Unical Lattner ALKON 50, ALKON 70, Lattner ALKON 70 Installation And Servicing Manual

00333990 - 1st edition - 05/12
ALKON 70
ALKON 50
INSTALLATION AND SERVICING MANUAL
Notice:
- In the Commonwealth of Massachusetts this boiler must be installed by a licensed Plumber or Gas Fitter.
Condensing gas boiler
®
LATTNER
2
CONTENTS
1 GENERAL INFORMATION ................................................................................................................................................................................ 3
1.1 Symbols used in this guide .......................................................................................................................................................................... 3
1.2 Correct use of the appliance ....................................................................................................................................................................... 3
1.3 Water treatment ............................................................................................................................................................................................ 3
1.4 Information to be passed over to the person in charge of the appliance ................................................................................................. 4
1.5 Safety warnings ............................................................................................................................................................................................ 4
1.6 Data badge .................................................................................................................................................................................................... 5
1.7 The following instruction............................................................................................................................................................................... 6
1.8 Tools, materials and additional equipment .................................................................................................................................................. 7
1.9 Disposal ........................................................................................................................................................................................................ 7
1.10General warnings ......................................................................................................................................................................................... 7
2 TECHNICAL FEATURES AND DIMENSIONS................................................................................................................................................. 8
2.1 Technical features ........................................................................................................................................................................................ 8
2.2 Dimensions ................................................................................................................................................................................................... 8
2.3 Main components ......................................................................................................................................................................................... 9
2.4 Boiler water circuit diagram ....................................................................................................................................................................... 11
2.5 Performance data ....................................................................................................................................................................................... 12
3 INSTRUCTIONS FOR THE INSTALLER........................................................................................................................................................ 13
3.1 General warnings ...................................................................................................................................................................................... 13
3.2 Code and standard approvals .................................................................................................................................................................. 14
3.3 Packaging .................................................................................................................................................................................................. 14
3.4 Minimum clearance ................................................................................................................................................................................... 15
3.5 Boiler location in a boiler house ................................................................................................................................................................ 16
3.6 Connections............................................................................................................................................................................................... 17
3.7 Installation on existing heating systems .................................................................................................................................................. 17
3.8 Gas connection ......................................................................................................................................................................................... 19
3.9 Connection return and flow system pipes ............................................................................................................................................... 20
3.10 Determination of primary boiler pump or boiler pump system.......................................................................................................... 21
3.11 Pressure relief valve drain pipe ................................................................................................................................................................ 22
3.12 Working pressure...................................................................................................................................................................................... 22
3.13 Connecting the expansion vessel in a single boiler system .................................................................................................................. 22
3.14 Underfloor Heating system....................................................................................................................................................................... 23
3.15 Condensing drain ...................................................................................................................................................................................... 23
3.16 Water treatment ......................................................................................................................................................................................... 24
3.17 Combustion air and ventilation openings ................................................................................................................................................. 25
3.18 Installation of the exhaust and air intake system .................................................................................................................................... 26
3.18 Flue outlet installation ................................................................................................................................................................................ 25
3.19 Room air system for installation using indorr combustion air ................................................................................................................ 26
3.20 Vent and air supply system for orizontal direct vent system ................................................................................................................. 29
3.21 Electrical connection ................................................................................................................................................................................. 30
Regulation in force .................................................................................................................................................................................... 30
Mains electrical connection 120V - 60 Hz ............................................................................................................................................... 30
Room thermostat and / or E8 heating controller connection .................................................................................................................. 31
Connection of the additional safety device.............................................................................................................................................. 31
3.22 Wiring diagrams ........................................................................................................................................................................................ 32
3.23 Ladder diagrams ....................................................................................................................................................................................... 34
3.24 Starting up .................................................................................................................................................................................................. 35
3.25 Filling the system ...................................................................................................................................................................................... 35
3.26 Initial lighting ............................................................................................................................................................................................... 36
Preliminary checks ................................................................................................................................................................................... 36
Ignition and switching off........................................................................................................................................................................... 36
Information to be supplied to the user ..................................................................................................................................................... 36
3.27 Testing ignition safety shut off device ...................................................................................................................................................... 38
3.28 Burner adjustment ..................................................................................................................................................................................... 39
3.29 Programming of the operational parameters ........................................................................................................................................... 41
3.30 Variation of input range for high altitude ................................................................................................................................................... 42
4 SERVICING SCHEDULE .................................................................................................................................................................................. 43
4.1 Instructions for inspection and servicing.................................................................................................................................................. 43
Table of the resistance values in function of the heating and domestic sensor temperature ................................................................. 43
4.2 Periodic examination of venting system ................................................................................................................................................... 44
4.3 Proper procedure for cleaning flue gas .................................................................................................................................................... 44
4.4 Proper procedure for cleaning the burner ................................................................................................................................................ 44
4.5 Visual inspection of the flame .................................................................................................................................................................... 45
4.6 Proper reassembly and resealing of the air intake system .................................................................................................................... 45
4.7 Verification and cleaning of the condensate evacuation siphon.............................................................................................................. 46
4.8 Sealing gasket between distributor and boiler body ................................................................................................................................46
5 FAULT FINDING ................................................................................................................................................................................................ 47
5.1 Error codes ................................................................................................................................................................................................ 47
5.2 Request of maintenance ........................................................................................................................................................................... 48
SPARE PARTS .................................................................................................................................................................................................. 49
Warning: this manual contains instructions to be used exclusively by the installer and/or a competent person in accordance with the current laws in force. The end user MUST not make any alterations to the boiler. Failure to follow the instructions indicated in this manual, which is supplied with the boiler, could cause injury to persons, animals or damage to property. LATTNER shall not be held liable for any injury and/or damage.
This unit is ready for operation with gas A (natural), you can make the transformation to work
with gas E and (propane HD) using proper kit provided by LATTNER
Warning:
Any operation on the unit must be performed by authorized personnel.
3
General Information
1.1 -SYMBOLS USED IN THIS GUIDE
When reading this guide particular care has to be given to the parts marked with the followings symbols:
1.2 - CORRECT USE OF THE APPLIANCE
The ALKON appliance has been designed utilizing today’s heating technology and in compliance with the current safety regulations.However, following an improper use, dangers could arise for the safety and life of the user or of other people, or damage could be caused to the appliance or other objects.The appliance is designed to be used in pumped hot water central heating systems. Any other use of this appliance will be
considered improper. LATTNER declines any responsibility for any damages or injuries caused by an improper use; in this case the risk is completely at the user’s responsibility .In order to use the appliance according to the scopes it was designed for it is essential to carefully follow the instructions indicated in this guide.
1.3 - WATER TREATMENT
The hardness of the mains water supply conditions the frequency with which the heat exchanger is cleaned.
In hard water areas where the main water can exceed 15°f total hardness, a scale reducing device is recommended. The choice of this device has to be made taking into consideration the characteristics of the water.
In order to improve the resistance to lime scale it is recommended to adjust the domestic hot water temperature
as near as possible to the one you really require.
We recommend you to check the state of cleanliness of the domestic hot water heat exchanger at the end of the first year and subsequently, on the basis of the lime scale found, this period can be extended to two years.
1
GENERAL INFORMATION
CAUTION
INDICATES A POTENTIAL HAZAR­DOUS SITUATION, WHICH IF NOT AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.
WARNING
INDICATES A POTENTIALLY HAZAR­DOUS SITUATION, WHICH IF NOT AVO­IDED, COULD RESULT IN DEATH OR SERIOUS INJURY.
DANGER
INDICATES AN IMMINENTLY HAZAR­DOUS SITUATION, WHICH IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
NOTICE
INDICATES SPECIAL ISTRUCTIONS ON INSTALLATION, OPERATION OR MAINTENANCE THAT ARE IMPORTANT BUT NOT RELATED TO PERSONAL INJURY OR PROPERTY DAMAGE.
CAUTION
RISK OF ELECTRIC SHOCK. INDICA­TES PRESENCE OF HAZARDS DUE TO ELECTRIC SHOCK.
WARNING!
If you do not follow these instructions exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT T O DO IF YOU SMELL GAS
- Do NOT try to light any appliance
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire dep.
4
General Information
WARNING!
The device should not be used by people with reduced physical, mental and sensory, experience and knowledge. These people must be well-informed and supervised during the work. Children must be supervised so they do not play with the appliance.
WARNING! The installation, adjustment, and servicing of this appliance must be carried out by a competent person and installed in accordance with the current standards and regulations. Failure to correctly install this appliance could cause injury to persons, animals or damage to property . The manufacturer shall not be held liable for any injury and/or damage.
DANGER!
Servicing or repairs of the appliance must be carried out by LATTNER authorised service technicians; LATTNER recommends drawing up a service contract. Bad or irregular servicing could compromise the safe operation of the appliance, and could cause injury to persons, animals or damage to property for which LATTNER shall not be held liable.
WARNING! Modifications to parts connected to the appliance
Do not carry out any modifications to the following parts:
- the boiler
- to the gas, air, water supply pipes and electrical current
- to the flue pipe, safety relief valve and its drainage pipe
- to the constructive components which influence the appliance’s safe operation
WARNING!
When tightening or loosening the screw pipe connections, use only adequate fork spanners. The improper use and/or the use of inadequate equipment can cause damages (for example water or gas leakages).
WARNING!
Indications for appliances operating with propane gas Ensure yourself that before installing the appliance the gas tank has been purged. For a correct purging of the tank contact the liquid gas supplier or a competent person who has been legally authorized. If the tank has not been correctly purged problems could occur during ignition. If this occurs contact the liquid gas tank’s supplier.
1.5 -SAFETY W ARNINGS
1.4 - INFORMATION TO BE HANDED OVER TO THE USER
Go through the information in this manual with the owner/operator and make sure that he or she is familair with all necessary operating instructions, in particular:
Hand over these instructions to the end user, together with any other literature regarding this appliance,
placed inside the envelope contained in the packaging. The user has to keep these documents in a safe
place in order to always have them at hand for future reference.
Inform the user on the importance of air vents and of the flue outlet system, stressing the fact that is absolutely
forbidden to make any alterations to the boiler.
Inform the user how to check the system’s water pressure as well as informing him how to restore the correct
pressure.
Explain the function of time and temperature controls, thermostats, heating controls and radiators, to ensure
the greatest possible fuel economy.
Remind the user that it is obligatory to carry out a comprehensive service annually and a combustion analysis
every two years (in compliance with the national law).
If the appliance is sold or transferred to another owner or if the present user moves home and leaves the
appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by the new owner and/or installer.
Failure to follow the instructions indicated in this guide, which is supplied with the boiler, could cause injury to persons, animals or damage to property . The manufacturer shall not be held liable for any such injury and/ or damage.
5
General Information
1.6 DATA BADGE
A sample Data Plate for a Alkon Boiler is shown in figure below.
DANGER Smell of gas
If you smell gas follow these safety indications:
- Do not turn on or off electrical switches
- Do no smoke
- Do not use the telephone
- Close the main gas tap
- Open all windows and doors where the gas leakage has occurred
- Inform the gas society or a company specialized in installing and servicing heating systems
DANGER Explosive and easily inflammable substances
Do not use or leave explosive or easily inflammable material (as for example: petrol, paint, paper) in the room where the appliance has been installed.
A sample DataPackaging for a Alkon Boiler is shown in figure below.
®
LATTNER
LATTNER
6
General Information
1.7 - THE FOLLOWING INSTRUCTION MUST BE FOLLOWED
- The boiler must only be used for its designated purpose,
as described in the Installation Instructions.
- Each unit is fitted with a data plate. Consult the details on
this plate to verify whether the boiler is compliant with its intended location, e.g.: gas type, power source and ven­ting classification.
- Only use the boiler with the accessories and spare parts
listed.
- Other combinations, accessories and consumables must
only be used if they are specifically designed for the inten­ded application and do not affect the system performance and the safety requirements.
- Maintenance and repairs must only performed by trained
professionals.
- Installation of a condensing gas boiler must be reported to
the relevant gas utility company and have it approved.
- You are only allowed to operate the condensing gas boiler
with the vent system that has been specifically designed and approved for this type of boiler.
- Please note that local permission for the vent system and
the condensate water connection to the public sewer sy­stem may be required.
You must also respect:
- The local building codes stipulating the installation rules.
- The local building codes concerning the air intake and
outlet systems and the chimney connection.
- The regulations for the power supply connection.
- The technical rules laid down by the gas utility company
concerning the connection of the gas connection to the local gas mains.
- The instructions and standards concerning the safety equi-
pment for the water/space heating system.
- The Installation Instructions for building heating systems.
- The boiler must be located in an area where leakage of
the boiler or connections will not result in damage to the area adjacent to the boiler or to lower floors of the structu­re. When such locations cannot be avoided, it is recom­mended that a suitable drain pan be installed under the boiler.
- The boiler must be installed in such way that the all com-
ponents are protected from water (dripping, spraying, rain etc.) during boiler operation and service.
- The boiler must not be installed on or against carpeting.
- Do not restrict or seal any air intake or outlet openings.
- If you find any defects, you must inform the owner of the
system of the defect and the associated hazard in writing.
DANGER.
Gas is flammable and may cause an explo­sion. Beware if you smell gas: there may be an explo­sion hazard!
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
- Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
WARNING WHAT TO DO IF YOU SMELL GAS
- Do NOT try to light any appliance.
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s in­structions.
- If you cannot reach your gas supllier, call the fire department.
WARNING Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the boiler.
Unsuitable heating system water can cause the formation of scale or sludge, which affects system efficiency. It can also cause corrosion and reduce life of the heat exchanger.
- You must follow Latner guidelines for boiler water quality.
- Thoroughly flush the system prior to filling.
- Follow the LATTNER cleaning instructions.
- Never use water that has been treated by a reverse osmosis, D.I., or distilled water to soften the water to fill the heating system.
- Do not use inhibitors or other additives unless appro­ved by LATTNER for that purpose!
- When frost protection of the heating system is desired, only use LATTNER-approved antifreezes. The allowed maximum concentration is 50%.
- When using oxygen-permeable pipes, e. g. for under floor heating systems, you must separate the system from the boiler using plate heat exchangers.
- Valve off boiler while flushing system, do not introduce any system cleaner into the boiler loop. Flush system thoroughly to remove all system cleaner before filling boiler.
Approved antifreeze (max. concentration 50%):
Rhomar RhoGard Mutli-Metal (AL safe)
Noble Noburst AL
Approved system cleaner:
Noble Noburst Hydronic System Cleaner
Fernox F3 Cleaner
Rhomar Hydro-Solv 9100
The system cleaners from NoBurst, Rhomar, and Fernox are not to be used in the boiler. The boiler must be closed off (valved off) from the rest of the system or not connected while the cleaners are in the system. The system should then be drai­ned and then thoroughly flushed with clean wa­ter to remove all the system cleaner.
Approved inhibitors:
Rhomar Pro-tek 922
Noble Noburst AL inhibitor
7
General Information
1.10 - GENERAL WARNINGS
This instruction manual is an integral and indispensable part of the product and must be retained by the person in charge of the appliance.
Please read carefully the instructions contained in this manual as they provide important indications regarding the safe installation, use and servicing of this appliance.
Keep this manual in a safe place for future reference. The installation and servicing must be carried out in
accordance with the regulations in force according to the manufacturer’s instructions and by legally competent authorized persons.
The installations for the domestic hot water production MUST be build, in their entirety, with materials (taps, pipes, fittings, etc.) approved for drinkable water.
By a competent person, we imply a person who has a specific technical qualification in the field of components for central heating systems for domestic use, domestic hot water production and servicing. The person must have the qualifications foreseen by the current laws in force.
Bad or irregular servicing could compromise the safe operation of the appliance, and could cause injury to persons, animals or damage to property. The manufacturer shall not be held liable for any such injury and/or damage.
Before carrying out any cleaning or servicing turn off the electrical supply to the boiler by means of the ON/OFF switch and/or by means of the appropriate shutdown devices.
Do not obstruct the intake/outlet terminal ducts. In the event of failure and/or faulty functioning of the appliance,
switch off the boiler. Do not attempt to make any repairs: contact qualified technicians.
Any repairs must be carried out by LATTNER authorized technicians and using only original spare parts. Non­observance of the above requirement may jeopardize the safety of the appliance.
To guarantee the efficiency and correct functioning of the appliance it is indispensable to have the boiler serviced annually by a qualified person.
If the boiler remains unused for long periods, ensure that any dangerous parts are rendered innocuous.
Before putting again into service an appliance which has been unused for a certain time, proceed to rinse the domestic hot water circuit, making the water flowing for the time necessary to draw the full content of the domestic circuit.
If the appliance is sold or transferred to another owner or if the present user moves home and leaves the appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by the new owner and/ or installer.
Only original accessories must be used for all appliances supplied with optionals or kits (including electrical ones). This appliance must be used only for the purposes for which it has been expressively designed. Any other use shall be considered incorrect and therefore dangerous.
Operating Limits of the boiler: Max. boiler temperature: 176 °F (80 °C) Max Allowable Working Temperature ASME: 200 °F Max. Allowable Working Pressure ASME: 92 psi
1.9 - DISPOSAL
- Dispose of the boiler packaging in an environmentally sound manner.
- Dispose of components of the heating system (e.g. boiler or control device), that must be replaced in an environ­mentally responsible manner.
1.8 - TOOLS, MATERIALS AND
ADDITIONAL EQUIPMENT
For the installation and maintenance of the boiler you will need:
- Standard tools for space heating, gas and water fitting
- Digital manometer that is capable of reading both positive and negative pressures
- Combustion analyzer
- Digital multimeter
- pH digital meter
- Metric Allen wrenches
- Metric socket wrenches
In addition, a handtruck with a fastening belt is useful.
8
Technical features and dimensions
2.1 - TECHNICAL FEATURES
The ALKON 50 and ALKON 70 boilers are a thermals gas fired units with an atmospheric fully pre-mixed burner.
They are supplied only in heating version.
These boilers have an input head power of: 176,000 Btu or 227,500 Btu (51,58 or 66,67 kW), These boi­lers are designed for use on gas category IV. The ALKON boiler is supplied complete with all the safety
and control devices in accordance with all the current regulations and its technical and functional features comply with the regulations prescribed by:
ANSI Z21.13 / CSA 4.9 - Gas-fired low pressure steam and hot water boilers
DESCRIPTION OF COMPONENTS AND FEATURES:
Aluminium heat exchanger/condenser;
Fully premixed burner working at constant CO2;
Electronic ignition;
Safety high limit thermostat;
• Flow temperature sensor;
• Return temperature sensor;
Automatic air vent;
Drain condensate siphon
Control panel with electrical protection;
2
R CH system return 1 ¼’’
M CH flow system 1 ¼’’ G Gas Inlet Ø ¾’’ Sc Outlet condensate drain siphon (from aluminium body)
Scf Outlet condensate drain siphon (from the flue pipe) SV Safety valve outlet A Air intake S Flue Outlet
TECHNICAL FEATURES AND DIMENSIONS
2.2 - DIMENSIONS
eBUS device;
CH temperature selector switch: 86 ÷176 °F (30 ÷ 80°C);
Flame modulation in function of the absorbed power;
Pump overrun function;
Additional functions : diagnostics of operation parameters
and troubles, antifreeze, technical functions and digital in­dication of failures.
Constant combustion ratio
Self adapting output depending on the length of flue ducts
Pump (only ALKON 70)
Smoke pressure switch
OPTIONAL KITS:
Kit of manifold for additional safety devices
Krömschröder controller E8/Expansion modules and
modulating thermostats (case for wall mounting)
Mixing bottle Kit
Chimney for single, battery or cascade mounting
Supporting frames
Kit of blind flanges and hydraulic manifolds
On-Off pump for ALKON 50.
VIEW FROM ABOVE
VIEW FROM BELOW
24.2’’
(615 mm)
RMG
Sc
Scf
SV
A
S
10.5’’
(266 mm)
36.6’’ (930 mm)
16.9’’
(430mm)
4.2’’
(107 mm)
3.1’’
(78 mm)
7,1’’
(180mm)
3,1’’
(78 mm)
3,9’’
(100 mm)
5,2’’
(132 mm)
4,3’’
(110 mm)
4,3’’
(110 mm)
3,3’’
(85 mm)
3,1’’
(78mm)
5,3’’
(135mm)
4.9’’ (125 mm)
10.5’’ (266 mm)
7.0’’ (179 mm)
9
Technical features and dimensions
2.3 - MAIN COMPONENTS ALKON 50
N.B.: The boiler cannot work on natural circulation
AIR
VENT
VALVE
MODULATING
FAN
SMOKE
PRESSURE
SWITCH
GAS VALVE
SPACER PIPE
REPLACEABLE
FOR MOUNTING
OF OPTIONAL
CIRCULATOR
FLOW
TEMPERATURE
SENSOR
RETURN
TEMPERATURE
SENSOR
OVERHEAT
THERMOSTAT
IGNITION
TRANSFORMER
MIN. WATER
PRESSURE
SWITCH
IGNITION
ELECTRODE
SAFETY VALVE
ALUMINIUM HEA T EXCHANGER/ CONDENSER
CONDENSATE
DRAIN
(Ø 1‘‘ - 25 mm)
FLUE
OUTLET PIPE
(Ø 3.14’’
- 80 mm)
PIPE WITH
SMOKE
SAMPLING
SIPHON
AIR INTAK E
OPENING
(Ø 3.14’’
- 80 mm)
R
1’’ ¼
R
1’’ ¼
G
¾’’
10
Technical features and dimensions
ALKON 70
PUMP
AIR
VENT
VALVE
MODULATING
FAN
SMOKE
PRESSURE
SWITCH
GAS VALVE
FLOW
TEMPERATURE
SENSOR
RETURN
TEMPERATURE
SENSOR
OVERHEAT
THERMOSTAT
IGNITION
TRANSFORMER
MIN. WATER
PRESSURE
SWITCH
IGNITION
ELECTRODE
SAFETY VALVE
ALUMINIUM HEA T EXCHANGER/ CONDENSER
CONDENSATE
DRAIN
(Ø 1‘‘ - 25 mm)
FLUE
OUTLET PIPE
(Ø 3.14’’
- 80 mm)
PIPE WITH
SMOKE
SAMPLING
SIPHON
DETECTION
ELECTRODE
AIR INT AKE
OPENING
(Ø 3.14’’
- 80 mm)
R
1’’ ¼
R
1’’ ¼
G
¾’’
11
Technical features and dimensions
ATTENTION! THE PRE- FORMING FOR THE BOILER PUMP IS ONLY FOR THE PUMP KIT SUPPLIED BY LATTNER
2.4 - BOILER WATER CIRCUIT DIAGRAM
1 Gas valve 2 CH flow temperature sensor 3 CH return temperature sensor 4 Condensate drain siphon 5 Overheat thermostat 6 Heat exchanger 7 Burner 8 Air vent valve 9 Flue outlet / Air intake 10 Fan 11 Premix 12 Room sealed chamber 13 Replaceable pipe for insertion optional pump
(only for ALKON 50)
pump only for ALKON 70 14 Pressure switch against lack of water 15 Safety valve supplied 16 Smoke pressure switch 17 Manomètre (optionelle)
M C.H flow G Gas supply R C.H. return
M
R
G
1
2
3
4
5
6
7
8
12
9
10
11
13
14
15
16
17
60
40 80
20 100
120
0
12
Technical features and dimensions
Minimum heat input
Nominal heat input (low) (*) Nominal heat input (high) (reduction for Altitude) Nominal heat output (HT) Minimum heat output (HT) Efficiency at full load (100%) Efficiency at min load Nominal heat output in condensing mode Minimum heat output in condensing mode Efficiency at nominal load in condensing mode Efficiency at min load in condensing mode Combustion efficiency at nominal load Combustion efficiency at min load Stand-by losses Flue gas temperature (Flue gas temp - room temp) Air excess λ
Condensate production max
Boiler category Minimum water flow rate in CH circuit Δt 36°F (20°C) Min. pressure in CH circuit Max. allowable pressure in CH circuit Water content in primary circuit Maximum operating temperature Minimum operating temperature
Electrical supply
Net weight Gross weight
2.5 - PERFORMANCE DATA
For information regarding the adjustment of: INJECTORS - BURNER PRESSURES – DIAPHRAGMS – OUTPUTS – GAS CONSUMPTIONS please refer to the paragraph BURNER ADJUSTMENT.
[Btu/hr (kW)] [Btu/hr (kW)] [Btu/hr (kW)] [Btu/hr (kW)] [Btu/hr (kW)] [%] [%] [Btu/hr (kW)] [Btu/hr (kW)] [%] [%] [%] [%] [%] [°F (°C)] [%] [lb/hr (kg/hr)]
[gal/min (l/min)] [psi (kPa)] [psi (kPa)] [gal (L)] [°F (°C)] [°F (°C)]
[V-Hz]
[lb (kg)] [lb (kg)]
55,800 227,500 204,750 199,000 47,700
87.45
85.50 298,600 54,000
91.46
96.7
98.4
98.3
0.22 124
20.6
20.3
IV
1.43
7.3 92 1 176 86
120 - 60
130 141
(16.35) (66.67) (60.01) (58.32) (13.98)
(70.0) (15.83)
(51.1)
(9.2)
(5.40) (50) (634) (3.9) (80) (30)
(59) (64)
ALKON 70
38,500 176,000 158,400 154,000 32,900
87.66
85.50 161,000 37,200
91.6
96.70
97.8
98.4
0.3 110
20.6
16.5
IV
1.01
7.3 92 1 176 86
120 - 60
111 121
(11.28) (51.58) (46.42) (45.13) (9.6)
(47.2) (10.9)
(43.3)
(7.5)
(3.86) (50) (634) (3.9) (80) (30)
(50) (55)
ALKON 50
Max dynamic gas pressure A (natural) Nominal dynamic gas pressure A (natural) Min. dynamic gas pressure A (natural)
Max dynamic gas pressure E (Propan HD) Nominal dynamic gas pressure E (Propan HD) Min. dynamic gas pressure E (Propan HD)
[in wc (kPa)] [in wc (kPa)] [in wc (kPa)]
[in wc (kPa)] [in wc (kPa)] [in wc (kPa)]
10.5
7.0
3.5
13.0
11.0
8.0
(2.61) (1.74) (0.87)
(3.23) (2.74) (1.99)
(*) For adjustments, refer to section 3.26 and 3.27
13
Instructions for the installer
3
INSTRUCTIONS FOR THE INSTALLER
3.1 - GENERAL WARNINGS
WARNING! This boiler has to be destined for the use for which it has been expressively designed for. Any other use shall be considered improper and therefore dangerous. This boiler is designed to heat water at a temperature inferior to boiling point at an atmospheric pressure.
WARNING! These appliances are exclusively designed to be installed inside adequate boiler rooms. Therefore these appliances must not be installed and operated externally. An outdoor installation could cause malfunctioning and could be dangerous. For external installations, it is recommended to use appliances which are specifically designed and predisposed for this purpose.
Before installing the boiler the following points have to be carried out by a competent engineer:
a) The whole system should be thoroughly flushed in order to remove any residual dirt or grime which could compromise the correct boiler operation. b) Check that the boiler has been preset for operating with the gas type available. This is verifiable via the indication on the packaging and on the data badge; c) Check that the chimney/flue pipe has an adequate draught,does not have any constrictions, and that no other appliance’s flue outlets have been fitted, unless the chimney is serving more than one heating appliance, according to the specific standards and regulations in force. The connection between the boiler and chimney/flue outlet can be made only after this verification has been carried out.
WARNING! In rooms where there is the presence of aggressive vapours or dust the appliance must operate independently from the air present in the boiler’s location room!
WARNING! The appliance must be installed by a qualified engineer, who complies to the technical­professional requirements, who, under his own responsibility, guarantees the compliance of the standards according to the latest regulations.
WARNING! The appliance must be installed only on a
closed, vertical flat wall, made of non combustible material. The appliance must be positioned so that at least the minimum operational and servicing
clearances are provided.
The boiler must be connected to a heating system which is compatible to its performance and output.
Before boiler installation, complete all of the following instructions:
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to one of the following:
- United States - Installation must conform to the requirements
of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.
- Canada - Installation must conform to the requirements of
CAN/CSA-B149.1 - Natural Gas and Propane Installation Code
Where required by the authority having jurisdiction, the installation must conform to the Standard ASME CSD-1
Controls and Safety Devices for Automatically Fired Boilers
NOTES:
- Installers must follow local regulations with respect to
installation of Carbon Monoxide (CO) Detectors. Also, follow the maintenance recommendations in this manual.
- FOR MASSACHUSETTS INSTALLATIONS: The boiler must
be installed by a plumber or gas fitter licensed within the Commonwealth of Massachusetts.
14
Instructions for the installer
3.3 - PACKAGING
The ALKON 50/70 boiler is supplied fully assembled in a strong cardboard box.
After having unpacked the boiler check that it is intact and undamaged.
CAUTION
Keep the packaging material (cardboard box, plastic bags, polyester protection etc.) out of
the reach of children as they can be dangerous.
LATTNER refuses all liability for injury to persons, animals or damage to property deriving from not having respected the above mentioned recommendations.
In the packaging, in addition to the boiler, you can also find the following contents:
- Tecnical documetation set
- N° 3 plastic plugs for fixing boiler Ø 0,47‘‘ (12 mm)
- Boiler support bracket
- Condensate evacuation siphon
- Aluminum pipe Ø 3.1‘‘ (80 mm) for smoke evacuation
- Thread Adapter Kit NPT/gas (Supply - Return - Gas),
with sealing rings.
- Gas Ball Valve
3/4”
3.2 - CODE AND STANDARDS APPROVALS
ALKON 50 - 70 has been reviewed for compliance with the applicable sections of the following North American Standards:
ANSI Z21.13 / CSA 4.9 - Gas-fired low pressure steam and hot water boilers
ASME SECTION IV: ASME Boiler and Pressure Vessel Code with addenda, Section IV: Rules for Construction of Heating Boilers
SCAQMD RULE 1146.2. EMISSIONS OF OXIDES OF NITROGEN FROM LARGE W ATER HEA TERS AND SMALL BOILERS AND PROCESS HEA TERS
CSD-1: CONTROLS AND SAFETY DEVICES FOR AUTOMATICALLY FIRED BOILERS
CAUTION The boiler may be damaged when not secu­red properly.
- Only transport the boiler using appropriate transportation equipment, such as a handtruck with a fastening belt or special equipment for maneuvering steps.
- When shipping the boiler must be secured on the tran­sportation equipment to prevent it from falling off.
- Protect all parts against impacts if they are to be transpor­ted.
- Follow the transportation markings on the packaging.
Packaged boilers must always be lifted and carried by two people, or you must use a handtruck or special equipment for transport.
14.6’’
(370 mm)
28.1’’
(715 mm)
40.4’’
(1025 mm)
15
Instructions for the installer
3.4 - MINIMUM CLARANCE FOR
SERVICING
Observe minimum distance of the boiler
TOP of the boiler: 24’’ (600 mm)
FRONT of the boiler: 12” + 24” = 36” (900 mm) RIGHT side: 12’’ (300 mm) LEFTside: 12’’ (300 mm) FLOOR/GROUND: 40’’ (1000 mm) BACK of the boiler: 0’’
Maintain an installation clearance from combustible construc­tion from hot water piping of at least 1" (25 mm).
- Remove the packaging materials.
- Do not tear the packaging.
- Lay the boiler on its back during unpacking. When
unpacking, the casing can be removed from the boiler. This part can be kept apart during installation. It must be placed on the boiler and fixed with the screw behind the door before the boiler is started up.
- The boiler can be mounted practically to any wall with the
suspension bracket and the enclosed mounting equip­ment.
- The wall must be flat and of sufficient strength in order to
be able to securely hold and support the boiler weight with its water content.
- Take note of the necessary space around the boiler for
installation of venting system, pipework and servicing. See drawing in section 3.4
The location of the boiler can be determined by using the draw on page 16. Remember to account for the spacing of the plumbing kit.
- Drill the necessary holes
- Install the mounting bracket to the wall using the supplied
mounting materials
CAUTION Lifting and carrying precautions. To avoid personal injury please follow these recommendations:
- Always lift the boiler with 2 people or use special equipment.
- When lifting the boiler, bend the knees, and keep the back straight and feet apart.
- Do not lift and twist at the same time.
- Lift and carry the boiler close to the body.
- Wear protective clothing and gloves to pro­tect from any sharp edges.
CAUTION Lift the boiler only by the boiler's rear wall.
- Dispose the packaging materials.
12.3’’ (311.5 mm)
11.8 ’’
300 mm
11.8’’
300 mm
39.4’’ 1000 mm
23.6’’
(600 mm)
10.5’’
266 mm
23.6’’
600 mm
Operating
space
16
Instructions for the installer
Special attention shall be paid to local regulations and laws about boiler houses and particularly to the obligation of keeping minimum clearances and empty space around the boiler. The installation shall be in compliance with all latest regulations and laws about boiler houses, installations of heating and hot-water systems, ventilation, chimneys capable of evacuating the flue gases of condensing boilers and any other applicable requirement.
When selecting the position for the installation of the boiler please comply to the following safety requirements:
Guarantee an easy access to the components of the boiler
to facilitate the possible operations of ordinary and extra­ordinary maintenance.
The room where the boiler will be placed must always be
frost free.
• The appliance must be installed exclusively on a vertical and solid wall, capable of adequately supporting the weight of the boiler;
• The wall must not be made of inflammable material.
3.5 - BOILER LOCATION INSIDE A BOILER HOUSE
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
Never use or store any chlorinated detergents or haloge-
nated hydrocarbons (e.g. in spraycans, solvents and de­tergents, paints, adhesives) in proximity of the boiler.
The boiler must be installed in such a way that it is pro-
tected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, condensa­te trap, control replacement, etc.)
This boiler is for intended for indoor installations only.
Products to avoid present in boiler room and/or around combustion air intake
Spray cans containing chloro-/fluorcarbons Ammonium and/or ammonium solutions Permanent wave solutions Chlorinated waxes and/or cleaners Swimming pool chemicals based on chlorine Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages with workshops
R
MG
S
3.3’’
(85 mm)
4.3’’
(110 mm)
4.3’’
(110 mm)
5.2’’
(132 mm)
7.0’’
(177 mm)
33.7’’ (856 mm)
34.1’’ (865.5 mm)
1.8’ (45 mm)
12.3’’ (311,5 mm)
10.4’’ (265 mm)
4.1’’ (103 mm)
2.2’’ (56.5 mm)
17
Instructions for the installer
Mark the 3 holes with the wall bracket, using a spirit level.
Install the wall bracket with the 3 screws
With 2 people, lift the boiler by holding it by its back and by
the transport rail and install it on the wall bracket
The boiler can be moved sideways to get the correct posi-
tion.
3.6 - CONNECTIONS
A) Thread Adapter Kit NPT/gas M=
CH system flow 1’’¼
R=
CH system return 1’’¼
G = Gas Ball Valve ¾”
RG = Gas Adaptor ¾‘‘
S = Condensate Drain
S
G
R
M
RG
3.7 - INSTALLATION ON EXISTING
HEATING SYSTEMS
- The circulation pump’s output, the head and flow direction
are suitable.
- The gas feeding supply pipe and the eventual tank are
constructed according to the regulations in force.
- The expansion vessels assure the total absorption of the
dilatation of the fluid contained in the system.
- The system has been cleaned of impurities and lime scale.
Boiler system flushing (Not Boiler heat exchanger)
When replacing an existing boiler the heating system should be flushed with the old boiler in
place before the new boiler is added to the sy­stem. If the old boiler has already been removed a bypass must be piped in when the new boiler is installed in order to facilitate the flushing of the system. The boiler must be valved off from the system, while the system is flushed. No system cleaner should ever enter the boiler heat exchanger because of its caustic nature it could damage the heat exchanger.
When the appliance is installed on existing systems, ensure yourself that:
- The flue outlet pipe is suitable for condensing boilers, for the temperature of the products of combustion, calculated and manufactured according to the regulations in force. It must be installed as much as possible in a straight line,
R
M
G
S
3.3’’
(85 mm)
4.3’’
(110 mm)
4.3’’
(110 mm)
5.2’’
(132 mm)
7.0’’
(177 mm)
33.7’’ (856 m m)
34.1’’ (865.5 mm)
1.8’’
(4.5 mm)
12.3’’ (311,5 mm)
10.4’’ (265 mm)
4.1’’ (103 mm)
2.2’’ (56.5 mm)
0,5’’
(12 mm)
0,5’’
(12 mm)
0,5’’
(12 mm)
A
18
Instructions for the installer
tested for soundness, insulated and must not have any occlusions or restrictions.
- The flue outlet pipe has a connection for the discharge of condensate.
- The boiler room has a suitable outlet for the discharge of condensate produce by the boiler.
- The electrical system has been fitted in compliance to the specific norms and the work has been carried out by a competent person.
19
Instructions for the installer
3.8 - GAS CONNECTION
DANGER
The gas connection must be carried out by a registered engineer who will have to respect
and comply to the regulations in force and to the requirements indicated by the local gas supplier. An incorrect installation could
cause injury to persons, animals or damage to property . The manufacturer shall not be held liable for any injury and/or damage.
WARNING LATTNER wall mounted boilers are built to run on Natural Gas or Propane Gas. The gas type the boiler is suitable for is indicated on the packaging label and on the data plate boiler. First check the identification plate on the boiler for the suitable gas type.
DANGER Do not use the boiler for another type of gas than indicated on the identification plate of the boiler. This will cause improper functioning and can damage the boiler.
Natural gas: refer to chapter 3.8.1 Propane gas: refer to chapter 3.8.2
Pipe sizing for natural gas
- Contact gas supplier to size the gas supply line and meter.
Gas piping
The boiler gas pipe is equipped with external 3/4" M-NPT thread, onto which the tail piece of the gas shut off valve can be connected. Use appropriate sealing.
The connection to the boiler must include a suitable method of disconnection and a gas control valve must be installed adjacent to the boiler for isolation purposes. The nominal inlet working gas pressure measured at the boiler should be 7" W.C. (18 mbar) for Natural gas (Gas A). Maximum pressure with no flow (lockup) or with the boiler running is 10.5 inches W.C. Minimum pressure with the gas flowing (verify during boiler startup) is 4.0 inches W.C.
Pipe sizing for propane gas
- Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator.
Propane Supply Pressure Requirements
- Adjust propane supply regulator provided by the gas sup­plier for 13 inches W.C. maximum pressure.
- Pressure required at gas valve inlet pressure port:
- Maximum 13 inches W.C. with no flow (lockup) or with boiler running.
- Minimum 8 inches W.C. with gas flowing (verify during boiler startup).
Ensure that the high gas pressure regulator is installed at least 6 to 10 feet upstream of the boiler.
Gas piping
- Use a gas shut off valve compatible with propane gases.
- A sediment trap must be provide upstream of the gas con­trols.
The boiler pipe is provided with external 3/4" M-NPT thread, onto which the tail piece of the gas shut off valve can be screwed. Use appropriate sealing.
The connection to the boiler must include a suitable method of disconnection. The nominal inlet working gas pressure measured at the boi­ler should be 11" W.C. (27 mbar) for Propane gas (Gas E). A gas control valve must be installed adjacent to the boiler for isolation purposes. The nominal inlet working gas pressure measured at the boiler should be 11 inch W.C. (27 mbar) for Propane gas (Gas E).
3.8.1 - GAS CONNECTION WITH NATURAL GAS
The gas supply connection must comply with lo­cal regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54. For Canada, the gas connection must comply with local regulations or, if such regulations do not exist,
with the CAN/CSA-B149.1-05 - Natural Gas and Propane Installation Code
Before installing the boiler it is recommended to
thoroughly clean all the supply piping in order to remove any eventual residual grime which could compromise the boilers correct functioning.
As a safety measure against gas leaks, LATTNER recommends installing a surveillance and protective system made up of a gas leakage detector combined with an on-off selenoid valve on the gas supply line.
DANGER Always check the safety of the gas pipe system by means of a bubble test using leak-search spray.
The boiler and its individual shut off valve must be disconnected from the gas supply piping sy­stem during any pressure testing of that system at test pressures in excess of 1/2 PSI (3.5kPa).
The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSI (3.5 kPa).
3.8.2 - GAS CONNECTION WITH PROPANE GAS
20
Instructions for the installer
3.9 - FLOW AND RETURN PIPE CONNECTIONS
WARNING! IT IS ABSOLUTEL Y FORBIDDEN TO FIT ON-OFF VAL VES ON THE GENERA TOR T O THE FORE OF THE SAFTEY DEVICES
WARNING! Before installing the boiler we recommend that the system is flushed out with a suitable product, in order to eliminate any metallic tooling or welding residues, oil and grime which could reach the boiler and affect the proper running of the boiler.
GATE VALVES
R
M
NOTICE When using plastic pipes, observe the supplier’s instructions especially those referring to recom­mended jointing techniques and the notes rela­ting to the heating system water.
NOTICE To prevent contamination in the heating system we recommend you integrate a dirt filter in the return pipe, near the boiler. In an old system it is a requirement to install a dirt filter. Also install shutoff valves to enable filter cleaning immedia­tely upstream and down stream of the dirt filter (scale cartridge or y-strainer).
When determining the size of the CH circuit pipes it is essential to bear in mind the pressure losses induced by any of the system’s components and by the configuration of the same system.
The route of the piping has to be conceived taking all the necessary precautions in order to avoid air locks and to facilitate the continuous purging of the system.
- Connect CH flow pipe to the Supply connection making sure it is not under stress. Use a supply pipe with a mini­mum diameter of 1’’¼ (32 mm).
- Connect the return pipe with a fiat rubber seal installed to the Return connection making sure it is not under stress. Use a return pipe with a minimum diameter of 1’’¼ (32 mm).
WARNING!
Ensure yourself that the system’s piping is not used as the earth clamps for the electrical or telephonic system. They are absolutely unsuitable for this use. In a short time this could cause serious damage to the piping, boiler and radiators.
NOTICE The pipe to be connected to the boiler must be cleaned before connecting in order to prevent dirt from entering and damaging the boiler.
21
Instructions for the installer
The following table gives an indication of the pump’s flow rate in function of the Δt of the primary circuit.
ALKON 50
ALKON 70
3.10 - PRIMARY BOILER PUMP OR BOILER SYSTEM PUMP
NOTE: The use of a mixing header fitted between the boiler circuit and the system circuit is always advisable. It becomes INDISPENSABLE if the system requires flow rates superior to the maximum permitted boiler flow rates, which is to say lower than 27 °F (15 K).
Pressure losses in wc
Q: water flow rate gal/h
PRESSURE A V AIBLE TO THE SYSTEM (red) PRESSURE LOSSES (Blue)
Power supply in btu (kW)
Max flow rate demanded in gal/h (l/h)
ΔΔ
ΔΔ
ΔT 27°F (15°C)
Max flow rate demanded in gal/h (l/h)
ΔΔ
ΔΔ
ΔT 36°F (20°C)
154,000 (45,13)
199,000 (58,32)
683
(2826)
513
(2120)
683
(3927)
663
(2946)
If determined by the installer or technical engineers must be sized according to the data of boiler and system.
In case of fixed raet pump is recommended to choose a circulator with flow rate and head at about 2/3 of the characteristic curve.
The
ΔΔ
ΔΔ
Δt between supply and
return boiler should never be less than 27 °F (15 K).
PRESSURE LOSSES ALKON 50
B
(1) VALUES REFER TO THE MAX SPEED (2) IF EQUIPPED WITH OPTIONAL PUMP
PRESSURE AV AIBLE ALKON 70 (1) ALKON 50 (2) (1)
A
The chart below shows, respectively:
A) Prevalence available net losses of the boiler (For boilers
equipped with a pump supplied by LATTNER)
B) Pressure drop between Return and Delivery (For boilers
supplied without pump)
Size of the pumps
22
Instructions for the installer
3.12 - WORKING PRESSURE
The boiler’s maximum allowable working pressure is set at 92 psa (634 kPa); whilst the minimum pressure is pre­charged to 7,3 psa (50 kPa).
3.11 - PRESSURE RELIEF VALVE DRAIN
PIPE
WARNING! Please remember that it is forbidden to interpose, between the boiler and the pressure relief valve, any type of cutting-off device. Moreover it is recommended to use cutting-off valves which do not exceed the maximum allowable operating pressure.
WARNING! In correspondence to the heating pressure relief valve foresee the installation of a discharge pipe with a funnel and a siphon which lead to an adequate drainage. The drainage has to be controllable by sight. If this precaution is not made, an eventual intervention of the pressure relief valve could cause injury to persons, animals or damage to property. The manufacturer shall not be held liable for any injury and/or damage.
3.13 - CONNECTING THE EXPANSION VESSEL IN A SINGLE BOILER SYSTEM
CAUTION Damage to the installation due to faulty pressure relief valve.
An expansion tank must be part of the central heating system. The expansion tank must be appropriate to the water content of the installation. The pre-charge pressure depends on the installation height above the mounted expansion tank.
1
R MG
NOTICE The expansion tank is NOT a part of the delivery and should be sourced locally. Please refer to the expansion tank manufacturer for further in­formation. Fill expansion tank to a minimum of 14.5 psi.
NOTICE For the boiler to function correctly, it is necessary to connect the expansion tank to the expansion tank connection on the boiler. If the expansion tank is not connected to the supplied connection damage to the boiler may occur.
This reliev valve comply with the standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21.22b-01(R08)/CSA 4.4b-01(R08) and/or the standard Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves CAN1-4.4-M80
23
Instructions for the installer
A
B
C
3.15 - CONDENSATE DRAIN
During the combustion process the boiler produces condensate which, through the “A” pipe, flows into the siphon. The condensate which forms inside the boiler has to be routed into an adequate drain by means of the pipe “B”. otherwise
the boiler will not function and can cause property damage.
The condensate must be drained from the boiler in accordan­ce with local, state or federal rules and regulations.
DANGER! Before commissioning the appliance fill the siphon and check the correct drainage of the condensate. If the appliance is used with the condensate drain siphon empty there could be danger of intoxication resulting from the escape of flue gasses.
The connection between the appliance and the sewage sy­stem must be carried out in compliance with the specific refe­rence standards, and in particular:
- prevent the end user utilizing the condensate produced;
- a siphon must be fitted (supplied with the boiler);
- there must be no bottlenecks;
- the connection must be made just under the bottom part of the boiler;
- it must be installed so as to avoid freezing of the liquid when the boiler is operating and prevent the eventual pres­surization of the sewage system;
- consent the correct downflow of the appliance’s liquid di­scharges;
- it must be made with materials which are resistant to con­densate
- if the condensate outlet of the boiler is lower than the drain, a condensate pump must be used.
- The condensate produced by the boiler has a pH value between 3 and 4.
- Do not drain the condensation water to the external rain gutter because of the danger of freezing and blockage of the drain.
- Install a neutralization unit if required by the local code
Condensate inlet coming from the flue outlet
Condensate drain pipe of boiler and chimney (to connect to the sewage system
Condensate inlet coming from the heat exchanger
NOTICE
Use materials approved by the authority having jurisdiction. in the absence of such authority, PVC and CPVC pipe must comply with ASTM D1785, F441 or D2665. Cement and primer must com­ply with ASTM D2564 or F493. For Canada, use ULC certified PVC or CPVC pipe, fittings and cement.
3.14 - UNDERFLOOR HEATING SYSTEM
(PLASTIC PIPES)
NOTICE
When using oxygen-permeable pipes, e. g. for floor heating systems, you must separate the
system using plate heat exchangers. No recourse can be made to the terms of the warranty in the event of failure to observe the regulations pertaining to plastic underfloor heating pipes.
WARNING
Before putting the boiler into operation fill the condensate trap with 1.27 cups / 300 ml of wa­ter. If the boiler will be installed in a high tempe­rature installation such as baseboard with a supply temperature of 160°F or above, fill the condensate trap with vegetable oil instead of water.
Periodic cleaning of the condensate disposal sy­stem must be carried out.
24
Instructions for the installer
3.16 - WATER TREATMENT
The chemical/physical features of the heating system’s water are fundamental for the boiler’s correct operation and safety.
Among the inconvenients caused by the bad quality of the feeding water, the most frequent and the most serious is the incrustation of the boiler thermal exchange surfaces.
Less frequent, but also serious, is the hydraulic circuit surfaces.
It is ascertained that the boiler incrustations, due to their low thermal conductivity , highly reduce the thermal exchange, even if with a thickness of some millimetres and provoque a very dangerous localised overheating.
We suggest to make the water treatment of the heating circuit in the following cases: a) When the hardness of the water is higher than 9 grains
(15°f); b) For C.H. installations with large water content; c) Renewal of the water system due to uncontrolled leakages; d) Subsequent refilling of the system due to maintenance
works on the installation; e) Presence of different metals in the hydraulic circuit. The scope of this treatment is finalized for eliminating or
substantially reducing the following problems:
- lime scale deposit
- corrosion sludge
- deposits
- microbiological growths (moulds, bacteria etc.)
An appropriate treatment of the supply water will prevent the above stated problems and will maintain the correct operation and efficiency of the generator in time.
For this purpose it will be necessary to fix the following chemical-physical characteristics of the water:
PH include between 6,5 and 8 Hardness 6 ÷ 9 grains (9 ÷ 15 fr)
Water hardness
When there is a water hardness of more than 6 to 9 grains hardness a water softener must be installed.
Sediment
If there is sediment in your domestic water supply sediment filter or other suitable device should be used to remove it.
THE INSTALLA TION MUST BE FORESEEN ON THE RETURN PIPE OF THE PRIMARY CIRCUIT DOWNSTREAM OF THE CIRCULATING PUMP.
WARNING!
All necessary precautions must be taken for preventing the formation and localization of oxygen in the system’s water. For this reason, ensure yourself that the plastic piping used in underfloor heating systems is impermeable to oxygen.
If any anti-freeze solutions are used ensure that they are compatible with aluminium and any other boiler components and materials.
WARNING! Any damage caused to the boiler due to the formation of lime scale or by corrosive water will not be covered by the warranty.
WARNING Appropriate steps must be taken to ensure
the indirect tank water heater does not be­come plugged by scale caused by hard wa­ter or sediment. If the indirect tank water heater becomes
plugged by either scaling from hard water of sediment it is not the responsibility of LA TT ­NER.
25
Instructions for the installer
3.17 - COMBUSTION AIR AND VENTILATION
OPENINGS
Provisions for combustion and ventiiation air must be made in accordance with section 5.3, Air for Combustion and Venti­lation, of the National Flue Gas Code, ANSI Z223.1/NFPA 54., or Sections 7.2, 7.3 or 7.4 of CAN/CSA-B149.1-05, installation Codes, or appiicabie provisions of the local building codes.
CAUTION BOILER DAMAGE AND OPERATIONAL FAILURES
Due to insufficient or improper openings for com­bustion air and/or ventiiation of the boiler room. Provisions for combustion air and ventiiation are always required, regardiess whether the combu­stion air is taken from the outside (sealed com­bustion) or inside (room air for combustion). Insufficient ventilation of the boiler room can lead to high air temperatures. This can result in boiler damage.
- Make sure that intake and exhaust openings are sufficiently sized and no reduction or closu­ re of openings takes place.
- When the problem is not resolved, do not ope­ rate the boiler.
- Please note these restrictions and its dangers to the operator of the boiler.
WARNING
BOILER DAMAGE !
Due to contaminated air.
- Boiler must be clear and free from combustible materials, gasoline and other flammable vapors and liquids, and corrosive liquids and vapors. Never use chiorine and hydrocarbon containing chemicals (such as spray chemicals, solution and cleaning agents, paints, giues etc) in the vicinity of the boiler.
- Do not store and use these chemicals in the boiler room.
- Avoid excessive dust formation and buildup.
NOTICE
When one expects contaminated combustion air (near swimming pools, chemical cleaning ope-
rations and hair salons), sealed combustion operation is recommended.
DANGER
Fire danger due to flammable materials or liqui­ds.
-Do not store flammable materials and liquids in the immediate vicinity of the boiler.
All Air from inside the Building (room air)
The closet shall be provided with two permanent openings communicating directly with an additional room(s). The total input of all gas utilization equipment installed in the combi­ned space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour of total input rating of all gas utilization equipment in the confined space, but no less than 100 square inches. One opening shall commence within 12 inches (305 mm) of the top, and one opening shall commen­ce within 12 inches (305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 4 inches (101 .6 mm).
All Air from Outdoor (seaied combustion)
The cioset shall be provided with two permanent openings, one commencing within 12 inches (305 mm) from the top, and one commencing within 12 inches (305 mm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawi or attic) that freely communicate with the outdoors. The minimum dimension of air openings shall be no less than 4 inches (101.6 mm).
1. Where directly communicating with the outdoors, each ope­ning shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclo­sure.
2. Where communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of ali equipment in the enclosure.
3. Where communicating with the outdoors through horizon tal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr of total input rating of ali equip­ment in the enclosure.
4. Where ducts are used, they shall be of the same cross­sectional area as the free area of the opening to which they connect.
26
Instructions for the installer
3.18 - INSTALLATION OF THE EXHAUST AND AIR INTAKE SYSTEM
NOTICE
Consult local and state codes pertaining to spe­cial building code and fire department requirements. Adhere
to national code requirements.
NOTICE
Observe the listed maximum lengths of vent sy­stem which are boiler model dependent.The ma­ximum permissible lenghts are listed at page 26
- 29
Minimum clearance of 4 ft (1.22m) horizontally from, and in no case above or below, unless a 4 ft (1.22 m) horizontal distan­ce is maintained, from electric meters, gas meters, regulators and relief equipment.
The minimum distance from adjacent public walkways, adja­cent buildings, openable windows and building openings shall not be less than those values specified in the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and / or the Natural Gas and Propane Installation Code, CAN/CSA B149.1
Do not extend exposed vent pipe outside the building beyond recommended distance. Condensate could freeze and block vent pipe.
Vent should terminate at least 3 ft (915 mm) away from adja­cent walls, inside corners and 5 ft (1525 mm) below roof ove­rhang (see figure).
it is not recommended to terminate vent above any door or window, condensate can freeze causing ice formations.
Do not use chimney as a raceway if another boiler or fire place is vented into or through chimney.
EXHAUST
INTAKE
12’’ (305 mm)
minimum
12’’ (305 mm)
minimum
12’’ (305 mm)
minimum
12’’ (305 mm)
minimum
12’’ (305 mm)
minimum
NOTICE Terminals should be positioned as to avoid pro­ducts of combustion entering openings into bu­ildings or other vents.
NOTICE Terminals should be positioned as to avoid pro­ducts of combustion entering openings into bu­ildings or other vents.
NOTICE
Maintain 12” of clearance above the highest anti­cipated snow level or grade or, whichever is gre­ater. Please refer to your local codes for the snow level in your area.
NOTICE
The whole route of the vent system must be in­stalled upwards, never downwards, completely nor partly.
NOTICE
The terminal should be located where dispersal of combustion products is not impeded and with due regard for the damage or discolouration that
might occur to building products in the vicinity (see above figure). In certain weather conditions condensation may also accumulate on the outside of the air inlet pipe. Such conditions must be considered and where necessary insulation of the inlet pipe may be required.
In cold and/or humid weather water vapor may condense on leaving the vent terminal. The effect of such ‘water condensation’ must be considered. The terminal must be located in a place not likely to cause a nuisance.
27
Instructions for the installer
When using indoor air, LATTNER strongly recommends the use of an indoor air filter. This boiler requires adequate combustion air for ventilation and dilution of flue gases. Failure to provide adequate combustion air can result in unit failure, fire, explosion, serious bodily injury or death. Use the following methods to ensure adequate combustion air is available for correct and safe operation of this boiler.
Important: Combustion air must be free of corrosive chemi­cals. Do not provide combustion air from corrosive environ­ments. Appliance failure due to corrosive air is not covered by warranty. Combustion air must be free of acid forming chemical such as sulfur, fluorine and chlorine. These chemicals have been found to cause rapid damage and decay and can become toxic when used as combustion air in gas appliances. Such chemicals can be found in, but not limited to bleach, ammonia, cat litter, aerosol sprays, cleaning solvents, varnish, paint and air fre­sheners. Do not store these products or similar products in the vicinity of this boiler.
3.19 - ROOM AIR SYSTEM
FOR INSTALLATION USING INDOOR COMBUSTION AIR
Boiler designed to be connected to an open flue which will terminate vertically through the roof. The combustion air is withdrawn directly from the room where the boiler is installed.
The flue system must be installed in accordance with the local and national Standards.
Use only original LATTNER flue outlet systems, which are provided from the follow manufacturer:
TABLE FLUE OUTLET SYSTEM
Damages caused by installation errors and for non­observance of the instructions given by the manufacturer will invalidate all the supplier’s contractual or extra contractual responsibilities.
If the boiler has to be replaced ALWAYS replace the flue outlet system.
The boiler has been tested and approved with the terminals
distributed by LATTNER that comply the requirement s of ANSI Z21.13 / CSA 4.9 for the following flue configurations.
Item Decription
Concentic extension
3.28 ft Concentic
extension
1.62 ft Elbow 90°
Elbow 45°
Horizontal Flue terminal
Venting terminal
Vertical Flue Terminal
Manufacturer
GROPPALLI
GROPPALLI
GROPPALLI
GROPPALLI
GROPPALLI
GROPPALLI
STABILE
Material
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Code LATTNER
00362445
00362446
00362442
00362441
00362439
00362440
00362244
WARNING: for this type of connection the room must com­ply with the same installation regulations valid for open chimney boilers.
The chimney must comply to the current regulations.
Flue outlet systems must be purchased from the dealer of products LA TTNER.
28
Instructions for the installer
L min = 39.4‘‘ (1 m) L max = 787.4‘‘ (20 m)
L
1
L2
L min = 39.4‘‘ (1 m) L max = 787.4‘‘ (20 m)
L max = L1+L2
L max = L1+L2
L1
L2
Preliminary operations: Fit the smoke evacuation pipe Ø 3.15‘‘ (80 mm), supplied in the carton, as shown in the picture.
FLUE OUTLETS Ø 3.15‘‘ (80 mm)
The total allowed linear maximum length of the smoke evacuation and air intake pipes, of Ø 3.15‘‘ (80 mm), is 787.4‘‘ (20 m), including one wide radius curve and one evacuation terminal.
ATTENTION! In the case in which danger of freezing subsists, the insulation of the smoke evacuation pipe is recommended on the whole length, in both cases, outside or in the chimney.
ATTENTION! For boiler have horizontal runs sloping upwards not less than 1/4 in / ft (21 mm / m) from the boiler to the vent terminal.
29
Instructions for the installer
Smoke evacuation by two separate ducts
Ø 3.15‘‘ (80 mm)
L min = 78.7‘‘ (2m)
39.37‘‘ (1 m) air intake + not less than 39.4 (1 m) smoke evacuation
L max = 787.4‘‘ (20 m)
393.7‘‘ (10 m) air intake + 393.7‘‘ (10 m) smoke evacuation
L
1
L2
COMBINATION DIRECT VENT SYSTEM
Boiler with separate air inlet and products outlet. These ducts can discharge into areas with different pressure. The two terminals must not be fitted on to two opposite walls.
Boiler designed for connection to horizontal inlet and out- let terminals, which admit fresh air to the burner and discharge the products of combustion to the outside through concentric or twin ducts.
The minimum distance between the inlet air duct and the flue outlet duct must be of 9.8 in and both terminals must be posi­tioned within a 19.6 in square section.
3.20 - VENT AND AIR SUPPLY SYSTEM
FOR ORIZONTAL DIRECT VENT SYSTEM
Smoke evacuation by two separate ducts
Ø 3.15‘‘ (80 mm)
L min = 78.7‘‘ (2m)
39.37‘‘ (1 m) air intake + not less than 39.37 (1 m) smoke evacuation
L max = 787.4‘‘ (20 m)
393.70‘‘ (10 m) air intake + 393.7‘‘ (10 m) smoke evacuation
L1
L2
ATTENTION! For boiler have horizontal runs sloping upwards not less than 1/4 in / ft (21 mm / m) from the boiler to the vent terminal.
30
Instructions for the installer
3.21 - ELECTRICAL CONNECTIONS
Regulations in force
The electrical connections to the boiler must be made in ac­cordance with all applicable local codes and the latest revision of the NFPA 70: National Electrical Code Installations should also conform with C22.1 - Canadian electrical code, part I (21st edition), safety standard for electri­cal installations if installed in Canada.
CAUTION
The boiler must be electrically grounded in ac­cordance with local codes, or in absence of lo­cal codes, with the National Electrical Code, NFPA 70: National Electrical Code C22.1- Ca­nadian electrical code, part I (21st edition), sa-
fety standard for electrical installations The gas, D.H.W. and the CH system pipes can­not be used as ground plates.
Ensure that the above safety electrical requirements subsist; in case of doubt, ask for a professionally qualified technician to check the appliance’s electrical system.
LA TTNER refuses responsibility for any damages arising from failure to earth the boiler correctly.
It is necessary that a qualified technician verifies that the electrical system is adequate to the appliance’s maximum absorbed power, indicated on the data plate, verifying in particular that the section of the system’s cables is suitable to the appliance’s maximum absorbed power.
CAUTION
For the appliance’s general electrical supply the use of adaptors, multiple sockets and/or extension cords is strictly forbidden. The use of any power supplied equipment implies the observance of several fundamental rules, such as:
- Do not touch the appliance with any wet part of your body and/or barefooted;
- Do not pull the supply cables
- Do not expose the boiler to sunlight, rain, etc., unless it is explicitly foreseen;
- Do not permit children or inexpert people to use the appliance.
Mains electrical supply connection 120 V - 60 Hz
Power supply cord
The boiler is provided complete with a power supply cord 59‘‘ (1,5 m) long and with a cross section area of 3 x 16 AWG
The electric connections of the boiler are shown in the section named “ACTUAL WIRING DIAGRAM” (paragraph 3.22)
WARNING! We remind you that upstream of the electrical connection, it will be necessary to foresee a service relay (NOT SUPPLIED) which, when the additional electrical safety devices (if any) intervene, shuts down the electrical supply to the on-off fuel valve fitted on the gas supply circuit, but not to the boiler so as to guarantee the running of the pump and permit the boiler to cool down.
DANGER! The electrical connections must be carried out only by a qualified engineer. Before carrying out the connections or any other operation on the electrical parts, always switch off and disconnect the electricity supply and ensure yourself that it cannot be accidentally turned on.
It is necessary to fit a double pole switch on the electrical supply line, having a contact separation in both poles, in an easy accessible position in order to make quick and safe the servicing operations.
FASTON BLOCKING If necessary the faston can be disconnected by slightly folding up, with a point, the blocking tongue ‘’ Á. ‘’.
A
CAUTION
External connection board connections WARNING
Danger of fatal accident due to electric shock. 120 VAC connections may be present on the external connection board when power is sup­plied to the boiler.
- No changes may be made to the wiring of the boiler.
- All connections should be designed in accor dance with the applicable regulations.
- Label all wires prior to disconnection when servicing controls. Wiring errors can cause im proper and dangerous operation.
- Verify proper operation after operation servi cing.
31
Instructions for the installer
Connection of the additional safety devices
- Gain access to the Y1 terminal board
- A Room Thermostat will be connected to the terminals 1 and 2 after removal of the existing bridge wire.
- For the Heating Controller connection use the
connecting terminals 3 and 4.
Room thermostat
E8 heat ing controller
CAUTION! Switch off and disconnect the electricity
supply before carrying out any operations on the electrical parts.
- For the connection remove the existing jumper.
CDS - 1 Prearrangement for the connection of the additional safety devices
LIGHTBLUE
LIGH TBLU E
LIGH TBLU E
For the connection of the E8 heating controller, to remove the “bridge wire” existing between the terminals 1 and 2.
Room thermostat and/or E8 heating controller connection
CAUTION Switch off and disconnect the electricity
supply before carrying out any operations on the electrical parts.
A hot water boiler installed above radiation level or as required by the Autority having jurisdiction, must be provided with a low water cutoff devices either as a part of the boiler or at the time of boiler installation.
32
Instructions for the installer
3.22 - WIRING DIAGRAM for ALKON 50
MDV = Motor 3 way valve P SYST. = Pump system SS = DHW sensor
Note: Any accessories shown in the drawn are not available for this model of boiler
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
21
ORANGE +
BLACK (-)
BROWN (PWM) BLUE (TACHO)
45
BLUE (N)
12
BROWN (L1)
3
RIL./REG.
ALIM. 120V
SRR
SR
BROWN
BROWN
BLUE
YELL/GREEN
E. RIV.
WHITE
BLACK
DK
BROWN
BLUE
BLUE
BLUE
BROWN
Fs1
BLACK BLUE BROWN ORANGE
P
BLUE
BROWN
YELL-GREEN
GREEN GREEN
WHITE
WHITE
WHITE
BROWN
BLUE
BROWN
GREEN
RED (CH)
WHITE (DHW)
IG
VM
L1
N
120 V - 60 Hz
SS
MDV
00333986
BLUE - N
BROWN - L
E. ACC
TR. ACC
BLUE BROWN
RED
YEL
/
GREEN
VG
YEL/GREEN
OR
Only with
BROWN BLUE
BLACK WHITE
TL
TF
B
L
A
C
K
BLUEPFBLUE
CDS-1
YELL-GREEN
BROWN
BLUE
P
BOILER
SYSTEM
P
1 (NC)
BROWN
3 ( C )
WHITE
BLUE
= Minimum water pressure switch = Ignition electrode = Detection electrode = Power switch On-Off = Pump boiler (optional) = CH sensor = CH return sensor
= Limit thermostat = Smoke thermostat (only pre-arran
g
ement) = Ignition transformer = Gas valve = Modulating fan detection/adjustment
DK E. ACC E. RIV. IG P SR SRR TL TF TR.ACC VG VM
CSD - 1 Prearra ngement for the connection of the additional safety devices
33
Instructions for the installer
WIRING DIAGRAM for ALKON 70
21
ORANGE +
BLACK (-) BROWN (PWM) BLUE (TACHO)
45
BLUE (N)
12
BROWN (L1)
3
RIL./REG.
ALIM. 120V
SRR
SR
BROWN
BROWN
BLUE
YELL/GREEN
E. RIV.
WHITE
BLACK
DK
BROWN
BLUE
BLUE
BLUE
BROWN
Fs1
BLACK BLUE BROWN ORANGE
P
BLUE
BROWN
YELL-GREEN
GREEN GREEN
WHITE WHITE
WHITE
BROWN
BLUE
BROWN
IG
VM
L1
N
120 V - 60 Hz
BLUE - N
BROWN - L
E. ACC
TR. ACC
BLUE BROWN
RED
YEL
/
GREEN
VG
YEL/GREEN
TL
TF
B
L
A
C
K
1 (NC)
BLUE
PF
BROWN
3 ( C )
WHITE
BLUE
BLUE
CDS-1
YELL-GREEN
BROWN
BLUE
P
BOILER
SYSTEM
P SYST. = Pump system
Note: Any accessories shown in the drawn are not available for this model of boiler
= Minimum water pressure switch = Ignition electrode = Detection electrode = Power switch On-Off = Pump boiler = CH sensor = CH return sensor
= Limit thermostat = Smoke thermostat (only pre-arran
g
ement) = Ignition transformer = Gas valve = Modulating fan detection/adjustment
DK E. ACC E. RIV. IG P SR SRR TL TF TR.ACC VG VM
CSD - 1 Prearra ngement for the connection of the additional safety devices
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
34
Instructions for the installer
3.23 - GENERAL LADDER DIAGRAM
L
N
AC/DC
CPU
P
F
G
120 V AC
15 kV
Fs1
FLAME
CAUTION HIGH VOLTAGE SPARK LEAD
SPARK
ROD
A8 - 1
IG
A
8 - 2
IG
A8 - 2
A
9 - 2
A
9 - 6
A
6 - 6
A
6 - 5
A
9 - 5
A
9 - 1
A
8 - 1
A3-5
SRR
RIBBON CABLE
A3
A3 6- A3-3
S
R
A3 4- A4-6PFA4-5 A4-4 A4-5TLA4-1
CDS-1
A2-3DKA2-1
888
DISPLAY
A1 - 4 A1 - 2
A1 - 1
A1 - 3
RL 4
RL 1
RL 2
RL 3
(*)
A4-4
A4-3
SL (**)
A
TTENTION
A
UTE TENSION CÂBLE D’ALLUMAGE
A4-2
35
Instructions for the installer
3.25 - FILLING THE SYSTEM
WARNING!
Do not mix the CH system’s water with anti­freeze or anti-corrosion solutions using wrong concentrations! It could cause damage to the washers and could provoke noise during normal boiler operation. LATTNER refuses all liability for injury to persons, animals or damage to property deriving from not having respected the above mentioned recommendations.
Before filling the heating system, the complete system, inclu­ding all zones, must be thoroughly cleaned and flushed to remove sediment. Flush until clean water runs free of sediment. LATTNER sug­gests using an approved system cleaner to flush the system, but not the boiler. Always use LATTNER approved antifree­zes. See the list at page 7. Never use reverse osmosis, D.I., or distilled water for filling the heating system.
WARNING!
Do not use petroleum-based cleaning or sea­ling compounds in the boiler system. Damage of seals and gaskets in boiler and system could occur, resulting in substantial property dama­ge.
The central heating installation needs to be fil­led with potable water.
Use only potable water or approved glycol for filling the heating system. When the water hardness of the filling water exceeds > 8 gpg the water has to be treated until below the maximum value of 8 gpg The pH value of the installation water must be
between 6.5 and 8.5. Check the pH value using proper equi­pment or by having the water analyzed by a water treatment company. If pH differs from above, contact LATTNER engineering for further assistance. Failure to adhere to the water quality requirements will result in a void of warranty.
Once all the connections are made, it is possible to fill the circuit. This operation has to be performed very carefully, by obser­ving the following steps (boiler in Off position):
- open the radiator bleeds and make ascertain the good operation of the automatic air vent fitted in the boiler.
- open progressively the filling valve and make sure the automatic air vent, in the system, work properly.
- close the bleeders of the radiators when water starts to come out.
- control via manometer (Optional) that the water pressure has reached a minimum value of 11,6/14,5 psi (0,8/1) bar
- close the filling valve and bleed again all the radiators.
- inspect for the soundness all the hydraulic connections.
- after the commissioning of the boiler and the reaching of the normal operation temperature, switch off the operation of the boiler and the pump and repeate the bleed opera­tion.
- let the installation cool down and, if necessary, add water in order to reach the minimum presure of 11,6/14,5 psi (0,8/1) bar
3.24 - STARTING UP: Filling and de-aerating
the boiler and installation
CAUTION Observe the following rules of safety:
- All work on the unit must take place in a dry environment.
- LATTNER units may never be in operation without their housing, except in connection with maintenance or adjustments.
- Never allow electrical or electronic components to come into contact with water.
NOTICE Carry out the following tasks in connection with maintenance, etc. to an already installed
unit:
- Shut down all programs
- Close the gas shut off valve
- Shut off the power at the main power switch
- Close the service valves (supply and return)
NOTICE T ake note of the following when maintenance or adjustments are needed:
- The unit must be able to function during these activities; for this reason, the unit’s supply voltage, gas pressure and water pressure must be maintained. Ensure that this is not a source of potential danger during these activities.
WARNING Following maintenance or other activities; always check the installation of all
parts through which gas flows (with bubble test using leak-search spray).
36
Instructions for the installer
37
Instructions for the installer
3.26 - INITIAL LIGHTING
PRELIMIARY CHECKS
CAUTION The first ignition must be carried out by a qualified technician. Failure to do so could cause injury to persons, animals or damage to property. LATTNER shall not be held liable for any injury and/or damage.
Before lighting the boiler check that:
- the boiler installation has been carried out in accordance with the specific Standards and regulations in force for the gas part and for the electrical part;
- the air supply and the discharge of the products of combustion are carried out in the correct way in accordance to the specific Standards and regulations in force;
- the gas supply system is correctly dimensioned for the boiler’s output and is fitted with all the safety and control devices prescribed by the regulations in force;
- the electrical supply must be 120 V - 60 Hz;
- the system has been filled with water (pressure registered on the gauge 11,6/14,5 psi (0,8/1) bar with pump not running);
- any on-off valves of the system are open;
- the mains supply gas corresponds to the one which the boiler has been calibrated for: otherwise convert the boiler to use the available gas (Using kit code and follow the instruction “GAS CONVERSION”); this operation must be carried out by a qualified technician in compliance to the regulations in force;
- the gas supply cock is open;
- there are no gas leaks;
- the external mains supply switch is on;
- the system’s safety valve on the boiler is not blocked and that it is connected to the sewage system;
- the condensate drain siphon has been filled with water;
DANGER! Before commissioning the appliance fill the siphon and check the correct drainage of the condensate. If the appliance is used with the condensate drain siphon empty there could be danger of intoxication resulting from the escape of flue gasses.
- there are no water leaks;
- all the necessary ventilation conditions and minimum clearance distances are guaranteed for subsequent servicing.
LIGHTING AND SHUTTING DOWN PROCEDURES For lighting and shutting down the boiler refer to the
“INSTRUCTIONS GUIDE FOR THE PERSON IN CHARGE OF THE APPLIANCE”
Information to be passed on to the user.
The usert be instructed on the use and operation of the boiler and in particular:
- Hand the booklet: “USER’S OPERATING INSTRUCTIONS”, as well as all the other literature relative to the appliance, and placed in the envelope contained in the packaging, to the user.
The user must retain this literature for any future reference.
- Inform the user of the importance of the air vents and of the flue outlet system, stressing the fact that absolutely no modification can be made.
- Inform theuser regarding the control of the system water pressure and how to restore it to the correct value.
- Explain and demonstrate to the user the correct function and adjustment of the temperature, thermostats and radiators for the economic use of the system.
- Remind the user that a comprehensive service and the measurement of the combustion efficiency should be carried out regularly (as requested by the national law).
- If the appliance is sold or transferred to another owner or if the present user moves home and leaves the appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by the new owner and/or installer.
38
Instructions for the installer
- Check that the boiler is connected to the electrical supply; the green indicator led “Q” (
) on the control
panel must be illuminated.
- Create a request in CH by pressing key indicate.
- Turn the gas valve knob, in OFF position.
- After 1sec, boiler switch off,
LIGHT BLUE
- Power on by switching ON-OFF switch
3.27 - TESTING THE IGNITION SAFETY
SHUT OFF DEVICE
Lock-out indicator led illuminated + fault indicator led
- Press Reset Key will displayed the fault code LF (loss
of flame), the boiler will retry ignition cycle (7 seconds) after which if was not removed the cause of the fault (gas tap) the boiler will shut off.
39
Instructions for the installer
1
1
1
3.28 - BURNER ADJUSTMENT
WARNING!
All the instructions indicated below are for the exclusive use of qualified LATTNER service technicians or installers.
All the boilers are supplied already calibrated and tested. If it is necessary to change the calibration due to gas conversion or adaptation to the mains supply system, the gas valve must be re-calibrated.
A) Max output adjustment
- Connect a suitable C0
2
gas analyser to the sampling
point in the flue inlet/outlet terminal.
- Pressing simultaneously the keys + (plus) and –
(minus) for at least 3 seconds the boiler will operate in the CH mode at the maximum output (led 1 illuminated).
- Check that the C0
2
values are within the values
indicated in the table “Burner pressures”
- If necessary correct the value by turning the adjustment
screw “A” in a CLOCKWISE direction to decrease the value and in an ANTICLOCKWISE direction in order to increase it.
B) Min output adjustment
- By pressing the key “- decrease” again the boiler will operate at the minimum output (led 1 blinking).
MAXIMUM OUTPUT ADJUSTMENT SCREW (A)
- To disenable the CHIMNEY SWEEPER MODE press the keys + (increase) and – (decrease) simultaneously (led 1 off).
- Check that the C0
2
values are within the values indicated
in the table “Burner pressures”
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
BLUE
YELLOW
LIGHT BLUE
VIOLET
BLUE
YELLOW
40
Instructions for the installer
C) COMPLETION OF THE BASIC ADJUSTMENTS
- Check the C0
2
values at the minimum and maximum
outlet
- If necessary make the required adjustments
To ensure correct operation the C0
2
values have to be adjusted with extreme care respecting the values indicated in the table.
- Close the sampling test point in the flue inlet/outlet terminal with the appropriate cap C.
MINIMUM OUTPUT ADJUSTMENT SCREW (B)
Tighten the maximum adjustment screw “A” in a clockwise direction until you arrive to the abutting end, than slacken for 7 turns. Verify the boiler ignition; if the boiler goes into lockout slacken the screw “A” again of one turn, than retry the ignition. If the boiler goes into lockout again, carry out the above indicated operations until the boiler is lighted. At this point carry out the burner adjustment as previously indicated.
- If necessary correct the value by turning the adjustment screw “B” in a CLOCKWISE direction to increase the value and in an ANTICLOCKWISE direction in order to decrease it.
Type of Gas
7 (1,74)
11 (2,74)
7 (1,74)
11 (2,74)
0.038 (1,07)
0.015 (0,42)
0.038 (1,07)
0.015 (0,42)
0.173 (4,91)
0.067 (1,90)
0.156 (4,42)
0.060 (1,71)
A (Natural) E (Propan HD)
A (Natural) E (Propan HD)
min (FL)
ALKON 50
9.5
10.8
9.5
10.8
92 93
82 83
24 24
24 24
0.22 (5,6)
0.22 (5,6)
0.22 (5,6)
0.22 (5,6)
9.5
10.8
9.5
10.8
Start
output %
IG
40 50
40 50
Check the C0
2
levels often, especially at low flow rate
INJECTORS – PRESSURES
CO
2
level
(%)
min
CO
2
level
(%)
max
Fan speedSupply
pressure
in wc (kPa)
Minimum gas
consumption
ft3/hr (m3/hr)
Ø Mixer
injectors
Øin (mm)
max
(FH)
Maximum gas
consumption
ft3/hr (m3/hr)
V max
fun
FU
10 10
10 10
ALKON 70
FOR HIGH AL TITUDE
Type of Gas
7 (1,74)
11 (2,74)
7 (1,74)
11 (2,74)
0.055 (1,56)
0.021 (0,60)
0.055 (1,56)
0.021 (0,60)
0.224 (6.35)
0.087 (2,46)
0.156 (5,72)
0.060 (2,21)
A (Natural) E (Propan HD)
A (Natural) E (Propan HD)
min (FL)
9.5
10.8
9.5
10.8
81 80
73 72
21 21
24 24
0.35 (9,0)
0.35 (9,0)
0.22 (5,6)
0.22 (5,6)
9.5
10.8
9.5
10.8
Start
output %
IG
50 50
50 50
CO
2
level
(%)
min
CO
2
level
(%)
max
Fan speedSupply
pressure
in wc (kPa)
Minimum gas
consumption
ft3/hr (m3/hr)
Ø Mixer
injectors
Øin (mm)
max
(FH)
Maximum gas
consumption
ft3/hr (m3/hr)
V max
fun
FU
12 12
12 12
FOR HIGH AL TITUDE
41
Instructions for the installer
3.29 - PROGRAMMING OF THE OPERATING PARAMETERS
WARNING! THESE OPERA TIONS ARE ACCESSIBLE TO TRAINED INST ALLERS AND SERVICE ENGINEERS ONL Y FOR CHANGING THE P ARAMETER SETTINGS
BURNER MODULA TION LEVEL IN IGNITION (IG)
By pressing the YELLOW key you have access to the first adjustable parameter BURNER MODULATION LEVEL IN
IGNITION (IG)
(Operation A)
By pressing the YELLOW key again the standard parameter setting is displayed.
(Operation B)
By pressing the keys + (increase) or – (decrease) a number of times the parameter can be changed.
(Operation C)
After setting the desired value pressing the YELLOW key stores this new value in the memory.
Press the YELLOW key and the LIGHT BLUE key simultane­ously to enter in the service mode SE and change the values of the pre-set operating parameters.
PUMP OVERRUN
Continue to change to the parameters by pressing the – key (decrease). The successive parameter which can be changed is: PUMP
OVERRUN (Po).
Repeat the operations A-B-C for setting the desired value from 1 to 10 minutes.
Standard setting: 5 minutes
CAUTION! DO NOT CHANGE THE PARAMETER
.
Standard Natural Gas setting
40 % 50 %
Standard LPG setting 50 % 50 %
ALKON 50
70
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
42
Instructions for the installer
SETTING OF THE MINIMUM HEA TING TEMPERA TURE
Continue to change to the parameters by pressing the – key (decrease). The successive parameter which can be changed is: SETTING
OF THE MINIMUM HEA TING TEMPERATURE (HL).
Repeat the operations A-B-C for setting the desired value from 68 to 140 °F (20 to 60°C)
Standard setting: 95° F (35°C)
SETTING OF THE MAXIMUM HEATING TEMPERATU­RE
Continue to change to the parameters by pressing the – key (decrease). The successive parameter which can be changed is: SETTING
OF THE MAXIMUM HEA TING TEMPERATURE (HH
Repeat the operations A-B-C for setting the desired value from 149 to 185 °F (65 to 85°C)
Standard setting: 176° F (80°C)
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
3.30 - VARIATION OF INPUT RANGE FOR HIGH ALTITUDE
It is necessary adjust nominal heat input by reducing the fan speed.
Modify the parameter FH from the boiler panel board: See factory parameter (supplied separately and modifia- ble only with access code).
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
Insert Code
Choose
LIGHT BLUE
VIOLET
YELLOW
BLUE
Reach the FH parameter by pressing key - several time
LIGHT BLUE
VIOLET
YELLOW
BLUE
(Operation A)
By pressing the YELLOW key again, the standard parameter setting is displayed.
(Operation C)
After setting the desired value pressing the YELLOW key stores this new value in the memory.
See value of parameter FH at table INJECTOR - PRESSURES page 38.
(Operation B)
By pressing the keys + (increase) or – (decrease) a number of times the parameter can be changed.
43
Servicing schedule
CAUTION To ensure the continued safe and efficient operation of the boiler it is highly recommended that it is checked at regular intervals and serviced when necessary, and that only original spare parts are used.
Regular attention will prolong the life of the boiler.
DANGER If the boiler is not checked and serviced regularly it could cause material and personal damages.
For this reason LATTNER recommends that a servicing contract should be made with our authorized After Sales Service Assistance Centre.
The boiler must have regular maintenance and cleaning in order to ensure reliable and efficient operation. Regular attention will prolong the life of the boiler.
The frequency of servicing will be determined by the service engineer and will depend on the appliance’s state of condition.
4
INSPECTION AND SERVICING SCHEDULE
4.1 - INSTRUCTIONS FOR INSPECTION
AND SERVICING
CAUTION To ensure a long life to all your boiler components and in order not to alter the conditions of the approved product, only original LATTNER spare parts must be used.
Before servicing always carry out the following steps:
- Disconnect the mains electricity supply.
- Separate the appliance from the electrical supply by me-
ans of a separating device with an opening contact of at least 3 mm (for example safety devices or power switches) and ensure yourself that it cannot be accidentally reinser­ted.
- Close the on-off valve fitted upstream of the boiler.
- If necessary, and in function of the type of work to be car-
ried out, close any on-off valves fitted on the CH flow and return pipes, as well as the cold water inlet valve.
- Remove the appliance’s front panel.
After having carried out all the necessary maintenance work always follow these steps:
- Open the CH flow and return valves as well as the cold
inlet valve (if previously closed),
- Purge and, if necessary, proceed with restoring the hea-
ting system’s pressure until a pressure of 0,8/1 bar is rea­ched.
- Open the on-off gas cock.
- Reconnect the appliance to the electrical supply and switch
on the mains electrical supply.
- Test for gas soundness, on the gas side and on the water
side.
- Replace the appliance’s front panel.
IMPORTANT:
After having performed the maintenance of the appliance remember to reset the counter by selecting “Cr” from the parameters menù and introducing the relevant resetting code.
Relation between the temperature (°C) and the nom. resistance (Ohm) of the heating sensor SR and the return heating sensor SRR.
T° F (C) 32 (0) 33.8 (1) 35.6 (2) 37.2 (3) 39.2 (4) 41 (5) 42.8 (6) 44.6 (7) 46.4 (8) 48.2 (9)
32 (0) 32755 31137 29607 28161 26795 25502 24278 23121 22025 20987 50 (10) 20003 19072 18189 17351 16557 15803 15088 14410 13765 13153 68 (20) 12571 12019 11493 10994 10519 10067 9636 9227 8837 8466 86 (30) 8112 7775 7454 7147 6855 6577 6311 6057 5815 5584
104 (40) 5363 5152 4951 4758 4574 4398 4230 4069 3915 3768 122 (50) 3627 3491 3362 3238 3119 3006 2897 2792 2692 2596 140 (60) 2504 2415 2330 2249 2171 2096 2023 1954 1888 1824 152 (70) 1762 1703 1646 1592 1539 1488 1440 1393 1348 1304 176 (80) 1263 1222 1183 1146 1110 1075 1042 1010 979 949 194 (90) 920 892 865 839 814 790 766 744 722 701
T ABLE OF THE RESISTANCE VALUES IN FUNCTION OF THE HEATING SENSOR (SR) AND RETURN HEATING SENSOR TEMPERA TURE (SRR)
Ex: At 101 °F (25°C), the nominal resistance is 10067 Ohm
At 194 °F (90°C), the nominal resistance is 920 Ohm
44
Servicing schedule
4.2 - PERIODIC EXAMINATION OF VENTING SYSTEM
4.3 - PROPER PROCEDURE FOR CLEANING FLUE GAS PASSAGEWAYS
(After 1 year maintenance)
Verify that the system of flue and chimney are unobstructed.
4.4 - PROPER PROCEDURE FOR CLEANING THE BURNER
The inspection of the boiler and venting system should be done every 1 years and full maintenance every 2 years, whichever occurs first. When doing this the circumstances of the boiler’s location must be taken into account. From this one can determine whether to deviate from this advice.
Please contact LATTNER for further guidance on the frequency and service requirements. Contact details can be found on the back page of this manual.
V erify that the air ventilation system, air intake and air intake pipes are unobstructed.
(After 1 year maintenance)
• Perform cleaning of the burners only by blowing, with com-
pressed air, acting from the “side flame”
• Verify visually the state of the spot weldings of the L profiles
and the burner mesh.
Compressed air
Wash with water the combustion chamber, avoiding to wet the electrical harness During this operation it will be necessary to ascertain that the condensate drain pipe is free, so that the washing water does not come out from the inspection hole.
Blow the combustion chamber with compressed air, trying to remove all the dirt still fixed to the fins.
Once the washing of the aluminium sections is finished, make sure the siphon for the evacuation of the conden­sate is free: if necessary clean it.
45
Servicing schedule
4.5 - VISUAL INSPECTION OF THE FLAME
4.6 - PROPER REASSEMBLY AND RESEALING OF THE VENT-AIR INTAKE SYSTEM
(2 and 4 yearmaintenance)
The burner must flame evenly over the entire surface when operating correctly. The flame must burn with a clear, ORAN­GE, stable flame.
Check the flame through the inspection glass
The flame pattern should be as shown in the figures below.
SATISFACTORY
ORANG E FLAME
FLAME: YELLOW = CO2 HIGH NOT SATISFACTORY BLUE = CO2 LOW NOT SATISFACTORY ORANGE = OK SATISFACTORY
After removing, inspected and possibly cleaned, Flue pipes and air intake, replace the tubes correctly.
Attention to the sense of double lip seals.
DOUBLE LIP SEAL
A
A
46
Servicing schedule
4.7 SEALING GASKET BETWEEN DISTRIBUTOR AND BOILER BODY
DANGER! It is absolutely necessary to replace the gasket at any time the inspection or mainte­nance is made on the burner.
When refitting the mixer tighten the nuts progressively and in crossed way, by using a dynamometric wrench adjusted at 7.37 lbf x ft (10 Nm).
Mixer
Gasket between mixer and boiler body.
Burner
Body
4.6 CLEANING THE CONDENSATE DRAIN SIPHON
In order to check and clean the siphon carry out the following steps:
- unscrew the plastic nuts (1) and (2) and to remove the
siphon;
- Verify if there are any deposits flush them out with clean
water;
- reassemble the siphon in reverse order.
DANGER Before commissioning the appliance fill the siphon via the filling hole and check the correct drainage of the condensate. If the appliance is used with the condensate drain siphon empty, the combustion adjustments could result completely wrong. Furthermore this could lead to danger of intoxication following the escape of flue gasses.
1
2
47
Fault finding
Description: Failure of the heating return sensor (SRR)
Corrective action: Check the efficiency of the sensor and/or wiring
Description: Over high temperature detected by the heating sensor (SR) >203°F (>95°C)
Corrective action: Check the system’s water circulation
Description: Loss of flame signal during boiler operation
Corrective action: Press the reset key on the panel
5
FAULT FINDING
2
1
3
5.1 - ERROR CODES
The boiler is fitted with an integrated diagnostic readout which,
in case of malfunction, consents the immediate individuation of the type of fault directly on the control panel display
In the following fault finding table our purpose is to give some technical information regarding the solutions to any problems which could occur during boiler operation or commissioning of the boiler.
When the fault signalling led (1) is on, press the LIGHT BLUE key (2) to check the error code on the display (3).
Code:
Description: Mains voltage < 96 Vac
Corrective action: Check that the mains voltage is <96 Vac, if the mains voltage is correct replace the control board.
Code:
Description: Insufficient gas pressure
Corrective action: Check the pressure; if the pressure is correct check the efficiency of the gas pressure switch and/or the wiring.
Code:
Description: Difference between the heating temperature sensor (SR) and the heating return sensor (SRR) too high
Corrective action: Check the installation
Code:
Code:
Code:
Code:
Description: No flame detected during the ignition phase.
Corrective action: Press the reset key on the control panel
Code:
Description: Low water pression Corrective action: Fill-up the water circuit
Code:
Description: Modulating fan failure
Corrective action: Check the fan’s wiring
Code:
Description: Modulating fan failure
Corrective action: Check the fan’s wiring
Code:
Description: Main heat exchanger frozen
Corrective action: Carefully de-frost the exchanger
Code:
Description: Intervention of the high limit thermostat (TL)
Corrective action: Press the reset key on the control panel
LIGHT BLUE
VIOLET
YELLOW
BLUE
48
Fault finding
The boiler has an integrated system that, after 15.000 ignitions (3 value displayed x 5000) Value switching On or
3.000 (3 value displayed x 1000) hours of operation of the burner, provides to signal that the boiler needs maintenance.
Such information is indicated on the display by the lighting
of the code .
The flashing of the code doesn’t inhibit the normal operation of the boiler.
Service the appliance and subsequently reset the counter by selecting “Cr” from the parameters menù and introducing the relevant resetting code.
5.2 - REQUEST OF MAINTENANCE
Code:
Code:
Description: Alteration of the operating parameters caused by EMC disturbances
Corrective action: Restore the factory parameters
Code:
Description: Flame signal detected before the ignition cycle
Corrective action: Disconnect the detection electrode’s wire from the control board; if the error code disappears replace the cable, otherwise replace the control board.
Code:
Description: Flame detected after burner OFF
Corrective action: Disconnect the gas valve’s wire from the control board; if the error code disappears replace the control board, otherwise replace the gas valve.
Code:
Description: Internal failure
Corrective action: Replace the control board
Description: Heating sensor failure
Corrective action: Check the sensor’s efficiency and/or wiring
Code:
Description: Common chimney obstruction Corrective action: Verify the chimney
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
LIGHT BLUE
VIOLET
YELLOW
BLUE
Insert Code
Confirm (yellow) to reset value
Choose
49
Spare parts
ALKON 50
13
36
37
41
39
38
3
9
33
23
31
43
20
10
32
12
1
18
2
14
16
2
25
4
22
26
4
4
4
27
28
17
8
21
6
29
7
35
6
39
11
24
42
5
15
44
44
34
40
45
50
Spare parts
ALKON 70
13
36
37
41
39
38
3
9
33
23
31
43
20
10
32
12
1
18
2
14
16
2
25
4
22
4
27
28
17
8
21
6
6
30
39
11
24
42
5
15
4
26
4
35
44
44
34
45
40
51
Spare parts
Pos. Code Description
Spare parts list
1 95000023 Assorted gasket
2 95000426 Gas valve gasket (10 pcs.)
3 95000610 Grommet (6 pcs.)
4 95000657 Silicon pipe 4x8
5 95000679 Sight glass
6 95000680 CH flow sensor
7 95000781 Safety valve 6 bar
8 95000936 Heat exchanger Alkon 50/70
9 95000933 PCB Alkon 70
95000934 PCB Alkon 50
10 951000105 Dash board Alkon 70
951000104 Dash board Alkon Alkon 50
11 95212123 RH casing
12 95212125 Front casing
13 95212658 LH casing
14 95250489 Fan seal
15 95251384 Ignition electrode
16 95251500 Burner seal
17 95251502 Burner
18 95260588 Automatic air vent
20 95261102 Switch
21 95261494 Overheat thermostat 203°F (95°C)
22 95261988 3.15’’ (80mm) seal (2 pcs.)
23 95261999 Cover protection switch
24 95262087 3.15’’ (80mm) seal
25 95262128 Gas valve
26 95263579 Ignition transformer
27 95263551 Fan Alkon 70
95263552 Fan Alkon 50
28 95262451 Mixer Alkon 70
95262789 Mixer Alkon 50
29 95262604 Low water switch
30 95263555 Pump GRUNFDFOS UPS 26-99 FC
31 95310239 Display case
32 95310726 Fascia board
33 95310885 Programming keys
34 95263580 Gas tap 3/4"NPT
35 95263581 Condensate trap
36 95600402 Wiring VM R – TL
37 95600403 Wiring SR – SRR
38 95600406 Wiring ALIM. 120V
39 95600405 Wiring E. RIL.
40 95603418 Smoke Pressostat
41 95600407 Wiring T.ACC.-VG-VM(A)-P (Alkon 70)
95600404 Wiring T.ACC.-VG-APM-VM(A) Alkon 50
42 95600377 Ignition lead
43 95630163 Display board
44 95251826 Adapter F 1" 1/4 GAZ - 1" 1/4 NPT
45 95251827 Adapter F 3/4" GAZ - 3/4" NPT
LATTNER declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to bring those changes that it will hold necessary to it own products or profits, without jeopardizing its essential characteristi­cs.
Lattner Boiler Mfg. Co.
1411 9th St. S.W. - P.O. Box 1527 - Cedar Rapids, IA 52404
319 - 366 - 0778 - 800 - 345 - 1527 - Fax: 319 - 366-0770
www.lattner.com
®
LATTNER
Loading...