Unical Modal 64-291 INSTALLATION USE AND SERVICING INSTRUCTIONS (05/03)

Page 1
MODAL
26740 - 11/04 rev. 0
INSTALLATION, USE AND SERVICING INSTRUCTION
(to be kept by the user)
Page 2
WARNING
When the boiler is operated with a pressure jet gas burner, because it does not belong to any of the categories among those listed in the Annex II to the Directive 97/23/CE (regarding pressure equipment) and beeing, furthermore, mentioned in the Directive 90/396/CE (Gas Appliance Direc­tive) to which the art. 1, clause 3, paragraph 6.5 makes reference, it is excluded from the scope of the Directive.
GENERAL INFORMATIONS Introduction
This manual supplies a summary of what has to be followed during the installation, use and servicing of the UNICAL boilers, MODAL range.
Choice of the boiler
For a correct choice and application of the MODAL boilers it is necessary to follow the instructions given in this manual.
Installation
The installation of the boilers and the auxiliary equipments, related to the heating system, must be in conformity with all the regulations and rules in force. It is law that all the gas appliances are installed, commissioned and serviced by a registered installer in accordance with the regulations below. Failure to install appliances correctly coul lead prosecution. It is in your own interest, and that of the safety, to ensure the law is complied with. The following must be complied with: Current Building Regulations and Clean Air Act. Water authority regulations. Local Authority Regulations and Regional Bylaws. Gas Safety Regulations. Any special regional requirements of local Electricity and Gas undertaking. Fire Service and Insurance Company requirements.
Commissioning
The main purpose of the commissioning is to verify the correct operation of all the safety and control devices. Before leaving the installation the commissioner has to control the operation of the boiler for, at least, a complete working cycle.
Guarantee
The boiler guarantee is bound to the compliance of the the requirements stated in this manual, and any non-fulfilment or modification will make it void.
Normative
It is the responsibility of the installer to fulfil all the regulations concerning the boiler house, the safety devices, the chimney, the fuel supply lines, the electrical installations and all the other local requirements and safety instructions.
Approvals
The UNICAL boilers, MODAL range, have been tested and CE certified for the gas operation by GASTEC ITALIA, who has recognised to these boilers the conformity certificate according to the following directives:
- Gas Appliances Directive (90/396 CE), compulsory as per 1st January 1996;
- Efficiency Directive (92/42 CE), compulsory as per 1st January 1998;
- The conformity to the Low Voltage Directive (73/23 CE), compulsory as per 1st January 1997 has been verified and ascertained by GASTEC ITALIA.
The conformity to the EMC (Electro Magnetic Compatibility 89/336 CE), compulsory as per 1st January 1996, is not applicable to the MODAL boilers because they do not have electronic components. For the time beeing there are no European Directives covering the oil fired boilers, except the Efficiency Directive (92/42 CE).
Data plate and Serial No.
The data plate, supplied in a separate enveloppe with the relevant documents, makes reference to a serial No, embossed in an aluminium plate riveted to the front tube plate in the lower RH side corner.
Use of the boiler This boiler has to be used for heating the water at a temperature not higher than the boiling temperature in the installation conditions.
2
Page 3
GAS SAFETY (INSTALLATION AND USE) REGULATIONS, 1994
It is law that all gas appliances are installed and serviced by a CORGI registered installer in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure the law is complied with. The installation of the boiler MUST also be in accordance with the latest I.E.E. Wiring Regulations, local building regulations, bye­laws of the local water authority, the building regulations and the Building Standards (Scotland) and any relevant requirements of the local authority.
HEALTH & SAFETY DOCUMENT No. 635
The Electricity at Work Regulations, 1989.
The manufacturer's notes must NOT be taken, in any way, as overriding statutory obligations.
IMPORTANT. These appliances are CE certificated for safety and performance. It is, therefore, important that no external control devices, e.g. flue dampers, economisers etc., are directly connected to these appliances unless covered by these Installation and Servicing Instructions or as other-wise recommended by Unical in writing. If in doubt please inquire.
Detailed recommendations are contained in the following British Standard Codes of Practice: BS 6891 Low pressure installation pipes. BS 5449 Forced circulation hot water
systems.
BS 5546 Installation of gas hot water
supplies for domestic purposes (2nd Family Gases).
BS 6644 Ventilation (for gas appliances of
rated input exceeding 60 kW).
Notes.
To obtain the gas consumption:­a. For l/s divide the gross heat input (kW) by
C.V. of the gas (MJ/m³).
b. For ft³/h divide the gross heat input (Btu/h)
by C.V. of the gas (Btu/ft³).
Any direct connection of a control device not approved by Unical could invalidate the certification and the normal appliance warranty.
3
Page 4
1
COSTRUCTIONAL-DIMENSIONAL
TECHNICAL CHARACTERISTICS .................... page 5
1.1 Construction of the MODAL boilers ...................................... page 5
1.2 Dimensions and hydraulic connections of MODAL boilers . page 6
2
2.1 Packaging .............................................................................. page 7
2.2 Handling ................................................................................. page 7
2.3 Positioning in the boiler house .............................................. page 7
2.4 Casing assembly ................................................................... page 8
2.5 Connection to the chimney ................................................... page 9
2.6 Feeding water quality ............................................................ page 9
2.6.1 Shunt pump .................................................................. page 9
2.6.2 Choice of the burner .................................................... page 9
STANDARD PANEL BOARD .................................. page 10
INSTALLATION .................................................................. page 7
3
4
5
3.1 Panel board type 21057 - functions description .................. page 10
3.2 Electrical wiring diagram for single phase burner & pump .. page 10
COMMISSIONING AND OPERATION ............ page 11
4.1 Positioning the turbulators .................................................... page 11
4.2 Preliminary check .................................................................. page 11
4.3 First commissioning .............................................................. page 11
4.4 Operation of the boiler........................................................... page 12
4.5 Switch off of the boiler........................................................... page 12
MAINTENANCE ................................................................ page 13
5.1 General rules ......................................................................... page 13
5.2 Ordinary maintenance ........................................................... page 13
5.3 Extraordinary maintenance ................................................... page 13
5.4 Cleaning of the boiler ............................................................ page 14
5.5 Check of the boiler operation ................................................ page 14
5.6 Check of the burner operation .............................................. page 14
5.7 Boiler house ........................................................................... page 14
4
Page 5
1
CONSTRUCTIONAL-DIMENSIONAL TECHNICAL CHARACTERISTICS
1.1 - CONSTRUCTION OF
THE MODAL BOILERS
The construction completely satisfies the requirements of the EN 303- part 1. The sheet metal parts of the pressure vessel are manufactured of certified carbon steel, type S235JRG2, according to EN 10025, with melting certificate 3.1.B, according EN 10024; whereas the pipes are of steel ST 37.0 according to DIN 1626. The welders and the WPS (Welding Procedures Specifications) have been approved according to EN 287 and EN 288 by TUEV (DE). The boilers are equipped with a reversible inged door, which can be opened, for this
reason, from L.H. or R.H. side. The outer shell is insulated with a glass wool matress, thick 60 mm, protected by a textile in mineral fiber. The upper part of the outer shell is equipped with uplift hook(s). The boilers are provided with two 1/2" bulb holders with inner diameter of 15 mm (for 3 bulbs each), suitable to locate the thermostats and thermometer bulbs. The casing side panels are provided with holes for the cables of the electrical supply, of the pumps, of the burner and any other
auxiliary equipment. Note:The MODAL boilers are to be equipped with ON/OFF burner; alternatively they an be equipped with a two stage or modulating burner, provided the minimum reachable heat input is not lower than the figure shown on the data plate for the fuel used on site.
fig. 1
5
Page 6
Fiber wool
Ceramic fiber
Blind burner plate 250x250
Burner plate insulation gasket 250x250
ø 180
ø 15075ø 180
MD 105÷186
MD 233÷291
Fiber wool
Ceramic fiber
Blind burner plate 200x200
Burner plate insulation gasket 200x200
ø 130
ø 130
75
1.2 - DIMENSIONS AND HYDRAULIC CONNECTIONS OF MODAL BOILERS
E
B
D
A
4
2
1
T3
F
G
T2-T5
121
258
T1e
T4
C
H
3
* - In the models MODAL 233 and MODAL 291 the connections T1-T2 are flanged.
The dimension H is applicable only to the models MODAL 233 and MODAL 291
D
4 Sight glass T1 C.H. flow T2 C.H. return
E
mm
mm
480
305
480
305
480
305
500
350
500
350
500
350
500
350
500
350
580
421
580
421
F
mm
115
115
115
130
130
130
130
130
165
165
mm
--
--
--
--
--
--
--
--
1482
1732
UNI 2278 PN16
Rp 1½
Rp 1½
Rp 1½
DN 65
DN 65
T1 - T2
H
G
1 Panel board 2 Burner connecting plate 3 Cleaning door
Output
(kW)
kcal/h
(64)
55.000 (76)
65.000 (93)
80.000
(105)
90.000
(116)
(140)
(163)
(186)
(233)
(291)
Input
(kW)
kcal/h
(71)
61.000 (84)
72.000
(102)
88.000
(115)
99.000
(128)
110.000 (155)
133.000 (180)
155.000 (206)
177.000 (258)
222.000 (322)
277.000
MODAL
Type
64
76
93
105
116
140
163
186
233
291
100.000
120.000
140.000
160.000
200.000
250.000
mm
690
690
690
760
760
760
760
760
860
860
DIMENSIONS
C
B
A
mm
722
722
722
812
812
812
812
812
937
937
mm
990
990
990
1205
1205
1205
1385
1385
1437
1687
mm
190
190
190
190
190
190
190
190
190
190
(*) Pressure losses with a water flow rate related to a delta T of 15 K.
CONNECTIONS
T3
Ø
ISO 7/1
mm
200
200
200
200
Rp 2
200
Rp 2
200
Rp 2
200
Rp 2
200
Rp 2
250
250
T4
mm
130
130
130
180
180
180
180
180
180
180
fig. 2
T3 Flue connection T4 Burner axis T5 Boiler drain
Combustion
chamber
dimensions
T5
ISO 7/1
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Rp ¾
Øi x Lg
mm
330 x 670
330 x670
330 x 670
390 x 850
390 x 850
390 x 850
390 x 1030
390 x 1030
470 x 1070
470 x 1320
Ø
Boiler
capacity
liters
86
86
86
126
126
126
151
151
203
247
Water side
press. loss(*)
m w.c.
0,10
0,13
0,16
0,10
0,10
0,14
0,20
0,25
0,22
0,30
Smoke
side press. losses
mm w.c.
1,5
1,8
2,5
3
3
5
8
14
18
22
working
pressure
Max.
allow.
bar
5
5
5
5
5
5
5
5
5
5
Weight
kg
212
212
212
309
309
309
349
349
485
555
DETAIL FOR DOOR
DRILLING
MODAL 64÷93
6
DETAIL FOR DOOR
DRILLING
MODAL 105÷291fig. 3 fig. 4
Page 7
2
X
INSTALLATION
2.1 - PACKAGING
The MODAL boilers are supplied complete with door and smoke chamber already fitted, whilst the casing with the insulation matress are contained in separate cardboard packaging(s). The panel board and the accessories are inside the combustion chamber. Before starting the installation make sure that
2.2 - HANDLING
The boiler can be moved into position by lifting, through the upper hook(s), or by the use of rollers placed under the strong L profiles of the basement.
2.3 - POSITIONING IN THE BOILER HOUSE
The installation of the boiler must be in accordance with the relevant requirements of the Gas Safety Regulations, current I.E.E. Regulations, local water authority bye-laws and it should also comply with any relevant requirements of the local gas supplier, local authority and the relevant Standard Codes of Practice and building regulations. The boiler house must be ventilated through permanent openings having a total surface not lower than 1/30th of the floor area of the boiler house, with a minimum of 0.5 m2. Ventilation by grilles communicating directly with the outside air is required at both, high and low levels. The boiler must be positioned so that there is enough space available for the following:
- Access around the boiler fore servicing
- Space to open the boiler front door
- Space to access the burner.
The installation of the boiler as close as possible to the chimney position is highly recommended. To allow the cleaning of the smoke pipes, in front of the boiler a clearance equal to the length of the boiler, has to be available. With the boiler door opened at 90°, the distance between the front of the door and the adjacent wall must be equal, at least, at the length of the burner. The boiler must stand on a non-combustible floor (i.e. concrete or brick), which must be flat, level and of a suitable load bearing capacity to support the weight of the boiler (when filled with water) and any ancillary equipment. Once the installation has been made the boiler must result perfectly horizontal and well stable (to avoid vibrations and noise).
the length and the width of the boiler body received correspond to the dimensions of the ordered boiler, shown in the previous tables and that the cartons, containing the casing, or part of it, are marked with the same model. In addition to the a. m. panel board, packed in its own carton, in the combustion chamber, as accessories, there are also:
- a carton containing the flanges for flow, return and safety connections (if applicable)
If it necessary, due to the dimensions of the boiler, it is possible to remove the front door and the smoke chamber to facilitate the introduction in the boiler house.
x = not shorter than the boiler body
with relevant gaskets and bolts, the cylindrical brush for the cleaning of the smoke pipes.
- cleaning brush handle extension.
- turbulators extractor.
- ceramic fiber rope for the insulation between the door and burner blast tube.
fig. 5
7
Page 8
7
6
3
5
4
1
2
5
1
3
2
4
6
6
2.4 - CASING ASSEMBLY
N.B. It is suggested to verify that the boiler is positioned in its final place and that all the hydraulic connections are made correctly before starting the casing assembly. Before opening the casing carton(s) make sure they are stamped with the right boiler model, corresponding to the boiler to be installed.
N.B.: The packaging containing the panel
board is delivered inside the combustion chamber, as well as the documents and the guarantee certificate.
Refer to diagram fig. 6 & 7 for details
A. Fit the insulation blanket (1) onto the boiler
shell and secure it in to place using the elasticated straps (2) provided, ensuring that the metal clips grip in to the external surface of the insulation.
B. Locate the side panels (3) and (4) with the
lower bend inside the bottom L profiles and the upper bend in the seats of front and rear tube plates. To determine which is the left and right panel ensure that the cable glands are po­sitioned facing toward the front edge.
C) After removal of the two side screws from
the panel board rotate its cover frontwards. Fit the panel board to the upper panel (5) and after having passed the cables (mains, room thermostat, burner etc.) through the cable glands fitted to the side panel insert these cables and the capillaries of thermometer and thermostats through the slots on its base. Fit the casing upper panel, complete with the panel board, to the side panels (3 & 4), directing the capillaries of thermostats and thermometer to the bulb holder.
D) Insert the thermometer and thermostat
bulbs in the bulb holders as shown in fig. 7 and connect the mains, the burner, the pump(s) and any ancillary equipment to the panel board.
Close the panel board. E) Fit the upper panel rear reinforcement (6). F) Remove the protective paper film from
data plate and ventilation requirement label
(7) and fit them at the top front corner of
the most accessible side panel after
removal of dust from the surface.
The data plate and label are in the
documents envelope.
1 Thermometer bulb 2 Working thermostat bulb 3 Safety thermostat bulb 4 Minimum thermostat bulb 5 Bulb holders 6 Bulb retaining clip
fig. 6
fig. 7
8
Page 9
L
Ø A
2.5 - CONNECTION TO THE
CHIMNEY
The chimney has a foundamental importance for the good operation of the boiler. Due to the low temperature of the smokes during the intermittent operation, it is necessary that the chimney is perfectly impermeable to the condensate of the combustion products and manufactured with corrosion resistant materials.
2.6 - FEEDING WATER
QUALITY
- The chemical-physical characteristics of
the C.H. system and reinstatement water
are foundamental for the good operation
and safety of the boiler.
- Among the inconvenients caused by the
bad quality of the feeding water the most
frequent and serious is the scaling of the
heat exchange surfaces.
- Less frequent, but also dangerous, is the
corrosion of the water side surfaces of all
the circuit.
- It is well known that the lime, due to its
very low thermal conductivity, reduces the
heat transfer so that also a scaling of a
The different connections must be sealed with an approved boiler putty so that the inlet of fresh air, with consequent increase of the possibility of condensate formation, is avoided. Furthermore the possible condensate or rain water comming from the chimney must be avoided from entering the smoke chamber of the boiler.
few millimeters produces very dangerous localized overheating. 1 mm of lime reduces the heat transfer from metal to water by 10%. It is suggested to make a water treatement in the following cases:
A- high hardness of the water available on
site (higher than 20°f). B- very large C.H. systems. C- large quantities of reinstatement water
due to water leaks. D- subsequent fillings of the system due to
maintenance works. E- mixing of different metals in the CH circuit.
As far as the cross section and the high of the chimney is concerned, it is necessary to make reference to the local and national rules in force.
In the flue pipe, between the boiler and the chimney, convenient sampling points for smoke temperature and combustion products analysis must be provided.
For the treatment of filling water it is suggested to address them self to specialized firms. The same firms are able to provide for the descaling of the boilers. Every C.H. system needs reinstatements of water, du to evaporation, small or large water leaks or for maintenance works. It is, therefor, necessary to be able to evaluate the entity of the reinstatement water to avoid inconvenients due to untreated water. For that reason it is suggested to fit, in the feeding line to the boiler, a water meter for small capacities.
2.6.1 - SHUNT PUMP
The MODAL boilers must always operate in forced circulation hot water systems and with a minimum return temperature of 55 °C.. So, it is suggestable to adopt a shunt pump, having also an anti-condensation purpose,
2.6.2 - CHOICE OF THE BURNER
The correct choise and the adjustment of the burner are foundamental for the best operation of the boilerand then they shall be accurate and not under evaluated. The burner will be selected by verifying that its working diagram (fuel flow rate - pressure in the furnace) is compatible with the same features declared for the boiler. Remember that the smoke side resistance, i.e. the counterpressure in the furnace, are referred to "0" draught at the chimney base. It is also convenient that the burner blast tube have its length not shorter than that shown in table 8 and that the flame have a shape suitable to the characteristics of the MODAL furnace.
In fact to better exploit all the heating surface of the reversed flame furnace it is necessary to use burners capable to guarantee a long and narrow flame at all operating conditions or also at minimum input in case of two stage or modulating burners.
installed between the flow and return connections, upstream an eventual 3 or 4 way mixing valve. This pump will be sized according to the following formula:
BOILER TYPE
MODAL 64 ÷ 93
MODAL 105 ÷ 140
MODAL 163 ÷ 186
MODAL 233 ÷ 291
Too short flames can cause a localized overheating of the front part of the furnace, and the combustion products, not sufficiently cooled down, entering the smoke pipes at a too high temperature, can cause important damages to the boiler. The burner manufacturing companies are able to supply the flame dimensions developped by their burners. More informations are given in the paragraph "Commissioning". .
øA
mm
130
180
180
180
L
mm
150
170
170
170
Q = P x 22
where Q = Water flow rate in liter/h
P = Boiler nominal output in kW
and the manometric head 1-2 m w.c.
fig. 8
BURNER BLAST TUBE DIMENSIONS
9
Page 10
3
31
42
11
41
12
13
32
E
E
E
E
L1 T2N S3T1 B4
IG
11
41
32
32
12
13
31
230V~ 50Hz
2
1
3
4
4-4
24
14
C
2
1
22
12
21
11
C
2
G-V
6-6
7-7
8-8
9-9
10-10
Ts
7
14 15
16
6 95 8 10
B
A
20
21
24
Pi
18
17
23
22
19
11
12
Ipi
Ib
(50°C)
(60°÷90°C)
(54°÷84°C)
(100°C)
Tm
Te1
F1 (max 4 A)
Te2
13
C
N
Ph
B5
T6
T7 T8
1 stage burner plug
st
2 stage burner plug (optional)
nd
STANDARD PANEL BOARD
3.1 - PANEL BOARD TYPE 21057 - FUNCTIONS DESCRIPTION
Through the main switch 11 the panel board and all the equipments connected to it will be under power. The switches 12 & 13 switch On and OFF the power to the burner and the Heating pump (via a relay, if necessary). With the thermostat 32 the working temperature of the boiler can be adjusted. This thermostat is provided with a DPDT contact, for the control of a two stage burner. The differential between the switching points of the two double pole is 6°C (not adjustable). The minimum thermostat, accessible through the opening of the panel board cover, switches OFF the C.H. pump during the reacing of the steady state and up to the obtention of 50 °C within the boiler. On the electrical supply line to the boiler a switch with fuses is to be forseen.
11 Illuminated main switch 12 Burner switch 13 C.H. pump switch 31 High limit thermostat
32 Working thermostat 41 General fuse 42 Thermometer
fig. 9
10
3.2 - ELECTRICAL WIRING DIAGRAM FOR SINGLE PHASE BURNER AND PUMP
In case the room thermostat is fitted, remove the link between 11 and 12
Ph Phase (230V ~50Hz) N Neutral F1 General fuse (max 4A) Ib Burner switch IG Illuminated main switch Ipi C.H. pump switch
Te11st stage working thermostat (60°C÷90°C) Te22nd stage working thermostat (54°C÷84°C) Tm Minimum thermostat (50°C) Ts High limit ther mostat (100°C) Pi C.H. pump A Burner lockout warning lamp (eventual)
B Hourmeter for 1st stage operation C Hourmeter for 2nd stage operation
fig. 10
Page 11
4
COMMISSIONING AND OPERATION
4.1 - POSITIONING THE TURBULATORS
The MODAL boilers are foreseen to operate at the nominal output declared. If the boiler
Turbulators removal
Detail 1: Fit the brush handle extension onto the turbulator remover Withdraw the pin from turbulator.
Detail 4: Turn up to unblock the turbulator.
is used at a lower ourput, the resulting smoke temperature can be lower than 160°C and in this case the turbulators can be positioned against the rear wall of the smoke chamber. In the other cases the turbulators are positioned inside of the relevant pipes at
Detail 2: Fit the pin in the radial hole with a hammer.
Detail 5: Withdraw the turbulator
approx 2 to 4 cm from the front tube plate. The commissioning of the burner will be done under the responsibility of a qualified burner technician, sent by the burner manufacturer. In that occasion a commissioning report will be filled in.
Detail 3: Screw the turbulator remover onto the turbulator.
Detail 6: Turn the remover counterclockwise to release the turbulator
The procedure from detail 3 to 6 has to be repeated for all the turbulators.
4.2 - PRELIMINARY CHECK
Once all the hydraulic, electrical and fuel connections have been made, before starting the boiler we suggest to ascertain that:
- The expansion vessel and the pressure
relief valve are correctly connected and are in no way interceptable.
- The bulb of thermometer, working, high
limit and minimum thermostats are well secured into their proper bulb holder.
- The turbulators are correctly fitted in all
the smoke pipes.
- The C.H. circuit has been washed and
rinsed and is free from solid impurities.
- The C.H. circuit is filled with water and has been completely purged.
- The pumps operate properly.
- The flow switch, the pressure relief valve, and the overheating discharge valve, if any, are adjusted at the right value.
- The fuel, hydraulic, electrical and safety connections are executed in confor mity with national and local requirements in force.
- There are no water leaks.
- The burner has been fitted according to the instructions of the burner manufacturer.
- The mains voltage and frequency are
4.3 - FIRST COMMISSIONING
At the commissioning stage of the boiler a qualified technician has to perform the following checks:
- Internal and external sound test of burner and fuel feeding pipe;
- Adjustment of the fuel throughput according
to the nominal input of the boiler (it is convenient to remember that the nominal input can be obtained by sharing the output shown in the table of pages 6), between the 1st and the 2nd stage, knowing that the 1st stage flame can go down to the
fig. 11
compatible with the burner and the electrical equipment of the boiler.
- The burner is adjusted for the fuel type, among those listed in the burner data plate, available on the installation site, and the burner output range is compatible with the boiler output.
- In the boiler house there are also the burner instructions.
- The C.H. pipes are properly insulated.
- The C.H. system is capable to absorb the heating quantity produced at the first start of the burner, during the test period.
The shunt pump is installed as prescribed in the paragraph 2.6.1.
60% of the nominal output.
Proceed, then, in the following way:
- Open the fuel feeding cock and check that there are no leaks in the feeding line,
- Ascertain that all the switches of the panel board are in OFF position and adjust
11
Page 12
the working thermostat to the minimum position.
- Switch ON the panel board through the main switch.
- Switch ON the C.H. pump: it will start to rotate as soon as the minimum water temperature thermostat detects 50°C.
- Switch the burner ON.
- Position the working thermostats of 1st and 2nd stages to the maximum setting to create a heat request.
During this phase check that:
- There are no smoke leaks from the front door, the burner plate and the chimney connection.
- There is a draught at the chimney base between 2 and 4 mm w.g.
- There are no water leaks.
- The different thermostats and the other installation safety devices work properly.
- The shunt pump operates correctly.
- The burner ignition is good.
- The burner characteristics (main adjustments and nozzle type) correspond to the boiler data plate.
With a burner properly adjusted it must be possible to reach easily, from a smoke sample taken at the chimney base, the values given below:
1) With light oil having a maximum viscosity
of 1.5 °E at 20 °C:
- CO2 = 12 to 13 %
- Smoke index < 1
- Smoke tempearture = 190 to 210 °C
2) With Natural Gas:
- CO2 = 9 to 10 %
- Smoke temperature = 180 to 200 °C (values related to a clean boiler, with water at 70 °C). It is suggested to adjust the fuel throughput to the actual needs of the C.H. installation (avoid to overcharge the boiler), without exceeding the a.m. smoke temperatures (never go below 160 °C).
4.4 - OPERATION OF THE BOILER
The HIGH EFFICIENCY MODAL boilers are forseen to operate with a return water temperature never below 54 °C when operated on light oil, and never below 59 °C when operated on gas, to avoid (or, at least, to reduce) the smoke acid condensation phenomenon, which can be the reason of a premature deterioration of the steel boiler body. The working thermostat, pos. 32 of the panel board, must be set at a temperature of approximately 80 to 85 °C. The room temperature will be compulsorily adjusted trhough a mixing valve and, eventually, an outer compensator.
4.5 - SWITCH OFF OF THE BOILER
- Switch OFF the burner (switch No.12 to 0
position).
- Leave the pumps working up to when they
are not stopped by the minimum thermostat.
- Switch Off the power to the boiler panel
board.
- If it is decided not to use the boiler for a
long period close also the gate valves of the fuel.
To homogenise the water temperature, or avoid as maximum as possible, returns into the boiler at a temperature below 54 °C when operated on oil, or 59°C when operated on gas, a properly dimensioned shunt pump must be fitted between flow and return pipes of the boiler. N.B.The metal sheet corrosion due to the acid condensate is not covered by the guarantee because it depends only from the operation of the C.H. system. The MODAL panel board is equipped with a low temperature thermostat not allowing the operation of the pump when the boiler temperature is below 50 °C (protection against cold starts).
12
Page 13
5
MAINTENANCE
5.1 - GENERAL RULES
- All the operations must be performed by
qualified personnel .
- Affix a Warning poster, to the entrance of
the boiler house, signalling: WARNING
...........boiler under maintenance.
- The operations must be performed after
having switched Off power supply (eventually removing the fuses to avoid accidental startings of the burner) and
5.2 - ORDINARY MAINTENANCE
The operation conditions of the boiler are notably varying from case to case and depend on the fuel used,on the burner adjustment, on the number of startings, on the characteristics of the heating system, etc., for which it is not possible to establish previously an interval of time between a service and the following one. It is therefore necessary that the technician establishes the interval in base to a first observation of the smudging state of the smoke circuit. Generally speaking we recommend the followings intervals of cleaning according to the type of fuel:
- Gas fired boilers: once a year.
- Oil fired boilers: twice a year, or more often
if there is reason to doubt of their good
operation. In any case local rules in terms of maintenance have to be followed. We advise, however, to shake the turbulators
- without removing them from the smoke pipes
- at least once every 15-20 days of boiler operation to avoid that the combustion residues can stop them so much to make
after having closed the valves of feeding of the fuel (particularly if gas is involved).
- To protect from the dust the electric equipments of the boiler house, the boiler panel board and the burner.
- Protect themselves with convenient suits, gloves, glasses and masks, use a vacuum cleaner for the removal of the soots and and put them in the special containers with
their removal extremely difficult. During the operations of ordinary maintenance it will be necessary to brush the tube bundle
- after the removal of the turbulators - and
the furnace and collect the soots through the cleaning doors on the smoke chamber. Besides it will be necessary to verify the good operation of the protection and control devices (thermostats, thermometers) of the boiler and of the plant (manometers, flow and pressure switches, expansion vessels) and all the safety devices. In this occasion it will be necessary to notice the quantity of reinstatement water used and decide, also in base to its hardness, an intervention of preventive descaling. It must be considered that the calcium and magnesium salts dissolved in the raw water, with repeated reinstatements, can cause deposits in the boiler that hinder the inner circulation and subsequent overheating of the wall plates with possible serious damages that cannot be attributed to the constructive geometry and/or to the materials used and/ to the constructive technique and, therefore, they are not covered by guarantee.
the indication of the content.
- The possible closing of valves of the heating circuit must be indicated by a warning signal.
To get a good operation and the maximum boiler efficiency, a regular cleaning of the combustion, the smoke pipes and the smoke chamber is necessary.
On the occasion of the ordinary maintenance it is useful to perform a small discharge from the boiler to verify if sludges escape. In affirmative case, it will be necessary to prolong the discharge up to get clear water. At the end of the drainage it will be necessary to reestablish the level of the water in the system. At the end of the smoke circuit cleaning, to the next restart check around the burner plate and the smoke chamber for smoke leaks. In the case some smoke leaks were noticed, first of all tighten the screws fitting the smoke and, not getting result, it will be necessary to replace the sealing gasket. Similarly it will be necessary to act on the front door, increasing at first the tightening of the screws and then, if necessary, by replacing the whole gasket. At the end check and, if necessary, restore the sealing of the connection of the chimney and of the burner with the door. The performed operations must be recorded on the log book of C.H. system.
5.3 - EXTRAORDINARY MAINTENANCE
Extraordinary maintenance of end season or for long periods of inactivity. It will be necessary to perform all the operations described in the preceding chapter and besides:
- Check the state of consumption of the
turbulators to replace them in time.
- To facilitate the extraction of the turbulators,
with the MODAL boilers a special
extractor is supplied.
- After the cleaning of the smoke circuit it is convenient to pass in the pipes smoke and in the furnace with a rag soaked of diluted solution of caustic soda. After having let to dry cross again all the surfaces with a rag soaked of oil. Perfectly close the the burner air intake to avoid a continuous passage of damp air through the boiler recalled by the chi­mney it self. It is advisable to put inside the furnace
some alive mortar that has an hygroscopic action.
- Do not empty the C.H. system and the boiler.
- Protect the screws with graphitized fat, nuts and pivots of the door.
- Show all the operations that must be perform to the following put into operation, particularly the operation of the shunt pump must be checked.
13
Page 14
5.4 - CLEANING OF THE BOILER
Follow the next sequence:
- Close the feeding of the oil.
- Cooldown the boiler to the ambient
temperature.
- Switch Off the electrical supply to the boiler
and the burner.
- Open the front door.
- Shake and remove the turbulators every
15-20 days of activity of the boiler to avoid that the residues of combustion can stop them so much to make difficult their removal).
- Clean the turbulators and the smoke pipes
by brushing them with the brush supplied.
- Reposition the turbulators.
- Remove the cleaning door and all the soot
from the smoke chamber.
- Re-fit the cleaning doors.
5.5 - CHECK OF THE BOILER OPERATION
For a safe operation of the boiler it is necessary to check:
- The good operation of the working
thermostat.
- The good operation of the high limit
thermostat.
- Verify the state of the refractory insulation of the combustion chamber door.
- Verify the state of the door sealing rope.
- Close the door of the furnace.
Turbulator
Round brush
- The adjustment and the good operation of the minimum thermostat.
- The good operation of the shunt system.
- The good operation of the outer compensator (if fitted).
fig. 12
fig. 13
Brush handle
Brush handle extension (if applicable)
- The good operation of all the other safety and control devices imposed by local requirements.
fig. 14
fig. 15
5.6 - CHECK OF THE BURNER OPERATION
- See the burner instruction manual.
- Follow all the local requirement in terms
of burner maintenance .
5.7 - BOILER HOUSE
For the combustion of oil or gas the burner needs air. Accordingly wide openings are foreseen for the entry of the air in the boiler house. These openings never have to be obstructed. Maintain the boiler house clean and dust free.
The boiler is not a closet: avoid to store any kind of materials. Maintain the entry of the boiler free and easy to reach in any moment. Ascertain that the boiler house is endowed with efficient emergency lamp.
14
Page 15
15
Page 16
AG S.P.A.
46033 Casteldario - Mantova - ITALIA - tel. +39.0376.57001 (r.a.) - telefax +39.0376.660556
Unical AG declines any liability for the inaccuriaces that may appear due to errors in trascription or printing. It also reserves the right to introduce those modifications to its products that it considers necesssary or useful, without compromising the essential characteristics of the said products.
www.unical.eu info@unical-ag.com
Loading...