection diagram example:
1
NPEL1
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
FL
1
C C CNC NC NO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
SE
Menu
B
Power supply, INAIL, Modulating pump, External sensor, Flow switch
230 V - 50 Hz
N
PE
L1
ENGLISH
PE
L1
2
D
N
KEY
No. Description
1 INAIL - Safety bodies
2 Main electrical panel (not supplied)
B Services connection return terminal board
D Wieland mobile pow. supp. socket 230 V -
50Hz
FL Terminals for Flow switch
SE Terminals for external Sensor
SMG Global ow sensor
P on_o󰀨 Manifold Pump Connections (on_o󰀨)
P mod Modulating pump Connections
Installation instructions
31
Connection diagram example: 2 modulex in pack managed by cascade manager
CH
P.
CH
Y4
1
2
3
4
1
2
3
123
4
5
6
Y3
Y2
1211 10 98765
4321
0
1
2
3
4
5
6
7
8
9
981011121314
2134567
Jp2
SE
24 V -DC
CM 140 - cascade manager
24 V -DC
BR
BK
R
S
M
G
FL
D
230 V - 50 Hz
L1
PE
N
2
L1
PE
N
1
C C CNC NC NO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
1
NPEL1
Menu
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
D
230 V - 50 Hz
L1
PE
N
2
L1
PE
N
1
NPEL1
Menu
+ 24 V
(-)
eBUS +
1
2
3
4
1
2
3
4
5
6
7
Menu
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
eBUS -
eBUS +
FL
1
C C CNC NC NO
1.3 (T.S.)
1.2 (P. min.)1.1 (P. max.)
SAFE
L
N
SS
M
Ext. MinDPIn
0-10V
P.
mod.
678910 11 12 FL TA
INAIL
Y2-BCM
12345
1
Y3-BCM
Y2-HSCP/UFLY
56
843
Y1-BMM1
4321
Y4-BCM
23
eBUS -
eBUS +
B
B
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
primary loop
(*) Note:
For the cascade connection, position the selector on the BCM in the indicated position.
(*)
(*)
(*) Note:
For the cascade connection, position the selector on the BCM in the indicated position.
32
CH
C
P.
CH
P. Car.
DHW
Stemp.
ACC
Y4
1
2
3
4
1
2
3
123
4
5
6
Y3
Y2
12 11 10 98765
4321
0
1
2
3
4
5
6
7
8
9
981011121314
2134567
Jp2
L
with direct zone and DHW production.
secondary loop
ENGLISH
Note: To congure cascade boiler management param­eters, refer to the specic installation manual.
Note:
Installation instructions
In case of installation with single boiler, the above connections must be made on the return terminal board (BCM board) inside the boiler.
Note:
Illustrative diagram, consider the total nominal
ow rate, any check valves (not supplied), and verify the e󰀩ciency of the ow switches at each ow rate in modulation.
33
Wilo Stratos modulating pump setting (ext. input enabling 0 - 10 V)
ON
ON
OFF
10V
ON
10V
34
3.11 - COMMISSIONING
Commissioning must be done by professionally
qualied personnel. Unical will not be held liable for damage to persons, animals or objects, due to
failure to comply with the aforesaid instructions.
does the installation meet the specic standards and regulations in force, both relating to the
gas part as well as the electrical part?
do the combustion air intake and ue gas exhaust take place properly according to what is dened by the specic rules and regulations in force?
is the fuel supply system sized according to the capacity required by the boiler? Is it equipped with all safety and control devices required by the standards in force?
is the power supply of the boiler 230V - 50Hz?
has the system been lled with water (approximately 0.8/1 bar pressure on the pressure gauge with the pump stopped)?
Has the condensation drain trap been lled with water as indicated in chapter 3.8?
are any system shut-o󰀨 gate valves open?
does the gas to be used correspond to the boiler calibration gas?: otherwise, perform the boiler conversion in order to use the gas available;
this operation must be carried out by technical sta󰀨 qualied in compliance with the standards in force;
is the gas supply valve open?
Before commissioning the boiler, check the following:
ENGLISH
has the system been checked for gas leaks?
is the outside main switch ON?
is the system safety valve e󰀩cient and is it connected to the drains?
is the condensation drain trap connected to the drains?
has the system been checked for water leaks?
are the ventilation conditions and minimum distances to perform any maintenance ensured?
have the GAS, HEATING and DOMESTIC HOT WATER pipes been cleaned thoroughly with products suitable for each circuit?
has a surveillance and protection system against gas leaks been installed? (Optional)
are the system pipes NOT used as the electrical system earthing?
has the system been sized properly bearing in mind the radiator pressure drops, thermostatic valves, radiator stop valves?
has the operator been trained and has the documentation been supplied?
Please tick the completed operations
Switching boiler on and o󰀨
To switch the boiler on and o󰀨, see the Uy reg­ulator manual
Installation instructions
35
3.12 -
3
1
2
4
MEASUREMENT OF THE COMBUSTION EFFICIENCY DURING INSTALLATION Generator Menu
3.12.1 - CALIBRATION FUNCTION (CHIMNEY SWEEP)
ATTENTION! Function reserved for After Sale Service Centres only.
3.12.2 - POSITIONING THE SENSORS
To determine the combustion e󰀩ciency
one must make the following measurements:
- measurement of the combustion air temperature
- measurement of the ue gas temperature and content of
CO2 taken in the relevant hole 2.
Take the measurements with the generator in steady state conditions (see par. 3.12.1).
ATTENTION!
These functions are explained in
chapter 2.9 (Burner menu) of the Uy P. TOUCH CONTROL instal­lation and maintenance manual.
All boilers leave the factory already calibrated and tested. However, if the calibration conditions
should be modied, it is necessary to recalibrate
the gas valve.
ATTENTION!
Remove cap 2, x the red cap 3 to the ue gas inlet 1. Insert the CO2 analysis sensor 4 in the cap hole. Perform the measurement. Remove the cap
and close the ue gas exhaust inlet with the
specic cap 2.
36
3.13 - ADJUSTING THE BURNER
A
B
B
B
A
C
D
All boilers leave the factory already calibrated and tested, however, if required, recalibrate the gas valves (MODULE 1, MODULE 2, etc.)
The following instructions are intended exclusively for authorised service personnel.
ENGLISH
ATTENTION!
To access the gas valves more easily, release the electrical panel “A” by means of the springs “B” (right and left). Slightly turn the electrical panel ”A” and lower the tilting panel “C”. Fix the tilting panel “C” for the time necessary for the adjustment operation, using the 2 M4 screws + washers ”D” (contained in the documentation bag).
Installation instructions
37
- Remove the cap and insert the CO2 analysis sensor in the
ue gas sample point of the intake/exhaust terminal, see
chap. 3.12.2.
1) Maximum output adjustment
- Operate the boiler in “calibration” mode at MAXIMUM OUT­PUT (see 3.12.1)
- Once the burner is on, check
that the “MAXIMUM” CO2 output value corresponds to that
indicated in the “NOZZLES - PRESSURE” table.
- If necessary, adjust the value by turning the ‘’S’’ adjustment
screw CLOCKWISE to decrease it and ANTICLOCKWISE to increase it
(see NOZZLES-CAPACITY-PRESSURE table).
2) Minimum output adjustment
- Operate the boiler in “calibration” mode at MINIMUM OUTPUT (see 3.12.1)
- Once the burner is on, check that the “MINIMUM” CO2 output value corresponds to what is indicated in the “NOZZLES ­PRESSURE” table.
- If necessary, adjust the value by turning (with a 2.5 mm hex
key) screw “R” CLOCKWISE to increase it, ANTICLOCK­WISE to decrease it
(see NOZZLES-CAPACITY-PRESSURE table).
(S)
ADJUSTMENT SCREW
MAXIMUM OUTPUT
In case of replacement of the Gas valve or
ignition di󰀩culties:
Tighten the maximum adjustment screw ”A”
clockwise up to the stop, then loosen by 7 turns. Check the boiler ignition, in case of a block, loosen the screw “A” again by one turn, then try igniting it again. If the boiler still stops running, perform the above operations again until the boiler ignites.
Now adjust the burner as previously illustrated.
(R)
ADJUSTMENT SCREW
MINIMUM OUTPUT
38
Follow this procedure to also adjust the other modules.
1
If the capacity read is too low, make sure the power feed and drain system (feed and drain pipes) are not clogged. If they are not clogged, make sure the burner and/or heat ex­changer is not dirty.
ENGLISH
ATTENTION To calibrate the VG (Gas Valves) in the boiler room, follow the procedures below.
The VG must be calibrated with chimney pressure = 0 Pa; for this reason:
- open the smoke duct 1 inspection door, after calibration, restore the door gasket.
INDICATIVE DIAGRAM, REFERRING TO BOILERS MODULEX 150 ÷ 350
C) CONCLUSION OF THE BASIC
CALIBRATIONS
- Check the CO2 values at minimum and maximum levels.
- If necessary, make any adjustments.
For proper operation, the CO2 values must be calibrated with particular attention, observing the values indicated in the table.
- Close the ue gas inspection inlet (1) with the specic cap
(2 - 3)
NOTE: Do not force the end stroke limits of the adjustment screw.
NOZZLES - PRESSURE - CAPACITY TABLE
MODULEX EXT: 440 - 550 - 660 - 770 - 900
Type of Gas Supply Press. Ø Noz-
[mbar] (mm) [Ø/mm] min FL max FU [%] [%]
min max IG
Nat. gas (G20) 20 9 NO 29 96 9.0 9.0 50
Nat. gas (G25) 25 9 NO 28 98 9.1 8.6 50
Nat. gas (G27) 20 9 YES 28 94 9.1 9.3 50
Propane (G31) 37 9 NO 28 90 10.2 10.4 50
MODULEX EXT: 348
Type of Gas Supply Press. Ø Noz-
[mbar] (mm) [Ø/mm] min max [%] [%]
min max IG
Nat. gas (G20) 20 9 NO 29 76 9.0 9.0 50
Nat. gas (G25) 25 9 NO 28 82 9.1 8.6 50
Nat. gas (G27) 20 9 YES 28 94 9.1 9.3 50
Propane (G31) 37 9 NO 28 73 10.2 10.4 50
zles
zles
Fan
deector
Fan
deector
Fan speed CO
Fan speed CO
levels Start.
2
levels Start.
2
power
power
Installation instructions
39
3.14 - EMERGENCY OPERATION AND SAFETY DEVICES
F1
AE
G
H
F
I
18:28
giov 30 20ott 18
effettiva
richiesta
76
°C
84
°C
generatore
10/10
modulazione
100
%
INFO MENU
status
sanitaria
25
°C
The BCM prevents system shutdown if the man-
agement of the Uy system or main boiler system
is out of service (Refer to the BCM manual)
A
YELLOW LED = ashing
(communication between BMM and BCM) ok
GREEN LED = on (Pump Active)
RED LED = on (Error code detected)
E Uy control panel
F TLG triggering lamp Main Limit Thermostat
G Fuse
H Main Switch
TLG Main Limit Thermostat, when it triggers it cuts
I
power to the boiler, the F lamp lights up. To rearm, remove the cap and press.
Condensate level sensor position
NOTE: The devices are positioned under the casing, next to the control unit.
NOTE: The emergency function only activates the
boiler burners at 100% on ow. All system loads,
including the manifold pump, must be manually controlled.
40
3.15 - PROGRAMMING THE OPERATING PARAMETERS
ATTENTION!
ATTENTION! Function reserved for After Sale Service Centres only.
BMM parameters
Code Symbol Description Unit Min. Max. Imp. Fab.
803 Srv Enabled Services 0 1
48
784 BC Local BUS address 0 7
816 MI Modbus Address 1 127
817 MT Modbus Time-out sec. 0 240
896 TU °Fahrenheit 0 1
799 AC Input 0/10V 0 2
376 DI1 Programmable Input #1 0 3
322 Po Pump: Post-circulation min. 1 30
341 PL Pump: Minimum Control % 0 100
313 Pr Pump: Maximum Control % 0 100
31 HL CH#1: Minimum Set-point °C 20 85
39 HH CH#1: Maximum Set-point °C 20 85
792 CHP CH: Max. Modulation % 0 100
619 IG Ignition Modulation % 30 80
527 PU Fan: PPR 0 3
486 FP Fan: Reg. Prop. 0 50
487 FI Fan: Reg. Int. 0 50
489 Fpl Fan: PWM min. % 5 15
337 Fr Modulation Gradient % 1.0
526 FU Fan: Max Max. Hz 50 120
319 FH Maximum Modulation % 1.0
346 FL Minimum Modulation % 1.0
314 Sb Modulation on Standby % 0 100
620 IP Postpurge: Fan % 0 100
617 IGL Ignition: Mod. Min. % 0 100
618 IGH Ignition: Mod. Max. % 0 100
353 HP CH PID: Proportional °K 0 50
354 HI CH PID: Integrative 0 50
478 Hd CH PID: Derivative 0 50
34 HY Burner Hysteresis °K 5.0 20.0
336 HS Temperature Gradient
483 rP
380 Al1 Programmable Sensor #1 0 2
777 AFC APS Control 0 2
805 LV Mains Voltage V 100 240
2590 Burner Output kW 10 1000
( ) LPG values
ChSet
CH#1: Set-point °C 20 85
°C/min
Gen: Temp. Max Di󰀨erential
°C 0.0 50.0
These functions are explained
in chapter 2.8 (DEVICES menu)
of the Uy P. TOUCH CONTROL
installation and maintenance manual.
100.0
100.0
100.0
0 30
ENGLISH
Installation instructions
41
BCM Parameters
Code Symbol Description Unit Min. Max. Imp. Fab.
803 Srv Enabled Services 16 27
483 rP Gen: Temp. Max Di󰀨erential °K 0.0 50.0
34 HY Burner Hysteresis °K 5.0 20.0
31 HL CH#1: Minimum Set-point °C 20.0 40.0
39 HH CH#1: Maximum Set-point °C 45.0 85.0
799 AC Input 0/10V 0 3
376 DI1 Programmable Input #1 0 2
322 Po Pump: Post-circulation min. 1 10
341 PL Pump: Minimum Control V 0 10
313 Pr Pump: Maximum Control V 0 10
792 CHP CH: Max. Modulation % 0 100
611 POT Gen: Err. Max. Parallel °K 0 30
612 POL Gen: Mod. Max. Parallel % 0 100
650 dL DHW: Minimum Set-point °C 25.0 45.0
385 dH DHW: Maximum Set-point 50.0 65.0
360 dt Heater Adjustment 0 15
656 drT DHW: Temp. Requested Di󰀨erential °K -20
20
657 drH DHW: Requested Temp. Hysteresis °K 1 20
310 DpT DHW Pump: Postcirc. sec. 5
660 dbT DHW: Temp. Maximum Boiler °C 50.0
48 ChSet CH#1: Set-point °C 20.0
600
85.0
85.0
64 ChPO1 CH#1: Parallel Supply 0 1
346 FL Minimum Modulation % 0 100.0
600 mB Burners: Min. Inserted 1 8
616 BSt Gen: Insertion Time sec. 30 900
613 BRt Gen: Removal Time sec. 30 900
336 HS Temperature Gradient °C/min 1 30
353 HP CH PID: Proportional °K 0 50
354 HI CH PID: Integrative °K 0 50
478 Hd CH PID: Derivative °K 0 50
816 MI Modbus Address 1 127
817 MT Modbus Time-out sec. 0 240
896 TU °Fahrenheit 0 1
309 St Application Code 0 1
368 VA1 Programmable Relay #1 0 1
369 VA2 Programmable Relay #2 0 1
771 PS Water Pressure Sensor 0 1
768 LG Sens. Min. Gas Pressure 0 1
793 COC Chimney Obstruction Sensor 0 2
622 FS Minimum Flow Sensor 0 1
42
3.16 - ERROR CODES
ENGLISH
Fault that causes the boiler to stop:
- The error code is displayed, the boiler has stopped running. After solving the failure, press Reset to restart the boiler.
CODE DESCRIPTION
detected on BMM
01
04
05
06
SAFETY THERMOSTAT Triggering of the safety thermostat (10)
BURNER
No gas or failed burner ignition
FLAME LOSS DURING OPERATION.
HIGH TEMPERATURE
Boiler temperature too high
INTERNAL FAULT
SOLUTIONS
Press the release button on the panel and/or check that the thermostat and its connections are not blocked, and make sure the INTC switches are closed (position 1)
Check the gas supply or that the ignition/detection electrode is working properly (4).
Check the detection electrode
Check pump operation and if needed clean the heat exchanger (24)
10 11
12 14 15
16
Flame detection prior to ignition (parasite
ame)
HEATING SENSOR (11)
Heating sensor fault
RETURN SENSOR (if present) Auxiliary (SRR) sensor interrupted
INSUFFICIENT WATER CIRCULATION
Primary circuit water circulation insu󰀩­cient (∆t > 40° C)
HEAT EXCHANGER
FREEZING ( 24 )
Heat exchanger freezing is detected. If
the heating sensor detects a temperature
below 2° C, burner ignition is inhibited
until the sensor detects a temperature
above 5°C.
Check the e󰀩ciency of the sensor (see Res/Temp table) (Par.4) or its
connections.
Check the wiring, if needed, replace the auxiliary sensor (22)
Check pump operation and its speed - remove any obstructions in the heating system
Disconnect power, close the gas valve, defrost the heat exchanger carefully.
Fault that does NOT cause the boiler to stop:
- The error code is displayed, the boiler has a heat­ing request, Reset icon (informing that a failure has been detected, even if the fault was temporary). Therefore, you must always carry out reset to can­cel the word “Error” displayed.
( Num ) = see key Par. 2.2
Installation instructions
43
22
NO AIR UPON IGNITION
Stop
UNEXPECTED AIR FLOW Blocked min pressure switch (closed)
23 24
26
27 30
32
CODE DESCRIPTION
2
17
19
28 29
37
38
40 56
57 58
SPEED OUT OF CONTROL
Alteration of the fan speed; the speed is not reached.
SPEED OUT OF CONTROL
Alteration of the fan speed; the speed is above that requested
NO AIR
Stop
FACTORY PARAMETERS
Alteration of the factory parameters or possible electromagnetic interferences.
Line voltage at 80% of the nominal val­ue. Wait until the line voltage is > 85% of the nominal value.
detected on HCM (BCM)
GAS PRESSURE MINIMUM PRES­SURE SWITCH TRIGGERED
stop e󰀨ect
HEAT EXCHANGER
FREEZING ( 24 )
stop e󰀨ect
FLOW OVERTEMPERATURE.
It is activated when the ow temperature
is > 95. Resetting is automatically carried out when the temperature is < 80. Eect: Stop burner, Pump On
CLOGGED OUTLETS
Stop
WATER IN THE COMBUSTION CHAM­BER
Stop
PARAMETERS MEMORY
DEFECTIVE
Flame Block
DAMAGED DEFAULT PARAMETERS due to electromagnetic interferences stop
FL INTERVENTION insu󰀩cient water
circulation Stop
NO REMOTE CONTROL DETECTED
Flame Block
BMM BOARD NOT DETECTED stop
FLOW SENSOR
Stop
Check that the fan head is at least 60 Pa.
Check fan operation (18) and the connections
Check fan operation (18) and the connections
Check that the fan head is at least 60 Pa.
Press the unblock key; if the anomaly persists, replace the board
Correction: if the line voltage is < 190Vac: the line voltage is really be­low the minimum limit, otherwise there is a monitor line error: replace BMM
SOLUTIONS
The ignition procedure is inhibited until gas pressure reaches the correct values.
Try to Reset since the system automatically activates an antifreeze function, therefore, it could only be a warning.
Circulation control
Check the Chimneys / Check the trap.
Check the combustion chamber / check the siphon.
Contact Customer Care
Contact Customer Care
Check water circulation
Check electrical connections e-BUS1
check electrical connections BMM and e-BUS
Connect a new sensor if the code disappears, replace the sensor other­wise check the electrical connections
93
The error codes are displayed in the info row of the remote console and remain there even if the fault is temporary. Therefore, you must always carry out a reset to cancel the word “Alarm” displayed.
44
ISPESL SAFETY DEVICES TRIG­GERING
Stop
check the safety devices, manually reset after releasing each individual safety device
4
INSPECTION AND MAINTENANCE
Inspections and maintenance performed profes­sionally and according to a regular schedule, as well as the use of original spare parts, are of the utmost importance for fault-free operation of the boiler and to guarantee its long life. Yearly maintenance of the appliance is mandatory in compliance with the Laws in force.
4.1 - INSPECTION AND MAINTENANCE INSTRUCTIONS
To assure long-term functioning of your appliance and to avoid altering its approved status, only original UNICAL spare parts must be used.
If a component needs to be replaced:
• Disconnect the appliance from the electrical mains and make
sure that it cannot be reconnected accidentally.
• Close the gas shut-o󰀨 valve upstream of the boiler.
• If needed, and depending on the intervention to be carried
out, close any shut-o󰀨 valves on the ow and return line of
the heating system, as well as the cold water inlet valve.
Failure to perform Inspections and Maintenance can entail material and personal damage
Once all maintenance operations are complete resume boiler operation
• Open the heating ow and return pipes, as well as the cold
water inlet valve (if closed previously).
• Vent and, if necessary, restore the heating pressure until
reaching a pressure of 0.8/1.0 bar.
• Open the gas shut-o󰀨 valve.
• Switch the boiler on
• Make sure the appliance is gas tight and watertight.
ENGLISH
OBLIGATION! wear protective gloves
TABLE OF THE RESISTANCE VALUES ACCORDING TO THE TEMPERATURE, HEATING SENSOR (SR) AND DHW SENSOR (SS) AND HEATING RETURN SENSOR, IF ANY (SRR)
T°C 0 1 2 3 4 5 6 7 8 9
0 32755 31137 29607 28161 26795 25502 24278 23121 22025 20987
10 20003 19072 18189 17351 16557 15803 15088 14410 13765 13153
20 12571 12019 11493 10994 10519 10067 9636 9227 8837 8466
30 8112 7775 7454 7147 6855 6577 6311 6057 5815 5584
40 5363 5152 4951 4758 4574 4398 4230 4069 3915 3768
50 3627 3491 3362 3238 3119 3006 2897 2792 2692 2596
60 2504 2415 2330 2249 2171 2096 2023 1954 1888 1824
70 1762 1703 1646 1592 1539 1488 1440 1393 1348 1304
80 1263 1222 1183 1146 111 0 1075 1042 1010 979 949
90 920 892 865 839 814 790 766 744 722 701
Relation between the temperature (°C) and the nom. resistance (Ohm) of the heating sensor SR and of the domestic hot water sensor SS
Example: At 25°C, the nominal resistance is 10067 Ohm At 90°C, the nominal resistance is 920 Ohm
Danger of burns!
Caution during maintenance operations.
Installation instructions
45
We recommend having qualified technical personnel carry out the provisions of current regulation concerning periodic maintenance checks.
Since the dust is vacuumed inside, the  ue gas side resistance,
through the boiler, increases which, eventually, will lead to a reduction of the thermal load (and, consequently, of the power). Before cleaning, check the thermal load (see 3.13) and the CO2 percentage (see 3.13). If the read load (with correct CO2) is around 5% of the indicated value, the boiler does not need to be cleaned. Therefore, the operation can be limited to cleaning the siphon
ATTENTION! A drop in thermal load may be caused by the obstruction of the exhaust duct or of the air inlet duct. Firstly check that this is not the cause.
If a load reduction is detected of more than 5%, check the cleanliness of the condensate collec­tion pan and of the burner. Clean the siphon also.
First phase – Disassembly
• Close the power and gas supply ensuring that the valve is
closed properly.
• Remove:
- all casings
- Act on the two rear closing hinges to remove the cover
- Remove the casing fastening screws, rear, front and lateral.
- Turn the indicated screw to lift the cover
- Remove the 2 cover fastening screws
46
- Remove the red silicon pipes and then the fan chamber
Element screws
ENGLISH
- Release the fan chamber fastening spring
(right/left side).
Installation instructions
- Remove screws “A” for each element
(with socket wrench and 13 mm  at spanner)
47
Element screws
- Remove screws “A” for each element (with 13 mm socket wrench)
- Remove the screws “B” (with 13 mm socket wrench / 13 mm hex spanner) and remove the fastening plates
- Remove the gas pipe fastening screws (right and left sides)
- Remove the four screws with a 10 mm socket wrench, then
the gas  ange
48
- Slightly lift the rear burner block and remove the 2 pins using a 5 mm hex spanner, until you reach the holes “C” (left and right side).
ENGLISH
- Lift the burner block (front part)
- Remove the gas  ttings from the gas manifold using the 36
mm  at spanner.
Installation instructions
49
Second phase – Cleaning
• Remove the gaskets and the burners.
• Dry clean the burners by blowing compressed air from the “ame side”
• Visually inspect the welding on the corner pieces and on the
burner mesh.
The burner gaskets must be replaced at each cleaning operation.
• Wash the combustion chamber with water, taking care not to
wet the electrical wiring.
During this operation, make sure that the condensate drain
pipe always remains clear so that the washing water does not leak from the inspection opening.
• Blow the combustion chamber with compressed air, trying to
remove any dirt still attached to the pins.
• When the parts have been washed, make sure that the con­densate drain trap is clear: clean it if necessary
• Inspect the ue gas exhaust pipe and the ue
Third phase – Re-assembly
• After cleaning the body and/or burners, put the burners back
in their seats
• Position the new graphite gaskets
When reassembling, proceed in reverse order, taking care to tighten the fastening
screws of the mixer/fan unit to the body, with
13 Nm tightening torque
ATTENTION AT EACH MAINTENANCE OPERATION, IT IS MANDATORY TO REPLACE THE SEALING GASKETS OF EACH BURNER.
• Before ignition, check that the condensation drain trap is properly lled with water.
• Before opening the gas supply valve again make sure that the previously loosened gas tting, is tight. To do this, open
the valve and check its seal with soapy solution.
• As a burner ignites, immediately check the seals between
each individual gas valve and its premixing chamber
• Analyse the combustion and check its parameters.
• Make sure that all opened gas pressure sockets are closed.
50
ENGLISH
PAGE LEFT INTENTIONALLY BLANK
Installation instructions
51
BL- N
BR - L1
R
BK
F-6,3A
A2
3
1
4
2
Modbus A
Modbus B
A1
Ufly
BR
BL
BK GND
BR eBU S+
R +24V
13 2
BR
BL
Y/G
BR
BK
BR
BL
BR
IG
2
1
GND
A4
3
1
4
2
1
23
A3
3
142
2 1
C
4L
1N
5L
2N
GND
+24V
eBUS+
IG1
IG2
YG/
Ufly
(M3)
ALIM.
230 V - 50 Hz
1b1a
BR
BL
Y/G
BCM
R
BR
BK
123
4
5
6
7
A2
A1
A4
A3
Y2
Y1
Y3
GND
1
2
123
BL
BR
Y G/
ST1
1
R
R
FILTER
4
N° MOD.
1
2-3
52 2-3/4-5
62 2-3/4-5
73 2-3/4-5/6-7
N
L1BR BL YG/
2
1
2
1
BK GN D
BR +e BUS
E.RIL.
1-7/8
TEFLON WH
BL
BR
YG/
ST2
1
BK (-)
BR (PWM)
BL (TA CHO)
OR (+)
OR +24V
BL XWDC
1 2
3 4
1
2
3 4
A2/A3-A2/A3
BMM2-7/8
PHS
1-2: FASEHNOT SENS. 2-3: FASE SENSIBH.
PIN1
123
4 56
789101112
123
4 5678
Y1
1 2
34
A2
1 2
34
A3
A1
123
456
A4
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
ROD1 ROD
F1
A2
BK GN D
BR +e BUS
OR +24V
BL XWDC
1 2
3
4
A3
(*) EXT 100 ÷ 350
C
NO
C NO
123
4 56
789101112
A4
S1R
WH
WH
SR
WH
WH
WH
BR
BL
BL
PF
min
TL T1L
BL
BL
ONLY
AUSTRALIA
MOD. 1
PF
min.
MOD. 2 - 7
BL
SR 2-7
PF
min
TL
2-7
WH
WH
WH
WH
BL
A4
123
4 56
789101112
123
456
A1
VM (R)
1 - 7 / 8
2345
A8
321 4
765 8
321
A7
4 5 6
A5
A6
eBUS + eBUS
+ 24 V
MOD. 1
KITSHC
(+24 V only
for 1SHC)
VM (A)
23
BR BL
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
BR BL
BL
BR
Y G/
ST1
1
VM (A)
23
ST1
1
VM (A)
23
BL
BR
Y G/
BR BL
1° Mod.
intermediate /
last module
FILTER POSITIONBETWEEN MOD.
ALIM.VENT.
ALIM.VENT.
EXT 100 ÷ 350
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
FILTER
(MV1)
BL BL
BK
BK
BK
BK
FILTER
ALIM.VENT.
EXT 440 ÷ 900
ALIM.VENT.
BMM
ONLY
AUSTRALIA
PF
min.
F1
4.2 - PRACTICAL CONNECTION WIRING DIAGRAM
L1
N
N
L1
N
L1
(MV1)
L1
L1
(M2)
N
(M1)
N
KEY
E. ACC. Ignition electrode
E. RIL. Detection electrode
HSCP / Uy Temperature control
SR Heating sensor (only mod.1)
SR 1...7 Local heating sensor
PF Flue gas press. switch (only mod.1)
PF min Flue gas minimum press. switch (only mod.1)
SL Condensate level sensor (mod.2)
T. ACC Ignition transformation
TL Limit thermostat
TL 1....7 Local limit thermostat
VG Gas valve
VM (A) Modulating Fan Power Supply
VM (R) Modulating Fan Det./Adjustment
SRR Global return sensor
PG
IG
Gas pressure switch
Main switch
52
SE
124
A4
ALIM (50)
+24V
GND
eBUS+
2134567
9
81011121314
2
1
C
NC
31
4
11
3
10
8
2
9
1
C
NO
13
6
A1
BR
WH
WH
WH
BR
BR
WH
BR
R
R
OR
OR
PF SL PG SRR
SMG
WH
WH
R
BK
BR
N
L1BR BL YG/
A5/A6-A5/A6
BMM2-7
2
1
2
1
E.RIL.
1-7/8
TEFLON WH
N
L
V1
N
L1
BL
BR
YG/
PHS
A8
321 4
765 8
321
A7
4 5 6
A5
2
1
A6
2
1
ROD1 ROD
F1
(*) EXT 440 ÷ 900
C
NO
C NO
123
4 56
789101112
A4
S1R
WH
BK
SR
WH
BK
WH
BR
BL
BL
PF
min
TL T1L
BL
BL
MOD. 1
MOD. 2 - 8
BL
SR 2-8
PF
min
TL
2-8
WH
BK
WH
BK
BL
A4
123
4 56
789101112
A8
321 4
765 8
321
A7
4 5 6
V2
VG
1 - 7 / 8
T. ACC.
1 - 7 / 8
1
E.ACC.
1 - 7 / 8
SILICON- R
YG/
BR
BL
A5
A6
N
BL
BR
Y G/
ST1
1
VM (A)
23
L1
N
BL
BR
Y G/
ST1
1
VM (A)
23
BK
BK
FILTER
(*)
NO
AUSTRALIA
ONLY
AUSTRALIA
PF
min.
ONLY
AUSTRALIA
PF
min.
VI
VIOLA
M2
+24V
G
V
TA
FL
INAIL
R
WH
Stemp. ACC
12 11 10 98 765
Y2
123
COLOURS
BLUE BROWN BLACK
ENGLISH
C.P.M.
P. Coll.
GREEN
P. CH
P. Car. DHW
GREY SKY BLUE ORANGE
1
2
3
4
PINK RED YELLOW YELLOW GREEN WHITE VIOLET
0-10V -
INGR ANA LOG.
GND 0-10V - INGR.
Modbus B
eBUS-
eBUS+
4321
Jp2
4
5
6
COM AND
USC ALL ARM SIGNAL
Modbus A
3
4
Y4
0
1
9
2
8
3
7
4
6
5
2
1
2134567
981011121314
COM AND
COM AND
COM .
3
1
2
Y3
0
9
8
7
6
5
PF
min
Installation instructions
TLG
LTLG
F
BCM (*) the connections reported below are only meant as an indication and are to be carried out on the services return terminal boards ‘‘B’’ indicated in chap. 3.10.
Main limit thermostat
Main limit thermostat lamp
Fuse
SMG Global ow sensor
S.temp ACC Storage tank temperature sensor
SE
External temperature sensor
ANALOG INPUT
GND 0-10V ING
0-10V C.P.M.
ALARM SIGNAL
Comm P. COLL
Comm P. CH
P. car DHW
COM.
Analogue input
Analogue input 0-10 V
Modulating Pump Control
Alarm Output
Boiler manifold pump control
Heating pump control
Storage tank loading pump control
Common
53
46033 Casteldario - Mantua - Italy - tel. +39 0376 57001 - fax +39 0376 660556
www.unical.eu
ed. 01/19
st
TRANSLATION OF ORIGINAL INSTRUCTIONS - 00338303EN - 1
AG S.p.A.
info@unical-ag.com - export@unical-ag.com - www.unical.eu
Furthermore, it reserves the right to modify its products as deemed necessary or useful, without a󰀨 ecting their essential features.
Unical shall not be held liable for any inaccuracies due to transcription or printing errors.
Loading...