Unical KONe C 24, KONe C 28, KONe R 24, KONe C 18, KONe R 28, KONe R 35, KONe C 35, KONm, KONm R 24, KONm C 18, KONm R 18, KONm R 28, KONm C 35, KONm C 28, KONm R 35, KONm C 24 Installation And Servicing Manual
At the end of its life cycle the product must not be disposed of as urban waste. It can be taken to
a special recycling centre managed by the local authorities, or to a dealer who oers this service.
Separate disposal of a domestic appliance avoids possible negative consequences for the
environment and human health deriving from inappropriate waste handling and allows the recovery
of the materials of which it is made, in order to obtain signicant energy and resource savings.
2
Attention: this manual contains instructions for the exclusive use of the professionally qualied installer
and/or maintenance technician in compliance with current legislation.
The user is NOT qualied to intervene on the boiler.
The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from
failure to comply with the instructions contained in the manuals supplied with the boiler.
1 GENERAL INFORMATION .............................................................................................................................4
1.1 General warnings ....................................................................................................................................4
1.2 Symbols used in the manual ...................................................................................................................5
1.3 Appropriate use of appliance ...................................................................................................................5
1.4 Information for system manager .............................................................................................................. 5
1.6 Technical data plate ................................................................................................................................7
1.7 Water treatment .......................................................................................................................................8
2 TECHNICAL FEATURES AND DIMENSIONS ..............................................................................................9
2.1 Technical features ...................................................................................................................................9
2.2 Main components view and dimensions .................................................................................................. 9
2.3 Available ow rate / pressure diagram .................................................................................................. 12
2.4 Operation data ....................................................................................................................................... 13
2.5 General features .................................................................................................................................... 14
3.1 General warnings ..................................................................................................................................15
3.8 Filling the system ................................................................................................................................... 22
4.4 Important notes ..................................................................................................................................... 39
The instruction booklet is an integral and essential
part of the product and must be kept by the user.
Read the warnings contained in this instruction
booklet carefully as they provide important guidelines
regarding installation, use and maintenance safety.
Keep the booklet with care for further consultation.
Installation and maintenance must be performed
in compliance with the standards in force according to the instructions of the manufacturer,
up to standard and by personnel qualied and
certied in compliance with law.
Systems for the production of domestic hot water MUST be constructed entirely with compliant
materials.
By professionally qualied personnel we mean:
personnel with specic technical skill in the eld
of heating system components for civil use, domestic hot water production and maintenance.
Personnel must have the qualications provided
for by current legislation.
Incorrect installation or improper maintenance can
cause damage to persons, animals or objects for
which the manufacturer is not responsible.
In case of failure and/or malfunctioning of the appli-
ance, switch it o and do not try to repair it or intervene on it directly. Contact only personnel qualied
in compliance with law.
Any repairs must be performed solely by personnel
authorised by Unical AG S.p.A., using original spare
parts only. Failure to comply with the above can
compromise the safety of the appliance and void
the warranty.
To guarantee appliance eciency and its correct
operation, yearly maintenance must be performed
by qualied personnel.
Should you decide not to use the appliance, parts
entailing potential sources of hazard must be made
safe.
Before commissioning an appliance that has not
been used, wash the domestic hot water production
system, making the water ow until it has been fully
replaced.
Should the appliance be sold or transferred to a new
owner or if you move and leave the appliance, always
make sure that the instruction booklet accompanies
it in order to be consulted by the new owner and/or
installer.
Before performing any cleaning or maintenance,
disconnect the appliance from the energy mains by
acting on the switch of the system and/or through
the specic cut-o devices.
Do not obstruct the terminals of the intake/exhaust
ducts.
Only original accessories must be used for all appliances with optionals or kits (including electric).
This appliance is intended solely for the use for which
it was expressly designed.
Any other use is to be considered improper and
therefore dangerous (*).
4
1.2 - SYMBOLS USED IN THE MANUAL
Pay special attention when reading this manual to the parts marked by the symbols:
DANGER!
Serious danger
to safety
and health
situation for the product
ATTENTION!
Possible dangerous
and the environment
DANGER!
Danger of burns!
1.3 - APPROPRIATE USE OF APPLIANCE
The boiler has been built according to the current level of engineering and acknowledged
technical safety rules.
Nonetheless, if improperly used, dangers could arise for the safety and life of the user
and other persons or damage to the equipment or other objects.
The appliance is designed to work in heating systems, with hot water circulation, for
the production of domestic hot water.
Any other use is considered improper.
For any damage resulting from improper use UNICAL AG. S.p.A. assumes no responsibility.
Use according to the intended purposes also includes strict compliance with the instructions in this manual.
NOTE!
Tips
for the user
OBLIGATION!
wear gloves
protective
NOTE!
For further details
refer to the Technical
Information:
at the web address
indicated
on page 2
1.4 - INFORMATION PROVIDED TO THE USER
The user must be instructed concerning the use and operation of his heating system, in particular:
• Deliver these instructions to the user, as well as other documents concerning the appliance
inserted in the envelope inside the packaging. The user must keep this documentation
safe for future consultation.
• Inform the user about the importance of the air vents and the ue gas exhaust system, highlighting their essential features and the absolute prohibition of modifying them.
• Inform the user concerning controlling the system's water pressure as well as operations to
restore it.
• Inform the user concerning correct temperature control, control units/thermostats and radiators
for saving energy.
• Please note that, in compliance with the standards in force, the inspection and maintenance of
the appliance must be carried out in compliance with the regulations and frequency indicated
by the manufacturer.
• Should the appliance be sold or transferred to a new owner or if you move and leave the appliance, always make sure that the instruction booklet accompanies it in order to be consulted
by the new owner and/or installer.
The manufacturer will not be held liable in the event of damage to persons, animals or
objects resulting from failure to comply with the instructions contained in this manual.
5
1.5 - SAFETY WARNINGS
ATTENTION!
The boiler cannot be used by children.
The boiler can be used by adults and only after having carefully read the user’s manual. Children should be supervised to ensure that they do not play or tamper with
the device.
ATTENTION!
The appliance must be installed, adjusted and maintained by professionally qualied
personnel, in compliance with the standards and provisions in force. Incorrect installation can cause damage to persons, animals and objects for which the manufacturer
cannot be held responsible.
DANGER!
NEVER attempt performing maintenance or repairs on the boiler on your own initiative.
Any work must be done by professionally qualied personnel. We recommend stipulating a maintenance contract.
Insucient or irregular maintenance can jeopardise the operating safety of the appliance and cause damage to persons, animals and objects for which the manufacturer
cannot be held responsible.
Changes to the parts connected to the appliance (once the appliance installation is complete)
Do not modify the following parts:
- the boiler
- the gas, air, water and electricity supply lines
- the ue gas pipe, the safety valve and the exhaust pipe
- the construction parts which aect the operating safety of the appliance
Attention!
To tighten or loosen the screwed ttings, use only appropriate xed spanners.
Incompliant use and/or inappropriate tools can cause damage (e.g. water or gas leakage).
ATTENTION!
Indications for propane gas-red appliances
Make sure that the gas tank has been deaerated before installing the appliance.
For state-of-the-art tank venting, contact the LPG supplier or person qualied in compliance
with the law requirement.
If the tank has not been professionally deaerated, ignition problems could arise.
In that case, contact the supplier of the LPG tank.
Smell of gas
Should a smell of gas be perceived, follow these safety guidelines:
- do not turn electric switches on or o
- do not smoke
- do not use the telephone
- close the gas shut-o valve
- air out the area where the gas leakage has occurred
- inform the gas supplier or a company specialised in installation and maintenance of heating
systems.
Explosive and easily ammable substances
Do not use or store explosive or easily ammable materials (e.g. petrol, paints, paper) in the
room where the appliance is installed.
DANGER!
Do not use the appliance as a supporting base for objects.
In particular, do not place receptacles containing liquids (Bottles, Glasses, Jars or Detergents)
on top of the appliance.
If the appliance is installed inside a housing, do not insert or rest other objects inside this housing.
6
1.6 - TECHNICAL DATA PLATE
The CE marking
certies the compliance of the equipment with the
essential safety requirements dened in the directives and applicable European regulations and that
its functioning satisfy applicable technical standards.
The CE marking is axed to each piece of equipment with an appropriate label.
KEY:
1 = CE monitoring body
2 = Type of boiler
3 = Boiler model
4 = Number of stars (directive 92/42 EEC)
5 = (S.N°) Serial Number
The CE declaration of conformity issued in accordance with international standards by the manufacturer, is placed in documentation envelope supplied with the product.
The treatment of the supply water
allows to prevent inconveniences
and maintain the functionality and
eciency of the generator over time.
The ideal water pH in heating systems
must be within:
VALUEMIN MAX
PH6.58
Hardness [°fr]915
To minimise corrosion, it is crucial to
use a corrosion inhibitor; in order for
it to work properly, the metal surfaces must be clean.
(see system protection ACCESSORIES sect. in domestic price list)
ATTENTION!
ANY DAMAGE TO THE BOILER
CAUSED BY THE FORMATION OF
FOULING OR BY CORROSIVE WATER
WILL NOT BE COVERED BY THE
WARRANTY.
ATTENTION (*) see general warnings 1.1
The heating only models are NOT
suitable for the production of water
for human consumption according
to Ministerial Decree D.M. 174/2004.
NOTE!
Further details in the section
‘‘Technical Information’’ on the
boiler
page of the www.unicalag.it website
1.8 - BOILER ANTIFREEZE
PROTECTION (*)
Make sure that E is lit up
on the display
(
using B / C.
(*) The Antifreeze protection is always active.
Even by disabling the heating and domestic hot
water services,
in this mode (
active.
)only the antifreeze function is
P
O
S
1
2
(*) Sensor 11 par. 2.2
Power supplies11 - SR (*)Status
ElectricGas
ONON< 6 °CON- Burner and Pump ON until T > 14°C
ONON< 2 °CONOnly when both the power supplies are ON:
ONOFF< 7 °COFF- Pump ON till T > 10°C
OFFONOFF- Burner and Pump OFF
OFFOFFOFF- Burner and Pump OFF
), select the mode
ANTIFREEZE FUNCTION
function
antifreeze
This protection can intervene only if
the electricity and gas supplies are
connected.
If one of the two is not available and
upon reset 11 (SR) a temperature of < 2
°C is detected, the appliance will behave
as described in tab. pos 2.
The heating system can be protected
eectively from frost by using antifreeze
products with inhibitor for heating
systems (specic for multidmetal).
Do not use car engine antifreeze
products as they could damage the
water gaskets.
Actions
- Burner and Pump OFF until T > 5°C
- When T > 5°C then Burner and Pump
ON until T > 14°C.
8
2
13
23
24
11
4
25
10
1
2
315 26 17 20
16
12
18
5
27
21
12
18
27
21
TECHNICAL FEATURES
AND DIMENSIONS
2.1 - TECHNICAL FEATURES
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
NOTE!
2.2 - VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS
KONe 18 / 24 RKONe 18 / 24 C
25
10
11
4
24
23
(*)
13
22
5
(*)
22
ENGLISH
Technical Features
3
26
15
20
View from above
View from below
9
KONe 28 / 35 RKONe 28 / 35 C
24
27
24
12
13
15
20
27
(*)
25
10
11
18
23
22
4
4
25
5
10
5
11
8
18
(*)
8
13
23
22
12
3
3
1
2
26
15
17
20
16
View from above
View from below
10
KEY
NO.C.E. S.E. Description
1dbSSDomestic hot water temperature
sensor
2FLS Flow switch with cold water lter
3VGGas valve
4FdE.
5Burner
6Combustion chamber
7AFTFFlue gas anti-overow thermostat
8Expansion vessel
9FR
HT
10HLTLSafety thermostat
11HbSRHeating temperature sensor
12HtPPump
13LpDKWater deciency pressure switch
14 Boiler drain valve
15Filling valve
16Diverter valve
17Plate heat exchanger
18FL
FH
19AFASPVFlue gas pressure switch
Ignition/detection electrode
ACC
/RIL
Heat exchanger
Fan
VM
20Safety valve
21Automatic by-pass
22rbSRR Return temperature sensor
23tfTLC Flue gas collector safety ther-
mostat
24Aluminium Heat Exchanger/Ca-
pacitor
25Vent valve
26Condensation drain trap
27SLArrangement for condensate
sensor level
CDomestic hot water outletG ½
GGas inletG ¾
FCold water inletG ½
MHeating system owG ¾
RHeating system returnG ¾
RcFilling valve
ScBoiler drain
SvsSafety valve drain
Scond
C.E.= ERROR CODES see
Condensation drain
par. 4.6
S.E. = WIRING DIAGRAM KEY
see par. 4.5
ENGLISH
Technical Features
11
2.3 - DIAGRAM OF FLOW RATE/PRESSURE AVAILABLE FOR
INSTALLATION
MODULATING PUMP
DIAGRAM OF FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION
KONe 18 - 24 = 6m
Avaible Head (m.c.a.) metres of waterAvaible Head (m.c.a.) metres of water
Combustion eciency at full load %97,697,297,697,26
Combustion eciency at part load%98,698,698,198,1
Heat losses through the casing (min.-max.)%2,0 - 0,672,0 - 0,6 1,47 - 0,431,47 - 0,2
(*) Net ue gas temperature tf-ta (max.)°C49,057,447,957,0
Flue gas mass ow rate (min.-max)g/s1,35 - 8,11,35 - 10,52 - 12,52 - 14,7
Air excess λ%24,324,323,023,0
CO
2
CO at 0% of O
(min. - max) ppm22 - 9522 - 11411 - 9311 - 120
2
%9,2 - 9,29,2 - 9,29,3 - 9,39,3 - 9,3
Maximum production of condensatekg/h2,93,84,55,3
NOx class6666
Chimney heat losses with burner ON (min. - max.) %1,4 - 2,41,4 - 2,91,9 - 2,41,9 - 2,8
Chimney heat losses with burner OFF%0,600,460,410,34
Prevalenza disponibile alla base del camino min. / max.
Pa2 / 702 / 702 / 702 / 70
Notes: (*) Room Temperature = 20°C Data obtained with appliance operated with Nat Gas (G20)
R 18 / C 18 R 24 / C 24 R 28 / C 28 R 35 / C 35
ENGLISH
2.4.1 - DATA ACCORDING TO ErP DIRECTIVE
DescriptionSymbolUnit KONe
R18 C18 R24 C24 R28C28 R35C35
Nominal Heat Output Pnominal kW17 232732
Seasonal space heating energy
eciency
Seasonal eciency class in
heating mode
For CH only and combination boilers: useful heat output
Useful Heat Output in high-temperature regime
(Tr 60 °C / Tm 80 °C)
Useful eciency at nom. heat output
in high-temperature regime
(Tr 60 °C / Tm 80 °C
Useful heat output at 30% of nom.
heat output in low-temperature
regime (Tr 30 °C)
Useful eciency at 30% of nom. heat
output in low-temperature regime
(Tr 30 °C)
Range-rated boiler: YES / NO YESYESYESYES
Auxiliary electricity consumption
At full loadelmaxkW0,0850,0850,1160,116
At part loadelminkW0,0120,0120,0120,012
In stand-by modeP
Other items
Dispersione termica in stand-byP
Emissions of nitrogen oxides ref. PCI (PCS)NOxMg/kWh37 (33) 50 (45)55 (50)43 (39)
Annual electricity consumptionQ
For CH & DHW production boilers
Declared load prole-XL-XL-XL-XL
Energy eciency in DHW production modeƞ
Appliance category
Minimum heat. circuit output (∆t 20 °C)l/min
Minimum heating circuit pressurebar
Maximum heating circuit pressurebar
Primary circuit contentl
Maximum operating temperature in heat. °C
Minimum operating temperature in heat. °C
Expansion vessel total capacityl
Expansion vessel pre-loadbar
Maximum system capacity (max temp. calc.)l
Minimum domestic hot water circuit ow ratel/min.
Minimum domestic hot water circuit pressurebar
Maximum domestic hot water circuit pressure bar
Domestic hot water specic ow rate (∆t 30 °C) ‘‘D’’l/min.
Production of D.H.W. in continuous operation with ∆t 45 K
Production of D.H.W. in continuous operation with ∆t 40 K
Production of D.H.W. in continuous operation with ∆t 35 K
Production of D.H.W. in continuous operation with ∆t 30 K
Production of D.H.W. in continuous operation with ∆t 25 K (*)
l/min.
l/min.
l/min.
l/min.
l/min.
Adjustable DHW temperature °C
Voltage/Frequency electric power supplyV-Hz
Fuse on the power supplyA (F)
Protection ratingIP
Net weightkg
Gross weightkg
F Factor-1-1-2-2
R Factor----
(*) mixed
R 18 C 18 R 24C 24 R 28 C 28R 35 C35
2H3P
II
1,2 1,2 1,7 1,7
0,5 0,5 0,5 0,5
3 3 3 3
2,22,22,22,2
85858585
30303030
8 81010
1 1 11
164 164 205205
-2 -2 -2 -2
-0,5 -0,5 -0,5 -0,5
-6 -6 -6 -6
-11,2 -11,2 -13 -16
- 7,4- 7,4- 8,6- 10,1
- 8,3- 8,3- 9,7- 11,4
- 9,5- 9,5- 11,1- 13,0
- 11,0- 11,0-12,9- 15,2
-13,3 -13,3 -15,5 -18,3
-
35-60
230/50230/50230/50230/50
3,153,153,153,15
X5D X5D X5D X5D
32,5 34 32,5 34 35,5 37 35,5 37
35,5 3735,5 3738,5 4038,5 40
2H3P
II
-
35-60
2H3P
II
-
35-60
2H3P
II
-
35-60
14
3
INSTALLATION INSTRUCTIONS
3.1 - GENERAL WARNINGS
ATTENTION!
This boiler is intended solely for
the use for which it was expressly
designed. Any other use is to be
considered improper and therefore
dangerous.
This boiler heats water at a temperature lower than the atmospheric
pressure boiling temperature.
Before connecting the boiler, have professionally qualied personnel:
a) Thoroughly wash all the piping of
the system to remove any residues
or impurities which could jeopardise proper operation of the boiler,
even from a hygienic point of view.
b) Check that boiler is set up to oper-
ate with the available type of fuel.
This can be seen written on the
package and on the technical feature
plate;
ATTENTION!
If there is dust and/or if there are
aggressive/corrosive vapours
present in the installation room,
the appliance must be protected
suitably and must be able to
operate independently from the air
in the room.
ENGLISH
ATTENTION!
Only mount the appliance on a closed
wall, made of non-ammable materi-
al, at, vertical so that the minimum
distances required for installation and
maintenance can be observed.
The boiler must be connected to a central heating system and/or domestic hot
water supply network compatible with its
eciency and output.
c) Check that the chimney/ue has an
appropriate draught, without any
bottlenecks, and that no exhausts
from other appliances are inserted,
unless the ue has been implemented to accommodate several utilities
according to specic standards and
regulations in force. Only after this
check can the fitting between the
boiler and chimney/ue be mounted;
3.2 - INSTALLATION STANDARDS
It must be installed by a professionally qualied
technician, who shall take the responsibility of
observing all local and/or national laws published
in the ocial journal, as well as the applicable
technical standards.
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler page of
the www.unicalag.it website
Installation Instructions
NOTE!
For further details relating to the standards, rules
and regulations for safe installation of the thermal
unit, refer to the section "Technical Information"
on the boiler page of the www.unicalag.it website
3.3 - PREVENTIVE VERIFICATION
AND VERIFICATION AND ADJUSTMENT OPERATIONS
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler page of the
www.unicalag.it website
15
H
P
L
3.4 - PACKAGING
The boiler is supplied completely assembled in a
sturdy cardboard box.
After having removed the appliance from
the packaging, make sure that the supply
is complete and undamaged.
The packaging elements (cardboard
box, straps, plastic bags, etc.) must be
kept out of the reach of children as
they are potential sources of danger.
Unical AG S.p.A. will not be held liable
for damage to persons, animals or ob-
jects due to failure to comply with the
instruction above.
OBLIGATION!
wear protective gloves
• The boilers must always be lifted and
carried by two people, or a carrier
carriage or special transport equipment must be used.
As well as the appliance, the packaging contains:
A DOCUMENTATION ENVELOPE
- System booklet
- User operating instructions booklet
- Instruction booklet for the installer and
maintenance engineer
- Warranty
- 2 Spare parts form
- Certicate of conformity
B - Connection predisposition paper template
C - Chimney spacer
21
P
depth
380 mm470 mm810 mm
L
width
H
height
16
3.5 - POSITIONING THE BOILER
When choosing the place of the installation of the
appliance, follow the safety instructions below:
- Place the appliance in rooms protected from frost.
- Avoid installation in rooms with a corrosive or very
dusty atmosphere.
- The appliance must only be installed on a vertical
and solid wall which can support its weight.
- The wall must not be made of ammable material.
e
KON
Since the temperature of the wall on which the boiler is installed and the temperature of the coaxial
exhaust pipe do not exceed, in normal operating
conditions, a room temperature beyond 60 K, it is
not necessary to observe the minimum distances
from ammable walls.
For boilers with double intake and exhaust pipes, in
the event of crossing ammable walls, insert insulation between the wall and the ue gas exhaust pipe.
Clearance
ENGLISH
KONe 24 C
KONe 35 C
Installation Instructions
17
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
FOR BOILERS WITH FORCED DRAUGHT
To connect the ue gas exhaust pipe, local and national standards must be observed
In the event the boiler is replaced, ALWAYS re-
C13xC13
% Slope towards inlet = 3%
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100DOUBLE Ø80
FROM [m]TO [m]FROM [m]TO [m]
15,51 + 1
COAXIAL Ø80/125DOUBLE Ø60
FROM [m]TO [m]FROM [m]TO [m]
181 + 1
Distance between air
inlet pipe and ue gas
exhaust pipe: min 250
mm - max 500
Horizontal exhaust and intake terminals directed
outside via coaxial or double pipes..
40
(20A+20S)
20
(10A+10S)
place the ue gas pipe as well.
The boiler is type approved for the exhaust congurations listed below:
C43xC43
Collective chimney ue system, consisting of two
pipes, one for combustion air intake and the other
one for combustion products evacuation, coaxial
or double.
C53x C53
C33xC33
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100DOUBLE Ø80
FROM [m]TO [m]FROM [m]TO [m]
170,5 + 0,5
COAXIAL Ø80/125DOUBLE Ø60
FROM [m]TO [m]FROM [m]TO [m]
191 + 1
ertical exhaust and intake terminals directed out-
side via coaxial or double pipes.
18
40
(20A+20S)
20
(10A+10S)
C53
NOT ALLOWEDC53
TOTAL LENGTH (LA intake + L Exhaust)
DOUBLE Ø80 DOUBLE Ø60
FROM [m]TO [m]FROM [m]TOA [m]
1 + 1
Separate combustion air intake and combustion
products evacuation pipes.
These pipes can discharge into areas with dierent
pressure.
40
(max 30 S)
1 + 1
(max 15 S)
20
C63xC63
Boiler intended for connection to a combustion air
intake and combustion products evacuation system,
approved and sold separately
ATTENTION:
The ue must comply with standards
in force.
C83xC83
Connection to a terminal for combustion air intake
and ue gas exhaust via a single or collective
chimney.
B23P
TOTAL LENGTH (LS)
DOUBLE Ø80
FROM [m]TO [m]
1 30
Connection to a combustion products evacuation
pipe outside the room; the combustion air is taken directly from the room where the appliance is
installed.
ATTENTION:
For the type of connection B23P the
room follows the same installation rules
for boilers with natural draught.
ENGLISH
C93x C93
Air / ue gas through concentric pipes in the boiler
room and single pipes in the chimney (combustion
air with counterlow in the chimney)
CAUTION
LT total length is a reference value
for the dimensioning of the ducts of A
(intake) and S (Exhaust). Subtracting
the values of LT reported, at values of
bends* / terminals* / extensions* you
get the value:
if > 0 = OK - POSSIBLE conguration
if < 0 = NO - WRONG conguration
Installation Instructions
(*) Values in the MT018 available on the website.
Please note: these values relate to
exhausts/made by means of rigid
pipes and smooth original UNICAL.
19
GENERAL INFORMATION ON THE FLUE GAS EXHAUST SYSTEM
Attention:
For all drain congurations
mount the chimney
spacer supplied with the boiler
NOTE!
For further details relating to pressure drops of the individual components, for information on standards,
rules and regulations for proper ue
gas exhaust, refer to the “Technical
Information” section on the boiler
page of the www.unicalag.it website
Concentric start
Rubber closure plugs
(DO NOT REMOVE)
20
It is recommended to only use original
Unical exhaust pipes.
The supplier will have no contractual
or extra-contractual liability for damage
caused due to incorrect installation and
use and in any case failure to comply
with the instructions provided by the
manufacturer.
Adapter for double systems
3.7 - CONNECTION
GGAS 3/4’’
Danger!
The gas connection must be carried out
only by a qualied installer who must respect and apply that foreseen by relevant
laws in force in the local prescriptions of
the supply company. Incorrect installation
can cause damage to persons, animals
and objects for which the manufacturer
cannot be held responsible.
If you smell gas:
a) Do not operate electric switches,
the telephone or any other object that
may cause sparks;
b) Immediately open doors and
windows to create air current
to purify the room;
c) Shut the gas cocks.
MFLOW 3/4’’
RRETURN3/4’’
Condensation drain
The boiler, during the combustion process, pro-
duces condensation that, through pipe “A”, ows
into the trap.
The condensation that forms inside the boiler ows
into a suitable drain via pipe “B”.
Danger!
Before commissioning the boiler
- check that the trap is assembled
properly
- check the trap and that the condensation is drained properly
If the appliance is used with an empty
condensation drain trap, there is an
intoxication hazard due to the release
of exhaust gasses.
If this precaution is not taken, triggering of the safety valve can cause damage to persons, animals and objects,
for which the manufacturer cannot be
held responsible.
The mains pressure must be within 1 and 3
bar (in the event of greater pressure install
a pressure reducer).
Installation Instructions
Condensation outlet, pipe to be connected to
the drainage system
21
The connection between the appliance
and the domestic waste system must
be made in compliance with the specic
reference standards.
NOTE!
Further details in the section
‘‘Technical Information’’ on the
boiler page of the Unical AG S.p.A.
website.
3.8 - FILLING THE SYSTEM
Attention!
Do not mix the heating water with incorrect concentrations of antifreeze or
anti-corrosion substances! This could
damage the gaskets and cause noise
during operation.
La Unical AG S.p.A. will not be held
liable for damage to persons, animals
or objects due to failure to comply with
the above instruction.
When the system connections have been completed,
the circuit can be lled.
This operation must be performed carefully, respecting the following phases:
- open the radiator vent valves and make sure the
automatic valve is working properly in the boiler.
- open the lling tap gradually, making sure that
the automatic air release valves installed on the
system work properly.
- close the radiator air release valves as soon as
water comes out.
- check the pressure gauge until pressure reaches
approximately 0.8/1 bar.
- close the lling tap and bleed air once again
through the radiator air release valves.
22
Danger of burns!
Attention to contact with ow pipe M
and (if boiler combi) with hot water
outlet pipe C.
- make sure that all the connections are watertight.
- after commissioning the boiler (see par. 3.10) and
bringing the system to the operating temperature,
stop the boiler and repeat the air bleed operations.
- let the system cool down and, if necessary, return
the water pressure to 0.8/1 bar.
(See par. 4.4).
A3
4
3 2 1
6
5
SE
TA 1/OTTA 2
WH
WH
Y
Y
BK
BK
TA
ON-OFF
3.9 - ELECTRICAL CONNECTIONS
Danger!
Only a qualied technician may perform the electrical installation.
Before performing connections or
any type of operation on electrical parts, always
disconnect electrical power and make sure that
it cannot be reconnected accidentally.
ENGLISH
ON/OFF room
thermostat connection (*)
- Remove the jumper and connect the room thermostat wires between terminals TA 2.
ON/OFF room thermostat connection
RT/OT (*)
Installation Instructions
- Connect the modulating thermostat wire between
terminals TA1/OT after having removed the jumper.
23
- Predisposed on the terminal board, terminals
SE
Electric power supply connectionExternal probe connection (*)
See par. 4.5 positioning on the board
(*) Optional
The boiler is equipped with a power cable,
boiler installation requires electric al con-
nection to the mains power supply. This
connection must be made up to standard,
as required the regulations in force.
Remember that a bipolar switch must be
nstalled on the boiler power line with over
3 mm between contacts, easy to access,
making maintenance quick and safe.
The power cable must be replaced by
technical personnel authorised by UNI-CAL AG S.p.A., using original spare parts
only. Failure to comply with the above can
jeopardise the safety of the appliance.
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler page of
the www.unicalag.it website
24
3.10 - COMMISSIONING
Commissioning must be done by profes-
sionally qualied personnel. Unical AG
S.p.A. will not be held liable for damage
to persons, animals or objects due to fail-
ure to comply with the above instruction.
does the installation meet the specic standards and regulations in force, both relating to the
gas part as well as the electrical part?
do the combustion air intake and ue gas exhaust take place properly according to
what is dened by the specic rules and regulations in force?
is the fuel supply system sized according to the capacity required by the boiler?
Is it equipped with all safety and control devices required by the standards in force?
is the power supply of the boiler 230V - 50Hz?
has the system been lled with water (approximately 0.8/1 bar pressure on the pressure gauge
with the pump stopped)?
Has the condensation drain trap been lled with water as indicated in chapter 3.7?
are any system shut-o gate valves open?
Before commissioning the boiler, check that:
ENGLISH
does the gas to be used correspond to the boiler calibration gas?: otherwise, perform the boiler
conversion in order to use the gas available (see section: 4.3”);
this operation must be carried out by technical sta qualied in compliance with the standards in force;
is the gas supply valve open?
has the system been checked for gas leaks?
is the outside main switch ON?
is the system safety valve ecient and is it connected to the drains?
is the condensation drain trap connected to the drains?
has the system been checked for water leaks?
are the ventilation conditions and minimum distances to perform any maintenance
ensured?
have the GAS, HEATING and DOMESTIC HOT WATER pipes been cleaned thoroughly with
products suitable for each circuit?
has a surveillance and protection system against gas leaks been installed? (Optional)
are the system pipes NOT used as the electrical system earthing?
Installation Instructions
has the system been sized properly bearing in mind the radiator pressure drops?
thermostatic valves, radiator stop valves
has the operator been trained and has the documentation been supplied?
Please tick the operations performed
Switching boiler on and off
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler
page of the unicalag.ag website
25
3.11 - MEASUREMENT OF COMBUSTION EFFICIENCY DURING INSTALLATION
3.11.1- ACTIVATION OF THE CALIBRATION FUNCTION
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
1ACTIVATION
Press the key (D) for at least 5 seconds, until
SErvice appears.
The user is NOT authorised to activate the function described below.
3MINIMUM OUTPUT
Press the key (C-), when the low ame symbol is
xed on the display.
All the symbols ash on the display.
2MAXIMUM OUTPUT
When the high ame symbol is xed on the display
and it alternates between SP and the ow temper-
ature, the boiler operates at maximum output.
Perform combustion analyses.
and it alternates between SP and the ow tem-
perature, the boiler operates at minimum output.
Perform combustion analyses.
4DISABLING
The “calibration” function stays active for 15 minutes.
To disable the CALIBRATION function before the
time elapses press the key (D) for 5 seconds, until
SErvice
disappears.
26
3.11.2 - POSITIONING THE PROBES
To determine the combustion eciency one must
make the following measurements:
- measurement of the combustion air temperature
taken in the relevant hole 1.
- measurement of the ue gas temperature and
content of CO2 taken in the relevant hole 2.
COAXIAL PIPES
A
SEPARATE PIPES
B
2
1
Air
probe
NOTE:
Do not insert the analyser probe in the
sample point immediately, in order to
prevent saturating the analyser.
Flue gas
probe
Flue gas
probe
Take the measurements with the generator in
steady state conditions (see par. 3.11.1).
PIPES Ø 80 TYPE B23
C
1
1
2
Air
probe
Flue gas
probe
It is important to perform the combustion
analysis on the combustion air as well,
(Making sure that the concentration of
oxygen is within O2 = 20.8%
tolerance 0.2 - 0.4 %).
This is to prevent any ue gas recirculation.
(*) ± 0,2 Acceptable range for G20 / G25 (+) ± 0,2 Acceptable range for G31 / G230
Note: for operation with Propane air (A.P.) follow the procedure to adapt to another gas at Par.
4.3 setting the parameter for operation with Propane (1) and follow the GAC Automatic Calibration procedure in Par. 4.3.1.
If the CO2 value detected is beyond the recommended range, check the integrity of the electrode.
If needed, replace the electrode.
If the problem persists one can use the function described below.
INCONVENIENCESSOLUTIONS
KONe 18 - 24 - 28 - 35
Flame noisy
in cold ignition
Flame noisy in
steady-state conditions
Flame noisy in
modulation
Act on parameter ‘’IG’’ using the RCh section ‘’TECHNICAL MENU’’ TSP
parameters increasing the value by 5 ÷ 10 % max
e
KON
18 - 24KONe 28 - 35
increase the CO
- max value for methane gas = 9.4 %
(min value > 9.0 %)
- max value for propane = 10.7 %
(min value > 10.3 %)
- max value for A.P. = 9,2 %
(min value > 9.4 %)
value
2
increase the CO2 value
- max value for methane gas = 9.5 %
(min value > 9.1 %)
- max value for propane = 10.7 %
(min value > 10.3 %)
- max value for A.P. = 9,2 %
(min value > 9.4 %)
Start-up
power
IG [%]
28
3.12.1 - COMBUSTION ADJUSTMENT FUNCTION ACTIVATION
This function allows a partial adjustment of the
CO2 value on the following modulation points:
Maximum output 100 %
Start-up output xx %
Minimum output 0 %
1ACTIVATION
Press the keys (B- and B+) at the same time for
at least 10 seconds, SErvice APPEARS.
MINIMUM OUTPUT
When the display alternates CO - 0
SELECTION
2
ENGLISH
CO ...scrolls on the display
MAXIMUM OUTPUT
When the display alternates CO - 100
START-UP OUTPUT
Select the modulation point on which to perform
the adjustment, (max output / start-up output / min
output) with key B+
Press key S
3
EDITING THE VALUE
When the ame ashes, correct the value with
keys C- or C+
VALUES
FROMTODEFAULT
-3 *
+3 *
(*) corresponds to about ± 0.5 points of CO
4 CONFIRM VALUE
4
Press key D
0
2
Installation Instructions
When the display alternates CO - with value XX.
The ame is xed
again.
DISABLING
5
Press the keys (B- and B+) at the same time for
at least 10 seconds, SErvice DISAPPEARS.
29
3.12.3 - ADAPTATION OF THE POWER TO THE HEATING SYSTEM
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
It is possible to adjust the maximum thermal capacity
in heating mode, by decreasing the burner pressure
value.
E.g.: KONe 24
to decrease the output of the
boiler to 18 kW, edit parameter
HP (about 70)
E.g.: KONe 28
to decrease the output of the
boiler to 20 kW, edit parameter
HP (about 65)
E.g.: KONe 35
to decrease the output of the
boiler to 24 kW, edit parameter
HP (about 68)
.
.
.
The user is NOT authorised to activate the function described below.
Act on parameter HP (par. 4.2 SE parameters list)
to achieve the value corresponding to the desired
output.
30
4
INSPECTIONS AND MAINTENANCE
Inspections and maintenance performed
professionally and according to a regular
schedule, as well as the use of original
spare parts, are of the utmost importance
for fault-free operation of the boiler and
to guarantee its long life.
Yearly maintenance of the appliance is
mandatory in compliance with Laws in
force.
4.1 - INSPECTION AND
MAINTENANCE INSTRUCTIONS
To assure long-term functioning of your appliance
and to avoid altering its approved status, only original
Unical AG S.p.A. spare parts must be used.
If a component needs to be replaced:
• Disconnect the appliance from the electrical mains
and make sure that it cannot be reconnected
accidentally.
• Close the gas shut-o valve upstream the boiler.
• If needed, and depending on the intervention to
be carried out, close any shut-o valves on the
ow and return line of the heating system, as well
Failure to perform Inspections and Maintenance can entail material and personal
damage.
ENGLISH
as the cold water inlet valve.
• Remove the front casing from the appliance.
Once all maintenance operations are complete
resume boiler operation
• Open the heating ow and return pipes, as well
as the cold water inlet valve (if closed previously).
• Vent and, if necessary, restore the heating pres-
sure until reaching a pressure of 0.8/1.0 bar.
• Open the gas shut-o valve.
• Switch the boiler back on.
• Make sure the appliance is gas tight and water-
tight.
• Remount the front casing of the appliance.
TABLE OF RESISTANCE VALUES, ACCORDING TO THE TEMPERATURE, TO THE HEATING PROBE 11 (SR)
AND TO THE DOMESTIC HOT WATER PROBE 1 (SS) AND ANY HEATING RETURN PROBE 22 (SRR) see par. 4.5.
Relation between the temperature (°C) and the nom. resistance (Ohm) of the heating probe SR and of the domestic hot
water probe SS
Example: At 25°C, the nominal resistance is 10067 Ohm At 90°C,the nominal resistance is 920 Ohm
Maintenance instructions
31
ROUTINE YEARLY VERIFICATION OPERATIONS
COMPONENT:VERIFY:CONTROL/INTERVENTION
METHOD:
FL
(domestic hot water
Is the minimum domestic hot water
ow rate 3 l/min.?
The burner must ignite with an
intake above or equal to: 3 l/min.
priority ow switch ( 2 )
VG
(Gas valve) ( 3 )
SR (heating sensor)( 11 )
SS (domestic hot water sensor)
( 1 )
SSR (return sensor) ( 22 )
E ACC/RIV. (ignition/detection
electrode) ( 4 )
TL (anti-overheating
limit thermostat) ( 10 )
DK (safety pressure switch
against water deciency) ( 13 )
Does the valve modulate properly? Open a hot water tap at maxi-
mum ow rate and then at minimum. Make sure that the ame
modulates.
Do the sensors maintain the
original characteristics?
12571 ohm at 20° C / 1762 ohm
at 70° C.
Measurement to be taken with
the wires disconnected (see
table Res/Temp).
Does the discharge of sparks before
putting the boiler in safe conditions last
less than 10 sec.?
Does the TL put the boiler in safety
conditions when overheating?
Detach the electrode ionisation
wire and check the securing
time.
Heat the TL until it intervenes
at 95°C and check that it inter-
venes at 95°.
Does the pressure switch block the
boiler if the water pressure is below
0.4 bar?
Without request: close the shuto valves of the heating circuit,
open the drain valve to make the
water pressure decrease. Before pressurising again, check
the pressure of the expansion
vessel.
Expansion vessel ( 8 )Does the vessel contain the right
amount of air?
Check the pressure in expen-
sion vessel (1 bar when the
boiler is empty). Pressurise the
boiler (open the pump automatic
vent valve). Open the heating
circuit closing valves.
Condensation drain trap (27)Has the trap got deposits on the
Clean the trap with water.
bottom?
Domestic hot water ow rate Filter in cold water inlet ( 2 )Clean the lter with limescale
remover.
Heat exchanger body ( 9 )1) Measure the Thermal Capacity
using a meter and compare the value with that contained in table 3.12.
The data measured indicates if the
exchanger needs cleaning.
It is recommended to use products purposely created by Unical AG S.p.A. (see system
protection ACCESSORIES
sect. in the domestic price list),
being careful to wash the area
2) Check that the space between
the rungs of the exchanger are not
clogged
Burner ( 5 )Check the state of cleanliness of the
burner mesh
with most rungs rst (lowest part
visible from above) and then the
upper part if necessary.
Remove any deposits using
compressed air, blowing from
the mesh side.
( Num ) = see key Par. 2.2
32
4.2 - PARAMETERS THAT CAN BE EDITED FROM THE CONTROL PANEL
ATTENTION!
Function reserved for Authorised Assistance Centres only.
Menu access:
InFInFormation
HiErrors Log
SESErvice
FAFactory
1ACTIVATION - SELECTION
DISPLAY
2
Press the key (B+) to display the parameters
list InF
PARAMETERS LIST InF
ENGLISH
Press the key (S) for 5 seconds
Press the key (B+)
INFORMATION
to access the menus
The display alternates the Parameter and Value
CODEDESCRIPTION
Heating temperature, - - if the heating sensor is faulty
External temperature, - - if there is
no external probe or if it is faulty
Domestic hot water temperature, - - if
there is no sensor or if it is faulty
Return temperature, - - if there is no
auxiliary sensor or if it is faulty
Dierential ∆t between ow and
return.
Heating temperature calculated,
(been ‘‘room zone’’ ON-OFF and
‘‘remote zone’’ OT+.)
Press the key (S) to access the Inf parameters
unit
Instantaneous fan speed
_ _ rpm x 100
Water pressure, is there is not pressure sensor, - - is displayed
Firmware version (Factory)
Maintenance instructions
Firmware version (Servicing)
33
(Hi) Errors Log
3
DISPLAY - FAULT
ACTIVATION - SELECTION See section 1 (4.2)
Press the key (S) to access the Hi parameters
unit,
The display alternates H and the number of the
position (01) in which the error is stored.
2
DISPLAY
Press the key (C+) to display the fault code (see
chap.5).
01 = last error
displayed
4
EDIT VALUE - RESET
08 = fault code (LP
Water deciency)
ref. chap. 4.6
Press the key (B+) to display the sequence of
faults between 01 ÷ 12
PARAMETERS LIST (Hi) Errors Log
PositionDescription
01
02
03
04
05
06
07
08
09
10
11
12
last error displayed
penultimate error displayed
last but two error displayed
................error displayed
................error displayed.
................error displayed.
................error displayed.
............... error displayed
............... error displayed
third error displayed
second error displayed
rst error displayed
Press the key (D) for over 5 seconds, to reset the
whole errors log.
This operation must only be performed in the
event one wants to delete the log completely (for
example, if important updates are made it may
therefore be useful to have a new chronological
reference of events).
5
DISABLING
Briey press the key (S) to go back to the main
menu See section 1 (4.2), or press it for over 5
seconds to exit.
34
(SE) Service parameters
EDITING THE VALUE
3
ACTIVATION - SELECTION See section 1 (4.2)
Press the key (S) to access the SE parameters
unit. These parameters can be edited without
restrictions, from the control panel.
2
DISPLAY
Press the key (B+) to display the parameters list
PARAMETERS LIST SE
CODERANGEDESCRIPTION
Post circulation
01
-2010
030
0/530
01
0100
2045
5085
2545
5065
0 = post 5’’ (default)
1 = continuous
External probe on panel
- 20÷10 °C
External probe on Regolafacile
0 = - 20 °C
30 = +10 °C (default 10)
Night reduction
0 = T.A. (default)
5 ÷ 30 = night reduction
Domestic hot water preheat function
0 = Not active (default)
1 = Active
Maximum heating modula-
tion level (default 100)
Minimum heating set point
level (default 30)
Maximum heating set point
level (default 85)
Minimum domestic hot water
set point level (default 35)
Maximum domestic hot water
set point level (default 60)
(default -10)
Press the key (C+) to access the parameter,
the parameter value ashes.
Correct the value with the keys (C+ or C-)
4 CONFIRM VALUE
4
Press key D
ENGLISH
Maintenance instructions
35
(FA) Factory Parameters
ACTIVATION - SELECTION See section 1 (4.2)
Press the key (S) to access the FA parameters
unit. These parameters can be edited by entering the ACCESS CODE.
2
ACCESS CODE.
Press the key (B+) to enter the access code Conrm with the key (D)
Once the access code has been entered, 1 or 2
Factory parameter units are displayed
the parameter value ashes.
Correct the value with the keys (C+ or C-)
4.3 - ADAPTATION
TO THE USE OF OTHER GAS
The boilers are produced for the type of gas specically requested upon ordering.
DANGER!
The conversion for the operation of
the boiler with a type of gas other
than that specically required in the
order, must be performed by pro-
fessionally qualied personnel, in
compliance with the standards and
regulations in force.
The manufacturer cannot be held
liable for any damage resulting from
a conversion operation that is incorrect or not performed in compliance
with the laws in force and/or with the
instructions given.
ATTENTION!
After performing the conversion for
the operation of the boiler with a type
of gas (e.g. propane gas) other than
that specically requested when or-
dering, the appliance will only work
with this new type of gas.
ENGLISH
ally deaerated, ignition problems could arise.
In that case, contact the supplier of the LPG tank.
Gas Conversion
NOTE!
Further details in the section
‘‘Technical Information’’ on the
boiler page of the www.unicalag.it
website
In order to change the gas one must change
the Factory parameter:
FA PARAMETERS (UNIT 1) par 4.2
CODEMETHANEPROPANE
01
Once the Gt parameter has been
edited one must perform the GAC
automatic calibration (Gas Adaptive
Calibration) Chapter 4.3.1
- when the conversion is complete, ll in the
information required on the label supplied in
the documentation envelope and apply it next
to the technical data label of the boiler.
ATTENTION!
Indications for propane gas-fired
appliances
Make sure that the gas tank has been
deaerated before installing the appliance.
For state-of-the-art deaeration of the
tank, contact the LPG supplier or a
person qualied in compliance with
law.
If the tank has not been profession-
EXAMPLE OF COMPILATION
Maintenance instructions
37
4.3.1 - GAC AUTOMATIC CALIBRATION
One can perform the GAC in domestic hot water
mode as well.
Make sure that there are no heating requests present and that all the valves of the heating system
are open.
If during this stage one wishes to disperse the heat
on the domestic hot water circuit, open at least 2 hot
water taps (ONLY AFTER HAVING ACTIVATED THE
GAC FUNCTION).
1ACTIVATION
Stage 2: START-UP OUTPUT CALIBRATION
When the display alternates tr - with value XX.
(1 min)
Stage 3: MINIMUM OUTPUT CALIBRATION
Press and hold the key (D) and press the keys
(B- and B+) at the same time for at least 10 sec-
onds, until service appears.
StArt scrolls on the display , the function is active
when the symbols ash.
Note: After the ignition sequence, which can also
take place after a few attempts, the boiler performs
the calibration which consists of 3 stages:
Stage 1: MAXIMUM OUTPUT CALIBRATION
When the display alternates tr - 0
Calibration is complete when the small ame
starts to ash.
DISABLING
2
See section 1 ACTIVATION
Note: If the display does not show errors it means
that the system has been calibrated properly.
Otherwise refer to chapter 4.6
"Error Codes".
When the display alternates tr - 100 (about 1 min.)
38
4.4 - IMPORTANT NOTES
REPLACING COMPONENTS
Before replacing components one must follow the
notes of chap. 4 "Inspections and maintenance".
To replace the components:
- GAS VALVE
- FAN
- BURNER,
- IGNITION/DETECTION ELECTRODE,
- MODULATION BOARD (in the event the
memory board CANNOT be reused) (*),
GAC calibration is required
MODULATION BOARD
A universal
board
memory
board (*)
B
(*) In the event the memory board can be reused, there is no need to reprogram parameters, settings and automatic calibration.
The memory board is
programmed by default for METHANE
gas operation.
In the event of LPG
operation the GT parameter must be edited
(Factory parameters),
see (Chap. 4.2).
ENGLISH
A
B
Act carefully, pay attention to the insertion direction of the memory board.
Maintenance instructions
39
P
N
L1
1 2
A8
3
4 5
BR
Y-G
BL
1
2
3
BL
BR
BK
(DHW)
(CH)
M
MDV
A4
32
1
4
A9
32
1
BK (-)
1
3
St2
BL (TACHO)
BR (PWM)
OR (+)
2
4
5
VM (R)
CMP (*)
2
1
GR (WSC)
BL
(YONOS) (-)
BR
MODULAT
.
(+12 V) NOT USED
P
N
L1
1
2
A8
3
4 5
MDV
A1
4
3 2
1
8
76
5
9
DKWHFLS
SS SR
BRWHBR
WH
WH
R
R
1 - COM
4 - NO
A1
4
3 2
1
8
76
5
9
DK
WH
SS SR
BR
WH
WH
BR
BL
1 - COM
4 - NO
RC
R
C
T.ACC
230 V
50 Hz
L
1
N
GND
Y/G
BL
BR
1
2
A7
123
4
A5
5612345
A8
4
A9
32
1
A1
4
3
2
1
8
7 6 5
9
A2
4
3 2
176
5
A4
32
1
A3
4
32
1
6
5
A6
MEMORY
CARD
VM (A)
1
2
3
St1
BL
BR
Y/G
L1
N
L1
N
C.I. A.P.S.
BR
Y-G
BL
GR
WH
R
(DHW)
(CH)
E. ACC./RIL.
R
A2
4
32
1
7 6
5
TLC
TL
SRR
G
G
WH
WH
WH
BL
A6
VI
WH
R
(Mod)
(On/Off)
+-
VG
EV2
EV1
OR
+-
A3
4
32
1
6
5
SE
BK
TA 1/OT TA 2
WH
WH
Y
Y
BK
BK
MDV
PK (WSC)
(YONOS)
G
ND
WH
SL
BK
CASING
4.5 - WIRING DIAGRAMPractical connection board
C.ISystemlling
A.P.S. Additional Pump
Supply
KEY
A1.....A9Services connectors
CMPModulating pump control
DKWaterdeciencysafetypressureswitch
E.ACC./RILIgnition/detection electrode
FLSDomestichotwaterrequestowswitch
MVDDiverter valve motor
PPump
SRFlowheatingsensor
SRRReturnheatingsensor
40
SS
TLLimitthermostat
Domestichotwaterprobe(Pred.forRmodels)
TLCFluegascollectorlimitthermostat
VGGas valve
VMModulating fan
SEExternalprobeconnectionterminals
TA1 / OTModulating TA connection terminals
TA2On/off TA connection terminals
detected if the H2O pressure
Transducer is present with
pressure > 2.5 bar; it is reset
automatically when H2O pressure < 2 bar
303SERVICE PARAMETERS
Service parameters altered due
to possible electromagnetic
interferences.
214POOR WATER CIRCULATION
Poor circulation in primary
circuit
175FLAME CONTROL FRE-
QUENCY BEYOND LIMIT
Depends on the power supply
mains (Frequency and voltage
beyond default limits)
156WATER CIRCULATION IN-
SUFFICIENT
Primary circuit water circulation
insucient (∆t > 35° C)
227INCORRECT SENSOR PO-
SITIONING Flow and return
sensors inverted
248SPEED OUT OF
CONTROL
Alteration of the fan speed; the
speed is not reached.
Check the wiring, if needed replace the auxiliary sensor (22)
Wait for the values to return to
default limits /
Replace the Transducer
Reset the altered parameters
via the panel and/or regolafacile
Check pump operation (12)
and speed, if there are any
obstructions or system closure.
Wait for the values to return to
the default limits
Check pump operation (12)and speed - remove any heating system obstructions - clean
the scaled domestic hot water
exchanger
Check the wiring (21) (22)
Check fan operation (18) and
the connections
Maintenance instructions
41
269SPEED OUT OF
CONTROL
Alteration of the fan speed; the
speed is above that requested
610HIGH TEMPERATURE
Boiler temperature too high
8
NO
WATER
11WATER DEFICIENCY
Insucient water pressure and
consequent intervention of the
minimum water pressure - pressure switch ( 13 ).
44
NO
WATER
12
WATER PRESSURE
detected if the pressure Transducer is present
Check fan operation (18) and
the connections
Check pump operation and if
needed
clean the exchanger (24)
Fill the heating circuit as described in chap. 3.8 and wait
for the values to return within
default limits.
If needed, check the electrical connections and replace
the minimum water pressure
switch.
Wait for the values to return
to default limits / Replace the
Transducer
1613EXCHANGER
FREEZING ( 24 )
Exchanger freezing is detected
If the heating sensor detects a
temperature below 2° C, burner ignition is inhibited until the
sensor detects a temperature
above 5°C.
1314
DOMESTIC HOT WATER SENSOR
Domestic hot water sensor
fault (1)
1215HEATING SENSOR (11)
Heating sensor fault
3816FACTORY PARAMETERS
Alteration of the factory parameters due to possible electromagnetic interferences.
1
LIMIT
THERM
4
BLOCK
17
SAFETY THERMOSTAT
Intervention of the safety thermostat (10)
18BLOCK
No gas or failed burner ignition
Disconnect the from the
power supply, close the gas
valve, defrost the exchanger
carefully.
Check the efficiency of the
sensor (see table Res/Temp)
(Par.4) or its connections.
Check the efficiency of the
sensor (see table Res/Temp)
(Par.4) or its connections.
Press the unblock key; if the
anomaly persists, replace the
board.
Press the unblock button on
the panel and/or check that the
thermostat or its connections
are not interrupted.
Check the gas supply or that
the ignition/detection electrode
is working properly (4).
42
1119PARASITE FLAME
Flame detected upon ignition
2020PARASITE FLAME
Flame detected after swtich-o
5
CHIMNEY
21FLUE GAS COLLECTOR
SAFETY THERMOSTAT
Intervention of the flue gas
collector safety thermostat (23)
Check the wiring of the Ign/Det.
electrode and remove any oxidation.
Check for humidity between drain wire
and ceramic, if necessary, replace
the electrode, press the unblock key,
if the anomaly persists, replace the
electrode (4).
Check the wiring and for any
leaks from the gas valve (3), if
needed replace the gas valve.
Rearm the thermostat manually and press the
unblock button on the panel.
Check the connections.
(F) 27 22
service
ERROR
Flow Gradient
Check if the pump switches o
suddenly.
(F) 2323
(F) 5324
service
(F) 5525
service
(F) 1826
(F) 43 27
Detected tab panel button pressed for longer than 30 “
Check keypad and reset the
status of the buttons. Or replace the electronic board
Clogged OutletsCheck the Chimneys / Check
the trap.
No CalibrationGAC Calibration 4.3.1
Electrode earthed on the Burner or presence of moisture
Regolafacile external sensorReplace the external probe /
Regolafacile
-80-
-81-
(*) if there is a condensation obstruction inside the ue gas manifold (before resetting) it is necessary
to proceed to a drying operation inside of the tank especially of the level sensor electrodes.
Regolafacile Internal SensorReplace Regolafacile
Eprom Error of RegolafacileReplace Regolafacile
Also reserves the right to bring those changes that it will hold necessary to it own products or prots, without jeopardizing its essential characteristics.