This INSTRUCTION MANUAL, which is an integr al and indispensable part of the product, must be handed over to the user b y the plumbers and
must be kept in a safe place for future reference. The manual m ust be handed ov er with the boiler should it be sold or transf erred.
This boiler must be used for the purposes for which it has been designed. Any other use shall be considered incorrect and therefore
dangerous.
The boiler must be installed in compliance with applicable laws and standards and according to the manufacturer’s instructions given in this
manual. Incorrect installation ma y cause injury to persons and/or animals and damage to property. The manufacturer shall not be held liab le for any
such injury and/or damage.
Damage and/or injury caused by incorrect installation or use and/or damage and/or injury due to non-observance of the manufacturer’ s instructions
shall relieve UNICAL from any and all contractual and e xtracontractual liability.
Before installing the boiler, check that the technical data corresponds to requirements f or its correct use in the system.
Check that the boiler is intact and that it has not been damaged during transport and handling. Do not install equipment which is patently damaged
and/or faulty.
Do not obstruct the air suction and/or heat dissipation grates.
Only original accessories must be used for all boilers supplied with optionals or kits (including electrical ones).
Dispose of the packaging with care as all the materials can be recycled. The packaging must therefore be sent to specific waste management
sites.
Keep the packaging out of the reach of children as it may represent a choking and suff ocation hazard.
In the event of failure and/or faulty functioning, switch off the boiler. Do not attempt to mak e repairs: contact qualified technicians.
Original parts must be used for all repairs to the boiler.
Non-observance of the above requirement may jeopardize the saf ety of the boilers and expose people, animals and property to danger.
To guarantee efficiency and correct functioning of the equipment it is legally binding to service the boilers once a year according to
the schedule indicated in the relative section of this manual.
In the event of long periods of inactivity of the boiler , disconnect it from the po wer mains and close the gas tap (W arning! In this case the boiler’ s
electronic anti-freeze function will not be operative).
Should there be a risk of freezing, add anti-freeze: it is not advisable to empty the system as this may result in damage; use specific anti-freeze
products suitable for multi-metal heating systems.
N.B.
For boilers which use gaseous fuel, if you smell gas:
- do not turn on or off electrical switches and do not turn on electrical appliances;
- do not ignite flames and do not smoke;
- close the main gas tap;
- open doors and windows;
- contact a Service Centre, qualified installer or the gas supply company.
Never use flames to detect gas leaks.
WARNING
This boiler has been built for installation in the country indicated on the technical data plate: installation in any other country may be a source
of danger for people, animals and property.
Read the warranty conditions and clauses on the warranty certificate attached to the boiler with care.
2
DAT A PLA TE
®
1
2
15
17
19
G20
2H
G20
2E
G30/G31
3+
G30 - 31
3B/P
G31
3P
1 = P.I.N. code
2 = Boiler type (only for condensing boiler)
3 = (S.N°) Serial Nr.
4 = Manufacture Date
5 = Model
6 = Appliance type
7 = Elettrical supply
8 = Maximum absorbed power - Insulation
protection
3
9
12
20 - 25
20
28-30/37
30 - 50
37 - 50
4
/
6
16
18
mbar
mbar
mbar
mbar
mbar
IT ES IE
PT GR
TR HR
CZ SK
HU
SI
GB
CN RU RO
LV E E LT
7
10
13
20
II 2H3+
II 2H3+
II 2H3B/P
II 2H3P
II 2HS 3B/P
II 2E3P
II 2H3P
I 2H
I 2H
9 = (Pn) Nominal Output
10 = (Pcond) Condensing Nominal Output
(only for condensing boiler)
11 = (D) Specific flow rate EN 625
12 = (Qn) Nominal heat input
13 = (Qnw) Nominal heat input for D.H.W.
system if there are different out puts
between the C.H. and D.H.W . circuits
14 = (NOx) NOx Class
5
20 ; 28-30/37 mbar
20 ; 28-30/37 mbar
20 ; 50 mbar
18 ; 50 mbar
25 ; 30 mbar
20 ; 50 mbar
20 ; 37 mbar
20 mbar
20 mbar
21
8
11
14
15 = (PMS) Max pressure C.H. system
16 = (T max) Max T emperature C.H. system
17 = (PMW) Max pressure D.H.W . system
18 = (T max) Temperature D.H.W. system
19 = Adjusted for gas type X
20 = Countr y of destination, Gas category,
Supply pressure
21 = Side for national brand
3
1
TECHNICAL FEA TURES
AND DIMENSIONS........................................................... pag.6
1.1 T echnical F eatures .................................................................. pag.6
Low NO
up by one sectional boiler body (so
called
separately or in cascade.
This heat module consists of two or
more thermal elements (from 4 to 7),
which cannot be separated from
each other, being under the same
protecting casing. These thermal elements are connected to a single
smoke exhaust manifold and are
controlled by a single microprocessor which manages completely the
temperatures from the point of view,
both operational and safety.
-If, for instance, one of the thermal
elements whose the boiler is composed, goes out of order, the other
thermal elements continue to supply their output. It is nearly impossible the boiler go completely out of
order.
-MODULEX has been examined ac-
cording the following European directives:
-(GAD) Gas Appliances Directive
-(BED) Boiler Efficiency Directive
by CERTIGAZ, under the No .
1312BP4012, for type B23 operation,
i.e. the boiler can be connected to a
traditional natural draught chimney,
and for operation in category I
–20 mbar).
It also conforms to the following European directives:
-EMC (Electro Magnetic Compatibi-
lity) Directive No. 89/336 CEE
-L VD (Low V oltage Directiv e)
-Machines Directive
-The boiler body, made by sections
of cast aluminium/magnesium/silicium alloy, is conceived to recover
the sensible and the latent heat of
the combustion gases, thus allowing to reach an efficiency of
109% on the N.C.V.
-Each thermal element, composed of
a combustion chamber with burner,
modulating fan with control pressure switch, gas valve, ignition device, flame control, NTC sensor for lo-
6
, condensing boiler, made
x
heat module
No. 73/23 CEE
No. 89/392 CEE
), set to operate
No. 90/396 CEE
No. 92/42 CEE
2H
(G20
cal temperature control and safety
thermostat, can deliver an output
between a maximum of 90 kW and a
minimum of 22 kW .
4
360
5
450
6
540
7
630
-Each single boiler is equipped with
NTC sensors for global temperature control on the flow and return manifolds.
-Total premix modulating burner
equipped with metallic sponge radiation burner.
Premix in the pre-combustion chamber. Automatic no return diaphragm
for separation from combustion
chamber.
-Combustion air suction/feeding system from the boiler house
-Possible cascade installation of 2 or
more MODULEX
-Heating Operation: setting of instantaneous output by a main microprocessor, with a comparison parameters pre-setting between the requested temperature (or calculated by
the outer compensator) and the global flow temperature.
-Logic of operation:
A) Output sharing on as many modules as possible at min. load (down
to 22 kW) for the max. efficiency.
B) Automatic operation hour splitting-up system for each module to
guarantee the best homogeneous
use.
C) DHW production by a priority sensor which, thanks to the dedicated
electronic board, drives a special
loading pump or a 3-way diverting
valve for the preparation of a storage tank with the possibility of presetting the D.H.W. circuit output, up
to maximum 360 kW .
D) Output check of each module for
any calibration and/or assistance by
secret access code.
-Control panel with alphanumeric display, programming keys, reset and
hydrometer .
-Displays: global flow/return temperature, DHW temperature, external tem-
60
75 l/h
90 l/h
105 l/h
perature.
-Adjustments: flow temperature, fan
speed, max/min. output percentage.
-Access to all testing/programming
parameters of each module: operation
test, operation time, boiler anti-frost
protection from 7°C, pump’s anti-
blocking system.
-Integral easily removable panel set
l/h
(painted steel panels).
-Condensate collecting tank equip-
ped with drain siphon and stainless steel smoke chamber.
-Built-in air vent.
-Weights and dimensions are limi-
ted (see table at par. 1.2).
1.2 - DIMENSION
MODULEX 360
Øi D
L.H. SIDE VIEW
B
A
ATTENTION
CHIMNEY
CONNECTION
INDIFFERENT
POSITION FROM THE
ONE SHOWN ARE
S
NOT ALLOWED.
C
110
UPPER VIEW
666
FRONT VIEW
576
1243
T
E
E
P
R
E
E
D
S
T
O
O
T
E
S
M
R
S
REAR VIEW
474
920
®
446
171
398
G
206
M
H
1372
232
R
974
124
MODULEX
Dimension
No. of Modules
Heightmm
Width ''L'' netmm
Width with packagingmm
Depth ''C''mm
Depth ''A''mm
Depth ''B''mm
Depth with packagingmm
Net weightkg
Gross weightkg
Connections
Gasmm
C.H. system Flow Mmm
C.H. system Retur n Rmm
Chimney connection ''D''mm
Chimney width ''H''mm
Condensate drain diametermm
474
fig. 1-a
360
4
1372
920
1020
1530
985
390
1200
430
496
DN50 PN 10/16
DN80 PN 10/16
DN80 PN 10/16
250
615
40
7
MODULEX 450 - 540 - 630
R.H. SIDE VIEW
G
F
=
UPPER VIEW
124
124
110
666
232
474
ATTENTION
CHIMNEY
CONNECTION
INDIFFERENT
POSITION FROM THE
ONE SHOWN ARE
NOT ALLOWED.
Øi D
206
1243
576
E
P
R
E
T
O
T
S
S
=
FRONT VIEW
(D) 1520
920
®
T
E
D
E
S
O
E
M
R
REAR VIEW
=
G
M
R
171
(E) 425
398
1372
974
425
600
350
175
H
MODULEX
Dimension
No. of Modules
Heightmm
Width ''L'' netmm
Width with packagingmm
Width ''D''mm
Width ''E''mm
Depth ''F''mm
Depth with packagingmm
Net weightkg
Gross weightkg
Connections
Gasmm
C.H. system Flow Mmm
C.H. system Retur n Rmm
Chimney connection ''D''mm
Chimney width ''H''mm
Condensate drain diametermm
450
1372
920
1020
1520
445
1120
1320
1340
510
584
DN50 PN 10/16
DN80 PN 10/16
DN80 PN 10/16
250
615
40
5
DN50 PN 10/16
DN100 PN 10/16
DN100 PN 10/16
S
540
1372
920
1020
1520
425
1256
1380
1700
620
700
300
720
40
6
DN50 PN 10/16
DN100 PN 10/16
DN100 PN 10/16
fig. 1-b
630
7
1372
920
1020
1520
425
1390
1514
1840
680
778
300
855
40
8
1.3 - TECHNICAL DATA
The Technical data plate is placed under the front jacket next to the control
panel.
kW
Efficiency at max. output (Tr 60 / Tm 80°C)%
Efficiency at min. output (Tr 60 / Tm 80°C)%
Efficiency at max. output (Tr 30 / Tm 50°C)%
Efficiency at min. output (Tr 30 / Tm 50°C)%
Efficiency at 30 % at part load (Tm 50°C)%
Efficiency at 30 % at part load (Tr 30°C)%
Efficiency Class acc. to Directive 92/42 CEE
Efficiency Class acc. to Directive 92/42 CEE (100%)%
Efficiency Class acc. to Directive 92/42 CEE (30%)%
Combustion efficiency at nominal load%
Combustion efficiency at part load%
Stand-by losses (Q min.)%
Stand-by losses (Q nom.)%
Flue gas temperature (min)°C
Flue gas temperature (max)°C
Flue gas mass flow rate (min)kg/h
Flue gas mass flow rate (max)kg/h
Excess of air λ%
(min)%
CO
2
CO2 (max)%
NOX (value according EN 297/A3 + EN 483)mg/kWh
NOX class
Flue losses with burner in operation (min.)%
Flue losses with burner in operation (max)%
Flue losses with burner off%
Min. water flow rate in CH circuit (∆T 20°C)l/h
Minimum pressure in CH circuitbar
Maximum pressure in CH circuitbar
DHW specific flow ratel
Gas Consumption Natural gas G 20 (20 mbar) Qnm
Gas Consumption Natural gas G 20 (20 mbar) Qminm
3
/h
3
/h
Max. available pressure at the chimney basePa
Condensate productionkg/h
Emissions
CO with 0% of O
in the flue systemppm
2
NOx with 0% of O2 in the flue systemppm
Sound leveldBA
Electrical data A
Voltage / FrequencyV/Hz
Fuse on main supplyA (F)
Max / Min absorbed powerW
Insulation degreeIP
Standby ConsumptionW
360
360
22
353,9
21,3
377,60
23,80
98,30
96,82
104,89
108,18
102,0
109,2
98,10
96,65
97,52
97,86
1,0
n.r
42
50
36,6
583,0
24,25
8,9
9,2
62
2,48
2,14
0,2
16237
0,5
73
38,06
2,33
100
22,7÷60
<35
<35
<50
230 / 50
540/41
40
10
4
5
6
-
28,3÷75
230 / 50
4
450
450
22
442,5
21,3
472,0
23,80
98,33
96,82
104,89
108,18
102,0
109,2
98,29
96,94
97,52
97,86
1,0
n.r
42
50
36,6
728,7
24,25
8,9
9,2
62
2,48
2,14
0,2
20296
0,5
88
47,58
2,33
100
<35
<35
<50
675/41
40
10
4
5
6
-
-
230 / 50
4
540
540
22
531,8
21,3
566,4
23,80
98,48
96,82
104,89
108,18
102,0
109,2
98,45
97,18
97,52
97,86
1,0
n.r
42
50
36,6
874,4
24,25
8,9
9,2
62
2,48
2,14
0,2
24355
0,5
103
57,10
2,33
100
34÷90
<35
<35
<50
810/41
40
10
104,89
108,18
4
1020,2
5
28414
6
-
39,7÷105
230 / 50
4
945/41
630
630
22
621,3
21,3
660,8
23,80
98,62
96,82
102,0
109,2
4
98,59
97,38
97,52
97,86
1,0
n.r
42
50
36,6
24,25
8,9
9,2
62
5
2,48
2,14
0,2
0,5
6
118
66,61
-
2,33
-
100
<35
<35
<50
4
40
10
9
1.4 - SIDE VIEW WITH MAIN COMPONENTS
FAN
GAS VALVE
GAS PIPE
BURNER
C.H. FLOW
C.H. RE TURN
CONDENSATE
COLLECTING
TRAYSMOKE
MANIFOLD
BOILER FRAME
FILLING-UP
ELBOW
Min. Depth 100 mm
ALUMINIUM/
SILICON HEAT
EXCHANGER
CONDENSATE
DRAIN
SIPHON
150
fig. 2
2.1 - COMPOSITION OF THE
SUPPLY
- Boiler body made of sections of alumi-
nium/magnesium/silicium alloy (5 to 8)
- Premix stainless-steel burner (4 to 7)
- Premixing chamber (8 to 14) with bu-
ilt-in non return valve
- Modulating fan (4 to 7) with air pres-
sure switch control
- Gas valve (2 for each module – from 8
to 14) with separated flame control
device SATRONIC (from 4 to 7)
- NTC sensors for local temperature con-
trol on each boiler section (5 to 8)
- NTC sensor for global flow manifold
10
temperature
- NTC sensor for global return manifold temperature
- High Limit thermostat on each boiler
section (5 to 8)
- Automatic air vent on the flow manifold
- Boiler draining/filling tap on return
manifold
- Minimum gas pressure switch on gas
manifold
- Condensate collecting tray
- Plastic pipe (1m) and fittings for condensate evacuation Ø40
- Smoke chamber terminal, with flue soc-
ket:
Ø 250 mm for models 360 and 450
Ø 300 mm for models 540 and 630
- Integral painted steel casing
- Modulation and control PCB (MBD)
with PC interface
- AM-4 PCB for DHW production and
outdoor temperature sensor
- Supplementary PCB type AM-5 (1 x
mod. 360; 2 x mod. 450 and mod. 540;
3 x mod. 630)
- Electronic card for interface
- Outdoor sensor (into the smoke chamber)
2
IINSTRUCTIONS FOR
INSTALLERS
2.1 - INSTRUCTIONS FOR INSTALLATION
The MODULEX boiler is foreseen for the
I
gas category and shall be installed
2H
in compliance with the latest regulations
or rules in force.
2.2 - INSTALLATION
2.2.1 - PACKING
The MODULEX boiler is delivered into a
strong carton box, complete of pallet (in
order to easily transport the boiler up to
the nearest point of installation place. The
procedures for unloading the boiler are
shown into the figure 3.
Remove both straps and finally the cardboard box from above, making sure the
product is intact. The packing elements
(cardboard box, straps, plastic bags,
etc…) shall not be left to children’s
hand since they may be dangerous.
For the pallet removal is necessary to lift
the boiler: it’s necessary to use a jib crane (like shown into the figure 3), in order
to avoid of damage the pressure
switches, gas valves or electric cables.
- Remove the jacket and prepare the
sling with the bands “A” (fig. 3) by taking
care of let the bands pass internally of
flow , return and gas manifolds.
- Bind the bends to the jib; during this
step be particularly careful.
Inside the packing,
on the rear part of the boiler, for Modulex 360 – 450
on the front part of the boiler, for Modulex 540 – 630
you can find the smoke chamber , containing:
- a plastic bag containing:
• 3 gaskets (1 rectangular between
condensate tray and flue terminal, 1
square between flue socket base and
flue terminal and 1 for flue socket Ø
250 or Ø 300 mm according to the
model
• 2 bends + 1 Tee piece + 1 plastic plug,
Ø 40 mm for condensate drain.
• the screws necessary for fixing
- A plate for the jacket closing, only for
models 540-630
- The outdoor sensor
- The siphon pipe for condensate drain
on the L.H. side of the boiler:
- the R.H. side panel connected to the
L.H. side one by a thermoretractable
film.
Special attention shall be paid to local regulations and laws about boiler houses and
particularly to the obligation of keeping
minimum clearances and empty space
around the boiler. The installation shall be
in compliance with all latest regulations
and laws about boiler houses, installations
of heating and hot-water systems, ventilation, chimneys capable of evacuating
the flue gases of condensing boilers and
any other applicable requirement.
2.2.3 - BOILER CONNECTION
The boiler Modulex leaves the factory predisposed for the hydraulic and gas connection on the back side of the boiler. The
smoke outlet is placed on the back side
When selecting the position for the
installation of the boiler it has to be
considered that, for the cleaning and
washing operations of the boiler
body , one of the boiler sides must be
accessible for the removal of a special baffle placed under the aluminum
sections.
of the boiler for MODULEX 360; it's placed on the R.H. side of the boiler for MODULEX 450 - 540 - 630.
For the smoke chamber fixing, use the
The boiler can be put on a flat and sufficiently strong base with the same di
mensions as the boiler ones and at least 100mm high (see fig. 5), in order to
assemble the condensate drain siphon.
An alternative to this base may be a
100 mm deep well next to the boiler as
siphon housing (see fig. 2). After installation the boiler shall be
perfectly horizontal and stable, to reduce any possible vibrations or noises.
screws and gaskets included into the instruction bag, and a cross screwdriver at
least 300 mm of length.
2.2.4 - CONNECTION TO THE
CHIMNEY
ATTENTION:
BEFORE ASSEMBLING THE CHIMNEY DUCT IT’S ABSOLUTELY NECESSARY TO SET A SUPPORT UNDER THE SMOKE CHAMBER TERMINAL
Into a condensing boiler, the smokes reach a very low temperature (Max 84°C).
So, it’s necessary that the chimney is
perfectly impermeable to condensation of
combustion products and built with materials corrosion resistant.
The various spigot joints have to be well
sealed and endowed with provided for
2.2.4.1 - MA TERIALS FOR FLUE
PIPES
As material can be used the stainless
steel AISI 316 L or AISI 316 Ti, with a
minimum wall thickness of 0.4 mm, or the
aluminium, with a minimum wall thickness
gaskets, so that to prevent the condensation spillage and the air entry.
For the chimney dimensioning, diameter
and height, it is necessary to make reference to the national and local regulations.
In order to avoid, during the operation, the
ice formation, the temperature of the inside wall in every point of the system for
the combustion products evacuation, for
all of its length, doesn't have to be lower
than 0°C.
For operation in condensing conditions
with the outdoor temperature of project, it
will be therefore necessary the realization of a system of confluent condensation drain, according to the installation
conditions, in the collection box of the
boiler or separated by it.
of 1.5 mm, or the PVDF (Polyvinildimethylfluorure), or the PPS (Simple transparent polypropylene), certified for this
use. Other materials and thicknesses are
also admitted, provided they guarantee at
least equivalent caracteristics.
In case of tubing of an existing chimney
360
450
540
630
the flue pipe has to be of aluminium (min.
thickeness of 1.5 mm) or of stainless
steel (min. thickness of 0,4 mm) and its
connections have to be water proof.
4
5
6
7
250
250
300
300
13
2.2.5 NOTES ON CONDENSATE
DRAIN
Avoid the condensate stagnation inside
the combustion products evacuation
system, (for this reason the evacuation
duct must have an inclination toward the
drain of at least 30 mm/m) except the
liquid column, inside the condensate
siphon (which needs to be filled with
water after installation: its minimum
height, when all the fans are in operation, must be at least 25 mm).
In order to avoid ice formation while the
INITIA L SIPHON
FILLING-UP PLUG
0
5
1
BOILER HOUSE
FLOOR
boiler is operating, which can cause the
stop of the boiler, the whole condensate
evacuation system has to be well insulated. It is forbidden to evacuate the condensate through a gutter: risk of ice formation and corrosion.
The condensate, before being evacuated to the sewer , has to be neutralised,
neutralization which can be obtained by
mixing the drain water coming from
washing machines, dish washing ma-
The upper part of the drain
pipe shall not be higher
than the tray bot tom.
chines, etc., which normally have a
basic pH. The connection to the sewer
will be through a visible drain. Given
the high acidity degree (pH 3 to 5) only
plastic materials can be used for the
condensate evacuation pipes. Moreover it must be dimensioned and constructed so as to allow the correct outflow of drains preventing any bottleneck
and any leakage.
0
5
1
* Min. height of the condensate column,
with all fans operating at max. speed,
requested by the EN standards.
2.2.6 - WATER TREATMENT
If the installation needs a water treatment the following conditions are to be
respected:
- the pH, for boilers with aluminium
alloy body, must always be within
6.5 and 8;
2.2.6.1 - REPLACEMENT OF AN EXI-
STING BOILER BY A MODULEX
In case of installation of a MODULEX on
an old C.H. system we recommend to
purge and to rinse properly the whole
system before connecting the new boiler.
To avoid misunderstandings it is sug-
** Min. height of the condensate column,
with all fans operating at max. speed. In
the case it is not possible to create a 100
- all precautions will be taken to avoid
the formation and localisation of oxygen in the water of C.H. systems. For
this reason it will be necessary that
in the C.H. systems using floor radiant
heating, the plastic pipes used are
impermeable to the oxygen;
- in case of utilisation of anti-frost so-
gested to interpose between the boiler
and the system, a plate heat exchanger.
On the contrary , in case of installation of a
MODULEX on a new system we recommend to make a simple water rinse of the
mm basement, install the boiler on the
floor and foresee a min. 100 mm well to
lodge the siphon (see fig. 2).
fig. 5
lutions, their compatibility with aluminium alloy and other components
of the C.H. system has to ascertained.
whole system and to fit a Y filter on the return pipe to the boiler, equipped with gate
valves.
14
2.3 - EXAMPLES OF
HEATING SYSTEMS
®
576
1243
E
T
E
P
R
D
E
E
S
O
O
T
T
E
M
R
S
S
The following system figures are to illustrate some, but not all types of heating
systems.
Flow
See fig. 16
1112 13
Return
Filter
Boiler pump
Fig. 6.1 Heating system with one group of radiators.
®
576
1243
T
E
E
E
R
P
S
E
D
O
O
T
T
E
M
S
S
R
Flow
See fig. 16
11
1213
Mixing bottle
Mixing bottle
Heating system
pump
D.H.W. Circuit
1718
See fig. 16
16
Heating circuit
Heating Circuit
Return
Filter
Boiler pump
Fig. 6.2 Installation of a boiler with a mixing bottle and connection to a heating circuit with DHW production (storage tank output< or = boiler
output).
Heating Circuit Heating Circuit
1243
Heating Circuit
®
576
T
E
E
P
E
D
R
S
E
E
O
O
T
T
R
M
S
S
Mixing bottle
Flow
See fig. 16
1112 13
Return
Filter
Boiler pump
Fig. 6.3 Heating system with mixing bottle and flow temperature control by an outer compensator. More radiator groups are
controlled by a dedicated outer compensator. The heating curve of the boiler outer compensator has to be adjusted at 5 K above the
temperature of the radiator group working at the highest temperature.
15
1243
Heating C ir cuit
See fig. 16
1617 18
Heating
system pump
D.H.W . Circuit
No ret urn
valve
®
576
T
E
E
E
R
P
S
D
E
O
O
T
E
T
R
M
S
S
Mixing bottle
Flow
See fig. 16
1213
11
Return
Filter
Boiler pump
Fig. 6.4 D.H.W. storage tank with loading pump installed on the secondary circuit, in parallel with the heating circuit.
Note: The Pr pump (heating pump) shall be off while the storage tank pump is running. In this case, the second digit of
parameter A shall be set to 2 (three-way valve).
For the connection of a boiler pump on the primary circuit or of a storage tank loading pump or a three-way valve, convenient
information can be found in the following table, which indicates the terminals supplied with 230 V in the different hypothesis.
Is there any heating demand?
Is there any D.H.W. demand?
YES/ NOYES / NOYES / NO
YESNOYES
YES
NO
NO
NO
D.H.W. priority system
configuration depending on 2
nd
figure of “A Parameter”
230 V - 50 Hz tension
is present at
terminals 16 - 18
230 V - 50 Hz tension
is present at
terminals 11 - 13
(see paragraph 3.2.8.2)
parameter A = x 0
parameter A = x 1
parameter A = x 2
The terminals 11 –13 will be supplied on tension 230 V in the case the pump after running is activated.
nd
2
figure
nd
2
figure
nd
2
figure
YES
NOYES
YESNONO
NOYESYES
YES
YES
YES
NO *
NO *
NO *
2.3.1 - VENTING OF THE C.H. SYSTEM
An effective air vent shall be foreseen
in the highest point of the system. Inside
2.3.2 - BOILER AND HEA TING
SYSTEM FILLING-UP &
DRAINING
For filling-up the system a filling tap has
to be foreseen on the system return pipe.
The filling-up can also be made through
the draining tap on the boiler return
manifold.
16
the boiler, there is an automatic air vent
on the flow manifold (see fig. 2). This air
In both the cases, an approved hydraulic
disconnection system has to be fitted.
Before connecting the boiler, carefully
rinse out the whole system by running
water .
The boiler is equipped with its own draining tap (see fig. 2 for its position).
Never use such a tap to drain the sys-
vent is foreseen for the boiler , not for
the whole system.
tem, since the system dirt could gather
in the boiler and compromise its operation. The system itself shall be equipped
with its own draining tap , whose size depends on the system capacity . The application of a filter on the return pipe to the
boiler is advisable.
2.3.3 - MAX ALLOWABLE WORKING
PRESSURE
The boiler max allowable working pressure is 6 bar, while the min. one is 0,8
bar.
The boiler does not have any special
protection device against water lack,
2.3.4 - SAFETY PRESSURE RELIEF
V AL VE (not supplied)
A safety valve dimensioned for the system capacity and in compliance with
local regulations in force shall be installed
2.3.5 - GAS MAINS
Due to the presence of a min. gas pressure switch, the gas main diameter shall
be calculated carefully. Even though the
since this function is carried out by the
safety thermostats of the modules with
timeliness. However, the installation of
a min. pressure switch as well as its electric connection are foreseen (1/4” con-
on the flow pipe (within 500 mm from the
boiler).
gas valves have their own filter,
UNICAL suggests one further filter easy
to be checked, to be installed on the
nection on the return manifold and electrical in series connection on the min.
gas pressure switch terminals).
gas pipe supply.
2.3 . 6 - HYDRAULIC COMPENSA T OR
OR OPEN MANIFOLD
For the correct operation of the boiler,
the use of an hydraulic compensator is
advisable because it guarantees:
- separation and gathering of circuit dirt
- best air venting
- hydraulic de-coupling of the two
hydraulic circulation circuits.
TABLE FOR THE RECOMMENDED
DIMENSION OF THE HYDRAULIC
COMPENSATOR
BOILER
CIRCUIT
360 kW
360 - 450
450
- 540 - 630 kW
Over
> 630 kW
F
I
L
T
E
R
kW
C.H. FLOW
KVKR
20.000
30.000
50.000
100.000
150.000
200.000
g
200
250
300
400
500
600
1/2’’
100
125
150
200
250
300
D
1/2’’
HV
e
C.H. FLOW
HEATING
g
c
SYSTEM
CIRCUIT
h
1/2’’
100
125
150
200
250
300
200
200
250
250
300
300
HR
b
a
1/2’’
300
300
300
300
400
400
1.000
1.000
1.000
1.500
1.500
1.800
C.H. RETURN
150
1.650
150
1.650
150
1.700
200
2.250
300
2.500
300
2.800
fig. 7
200
200
200
200
200
200
17
2.3.7 - FILTER
UNICAL suggests the installation of a Y
filter with two gate valves on the return
pipe so that it can be cleaned if necessary. Such filter shall protect the boiler
2.3.8 - BALL V ALVES
Unical suggests the installation of ball
gate valves on the system flow/return
pipes. In this case the boiler, if necessary, can be disconnected or drained,
without having to drain the whole sys-
2.3.9 - FEEDING W ATER QUALITY
-The system and reinstatement
water chemical-physical features
are fundamental for the boiler correct operation and safety.
-Among the inconveniences caused by feeding water low qualities the most frequent and serious
one is the scale deposit on heat
exchange surfaces.
-Less frequent but not less serious
is the water side corrosion of all
heating circuits surfaces.
-It is known that calcareous scales
reduce heat exchange due to their low heat conductivity, so that
even few mm-thick scales may
cause very dangerous localised
overheating.
from the heating system dirt. Its regular
cleaning has to be foreseen.
tem. A closed expansion vessel, properly dimensioned and equipped with its
safety valve, shall be fitted between the
gate valves and the boiler.
-Water treatment is advisable in the
following cases:
A)high hardness of the available
water (> 20°f)
B)very large heating systems
C)high quantities of reinstatement
water due to leakages or maintenance works
-The use of an inhibitor is advisable to treat feeding waters and to
protect heating systems against
calcareous scales, corrosion and
microbiologic growth. In case of
freezing as well, the use of an antifrost together with the inhibitor is
advisable.
-Qualified companies can provide
boiler de-scaling.
WARNING!
Never intercept safety devices, such
as safety valve and expansion vessel.
-Any system needs water re-filling
because of evaporation, small or
substantial leakages and maintenance. It is then necessary to calculate the water quantity requested to avoid new inconveniences
due to untreated water.
To this purpose, the installation of
a water flow-meter is advisable on
reinstatement pipe.
2.3.10- BOILER ANTIFROST
PROTECTION
Should the flow temperature (measured
at global flow temperature NTC) decrease under 7°C, the system pump is
set up. Should temperature ulteriorly
18
decrease (under 3°C), all modules shall
start at min. output until the return temperature reaches 10°C. Such protection
device is exclusively for the boiler. For
the protection of the whole system, a second anti-frost thermostat is necessary to
switch on the heating system pump.
2.3.11 - MINIMUM W ATER FLOW RA TE
A minimum water flow rate, as shown in
the table on the right, is to be guaranteed
through the boiler at any time.
RICIRCULATION PUMP
The recirculation pump shall have a
manometric head able to assure the
water flow rate as per the diagram of fig.
8.
Pumps shall be calculated by installers or technical engineers according
to boiler and system parameters.
8
7,5
7
6,5
6
2
5,5
(mH O)
5
4,5
4
3,5
3
PRESSURE LOSSES
2,5
2
1,5
1
0,5
0
02,5 57,5 10
12,5
kW output
The water side resistance curve of the
boiler is shown in fig. 8.
The pump is not an integral part of the
boiler.
WATE R SIDE
PRESSURE LOSSES
15 17,5
20
22,5 25 27,5 30 32,5
WATER FLOW m³/h
360 450 540 630
30,96 38,70 46,44 54,18
20,64 25,80 30,96
15,48 19,35 23,22
36,12
27,09
It's recommended to choose a circulator with the rate and discharge head
around 2/3 of its charactestic curve.
630
450540
360
35
37,5 40
45 47,5 50 52,5 55
42,5
fig. 8
2.4 - BOILER OPERATION
The boiler consists of mutually connected combustion chambers; each of them
has its own burner, fan with air pressure switch for control, two gas valves
with ignition and ionisation device.
Each group of these components is
called thermal element.
Max. output of a thermal element is 90 kW .
So, a 630 kW boiler consists of 7 thermal
elements.
Each thermal element has its own temperature sensor NTC - Negative T emperature Coefficient - called local NTC,
which locally checks the flow tempera-
ture of each thermal element.
The flow temperature at the boiler outlet
and the return temperature at the boiler
inlet are controlled by global NTC temperature sensors (see fig. 2).
In case of more heat request by heating
or DHW systems, the boiler starts up and
water will be heated by an aluminium boiler body . Then the boiler pump sends water to the mixing bottle and from here to
the radiators, according to the heating
system choosen.
The combustion air is supplied by fans
and taken in from the boiler room. The
combustion air is then pushed into the
pre-combustion chamber through a diaphragm. Beyond the diaphragm, the air
mixes with gas and such mixture passing through the non-return valve is sent
to the burner. Then, on leaving the burner
surface, the air/gas mixture ignites electrically and the resulting combustion gases, after being transported (and cooled)
through finned tubes, enter the condensate collecting manifold and then are
evacuated through the chimne y .
19
2.4.1 - GENERAL DESCRIPTION
When there is an heat request from a
room thermostat or an outer compensator, the Modular Boiler Drive (MBD) calculates the necessary output according
to the difference between the set temperature (or the temperature calculated by
the outer compensator) and the global
flow temperature. The number of thermal
elements (each thermal element represents a maximum output of 90 kW) x
100% determines the maximum output
expressed in %.
When the output has been determined, the
boiler pump (not supplied by Unical) is set
up and the fan of one thermal element is
set in motion at starting speed. The gas
valve opens and ignition is to occur within 5 sec. When the ionisation electrode
detects the flame, the thermal element
starts operating.
Subsequently other thermal elements are
likely to start in the same way . One of the
operation principles for this boiler is letting as many burners as possible operate simultaneously at minimum load to
reach the maximum efficiency .
For example, if a 4 thermal element boiler
is requested to operate at its max output,
this shall be 400% i.e. :
90 kW x 4 thermal elements =
360 kW = 400%.
If it is requested to operate at 200% output, thanks to the output sharing system
on the highest number of thermal elements, each thermal element will operate
at 50% output i.e. :
200% : 4 thermal elements = 50%
equal to a total of 180 kW , that is 45 kW
for each thermal element.
Such principle provides clearly efficiencies much higher than those obtained in
traditional groups of small boilers installed
in cascade.
When the output shared on each thermal
element is less than 22 kW , one thermal
element after the other is automatically
excluded and the remaining output is
shared on thermal elements having the
smallest number of operation hours (by
the automatic operation-time calculating
system).
Modulation, i.e. output reduction, is based
on the difference between the set temperature (or the temperature calculated by
the outer compensator) and the global
flow temperature.
When no ignition occurs, the ignition device puts to lock out position the thermal
element concerned.
1 Thermal element = 90 kW = 100%
4 Thermal elem. = 90 kW x 4 = 360 kW = 400%
4 thermal elements of 90 kW each working
kW
at 50% of the output give = 180 kW = (200%),
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
mod 1
5
0
i.e. 45 kW / thermal element
400% : 360kW = 200% : X
X = (200x360) : 400 = 180 kW
Output shared on 4 thermal elements : total output
output shared on 4 thermal elements
= 180:360 = 0,5 = 50%
% (p.c.i.)
109
107
1 thermal
element
50 % = 45 kW
105
1 thermal
element
100 % = 90 kW
20
22
Efficiency of a thermal element working at full capacity
(90 kW) = 103 % (in condensation)
Efficiency of a thermal element working at reduced capacity
(45 kW) = 107 % (in condesation)
Efficiency of a thermal element working at minimum capacity
(22 kW) = 109 % (in condesation)
All the thermal elements work in parallel at the same output, equalizing,
thus, the C.H. system efficiency to the one of the thermal element.
408060
45
90
P
(kW)
20
Ignition diagram, for Modulex 630, with 7 burners. (6 are working, 1 is during ignition procedure).
2.4.2 IGNITION SEQUENCE
5 seconds after the switch ON-OFF is
IGNITION SEQUENCE DIAGRAM
ON, the pump is set up together, eventually, with the 3-way valve in the case
of a heat request from the Room Thermostat. The ignition PCB (“CVI” means
Combined Valve and Ignition) is powered on and, after 24 sec, the fan is set in
motion and reaches the starting speed;
it stays in operation making the prepurge of the combustion chamber for
10 sec; in the meanwhile the air pressure switch, actuated by the fan, switches from C-NO (open position) to C-NC
(closed position) allowing the ignition
spark to be obtained and the gas valve
to be opened after 5 to 8 sec allowing
the AIR/GAS mixture. If within the safety
time there is no burner lighting the burner is put definitely in lockout position (the
relevant red push button, on the front panel board, will light).
When heating and/or DHW request ceases, the pump stays in overrun according
to relevant pre-set times. Such sequence
is the same for the other burners without,
quence in their assembling order, but in
their operation hours.
necessarily, keeping the lighting se-
Fig. 9
Fig. 9
21
2.4.3 - SUPPLEMENT AR Y BOARD
The Modular Boiler Drive (MBD) in fig.
9, supplied for each boiler by Unical,
manages to check a two-burner group
(2 x 90 = 180 kW). For boilers with output
> 360 kW, 2 or 3 supplementary boards
AM-5 are assembled by the manufacturer, each of them managing to check
up to 2 burners. For example, a boiler
with 5 burners (450 kW) is equipped with
two supplementary boards AM-5.
The supplementary boards have two
small dip-switches, which shall be positioned according to the patterns here
below, regardless the number of supplementary boards AM-5 fitted (such
operation is carried out at the manufacturer’s workshop and will also be done
on site in case of the replacement of a
faulty one).
X1 = CVI supply (ignition PCB)
X2 = CVI supply (ignition PCB)
X3 = 230 V electrical supply from mains
X7 = to MDB by flat cable
AM-5
X3
X1
X2
DIPSWITCH 2
X7
DIPSWITCH 1
Fig 10
Fig. 11-
SUPPLEMENTARY BOARD.
POSITIONING OF THE DIPSWITCHES
O
AM-4
AM-4
F
F
2
1
Thermal element
AM-5
N.1
O
F
F
2
1
Thermal element
AM-5
N.1
O
F
F
2
1
AM-5 and AM-4 boards
positioning
for a MODULEX 360.
Thermal element
AM-5
O
F
F
AM-5 and AM-4 boards
positioning
2
1
N.2
O
F
F
for a MODULEX or 0.45054
O
F
F
AM-5 and AM-4 boards
2
2
1
1
positioning
for a MODULEX 630
22
AM-4
Thermal element
AM-5
N.1
Thermal element
AM-5
N.2N.3
Thermal element
AM-5
2.4.4 - DOMESTIC HOT W A TER (DHW)
MODE OPERA TION
Each boiler is equipped with an AM-4
board, necessary to control a D.H.W
tank and to receive a 0 - 10V signal from
an outer compensator (se fig. 11). If there
is a heat request, the MBD can control
either a storage tank loading pump or a
3-way diverting valve. So the boiler will
ignite and operate according to what
previously described. The global flow
water temperature, set as standard 20
K higher than the requested DHW temperature, is modulated as well. By using dip-switches, it is possible to limit
the boiler output when working in D.H.W
mode, in order to avoid overheat when
the DHW storage tank absorbed output
is less than the boiler produced one.
DHW production has always priority on
heating. Some examples about hydraulic and electric connections of a hot
water storage tank are shown in the figures 6.1 - 6.2 - 6.4 .
For example:
If we combine a 90 kW storage tank to a
Modulex 360, setting the dip-switch 1 to
“OFF “ and the dip-switch 2 to “OFF”, so
as to adjust the functioning of the number of modules on the basis of the storage tank's requests (one module will function).
If we combine a 180 kW storage tank to
a Modulex 360, setting the dip-switch 1
to “OFF “ and the dip-switch 2 to “ON”,
two modules will function.
If we combine a 270 kW storage tank to
a Modulex 360, setting the dip-switch 1
to “ON “ and the dip-switch 2 to “OFF”,
three modules will function.
If we combine a 360 kW storage tank to
a Modulex 360, setting the dip-switch 1
to “ON “ and the dip-switch 2 to “ON”, four
modules will function.
X1= diverting valve or storage tank
loading pump
X2= outer compensator / D.H.W. tank
NTC
X7= to the MBD by flat cable
AM-4
X1
DIPSWITCH 2
Flue
Temp.
DHW
Tank
NTC
0-10 V
X2
X7
DIPSWITCH 1
Fig 11
IN THE MODULEX BOILERS WITH AN
OUTPUT HIGHER THAN 360 KW
DIPSWITCH CURSOR POSITION
REGULATION
CONFIGURATION
360 kW
O
F
F
2
1
Four modules are
ignited (360 kW )
270 kW180 kW
O
F
F
2
1
Three modules are
ignited (270 kW )
Two modules are
ignited (180 kW )
In order to guarantee the best D.H.W.
production the dip-switches present
configuration allows a maximum availability up to 360 kW .
90 kW
O
F
F
21
Just one module is
O
F
F
2
1
ignited (90 kW )
2.5 - OPERATION IN CASE
OF TECHNICAL INTERVENTION
For after sale service and test reasons,
any single thermal element or all simultaneously can be kept operating at full
or reduced load. In this way the CO
2
lev-
el can be checked and, if necessary , adjusted at full or reduced load (for any single thermal element or for all simultaneously).
Thanks to this option the search for failures on each thermal element will result easier.
23
2.6 - ELECTRIC
CONNECTIONS
The MODULEX electrical connections
are defined in the chapter “Wiring diagram” (paragraph 2.6.1).
For electrical features see appliance data
plate.
The boiler installation needs a supply
of 230 V – 50 Hz – single phase, and
must be workmanlike performed, as foreseen by the local and international electrical rules in force and without the utilisation of adapters, multiple sockets or
extension cords. It is fundamental to
check this safety requirement. If in any
doubt, ask for an accurate control of your
electric system by highly qualified personnel.
UNICAL is not liable for any damage
caused by unproper earthing system.
The gas and water feeding pipes and
the C.H. system pipes cannot be used
as earthing means.
Boiler electric safety is guaranteed only
when it is properly connected to an efficacious earthing system in compliance
with the regulations in force.
The use of any power supplied equip-
ment implies the observance of some fundamental rules, such as:
- do not touch the boiler with any wet
part of your body and/or barefooted;
- do not pull the supply cable;
- do not expose the boiler to sunlight,
rain, etc…;
- keep the boiler away from untrained
people.
The boiler supplying cable shall not be
replaced by the user. In case of any
damage to the cable, stop the boiler
and contact qualified personnel for its
replacement.
For the technical characteristics see the
boiler data plate.
The boiler electrical supply (230 V – 50
Hz – single phase) is to be done directly on the three pole plug A (fig. 12) supplied with the boiler. This boiler is phase
sensitive, it means that Phase and Neu-tral wires from mains have to be connected to Phase and Neutral terminals
of the three pole plug, otherwise the
boiler will go in lockout position.
It is necessary to fit a double pole switch
on the supply line in an easy accessi-
ble position in order to make quick and
safe the service operations.
WARNING!
230 V cables shall be separated from
24 V ones, using the two plastic conduits supplied within the boiler casing
L.H. side panel.
A
Fig. 12
TABLE OF RESISTANCE OF
NTC1 - NTC2 - NTC3
Relationship between temperature (°C) and
nominal resistance (Ohm) of the sensors
NTC1 - NTC2 - NTC3
2.6.2 - WIRING CONNECTIONS OF THE IGNITION ELECTRONIC CARD
Connections detail
to the ignition electronic card
for each modul.
E. ACC.Ignition electrode
E. RIV Ionisation electrode
PRRest button (on main
board)
LBLockout warning light
(on main board)
TLHigh limit thermostat
(local)
PVFan air pressure
switch
Fig. 15
2.6.3 - ELECTRICAL CONNECTION
TO AN OUTER COMPENSATOR, A ROOM THERMOSTAT
OR AN OUTER TEMPERATURE SENSOR
Outer compensator: connect the com-
pensator 0-10V outlet signal to terminals 9 - 10 of the 20-pole terminal-strip
(see fig. 16). By using this signal it is possible to set a global flow temperature depending on the outdoor temperature.
ON/OFF room thermostat or programmer: it shall be connected to the termi-
nals 5-6 of the 20-pole terminal-strip (see
Note. The terminals 11 – 13 and 16 – 18 must be used to control a 3-way valve or a DHW tank loading pump or a boiler pump through
relays, as shown in the hydraulic schemas of fig. 6.1 to fig. 6.6. NEVER supply directly from these terminals the a.m. devices .
ADDITIONAL
SECURITY
(LOW
OUTSIDE
SENSOR
WATER
PRESSURE)
fig. 16).
Outdoor sensor: supplied as standard,
it must be fitted on an outer wall exposed
to North or North-East, at a minimum
height from floor of 2.5 m. The mounting
in proximity of opening windows and
doors and ventilation grates has to be
avoided. Never fit the outdoor sensor in a
sunny position. It shall be connected to
terminals 3 - 4 of the 20-pole terminal-strip
(see fig. 16).
T o avoid electromagnetic disturbances it is necessary to separate the
external sensor wiring (between
sensor and terminal strip) from the
230 or 400 V harness (a plastic conduit
STORAGE TANK
SENSOR OR
THERMOSTA T
PRIMARY SYSTEM
ON-OFF
PUMP
for 230 or 400 V harness and one for 24
V wiring)
Depending on the outdoor temperature
detected by the sensor the boiler will modulate and adjust the flow temperature according to the programmed heating curve
(see fig. 19).
ON/OFF room thermostat in combination with outdoor sensor: When both
devices are connected as shown here
below, the boiler will modulate and adjust the flow temperature according to
the room and outdoor temperature detected by the two sensors (see fig. 19).
DHW PUMP OR
3-W AY V A LVE
The intervention of the
additional security
provokes the block of the
boiler and error code
is displayed.
26
ROOM THERMOSTAT
AND/OR ON/OFF
TIMER
E26
BMS
CONNECTION
230 V24 V
ALARM SIGNAL
(VOLT FREE CONTACT)
MAIN SUPPLY
FROM THE
FILTER
Fig. 16
2.6.4 - DHW STORA GE T ANK
DHW production by an outer storage
tank connected to the boiler can be carried out by an electric diverting valve or
a separated storage tank loading pump
Both devices can be chosen via the control panel push buttons, by selecting the
right parameter A (see paragraph
3.2.8.2, parameter A - 2
nd
digit).
The DHW tank NTC sensor, supplied
as an option, will be connected to the
terminals 7 – 8 of the 20-pole terminalstrip.
ELECTRICAL CONNECTION OF THE THREE WAY VALVE
16
17
18
LN
3-WA Y V AL VE CONNECTION
satisfied
DHW tank
3-contact relay
na
c
nc
Boiler AB
M
B
DHW tank
Line
V.D. Engine
Power
Neutral
A Heating system
WARNING!
There is a 230 V tension between terminals 16 - 18 only when there is a heat
demand by the DHW NTC sensor or by a DHW thermostat; in this case the display
4 XX
will show :
(see 3.2.5).
16
17
18
LN
3-contact re l ay
3-WAY VAL VE CONNECTIO N
not satisfied
DHW tank
na
c
nc
M
B
DHW tank
A Heat ing syste m
Boiler AB
Line
Neutral
V.D. Engine
Power
ELECTRICAL CONNECTION OF A DHW TANK
LOADING PUMP
16
17
18
LN
DHW tank loading pu mp
Tank satisfied
DHW
16
17
18
LN
DHW tank loading pump
DHW
Tank not satisfied
3-contact relay
na
nc
DHW tank
c
Line
Neutral
Pump Engine
Power
3-contact relay
na
nc
DHW tank
c
Line
Neutral
Pump Engine
Power
WARNING!
There is a 230 V tension between terminals 16 - 18 only when there is a heat
demand by the DHW NTC sensor or by a DHW thermostat; in this case the display
will show :
4 XX
(see 3.2.5).
ELECTRICAL CONNECTION OF A BOILER PUMP (OR A DHW LOADING
PUMP IF WITH A 3-WA Y VALVE) Boiler pump or DHW loading pump
11
12
13
LN
CH loading pump/
DHW tank loading pump
3-contact re lay
na
c
nc
Line
Neutral
DHW tank
Pump Engine
Power
11
12
13
LN
CH loading p ump/
DHW tank loading pu mp
3-contact relay
na
c
nc
Line
Neutral
DHW tank
Pump Engine
Power
WARNING!
There is a 230 V tension between terminals 11 - 13 only when there is a heat
demand by the DHW NTC sensor or by a DHW thermostat; in this case the display
4 XX
will show :
(see 3.2.5).
Fig. 17
27
3
OPERATION OF THE MAIN PCB, NAMED MBD
(MODULAR BOILER DRIVE)
3.1 - GENERAL
DESCRIPTION
The Standby mode is on 5 sec. after
starting or resetting the boiler. Subsequently the pump is set up for 1 min. If
no heat is requested, this procedure is
Reset buttons for the
Pressure
gauge
1
different thermal element
576
243
P
E
T
S
Step
+ -
performed every 24h (automatic anti-jamming system for boiler pump or re-circulation pump). If a DHW production boiler
does not use a 3-way valve but rather a
On/Off switch
Lockout warning light
T
E
E
D
S
O
E
R
ResetDisplay
T
S
Store
E
R
O
M
Mode
storage tank loading pump, such a pump
is set up for 1 min every 24h if no heat is
requested. In this way the pump will not
jam.
®
Fig. 18
Operation and indications on the display (example with 7 thermal elements)
3.2 - OPERATION AND
DISPLAY
INSTRUCTIONS
The control panel has 5 function keys,
STEP - +/- -STORE - MODE - RESET,
one display, one ON/OFF main switch,
2 to 7 reset buttons with lockout warning light and one pressure gauge. All
different operation modes are displayed by slightly pressing the
mode
key.
If no other keys are pressed within 15
minutes from the last pressing, except
when the
board will go into
playing
Standby
TEST
mode is used, the panel
standby
mode dis-
the global flow temperature.
mode gives information as
shown in par. 3.2.6 concerning the
MODULEX instantaneous operation
phase.
28
3.2.1 -
“MODE”
KEY
The default set mode of the boiler is
stand-by
mode. By this mode, the 4digit (letters or figures) display shows
the flow temperature or the operation
state (from 0 to 9 – see par. 3.2.7).
The indication on the display will be:
, where the 1st digit indicates the
number of step (operation state - see
par. 3.2.7) while the 3
rd
and 4th ones the
flow temperature value.
By slightly pressing the
(abbreviation for
mode
parameter
key,
), which is
one of the 6 operation modes (main
menu), is displayed.
By slightly pressing the
mode
key again,
the 4-digit display will show .
3.2.2 -
''STEP''
KEY
Once one mode, among the four modes
mentioned above (i.e. para – data – test
– hour), has been selected by pressing
mode
key, it is possible to choose, by
pressing
step
key, the parameter and
After entering the access code, strictly
reserved to the installer and the service
technicians, it is possible to go into the
extended programming menu and into
the following modes:
and
By slightly pressing the
mode
key again,
the 4-digit display will show .
In this mode it is possible, only by the
installer or service technician, to make
the fine adjustment of the combustion
for the complete boiler or for each single thermal element at high or low output (see par. 3.2.10), acting on the CO
level.
the thermal element (or the whole boiler)
whose values have to be changed or to
be checked.
By slightly pressing the
mode
the 4-digit display will show .
In this mode it is possible to check, only
by the installer or service technician,the
operation time for each b urner. It is also
possible to calculate the total operation
time of the boiler.
2
key again,
3.2.3 - "
+ / -" KEY
Once the values requested have been
entered, it is necessary to store them in
order to make them operative. To this
purpose, press
store
.
3.2.4 - "STORE" KEY
Once the values requested have been
entered, it is necessary to store them in
order to make them operative. To this
purpose, press store.
3.2.5 - SERVICE CODE
The access to some programming parameters is reserved only to service
technicians and, if necessary, to the installer. This access is protected by a
secret service code.
To enter this code proceed in the fol-
In the par. 3.2.6 is shown the procedure
how to get into the extended programming menu.
lowing way:
Keep
mode
and
step
keys pressed simultaneously: C.XX (a random code) is
displayed.
By using the ''+/-'' key, replace this code
with the secret one and, always keep-
ing
mode
and
step
keys pressed, press
store
. When the right code has flashed
once, it has been stored.
After entering the service code, the display reverts to
stand-by
mode.
29
3.2.6 - PROGRAMMING ACCESS PROCEDURE
it selects:
- pa r a me t e r s
- data (all/single)
- test (all/single)
x
xx
mode
By pressing
mode
By pressing
mode
By pressing
P
E
T
S
+/- :
it increases
or decreases
the displayed
value
= Stand-by mode Display
By pressing see par 3.2.8
The User has
access to these
three parameters
only (see 3.2.8.1)paragraph
The User has not access
to these parameters.
Only the installer or
service technician can
get access by previously
entering the service code
(see 3.2.8.2)paragraph
By pressing
By pressing
(see paragraph 3.2.9.1)
Single burner (1 to 7) DATA
are not programmable by the
user. Only the Installer can
enter DATA by a service
code (see 3.2.9.2).paragraph
step
By pressing Step,
without any service code.
step
step
All about the burner 1 is applicable to all
other burners (2 to 7).
The parameter number is not displayed.
*
(see the following page)
It displays when
in DATA mode.
It stores when
in PARA mode.
It shows the number of step (from 0 to 9 – see 3.2.7)
It shows the number of the parameter displayed (from 1 to 9 and from A to N)
E
R
O
T
S
They show the regulation value of the displayed parameter.
1
.
0
6
By pressing step
20
.
38
.
4x
9
.
a
nx
.
As above
1
By pressing step
As above
0
By pressing
As above
x.
By pressing
As above
xx.
By pressing step
As above
x
x
By pressing step
As above
x
E
D
O
M
it
chooses
the mode
step
step
By pressing
E
R
Reset
the boiler
paragraph
15
.
0
NOTE: Once the mode has been
selected by the key, the installer can
enter the different parameters by pressing
step
the key. After some minutes
from last pressing one of the 5 keys,
the boiler shall switch to mode .
If, on the contrary, the installer wishes to switch
to the following mode, , press the
mode
.
store
mode
key once again.
.
By pressing
step
.
By pressing
step
As above
.
By pressing
step
As above
.
By pressing
step
*
*
.
.
x
x
x
x
xx
By pressing
store
xx
By pressing
store
xx
By pressing
store
xx
By pressing
store
T
E
S
150.
.
.
.
.
.
.
x
.
xxx
xx
By pressing
store
x
x
By pressing
store
x
x
By pressing
store
x
x
By pressing
store
xx
By pressing
store
xx
By pressing
store
xx
By pressing
store
xx
By pressing
store
stand-by
*
x
30
3.2.6 - Continuous
it selects:
- parameters
- data (all/single)
- test (all/single)
mode
By pressing
mode
By pressing
P
E
T
S
+/- :
it increases
or decreases
the displayed
value
By pressing
see par
step
. 3.2.10
By pressing
step
.
By pressing
step
.
By pressing
step
By pressing se e par. 3.2.12
The User has not access
to these parameters.
Only the installer or
service technician can
get access by previously
entering the service code
(see paragraph 3.2.8.2)
step
E
R
O
T
S
It displays when
in DATA mode.
It stores w h en
in PARA mode.
ALL OFF
and
are flashing
alternately.
+
and
bur.1 OFF
are flashing
alternately.
+
and
bur.7 OFF
are flashing
alternately.
+
By pressing
By pressing
step
step
E
D
O
M
it
chooses
the mode
By pressing
By pressing
By pressing
By pressing
By pressing
By pressing
bur.1 XXXX
and
are flashing alternately
.
+
bur.2 XXXX
and
are flashing alternately
.
bur.7 XXXX
and
are flashing alternately
.
+
-
+
-
+
-
+
+
E
S
E
R
Reset
the boiler
paragraph
see 3.2.10
xXXX
paragraph
see 3.2.10
xXXX
see 3.2.10
xXXX
paragraph
T
By pressing
Display in modeStand-by
xx
x
After the 1st burner has been adjusted, push step in order to control the next burner and switch it on.
Before the new burner adjusting it’s necessary to switch-off the pre vious one. Do it by pushing as much time as necessary the button step up to
visualize the burner already adjusted: set it OFF.
Only now it will be possible to do the smoke combustion analysis of the ne w burner .
From 1°C more than parameter 4 value, up to 60°C
=
step
31
3.2.7 -
STAND-BY
The first digit indicates the number of
the step in which the boiler is; e.g. 0. In
this case the last two digits will indicate
StepDescription
No.
0 =standby: no heat request
1 =the fan of the thermal element shown on the display reaches the starting speed
2 =the safety time of the thermal elements shown on the disaplay elapsed without any problem
3 =the boiler is running to supply the heat requested by the heating system
4 =the boiler is running to fulfil the DHW production request
5 =the thermal element shown on the display is in pre-purging
6 =the burner is stopped on request of a control device
7 =the post-circulation after a C.H. system heat request is active
8 =the post-circulation after a DHW storage tank heat request is active
9 =complete switch Off, usually with an “E” error number or with burner off during the DHW preparation
List of the steps and the relevant functions the boiler is carrying out.
MODE
X
X
the water flow temperature. Should the
first digit be 4, the last two digits would
indicate the loading temperature of the
heat exchanger of DHW tank.
For the steps 1 - 2 and 5 the thermal
element starting steps are displayed instead of the flow temperature.
The following table is a list of all the
different program steps with the relevant
description on the right.
3.2.8 -
PARA
MODE
When in
and is displayed.
3.2.8.1 - OPERA TION PARAMETERS PROGRAMMABLE BY INST ALLER AND USER
Para-DescriptionPossible AdjustmentFactory Adjustment
metersadjustemnt range
1Requested DHW Temperature in the
2C.H. and D.H.W. production
stand-by
storage tank40-65 °C6 0 40-65 °C
ON or OFF options00 = DHW production and Heating0100,01,02,11,12
, press the
mode
key
are both OFF
01 = DHW production is OFF and
Heating is ON (boiler pump stops:
only makes post-circulation according
parameter 9)
02 = DHW production is OFF and
Heating is ON (boiler pump is
always running)
11 = DHW production and Heating
are both ON (boiler pump stops;
only makes post-circulation according
parameter 9)
12 = DHW production and Heating
are both ON (boiler pump is
always running)
3Global Flow Temperature Regulation30-90 °C 80 30-90°C
32
3.2.8.2 - OPERA TION PARAMETERS PROGRAMMABLE ONLY BY INSTALLER AFTER ENTERING THE SER VICE CODE
(Available at UNICAL Service)
Para-DescriptionAdjustment
metersrange
4Min. global flow temperature adjustment, for outer thempetrature of 20°
when using the heating curve (see fig. 19)15 to 60°C
5Min. outer temperature used in the calculation of the C,H. system, when
using the heating curve (see fig. 19)-20 to 10°C
6Heating stop temperature when the value calculated by the outer NTC
sensor is lower than the pre-set temperatureDa 1 K > t° di regolazione
del parametro 4 fino a 60°
7This parameter for night shift of flow temperature (see fig. 19)
81
is use only when programmer is fitted.
When the1
st
digit: adjustment of the outer temperature read by the outer sensor–5 to 5 K
nd
2
digit: C.H. hysteresis, i. e. the temperature difference against the
st
digit of the parameter A (see below) is 1 the reduction is active.0 to 40 K
set temperature to which the boiler should restart. By the way it is convenient
to consider that the switching off temperature is always 5K above the set point 0 to 9 K
9Post-circulation time of boiler pump in C.H. mode3 to 99 min
ATwo digit parameter:
is used to make the configuration of Heating system and DHW production
If heating system is controlled by:
- ON/OFF room thermostat or programmer1
- outer sensor (based on parameter 6 - see paragraph 3.3.2); if the
programmer is fitted the night shift of flow temperature is active1
- outer compensator with 0 - 10 V outlet, where 0 V corresponds to the
minimum flow temperature and 10 V to the maximum temperature1
st
digit = 0x (*)
st
digit = 1x (*)
st
digit = 2x (*)
If D.H.W . production is contr olled by:
- Storage tank loading pump, (downstream the mixing bottle) or
3 way valve normally open towards C.H. system (upstream the mixing bottle)2
- Storage tank loading pump (upstream the mixing bottle)2
- Reversed 3 way valve (normally open towards DHW tank)2
nd
digit = x0
nd
digit = x1 (solution not used)
nd
digit = x2
BDifferential temperature rise which increases the boiler flow temperature
during the DHW request (increase of parameter 1) in order to fulfil the
request regardless the heating set temperature (parameter 3)5 to 25 K
CMaximum fan speed in C.H. mode operation (x 100)
DMaximum fan speed in DHW mode operation (x 100)
EMinimum fan speed (x 100)
(factory set 58)
(factory set 58)
(factory set 22)
10 to 60 rpm
10 to 60 rpm
10 to 60 rpm
FStarting speed, in percentage of the maximum speed, shown on the10 to 100%
parameter C (increasable when flue discharge is difficult)
(factory set 75)Do not regulate under 50%
GFlow temperature adjustment to 0 V when using an outer compensator0 to 50 °C
HFlow temperature adjustment to 10 V when using an outer compensator50 to 90 °C
JCombined Parameter : (two digits)
Alarm:- the alarm switch is closed when the 1 to 7 modules are in
lockout position (see note 1).1
st
digit = 1x to 7x (see note 1)
Pump post-circulation time or 3-way valve commutation delay
after D.H.W. has reached the set point temperature
- adjustable by 30 sec steps up to (9 x 30 sec = ) 270 sec2
nd
digit = x0 to x9 (x 30 sec.)
LHysteresis (difference between the switching ON and switching OFF boiler
temperatures during the DHW production) (see Note 2)5 to 14 K
NType of burner control and number of thermal elements
2
(*) Should the outer sensor (terminals 3-4) and the ON-OFF room thermostat or a timer (terminals 5-6) be connected, on opening the thermostat or the
timer (terminals 5-6) with parameter A in 0x, the boiler will be switched off; on the contrary with parameter A in 1x the boiler will switch to night shift
mode. If a link connects the terminal 5 to the terminal 6, the boiler will not switch to night shift mode.
NOTE 1: By entering a figure from 1 to 7 it is possible to determine the number of faulty burner from which a lockout warning signal (alarm) is desired.
NOTE 2: Should the DHW recirculation be used, the parameter L reduces the number of ignitions if the hysteresis value is high.
st
digit of the parameter3x = Unical standard regulation
1
nd
digit of the parameterx1-x7 = No. of boiler burners
33
3.2.9 -
DATA
MODE
Data
mode gathers a set of data about
the operation state of the boiler and of
each thermal element. By using the
step
key it is possible to scroll all v alues. The
table here below shows the data con-
tents concerning the whole boiler. When
entering the service code, all other data
(from 1 to 7 burners) are also programmable.
3.2.9.1 - OPERA TION PARAMETERS ACCESSIBLE TO INST ALLER AND USER
DataData ref.SignificationUnit
series
Data1Global flow temperature°C
relevant2Global return temperature°C
to the whole 3DHW temperature°C
boiler4Outer temperature°C
5Smoke temperature (not implemented)° C
6Flow temperature adjustment°C
7 *Fan speed adjustmentrpm xxxx
8Output calculated in % (on the complete boiler)% xxxx
3.2.9.2 - PARAMETERS ACCESSIBLE ONLY TO THE INSTALLER BY PREVIOUSLY ENTERING THE SERVICE CODE
DataData ref.SignificationUnit
series
Data1Local flow temperature, NTC1°C
relevant2Local flow temperature, NTC2° C
to bur.13*Thermal element 1 fan speed adjustment 1rpm xxxx
4*Thermal element 1 actual fan speed 1rpm xxxx
Data1Local flow temperature, NTC2°C
relevant2Local flow temperature, NTC3° C
to bur.23*Thermal element 1 fan speed adjustment 2rpm xxxx
4*Thermal element 1 actual fan speed 2rpm xxxx
Data1Local flow temperature, NTC3°C
relevant2Local flow temperature, NTC4° C
to bur.33*Thermal element 1 fan speed adjustment 3giri/min xxxx
4*Thermal element 1 actual fan speed 3giri/min xxxx
Data1Local flow temperature, NTC4°C
relevant2Local flow temperature, NTC5° C
to bur.43*Thermal element 1 fan speed adjustment 4rpm xxxx
4*Thermal element 1 actual fan speed 4rpm xxxx
Data1Local flow temperature, NTC5°C
relevant2Local flow temperature, NTC6° C
to bur.53*Thermal element 1 fan speed adjustment 5rpm xxxx
4*Thermal element 1 actual fan speed 5rpm xxxx
Data1Local flow temperature, NTC6°C
relevant2Local flow temperature, NTC7° C
to bur.63*Thermal element 1 fan speed adjustment 6rpm xxxx
4*Thermal element 1 actual fan speed 6rpm xxxx
Data1Local flow temperature, NTC7°C
relevant2Local flow temperature, NTC8° C
to bur.73*Thermal element 1 fan speed adjustment 7rpm xxxx
4*Thermal element 1 actual fan speed 7rpm xxxx
* Note: The parameter figure is not displayed
34
3.2.10 -
Test
TEST
MODE
mode can be used for service purposes, so that each single burner can
operate individually.
This mode is be used even when adjusting CO
% for each single burner
2
(see par. 3.5).
StepOptionSignification
ALL= OFFAll thermal elements are OFF
= HHHAll thermal elements start at high output
= LLLAll thermal elements start at low output
bur. 1= OFFThermal element 1 is OFF
= HIThermal element 1 starts at high output
= LOThermal element 1 starts at low output
bur. 2= OFFThermal element 2 is OFF
= HIThermal element 2 starts at high output
= LOThermal element 2 starts at low output
bur. 3= OFFThermal element 3 is OFF
= HIThermal element 3 starts at high output
= LOThermal element 3 starts at low output
bur. 4= OFFThermal element 4 is OFF
= HIThermal element 4 starts at high output
= LOThermal element 4 starts at low output
bur. 5= OFFThermal element 5 is OFF
= HIThermal element 5 starts at high output
= LOThermal element 5 starts at low output
bur. 6= OFFThermal element 6 is OFF
= HIThermal element 6 starts at high output
= LOThermal element 6 starts at low output
bur. 7= OFFThermal element 7 is OFF
= HIThermal element 7 starts at high output
= LOThermal element 7 starts at low output
Test
mode is accessible only after
entering the service code.
The following table is a general list of
all
test
modes.
The burner No. and its operation state
(OFF, HI and LO) alternatively flash on
the screen.
By choosing the status OFF, HI or LO by
the
+/-
key and pressing successively
store
, it is possible to store the choice
and make it operative.
3.2.11 -
HOUR
MODE
This mode, which is accessible only after entering the service code, shows the
operation time for each thermal element.
Select by the
step
key the burner whose
operation time is wanted to be known.
The burner No., as well as the number
of operation hours, alternatively flash
on the display.
DisplayOperation time rangeMultiplication coefficient
x.xxxFrom 0.000 to 9.999 hours Multiply the figures before comma
by 1000 and the figures after
comma by 1
xx.xxFrom 10.00 to 99.99 hours Multiply the figures before comma
by 1000 and the figures after
comma by 10
xxx.xFrom 100.0 to 999.9 hours Multiply the figures before
comma by 1000 and the figures
after comma by 100
Eg.
The figure 33.45 means the thermal element operation time is (33x1000 = 33,000) +
(45x10 = 450) = 33,450 h, equal to about 4-year continuous operation.
35
3.3 - HEATING MODE
OPERATION
The boiler can fulfil different requests
for more heat by parameter A.
When leaving the workshop, the boiler
has its parameter A set to 01 by default.
Its verification is however advisable at
boiler commissioning.
3.3.1 - HEATING MODE OPERATION
BY ROOM THERMOSTAT
By giving the 1
st
figure of the parameter
A the value 0 (e.g. A-0x) it means that
the request for more heat is driven by a
room thermostat.
A simple thermostat ON/OFF can be
used as room thermostat.
3.3.2 - HEATING MODE OPERATION
BY OUTDOOR SENSOR
By giving the 1
st
figure of the parameter
A the value 1 (e.g. A-1x) it means that
the request for more heat is driven by
an outer sensor. When the outer sensor, which is normally supplied as standard, is installed, a heating curve is to be
determined.
The flow temperature will be calculated
in accordance with the detected outer
temperature.
The boiler will begin modulating according to this flow temperature. When a
heating curve is set, the parameters on
the right are very important.
The boiler will switch off, if the flow
temperature exceeds by 5K the preset flow temperature value (i.e. Parameter 3). The boiler will start again
as soon as the flow temperature has
gone under the pre-set value (Parameter 3) minus the heating system hysteresis (Parameter 8).
The diagram beside is referring to the next
example:
Global flow temperature = 90°C
(param. 3)
Minimum global flow temperature = 15
°C (param 4)
Minimum outer temperature = -20°C
(param. 5)
Night shift = 10°C (param 7).
The setting of the flow (modulated) temperature can be done by Parameter 3.
A communicating room thermostat can
also be used as remote control panel.
To this purpose Unical offers an interface board, which will allow the boiler
and the room thermostat to communi-
temperature exceeds by 5K the preset flow temperature value (i.e. Parameter 3). The boiler will start again
as soon as the flow temperature has
gone under the pre-set value (Parameter 3) minus the heating system hysteresis (Parameter 8).
cate.
The boiler will switch off, if the flow
Parameter 3:Maximum global flow temperature setting at the minimum
outer temperature
Parameter 4:Minimum global flow temperature setting at the outdoor tempera
ture of 20°C
Parameter 5:Minimum outdoor temperature
Parameter 6:Temperature block upon request for heat. If, according to the
outdoor temperature, the flow temperature value is lower than the
parameter 6, there will be no heat request. This parameter can
be used in summer: when the outer temperature is high, a 25°C
regulation can be calculated whereas the parameter 6 can be
set to 30°C. In this case the request for heat will be stopped,
preventing the radiators from overheating.
Parameter 7:The open contact of a room thermostat makes temperature de
crease during the night(night shift) - see note (*) on paragraph
3.2.8.2). The night temperature decrease can be set to 0 - 40K
by the parameter 7.
Parameter 8:If it should be necessary to make a slight adjustment of the
measured outer temperature because, for instance, the outer
sensor NTC calibration tolerance is too high, it is possible to
make an adjustment of ± 5K on the measured value, by the
parameter 8.
Parameters to set by outdoor sensor.
Global flow
temperature
100
°C
90
80
70
60
Adjusting range of
parameter 7 (0-40 K)
50
Adjusting range of
parameter 3 (30-90°C)
40
30
20
Adjusti ng
range of
paramet er 6
(15-30°C)
10
0
parameter 6
-25 -2 0
parameter 3
parameter 7
-15 -10-50
Adjusting range of parameter 5
510
Outdoor temperature °C
parameter 4
15 20 25 30
Adjus ting range of
parameter 4 (15-60°C)
Fig. 19
36
Heating Curve Parameters
3.3.3 - HEA TING MODE OPERATION
BY OUTER COMPENSA TOR (0
– 10 V signal)
By giving the 1
A the value 2 (e.g. A-2x) it means that
the request for more heat is driven by
an outer compensator.
When an outer compensator with 0 –10
V outlet signal is employed, this signal
can be combined with the boiler. By the
AM-4 PCB, the outer compensator can
be combined with the boiler. The connection can be carried out on the terminal-strip of fig. 16 (terminals 1-2).
The parameters applied are shown on
the right.
The boiler will switch off, if the flow
st
figure of the parameter
Parameter G:the setting is carried out at a 0 V signal, equivalent to the mini
mum global flow temperature (parameter 4)
Parameter H:the setting is carried out at a 10 V signal, equivalent to the mini-
mum outer temperature (parameter 3)
Parameter 6:Temperature block upon heat request. According to the outer
temperature there will be no request for heat the if the calculated setting point for the flow temperature is lower than the parameter 6. This parameter can be used in summer: when the outer
temperature is high, a 25°C regulation can be calculated where
as the parameter 6 can be set to 30°C. In this case the request
for heat will be stopped, preventing the radiators from overheat
ing.
temperature exceeds by 5K the preset flow temperature value (i.e. Parameter 3). The boiler will start again
as soon as the flow temperature has
Note: outdoor sensor and 0 - 10V outer compensator cannot be connected simultaneously.
gone under the pre-set value (Parameter 3) minus the heating system hysteresis (Parameter 8).
3.4 - DOMESTIC HOT
WATER (DHW) MODE
OPERATION
The boiler DHW mode operation is got
3.4.1 - DHW CONTROLED BY A NTC
SENSOR ON DHW STORAGE
TANK
The storage tank NTC sensor, available at UNICAL’s, is connected to terminals 7-8 (fig. 16). For the electrical connection of the storage tank loading
pump or diverting valve see examples
in fig. 6.1 – 6.6 and wiring diagrams of
fig. 17.
Priority system wiring:
From the terminal-strip of fig. 16 it is
possible to use a 230 V signal to activate the storage tank loading pump
or the diverting valve. To connect a
motorised 3-way diverting valve, refer to the wiring diagrams at par . 2.6.4.
It is advisable to use the activation
through the special AM-4 PCB, supplied
as standard in the panel board.
This PCB can work together with a normal thermostat or a NTC sensor controlling the storage DHW tank and an
storage tank loading pump or a 3-way
Parameter 1:Storage tank hot water set temperature
Parameter 2:DHW Production ON
Parameter b:Flow temperature increase : the boiler water modulated
temperature is equal to parameter 1 + parameter b.
Parameter J:Storage tank loading pump post-circulation (max. 270 sec)
Parameter L:hysteresis between 5 and 14 °C.
The following beside parameters are fundamental for the DHW mode operation.
signal to supply the storage tank loading pump through a relay . For its electrical connections and programming,
refer to figs 6.1 – 6.2 – 6.4 - 6.8 and 17.
valve.
The DHW mode operation takes priority on the heating system.
The terminals to be used are shown in
fig. 16. As for possible configurations see
fig. 17.
perature value (Parameter 1) plus the preset hysteresis (Parameter L). The boiler
will begin modulating at the temperature
equal to Parameter 1 plus Parameter b.
The DHW mode operation will stop when
The DHW mode operation is requested
when the storage tank water temperature goes under the pre-set DHW tem-
the storage tank water temperature exceeds by 5K the pre-set temperature of
Parameter 1.
3.4.2 - DHW CONTROLED BY
STORA GE TANK THERMOST AT
The conditions mentioned at par. 3.4.1
above can be applied for this type of
operation as well, provided that the
DHW request results from the closing
of the hot water thermostat contact (connected to terminals 7 - 8 of fig. 16 to its
sensor inside a proper storage tank
sheath).
In this case the parameter 1 value is to
be higher than or equal to the pre-set
DHW thermostat temperature. This is
necessary to ensure that the boiler begins modulating at the correct flow temperature.
Check all other parameters.
37
3.5 - BUNER PRESSURE
ADJUSTMENT
Unscrew the sampling point cap.
Insert the analyser sensor into the sampling point and adjust the burner to test
to low flame operation (test mode). Read
the percentage of CO
between 8,9 and 9,2%. If its value is not
included between these values, adjust
it by using the adjusting screw A (see
fig. 20) you can get after removing by
an ALLEN wrench the screw cap on the
gas valve. By turning it clockwise, the
CO
percentage increases, while it de-
2
creases anticlockwise. Follow the same
procedure to adjust the other burners.
If the CO
percentage is too low, check
2
if the air and smoke ducts are not obstructed. If they are not obstructed, check
if the burner and/or the exchanger (aluminium sections) are well cleaned.
WARNING!
The burner can be adjusted only when
operating at low flame.
, which must be
2
Smoke sampling point
Fig. 19
A
Fig. 19
Fig. 20
38
4
ERRORS
4.1 - BLANK DISPLAY
In case of blank display, check if the terminals 19 and 20 of the terminal strip (fig.
16) are 230V powered. In case of no power, check if the fuse is intact. Check then
if the switch On/Off is set to ON. At any
short circuit of the pump (or 3-way valve),
4.2 - THE BOILER DOES
NOT FULFILL THE DHW
PRODUCTION
REQUEST
replace the 2 AF fuse. Moreover check if
the display flat cable is properly connected to the MBD (the main PCB) and the
display. Should the problem persist despite that the fuse and the power supply
are OK, the MBD needs changing.
WARNING:THE FUSE IS INT O THE 230
V CIRCUIT. MAKE SURE THAT THE
POWER IS OFF BEFORE CHECKING.
Check the storage tank NTC sensor and
its wiring.
Check the 3-way valve and its wiring.
The boiler does not fulfil the heat request
for the heating system: check if all elec-
trical connections of the room thermostat (on terminals 5-6 of the 20-pole
terminal strip) and, if necessary , of the
outer sensor (on terminals 3-4 of the
20-pole terminal strip) or of the outer
compensator (on terminals 1-2 of the
20-pole terminal strip) have been performed properly; check if there are
any cut cables (see fig. 16).
Check the storage tank loading pump and
its wiring.
Check all programming parameters.
4.3 - DIAGNOSTICS CVI
ELECTRONIC CARD
In case of failure, the LED ‘’A’’ will be con-
tinuously lighted. Every 10 seconds
the light will be interrupted by a blinking
code reporting the failure reason. The se-quence here reported will be repeated
up to the reset.
A
Fig. 21
Sequence
Light
period
for 10 seconds
Error code
Lock out within
safety time
False light during
the detection period
Air pressure switch in
close position
Time out air pressure
switch
Air pressure switch
in open position
Leak of flame
OFF
period
for 0,6 seconds
Blinking
code
Blinking
code
OFF
period
for 1,2 seconds
Possible fault
Within safety time,
flame not detected
the ionisation electrode
could be faulty
Air pressure switch with
attached close contact
The air pressure switch
doesn’t close the contact
within the required time
The air pressure switch
doesn’t open during the
ignition or the operation
Leak of flame during
the operation
4.4 - BURNER LOCKOUTS
A burner lockout is detected by the numbers of the thermal element the error refers to, followed by a blinking spot. The
three following digits indicate the error
Description
= Short blink
= Long blink
nature. See the tables 4.5.1 to 4.5.4 to
know the meaning of all error codes. The
errors that do not refer to a single thermal
element but to the boiler as a whole are
presented by the error number E, followed by two digits.
Warning! To reset the boiler, press
both the reset button of each burner
and the reset key.
39
4.5 - ERROR CODES
ALARM means that the alarm signal is
on if a signal relay is connected to ter-
minals 14-15 (tension free contacts).
When the display shows the error codes
listed in the table 4.5.1 here below, the
alarm signal can be coupled with them.
4.5.1 - ERROR CODES BY ALARM
Error codeDescriptionAlarm
b01Failure of the boiler thermal element No. 1Yes
b02Failure of the boiler thermal element No. 2Yes
b03Failure of the boiler thermal element No. 3Yes
b04Failure of the boiler thermal element No. 4Yes
b05Failure of the boiler thermal element No. 5Yes
b06Failure of the boiler thermal element No. 6Yes
b07Failure of the boiler thermal element No. 7Yes
E92Failure of all boiler thermal elementsYes
Possible Causes and Solutions
-
Defective fan
- Power supply cable with phase/neutral re versed (the boiler is phase-sensitive , see par. 2.6.1)
- Safety thermostat is open: check the wiring and/or the thermostat. Check if water circulation is sufficient.
- No ignition and/or ionisation:check if the gas supply is sufficient check the ignition and/or ionisation electrode
check the gas valve adjustment(see par. 3.5)
Note: The errors b 01÷07 shall foresee a specific programming to give an alarm-signal. See parameter J, 1st figure, par. 3.2.8.2.
4.5.2 - ERROR CODES RELATED TO LOCAL TEMPERATURES
Error codeDescriptionAlarm
L1 4Local Temperature NTC 1 in shor t circuitno
L2 4Local Temperature NTC 2 in shor t circuitno
L3 4Local Temperature NTC 3 in shor t circuitno
L4 4Local Temperature NTC 4 in shor t circuitno
L5 4Local Temperature NTC 5 in shor t circuitno
L6 4Local Temperature NTC 6 in shor t circuitno
L7 4Local Temperature NTC 7 in shor t circuitno
L8 4Local Temperature NTC 8 in shor t circuitno
L1 3Open Connector on the Local Temperature NTC 1no
L2 3Open Connector on the Local Temperature NTC 2no
L3 3Open Connector on the Local Temperature NTC 3no
L4 3Open Connector on the Local Temperature NTC 4no
L5 3Open Connector on the Local Temperature NTC 5no
L6 3Open Connector on the Local Temperature NTC 6no
L7 3Open Connector on the Local Temperature NTC 7no
L8 3Open Connector on the Local Temperature NTC 8no
E31Global Flow NTC in short circuitno
E36Global Flow NTC has an open connector (failure for other NTCs)n o
E32Global Return NTC in short circuitno
E37Global Return NTC has an open contactno
Possible Causes and Solutions
-The Local Flow Temperature NTC of the component involved is defective
-The Global Retur n Temperature NTC is defective
-The water circulation through the thermal element involved is insufficient
Note: in the case of more NTC failures at the same time, the most important one prevails.
E.g.: “E” failures prevail on “L” failures; if “L” codes are equivalent, the code with the lowest first digit prevails; in the case that the
first digits are equivalent, the code with the highest second digit prevails.
40
Continuous
Error codeDescriptionAlarm
L1 2Local Flow Temperature of Component 1 > 98°Cno
L2 2Temperatura locale di mandata dell’elemento 2 > 98°Cno
L3 2Temperatura locale di mandata dell’elemento 3 > 98°Cno
L4 2Temperatura locale di mandata dell’elemento 4 > 98°Cno
L5 2Temperatura locale di mandata dell’elemento 5 > 98°Cno
L6 2Temperatura locale di mandata dell’elemento 6 > 98°Cno
L7 2Temperatura locale di mandata dell’elemento 7 > 98°Cno
L8 2Temperatura locale di mandata dell’elemento 8 > 98°Cno
L1 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 1 is too highno
L2 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 2 is too highno
L3 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 3 is too highno
L4 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 4 is too highno
L5 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 5 is too highno
L6 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 6 is too highno
L7 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 7 is too highno
L8 1The difference between the Global Return T emperature and the Local Flow Temp. of thermal elements 8 is too highno
Possible Causes and Solutions
As for the above mentioned conditions, they can be due to wiring break, short circuit or failure of the NTC involved, or
over temperature of the heat module involved due to insufficient water circulation.
4.5.3 - ERROR CODES RELATED T O GAS PRESSURE, MBD, AM-4 and AM-5
Error codeDescriptionAlarm
E26The Min. Gas Pressure Switch is open (or the low water pressure optional is open)no
E90The module AM-4 has not been detected (see par. 2.4.3)no
E91The module AM-5 has not been detected (or the number of modules AM-5
is wrong (see par. 4.2.2)no
Error inside the MBDno
Error of Communicationno
The Global Flow Temperature is too highno
To verify position dipswitches E90 page 24.
For E91,see page 25 position dipswitches
Check the water pressure into the boiler ( it must be higher than 1 bar). If necessary, reset at 3 bar .
4.5.4 - ERROR CODES RELATED TO GLOBAL TEMPERATURES
Error codeDescriptionAlarm
E18Global Flow Temperature > 95°Cno
E19Global Return Temperature > 95°Cn o
E92All modules in errorSi
Possible causes and solutions
The NTC and/or wiring of the global temperature involved is defective
Insufficient or even no circulation of water due to the obstruction of the sections or the pump stop.
Note: In the case that one of the terminal strip “X 11” to “X17” controlling the fans is not connected, the fan runs at max speed and
the thermal element is not switched on.
41
5
MAINTENANCE
5.1 - MAIN FEATURES
If the boiler is correctly adjusted, it about
doesn't need maintenance; it only needs
to be checked once a year and, if necessary, be cleaned. In any case the frequency of the cleaning depends on the
cleaness of the air sucked for the combustion. As much as the dust present in
the air will be sucked inside the combustion chamber, the smok e side resistance will increase, which, finally, will
result in a reduced heat input (and consequently a reduced output).
Before cleaning the boiler body sections,
check the boiler input and the CO
centage (see 3.5). If the actual input (with
the correct CO
shown in the chapter 3, the boiler does
) is within 5% of the value
2
not need to be cleaned.
The operation then, can be limited to
the cleaning of the siphon.
Note! A reduction of the input can be
caused by the obstruction of the evacuation duct or of the air intake. Check,
first of all, that this is not the reason.
per-
2
electric connection of flow sensor “B”
(black), return “C” (white) and the water pressure gauge connection “D”
D
B
C
• Only for Modulex 450-540-630, remo-
ve the electric connections of the modules, marked by the label 1…..6 or 7
(limit thermostat, ignition and detection
electrode, hearting and immersion sensor)
The sequence here reported for the
modules inspection is for a MODULEX 360.
For boilers MODULEX 450, 540
and 630 these steps are a little
different, for example for the cable
removal and for the opening that will
be done on the opposite side (left
side).
• Remove the 2 screws “G” on the front
right and rear right frame supports
(both on the left for Modulex 450-540-
630) with 13 mm tool
G
1st phase –
Opening for modules inspection
• Close the voltage and gas feeding
• Unloose the gas inlet connection and
separate the gas feeding pipe from the
boiler
• Remove all the jackets
• Remove the plug “A” for 230V supply
of the boiler
A
• Remove the safety spring “H” of the
support bar “L” for upper opening.
• Remove all the mixer outer fixing
screws “E” with 13 mm pipe tool.
H
E
• Lift up the upper boiler part “I”. For
Modulex 450-540-630 the opening will
be done on the opposite side.
• Remove all the mixer inner fixing
screws “F” with 14 mm pipe tool.
I
F
• Remove the cover in order to access
to the electric section
Only for Modulex 360, remove the
42
• Set the support bar “L” in the provi-
ded for position on frame support “M”,
locking it with the spring “H”
M
L
H
• The boiler is open
nd
2
phase
baffle removal
• Access to the condensation collector
by removing the Ø 10 screws of the
inspection flange “P”, on the opposite
side of the chimney connection.
P
• Remove the Ø 7 fixing screw “Q” of
baffle “R”
rd
phase – Cleaning
3
• Blow into the burners compressed air
from flame side (metallic spounge) to
the gas side (slick).
• Wash, with a water jet, the combustion
chamber: pay attention to not to wet
the electrical wiring. During this operation ascertain that the condensate
evacuation pipe is always free, so that
the water cannot come out from the
tray.
• Blow with compressed air in the combustion chamber, in betw een the sections, so that all dirty parts are removed from the aluminum protrusions.
• Inspect the flue duct and the smoke
chamber.
• Remove the burner gaskets “N”, remo-
ving the fixing screws “O”, and the burners.
O
N
The burner gaskets have to be replaced every maintenance operation; they
have to be set between the burner and
the mixer, NOT BETWEEN THE BURNER AND THE ALUMINIUM BODY!!
4th phase – Reassembly
Q
• Replace the burner sealing gaskets
• Proceed with the re-assembling fol-
lowing the same steps at the contrary.
Note: for the baffle “Q” setting into the
condensation collector, use the provided for sliding tracks.
• Before starting the boiler ascertain that
the condensate siphon is filled with
water.
• Before opening the gas feeding, che-
ck that the gas connection (previously
disconnected) is now correctly sealed.
T o do this, open the gas coc k and che-
R
ck the soundness of the coupling using
a soap solution.
• As soon as a burner is put into operation check immediately the soundness
between the gas valve and the relevant premixing chamber.
• Make the combustion analysis and
check the combustion parameters..
• Make sure that all the gas pressure
test nipples, previously open, are closed and tight.
R
BAFFLE POSITION
If removed or moved
during the boiler cleaning, it has to be set again
into the original position.
43
The Unical declines every responsibility for the possible inaccuracies if owed to errors of tran-
script or press. Also reserves the right to bring those changes that it will hold necessary to it own
products or profits, without jeopardizing its essential characteristics.
AGS.P.A.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.